William Fisher Architecture, Inc. 603 Front Street, Santa Cruz, California 95060 831 246 - 0117 bill@modern - architecture.com modern - architecture.com Licensed Architect William Fisher C−11008 10/31/19 RENEWS ON A I N O F I L A R C COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC. Date Printed: 10/2/2019 11:29:52 AM Cabrillo College A0.0 Cabrillo College Room 356, Building 350 2600 Soquel Ave. Aptos, CA 95003 Issue Date General Notes and Project Information DON'T SCALE THE DRAWINGS. STUDY THE CONTRACT DOCUMENTS AND THE FIELD CONDITIONS BEFORE BIDDING OR DOING WORK ON THIS PROJECT. IMMEDIATELY REPORT TO THE ARCHITECT ANY ERRORS, OMISSIONS, OR UNCLEAR DIRECTIONS. THE ARCHITECT WILL EVALUATE THE PROBLEM AND MAKE A WRITTEN INTERPRETATION. NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DEVIATIONS OR VARIATIONS FROM THE DRAWINGS OR SPECIFICATIONS SHOWN HEREIN. DIMENSIONS MARKED "CLEAR" SHALL BE MAINTAINED AND SHALL ALLOW FOR THICKNESS OF FINISH MATERIALS. DIMENSIONS ARE TAKEN FROM FACE OF FINISH (FOF), OR FROM CENTER LINES AS INDICATED. THE GENERAL CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE PROJECT. THE ARCHITECT MUST BE NOTIFIED IMMEDIATELY OF ANY DEVIATIONS OR VARIATIONS FROM THE DRAWINGS OR SPECIFICATIONS SHOWN HEREIN. "ALIGN" MEANS TO LOCATE FINISHED FACES IN SAME PLANE. "APPROVED" MEANS, UNLESS INDICATED OTHERWISE BY THE ARCHITECT, APPROVED IN WRITING BY THE ARCHITECT. "AS DIRECTED" OR "AS INDICATED" MEANS AS DESCRIBED EITHER VERBALLY OR IN WRITING BY THE ARCHITECT. "AS INDICATED" NORMALLY REFERS TO AN ITEM EXPLAINED IN THE CONTRACT. "THE CONTRACTOR" REFERS TO THE GENERAL CONTRACTOR, NOT HIS SUBCONTRACTORS. "PROVIDE" MEANS THAT THE CONTRACTOR SHALL FURNISH AND INSTALL. "UNLESS NOTED OTHERWISE", "UNO", OR "UNLESS INDICATED OTHERWISE" MEANS THAT THE ITEM DESCRIBED IS TYPICAL AS SHOWN EXCEPT AS WHERE SPECIFICALLY CALLED OUT AS DIFFERENT. "VERIFY" MEANS, UNLESS INDICATED OTHERWISE BY THE ARCHITECT, TO OBTAIN WRITTEN VERIFICATION OF THE ITEM OR METHOD INDICATED FROM THE ARCHITECT. THIS VERIFICATION MIGHT INCLUDE ELABORATION OR EXPLANATION BY THE ARCHITECT REQUIRING A MORE COMPLEX CONSTRUCTION SOLUTION THAN MIGHT BE ASSUMED BY READING THE DRAWING WITHOUT THE VERIFICATION, THEREFORE PLEASE MAKE VERIFICATIONS AS EARLY AS POSSIBLE BEFORE BIDDING THE WORK. APPROVED SHOP DRAWINGS DO NOT CONSTITUTE VERIFICATION. ANY ERROR, OMISSION, OR OTHER CONFLICT BETWEEN THESE DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR HIS RESOLUTION AS SOON AS IT IS DISCOVERED. INFORM THE ARCHITECT IMMEDIATELY IF THE DRAWINGS, SPECIFICATIONS, OR OTHER CONSTRUCTION DOCUMENTS DON'T SEEM TO COMPLY WITH CURRENT APPLICABLE LAWS, CODES, OR REGULATIONS. U.N.O., APPLY, INSTALL, CONNECT, ERECT, CLEAN, AND CONDITION PRODUCTS PER THEIR MANUFACTURER'S CURRENT WRITTEN INSTRUCTIONS. VERIFY WITH MANUFACTURERS THEIR EQUIPMENT REQUIREMENTS (FOR INSTANCE, STRUCTURAL BLOCKING OR SUPPORT, ELECTRICAL OR MECHANICAL REQUIREMENTS, ETC.). OBTAIN EQUIPMENT SPECIFICATIONS FROM MANUFACTURER(S) TO HELP ENSURE PROPER FIT AND OPERATION. SURVEY FIELD CONDITIONS AND VERIFY FEASIBILITY OF INDICATED WORK, FOR INSTANCE LOCATIONS OF OUTLETS IN RELATION TO STRUCTURAL ELEMENTS. COVER HVAC DUCTS AIRTIGHT DURING CONSTRUCTION All work shall comply with 2016 California Building Code (Building Code), , 2016 California Electrical Code (Electrical Code), 2016 California Mechanical Code (Mechanical Code), 2016 California Plumbing Code (Plumbing Code), 2016 California Energy Code (Energy Code), 2016 California Fire Code (Fire Code), 2016 California Green Code (Green Code). CABRILLO COLLEGE ROOM 356 (REMODEL) 350 BUILDING PROJECT INFORMATION PROJECT DESCRIPTION GENERAL NOTES DIRECTIONS From Hwy 1 S, take Park Ave exit, turn left on Park Ave, turn right on Soquel Dr., site is on the left. From Hwy 1 N, take Park Ave exit, turn right on Park Ave, turn right on Soquel Dr., site is on the left. New Brighton State Beach Park Ave S o quel Dr . C abrillo C ollege Dr. P e ri mete r Rd . C a br i l l o Col lege SITE H W Y 1 N Site Address: 6500 Soquel Drive, Aptos, CA 95003, Building 350 APN: 03726103 Zoning: PF Construction Type: 1 Hour Construction Non - sprinklered CONTACT INFORMATION CLIENT Cabrillo College Contact: Mary Talpas Phone: (831) 477 - 5288 Email: [email protected] ARCHITECT William FIsher Architecture, Inc. Contact: Brian Lawler blawler@modern - architecture.com (650) 392 - 9233 Remodel of existing room 356 and HVAC system upgrade. Reconfigure space within existing shell for new electrical layout and addition of concrete equipment pad at exterior of building for new HVAC equipment. SCOPE OF SERVICES Base Responsibilities : Demolish, remove, replace and configure existing space as shown on plans. DESIGN CRITERIA FURTHER QUESTIONS During bidding process please direct all questions or requests for additional detailing to Cabrillo College Purchasing Department: [email protected] Sheet List A0.0 General Notes and Project Information A2.0 Floor Plans A3.1 Details E01 Electrical Symbols, Notes E10 Electrical Floor Plans - Demo E20 Electrical Power Plan E30 Electrical Lighting Plan E40 Electrical Low Voltage/ Signal Plan E50 Electrical Specifications M0.1 Mechanical Legends, Notes and Schedules M1.1 Mechanical Demolition Floor and Attic Plans M2.1 Mechanical New Work Plan M3.1 Mechanical Details P0.1 Plumbing Legend, Notes, Schedules and Details P1.1 Plumbing Demolition and New Work Plans Revision Schedule Rev. No. Date Room 356 Staging Area Contact Mary Talpas for specific direction on staging and contractor parking areas.

Upload: others

Post on 21-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

Willi

am

Fis

her A

rc

hit

ectu

re, In

c.

603 F

ront

Str

eet,

Santa

Cru

z, C

alif

orn

ia 9

5060

831 2

46-0

117 b

ill@

modern

-arc

hitectu

re.c

om

modern

-arc

hitectu

re.c

om

Licensed

Architect

William Fisher

C−11008

10/31/19RENEWS ON

AINOFIL

AR

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:10/2/2019 11:29:52 AM

Cabrillo College

A0.0

Ca

bri

llo C

olle

ge

Ro

om

35

6, B

uild

ing

350

260

0 S

oq

ue

l A

ve

.A

pto

s,

CA

95

003

Issue Date

Gen

era

l N

ote

s a

nd

Pro

ject

Info

rmatio

n

DON'T SCALE THE DRAWINGS.

STUDY THE CONTRACT DOCUMENTS AND THE FIELD CONDITIONS BEFORE BIDDING OR DOING WORK ON THIS PROJECT. IMMEDIATELY REPORT TO THE ARCHITECT ANY ERRORS, OMISSIONS, OR UNCLEAR DIRECTIONS. THE ARCHITECT WILL EVALUATE THE PROBLEM AND MAKE A WRITTEN INTERPRETATION.

NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DEVIATIONS OR VARIATIONS FROM THE DRAWINGS OR SPECIFICATIONS SHOWN HEREIN.

DIMENSIONS MARKED "CLEAR" SHALL BE MAINTAINED AND SHALL ALLOW FOR THICKNESS OF FINISH MATERIALS.

DIMENSIONS ARE TAKEN FROM FACE OF FINISH (FOF), OR FROM CENTER LINES AS INDICATED.

THE GENERAL CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE PROJECT. THE ARCHITECT MUST BE NOTIFIED IMMEDIATELY OF ANY DEVIATIONS OR VARIATIONS FROM THE DRAWINGS OR SPECIFICATIONS SHOWN HEREIN.

"ALIGN" MEANS TO LOCATE FINISHED FACES IN SAME PLANE.

"APPROVED" MEANS, UNLESS INDICATED OTHERWISE BY THE ARCHITECT, APPROVED IN WRITING BY THE ARCHITECT.

"AS DIRECTED" OR "AS INDICATED" MEANS AS DESCRIBED EITHER VERBALLY OR IN WRITING BY THE ARCHITECT. "AS INDICATED" NORMALLY REFERS TO AN ITEM EXPLAINED IN THE CONTRACT.

"THE CONTRACTOR" REFERS TO THE GENERAL CONTRACTOR, NOT HIS SUBCONTRACTORS.

"PROVIDE" MEANS THAT THE CONTRACTOR SHALL FURNISH AND INSTALL.

"UNLESS NOTED OTHERWISE", "UNO", OR "UNLESS INDICATED OTHERWISE" MEANS THAT THE ITEM DESCRIBED IS TYPICAL AS SHOWN EXCEPT AS WHERE SPECIFICALLY CALLED OUT AS DIFFERENT.

"VERIFY" MEANS, UNLESS INDICATED OTHERWISE BY THE ARCHITECT, TO OBTAIN WRITTEN VERIFICATION OF THE ITEM OR METHOD INDICATED FROM THE ARCHITECT. THIS VERIFICATION MIGHT INCLUDE ELABORATION OR EXPLANATION BY THE ARCHITECT REQUIRING A MORE COMPLEX CONSTRUCTION SOLUTION THAN MIGHT BE ASSUMED BY READING THE DRAWING WITHOUT THE VERIFICATION, THEREFORE PLEASE MAKE VERIFICATIONS AS EARLY AS POSSIBLE BEFORE BIDDING THE WORK. APPROVED SHOP DRAWINGS DO NOT CONSTITUTE VERIFICATION.

ANY ERROR, OMISSION, OR OTHER CONFLICT BETWEEN THESE DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR HIS RESOLUTION AS SOON AS IT IS DISCOVERED.

INFORM THE ARCHITECT IMMEDIATELY IF THE DRAWINGS, SPECIFICATIONS, OR OTHER CONSTRUCTION DOCUMENTS DON'T SEEM TO COMPLY WITH CURRENT APPLICABLE LAWS, CODES, OR REGULATIONS.

U.N.O., APPLY, INSTALL, CONNECT, ERECT, CLEAN, AND CONDITION PRODUCTS PER THEIR MANUFACTURER'S CURRENT WRITTEN INSTRUCTIONS.

VERIFY WITH MANUFACTURERS THEIR EQUIPMENT REQUIREMENTS (FOR INSTANCE, STRUCTURAL BLOCKING OR SUPPORT, ELECTRICAL OR MECHANICAL REQUIREMENTS, ETC.). OBTAIN EQUIPMENT SPECIFICATIONS FROM MANUFACTURER(S) TO HELP ENSURE PROPER FIT AND OPERATION.

SURVEY FIELD CONDITIONS AND VERIFY FEASIBILITY OF INDICATED WORK, FOR INSTANCE LOCATIONS OF OUTLETS IN RELATION TO STRUCTURAL ELEMENTS.

COVER HVAC DUCTS AIRTIGHT DURING CONSTRUCTION

All work shall comply with 2016 California Building Code (Building Code), , 2016 California Electrical Code (Electrical Code), 2016 California Mechanical Code (Mechanical Code), 2016 California Plumbing Code (Plumbing Code), 2016 California Energy Code (Energy Code), 2016 California Fire Code (Fire Code), 2016 California Green Code (Green Code).

CABRILLO COLLEGEROOM 356 (REMODEL)

350 BUILDING

PROJECT INFORMATIONPROJECT DESCRIPTIONGENERAL NOTES

DIRECTIONS

From Hwy 1 S, take Park Ave exit, turn left on Park Ave, turn right on Soquel Dr., site is on the left.

From Hwy 1 N, take Park Ave exit, turn right on Park Ave, turn right on Soquel Dr., site is on the left.

New Brighton State BeachPark

Ave

Soquel Dr.

Cabrillo

Colle

ge D

r.

Perimeter Rd.

Cabrillo College

SITE

HWY 1

N

Site Address: 6500 Soquel Drive, Aptos, CA 95003, Building 350APN: 03726103Zoning: PFConstruction Type: 1 Hour ConstructionNon-sprinklered

CONTACT INFORMATION

CLIENTCabrillo College

Contact:Mary TalpasPhone: (831) 477-5288Email: [email protected]

ARCHITECTWilliam FIsher Architecture, Inc.

Contact:Brian [email protected](650) 392-9233

Remodel of existing room 356 and HVAC system upgrade. Reconfigure space within existing shell for new electrical layout and addition of concrete equipment pad at exterior of building for new HVAC equipment.

SCOPE OF SERVICES

Base Responsibilities: Demolish, remove, replace and configure existing space as shown on plans.

DESIGN CRITERIA

FURTHER QUESTIONS

During bidding process please direct all questions or requests for additional detailing to Cabrillo College Purchasing Department: [email protected]

Sheet List

A0.0 General Notes and Project Information

A2.0 Floor Plans

A3.1 Details

E01 Electrical Symbols, Notes

E10 Electrical Floor Plans - Demo

E20 Electrical Power Plan

E30 Electrical Lighting Plan

E40 Electrical Low Voltage/ Signal Plan

E50 Electrical Specifications

M0.1 Mechanical Legends, Notes and Schedules

M1.1 Mechanical Demolition Floor and Attic Plans

M2.1 Mechanical New Work Plan

M3.1 Mechanical Details

P0.1 Plumbing Legend, Notes, Schedules and Details

P1.1 Plumbing Demolition and New Work Plans

Revision Schedule

Rev. No. Date

Room 356

Staging Area

Contact Mary Talpas for specific direction on staging and contractor parking areas.

Page 2: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

12

11

10

9

8

13

D E H J

47' -

7"

2' -

3"

18' -

1"

8' -

11"

18' -

4"

27' - 9"

8' - 3" 19' - 6"

10

' -

1"

EQ. 10' - 0" EQ.

2x4 Wall furring o/ (E) masonry wall, finish w/ 5/8" gypsum board, painted.

Remove (E) floor finish, replace w/ (N) carpeting

(N) 5/8" gypsum board, painted

(N) Storefront system to match (E) storefront system in same opening.

(E) Concrete walkway deck

(N) Concrete equipment pad below concrete walkway

(N) Chainlink fence enclosure

(N) Mechanical equipment, refer mechanical drawings

A2.010

(N)

Sto

refr

ont

Ele

vation

4

A2.0

1/4

":12"

Slo

pe

(N) Push plate for Horton Automatics Series 4100 LE Swing Door Operators

(N) Outdoor work surface, to be installed over (E) guardrail

7' -

0"

2

12

11

10

9

8

13

D E H J

Remove and replace all (E) gypsum board from wall studs. Replace w/ (N) 5/8" gypsum board, painted

Demolish (E) walls and ceilings of (E) darkroom cubicles

Remove (E) metal lockers, patch and repair (E) walls and floor as needed, typ.

Remove (E) storefront

Remove (E) floor finish, replace w/ (N) carpeting

Demolish all (E) built-in cabinets, dividers, counters, etc.

12

11

10

9

8

13

D E H J

A.F.F.2' x 4' ACT System

10' - 6"

(N) Chain link fence at underside of deck

A2.0

9

A2.0

7

A2.0

6

(N) HVAC equipment, refer mechanical drawings

6' - 7" 2' - 2"

7' - 0" 1' - 9"

13

A2.0

8

(E) Cast concrete deck

1/4":12" Slope(N) Equipment pad

(E) Concrete column beyond

(E) Concrete pier beyond

(E) Concrete pier beyond

(E) Concrete grade beam

5" 8" 5"

1' -

0"

1' - 6"

No. 4 vert @ 16" o.c.

(2) No. 4 vert @ bottom

No. 4 vert @ 16" o.c., alternate bend direction

(E) Column pier, V.I.F., ensure all work for (N) equipment pad will not conflict with (E) columns.

3" clear, typ.

Footing on three sides of pad, step as required

be

low

gra

de

6"

min

.

8"

3" m

in.

1' -

0"

(E) Masonry wall

No. 4 bars @ 16" o.c. e.w. , top & bottom

1/2" asphalt impregnated fiberboard (or equal) expansion joint

(N) Equipment slab

(2) No. 4 bars at bottom

8"

3" clr., typ.

(E) building footing

4" Crushed rock

4"

Compact soil under slab 95%

(N) Chainlink fence

(N) Chainlink horizontal support

+8'-0"

A.F

.F.

Chamfer edges 1", typ.

1' -

0"

min

.

No. 4 vert & horiz @ 16" o.c.

Bend bars 90° at corners, 3" radius

No. 4 bars @ 16" o.c. e.w., top & bottom

Chainlink fence

8"

8"

4" Crushed rock

4"

Compact soil under slab 95%

6' - 0" V.I.F.

8' -

8"

V.I

.F.

(N) Storefront to match (E) Storefront entry into room 356

1' - 6" 3' - 0" 1' - 6"

3' -

6"

3' -

6"

1' -

8"

4

A3.1

5

A3.1

6

A3.1

6"

10

"

± 4"

± 4

"

Chamfer concrete pad edges 1" typ

Chainlink fence vertical support, attach to pad w/ anchored flange, set anchors in epoxy, ensure anchors do not conflict with rebar.

Chainlink fence

Chainlink fence horizontal support, refer specifications

Reinforcing bars, refer pad details

Vertical concrete below, refer pad details

Willi

am

Fis

her A

rc

hit

ectu

re, In

c.

603 F

ront

Str

eet,

Santa

Cru

z, C

alif

orn

ia 9

5060

831 2

46-0

117 b

ill@

modern

-arc

hitectu

re.c

om

modern

-arc

hitectu

re.c

om

Licensed

Architect

William Fisher

C−11008

10/31/19RENEWS ON

AINOFIL

AR

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:10/2/2019 2:42:05 PM

Cabrillo College

A2.0

Ca

bri

llo C

olle

ge

Ro

om

35

6, B

uild

ing

350

260

0 S

oq

ue

l A

ve

.A

pto

s,

CA

95

003

Issue Date

Flo

or

Pla

ns

1/4" = 1'-0"1

Level 1 - Proposed1/8" = 1'-0"

3Demo

Revision Schedule

Rev. No. Date

2 10-2-2019

1/8" = 1'-0"2

Reflected Ceiling Plan

1/4" = 1'-0"4

Equipment Pad Section3/4" = 1'-0"

9Equipment Pad Footing

3/4" = 1'-0"7

Equipment Pad at Building Wall

3/4" = 1'-0"6

Equipment Pad Fence Top

3/4" = 1'-0"8

Equipment Pad Edge

1/4" = 1'-0"10

(N) Storefront Elevation

Refer details 1, 2, 3, & 4 on sheet A3.1 for suspended ceiling bracing and wire connections.

3/4" = 1'-0"5

Equipment Pad Fence Post, typ.

2

Page 3: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

Bracing Assemblies are required at not more than 12 ft. x 12 ft. on center

Exterior Interior

(E) Concrete walkway(E) Concrete floor

(N) Metal Storefront, door and glazing to match (E) Rm. 356 storefront, door and glazing.

ExteriorInterior

(E) Masonry Wall

(N) 2x4 Wall furring, refer plans

(N) Metal storefront, door and glazing to match (E) Rm. 356 storefront, door and glazing.

ExteriorInterior

(N) Entry Door

(N) Metal storefront, door and glazing to match (E) Rm. 356 storefront, door and glazing.

Smooth & level finished surface, confirm material with owner prior to installation.

Wedges every 24" o.c. & 2" from ends, 2 min.

1 1/2"Attach to (E) guard rail w/ flat-head wood screwes every 12" o.c., 3 min. per section

(E) Guardrail

1 1/2"± 1' - 0" V.I.F.

Willi

am

Fis

her A

rc

hit

ectu

re, In

c.

603 F

ront

Str

eet,

Santa

Cru

z, C

alif

orn

ia 9

5060

831 2

46-0

117 b

ill@

modern

-arc

hitectu

re.c

om

modern

-arc

hitectu

re.c

om

Licensed

Architect

William Fisher

C−11008

10/31/19RENEWS ON

AINOFIL

AR

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:10/10/2019 4:44:45 PM

Cabrillo College

A3.1

Ca

bri

llo C

olle

ge

Ro

om

35

6, B

uild

ing

350

260

0 S

oq

ue

l A

ve

.A

pto

s,

CA

95

003

Issue Date

De

tails

Revision Schedule

Rev. No. Date

4 Date 2

N.T.S.1

Suspended Ceiling Bracing AssemblyN.T.S.

2Suspended Ceiling Wire Connection Grid

N.T.S.3

Suspended Ceiling Wire to Wood Framing

3" = 1'-0"4

Storefront Sill3" = 1'-0"

5Storefront Jamb (Head Similar)

3" = 1'-0"6

Storefront Jamb @ Door (Head Similar)

1 1/2" = 1'-0"7

(N) Outdoor Work Surface

4

Page 4: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

E01

Willia

m F

is

he

r A

rc

hite

ctu

re

, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William FisherC-11008

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

Date Printed:

9/10/2019

Cabrillo C

ollege

Room

356, B

uilding 350

2600 S

oquel A

ve.

Aptos, C

A 95003

Issue Date

Revision Schedule

Rev. No. Date

303 P

OT

RE

RO

S

T. S

UIT

E 42-304

SA

NT

A C

RU

Z, C

A 95060

PH

ON

E: (831)430-3605

FA

X: (831)430-9490

PD

G P

RO

JE

CT

N

O.: 19120.00

PR

IM

E D

ES

IG

N G

RO

UP

ELE

CT

RIC

AL S

YM

BO

LS

,

NO

TE

S

AutoCAD SHX Text
300/3
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E) MAIN SWITCHBOARD 'MSB' 2000AMP, 277/480V, 3 , 4W
AutoCAD SHX Text
(E) MTR CNTL CENTER 'MCC'
AutoCAD SHX Text
3P
AutoCAD SHX Text
%%U2000A
AutoCAD SHX Text
%%U(E)
AutoCAD SHX Text
%%UM
AutoCAD SHX Text
(E) METER AND CT COMPARTMENT
AutoCAD SHX Text
LIGHT FIXTURE, CLG. MTD. SUSPENDED
AutoCAD SHX Text
LIGHT FIXTURE, BOLLARD, GROUND MTD.
AutoCAD SHX Text
LIGHT FIXT. FLOOD, LANDSCAPE, GROUND MTD. 2-HEADS
AutoCAD SHX Text
EXHAUST FAN AND LIGHT COMBO UNIT
AutoCAD SHX Text
LIGHT FIXTURE, WALL MOUNTED, SURFACE, W/ PNL CIRC #
AutoCAD SHX Text
FIXTURE TYPE IDENTIFIER TAG - SEE FIXTURE SCHEDULE
AutoCAD SHX Text
j
AutoCAD SHX Text
10
AutoCAD SHX Text
a
AutoCAD SHX Text
10
AutoCAD SHX Text
"k" INDICATES FIXTURES SWITCHED, "3" INDICATES 3-WAY.
AutoCAD SHX Text
SWITCH, SINGLE GANG, +48" FINISH FLOOR TO CENTER
AutoCAD SHX Text
3
AutoCAD SHX Text
k
AutoCAD SHX Text
"j" INDICATES CONTROLLING SWITCH, "10" INDICATES CIRCUIT#.
AutoCAD SHX Text
"a" INDICATES CONTROLLING SWITCH, "10" INDICATES CIRCUIT#.
AutoCAD SHX Text
SWITCH, W/ INTEGRATED TIMER FOR TIMED OPERATION
AutoCAD SHX Text
FL
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
H
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
OCCUPANCY SENSOR: WATTSTOPPER #W-2000H
AutoCAD SHX Text
OCCUPANCY SENSOR: WATTSTOPPER #DT-355-U
AutoCAD SHX Text
OCCUPANCY SENSOR: WATTSTOPPER #W-1000A
AutoCAD SHX Text
OCCUPANCY SENSOR: WATTSTOPPER #W-500A
AutoCAD SHX Text
5
AutoCAD SHX Text
PP
AutoCAD SHX Text
OCCUPANCY SENSOR POWER PACK:-WATTSTOPPER
AutoCAD SHX Text
TO
AutoCAD SHX Text
S
AutoCAD SHX Text
OS
AutoCAD SHX Text
S
AutoCAD SHX Text
EXIT SIGN, WIRED CONSTANT HOT, WITH BATTERY BACK-UP. SHADED QUADRANT INDICATES FACING DIRECTION. ARROW ON FACE IF NOTED. COMBINATION EXIT SIGN AND EGRESS LIGHT IF NOTED ON FIXTURE SCHEDULE.
AutoCAD SHX Text
OS1
AutoCAD SHX Text
S
AutoCAD SHX Text
OCCUPANCY SENSOR SWITCH: WALL MOUNTED PIR DUAL RELAY: WATTSTOPPER #WI-300A
AutoCAD SHX Text
OCCUPANCY SENSOR SWITCH: WALL MOUNTED PIR SINGLE RELAY WATTSTOPPER #WI-200
AutoCAD SHX Text
NEW 2X2 LAY-IN OR SURFACE LIGHT FIXTURE. SEE FIXTURE SCHEDULE.
AutoCAD SHX Text
SYMBOL LEGEND-LIGHTING-COMMERCIAL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
SWITCH, SINGLE GANG, +48" FINISH FLOOR TO CENTER
AutoCAD SHX Text
CAN LIGHT FIXTURE, CEILING MOUNTED, RECESSED
AutoCAD SHX Text
LIGHT FIXTURE, WALL MOUNTED, SCONCE
AutoCAD SHX Text
EMERGENCY FLOOD LIGHT, WIRED CONSTANT HOT
AutoCAD SHX Text
NEW 2X4 LED LAY-IN LIGHT FIXTURE. SEE FIXTURE SCHEDULE.
AutoCAD SHX Text
W/ BATTERY BACK-UP
AutoCAD SHX Text
NEW SURFACE STRIP LIGHT FIXTURE. SEE FIXTURE SCHEDULE.
AutoCAD SHX Text
S
AutoCAD SHX Text
TS
AutoCAD SHX Text
7-DAY ASTRONOMIC TIME SWITCH WITH MINIMUM 2 INDEPENDENT CHANNELS. PROVIDE MORE CHANNELS IF DIRECTED BY CONTROL DIAGRAM.
AutoCAD SHX Text
DIMMER SWITCH. CONTRACTOR SHALL CONFIRM COMPATIBILITY WITH LIGHTS CONTROLLED FOR PROPER OPERATION IN COMPLIANCE WITH TITLE 24 TABLE 130.1-A
AutoCAD SHX Text
EXTERIOR POLE MOUNTED PARKING/AREA LIGHT.
AutoCAD SHX Text
#
AutoCAD SHX Text
FINISH FLOOR
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CL OF HANDLE
AutoCAD SHX Text
CONDUIT STUB OUT
AutoCAD SHX Text
J
AutoCAD SHX Text
#
AutoCAD SHX Text
POWER POLE FOR CONNECTION TO MOD. FURN.
AutoCAD SHX Text
SHEET NOTE TAG
AutoCAD SHX Text
CONDUIT STUB UP
AutoCAD SHX Text
MOTOR RATED DISCONNECT SIZED TO EQUIPMENT NAMEPLATE
AutoCAD SHX Text
JUNCTION BOX, W/ 3/4" EMT STUBBED UP TO HEIGHT AS
AutoCAD SHX Text
DIRECTED BY CLIENT
AutoCAD SHX Text
ELECTRICAL PANEL
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
SYMBOL LEGEND-POWER
AutoCAD SHX Text
PNL-CKT
AutoCAD SHX Text
CIRCUIT OR HOMERUN WITH 2#12 HOT LEGS, 1#12 NEUTRAL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
OR SWITCH
AutoCAD SHX Text
DATA BOX
AutoCAD SHX Text
CONVENIENCE
AutoCAD SHX Text
VISUAL ALARM DEVICE
AutoCAD SHX Text
80" A.F.F. OR 6" BELOW CLG.
AutoCAD SHX Text
WHICHEVER ONE IS LOWER.
AutoCAD SHX Text
15" MIN.
AutoCAD SHX Text
44"
AutoCAD SHX Text
80"
AutoCAD SHX Text
6"
AutoCAD SHX Text
TELEPHONE AND/OR
AutoCAD SHX Text
RECEPTACLE BOX
AutoCAD SHX Text
CONTROL DEVICE
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
B
AutoCAD SHX Text
HOME RUN TO PANEL WITH 1 HOT LEG, 1 NEUTRAL + 1GND
AutoCAD SHX Text
ALL #12 CU U.O.N.
AutoCAD SHX Text
CIRCUIT OR HOMERUN WITH 3#12HOT LEGS, 1#10 NEUTRAL
AutoCAD SHX Text
AND 1#12 GND U.O.N.
AutoCAD SHX Text
C
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
B
AutoCAD SHX Text
VERIFY COLOR BEFORE ORDERING DEVICES
AutoCAD SHX Text
MOTOR RATED DISCONNECT, WEATHERPROOF, SIZED TO EQUIPMENT
AutoCAD SHX Text
NAME PLATE RATING. F INDICATES DUAL ELEMENT FUSE PER PHASE.
AutoCAD SHX Text
F
AutoCAD SHX Text
AND 1#12 GND U.O.N.
AutoCAD SHX Text
RATING. F INDICATES DUAL ELEMENT FUSE PER PHASE.
AutoCAD SHX Text
F
AutoCAD SHX Text
WP
AutoCAD SHX Text
G
AutoCAD SHX Text
120V, 15A NEMA 5-15R DUPLEX SPEC GRADE RECEPTACLE LEVITON: 5252 OR EQUAL. 'G' INDICATES GFCI PROTECTED. 'WP' INDICATES GFCI PROTECTED AND WP, GASKETTED COVER. WP WHILE IN USE COVER FOR ANY OUTLET EXPOSED TO DIRECT WATER CONTACT.
AutoCAD SHX Text
(2) 120V, 15A NEMA 5-15R DUPLEX SPEC GRADE RECEPTACLES MOUNTED SIDE-BY-SIDE IN 4 SQUARE BOX. "QUAD RECEPT" LEVITON: 5252 OR EQUAL.
AutoCAD SHX Text
120V, 20A NEMA 5-20R DUPLEX INDUSTRIAL GRADE RECEPTACLE LEVITON: 5352 OR EQUAL
AutoCAD SHX Text
(2) 120V, 20A NEMA 5-20R DUPLEX SPEC GRADE RECEPTACLES MOUNTED SIDE-BY-SIDE IN 4 SQUARE BOX. "QUAD RECEPT" LEVITON: 5352 OR EQUAL
AutoCAD SHX Text
HALF SWITCHED NEMA 5-15R DUPLEX SPEC GRADE RECEPTACLE LEVITON: 5252 OR EQUAL W/ TAB SPLIT.
AutoCAD SHX Text
SPECIAL OUTLET PLUG, REFER TO SHEET NOTES FOR SPEC.
AutoCAD SHX Text
48" MAX.
AutoCAD SHX Text
RECEPTACLE BOX
AutoCAD SHX Text
44" MAX.
AutoCAD SHX Text
48" MAX. TO
AutoCAD SHX Text
TOP OF BOX
AutoCAD SHX Text
SWITCH OR
AutoCAD SHX Text
%%UABBREVIATIONS
AutoCAD SHX Text
CO
AutoCAD SHX Text
WP
AutoCAD SHX Text
UON
AutoCAD SHX Text
NTS
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(N)
AutoCAD SHX Text
EL
AutoCAD SHX Text
NL
AutoCAD SHX Text
AC
AutoCAD SHX Text
UC
AutoCAD SHX Text
MOUNTED ABOVE COUNTER @ 44" TO CENTER. COORDINATE MOUNTING HEIGHT, DEPTH AND ORIENTATION WITH COUNTER MANUFACTURER, ARCHITECT AND CUSTOMERS REP.
AutoCAD SHX Text
CONDUIT ONLY WITH YELLOW POLYPROPELENE PULL ROPE FULL LENGTH OF RACEWAY AND ANCHORED AT EACH END
AutoCAD SHX Text
EXTERIOR LIGHT - ON AT DUSK, OFF AT SET TIME
AutoCAD SHX Text
EXISTING EQUIPMENT
AutoCAD SHX Text
NEW EQUIPMENT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NIGHT LIGHT - ON AND OFF WITH PHOTO-CELL/SENSOR
AutoCAD SHX Text
MOUNTED BELOW COUNTER AT STANDARD HEIGHT
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
EQUIPMENT OF WEATHERPROOF CONSTRUCTION
AutoCAD SHX Text
NIC
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text
G
AutoCAD SHX Text
GFCI PROTECTED IF SHOWN BY RECEPTACLE
AutoCAD SHX Text
CU
AutoCAD SHX Text
COPPER CONDUCTOR OR BUS
AutoCAD SHX Text
IG
AutoCAD SHX Text
ISOLATED GROUND CONDUCTOR OR BUS
AutoCAD SHX Text
TYP
AutoCAD SHX Text
TYPICAL FOR ALL OCCURRENCES OF SAME SYMBOL/NOTE
AutoCAD SHX Text
(R)
AutoCAD SHX Text
EXISTING EQUIPMENT TO BE REMOVED
AutoCAD SHX Text
AL
AutoCAD SHX Text
ALUMINUM CONDUCTOR OR BUS
AutoCAD SHX Text
SYMBOL LEGEND-COMMUNICATIONS AND F/A
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
COMBINATION PHONE AND DATA OUTLET
AutoCAD SHX Text
DUAL DATA OUTLET W/ 2 CAT6 CABLES TO LOCAL MEDIA CAB.
AutoCAD SHX Text
COMBINATION OUTLET, FLOOR MTD.
AutoCAD SHX Text
MEDIA
AutoCAD SHX Text
TENANT TELEPHONE AND CABLE TV MEDIA SUB PANEL
AutoCAD SHX Text
COMBINATION SMOKE AND CARBON MONOXIDE DETECTOR AND ALARM. 120VAC POWERED WITH 12VDC BATTERY BACK UP.
AutoCAD SHX Text
SMOKE DETECTOR AND ALARM. 120VAC POWERED WITH 12VDC BATTERY BACK UP.
AutoCAD SHX Text
DAYLIGHTING SENSOR FOR LOCAL ROOM MULTI-LEVEL CONTROL. REFER
AutoCAD SHX Text
DLS
AutoCAD SHX Text
TITLE 24 CEnC SECTIONS 130.1(d) AND TABLE 130.1-A FOR MORE INFO.
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E) UNDERGROUND FEEDERS: (1) 3" PVC FOR POWER AND (1) 3.5 PVC FOR SIGNAL
AutoCAD SHX Text
(E) FLUSH IN-GRADE PULL BOX # PB81
AutoCAD SHX Text
(E) UNDERGROUND FEEDERS: (1) 3" PVC FOR POWER AND (1) 3.5 PVC FOR SIGNAL
AutoCAD SHX Text
175/3
AutoCAD SHX Text
(E) PANEL 'L1' 400AMP, 277/480V, 3 , 4W
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
300A/3P
AutoCAD SHX Text
100/3
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E) TRANSFORMER TRANSFORMER 'T1' 112.5KVA
AutoCAD SHX Text
1/0 GEC
AutoCAD SHX Text
5/8"X10' GRND RD
AutoCAD SHX Text
(E) DISTR. PANEL 'DP' 300A, 120/208V, 3ph
AutoCAD SHX Text
(E)
AutoCAD SHX Text
100/3
AutoCAD SHX Text
(E)
AutoCAD SHX Text
150/3
AutoCAD SHX Text
100/3
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E) PANEL 'R1'
AutoCAD SHX Text
(E) PANEL 'DR1'
AutoCAD SHX Text
(E) PANEL 'DR2'
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
1
AutoCAD SHX Text
E01
AutoCAD SHX Text
NONE
AutoCAD SHX Text
SINGLE LINE DIAGRAM
AutoCAD SHX Text
50/3
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E) PANEL 'R2'
AutoCAD SHX Text
CEILING MOUNTED SPEAKER
AutoCAD SHX Text
CEILING MOUNTED DROP DOWN MICROPHONE
AutoCAD SHX Text
WAP
AutoCAD SHX Text
WIRELESS ACCESS POINT W/ 1 CAT6 CABLE TO LOCAL MEDIA CAB.
AutoCAD SHX Text
PANEL DR2 NOTES
AutoCAD SHX Text
1. EXISTING CIRCUIT BREAKER TO REMAIN. DISCONNECT EXISTING CONDUCTORS AND REMOVE. CONNECT NEW CIRCUIT CONDUCTORS. EXISTING CIRCUIT BREAKER TO REMAIN. DISCONNECT EXISTING CONDUCTORS AND REMOVE. CONNECT NEW CIRCUIT CONDUCTORS. 2. EXISTING CIRCUIT BREAKER TO REMAIN. DISCONNECT EXISTING CONDUCTORS AND REMOVE. EXISTING CIRCUIT BREAKER TO REMAIN. DISCONNECT EXISTING CONDUCTORS AND REMOVE. 3. EXISTING CIRCUIT BREAKER TO REMAIN. EXISTING CIRCUIT BREAKER TO REMAIN. 4. EXISTING CIRCUIT BREAKER AND CONDUCTORS TO REMAIN. EXISTING CIRCUIT BREAKER AND CONDUCTORS TO REMAIN. 5. REMOVE EXISTING CIRCUIT BREAKER(S) AND CONDUCTORS. INSTALL NEW BREAKER SHOWN AND CONNECT NEW CONDUCTORS.REMOVE EXISTING CIRCUIT BREAKER(S) AND CONDUCTORS. INSTALL NEW BREAKER SHOWN AND CONNECT NEW CONDUCTORS.
AutoCAD SHX Text
D
AutoCAD SHX Text
S
AutoCAD SHX Text
CD
AutoCAD SHX Text
FIRE ALARM HORN/STROBE CANDELA AS INDICATED ON PLANS
Page 5: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

364365

356E

356D

356C

356B

356A

356

361

366

357

360

359

358

354

363 M

362W

12

11

10

9

8

PROJECT

N

WE

S

E10

Willia

m F

is

he

r A

rc

hite

ctu

re

, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William FisherC-11008

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

Date Printed:

9/10/2019

Cabrillo C

ollege

Room

356, B

uilding 350

2600 S

oquel A

ve.

Aptos, C

A 95003

Issue Date

Revision Schedule

Rev. No. Date

303 P

OT

RE

RO

S

T. S

UIT

E 42-304

SA

NT

A C

RU

Z, C

A 95060

PH

ON

E: (831)430-3605

FA

X: (831)430-9490

PD

G P

RO

JE

CT

N

O.: 19120.00

PR

IM

E D

ES

IG

N G

RO

UP

ELE

CT

RIC

AL F

LO

OR

PLA

NS

- D

EM

O

AutoCAD SHX Text
EXISTING PANEL 'DR1'
AutoCAD SHX Text
EXISTING PANEL 'DR2'
AutoCAD SHX Text
EXISTING PANEL 'R1'
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
4
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
3
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
1
AutoCAD SHX Text
E10
AutoCAD SHX Text
1/4"=1'-0"
AutoCAD SHX Text
EXISTING/DEMOLITION PLAN
AutoCAD SHX Text
KEYED SHEET NOTES
AutoCAD SHX Text
EXISTING PANEL TO REMAIN AS IS
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
EXISTING PANEL. "DR2". CONTRACTOR SHALL DISCONNECT CIRCUIT CONDUCTORS FROM ALL CIRCUIT BREAKERS SERVING ELECT. EQUIPMENT BEING REMOVED. SEE NEW ELECT. PLAN AND PANEL SCHEDULES FOR NEW CIRCUIT REQUIREMENTS.
AutoCAD SHX Text
CONTRACTOR SHALL REMOVE ALL POWER, LIGHTING AND LOW VOLTAGE EQUIPMENT AS ASSOCIATED CONTROL DEVICES, EXPOSED RACEWAYS AND CONDUCTORS BACK TO SOURCE.
AutoCAD SHX Text
4
AutoCAD SHX Text
TYPICAL EXISTING WALL TO BE REMOVED.
Page 6: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

12

11

10

9

8

13

D E H J

Mechanical Equipment Pad on

Lower level

PROJECT

N

WE

S

E20

Willia

m F

is

he

r A

rc

hite

ctu

re

, In

c.

603 F

ront S

treet, S

anta C

ruz, C

alifornia 95060

831 246-0117 bill@

modern-architecture.com

modern-architecture.com

LicensedArchitect

William FisherC-11008

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

Date Printed:

9/10/2019

Cabrillo C

ollege

Room

356, B

uilding 350

2600 S

oquel A

ve.

Aptos, C

A 95003

Issue Date

Revision Schedule

Rev. No. Date

303 P

OT

RE

RO

S

T. S

UIT

E 42-304

SA

NT

A C

RU

Z, C

A 95060

PH

ON

E: (831)430-3605

FA

X: (831)430-9490

PD

G P

RO

JE

CT

N

O.: 19120.00

PR

IM

E D

ES

IG

N G

RO

UP

ELE

CT

RIC

AL P

OW

ER

P

LA

N

AutoCAD SHX Text
EXISTING PANEL 'DR2'
AutoCAD SHX Text
DR2-CKT
AutoCAD SHX Text
IU
AutoCAD SHX Text
201
AutoCAD SHX Text
DR2-8,10
AutoCAD SHX Text
+60"
AutoCAD SHX Text
+60"
AutoCAD SHX Text
+60"
AutoCAD SHX Text
OU
AutoCAD SHX Text
201
AutoCAD SHX Text
F
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
DR2-2,4,6
AutoCAD SHX Text
#8
AutoCAD SHX Text
5
AutoCAD SHX Text
DR2-13
AutoCAD SHX Text
DR2-3
AutoCAD SHX Text
DR2-5
AutoCAD SHX Text
DR2-3
AutoCAD SHX Text
DR2-3
AutoCAD SHX Text
5
AutoCAD SHX Text
DR2-15
AutoCAD SHX Text
DR2-5
AutoCAD SHX Text
DR2-1
AutoCAD SHX Text
DR2-1
AutoCAD SHX Text
DR2-11
AutoCAD SHX Text
5
AutoCAD SHX Text
2
AutoCAD SHX Text
#10
AutoCAD SHX Text
DR2-1
AutoCAD SHX Text
DR2-1
AutoCAD SHX Text
+60"
AutoCAD SHX Text
DR2-7
AutoCAD SHX Text
DR2-9
AutoCAD SHX Text
4
AutoCAD SHX Text
3
AutoCAD SHX Text
6
AutoCAD SHX Text
CLG.
AutoCAD SHX Text
7
AutoCAD SHX Text
DR2-14
AutoCAD SHX Text
8
AutoCAD SHX Text
J
AutoCAD SHX Text
J
AutoCAD SHX Text
DR2-16
AutoCAD SHX Text
9
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
1
AutoCAD SHX Text
E20
AutoCAD SHX Text
1/4"-1'-0"
AutoCAD SHX Text
ELECTRICAL POWER PLAN
AutoCAD SHX Text
GENERAL SHEET NOTES
AutoCAD SHX Text
VERIFY ALL EQUIPMENT LOCATIONS AND HEIGHTS WITH CABRILLO COLLEGE.
AutoCAD SHX Text
KEYED SHEET NOTES
AutoCAD SHX Text
NEW OUTDOOR HVAC UNIT "OU-1": 35 MCA, 208V, 3ɸ.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
6
AutoCAD SHX Text
FOR CONNECTION OF MEDIA CART.
AutoCAD SHX Text
FOR CONNECTION OF PROJECTION SCREEN.
AutoCAD SHX Text
FOR CONNECTION OF LED TV.
AutoCAD SHX Text
SEE PANEL SCHEDULE FOR REQUIREMENTS.
AutoCAD SHX Text
NEW INDOOR HVAC UNIT "IU-1": 4.29 MCA, 208V, 3ɸ.
AutoCAD SHX Text
7
AutoCAD SHX Text
FLUSH CEILING RECEPTACLE FOR WIRELESS ACCESS POINT POWER
AutoCAD SHX Text
8
AutoCAD SHX Text
RECEPTACLE AT +7'-0" FOR CONNECTION OF SECURITY ALARM PANEL TRANSFORMER. SECURITY ALARM SYSTEM COMPONENTS AND INSTALLATION TO BE INCLUDED IN GENERAL CONTRACTOR'S BID.
AutoCAD SHX Text
9
AutoCAD SHX Text
FLUSH J-BOXES WITH 120V CIRCUIT CONDUCTORS IN CONCEALED 3/4" CONDUIT AND CONNECTIONS TO DOOR ACTUATOR, INDOOR ADA PUSHBUTTON AND EXTERIOR ADA PUSHBUTTON. VERIFY EXACT REQUIREMENTS AND LOCATIONS WITH ARCHITECT AND EQUIPMENT MANUHACTURER.
Page 7: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

12

11

10

9

8

13

D E H J

PROJECT

N

WE

S

E40

Willia

m F

is

he

r A

rc

hite

ctu

re

, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William FisherC-11008

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

Date Printed:

9/10/2019

Cabrillo C

ollege

Room

356, B

uilding 350

2600 S

oquel A

ve.

Aptos, C

A 95003

Issue Date

Revision Schedule

Rev. No. Date

303 P

OT

RE

RO

S

T. S

UIT

E 42-304

SA

NT

A C

RU

Z, C

A 95060

PH

ON

E: (831)430-3605

FA

X: (831)430-9490

PD

G P

RO

JE

CT

N

O.: 19120.00

PR

IM

E D

ES

IG

N G

RO

UP

ELE

CT

RIC

AL LO

W

VO

TLA

GE

/ S

IG

NA

L P

LA

N

ELEC.

UP

ROOM

MECH.

ROOM

PROJECT

N

WE

S

AutoCAD SHX Text
EXISTING PANEL 'DR2'
AutoCAD SHX Text
CLG.
AutoCAD SHX Text
CLG.
AutoCAD SHX Text
CLG.
AutoCAD SHX Text
CLG.
AutoCAD SHX Text
WAP
AutoCAD SHX Text
1
AutoCAD SHX Text
+60"
AutoCAD SHX Text
+60"
AutoCAD SHX Text
+60"
AutoCAD SHX Text
+60"
AutoCAD SHX Text
30CD
AutoCAD SHX Text
30CD
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
1
AutoCAD SHX Text
E40
AutoCAD SHX Text
1/4"-1'-0"
AutoCAD SHX Text
ELECTRICAL LOW VOLTAGE SIGNAL PLAN
AutoCAD SHX Text
GENERAL SHEET NOTES
AutoCAD SHX Text
SEE SHEET E01 FOR SYMBOL LEGEND. VERIFY ALL LOCATIONS AND REQUIREMENTS WITH CABRILLO COLLEGE.
AutoCAD SHX Text
KEYED SHEET NOTES
AutoCAD SHX Text
CEILING PROJECTOR. PROVIDE POWER AND MEDIA CABLE TO SOURCE AS DIRECTED.
AutoCAD SHX Text
1
AutoCAD SHX Text
(E) FIRE ALARM PANEL NOTIFIER NFS-320
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
2
AutoCAD SHX Text
E40
AutoCAD SHX Text
1/4"-1'-0"
AutoCAD SHX Text
FIRE ALARM PANEL LOCATION PLAN LOWER LEVEL
AutoCAD SHX Text
EXISTING (2) 12V 7Ah BATTERIES
AutoCAD SHX Text
EXISTING FACP-8 NOTIFIER NSF-320
AutoCAD SHX Text
NAC-109
AutoCAD SHX Text
(E) DEDICATED 120V, 20A CIRCUIT WITH RED MARKINGS LABELED "FIRE ALARM CONTROL CIRCUIT"
AutoCAD SHX Text
NAC-110
AutoCAD SHX Text
(E) SPARE
AutoCAD SHX Text
EOL
AutoCAD SHX Text
EOL
AutoCAD SHX Text
TO EXISTING NOTIFICATION DEVICES TO REMAIN
AutoCAD SHX Text
TO EXISTING NOTIFICATION DEVICES TO REMAIN
AutoCAD SHX Text
TO EXISTING INITIATION DEVICES TO REMAIN
AutoCAD SHX Text
30CD
AutoCAD SHX Text
30CD
AutoCAD SHX Text
NEW DEVICES AND WIRING
AutoCAD SHX Text
(E) SPARE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
3
AutoCAD SHX Text
E40
AutoCAD SHX Text
1/4"-1'-0"
AutoCAD SHX Text
FIRE ALARM RISER DIAGRAM
Page 8: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

E50

Willia

m F

is

he

r A

rc

hite

ctu

re

, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William FisherC-11008

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

Date Printed:

9/10/2019

Cabrillo C

ollege

Room

356, B

uilding 350

2600 S

oquel A

ve.

Aptos, C

A 95003

Issue Date

Revision Schedule

Rev. No. Date

303 P

OT

RE

RO

S

T. S

UIT

E 42-304

SA

NT

A C

RU

Z, C

A 95060

PH

ON

E: (831)430-3605

FA

X: (831)430-9490

PD

G P

RO

JE

CT

N

O.: 19120.00

PR

IM

E D

ES

IG

N G

RO

UP

ELE

CT

RIC

AL

SP

EC

IF

IC

AT

IO

NS

Page 9: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

William

F

ish

er A

rch

itectu

re, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William Fisher

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:

7/19/2019 1:28:28 PM

Cabrillo College

Ca

brillo

C

olle

ge

Ro

om

3

56

, B

uild

in

g 3

50

26

00

S

oq

ue

l A

ve

.

Ap

to

s, C

A 9

50

03

Issue Date

Revision Schedule

Rev. No. Date

9699 Blue Larkspur Lane, Suite 203 Monterey, CA 93940Telephone (831) 373-4390 / Facsimile (831) 373-6522www.listengineering.com © LEC 2019Job No. 19023.00

List EngineeringMechanical Consultants

S

R

R

I

S

T

E

G

E

E

No. 23440

L

I

T

A

T

F

O

E

CA

A N

H

M

C

E

E

R

A

I

N

R

F

O

I

L

A

C

L

A

F

ES

O

D

E

P

R

M

N

O

R

N

I

G

E

N

S

I

O

A

N

L

L

E

U

B

EXP. 12-31-20

D

M0.1

ME

CH

AN

IC

AL

L

EG

EN

D,

NO

TE

S A

ND

SC

HE

DU

LE

S

GENERAL MECHANICAL NOTES

TRANSFER AIR

TURNING VANES

THERMOSTAT at + 48"

TO BE REMOVED

VOLUME DAMPER

T

SPIN-IN EXTRACTOR/DAMPER

EXTENT OF DEMOLITION

POINT OF CONNECTION

SUPPLY OR OUTSIDE AIR

SPEED CONTROL SWITCH

P/T PLUG

RETURN OR EXHAUST AIR

FIRE/SMOKE DAMPER

DIAMETER

CONDENSATE DRAIN

CENTER LINE

BYPASS TIMER

Ø

CD

BT

L

C

FIRE DAMPER

PENE PENETRATION

SAD SUPPLY AIR DUCT

VIF VERIFY IN FIELD

W/O WITH OUT

WT WEIGHT

WC WATER COLUMN

W/ WITH

VD VOLUME DAMPER

V VOLT

UON UNLESS OTHERWISE NOTED

UCD UNDERCUT DOOR

TYP TYPICAL

TV TURNING VANES

STD STANDARD

SS STAINLESS STEEL

SP STATIC PRESSURE

SD SUPPLY DIFFUSER

SA SUPPLY AIR

RPM REVOLUTIONS PER MINUTE

(RL) RELOCATE

RAD RETURN AIR DUCT

RA RETURN AIR

P/T PRESSURE / TEMPERATURE

PSI POUNDS PER SQUARE INCH

PRV PRESSURE REDUCING VALVE

P/N PART NUMBER

PH PHASE

PD PRESSURE DROP

PC PLUMBING CONTRACTOR

OSA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

NTS NOT TO SCALE

NIC NOT IN CONTRACT

(N) NEW

MC MECHANICAL CONTRACTOR

MBH 1,000 BTU/HR

LWT LEAVING WATER TEMPERATURE

LBS POUNDS

KW KILOWATTS

HP HORSE POWER

GPM GALLONS PER MINUTE

GC GENERAL CONTRACTOR

FTR FLUE THRU ROOF

FT.HD. FEET HEAD

FSD FIRE SMOKE DAMPER

FLA FULL LOAD AMPS

FD FIRE DAMPER

FC FLEXIBLE CONNECTION

°F DEGREES FAHRENHEIT

EWB ENTERING WET BULB

EDBENTERING DRY BULB

EC ELECTRICAL CONTRACTOR

EAD EXHAUST AIR DUCT

(E) EXISTING

AD ACCESS DOOR

AFF ABOVE FINISH FLOOR

BD BALANCING DAMPER

AP ACCESS PANEL

AL ACOUSTICALLY LINED

BHP BRAKE HORSE POWER

BTU BRITISH THERMAL UNIT

BDD BACKDRAFT DAMPER

BJ BETWEEN JOIST

C. CONDUIT

CFM CUBIC FEET PER MINUTE

CD CONDENSATE DRAIN

CA COMBUSTION AIR

DL DOOR LOUVER

X

X

XX

X

X

XX

X

X

XX

X X X

SYMBOLS & ABBREVIATIONS (MECHANICAL)

EXHAUST DUCT

UP, DOWN, PENE & DEMO

RETURN DUCT

UP, DOWN, PENE & DEMO

SUPPLY DUCT

UP, DOWN, PENE & DEMO

EXHAUST, RETURN, SUPPLY

AIR DUCT (EXISTING)

EXHAUST, RETURN, SUPPLY

AIR DUCT (NEW)

DEMO DEMOLITION

POC POINT OF CONNECTION

EWT ENTERING WATER TEMPERATURE

EODEXTENT OF DEMOLITION

ETREXISTING TO REMAIN

CONTROL SWITCH

S

DRAWING INDEX

DWG #

M0.1

M0.2

M1.1

M2.1

M3.1

DRAWING DESCRIPTION

MECHANICAL LEGEND, NOTES AND SCHEDULES

TITLE 24 ENERGY DOCUMENTATION

MECHANICAL DEMOLITION FLOOR AND ATTIC PLANS

MECHANICAL NEW WORK PLAN

MECHANICAL DETAILS

1. ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE 2016 CALIFORNIA

MECHANICAL CODE, CALIFORNIA PLUMBING CODE, CALIFORNIA BUILDING CODE, NATIONAL FIRE

PROTECTION CODES, AND ALL OTHER APPLICABLE CODES AND REGULATIONS, INCLUDING THE 2016

CALIFORNIA ENERGY CONSERVATION STANDARDS OF TITLE 24.

2. LOCATIONS OF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES ARE DETAILED ON THE

ARCHITECTURAL REFLECTED CEILING PLAN AND ROOM ELEVATIONS.

3. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT

MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS, TRANSITIONS, DAMPERS, VALVES,

AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.

4. ALL DUCTWORK SHALL BE CONSTRUCTED, ERECTED, AND TESTED IN ACCORDANCE WITH THE

APPLICABLE SMACNA STANDARDS.

5. DUCTWORK SHALL BE INSULATED WITH 2” FIBERGLASS INSULATION AND ALL SERVICE JACKET.

PROVIDE 1” ACOUSTICAL LINER WHERE SHOWN ON PLANS. DUCT DIMENSIONS ON PLANS ARE NET

CLEAR INTERIOR.

6. MANUAL DAMPERS SHALL BE PROVIDED IN ALL DUCT BRANCHES TO INDIVIDUAL DIFFUSERS, GRILLES

AND REGISTERS.

7. ALL EQUIPMENT, DUCTS, PIPING, AND OTHER DEVICES AND MATERIALS INSTALLED OUTSIDE THE

BUILDING OR OTHERWISE EXPOSED TO THE WEATHER SHALL BE COMPLETELY WEATHERPROOFED.

8. PIPES AND DUCTWORK SHALL BE SUPPORTED AND BRACED PER SMACNA “GUIDELINES FOR SEISMIC

RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING PIPING SYSTEMS.”

9. EXPOSED PIPING ALLOWED ONLY WHERE INDICATED. PROVIDE ESCUTCHEONS IN FINISHED AREAS.

10. PROVIDE ROUGH-IN AND FINAL CONNECTIONS FOR EQUIPMENT PROVIDED UNDER OTHER DIVISIONS

OF THE SPECIFICATIONS. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF EQUIPMENT.

11. PENETRATIONS OF RATED ASSEMBLIES SHALL BE FIRE STOPPED BY AN APPROVED MATERIAL AS

PRESCRIBED IN CBC SECTION 714.

12. REFER TO STRUCTURAL DRAWING FOR LOCATIONS OF BEAMS, SHEAR WALLS AND MEMBERS. ALL

DRILLING OF STRUCTURAL BEAMS AND MEMBERS TO BE COORDINATED WITH THE STRUCTURAL

ENGINEER. ALL HOLES SHALL BE MINIMUM SIZE AND APPROVED BY STRUCTURAL ENGINEER PRIOR

TO DRILLING.

13. STRUCTURAL STEEL SHALL CONFORM TO ASTM A-36. BOLTS SHALL CONFORM TO ASTM A-307.

FABRICATION, ERECTION, WELDING AND PAINTING SHALL BE IN ACCORDANCE WITH THE LATEST

EDITION OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION SPECIFICATIONS. ALL STEEL

EXPOSED TO WEATHER SHALL BE GALVANIZED.

14. DUCTWORK VISIBLE THROUGH DIFFUSERS AND REGISTERS SHALL BE PAINTED FLAT BLACK.

15 INSULATION MATERIAL SHALL MEET THE STATE QUALITY STANDARD PER SECTION 120.4 OF THE 2016

CALIFORNIA ENERGY CODE (CEC).

16. ALL PIPING AND DUCTWORK SHALL BE INSULATED CONSISTENT WITH THE REQUIREMENTS OF 2016

CEC SECTION 120.3 AND TABLE 120.3-A.

17. ALL HVAC SYSTEMS SHALL MEET THE CONTROL REQUIREMENTS PER SECTIONS 112 AND 122 CEC.

18. ALL HVAC EQUIPMENT AND APPLIANCES SHALL MEET THE REQUIREMENTS OF SECTIONS 111-113, 115,

AND 120-129 CEC.

OUTDOOR UNIT (CONDENSER) VRF HEAT PUMP SCHEDULE

CODE

OU-201

NOTES:

1. DISCONNECT, SERVICE VALVES, FACTORY CONTROLS, INSULATED REFER PIPING

DESCRIPTION

VRF CONDENSER HEAT PUMP

LOCATION

ROOM 356

NOMINAL CAPACITY

TONS

5

CAPAICY (BTUH)

COOLING

60,000

HEATING

66,000

EFFICIENCY

SEER

16.5

COP

3.70

MCA

35

MOCP

40

ELECT

V/PH

208/3

CONTROL

THERMOSTAT

WEIGHT

(LBS)

325

HEIGHT

(IN)

52

PART

NO.

PUMY-P60NKMU-BS

MFG

MITSUBISHI

REMARKS

1

HANGERS AND PIPING SUPPORTS

SIZE OF PIPE (INCH)

COPPER TUBE & PIPE

1-1/2" & SMALLER

2" AND LARGER

SPACING OF SUPPORTS (FEET)

HORIZONTAL

6'

10'

VERTICAL

EACH FLOOR, NOT TO

EXCEED 10'

PIPE SIZE

1/2" TO 4"

2013 CALIFORNIA PLUMBING CODE TABLES 313.6

TYPE OF JOINT

SOLDERED OR

BRAZED

THREADED HANGER ROD SIZE

3/8"

INSTALL LISTED PIPE HANGER SUPPORT

COMPONENTS PER MFR. RECOMMENDATIONS. VERIFY

ALL ATTACHMENT TO STRUCTURE WITH STRUCTURAL

ENGINEER PRIOR TO INSTALLATION. PIPE HANGERS

AND SUPPORTS, MATERIALS, DESIGN AND

MANUFACTURE SHALL CONFORM TO ANSI/MSS SP-58.

CLEVIS HANGER

JOIST HANGER

THREADED

HANGER ROD

FOR SIZE

SEE TABLE

LAG BOLT

EXPANSION BOLT

CLEVIS

THREADED

HANGER

ROD TO

STRUCTURE

PROVIDE PIPE SLEEVE

ESCUTCHEON AT ALL

PENETRATIONS

2013 CALIFORNIA PLUMBING CODE TABLES 313.1

5" TO 8" 1/2"

VRF INDOOR UNIT (FAN COIL) SCHEDULE

CODE

IU-201

NOTES:

1. "CANFAB PEFY SERIES" MIXING BOX WITH MOTORIZED ACTUATOR AND CONTROLS POWERED BY INDOOR UNIT, (2" MERV 13).

2. CONDENSATE PUMP, THERMOSTAT, CO2 SENSOR SPRING ISOLATION MOUNTING, BMS INTERFACE.

DESCRIPTION

DUCTED

LOCATION

ATTIC

AREA SERVES

RM. 356

NOMINAL CAPACITY

TONS

4.5

CAPACITY (BTUH)

COOLING

54,000

HEATING

60,000

CFM

1,400

OSA

650

SP (in)

0.64

MCA

4.29

MOCP

15

ELECT

V/PH

208/1

CONTROL

THERMASTAT

SOUND

dBA

41

WEIGHT

(LBS)

175

HEIGHT

(IN)

15

PART

NO.

PEFY-P54NMHU-E2

MFG

MITSUBISHI

REMARKS

1,2

GRILLES & REGISTERS

CODE

CD-1

RG-1

TG-1

NOTES:

1. PROVIDE NECK TRANSITIONS

2. 1/2"x1/2"X1/2" GRID

DESCRIPTION

SUPPLY

RETURN

TRANSFER

LOCATION

RM 356

RM 356

RM 356

SIZE

24"x24"

24"x24"

24"x24"

NECK

10"

18"x18"

18"x18"

MAX

CFM

300

1,200

1,200

MAX

SP

--

--

--

DUCT

SIZE

10"

16"

16"

BLADE

SPACING

--

--

--

BLADE

DEFLECTION

--

--

--

MTG

LAY-IN

LAY-IN

LAY-IN

PN

MCD

50F

50F

MFR

TITUS

TITUS

TITUS

REMARKS

1

1,2

1,2

OUTSIDE AIR REQUIREMENT

FLOOR AREA

FT2

1,300

PEOPLE

45

CONTINUOUS VENTILATION TOTAL:

ACCOMPLISHED BY:

MODULATING MIXING BOX SET TO MINIMUM OSA.

OSA TO 100% UPON DEMAND PER CO2 SENSOR

FACTOR

CFM/FT2

0.12

FACTOR

CFM/PERSON

10

CFM

156

CFM

450

606 CFM

CHAPTER 11 REFRIGERATION CONCENTRATION LIMIT

COMPLIANCE CALCULATION:

R410A = 26 LBS./ 1000 CU. FT. OF SPACE MAXIMUM PER

CPC TABLE 1102.2.

OU-201 CHARGE = 21.0 LBS.

TOTAL SPACE CONCENTRATION = 1.7 LBS/ 1,000 CU.FT.

AutoCAD SHX Text
S
AutoCAD SHX Text
X
Page 10: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

X

XX

XX

XX

XX

X

XX

XX

XX

XX

X

XX

X

X

X X

X X

X X

X

X

X X

X X X

X

X

X

X X

X

X

X

X

X

X

X

X

X X X X X X X X X X X X

X X X X X X X X X X X X X

X

X

X X

(E)12"x12" EA

DUCT BELOW

38"x14" SA

(E)EA HOOD

(E)36"x14"

TYP. 11

(E

)38"x14"

(E)12"x12"

TYP. 5

(E)36"x18",UP

(E)28"x38",UP

(E)BASE HEATER

21"H x 6"W x 8'H

XX

XX

XX

X

XX

XX

XX

XX

X

X

X

X

X

X X

XX

X X

X X

X X

X X

X

X

X

X

X

X

X

X

X

X

X X

X

X

X X

X

X

X X

X

X

X X

X X

XX

XX

X

XX

XX

X

X

X

X

X X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

(E)12"x12"

RM. 356

(E)EA HOOD

(E

)38"x14"

(E)HHWS & R

RISERS.

X

1

2

HED

8

9

10

11

12

X

X

X

X

X X

XX

X X

X

X

X

X

X

X

X

X

X

X

X

X

XX

XX

X X X

XX

XX

XXX

X

X

X

X

X

X

(E) 98"x26"

(E) 74"x26"

(E) 50"x26"

(E) AH-6

(E) 38"x28"

SA DROP

(E) 38"x18"

EA DROP

(E) LOUVER

PLENUM

(E) LOUVER

ROOF LINE

(E) AH-5

(E) EA RISER.

(E) EF-8

2

POD

POD

8

9

10

11

12

HED

William

F

ish

er A

rch

itectu

re, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William Fisher

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:

7/19/2019 1:28:28 PM

Cabrillo College

Ca

brillo

C

olle

ge

Ro

om

3

56

, B

uild

in

g 3

50

26

00

S

oq

ue

l A

ve

.

Ap

to

s, C

A 9

50

03

Issue Date

Revision Schedule

Rev. No. Date

9699 Blue Larkspur Lane, Suite 203 Monterey, CA 93940Telephone (831) 373-4390 / Facsimile (831) 373-6522www.listengineering.com © LEC 2019Job No. 19023.00

List EngineeringMechanical Consultants

S

R

R

I

S

T

E

G

E

E

No. 23440

L

I

T

A

T

F

O

E

CA

A N

H

M

C

E

E

R

A

I

N

R

F

O

I

L

A

C

L

A

F

ES

O

D

E

P

R

M

N

O

R

N

I

G

E

N

S

I

O

A

N

L

L

E

U

B

EXP. 12-31-20

D

M1.1

ME

CH

AN

IC

AL

D

EM

OL

IT

IO

N

FL

OO

R A

ND

A

TT

IC

P

LA

NS

2

M1.1

SCALE:1/4"=1'-0"

MECHANICAL - DEMOLITION FLOOR PLAN

DEMOLITION NOTE

1. REMOVE EXISTING WATER SOURCE

BASE HEATER AND HHWS & R PIPING IN

WALL AND CAP BRANCHES IN ATTIC

SPACE.

2. REMOVE EXISTING EQUIPMENT AND

DUCTING AS INDICATED.

GENERAL NOTES

1. FIELD VERIFY LOCATION, SIZE AND

CONNECTIONS OF ALL EXISTING

EQUIPMENT DUCTING AND PIPING.

2. PATCH AND REPAIR PER

ARCHITECTURAL SPECIFICATIONS, ALL

ROOF AND WALL OPENINGS

RESULTING FROM THE REMOVAL OF

EQUIPMENT, VENTING, DUCTING AND

PIPING.

1

M1.1

SCALE:1/4"=1'-0"

MECHANICAL - DEMOLITION ATTIC PLAN

0 42 81SCALE: 1/4" = 1'-0"

0 42 81SCALE: 1/4" = 1'-0"

NORTH

Page 11: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

IU-201 T

IU

201

OU

201

CD-1

250 CFM

CD-1

230 CFM

CD-1

230 CFM

CD-1

230 CFM

CD-1

230 CFM

CD-1

230 CFM

TG-1

M3.1

1

10"Ø

14"Ø

10"Ø

1

0

"

Ø

20"x12" AL

20"x16" AL

10"Ø

10"Ø

10"Ø

12"Ø

POC

(E

) 74"x26" O

SA

(E) 50"x26" OSA

1

2

3

4

5

24"x18"

REFRIGERANT LINE SET

CO2 S

POC

BD, TYPICAL

(E)EQUIPMENT

(E) 98"x26" OSA

(E) LOUVER

6

IN CEILING SPACE

M3.1

2

M3.1

3

M3.1

5

M3.1

4

16"Ø

RG-1

TYP. 2

TG-1

OSA

DUCT

40"x10"

RELIEF/ BDD

TYPICAL

TYPICAL

TYPICAL

M3.1

3

(E) EAD RISER

16"Ø

(3/8" LIQUID, 3/4" GAS)

8

9

10

11

12

13

JHED JHED

William

F

ish

er A

rch

itectu

re, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William Fisher

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:

7/19/2019 1:28:28 PM

Cabrillo College

Ca

brillo

C

olle

ge

Ro

om

3

56

, B

uild

in

g 3

50

26

00

S

oq

ue

l A

ve

.

Ap

to

s, C

A 9

50

03

Issue Date

Revision Schedule

Rev. No. Date

9699 Blue Larkspur Lane, Suite 203 Monterey, CA 93940Telephone (831) 373-4390 / Facsimile (831) 373-6522www.listengineering.com © LEC 2019Job No. 19023.00

List EngineeringMechanical Consultants

S

R

R

I

S

T

E

G

E

E

No. 23440

L

I

T

A

T

F

O

E

CA

A N

H

M

C

E

E

R

A

I

N

R

F

O

I

L

A

C

L

A

F

ES

O

D

E

P

R

M

N

O

R

N

I

G

E

N

S

I

O

A

N

L

L

E

U

B

EXP. 12-31-20

D

M2.1

ME

CH

AN

IC

AL

N

EW

W

OR

K

PL

AN

1

M2.1

SCALE:1/4"=1'-0"

MECHANICAL - NEW WORK PLAN

GENERAL NOTES

1. FIELD VERIFY EXISTING CONDITIONS,

SIZES AND LOCATION OF POINTS OF

CONNECTION.

2. EXHAUST AND OUTSIDE AIR SHALL BE

ACCOMPLISHED BY CONNECTION TO

EXISTING DUCTWORK. THERE SHALL BE

NO NEW PENETRATIONS THRU ROOF.

SHEET NOTES

1. CONNECT NEW OUTSIDE AIR (OSA) DUCT

TO EXISTING BRANCH FROM OSA MAIN.

2. MIXING BOX WITH MODULATING OA AND

RA DAMPER AND CONTROLS. SET OSA

PER SCHEDULE.

3. OFFSET REFRIGERANT LINE SET DOWN

THRU WALL TO WITHIN FIRST LEVEL

CEILING AND ROUTE LINES TO

EXTERIOR WALL PENETRATION.

4. REFRIGERANT LINE SET THRU EXTERIOR

WALL, WEATHER TIGHT PIPE SLEEVE AT

6" ABOVE INTERIOR FINISHED FLOOR.

OFFSET LINE SET TO EQUIPMENT PAD.

5. CONDENSER UNIT MOUNTED ON

CONCRETE PAD. LOCATE UNIT PER

MANUFACTURES RECOMMENDED

CLEARANCES.

6. CONNECT NEW RELIEF DUCT TO

EXISTING EXHAUST DUCT.

SEQUENCE OF OPERATION

1. IU-2O1 OPERATION SHALL BE

CONTROLLED BY THERMOSTAT.

2. MIXING BOX OSA DAMPER SHALL

FULLY OPEN AND RA DAMPER SHALL

FULLY CLOSE UPON SIGNAL FROM CO2

DETECTIOR.

NORTH0 42 81SCALE: 1/4" = 1'-0"

Page 12: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

William

F

ish

er A

rch

itectu

re, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William Fisher

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:

7/19/2019 1:28:28 PM

Cabrillo College

Ca

brillo

C

olle

ge

Ro

om

3

56

, B

uild

in

g 3

50

26

00

S

oq

ue

l A

ve

.

Ap

to

s, C

A 9

50

03

Issue Date

Revision Schedule

Rev. No. Date

9699 Blue Larkspur Lane, Suite 203 Monterey, CA 93940Telephone (831) 373-4390 / Facsimile (831) 373-6522www.listengineering.com © LEC 2019Job No. 19023.00

List EngineeringMechanical Consultants

S

R

R

I

S

T

E

G

E

E

No. 23440

L

I

T

A

T

F

O

E

CA

A N

H

M

C

E

E

R

A

I

N

R

F

O

I

L

A

C

L

A

F

ES

O

D

E

P

R

M

N

O

R

N

I

G

E

N

S

I

O

A

N

L

L

E

U

B

EXP. 12-31-20

D

M3.1

ME

CH

AN

IC

AL

D

ET

AIL

S

RECTANGULAR DUCT SUPPORTS

5

M3.1 NO SCALE

1. FOR HANGERS SIZE AND SPACING, SEE SMACNA HVAC RECTANGULAR DUCT HANGERS MINIMUM

SIZE TABLE 5-1.

2. FOR UPPER ATTACHMENT TO BUILDING, SEE SMACNA HVAC FIG. 5-2, FIG. 5-3, AND FIG. 5-4 WITH

SPECIFIC BUILDING STRUCTURAL ENGINEER APPROVAL. FOR LOWER HANGER ATTACHMENTS,

SEE SMACNA HVAC FIG. 5-5.

3. FOR BRACING AND OTHER SEISMIC REQUIREMENTS, SEE GUIDELINES FOR SEISMIC RESTRAINTS

OF MECHANICAL SYSTEMS & PLUMBING PIPING SYSTEMS PUBLISHED BY SMACNA AND PPIC AS

APPROVED BY OFICE OF STATE ARCHITECT 10/32/82, OSHPD PRE-APPROVED R0010. ALSO REFER

TO NATIONAL UNIFORM SEISMIC INSTALLATION GUIDELINES (NUSIG) 1991 AS APPROVED BY

OFFICE OF THE CALIFORNIA STATE ARCHITECT, OSHPD PRE- APPROVED R0215.

NOTES:

STRAP HANGERS

SCREWS

BOLT CORNERS

TRAPEZE HANGERS

1" MINIMUM

HANGER STRAPS

60" MAX.

ANGLE HANGER

ROD HANGER

BAND (2)1"x16 GA

HANGER ROD

LOAD RATED FASTENER

BAND (2)1"x18 GA

STRAP HANGER

OVER 50 INCH DIA.

50 INCH DIA. MAX.

24 INCH DIA. MAX.

(WIRE HANGERS

NOT PERMITTED)

NOTES:

1. FOR HANGER SIZE AND SPACING, SEE SMACNA HVAC

MINIMUM HANGER SIZES FOR ROUND DUCT TABLE 5-2.

2. FOR UPPER ATTACHMENT TO BUILDING SEE SMACNA

HVAC FIG. 5-2, FIG. 5-3, AND FIG 5-4. FOR LOWER SUPPORTS

SEE SMACNA HVAC FIG. 5-5.

3. FOR BRACING AND OTHER SEISMIC REQUIREMENT SEE

GUIDELINES MECHANICAL SYSTEMS AND PLUMBING.

ALSO REFER TO NATIONAL UNIFORM SEISMIC INSTALLATION.

ROUND DUCT SUPPORTS

4

M3.1 NO SCALE

FAN COIL, BS AND ERV UNIT MOUNTING DETAIL

1

M3.1 NO SCALE

2" DEFLECTION SPRING ISOLATOR

DUCTED FAN COIL,

BS UNIT OR ERV.

(2)1/2"Ø LAG BOLT

TO BLOCKING MIN. 3-1/2" EMBED

OR (2)1/2"Ø THUR BOLTS, NUTS &

WASHERS WHEN ATTACHING TO

JOISTS.

WOOD JOISTS

3/8"Ø BOLTS AND WASHERS

SWAY BRACE AS REQUIRED.

3/8" Ø THREADED ROD

CONDENSATE DRIP PAN

3/8"Ø BOLTS AND WASHERS

CONDENSER MOUNTING DETAIL

2

M3.1 NO SCALE

2"

TYP

(E) 6" CONCRETE

HOUSEKEEPING PAD

SEE STRUCTURAL

DRAWINGS.

3" M

IN

EM

BE

D

3/8"Ø EXPANSION

BOLT. USE HILTI

KB-TZ (TYP)

EQUIPMENT

NOTES:

1. IF THERE IS INSUFFICIENT HEADROOM

FOR TOP CONNECTION

AS DETAILED, USE SIDE CONNECTION.

CEILING DIFFUSER INSTALLATON

3

M3.1 NO SCALE

D MIN.

6" MIN.

D

D

ROUND DUCT ADAPTER FOR

RECTANGULAR DIFFUSERS

CEILING DIFFUSER

TOP CONNECTION

2-3/4" MIN.

THERMAL DUCT INSULATION

R = D

MAX. 6FT. LENGTH FLEXIBLE

DUCT FULLY EXTENDED

SIDE CONNECTION

DIFFUSERCEILING

DIFFUSER NECK SIZE

MAX. 6FT. LENGTH FLEXIBLE

DUCT FULLY EXTENDED

ROUND DUCT CONNECTOR

UNIT FOOT

EQUIPMENT

USE B-LINE CHANNEL

AND CLAMPING SYSTEM

OR EQUAL

PIPING

B-LINE SERIES

C6 OR EQUAL

FINISHED GRADE

SUPPORT FOR PIPING

6

M3.1 NO SCALE

Page 13: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

William

F

ish

er A

rch

itectu

re, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William Fisher

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:

7/19/2019 1:28:28 PM

Cabrillo College

Ca

brillo

C

olle

ge

Ro

om

3

56

, B

uild

in

g 3

50

26

00

S

oq

ue

l A

ve

.

Ap

to

s, C

A 9

50

03

Issue Date

Revision Schedule

Rev. No. Date

9699 Blue Larkspur Lane, Suite 203 Monterey, CA 93940Telephone (831) 373-4390 / Facsimile (831) 373-6522www.listengineering.com © LEC 2019Job No. 19023.00

List EngineeringMechanical Consultants

S

R

R

I

S

T

E

G

E

E

No. 23440

L

I

T

A

T

F

O

E

CA

A N

H

M

C

E

E

R

A

I

N

R

F

O

I

L

A

C

L

A

F

ES

O

D

E

P

R

M

N

O

R

N

I

G

E

N

S

I

O

A

N

L

L

E

U

B

EXP. 12-31-20

D

P0.1

PL

UM

BIN

G L

EG

EN

D,

NO

TE

S, S

CH

ED

UL

ES

AN

D D

ET

AIL

S

1. ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE 2016 CALIFORNIA PLUMBING

CODE AND ALL OTHER APPLICABLE CODES AND REGULATIONS, INCLUDING THE 2016 CALIFORNIA

ENERGY CONSERVATION STANDARDS OF TITLE 24.

2. LOCATION OF ALL ROOF OPENINGS AND THE LOCATION OF ALL ROOF MOUNTED EQUIPMENT

SUPPORTS ARE DETAILED ON THE STRUCTURAL AND ARCHITECTURAL PLANS.

3. PLATFORMS, CURBS AND FLASHING FOR EQUIPMENT SHALL BE AS INDICATED ON THE STRUCTURAL

AND ARCHITECTURAL PLANS. COORDINATE THE EXACT SIZES OF REQUIRED OPENINGS AND

SUPPORT FOR THE FURNISHED EQUIPMENT.

4. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT

MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, AND OTHER

DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.

5. ALL EQUIPMENT, PIPING, AND OTHER DEVICES AND MATERIALS INSTALLED OUTSIDE THE BUILDING

OR OTHERWISE EXPOSED TO THE WEATHER SHALL BE COMPLETELY WEATHERPROOFED.

6. PIPES SHALL BE SUPPORTED AND BRACED PER SMACNA “GUIDELINES FOR SEISMIC RESTRAINTS OF

MECHANICAL SYSTEMS AND PLUMBING PIPING SYSTEMS.”

7. COORDINATE PLUMBING SYSTEMS WITH WORK OF OTHER TRADES PRIOR TO ANY FABRICATION OR

INSTALLATION. PROVIDE ALL FITTINGS, OFFSETS, AND TRANSITIONS AS REQUIRED FOR A COMPLETE

WORKABLE INSTALLATION.

8. EXPOSED PIPING ALLOWED ONLY WHERE INDICATED. PROVIDE ESCUTCHEONS IN FINISHED AREAS.

9. MAINTENANCE LABEL SHALL BE AFFIXED TO ALL PLUMBING EQUIPMENT.

10. PROVIDE ROUGH-IN AND FINAL CONNECTIONS FOR EQUIPMENT PROVIDED UNDER OTHER DIVISIONS

OF THE SPECIFICATIONS. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF EQUIPMENT.

11. PENETRATIONS OF RATED ASSEMBLIES SHALL BE FIRE STOPPED BY AN APPROVED MATERIAL AS

PRESCRIBED IN CBC SECTION 714.

12. REFER TO STRUCTURAL DRAWING FOR LOCATIONS OF BEAMS, SHEAR WALLS AND MEMBERS. ALL

DRILLING OF STRUCTURAL BEAMS AND MEMBERS TO BE COORDINATED WITH THE STRUCTURAL

ENGINEER. ALL HOLES SHALL BE MINIMUM SIZE AND APPROVED BY STRUCTURAL ENGINEER PRIOR

TO DRILLING.

13. FIELD VERIFY LOCATION AND SIZE OF ALL EXISTING PIPING, DUCTWORK AND EQUIPMENT PRIOR TO

FABRICATION OF ANY NEW WORK.

14. ALL WATER CLOSETS CONTROLS SHALL BE ON THE SIDE OF THE FIXTURE AWAY FROM THE WALL.

15. ALL FAUCET CONTROLS SHALL BE OPERABLE WITH THE HAND AND SHALL NOT REQUIRE TIGHT

GRASPING, PINCHING OR TWISTING OF THE WRIST.

16. PC SHALL PROVIDE CONCRETE INSERTS FOR HANGING PLUMBING EQUIPMENT, COORD. W/ GC.

GENERAL PLUMBING NOTES

GREASE WASTE (EXISTING)

(N) WASTE PIPING (ABOVE FLOOR)

WASTE PIPING (EXISTING)

VACUUM PIPING (NEW)

SUB-SOIL PIPING

STORM DRAIN (NEW)

VENT PIPING (NEW)

UNION

STRAINER

STORM DRAIN (EXISTING)

ROOF DRAIN

RAIN WATER LEADER

T & PRV RELIEF VALVE

PRESSURE REDUCING VALVE

PIPE TEE DOWN

PIPE TURNING DOWN (DROP)

PIPE TURNING UP (RISE)

RWL

REDUCER

PETES PLUG

OXYGEN PIPING (EXISTING)

HOSE BIBB ((E) 3/4" MIN.)

PIPE HANGER

HPG

GATE VALVE

GLOBE VALVE

DIRECTION OF FLOW

DRY STANDPIPE

FIRE SPRINKLER PIPING

FLANGED UNION

FLOOR DRAIN/ AREA DRAIN

FLOOR SINK

FM FORCE MAIN

GAS COCK

BALANCING COCK

COMPRESSED AIR PIPING (E)

CAP

CHECK VALVE

CLEANOUT

BALL VALVE

FL

DSP

WSP WET STANDPIPE (NEW)

TRAP PRIMER (TP)

GCO GROUND CLEANOUT

VTR VENT THRU ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

WM WATER METER

VIF VERIFY IN FIELD

V VENT

TP TRAP PRIMER

SS SANITARY SEWER

SOV SHUTOFF VALVE

SD STORM DRAIN

RD ROOF DRAIN

PVC POLYVINYL CHLORIDE PIPE

PRV PRESSURE REDUCING VALVE

PIV POST INDICATION VALVE

PC PLUMBING CONTRACTOR

OFD OVERFLOW DRAIN

(N) NEW

NPW NON POTABLE WATER

MC MECHANICAL CONTRACTOR

LAV LAVATORY

IE: INVERT ELEVATION

DCW DOMESTIC COLD WATER

HB HOSE BIBB

GPM GALLONS PER MINUTE

GC GENERAL CONTRACTOR

FSC FIRE SPRINKLER CONTRACTOR

FD FLOOR DRAIN

FCO FLOOR CLEANOUT

FC FLEX CONNECTOR

EL ELEVATION

EC ELECTRICAL CONTRACTOR

(E) EXISTING

DSP DRY STAND PIPE

DS DOWN SPOUT

DN DOWN

DCV DETECTOR CHECK VALVE

HWS HOT WATER SUPPLY

CD CONDENSATE

CAST IRON

CFH CUBIC FEET PER HOUR

CB CATCH BASIN

BV BALL VALVE

AP ACCESS PANEL

AFF ABOVE FINISH FLOOR

BACKFLOW PREVENTOR

REDUCED PRESSURE

POINT OF CONNECTION

TO EXISTING

RPBFP

SYMBOLS & ABBREVIATIONS (PLUMBING)

LPG

O2

A

GW

SD

SD

VAC

LIQUID PETROLEUM GAS

PIPING (EXISTING)

WASTE PIPING -

UNDERGROUND (NEW)

WATERHAMMER ARRESTOR

(WHA)

DEIONIZED WATER (EXISTING)D

VACUUM PIPING (EXISTING)VAC

VENT PIPING (EXISTING)

WSP WET STANDPIPE (EXISTING)

CA COMPRESSED AIR PIPING

(F) FIRE SPRINKLER PIPING

DHW DOMESTIC HOT WATER

FM FORCE MAIN

CI

FS FLOOR SINK

DHWR DOMESTIC HOT WATER RETURN

HPG HIGH PRESSURE GAS

LPG LOW PRESSURE GAS

O2 OXYGEN

PP PETES PLUG

POC POINT OF CONNECTION

POD POINT OF DEMOLITION

RWL RAIN WATER LEADER

VAC VACUUM

SDCW SOFT DOMESTIC COLD WATER

SDHW SOFT DOMESTIC HOT WATER

GW GREASE WASTE

RWL RAIN WATER LEADER (EXISTING)

DOMESTIC COLD

WATER (NEW)

GAS PIPING (EXISTING)G

GAS PIPING (NEW)G

HIGH PRESSURE GAS

PIPING

LPG

LIQUID PETROLEUM GAS

PIPING (NEW)

OXYGEN PIPING (NEW)

O2

GREASE WASTE (NEW)GW

AV ACID VENT

AW ACID WASTE

CHROME PLATEDCP

FL FIRE LINE

AV ACID VENT

DOMESTIC COLD

WATER (EXISTING)

DOMESTIC HOT WATER

(EXISTING)

DOMESTIC HOT WATER (NEW)

DOMESTIC HOT WATER RETURN

(EXISTING)

DOMESTIC HOT WATER RETURN

(NEW)

AFCO ACID FLOOR CLEANOUT

AGCO ACID GRADE CLEANOUT

AFD ACID RESISTANT FLOOR DRAIN

AVTR ACID VENT THRU ROOF

AWCO ACID WALL CLEANOUT

PIPE (ABOVE THE CEILING)

VB VALVE BOX

PIPE SUPPORT

1

P0.1 NO SCALE

JOIST HANGER

LAG BOLT

CLEVIS HANGER

EXPANSION BOLT

CLEVIS

HANGERS AND PIPING SUPPORTS

SIZE OF PIPE (INCH)

GAS PIPING (STEEL, BRASS & TINNED COPPER)

1/2"

3/4"-1"

1-1/4" AND LARGER

WATER OR DWV PIPING (STEEL & BRASS)

3/4" & SMALLER

1" AND LARGER

COPPER TUBE & PIPE

1-1/2" & SMALLER

2" AND LARGER

SPACING OF SUPPORTS (FEET)

HORIZONTAL

6'

8'

10'

10'

12'

6'

10'

VERTICAL

6'

8'

EVERY FLOOR LEVEL

EVERY OTHER FLOOR

NOT TO EXCEED 25'

EACH FLOOR, NOT TO

EXCEED 10'

PIPE SIZE

1/2" TO 4"

5" TO 8"

10" TO 12"

2013 CALIFORNIA PLUMBING CODE TABLES 313.6

TYPE OF JOINT

THREADED OR

WELDED

THREADED OR

WELDED

SOLDERED OR

BRAZED

THREADED HANGER ROD SIZE

3/8"

1/2"

5/8"

THREADED

HANGER ROD TO

STRUCTURE

THREADED HANGER ROD

FOR SIZE SEE TABLE

PROVIDE PIPE SLEEVE

ESCUTCHEON AT ALL

PENETRATIONS

INSTALL LISTED PIPE HANGER SUPPORT COMPONENTS PER MFR. RECOMMENDATIONS.

VERIFY ALL ATTACHMENT TO STRUCTURE WITH STRUCTURAL ENGINEER PRIOR TO

INSTALLATION. PIPE HANGERS AND SUPPORTS, MATERIALS, DESIGN AND

MANUFACTURE SHALL CONFORM TO ANSI/MSS SP-58.

2013 CALIFORNIA PLUMBING CODE TABLES 313.1 & TABLE 1210.2.4.1

DRAWING INDEX

DWG #

P0.1

P1.1

DRAWING DESCRIPTION

PLUMBING LEGEND, NOTES SCHEDULES AND DETAILS

PLUMBING DEMOLITION AND NEW WORK PLANS

Page 14: C−11008 CABRILLO COLLEGE ROOM 356 (REMODEL) 350 … · ROOM 356 (REMODEL) 350 BUILDING GENERAL NOTES PROJECT DESCRIPTION PROJECT INFORMATION DIRECTIONS From Hwy 1 S, take Park Ave

X X

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

(E)SINK

RM. 356

2

1

1

(E)SINK

2

HED

8

9

10

11

12

HED

8

9

10

11

12

IU-201

(E) JANITOR

SINK

3

CO

CO

CO

2

TYPICAL

1

SLOPE

P0.1

1

William

F

ish

er A

rch

itectu

re, In

c.

60

3 F

ro

nt S

tre

et, S

an

ta

C

ru

z, C

alifo

rn

ia

9

50

60

83

1 2

46

-0

11

7 b

ill@

mo

de

rn

-a

rch

ite

ctu

re

.co

m

mo

de

rn

-a

rch

ite

ctu

re

.co

m

LicensedArchitect

William Fisher

10/31/19

RENEWS ON

A

I

N

O

F

I

L

A

R

C

COPYRIGHT 2019, WILLIAM FISHER ARCHITECTURE, INC.

Date Printed:

7/19/2019 1:28:28 PM

Cabrillo College

Ca

brillo

C

olle

ge

Ro

om

3

56

, B

uild

in

g 3

50

26

00

S

oq

ue

l A

ve

.

Ap

to

s, C

A 9

50

03

Issue Date

Revision Schedule

Rev. No. Date

9699 Blue Larkspur Lane, Suite 203 Monterey, CA 93940Telephone (831) 373-4390 / Facsimile (831) 373-6522www.listengineering.com © LEC 2019Job No. 19023.00

List EngineeringMechanical Consultants

S

R

R

I

S

T

E

G

E

E

No. 23440

L

I

T

A

T

F

O

E

CA

A N

H

M

C

E

E

R

A

I

N

R

F

O

I

L

A

C

L

A

F

ES

O

D

E

P

R

M

N

O

R

N

I

G

E

N

S

I

O

A

N

L

L

E

U

B

EXP. 12-31-20

D

P1.1

PL

UM

BIN

G

DE

MO

LIT

IO

N A

ND

N

EW

WO

RK

P

LA

NS

2

P1.1

SCALE:1/4"=1'-0"

PLUMBING FLOOR PLAN - NEW WORK

DEMOLITION NOTE

1. REMOVE EXISTING SINK AND FAUCET

SETS.

2. REMOVE EXISTING DRAIN, ISLAND

VENT AND WATER SUPPLY PIPING

ABOVE FLOOR. CAP EXISTING

BRANCHES BELOW FLOOR.

GENERAL NOTES

1. FIELD VERIFY LOCATION, SIZE

CONNECTIONS AND SERVICE OF ALL

EXISTING EQUIPMENT AND PIPING.

2. PATCH AND REPAIR PER

ARCHITECTURAL SPECIFICATIONS, ALL

WALL, FLOOR AND ROOF OPENINGS

RESULTING FROM THE REMOVAL OF

EQUIPMENT, VENTING AND PIPING.

SHEET NOTES

1. CONNECT 3/4" CONDENSATE DRAIN TO

IU-201 WITH CONDENSATE PUMP.

2. 3/4" CONDENSATE DRAIN IN CEILING

SPACE. SLOPE MINIMUM 1/4" PER FOOT

SLOPE.

3. DISCHARGE CONDENSATE DRAIN

INDIRECTLY WITH MINIMUM 1" AIR GAP

AND TURNED DOWN ELBOW TO

EXISTING JANITOR SINK.

0 42 81SCALE: 1/4" = 1'-0"

NORTH

GENERAL NOTES

1. FIELD VERITY EXISTING CONDITIONS,

SIZES AND LOCATIONS OF POINTS OF

CONNECTION.

1

P1.1

SCALE:1/4"=1'-0"

PLUMBING FLOOR PLAN - NEW WORK

0 42 81SCALE: 1/4" = 1'-0"