www.ormazabal.com Reliable innovation. Personal solutions. MV/LV Transformers for Distribution Network Solutions Distribution Transformers Up to 36 kV and up to 5 MVA IEC Standards

Upload: jobpei2

Post on 24-Nov-2015

26 views

Category:

Documents


2 download

DESCRIPTION

CA-109-EN-1311

TRANSCRIPT

  • www.ormazabal.com

    Reliable innovation. Personal solutions.

    MV/LV Transformers for Distribution Network Solutions

    Distribution TransformersUp to 36 kV and up to 5 MVA IEC Standards

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    Contens

    IntroductIon _________________________ 1Preface 1

    Your Electrical Network 2

    Your Business and DNS Applications 2

    Our Product Map (SSS& DNS) 3

    MaIn features _______________________ 4Safety 4

    Reliability 6

    Efficiency 6

    Sustainability 7

    Continuous innovation 7

    technIcal detaIls ______________________ 8Family 8

    Applied Standards 8

    Constructive structure 8

    desIgn characterIstIcs __________________ 9Low voltage connection 9

    Medium voltage connection 9

    Standard equipment 10

    Optional equipment 11

    Other dielectric liquids 11

    Type of Transformers ____________________________________ 12

    Characteristics 24 kV: D0 CK (AB) 12

    Characteristics 24 kV: C0 CK (AC) 14

    Characteristics 24 kV: C0 BK (CC) 16

    Characteristics 36 kV: B036 BK36 18

    The quality of the products designed, manufactured and installed by Ormazabal is backed by the implementation and certification of a quality management system, based on international standard ISO9001:2008.Our commitment to the environment is reaffirmed with the implementation and certification of an environmental management system as laid down in international standard ISO14001.In view of the constant evolution in standards and design, the characteristics of the elements contained in this catalogue are subject to change without prior notification.These characteristics, as well as the availability of components, are subject to confirmation by Ormazabal.

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    1

    PrefaceThe incorporation into Ormazabal in 2001 of the distribution transformer manufacturer Cotradis constituted a strategic milestone for us.

    The exchange of know-how between our technical teams has significantly reinforced the value added for our customers.

    Growing energy demands, higher quality requirements in energy supply and the priority to reduce the consumption of natural resources require the use of equipment which responds with high levels of reliability, safety and energy efficiency.

    Focusing on the needs of our customers and mastering new technologies allows us to offer products which comply with these requirements.

    Our specialisation in Medium Voltage is backed by the certification of our transformers in major European electrical companies.

    We manufacture a wide range of dielectric liquid immersed distribution transformers, compliant with all of the requirements in current international regulations and with a range of powers from 25 kVA to 5000 kVA and insulation levels up to 36 kV.

    Furthermore, close collaboration with our customers enables us to develop transformers conforming to their own particular standards and specifications.

    Ormazabal is the leading provider of personalized solutions to electrical utilities, to energy end users as well as renewable energy systems applications based on our own technology.

    We encourage the development of the electrical sector concerning the challenges of the future energy needs. We cooperate with the world's leading local, regional and global companies in the electrical sector with a strong commitment to innovation for personal safety, network reliability, energy efficiency, and sustainability.

    Our highly qualified and focused team of professionals thrilled by innovation have developed our own products and solutions during our more than a century long consolidated history, always by establishing close relationship with our clients towards achieving mutual long term benefits.

    Velatia is an international industrial and technological group which operates in the areas of electrical networks, electronics and communication networks as well as in the consulting, security and aviation sectors, where security, efficiency and reliability are valued.

    Grupo Ormazabal is now called Velatia. We have combined our forces to transform ourselves into a stronger group. Made up of companies with more than a hundred years of experience and committed to innovation to meet the present and future needs of our customers, wherever they may be.

    The solutions of the companies in Velatia seek to make the world a more connected, more sustainable, smarter, better connected, safer, more humane place.

    Introduction

    Kalkbukt PV Plant (Republic of South Africa)

    Public Distribution EDF utility (France)

    Athletic Bilbao Stadium (Bilbao, Spain)

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    2

    Your Electrical Network"Your dedicated partner for reliable and intelligent electrical network"

    Your Business and DNS ApplicationsClose relationship with our customers and the profound knowledge of the electrical business are the keys to success that enable us to offer Distribution Network Solutions (DNS) based on high added value products and services adapted to the needs of the electrical utilities, electrical energy end users and renewable energies.

    Smart GridTransmission & Distribution

    Generation

    Infrastructures Industrial Tertiary

    Wind Solar

    Dispatchable RES

    Distributors OEM EPC

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    3

    Our Product Map (SSS& DNS)We believe that excellence does not lie solely in offering effective products and services, but also in the ability to respond to individual requirements and demands.

    We provide our clients with personalised projects for efficient energy management via Primary and Secondary Distribution equipment and solutions.

    Our Business Lines

    SSS: Substation Solution for primary distribution

    DNS: Distribution Network Solutions for secondary distribution

    Our products for your segment

    CPG.1 CPG.0 GAE 1250kMAX AMCCiBOR ORMA-

    CONTAINERPrefabricated substationsA-CiBOR NVL-CiBOR

    CGM.3 GAE GA CGMCOSMOS [IEC - ANSI/IEEE]CGMCOSMOS

    [HN]EA

    Protection, automation and controlDistribution transformers Low voltage

    boardConventional oil ORGANIC TPC

    Concrete prefabricated transformer substations (TS) Metallic prefabricated TS CEADS

    Switching nodesUnderground Walk-in Compact

    Concrete enclosure for transformer substations (TS) Metallic enclosure for TS

    Photovoltaic substation

    Mobile substationUnderground Walk-in Modular

    Current family ekorSYS family

    Advanced metering, sensing & analytics and communications

    Protection, automation and control

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    4

    SafetyOur transformers are subjected to the tests described in the IEC 60076 series of standards.

    We have our own laboratories for this purpose, equipped with modern, precise measurement devices and systems that are certified and calibrated according to the directives of the ISO 9001 standard, to ensure that our products comply with the most demanding quality standards.

    Routine testAll of the transformers manufactured are subjected to the following routinetests, in accordance with IEC60076-1:Winding resistance measurement.Measurement of the voltage ratio

    and verification of the vector group.

    Measurement of the short-circuit impedance and load losses.

    Measurement of no -load losses and current.

    Dielectric routine tests:Separate source AC withstand

    voltage test (also known as Applied over-voltage test or Power frequency test)

    Induced AC voltage test (ACSD) (also known as Short duration induced AC withstand voltage test)

    Separate source AC withstand voltage test(Applied over-voltage test or Power frequency test)

    MV LVHighest voltage for the equipment, Um, (Insulation Level).

    [kV] 12 17.5 24 36 1.1 3.6

    Rated withstand Voltage of the test (1minute).

    [kV] 28 38 50 70 3 10

    Type testWith our customers agreement, the following tests are performed in accordance with current international regulations:Temperature-rise test.Dielectric type tests: Lightning impulse (LI) test.

    Lightning impulse (LI) test

    MV LVHighest voltage for the equipment, Um, (Insulation Level).

    [kV] 12 17.5 24 36 1.1 3.6Rated withstand Voltage for Lightning impulse test (1.2 / 50s).

    [kV] 75 95 125 170 20 20

    Main features

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    5

    Special testSpecial tests specifically requested by the customer:Special dielectric tests.Partial discharge measurement

    test.Winding capacities measurement

    earth and between windings.Zero-sequence (homopolar)

    impedance measurement (in three-phase transformers).

    Ability to withstand Short-circuit test (IEC 60076-5), performed in accredited external and internal laboratories (HPL).

    Sound level measurement(IEC 60076-10).

    Measurement of no-load current harmonics.

    Measurement of insulation resistance and/or measurement of the dissipation factor (tan delta) of the insulation capacitances.

    Additional testDielectric Oil Tests

    The transformers operative life is largely related to the quality of the dielectric liquid. We assure the highest quality standards by means of strict qualification and product auditing processes as well as by applying the most advanced technologies in the treatment process.Density at 20CViscosity at 40CWater contentBreakdown voltageDielectric dissipation factor Interfacial tensionAcidityFlash point

    Tank TestsEN 50464-4 Endurance test

    Paint TestsFilm Thickness measurementAdherence testHardness testBend test Impact testCupping testSalt spray test

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    6

    ReliabilityThe quality and reliability of our products is demonstrated through the testing and certification of our transformers in independent, internationally-renowned laboratories.

    Furthermore, the technological development and passion for innovation, which has been fundamentally apparent throughout the history of our company, is reinforced by our High Power Laboratory (HPL) with a capacity up to 2500 MVA.

    These are our own facilities which enable ongoing tests and which combined with our highly-qualified staff, further certify our technological independence.

    Together with external organisations and official bodies, we also participate in market quality control campaigns to assure the verification of our products.

    Efficiency Dielectric Liquid completely immersed Hermetically-Sealed TransformerHermetically-sealed tanks: No expansion tank is needed.

    Less dielectric liquid used than in other types of transformer.

    No contact between the dielectric liquid and external agents (air, humidity, pollution, etc.)

    Prevents deterioration of the dielectrics characteristics.

    Low-level maintenance.

    Minimal risk of leakages: Tank robustness (high quality materials).

    Welding processes carried out by qualified staff.

    Leak tests performed in all transformers.

    Minimal Environmental ImpactRespect for the environment: Use of highly-recyclable materials.

    Rationalisation in the use of raw materials.

    Optimised transformer dimensions

    Optimum consumption of raw materials:

    Materials selection.

    Maximisation of their characteristics.

    Low electrical energy consumption:

    Advanced technology in design, manufacturing and testing.

    Minimal loss transformers.

    Safe, reliable products.

    ISO 14001 certification.

    Low Noise LevelAn optimum design and assembly

    of the ferromagnetic core enables us to drastically reduce the level of noise generated by the transformer.

    There are two components that identify the level of noise produced by a transformer: LwA = LpA + KSWhere:

    LwA: Acoustic Power (cause)

    LpA: Acoustic Pressure (effect)

    KS factor (>0) which depends on the size of the transformer.

    To define a transformer, the use of Acoustic Power LwA is recommended since it is a value which is independent from the environment and is therefore the best magnitude for assessing the acoustic emissivity of a transformer.

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    7

    PCB FreeOur transformers are only

    manufactured using new components and without any PCBs, in strict compliance with current regulations.

    Electromagnetic CompatibilityOur transformers are passive elements in terms of electromagnetic compatibility. In other words, they work satisfactorily without adding electromagnetic noise that is intolerable for equipment in their surroundings and they withstand such interference caused by other devices.

    The currents that circulate through the conductors connected to the transformers, especially low-voltage ones, can cause significant electromagnetic fields. The installation designer must make sure that these cables are laid such that the fields are minimised or, if necessary, measures must be adopted to limit their effects.

    Sustainability Sustainability, understood as the best compromise between satisfying social demands, caring for the environment and financial aspects.

    Social DemandsSafety of people and goods.Continuity of service.

    Financial AspectsOptimum use of raw materials.Longer equipment life, endurance

    and robustness.Equipment adaptable to network

    evolution.Equipment durability.

    Caring for the EnvironmentReduction in the volume of

    dielectric liquid.Minimal dimensions.Minimal losses in the transformer.Low risk of oil leakage.Non-aggressive for the

    surrounding environment.Recyclability.

    Continuous innovationOur commitment to innovation places us at the technological forefront of Europe.

    Therefore our products meet the most demanding worldwide requirements and are certified by internationally renowned laboratories.

    Recently we have extended our product range to 5 MVA and also we have developed several new transformers with lower losses.

    Our quality, environmental and health& safety prevention policies establish our commitment to fostering and being part of an environmentally-responsible society.

    Within this framework, our quality management system is internationally recognised through ISO 9001 certification.

    Furthermore, our strong commitment to the environment is reflected in the implementation of an environmental management system, certified according to the ISO 14001 standard, which monitors the impact of activities on the environment.

    This policy also aims to promote and establish a culture of excellence and respect for personal health and safety, in accordance with standard OHSAS 18001. Its scope ranges from our team of professionals and partners to the end user.

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    8

    Technical detailsFamilyFrom25to5000kVAInsulationLevel 24 and 36 kV

    Dielectric Liquid Immersed Transformers

    DescriptionThese transformers comply with the following characteristics: Three-phase transformers,

    50Hz for installation indoors or outdoors

    Hermetically-sealedCompletely Immersed in mineral

    oil in accordance with standard IEC 60296.

    ONAN cooling.Colour: RAL 7033 (other colours

    under request).

    The data and values shown correspond to the Normal Service Conditions referred to in standard IEC 60076-1.

    For other configurations, please contact our Technical-Commercial Department.

    Applied StandardsThe transformers comply with the following standards:EN 50464IEC 60076

    Constructive structureActive partThe active part of the transformer is the energy transformation system, composed of the ferromagnetic core, the windings and the medium and low voltage connections.

    Tank and dielectricThe transformers tank and the dielectric liquid provide the necessary insulation and cooling.

    2

    1

    1. Active part2. Tank and dielectric

    Windings Advantages Concentric windings. Insulation between layers: Cellulose with epoxy

    resin which compacts the coils, once cured. Coils are manufactured using the latest

    techniques and machinery.

    Optimised to withstand short circuit forces.

    Expertise in coil cooling. Careful manufacturing of coils and cooling

    channels.

    Improved heat dissipation in the windings.

    Use of high-quality cellulosic materials. Optimum handling and storage to preserve

    insulation properties. Guaranteed insulation.

    Connections and Tap Changer Advantages

    MV and LV terminals. Transformer connection to the outside.

    Off-circuit Tap changer. Secondary voltage can be adjusted precisely.

    Tank and Dielectric Liquid Advantages

    Elastic Corrugated tank with cooling fins.

    Increased heat dissipation surface. Absorption of variations in the volume of the dielectric

    liquid caused by changes in its temperature. Mechanical and electrical protection.

    Completely filled with dielectric liquid and hermetically sealed tank.

    No aging of the dielectric liquid as there is no contact with the air.

    Minimal maintenance requirements. Small size. No expansion tank or air dehydrating needed Lighter in weight. Electromagnetic field shielding.

    Immersed in dielectric liquid. Lower noise level. Better behaviour in the event of overloads and

    harmonics.

    Surface treatment and paint. Protection against corrosion, atmospheric agents, insolation and impacts.

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    9

    Design characteristicsLV single phase Busbar Bushings (optional)

    LV connection Flags

    Metric M12 Metric: from M20 to M55

    Low voltage connectionLV porcelain bushings for 420 V - B2*

    Rated Power [kVA] 25 40 50 63 100 160 250 400 500 630 800 1000 1250 1600 2000 2500

    Rated current [A] 250 250 250 250 250 250 630 630 1000 1000 1600 1600 2000 3150 3150 4000Dimension - Metric d1 M12 M12 M12 M12 M12 M12 M20 M20 M30 M30 M42 M42 M42 M48 M48 M55Material Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass Copper Copper Copper Copper

    Connections parts LV FlagsMetric M12 M12 M12 M12 M12 M12 M20 M20 M30 M30 M42 M42 M42 M48 M48 M55

    e [mm] - - - - - - 32 32 32 32 40 40 40 40 40 70f0 [mm] 40 40 40 40 40 40 60 60 60 60 100 100 100 120 120 150 [mm] 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 18

    LV single pole busbar bushings for indoor installation (optional)Rated Power [kVA] 25 40 50 63 100 160 250 400 500 630 800 1000 1250 1600 2000 2500

    Rated current [A] - - - - - - 630 630 1600 1600 1600 1600 - - - -Material - - - - - - Al Al Copper Copper Copper Copper - - - -

    Please contact Ormazabal for ohter secondary voltages and technical values above 2500 kVA.

    Medium voltage connectionConnectors for mv plug-in bushings (not supplied with the transformer)

    Insulation [kV] 24 36Type A elbow connector (250 A)

    Ref. EUROMOLD K-158LRType B elbow connector (400 A)

    Ref. EUROMOLD M-400LR

    Type A straight connector (250 A)Ref. EUROMOLD K-152SR -

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    10

    Uninhibited mineral insulating oil IEC 60296

    1. Off-circuit regulation tap changer (can only be operated without voltage) IEC 60214

    Off circuit voltage tap changer for dual primary voltage transformers (can only be operated without voltage)

    IEC 60214

    2. MV porcelain bushings EN 50180

    3. LV porcelain bushings EN 50386

    4. LV connection Flags 630 kVA

    5. 2 Earthing terminals in the tank EN 50216-4

    6. Draining and sampling device EN 50216-4

    7. Filling device EN 50464-1

    8. Rating plate EN 50464-1

    9. 2 Lifting eyes EN 50464-1

    10. 4 Latching eyes EN 50464-1

    11. 4 Pulling eyes EN 50464-1

    12. Thermometer pocket EN-50216-4

    13. Wheels 250 kVA EN-50216-4

    Standard equipment

    1 4

    29

    73

    2

    8

    5

    1210

    11

    13

    6

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    11

    Other dielectric liquidsORGANIC transformers: Natural,

    biodegradable ester for application in electrical transformers. Class K with fire point greater than 300 C.

    Dielectric liquid silicone according to the IEC 60836 standard, Class K with fire point greater than 300 C.

    Synthetic biodegradable ester for application in electrical transformers according to the IEC61099 standard. Class K, with fire point greater than 300C.

    Optional equipment

    1. MV plug-in bushings EN 50180

    2. LV single pole busbar bushings EN 50387

    3. Thermometer: measures the temperature of the top layer of the insulation liquid. Available with 2 contacts (alarm and trigger) and upper limit marker.

    4. Protection relay Functions: Internal tank pressure control Dielectric liquid temperature control Oil level control and gas detection

    EN 50216-3

    5. Dielectric liquid collection device

    6. Terminal cover box

    7. Pole mounting brackets and support for surge arresters (application for pole mounted transformers up to 160 kVA).

    21

    6

    3

    5

    4

    7

    7

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    12

    Type of transformersCharacteristics 24 kV: D0 CK (AB) From250upto5000kVAInsulationLevel24kVDielectric Liquid Immersed Transformers

    Electrical characteristics 24 kV: D0 CK (AB)Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500(*)

    Rated Voltage (Ur)Primary [kV] 20No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Dyn11/ Dyn5No-Load Losses - Po [W] List D0 530 750 880 1030 1150 1400 1750 2200 2700 3200Load Losses - Pk [W] List Ck 3250 4600 5500 6500 8400 10500 13500 17000 21000 26500Short-Circuit Impedance (%) at 75C 4 4 4 4 6 6 6 6 6 6Sound Power Level LwA [dB] List D0 60 63 64 65 66 68 69 71 73 76

    Voltage drop at full load (%)cos=1 1.37 1.22 1.16 1.11 1.19 1.22 1.25 1.24 1.22 1.23cos=0.8 3.33 3.25 3.21 3.17 4.44 4.47 4.49 4.48 4.47 4.47

    Efficiency (%)load 100%

    cos=1 98.51 98.68 98.75 98.82 98.86 98.82 98.79 98.81 98.83 98.83cos=0.8 98.15 98.36 98.44 98.53 98.58 98.53 98.50 98.52 98.54 98.54

    load 75%cos=1 98.76 98.90 98.96 99.02 99.06 99.04 99.01 99.03 99.04 99.04cos=0.8 98.45 98.63 98.70 98.78 98.83 98.80 98.77 98.79 98.81 98.81

    Dimensions [mm]Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500A (Length) 1376 1537 1622 1622 1932 1997 2007 1922 1965 2093B (Width) 930 941 962 962 1161 1200 1200 1224 1277 1487C (Height to cover) 915 1004 1026 1092 1112 1158 1230 1517 1715 1737D1 (Height to MV with porcelain bushings) 1300 1389 1411 1477 1497 1543 1615 1902 2100 2122D3 (Height to MV Plug-In bushings) 1004 1093 1115 1181 1201 1247 1319 1606 1804 1826D2 (Height to LV with Flags) 1149 1238 1287 1353 1445 1491 1563 1886 2084 2167F (Separation between MV bushings) 275 275 275 275 275 275 275 275 275 275H (separation between LV bushings) 150 150 150 150 150 150 150 200 200 200J (Distance between wheel axis) 670 670 670 670 670 670 820 820 820 1070K (wheel width) 40 40 40 40 40 40 70 70 70 70 (wheel diameter) 125 125 125 125 125 125 200 200 200 200L (Wheel) 110 110 110 110 110 110 165 165 165 165

    Oil Volume [Litres] 260 330 390 410 510 530 540 1000 1200 1400Total weight [Kg] 1010 1330 1600 1750 2250 2430 2750 3850 4750 5350

    Lifting Eyes LV Bushings MV Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    Draining and Sampling Device

    Earth connectionM12

    MV Regulation Tap Changer

    Filling Device

    Lifting Eyes

    LV Bushings

    MV Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    MV Regulation Tap Changer

    Filling Device

    Draining and Sampling Device

    Earth connectionM12

    F F F

    J

    H H

    A

    H

    B

    F

    K

    D2

    M

    L

    D2

    M LC

    J

    D1D3C

    KJ J

    H H

    A

    B

    H

    MV Plug-In Bushings MV Porcelain Bushings

    (*) Please contact Ormazabal for technical values above 2500 kVA.

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    13

    Characteristics 24 kV: D0 CK (AB) From25upto160kVAInsulationLevel24kVDielectric Liquid Immersed Transformers

    LV Bushings

    MV Bushings Surge arresters support (Op) Lifting Eyes

    Latching eyes

    Filling Device

    MV Regulation Tap Changer

    Wheel Frames (skids)

    Thermometer Pocket(optional)

    Draining and Sampling Device

    Earth connectionM12

    MV Porcelain BushingsF

    JK

    A

    H H H

    B

    D2 D

    1C

    LL80

    J

    140

    F

    Electrical characteristics 24 kV: D0 CK (AB)Rated Power [kVA] 25 40 50 63 100 160

    Rated Voltage (Ur)Primary [kV] 20No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Yzn11/Dyn11 Dyn/YznNo-Load Losses - Po [W] List D0 95 125 145 175 260 375Load Losses - Pk [W] List Ck 700 940 1100 1270 1750 2350Short-Circuit Impedance (%) at 75C 4 4 4 4 4 4Sound Power Level LwA [dB] List D0 47 49 50 51 54 57

    Voltage drop at full load (%)cos=1 2.84 2.40 2.26 2.08 1.81 1.54cos=0.8 3.96 3.83 3.77 3.70 3.57 3.43

    Efficiency (%)load 100%

    cos=1 96.92 97.41 97.57 97.76 98.03 98.33cos=0.8 96.18 96.78 96.98 97.21 97.55 97.92

    load 75%cos=1 97.46 97.87 98.00 98.15 98.37 98.61cos=0.8 96.84 97.35 97.52 97.70 97.97 98.26

    Dimensions [mm]Rated Power [kVA] 25 40 50 63 100 160A (Length) 888 888 888 926 1006 1205B (Width) 704 704 704 735 796 848C (Height to cover) 768 810 810 844 889 847D1 (Height to MV with porcelain bushings) 1153 1195 1195 1229 1274 1232D3 (Height to MV Plug-In bushings) 857 899 899 933 978 936D2 (Height to LV with Flags) 918 960 960 994 1039 997F (Separation between MV bushings) 275 275 275 275 275 275H (separation between LV bushings) 80 80 80 80 80 80J (Distance between wheel axis) 520 520 520 520 520 520K (wheel width) 40 40 40 40 40 40 (wheel diameter) 125 125 125 125 125 125L (Wheel) 110 110 110 110 110 110Distance between pole mounting brackets 530 530 530 530 530 530

    Oil Volume [Litres] 100 105 105 120 155 200Total weight [Kg] 360 400 435 515 610 770

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    14

    Characteristics 24 kV: C0 CK (AC) From250upto5000kVAInsulationLevel24kVDielectric Liquid Immersed Transformers

    Lifting Eyes LV Bushings MV Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    Draining and Sampling Device

    Earth connectionM12

    MV Regulation Tap Changer

    Filling Device

    Lifting Eyes

    LV Bushings

    MV Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    MV Regulation Tap Changer

    Filling Device

    Draining and Sampling Device

    Earth connectionM12

    F F F

    J

    H H

    A

    H

    B

    F

    K

    D2

    M L

    D2

    M LC

    J

    D1D3C

    KJ J

    H H

    A

    B

    H

    MV Plug-In Bushings MV Porcelain Bushings

    Electrical characteristics 24 kV: C0 CK (AC)Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500(*)

    Rated Voltage (Ur)Primary [kV] 20No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Dyn11/ Dyn5No-Load Losses - Po [W] List C0 425 610 720 860 930 1100 1350 1700 2100 2500Load Losses - Pk [W] List Ck 3250 4600 5500 6500 8400 10500 13500 17000 21000 26500Short-Circuit Impedance (%) at 75C 4 4 4 4 6 6 6 6 6 6Sound Power Level LwA [dB] List C0 55 58 59 60 61 63 64 66 68 71

    Voltage drop at full load (%)cos=1 1.37 1.22 1.17 1.11 1.22 1.22 1.25 1.24 1.25 1.23cos=0.8 3.33 3.25 3.22 3.17 4.47 4.47 4.49 4.48 4.48 4.47

    Efficiency (%)load 100%

    cos=1 98.55 98.71 98.77 98.85 98.85 98.85 98.83 98.84 98.83 98.85cos=0.8 98.20 98.40 98.47 98.56 98.56 98.57 98.54 98.56 98.55 98.57

    load 75%cos=1 98.81 98.95 98.99 99.05 99.07 99.07 99.06 99.07 99.06 99.08cos=0.8 98.52 98.69 98.74 98.82 98.84 98.85 98.82 98.84 98.83 98.85

    Dimensions [mm]Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500A (Length) 1376 1537 1622 1622 1932 1997 2007 1922 1965 2157B (Width) 930 941 962 962 1161 1245 1224 1224 1277 1487C (Height to cover) 960 1004 1026 1114 1123 1158 1252 1517 1715 1737D1 (Height to MV with porcelain bushings) 1345 1389 1411 1499 1508 1543 1637 1902 2100 2122D3 (Height to MV Plug-In bushings) 1049 1093 1115 1203 1212 1247 1341 1606 1804 1826D2 (Height to LV with Flags) 1194 1238 1287 1375 1456 1491 1585 1886 2084 2167F (Separation between MV bushings) 275 275 275 275 275 275 275 275 275 275H (separation between LV bushings) 150 150 150 150 150 150 150 200 200 200J (Distance between wheel axis) 670 670 670 670 670 670 820 820 820 1070K (wheel width) 40 40 40 40 40 40 70 70 70 70 (wheel diameter) 125 125 125 125 125 125 200 200 200 200L (Wheel) 110 110 110 110 110 110 165 165 165 165

    Oil Volume [Litres] 270 320 390 395 480 510 550 1020 1230 1390Total weight [Kg] 1090 1355 1640 1835 2310 2510 2905 4020 4850 5525

    (*) Please contact Ormazabal for technical values above 2500 kVA.

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    15

    Characteristics 24 kV: C0 CK (AC) From25upto160kVAInsulationLevel24kVDielectric Liquid Immersed Transformers

    LV Bushings

    MV Bushings Surge arresters support (Op) Lifting Eyes

    Latching eyes

    Filling Device

    MV Regulation Tap Changer

    Wheel Frames (skids)

    Thermometer Pocket(optional)

    Draining and Sampling Device

    Earth connectionM12

    MV Porcelain BushingsF

    JK

    A

    H H H

    B

    D2 D

    1C

    LL80

    J

    140

    F

    Electrical characteristics 24 kV: C0 CK (AC)Rated Power [kVA] 25 40 50 63 100 160

    Rated Voltage (Ur)Primary [kV] 20No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Dyn11/ Dyn5 Dyn/YznNo-Load Losses - Po [W] List C0 75 105 125 145 210 300Load Losses - Pk [W] List Ck 700 940 1100 1270 1750 2350Short-Circuit Impedance (%) at 75C 4 4 4 4 4 4Sound Power Level LwA [dB] List C0 45 47 47 48 49 52

    Voltage drop at full load (%)cos=1 2.84 2.40 2.26 2.08 1.81 1.54cos=0.8 3.96 3.83 3.77 3.70 3.57 3.43

    Efficiency (%)load 100%

    cos=1 96.99 97.45 97.61 97.80 98.08 98.37cos=0.8 96.27 96.84 97.03 97.27 97.61 97.97

    load 75%cos=1 97.56 97.93 98.06 98.21 98.43 98.67cos=0.8 96.97 97.43 97.58 97.78 98.05 98.34

    Dimensions [mm]Rated Power [kVA] 25 40 50 63 100 160A (Length) 888 888 888 926 1.006 1.205B (Width) 704 704 704 735 796 848C (Height to cover) 780 869 828 859 911 847D1 (Height to MV with porcelain bushings) 1165 1254 1213 1244 1296 1232D3 (Height to MV Plug-In bushings) 869 958 917 948 1.000 936D2 (Height to LV with Flags) 930 1.019 978 1.009 1.061 997F (Separation between MV bushings) 275 275 275 275 275 275H (separation between LV bushings) 80 80 80 80 80 80J (Distance between wheel axis) 520 520 520 520 520 520K (wheel width) 40 40 40 40 40 40 (wheel diameter) 125 125 125 125 125 125L (Wheel) 110 110 110 110 110 110Distance between pole mounting brackets 530 530 530 530 530 530

    Oil Volume [Litres] 100 110 100 125 150 190Total weight [Kg] 370 440 445 520 670 790

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    16

    Characteristics 24 kV: C0 BK (CC)From250upto5000kVAInsulationLevel24kVDielectric Liquid Immersed Transformers

    Lifting Eyes LV Plug-In Bushings MV Porcelain Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    Draining and Sampling Device

    Earth connectionM12

    MV Regulation Tap Changer

    Filling Device

    Lifting Eyes

    LV Plug-In Bushings

    MV Porcelain Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    MV Regulation Tap Changer

    Filling Device

    Draining and Sampling Device

    Earth connectionM12

    F F F

    J

    H H

    A

    H

    B

    F

    K M L

    D2

    M L

    D2

    C

    J

    D1D3C

    KJ J

    H H

    A

    B

    H

    LV Plug-In Bushings MV Porcelain Bushings

    Electrical characteristics 24 kV: C0 BK (CC)Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500(*)

    Rated Voltage (Ur)Primary [kV] 20No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Dyn11/ Dyn5No-Load Losses - Po [W] List D0 425 610 720 860 930 1100 1350 1700 2100 2500Load Losses - Pk [W] List Bk 2750 3850 4600 5400 7000 9000 11000 14000 18000 22000Short-Circuit Impedance (%) at 75C 4 4 4 4 6 6 6 6 6 6Sound Power Level LwA [dB] List C0 55 58 59 60 61 63 64 66 68 71

    Voltage drop at full load (%)cos=1 1.17 1.04 1.00 0.93 1.05 1.08 1.06 1.05 1.08 1.06cos=0.8 3.22 3.13 3.10 3.06 4.35 4.37 4.38 4.35 4.35 4.35

    Efficiency (%)load 100%

    cos=1 98.75 98.90 98.95 99.02 99.02 99.00 98.98 99.03 99.03 99.03cos=0.8 98.44 98.63 98.69 98.77 98.78 98.75 98.73 98.79 98.79 98.79

    load 75%cos=1 98.96 99.08 99.13 99.18 99.20 99.19 99.17 99.21 99.21 99.21cos=0.8 98.70 98.86 98.91 98.98 99.00 98.98 98.97 99.01 99.02 99.02

    Dimensions [mm]Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500A (Length) 1376 1537 1622 1569 1997 1997 2007 1965 1965 2480B (Width) 930 941 962 962 1200 1200 1182 1277 1277 1426C (Height to cover) 915 1004 1092 1169 1158 1158 1373 1671 1715 1836D1 (Height to MV with porcelain bushings) 1300 1389 1477 1554 1543 1543 1758 2056 2100 2221D3 (Height to MV Plug-In bushings) 1004 1093 1181 1258 1247 1247 1462 1760 1804 1925D2 (Height to LV with Flags) 1149 1238 1353 1430 1491 1491 1706 2040 2084 2266F (Separation between MV bushings) 275 275 275 275 275 275 275 275 275 275H (separation between LV bushings) 150 150 150 150 150 150 150 200 200 200J (Distance between wheel axis) 670 670 670 670 670 670 820 820 820 1070K (wheel width) 40 40 40 40 40 40 70 70 70 70 (wheel diameter) 125 125 125 125 125 125 200 200 200 200L (Wheel) 110 110 110 110 110 110 165 165 165 165

    Oil Volume [Litres] 260 325 390 390 520 500 660 1200 1245 1340Total weight [Kg] 1100 1420 1810 1920 2530 2560 3200 4950 5150 5750

    (*) Please contact Ormazabal for technical values above 2500 kVA.

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    17

    LV Bushings

    MV Bushings Surge arresters support (Op) Lifting Eyes

    Latching eyes

    Filling Device

    MV Regulation Tap Changer

    Wheel Frames (skids)

    Thermometer Pocket(optional)

    Draining and Sampling Device

    Earth connectionM12

    MV Porcelain BushingsF

    JK

    A

    H H H

    B

    D2 D

    1C

    L

    80

    J

    140

    F

    Characteristics 24 kV: C0 BK (CC)From25upto160kVAInsulationLevel24kVDielectric Liquid Immersed Transformers

    Electrical characteristics 24 kV: C0 BK (CC)Rated Power [kVA] 25 40 50 63 100 160

    Rated Voltage (Ur)Primary [kV] 20No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Yzn11 / Yzn5 Dyn/YznNo-Load Losses - Po [W] List C0 75 105 125 145 210 300Load Losses - Pk [W] List Bk 560 750 875 1050 1475 2000Short-Circuit Impedance (%) at 75C 4 4 4 4 4 4Sound Power Level LwA [dB] List C0 45 47 47 48 49 52

    Voltage drop at full load (%)cos=1 2.29 1.94 1.81 1.73 1.54 1.32cos=0.8 3.79 3.63 3.57 3.53 3.43 3.31

    Efficiency (%)load 100%

    cos=1 97.52 97.91 98.04 98.14 98.34 98.58cos=0.8 96.92 97.40 97.56 97.68 97.94 98.23

    load 75%cos=1 97.96 98.27 98.38 98.47 98.63 98.83cos=0.8 97.47 97.85 97.98 98.09 98.30 98.54

    Dimensions [mm]Rated Power [kVA] 25 40 50 63 100 160A (Length) 888 888 926 926 1006 1205B (Width) 704 704 704 704 796 848C (Height to cover) 780 869 848 899 911 847D1 (Height to MV with porcelain bushings) 1165 1254 1233 1284 1296 1232D3 (Height to MV Plug-In bushings) 869 958 937 988 1000 936D2 (Height to LV with Flags) 930 1019 998 1049 1061 997F (Separation between MV bushings) 275 275 275 275 275 275H (separation between LV bushings) 80 80 80 80 80 80J (Distance between wheel axis) 520 520 520 520 520 520K (wheel width) 40 40 40 40 40 40 (wheel diameter) 125 125 125 125 125 125L (Wheel) 110 110 110 110 110 110Distance between pole mounting brackets 530 530 530 530 530 530

    Oil Volume [Litres] 100 110 115 125 160 190Total weight [Kg] 380 460 490 548 690 820

  • Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

    18

    Characteristics 36 kV: B036 BK36From250upto5000kVAInsulationLevel36kVDielectric Liquid Immersed Transformers

    Lifting Eyes

    LV Plug-In BushingsMV Porcelain Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    MV Regulation Tap Changer

    Filling Device

    LV Plug-In Bushings

    Draining and Sampling Device

    Earth connectionM12

    Lifting Eyes

    LV Plug-In Bushings MV Porcelain Bushings

    Wheel Frames (skids)

    Thermometer Pocket

    MV Regulation Tap Changer

    MV Porcelain Bushings

    Filling Device

    Draining and Sampling Device

    Earth connectionM12

    F F

    KJ J K

    J J

    J

    F F

    A

    H H H

    B

    D2

    C D3

    D2 D1C

    LM

    M L

    A

    B

    H H H

    Electrical characteristics 36 kV: B036 BK36Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500(*)

    Rated Voltage (Ur)Primary [kV] 25No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Dyn11 / Dyn5No-Load Losses - Po [W] List B036 650 930 1100 1300 1500 1700 2100 2600 3150 3800Load Losses - Pk [W] List BK36 3500 4900 5600 6500 8400 10500 13500 17000 21000 26500Short-Circuit Impedance (%) at 75C 4.5 4.5 4.5 4.5 6 6 6 6 6 6Sound Power Level LwA [dB] List B036 62 65 66 67 68 68 70 71 73 76

    Voltage drop at full load (%)cos=1 1.49 1.32 1.21 1.13 1.22 1.22 1.25 1.24 1.22 1.23cos=0.8 3.72 3.62 3.55 3.50 4.47 4.47 4.49 4.48 4.47 4.47

    Efficiency (%)load 100%

    cos=1 98.37 98.56 98.68 98.78 98.78 98.79 98.77 98.79 98.81 98.80cos=0.8 97.97 98.21 98.35 98.48 98.48 98.50 98.46 98.49 98.51 98.51

    load 75%cos=1 98.62 98.79 98.88 98.96 98.97 99.00 98.98 99.00 99.01 99.01cos=0.8 98.28 98.49 98.60 98.71 98.72 98.75 98.72 98.75 98.77 98.77

    Dimensions [mm]Rated Power [kVA] 250 400 500 630 800 1000 1250 1600 2000 2500A (Length) 1376 1537 1622 1592 1932 1997 2007 1922 1965 2093B (Width) 930 941 962 962 1161 1200 1200 1224 1277 1487C (Height to cover) 915 1004 1026 1092 1112 1158 1230 1517 1715 1737D1 (Height to MV with porcelain bushings) 1368 1442 1464 1530 1550 1596 1668 1955 2153 2175D3 (Height to MV Plug-In bushings) 1050 1139 1161 1227 1247 1293 1365 1652 1850 1872D2 (Height to LV with Flags) 1149 1238 1287 1353 1445 1491 1563 1886 2084 2167F (Separation between MV bushings) 375 375 375 375 375 375 375 375 375 375H (separation between LV bushings) 150 150 150 150 150 150 150 200 200 200J (Distance between wheel axis) 670 670 670 670 670 670 820 820 820 1070K (wheel width) 40 40 40 40 40 40 70 70 70 70 (wheel diameter) 125 125 125 125 125 125 200 200 200 200L (Wheel) 110 110 110 110 110 110 165 165 165 165

    Oil Volume [Litres] 260 340 390 410 500 530 550 1000 1200 1400Total weight [Kg] 1000 1330 1600 1800 2220 2480 2780 3850 4850 5350

    (*) Please contact Ormazabal for technical values above 2500 kVA.

  • Dielectric liquid immersed transformersTransformers for Distribution Network Solutions up to 36 kV

    19

    LV Bushings

    MV Bushings Surge arresters support (Op)

    Lifting Eyes

    Latching eyes

    Filling Device

    MV Regulation Tap Changer

    Wheel Frames (skids)

    Thermometer Pocket(optional)

    Draining and Sampling Device

    Earth connectionM12

    Characteristics 36 kV: B036 BK36 From25upto160kVAInsulationLevel36kVDielectric Liquid Immersed Transformers

    F

    J

    H

    A

    B

    HH

    JK

    D2

    D1

    C

    L

    140

    80

    FMV Porcelain Bushings

    Electrical characteristics 36 kV: C036 BK36Rated Power [kVA] 25 40 50 63 100 160

    Rated Voltage (Ur)Primary [kV] 20No-load Secondary [V] 400 / 410 / 415 / 420 (to be defined)

    Vector Group Yzn11 / Yzn5 Dyn/YznNo-Load Losses - Po [W] List B036 115 165 190 225 320 460Load Losses - Pk [W] List Bk36 900 1110 1250 1435 1950 2550Short-Circuit Impedance (%) at 75C 4.5 4.5 4.5 4.5 4.5 4.5Sound Power Level LwA [dB] List B036 50 51 52 53 56 59

    Voltage drop at full load (%)cos=1 3.64 2.84 2.57 2.35 2.03 1.68cos=0.8 4.50 4.35 4.26 4.17 4.01 3.83

    Efficiency (%)load 100%

    cos=1 96.10 96.91 97.20 97.43 97.78 98.15cos=0.8 95.17 96.17 96.53 96.81 97.24 97.70

    load 75%cos=1 96.79 97.44 97.67 97.86 98.15 98.45cos=0.8 96.02 96.82 97.11 97.34 97.69 98.06

    Dimensions [mm]Rated Power [kVA] 25 40 50 63 100 160A (Length) 888 926 926 926 1006 1205B (Width) 704 725 725 725 796 848C (Height to cover) 768 810 810 859 889 847D1 (Height to MV with porcelain bushings) 1221 1263 1263 1312 1342 1300D2 (Height to LV with Flags) 918 960 960 1009 1039 997F (Separation between MV bushings) 375 375 375 375 375 375H (separation between LV bushings) 80 80 80 80 80 80J (Distance between wheel axis) 520 520 520 520 520 520K (wheel width) 40 40 40 40 40 40 (wheel diameter) 125 125 125 125 125 125L (Wheel) 110 110 110 110 110 110Distance between pole mounting brackets 530 530 530 530 530 530

    Oil Volume [Litres] 100 125 130 130 160 200Total weight [Kg] 330 430 475 490 610 760

  • 20

    Notes

    Dielectric liquid immersed transformers Transformers for Distribution Network Solutions up to 36 kV

  • CA-109-EN-1311