c ontingency ranking by time domain simulations
DESCRIPTION
C ontingency Ranking by Time Domain Simulations. ECE 422/522 Russell Patterson Micah Till Terry Jones. Project Goals. Identify top five critical contingencies in Zones 2-A and 2-B. Project Goals. Rank the top five contingencies by the stability criterion. - PowerPoint PPT PresentationTRANSCRIPT
Contingency Ranking byTime Domain Simulations
ECE 422/522Russell Patterson
Micah TillTerry Jones
Project Goals
• Identify top five critical contingencies in Zones 2-A and 2-B
Project Goals
• Rank the top five contingencies by the stability criterion.
• Rank the top five contingencies by their Critical Clearing Time and compare the ranking with that based on values of
• Determine the effect of varying load models
Task 1: Rank N-1 Contingencies
• A study was created in TSAT using the Case Wizard• Contingencies were ranked by the stability criterion:
(1)• The results of this analysis are presented below
Contingency (η) Faulted Line Zon
eLM1-1 -68.43 172 to 83 circuit 1 2-A
LM1-2 -68.41 172 to 173 circuit 1 2-A
LM1-3 -65.31 169 to 168 circuit 1 2-A
LM1-4 -65.31 169 to 114 circuit 1 2-A
LM1-5 -63.99 171 to 170 circuit 1 2-A
Task 1: Rank N-1 Contingencies
• Bus 83 is the major bottleneck for power flow between Zones 1-A and 2-A
• As seen, all of the buses in Table 2 are electrically close to bus 83
• Many of these branches are negative reactance, which means they represent series capacitors
• In reality, some of the series capacitors would be bypassed during faults
almost 4GW
Briefly - Series Capacitors
• Used to increase the MW transfer capability of the path (XL – XC)
• 60% series compensation means XC = 60% of XL
• Too much compensation can lead to problems like overvoltage and subsynchronous resonance (SSR)
P=𝑉 𝑆𝑉 𝑅
𝑋 sin∅
Briefly - Series Capacitors
• subsynchronous resonance (SSR) can result if too much series compensation is applied
• More XC means higher fR
• SSR usually in the range of 10 to 50Hz
rad/s
Hz
IEEE definition: “Subsynchronous resonance (SSR) is an electric powercondition where the electric network exchanges energy with a turbine/generator at one or more of the natural frequencies of thecombined system below the synchronous frequency of the system.”
Reference: EPRI Power Systems Dynamics Tutorial
Briefly - Series Capacitors
• Series capacitors are bypassed when current through produces voltage across of 150-300%
• Initially bypassed by arrester (non-linear)
• Hard bypassed prior to exceeding MOV energy capability
V
I
Briefly - Series Capacitors
• Series capacitors directly in faulted line will be hard bypassed
• Series capacitors farther away will likely just be partially bypassed as their voltage peaks
• Those not hard bypassed will be quickly re-inserted after fault is cleared
• Hard bypassed will take as long as 5-cycles to reinsert (if at all)
Briefly - Series Capacitors
Series compensation at Dafang, China
Ref: “Series Capacitor By-pass Switch – ABB”
Briefly - Series Capacitors
How can series capacitor bypassing be handled in transient stability analysis?
• TSAT – create user defined model which can be accessed in dynamic editor as SERUDM (TSAT has a test case of a thyristor-controlled series compensator (TCSC) model)
• PSS/E has model called SCGAP2• PSLF has model called SCGAP
Task 1: Rank N-1 Contingencies
• To test the assumption that properly modeled series capacitor bypassing would change the results, a 3-phase fault was place close-in to bus 83 and the rotor angle of generator 112 was recorded.
• This was repeated with the capacitive branches shorted out (bypassed).
• Note that while the results will eliminate the effects of series capacitors, they still will not accurately reflect system response
Task 1: Rank N-1 Contingencies
• Initial run in black, run with series capacitors bypassed in red• Note that initial case loses stability shortly after fault inception
Task 2: Critical Clearing Time• TSAT was able to identify the CCT by gradually
increasing the clearing time until the stability criterion became negative.
• The closer the faulted line is to generator 112, the smaller the CCT
Contingency
CCT (cycles) Faulted Line
LM1-1 4.58 172 to 83 circuit 1
LM1-2 4.58 172 to 173 circuit 1
LM1-3 1.76 169 to 168 circuit 1
LM1-4 1.76 169 to 114 circuit 1
LM1-5 1.76 171 to 170 circuit 1
Task 2: Critical Clearing Time• Cannot transmit
power through zero voltage bus
P=𝑉 𝑆𝑉 𝑅
𝑋 sin∅
Task 3: Load Model Comparison
• The load models were varied as shown:
• Note that conversion to a constant impedance load was required below a certain threshold for TSAT to calculate solutions for all contingencies
• Results for LM2, LM3, and LM4 were compared to the CCT values from LM1
Load Model Description Conversio
n
LM1 P as 100% constant IQ as 100% constant Z V = 0.7 p.u.
LM2 P and Q as 100 % constant Z N/A
LM3 P and Q as 100 % constant I
V = 0.35 p.u.
LM4 P and Q as 100 % constant P
V = 0.85 p.u.
Task 3: Load Model Comparison
• Constant impedance (LM2) performs better than the mixed model (LM1)
• Constant current (LM3) and power (LM4) cannot solve unless certain buses are converted back to constant impedance (LM2)
• Even after this, LM3 and LM4 underperform LM1
Contingency
CCT (cycles)
LM1 LM2 LM3 LM4
LM1-1 1.77 2.89 1.20 0.50LM1-2 1.77 2.89 1.20 0.50LM1-3 4.58 6.64 2.05 0.50LM1-4 4.58 7.11 2.05 0.50LM1-5 1.77 2.89 1.20 0.50
Task 3: Load Model Comparison
Thank You!