cable cost cutters for the wind sector
TRANSCRIPT
July/August 2013 | Renewable Energy Focus14
While the social, economic and
political drivers for wind energy pick
up momentum, there are also huge
opportunities for technical innovation
in the industry, particularly as wind
farms increase both in physical size
and generation capacity.
Often overlooked by the casual ob-
server, cable plays a vital role in wind
power. A single wind turbine might
contain as many as 50 to 100 individu-
al types of cable, housed in its nacelle,
tower and base, each taking a role
in power transmission, distribution,
control or communications. Cable
manufacturers have a responsibility to
ensure that their customers achieve
more from infrastructure investment.
Turbine design dictates cable confi guration
The arrangement of electrical
components in a wind turbine dictates
AS THE wind turbine sector develops and
matures, effi cient use of cable is one area
where turbine OEMs can streamline their
processes, says Thibaut Zumsteeg from
cable supplier Nexans.
Cables play a vital role in the wind power industry and it’s one area where turbine
manufacturers can streamline
the type and confi guration of cables
to be used. Housed in the nacelle,
the generating components include
the generator, gearbox, drive train
and brake assembly. They are linked
to the tower via a loop or looping
cable, named because it loops into
the nacelle as it turns into the wind.
The loop cable transmits power to
the lower section of the tower, where
cable is fi xed to the tower structure,
before connecting to the grid.
Turbine cables are typically a
mixture of low voltage (LV) and me-
dium voltage (MV) cables, with their
selection depending on the voltage
rating and design of the generator and
it is the location of the transformer
that is the deciding factor.
Performing the role of stepping up
the voltage from the LV generator to
20-36kV for transmission to the grid,
the transformer can be located in
the nacelle itself, the central or lower
sections of the tower or even outside
the tower.
For models where the transformer
is in the nacelle, a MV cable rated at
36kV connects the transformer to the
distribution point at the base of the
tower. This allows turbines to oper-
ate at higher voltages and therefore
deliver more power, a popular trend in
onshore turbines today.
Conversely, when the transformer
is housed in the central or lower
section of the tower, an LV cable rated
at 0.6-1kV connects the generator to
the transformer.
In the case of a Double Fed
Induction Generator (DFIG), both LV
and ‘low’ MV cables can be installed
as loop cables between the nacelle and
the tower.
Beyond the basic confi guration
of the turbine, cable type is deter-
mined by the location and role, with
all cable required to meet the UL
and CSA standards. Loop cables, in
particular, must pass stringent testing
to meet the demands of their specifi c
application.
Four types of turbine cableNacelle power cables• : LV cables in
the nacelle need to withstand the
tough environment of the nacelle,
which demands a small bending
radius, resistance to aggressive
chemicals and ozone, and the
ability to withstand temperatures
as high as 105˚C and as low as
-40˚C. LV cables in the nacelle
tend to be specifi ed with a
specialist insulation and sheath in
rubber or another compound with
similar performance. Single core
MV cables also perform a role in
the nacelle, often as output
connections from the winding
bars of Class H generators and
current converter cabinets. These
need to carry high levels of
current in extremely hot conditions
of up to 180˚C and are silicone
insulated.
Loop cables from nacelle to tower• :
Moving down from the nacelle, the
MV and LV cables used as loop
cables need to be both light and
fl exible so that they can withstand
the torsional stress applied by up
to four full rotations of the nacelle
Cable cost cutters for the wind sector
Renewable energy • technology update
focus:Technology
REF0413_Focus_Technology_Nexans 14 29-07-13 14:26:39
15July/August 2013 | Renewable Energy Focus
About: Thibaut Zumsteeg is Global Marketing Manager for Wind Energy, Nexans
in either direction. Depending on
the requirements, loop cables can
come in single-, three- or four-core
versions. The insulation and sheath
of loop cables need to be resistant
to oil, abrasion, UV, ozone and tem-
peratures ranging from -40 to
90˚C. Low Smoke halogen free
(LS0H) insulation and sheath
materials are also increasingly in
demand and lifetime testing con-
fi rms that cables are fi t for purpose
for the design life of the turbine.
Tower cables• : Connecting the
nacelle to the switchgear at the
base of the tower, whether the
transformer is located in the
nacelle or the body of the tower,
tower cables are an extension of
the loop cable. In the case of tur-
bines where the transformer is in
the nacelle, the MV loop cable
extends as a single length to the
switchgear. Conversely, when the
transformer is in the tower itself,
the LV loop cable is connected to
the transformer via a fi xed instal-
lation cable made of highly conduc-
tive copper or aluminium for
effi cient transmission. Whatever
the arrangement, LV and MV
cables need to have proven resist-
ance to oil, abrasion, UV and ozone.
They also need to operate reliably
from -40 to 90˚C and are often
specifi ed in a LS0H design.
Communication cables• : The set of
cables is not complete without con-
trol and data transmission cables.
Comprising anything from two to
100 cores, control cables are fl exi-
ble, usually shielded for EMC pro-
tection and carry small currents of
300 V to 1 kV to control the tur-
bine’s motor drive, braking, posi-
tioning and rotor speed. On the
other hand, electronic and data
transmission cables carry the sig-
nals that control all electronic and
mechanical devices and carry data
from sensors that measure wind
speed, temperature and perform-
ance. Increasingly these are EMC
shielded and include thermoplastic
modifi ed 2 – 5 core sensor multi-
core and multipair cables to carry
data. Two-core Fieldbus cables are
used in parallel with power cables
to carry signals to control elec-
tronic and mechanical devices.
Cable manufacturers have a responsibility to ensure customers achieve more from their investments
Two-core Profi bus cable is also
used, delivering up to 12 Mbits for
complex control and data trans-
mission cables that deliver speeds
comparable to Industrial Ethernet.
Finally, fi bre-optic cables deliver
high capacity for the transmission
of monitoring and control data.
Loop cable testingOf all the cables in a wind turbine,
it is the loop cable that experiences
the highest levels of mechanical
stress. During the 20-year lifetime
of a typical turbine, a loop cable
will undergo thousands of cycles of
twisting as the nacelle rotates. Cable
manufacturers carry out testing on
cable to ensure their torsion and
strength performance.
Normal practice is to test 10 metre
lengths of cable and it needs to with-
stand a minimum rotational angle per
meter over at least 2,000 cycles that
the turbine will experience through-
out its lifetime (or more if specifi ed
by the OEM). While the goal is to ac-
commodate up to four full rotations of
the nacelle before the operator’s main-
tenance staff must step in, the reality
is that turbines usually only reach up
to two and a half complete rotations.
InstallationOEMs have a number of options
when ordering cable, the fi rst of which
is to order cable by the drum and cut
it themselves or use harness makers to
prepare lengths for installation. Alter-
natively, cable lengths can be cut to size
by the cable manufacturer and deliv-
ered ready for installation. There is a
new trend for OEMs to order cable kits
from the manufacturer, which include
pre-cut cable lengths, stripped and fi t-
ted with the appropriate connectors, to
speed up the installation process.
Because a turbine’s tower can ex-
tend to 140 metres in height, it is im-
possible to transport as a single unit.
Instead, four or fi ve tower sections of
up to 25 metres are preinstalled with
cable lengths, which are connected
on-site, with short lengths of up to
60 centimetres at either end of each
tower section allowing for straightfor-
ward connection by specialist electri-
cal installers on-site.
With this in mind, Nexans is working on solutions for the next
generation of wind turbine projects,
where the industry will be able to
order precise lengths of cable set out
in plans, minimising waste and time
needed for costly on-site installation.
One major international wind tur-
bine manufacturer, Nordex, has been
benefi tting from Nexans’ approach to
supplying cable sets and kits.
A framework agreement sees
Nexans supplying customised power
cable sets (cable cut to length) and
kits (pre-terminated cables custom-
ised for each turbine) for high ef-
fi ciency wind turbines. Ordered direct
from Nexans by Nordex’s tower man-
ufacturers, the cables, connectors and
kits are supplied ready to install for
onshore wind projects across Europe
and kits have already been supplied to
tower manufacturers worldwide.
As the wind turbine sector devel-
ops and matures, effi cient use of cable
is one area where turbine OEMs can
streamline their processes. Cable and
accessories need to off er guaranteed
performance and deliver power but
new developments in the cable indus-
try mean that installation can be faster
and more effi cient than ever before.
Technology
REF0413_Focus_Technology_Nexans 15 29-07-13 14:26:40