SOLUTION DESIGN GUIDE Cable Management Solutions for Brocade High-Density Port Blades 53-1003738-02 8 February 2017

Upload: hoangkhanh

Post on 29-Jun-2018

265 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

SOLUTION DESIGN GUIDE

Cable Management Solutions forBrocade High-Density Port Blades

53-1003738-028 February 2017

Page 2: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

© 2017, Brocade Communications Systems, Inc. All Rights Reserved.

Brocade, the B-wing symbol, and MyBrocade are registered trademarks of Brocade Communications Systems, Inc., in the United States and in othercountries. Other brands, product names, or service names mentioned of Brocade Communications Systems, Inc. are listed at www.brocade.com/en/legal/brocade-Legal-intellectual-property/brocade-legal-trademarks.html. Other marks may belong to third parties.

Notice: This document is for informational purposes only and does not set forth any warranty, expressed or implied, concerning any equipment,equipment feature, or service offered or to be offered by Brocade. Brocade reserves the right to make changes to this document at any time, withoutnotice, and assumes no responsibility for its use. This informational document describes features that may not be currently available. Contact a Brocadesales office for information on feature and product availability. Export of technical data contained in this document may require an export license from theUnited States government.

The authors and Brocade Communications Systems, Inc. assume no liability or responsibility to any person or entity with respect to the accuracy of thisdocument or any loss, cost, liability, or damages arising from the information contained herein or the computer programs that accompany it.

The product described by this document may contain open source software covered by the GNU General Public License or other open source licenseagreements. To find out which open source software is included in Brocade products, view the licensing terms applicable to the open source software, andobtain a copy of the programming source code, please visit http://www.brocade.com/support/oscd.

Cable Management Solutions for Brocade High-Density Port Blades2 53-1003738-02

Page 3: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

ContentsPreface...................................................................................................................................................................................................................................5

Purpose of This Document....................................................................................................................................................................................................................5Audience........................................................................................................................................................................................................................................................ 5Objectives......................................................................................................................................................................................................................................................5Terminology..................................................................................................................................................................................................................................................6Related Documents...................................................................................................................................................................................................................................6Document History......................................................................................................................................................................................................................................6About Brocade............................................................................................................................................................................................................................................ 6

Overview............................................................................................................................................................................................................................... 7

Planning .............................................................................................................................................................................................................................11Challenges with Unstructured High-Density Solutions...........................................................................................................................................................12Using a Structured Approach.............................................................................................................................................................................................................12

Cabling High-Density and High-Port-Count Fiber Equipment................................................................................................................................. 13Cabling Standards...................................................................................................................................................................................................................................15

Data Center Specific Standards...............................................................................................................................................................................................15General Commercial Building Cabling Standard..............................................................................................................................................................15Cabling Administration Standards.......................................................................................................................................................................................... 16

Establishing a Naming Scheme........................................................................................................................................................................................................16

Cable Management Setup and Configuration............................................................................................................................................................17Corning .......................................................................................................................................................................................................................................................17

Point-to-Point Structured Cabling Options........................................................................................................................................................................17Cross-Connect Structured Cabling Options...................................................................................................................................................................... 18

Data Center Systems.............................................................................................................................................................................................................................19Methode Data Solutions Group........................................................................................................................................................................................................ 21

Equipment Requirements ......................................................................................................................................................................................................... 22Cabling Solutions...........................................................................................................................................................................................................................23

R&M..............................................................................................................................................................................................................................................................23Port Replication Structured Cabling Options.....................................................................................................................................................................24Direct Interconnect Structured Cabling Approach........................................................................................................................................................... 25

DCX 8510 Cabling Installation (Front Side, Director Ports to Patch Panel)....................................................................................................... 26Cabling Installation (Back Side, from Devices to Patch Panel).............................................................................................................................................27

Servicing High-Density Solutions ................................................................................................................................................................................29Connecting a Cable to an Empty QSFP....................................................................................................................................................................................... 29Removing a Cable from a Populated QSFP............................................................................................................................................................................... 29

Best Practices for Managing the Cabling....................................................................................................................................................................30During Installation................................................................................................................................................................................................................................... 30Daily Practices..........................................................................................................................................................................................................................................31Summary....................................................................................................................................................................................................................................................31

Appendix A: Cable-to-Port Mapping........................................................................................................................................................................... 32

Appendix B: DCS-MTP–to–MTP-Port Mapping...................................................................................................................................................... 34

Appendix C: DCS-MTP–to–LC-Port Mapping.......................................................................................................................................................... 35

Appendix D: Equipment List.......................................................................................................................................................................................... 36

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 3

Page 4: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Director Chassis.......................................................................................................................................................................................................................................36Patch Cables for QSFP Connections.............................................................................................................................................................................................36Patch Panels..............................................................................................................................................................................................................................................38Custom Director Trunks....................................................................................................................................................................................................................... 40Velcro Cable Wraps................................................................................................................................................................................................................................40Labelers.......................................................................................................................................................................................................................................................40

Appendix E: FC16-64 Supported Connection Distances.......................................................................................................................................41

Appendix F: Cable Management and Patch Panel Vendors....................................................................................................................................42

Appendix G: Reference Materials..................................................................................................................................................................................44

Cable Management Solutions for Brocade High-Density Port Blades4 53-1003738-02

Page 5: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Preface• Purpose of This Document.............................................................................................................................................................................. 5• Audience...................................................................................................................................................................................................................5• Objectives................................................................................................................................................................................................................ 5• Terminology............................................................................................................................................................................................................ 6• Related Documents............................................................................................................................................................................................. 6• Document History................................................................................................................................................................................................ 6• About Brocade.......................................................................................................................................................................................................6

As the number of devices connected to Fibre Channel fabrics increases, the demand for options to simplify connectivity grows as well.MPO/MTP connections with QSFP optics are increasingly being deployed to enable consolidation of optics and cabling as well as futuresupport for high-speed 128-Gbps parallel Fibre Channel connections. Brocade supports the use of QSFP optics on multiple products,including the FC16-64 high-density port blade for the Brocade DCX 8510 Backbone, UltraScale Inter-Chassis Link connections on theBrocade DCX 8510 and X6 Director families, and the Q-Flex ports on the Brocade G620 Switch. The QSFP form factor has beenwidely deployed across the networking industry for Ethernet (40-Gbps and 100-Gbps speeds) and Fibre Channel connectivity, makingcabling options readily available. This document provides customers deploying FC16-64 high-density port blades with generalguidelines for proper optical fiber cable management.

Purpose of This DocumentUsing QSFP optics to connect to device ports may not be familiar to many Fibre Channel users. This document provides customers whodeploy FC16-64 high-density port blades with general guidelines for proper optical fiber cable management.

AudienceThis guide is for technical lT architects and Storage Area Network (SAN) administrators who are responsible for SAN design and/orinfrastructure management based on the Brocade DCX 8510 Backbone equipped with FC16-64 blades.

ObjectivesThis document provides best practices in cable deployment and management to avoid many unforeseen challenges that SAN designersface when implementing cabling solutions to support QSFP connectivity in a storage fabric. While not intended as a definitive cabledesign document, it does introduce concepts and guidelines to help you avoid potential issues that can result from poor cableimplementation practices.

This guide provides:

• An overview of the FC16-64 high-density FC port blade and QSFP optics

• Structured high-density cable management solutions based on MPO/MTP® connectors and patch panels

• Best practice guidelines and recommendations for optical fiber cabling

• Part numbers for optical cables and patch panels and vendor contact information

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 5

Page 6: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

TerminologyThe following are some commonly used terms that you will find throughout this guide.

Term Description

LC Lucent Coupler supporting single-channel SFP, SFP+, or XFP transceivers.

MPO/MTP® MPO is an industry term for Multifiber Push-On connector; MTP® is a trademarked name of an MPO connector with designenhancements to improve mechanical and optical performance. MTP is often used synonymously with MPO.

NOTEThe terms MPO and MTP may be used in this document in combination or interchangeably to represent but areunderstood to be compatible designs.

patch cord Single or multiple strand of fiber cables used for connectivity.

QSFP cable A fiber cable that supports up to four independent, bidirectional channels.

QSFP transceiver Quad-SFPs (QSFP) are transceivers that support up to four channels or ports from a single optic.

RU Rack Unit (4.4 centimeters/1.75 inches).

Related Documents• Best Practices Guide: Cabling the Data Center (PN: GA-BP-036-01)

• Brocade FC16-64 Port Blade QuickStart Guide

• Brocade DCX 8510-8 Backbone Hardware Installation Guide

• Brocade DCX 8510-4 Backbone Hardware Installation Guide

• Brocade X6-8 Director Hardware Installation Guide

• Brocade X6-4 Director Hardware Installation Guide

Document HistoryDate Version Description

March 2015 1.0 Initial release.

February 2017 2.0 Updated with Gen 6 hardware references.

About BrocadeBrocade® (NASDAQ: BRCD) networking solutions help the world's leading organizations transition smoothly to a world whereapplications and information reside anywhere. This vision is designed to deliver key business benefits such as unmatched simplicity,non-stop networking, application optimization, and investment protection.

Innovative Ethernet and storage networking solutions for data center, campus, and service provider networks help reduce complexity andcost while enabling virtualization and cloud computing to increase business agility.

To help ensure a complete solution, Brocade partners with world-class IT companies and provides comprehensive education, support,and professional services offerings (www.brocade.com).

Terminology

Cable Management Solutions for Brocade High-Density Port Blades6 53-1003738-02

Page 7: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

OverviewAs data centers scale to handle higher amounts of stored data with a need to access that data as faster speeds, the use of MTP/MPOconnectivity has grown as well. Brocade now offers MPO connectors with QSFP optics on several models of their SAN switching line,including the following.

Brocade DCX 8510 Backbone with FC16-64 Port Blade

The FC16-64 high-density 64-port Fibre Channel blade for the Brocade DCX 8510 Backbone family combines industry-leading portdensity, scalability, reliability, and energy efficiency to maximize the benefits of SAN and server consolidation. The FC16-64 enables midto large enterprise customers to deploy high-density modular chassis-based solutions that minimize the physical footprint withoutcompromising performance. High-density Fibre Channel port blades increase chassis density by 33 percent over a chassis populatedwith 48-port blades, enabling the Brocade DCX 8510-8 to scale up to 512 ports and the Brocade DCX 8510-4 to scale up to 256ports with 16-Gbps performance.

Inter-Switch Cabling of High-Port-Count Fiber Equipment

UltraScale Inter-Chassis Links provide 100-meter optical connectivity for up to 12 Brocade director chassis to a common core-edge orup to 9 directors in an active-active mesh chassis topology. These high-density chassis topologies using QSFP connectors fromdedicated ports on the core routing blades consolidate inter-switch cabling by 75 percent and free up to 25 percent of chassis ports touse for server and storage device connections. This provides the equivalent of up to 640 line-speed connections in a single14U chassis,the highest density available per RU.

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 7

Page 8: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 1 Brocade DCX 8510-4 with Four FC16-48 FC Port Blades and Two CR Blades with Eight ICL Ports Each—With anFC16-64 Blade to the Right

To reduce investment cost, energy consumption, and cabling requirements, Brocade uses a space-efficient, 4-channel QSFP (QuadSmall Form-factor Pluggable) optic on the FC16-64 blade, DCX 8510 or X6 ICLs, and Q-Flex ports that enable high-density portconfigurations as well as improved serviceability and simplicity of use (Figure 3). These QSFPs retain all the performance andfunctionality of the standard SFP+ and still support individual, per-port LED indicators for easy troubleshooting and diagnostics.

The Brocade G620 is a 64-port, high-density Fibre Channel switch to support rapid growth, demanding workloads, and data centerconsolidation in small- to large-scale enterprise infrastructures. This high-density design enables organizations to connect more devicesacross the data center with a smaller footprint, reducing costs and management complexity. To enable maximum flexibility and scalability,the Brocade G620 is configurable from 24 to 64 ports with 48 SFP+ and 4 Q-Flex ports. Organizations can quickly scale from 24 to64 ports with a combination of 12-port SFP+ Ports on Demand (PoD) licenses and a 16-port Q-Flex PoD. Each of the four Q-Flexports is capable of supporting 4×32-Gbps or 128-Gbps speeds for device port or ISL port connectivity. As an ISL connection, theQ-Flex ports can be broken out into individual 32-Gbps connections or can be connected to an FC16-64 blade in a core director usinga 16-Gbps QSFP optic in the Q-Flex port.

Cable Management Solutions for Brocade High-Density Port Blades8 53-1003738-02

Page 9: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 2 Brocade G620 Switch with 4 x Q-Flex MPO Connectors

FIGURE 3 Quad SFP (QSFP) Optical Transceiver with Pull Tab

The following table provides an overview of the differences between standard SFP+ optics and QSFPs. QSFPs leverage the sametechnology as standard SFPs but combine four channels into one optic to better support high-density SAN solutions.

Specification SFP+ QSFP

Speed Grades 2/4/8 Gbps

4/8/16 Gbps

8/16/32 Gbps

4/8/16 Gbps

16/32 Gbps

Operating Distance Same Same

Availability of SWL Transceivers Yes Yes

Availability of LWL Transceivers Yes No

Regulatory Compliance Same Same

Dimensions: Fiber Pitch 5.25–6.25 mm 0.25 mm

Dimensions: Width 13.55 mm 18.35 mm

Dimensions: Depth 56.40 mm Excluding pull-tab: 68.00 mm

Including pull-tab: 132.00 mm

Patch Cord Compatibility LC-LC patch cord MPO/MTP–MPO/MTP or MPO/MTP–LC

Breakout patch cords

Optics Supplier Brocade Brocade

Brocade requires the use of OM-3 or OM-4 fiber cables with QSFP optics to attain FC standards for connectivity distance. Refer to Appendix D: Equipment List on page 36 for cable manufacturer and part number details.

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 9

Page 10: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

The following MTP-terminated cables (Figure 4) provide the same flexibility in connectivity as standard LC cables:

• MTP-4xLC breakout cable assembly: Provides the FC16-64 port blade or G620 Q-Flex ports with the ability to connect toport blades, switches, hosts, or storage devices utilizing LC connectors or patch panels.

• MTP-MTP cable assembly: Allows one FC16-64 port blade to connect to an MPO/MTP patch panel or another FC16-64port blade as an ISL, as well as connecting ICL ports between DCX 8510 or X6 directors.

FIGURE 4 MPO/MTP–to–LC Breakout Cable (Left) and MPO/MTP–to–MPO/MTP Cable (Right)

Cable Management Solutions for Brocade High-Density Port Blades10 53-1003738-02

Page 11: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Planning• Challenges with Unstructured High-Density Solutions..................................................................................................................... 12• Using a Structured Approach....................................................................................................................................................................... 12• Cabling Standards............................................................................................................................................................................................. 15• Establishing a Naming Scheme.................................................................................................................................................................. 16

As port density per director and per rack increases, having an appropriate cable management plan is key during servicing or scaling of afabric and eases troubleshooting. The cable management plan should include current and future SAN design requirements. Cables canbe managed in a variety of ways, such as by routing cables below the chassis, to either side of the chassis, through cable channels on thesides of the cabinet, or by using patch panels. When planning a cable management solution and the cable routing path, consider thelocation of the rack’s power strip and the DCX 8510/X6 power supplies to eliminate cable interference when servicing the powersupplies and cords. Additionally, note the location of the X6-8's half-height control processor blades on the far left side of the chassis toensure unblocked access to management ports.

FIGURE 5 Brocade X6-8 Director with Control Processor Blades in Slots 1/2 Position

The cable management plan may involve wiring a new data center or upgrading the cabling in an existing data center.

• If an existing data center is being upgraded, evaluate, capture, and understand the present cabling infrastructure thoroughly.

• Document the current (if any) and projected network topologies using an application such as Microsoft Visio or Excel. Focus onthe physical aspects, especially equipment interfaces. Document the various cable types and counts present, proposed, andprojected; the approximate routed distances to distribution areas and equipment; and the present and anticipated equipmentport counts. Additionally, document any areas of concern and any established internal cabling standards.

• Plan to accommodate for current and future growth. Build in flexibility, so that the patching structure will allow a device toconnect to any other device in the data center. This built-in flexibility will permit devices to be located anywhere within the datacenter.

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 11

Page 12: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Challenges with Unstructured High-Density SolutionsAll three growth factors—volume, performance, and distance—have placed enormous strain on IT organizations, requiring miles of cableinfrastructure to interconnect servers, storage, and Fibre Channel fabrics for fast, reliable data and application delivery. Unfortunately,many organizations still rely on traditional point-to-point cable solutions, reactively deploying cables one at a time to suit immediateneeds.

The resulting cable clutter inhibits intelligent, pragmatic growth and contributes to an inefficient growth strategy that will only worsen overtime. The tasks of verifying proper connectivity, troubleshooting, and managing device change also become more complex and time-consuming and can lead to planned or unplanned downtime of critical business applications.

This inefficient approach also contributes to the overheating of data centers—particularly within raised flooring and around the rackswhere cable clutter primarily occurs—requiring additional resources to cool the systems.

FIGURE 6 Cable Clutter

Using a Structured ApproachCable management solutions designed specifically for Brocade SAN infrastructures with the Brocade DCX 8510 Backbone withFC16-64 port blades enable a reliable, flexible, and highly efficient cable infrastructure throughout the data center.

Depending on their specific requirements, organizations can choose from various structured fiber-optic cable management solutions. Bymoving from traditional low-density, duplex patch-cord cable solutions to high-density, structured cable solutions, organizations canimplement the physical layer in a much more manageable and flexible manner while streamlining data center reconfigurations andsimplifying management. These cable technologies are also more energy efficient, and they help organizations consolidate their ITinfrastructures.

Challenges with Unstructured High-Density Solutions

Cable Management Solutions for Brocade High-Density Port Blades12 53-1003738-02

Page 13: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Cabling High-Density and High-Port-Count Fiber EquipmentAs networking equipment becomes denser and port counts in the data center increase to the hundreds and thousands, managing cablesconnected to these devices becomes a difficult challenge. Traditionally, connecting cables directly to individual ports on low-port-countequipment was considered manageable. Applying the same principles to high-port-count equipment made the task more tedious,eventually becoming nearly impossible to add or remove cables connected directly to the equipment ports.

Structured cabling uses optical fiber connector housings that are connected through permanent links of optical cabling, typicallyconfigured in a physical star topology from the various areas within the data center (storage, servers, SAN, and network). Usingpreterminated MTP cabling from each of these areas to a central patching area provides an infrastructure where any port from any devicecan be connected to any other port.

Typical components used in optical cabling infrastructure are shown in the following table

MTP Trunk Assembly MTP-terminated optical fiber trunk assembliesare typically 8–288 fibers and create thepermanent fiber links between patch panels in astructured cabling environment. Theseassemblies are preterminated from themanufacturer with MTP connectors at aspecified length and have a pulling grip for easyinstallation.

Connector Housing Connector housings are physically mounted in a19-in. rack or cabinet. They are typically offeredin various sizes such as 1U, 2U, or 4U, whichrefers to the amount of rack space required formounting.

MTP-LC Module MTP-to-LC modules are installed into theconnector housings. They breakout the MTPconnection from the trunk cables into LCconnectivity. Thus, the trunk cables plug into therear MTP of the module, and LC jumpers pluginto the front of the module.

Using a Structured Approach

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 13

Page 14: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

MTP Adapter Panel MTP adapter panels (sometimes calledbulkheads) are installed into the housings. Theyoffer a connection point between the MTPtrunks and the MTP jumpers or breakoutharnesses. Thus, the trunk cables will plug intothe rear of the panel, and the MTP jumpers orharnesses will plug into the front of the panel.

MTP-LC Harness (breakout cable) MTP-LC harness assemblies are used forbreaking out the MTP connector into multipleLC connections.

MTP or LC Jumpers LC and MTP jumpers serve to create theconnection between device ports and thestructured cabling.

When cabling high-density, high-port-count MTP equipment, such as the Brocade DCX 8510 with FC16-64 blades, therecommendation is to preconnect the director blades with MTP/MPO jumpers with connectivity to dedicated connector housings. From

Using a Structured Approach

Cable Management Solutions for Brocade High-Density Port Blades14 53-1003738-02

Page 15: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

these housings, the MTP jumpers interconnect to MTP/MPO-based structured cabling for breakout into LCs in another connectorhousing at the other end of the cabling link (see Figure 7).

FIGURE 7 Structured Cabling Example for MTP Connectivity to LC Breakout in Central Patching Area

Once fully cabled, the housing(s) in this central patching area functions as if it were “remote” ports for the director ports. These dedicatedpatch panels for patching may be located in the same or adjacent cabinet as the director (typically in small data center footprints) or in aseparate central patching area (typically in medium-large data center footprints). Using this strategy drastically reduces equipment cablingclutter and improves cable management.

Cabling StandardsIndustry cabling standards are designed to protect the end user, providing a firm foundation for establishing a coherent infrastructure andguidelines for maintaining high levels of cable performance. Cabling standards define cabling specifications that look out to the nextseveral years, thus supporting future needs for higher speed transmissions. Standards enable vendors to use common media,connectors, test methodologies, and topologies, and they allow planners to design a cabling layout in the data center without worryingabout compatibility issues.

There are a number of standards organizations and standards. The best-known cabling standards are listed below.

Data Center Specific Standards• United States—ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

• Europe—CENELEC EN 50173-5 Information Technology—Generic Cabling Systems—Part 5: Data Centres

• International—ISO/IEC 24764 Information Technology—Generic Cabling for Data Centres

General Commercial Building Cabling Standard• United States—ANSI/TIA-568 Generic Telecommunications Cabling for Customer Premises

• Europe—EN 50173-1 Performance Requirements of Generic Cabling Schemes

• International—CSA ISO/IEC 11801:2009 Information Technology: Generic Cabling for Customer Premises

Cabling Standards

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 15

Page 16: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Cabling Administration Standards• United States—ANSI/TIA-606 Administration Standard for the Commercial Telecommunications Infrastructure

NOTECabling standards are reviewed and changed every five to ten years, which allows them to keep pace with technology advancesand future requirements. Standards may be purchased online from IHS at http://global.ihs.com/.

Establishing a Naming SchemeOnce the logical and physical layouts for the cabling are defined, apply a logical naming scheme that will uniquely and easily identify eachcabling component. Effective labeling promotes better communications and eliminates confusion when someone is trying to locate acomponent. Labeling is a key part of the process and should not be skipped. A suggested naming scheme for labeling and documentingcable components is suggested below (examples appear in parentheses):

• Building (SJ01)

• Room (SJ01-5D11)

• Rack or Grid Cell: Can be a grid allocation within the room (SJ01-5D11-A03)

• Patch Panel: Instance in the rack or area (SJ01-5D11-A03-PP02)

• Workstation Outlet: Instance in the racks or area (SJ01-5D11-A01-WS02)

• Port: Instance in the patch panel or workstation outlet (SJ01-5D11-A03-PP02_01)

• Cable (each end labeled with the destination port)

(Building and room may be excluded if there is only one instance of this entity in the environment.)

Once the naming scheme is approved, start labeling the components. Be sure to create a reference document that will become part ofthe training for new data center administrators.

NOTEAdditional recommendations can be found in the ANSI/TIA-606 standard, Administration Standard for the CommercialTelecommunications Infrastructure.

Establishing a Naming Scheme

Cable Management Solutions for Brocade High-Density Port Blades16 53-1003738-02

Page 17: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Cable Management Setup andConfiguration

• Corning ................................................................................................................................................................................................................. 17• Data Center Systems....................................................................................................................................................................................... 19• Methode Data Solutions Group...................................................................................................................................................................21• R&M........................................................................................................................................................................................................................ 23

A cable management solution using an MPO/MTP patch panel allows for easy management of high-density cabling, even for a BrocadeDCX 8510-8 with up to eight FC16-64 port blades. The traditional method of cabling blades with SFP ports uses MTP-LC modules tobreakout the MTP trunk assemblies into LC ports for jumper connectivity into the SAN director. Or, for improved cabling, MTP-LCharnesses are used to transition the MTP connector to LC leads that connect into the SAN director ports. Larger installations withmultiple units may require multiple patch panels to accommodate the transition from the MTP connectivity to the traditional LCconnectivity, which can use up to an additional 10 RU of valuable rack space. With the use of QSFP transceivers on the FC16-64blades, cabling density can be further optimized through the use of MTP patch cords from the structured cabling directly into the SANdirector ports, with breakouts to LCs at the other end of the cabling link. Structured cabling solutions are available from multiple leadingvendors and allow for higher consolidation of cabling into a compact patch panel, cabling, and connectivity. The following are examplesof several vendors’ solutions for cable management configurations for the FC16-64. Please consult with your preferred cabling providerto learn about solutions available from alternative vendors.

NOTEPart numbers for the various design options are shown in Appendix D.

CorningCorning provides a structured cabling solution for the Brocade DCX 8510 FC16-64 port blades that can be deployed in either point-to-point trunk implementations or using a cross-connect for port replication. In both designs, density is maximized using Corning’sEDGE8

™solutions with MTP-based connectivity. MTP jumpers are installed from each of the QSFP ports on the FC16-64 blade to

MTP adapter panels in an EDGE8 patch panel. Using high-density EDGE8 housings and 4-port MTP adapter panels, a full BrocadeDCX 8510-8 can be supported with one 2U EDGE8 housing, and a full Brocade DCX 8510-4 can be supported with one 1U EDGE8housing.

Point-to-Point Structured Cabling OptionsAs shown in Figure 8, from the housing at the director cabinet, MTP-terminated trunk assemblies are installed to the end equipmentcabinets and landed in MTP adapter panels in an EDGE8 housing or bracket at the end equipment (server) as well. From each MTP portin the housing, an 8-fiber MTP-to-LC harness assembly is installed and the 4xLC Uniboot legs of the assembly are installed to the SFPports at the host or storage equipment. This design would be utilized when the four SFP ports are located on the same device in nearbyproximity for clean cable management and when these ports are operating on the same fabric via a single QSFP port at the director.

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 17

Page 18: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 8 Connectivity Line Diagram for Point-to-Point Structured Cabling with 8-Fiber Harness

As most servers have a single dual-port HBA to support redundancy over separate fabrics, the typical installation requires that the (4)16GFC channels transmitting from each QSFP port on the FC16-64 blade be broken out to different/multiple servers, rather than allfour channels terminating at the same device. The LC harness legs from the design can be ordered with longer LC legs in order to splitthem between multiple devices; however this often results in messy or congested cable/jumper management at the servers.

For servers, or other end equipment, where the 4xLC ports are not located in close proximity on a single device or are being splitbetween multiple devices, a more manageable approach is to land the MTP-terminated trunk assemblies into MTP-to-LC modules,where individual LC jumpers can be used for each of the 4xLC ports, as shown in Figure 9.

FIGURE 9 Connectivity Line Diagram for Point-to-Point Structured Cabling with Module Breakouts

Cross-Connect Structured Cabling OptionsUtilizing a cross-connect design enables port replication of the SAN director ports, which in turn provides for a flexible patchinginfrastructure where any SAN director port can be connected easily to any host, storage, or switch port. In this design, the director isprecabled with a high-density solution, moving the patching functions to a central patching field, which is typically designed for jumpermanagement. By moving the patching function to this central patching area, risk of damage to director ports is eliminated as day-to-daymoves, adds, and changes (MACs) occur only at this passive patching field, and not directly at the QSFP transceiver ports. DeployingMTP trunk assemblies from the director cabinets to the central patching area is typically accomplished with high-fiber-count trunk

Corning

Cable Management Solutions for Brocade High-Density Port Blades18 53-1003738-02

Page 19: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

assemblies (rather than multiple low-fiber-count assemblies), reducing required pathway spaces and reducing installation time for thisbackbone structured cabling. With the 48-port FC16-48 blade, it is common to utilize 96-fiber trunks so that each trunk is allocated toa blade for ease of servicing the director. In the case of the FC16-64 blade, (4) 32-fiber trunks can be deployed per blade, or a 96-fiberand a 32-fiber trunk can be utilized per blade to maintain 1:1 assignment.

Design scenarios with the corresponding part numbers can be found at http://csmedia.corning.com/CableSystems//Resource_Documents/application_engineering_notes_rl/AEN152.pdf.

Data Center SystemsThe 64-Channel FC16-64 Mimic Adapter Panel available through Data Center Systems (DCS) is a 10U, modular adapter panel thatsupports 64 LC connections distributed in 16 groups, each containing 4 channels. Segments are numbered with an overlay to mapprecisely with QSFP ports and FC channels on the face of the Brocade FC16-64 blades. Located at the central access point (CAP),utilizing a DCS 10U, 8-Slot Modular Patch Panel Enclosure populated with eight DCS 64-Channel FC16-64 Mimic Adapter Panels,this solution provides a “mimic” of a fully populated DCX 8510-8 director chassis. Introducing the Mimic at the CAP improvesmanageability and mitigates risk associated with all MACs by taking management of up to 512 ports away from the active director.Converting from the 16 QSFP ports on the face of each FC16-64 blade to LC connectors required at the central patching location(CPL) can be accomplished in the following ways:

• Implementing the structured connectivity solution shown in Figure 10 provides the least amount of mated pair insertion loss.

• Quantity (2) DCS 32-channel, 96-fiber OM4 Plenum trunks terminated with (16) MTP/MPO connectors at the FC16-64blade and (32) LC-Duplex connectors at the back of the DCS 64-Channel FC16-64 Mimic Adapter Panel (Figure 11) at thecentral patching location.

• Quantity (1) DCS 64-Channel FC16-64 Mimic Adapter Panel (Figure 11).

To further enhance management, DCS offers Mimic Adapter Panels and Cassettes with color schemes to distinguish between A and Bfabrics as well as backup.

Data Center Systems

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 19

Page 20: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 10 Data Center Systems—Centralized Structured Connectivity Solution—Core Edge Topology

Data Center Systems

Cable Management Solutions for Brocade High-Density Port Blades20 53-1003738-02

Page 21: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 11 Data Center Systems 64-Channel FC16-64 Mimic Panel for DCX 8510

Methode Data Solutions GroupMethode's Fast Channel

™ Switch Connect (FCSC) provides a physical-layer, prekitted solution optimized for Brocade's FC16-64 blade.

Features include:

• A set of preconfigured multiport QSFP+ harness cable assemblies, with lengths tuned to ease installation and present anorganized and aesthetically pleasing dressed-in appearance.

• 2RU Conversion Patch Panel for routing and interconnecting the QSFP+ harnesses to the backbone trunk.

• Multifiber backbone trunk cable assembly.

Fast Channel Switch Connect maximizes channel density, space and fiber utilization, and simplicity with an elegant standards-baseddesign that also ensures a future-proof investment. The design is forward-compatible with all emerging networking-standards roadmapsand is available in a variety of kits to support a wide range of Brocade switch models and blade types.

Each QSFP+ harness is a "Y" cable that plugs into two QSFP+ ports on the FC16-64 blade, compressing two sets of four data channels(eight channels total) into a single high-capacity MTP connector on the backside of the 2RU Conversion Patch Panel. There are eightharnesses required per blade and eight backside MTP connectors, mounted on one coupler plate. The 2RU Conversion Patch Panelsupports the capacity of a fully populated 8-slot director (or two 4-slot directors) for a total of 64 harnesses and 64 backside MTPconnectors mounted to 8-coupler plates that provide connectivity to 512 channels.

Methode Data Solutions Group

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 21

Page 22: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 12 2 x 1 MTP Conversion Harness

FIGURE 13 Fast Channel Switch Connect Conversion Cabling Kit with a Premeasured Cabling Harness for the DCX 8510

Using 2 x 1 MTP conversion harnesses as shown above, Fast Channel Switch Connect can reduce cabling time per port up to50 percent when integrated with LC connection cabling options.

Equipment RequirementsThe following items are required to implement patch-panel connectivity using the Brocade DCX 8510 with eight FC16-64 port blades:

• One “QCB-xxxx44” FAST CHANNEL-SWITCH CONNECT kit per blade. Each kit contains eight 2x1 MTP conversion harnesscables (with custom lengths to minimize cable slack). A fully populated DCX 8510 therefore requires eight of these kits,providing 64 harnesses total.

• One 64-port MTP-MTP FAST CHANNEL-SWITCH CONNECT Conversion Patch Panel.

• Roll of Velcro and scissors or precut Velcro cable wraps.

Methode Data Solutions Group

Cable Management Solutions for Brocade High-Density Port Blades22 53-1003738-02

Page 23: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

• Labeling kit.

Cabling SolutionsOnce the cable labeling scheme has been defined as described in Establishing a Naming Scheme on page 16, label the ports on theMTP patch panel using the cable-to-port mapping table listed in Appendix A. It is important to map the DCX 8510 slot and port numberto the patch panel/shelf/port number on the MTP patch panel.

An optimal solution uses custom length cabling with cable lengths that have been premeasured to fit the distance from the QSFP port tothe corresponding patch panel connection.

Alternatively, 1- or 2-meter cables can be used to connect the director ports to the ports on the patch panel if the patch panel is placeddirectly above or below the DCX. If this is not possible and the patch panel is at the top of the rack, a 3-meter length cable isrecommended.

Install the patch panels below the cable comb with a 1-RU gap between the cable comb and the patch panel. For additional details, referto the installation guide that ships with the patch panels.

R&MR&M's high-density structured Netscale solutions support up to 120 ports per rack unit. The Netscale product allows FC16-64 bladesto be deployed in either direct interconnect implementations or in a port replication fashion. Using Netscale with MTP-MTP cableassemblies and 18-port MTP cassettes, a Brocade DCX 8510-8 fully populated with FC16-64 blades can be supported with two 1UNetscale housings, and a DCX 8510-4 can be mapped with just a single 1U housing. For deployments using breakout cabling toconnect 4xLCs to each QSFP, the required rack space increases to 5U and 3U, respectively.

FIGURE 14 A Sample Configuration of a 3U Netscale Housing with 12- and 18-Port LC-to-MTP Modules and a Netscale RearCabling Manager

R&M

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 23

Page 24: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Port Replication Structured Cabling OptionsReplicating ports within an optical cross-connect patch panel (outlined with a dotted line in Figure 15) provides flexibility in connectingany Brocade DCX 8510 blade port to any HBA, switch, or storage port within the data center, allowing the use of any desired linkconfiguration. The cross-connection allows:

• Meshing of switch ports

• Clean mixing of SFP+ to SFP+, SFP+ to QSFP, and QSFP to QSFP links

• Ease of documentation

FIGURE 15 32-Gbps Connectivity with SFP+ Port Replication at a Cross-Connect

This approach precables the DCX 8510 with high-density MTP-MTP assemblies, moving the patching location away from the blade tothe cross-connect. The heavy usage of cross-connect panels makes it critical to automate the documentation. When deployed with "low-density" 12-port LC-to-MTP modules shown in Figure 16, Netscale can be equipped with R&MinteliPhy, yielding a reduced density of80 ports per rack unit. The inteliPhy system integrates RFID sensors into the individual Netscale modules, which read the ID written intothe RFID tags on the LC jumpers (Figure 16).

FIGURE 16 Netscale 18-Port LC-to-MTP Module (Left), 12-Port LC-to-MTP Module with Integrated R&MinteliPhy RFID Sensor Bar(Center), and LC Push-Pull Uniboot Connector with Integrated RFID Tag (Right)

In a 16G Fibre Channel deployment with the Brocade DCX 8510,high-fiber-count MTP-terminated trunk cables enable simplification ofcabling. Permanent structured cabling links using these MTP-based trunks create connector patching fields at each end. Then short LCjumpers or LC-MTP fan-out assemblies make the connection from the patch field to the SFP+ transceivers at the servers or storagedevices. The patch-panel field with the Netscale housing allows the end device to be connected to any HBA port across multiple serversbecause the devices terminate at the patch-panel field.

R&M

Cable Management Solutions for Brocade High-Density Port Blades24 53-1003738-02

Page 25: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Direct Interconnect Structured Cabling ApproachSome links may not require the flexibility of having a cross-connect, in which case a direct interconnect may be deployed. In this situation,the structured cabling (MTP trunk) is still terminated inside the Netscale housing at the network equipment. An interconnect using anMTP jumper from the MTP cassette, such as in Figure 17, connects directly to the SAN director.

FIGURE 17 Netscale 8-Port MTP Cassette (Left) and 12-Port MTP Cassette with Integrated R&MinteliPhy RFID Sensor Bar (Right)

Figure 18 shows an FC16-64 interconnect link between a Brocade DCX 8510-8 and servers. The MTP jumpers are installed toQSFP+ transceivers in the FC16-64 blade and lead to MTP cassettes in a Netscale housing. These MTP cassettes are then connectedto LC-to-MTP modules within another housing via MTP trunk cables. Once fully cabled, this Netscale housing represents the "remote"16G ports for the DCX 8510-8. These dedicated Netscale housings should ideally be located above the equipment whose cabling theymanage.

FIGURE 18 Connectivity Schematics for Direct Interconnect Structured Cabling with MTP Cassette and LC-to-MTP Module

R&M

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 25

Page 26: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

DCX 8510 Cabling Installation (FrontSide, Director Ports to Patch Panel)

• Cabling Installation (Back Side, from Devices to Patch Panel)....................................................................................................... 27

1. For a DCX 8510-8 chassis with vertically mounted blades, start cabling from the bottom QSFP port group (e.g. ports 0–3),working up the blade to the top QSFP port (60–63). In this way, cables can be installed on top of the waterfall as the cablesdrop down, rather than trying to work below the cascading cables. Similarly, for a DCX 8510-4 with horizontally mountedblades, start at the right and work to the left for cabling that will be routed on the right side.

2. Bundle the cables using Velcro cable wraps in groups of eight to match the ASIC or trunk boundaries (0–31, 32–63). This willfacilitate servicing the system through easy identification of the cable path.

3. Work up to the top port.

4. Connect each cable to an MPO/MTP patch panel port using the numbering schema defined in Appendix A.

5. If a different methodology is chosen, it is important to be consistent across all port blades and patch panel ports. This willminimize the confusion as to which director ports are allocated to which MPO/MTP patch panel ports. Allocate 30centimeters(12inches) of slack at the patch panel to enable the patch panel’s top and middle shelf to be raised into the up position forservicing.

6. Route the cables down to the bottom of the DCX 8510 chassis (8-slot) and then to the left/right and to the cable managementarea at the side of the enclosure/rack and then down. If using a cabling harness, all harnesses/cables are routed straight downand into the patch panel, reducing the cable management required on the sides of the rack. On a 4-slot director chassis, cablescan be routed to the right of the chassis (Figure 9 on page 18).

NOTEOn an 8-slot director, do not route cables from Slot 1-4 toward the right since this could cause the fiber cables to bedamaged if ICL cables are used in the configuration.

Cable Management Solutions for Brocade High-Density Port Blades26 53-1003738-02

Page 27: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 19 256-Port Wrapped/Bundled and Completed Cabling Solution

Cabling Installation (Back Side, from Devices to PatchPanel)When connecting cables from outside devices to the backside of the patch panel, the MPO cables can be connected to the back of thepatch panel, paying attention to the defined cable number schema (refer to Appendix B and Appendix C).

Cabling Installation (Back Side, from Devices to Patch Panel)

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 27

Page 28: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

FIGURE 20 Device–to–Patch-Panel Trunk Cabling

NOTEAs a best practice, cables from the same vendor should be used when implementing a trunked cabling solution.

Cabling Installation (Back Side, from Devices to Patch Panel)

Cable Management Solutions for Brocade High-Density Port Blades28 53-1003738-02

Page 29: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Servicing High-Density Solutions• Connecting a Cable to an Empty QSFP..................................................................................................................................................29• Removing a Cable from a Populated QSFP..........................................................................................................................................29

When servicing during an anomaly due to cable density, identifying and servicing individual fiber cables at the port level can be achallenge. The QSFP transceivers used in the FC16-64 port blade are fitted with a pull-tab to aid in installation and removal. Thefollowing steps will ease the servicing process.

Connecting a Cable to an Empty QSFP1. Remove the QSFP optic from the port. Hold the QSFP pull-tab firmly and gently pull the QSFP away from the connected port.

2. Verify that the chosen optical cable supports QSFPs.

3. Connect the cable to the QSFP.

4. Insert the QSFP into the port. Hold the pull-tab on the QSFP firmly, and insert the QSFP into the port, and slide it back into theport until the transceiver clicks (locks into place).

Removing a Cable from a Populated QSFP1. Remove the QSFP from the port.

a. Make sure that the patch cable is not wrapped around the pull-tab.

b. Loosen any cable ties used for holding the cables in place.

c. Hold the QSFP pull-tab firmly, and gently pull the QSFP away from the connected port.

2. Disconnect the cable from the QSFP.

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 29

Page 30: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Best Practices for Managing the Cabling• During Installation..............................................................................................................................................................................................30• Daily Practices.....................................................................................................................................................................................................31• Summary...............................................................................................................................................................................................................31

Whether implementing, upgrading, or maintaining cabling in the data center, establish a set of guidelines that are thoroughly understoodand supported by the staff. Here are some cable management pointers.

During Installation• Avoid overbundling the cables or placing multiple bundles on top of each other, which can degrade the performance of the

cables underneath.

• Keep fiber and copper runs separated. The weight of the copper cables can crush fiber cables that are placed underneath.

• Consider using cables that are resistant to bend loss.

• Avoid mounting cabling components in locations that block access to other equipment (power strip or fans) inside and outsidethe racks.

• Keep all cable runs under 90 percent of the maximum distance supported for each media type as specified in the relevantstandard. This extra headroom is for the additional patch cables that will be included in the end-to-end connection.

• Install higher cable types (OM3 or OM4 only) that will meet current and future application requirements.

• Cabling installations and components should be compliant with industry standards.

• Do not stress the cable by doing any of the following:

– Applying additional twists– Pulling or stretching beyond its specified pulling load rating– Bending it beyond its specified bend radius, and certainly not beyond 90 degrees– Creating tension in suspended runs– Stapling or applying pressure with cable ties

• Avoid routing cables through pipes and holes. This may limit additional future cable runs.

• Label cables with their destination at every termination point (this means labeling both ends of the cable).

• Test every cable as it is installed and terminated. It will be difficult to identify problem cables later.

• Locate the main cabling distribution area nearer the center of the data center to minimize cable distances.

• Do not route cables such that they block equipment cooling fans and restrict airflow.

• Use thin and high-density cables wherever possible, allowing more cable runs in tight spaces. Ensure that the selected cablesmeet standards specifications.

• Dedicate outlets for terminating horizontal cables; that is, allocate a port in the patch panel for each horizontal run.

• Include sufficient vertical and horizontal managers in your design; future changes may involve downtime as cables are removedduring the changes.

• Utilize modular cabling systems to map ports from equipment with high-density port counts, as described in CableManagement Setup and Configuration on page 17.

Cable Management Solutions for Brocade High-Density Port Blades30 53-1003738-02

Page 31: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Daily Practices• Avoid leaving loose cables on the floor that create a major safety hazard. Use the horizontal, vertical, or overhead cable

managers.

• Avoid exposing cables to direct sunlight and areas of condensation.

• Do not mix different cable types within a bundled group.

• Remove abandoned cables that can restrict air flow and contribute to possible increases in operational temperatures that canaffect the longevity of the system.

• Keep some spare patch cables. The types and quantity can be determined from the installation and projected growth. Try tokeep all unused cables bagged and capped when not in use.

• Use horizontal and vertical cable guides to route cables within and between racks. If “cable spool” devices are used in cablemanagers to avoid kinks and sharp bends in the cable, use caution not to wrap patch cords around these spools like a hose on ahose reel.

• Document all cabling components and their linkage between components, and make sure that this information is updated on aregular basis. The installation, labeling, and documentation should always match.

• Use the correct length patch cable, leaving some slack at each end for end device movements.

• Bundle cables together in groups of relevance (for example, ISL cables and uplinks to core devices), as this will easemanagement and troubleshooting.

• When bundling or securing cables, use Velcro-based cable wraps every 1 to 2 meters. Avoid using zip ties as they applypressure on the cables.

• Avoid routing cables over equipment and other patch panel ports. Route below or above and into the horizontal cable managerfor every cable.

• Maintain the cabling documentation, labeling, and logical/physical cabling diagrams.

SummaryAlthough cabling represents less than 10 percent of the overall data center network investment, it can be expected to outlive mostnetwork components and be the most difficult and potentially costly component to replace. When purchasing the cabling infrastructure,consider not only the initial implementation costs, but also the subsequent costs. Understand the full lifecycle and study local industrytrends to arrive at the right decision for your environment.

Choose the strongest foundation to support present and future network technology needs—comply with TIA/ISO cabling standards.Build in additional capacity, as it is much easier to install now than later. Use higher bandwidth grades of cabling to postpone having tore-cable as technologies advance. The cabling itself calls for the right knowledge, the right tools, patience, a structured approach, andmost of all, discipline. Without discipline, it is common to see complex cabling “masterpieces” quickly get out of control, leading toincreased support costs and increased downtime.

Since each environment is different, there is no single solution that will meet all of your cable management needs. Following theguidelines and best practices highlighted in this solution design guide will help provide you with the information required to successfullydeploy a cabling infrastructure in your data center.

Summary

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 31

Page 32: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Appendix A: Cable-to-Port MappingNOTEFor easy identification of devices, print and paste the following table on the rack door or in a log book located near therack.

Cable Management Solutions for Brocade High-Density Port Blades32 53-1003738-02

Page 33: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 33

Page 34: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Appendix B: DCS-MTP–to–MTP-PortMapping

Cable Management Solutions for Brocade High-Density Port Blades34 53-1003738-02

Page 35: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Appendix C: DCS-MTP–to–LC-PortMapping

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 35

Page 36: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Appendix D: Equipment List

Director ChassisChassis Description

Brocade DCX 8510-8 Built for large enterprise networks, the 14U Brocade DCX 8510-8 has 8 vertical blade slots to support up to 51216Gb Fibre Channel ports.

Brocade DCX 8510-4 Built for midsize networks or edge connectivity in larger networks, the 8U Brocade DCX 8510-4 has 4 horizontalblade slots to support up to 256 16Gb Fibre Channel ports.

Patch Cables for QSFP ConnectionsThe QSFP patch cables listed below are for use in the FC16-64 port blade. These cables are used to connect end devices to patchpanel ports and to connect ports between two local patch panels. The cable part numbers are provided as a reference only and have notbeen tested or qualified by Brocade.

Type Description Length Corning P/N (Type B Polarity Assemblies part numbers listed below. Only one Jumper neededwith EDGE8.)

Device (QSFP) to Device(QSFP) (MTP non-pinned/non-pinned)

Patch Panel to Device (QSFP)(MTP pinned/non-pinned)

Patch Panel to Patch Panel(QSFP) (MTP pinned/non-pinned)

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

1 m JE6E608QE8-NB001M JE6E608QE8-NB001M JE6E608QE8-NB001M

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

3 m JE6E608QE8-NB003M JE6E608QE8-NB003M JE6E608QE8-NB003M

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

20 m JE6E608QE8-NB020M JE6E608QE8-NB020M JE6E608QE8-NB020M

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

50 m JE6E608QE8-NB050M JE6E608QE8-NB050M JE6E608QE8-NB050M

Device (QSFP) to Device(SFP+) (MTP non-pinned toLC)

Patch Panel to Device (SFP+)(MTP non-pinned to LC)

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

1 m HE67908QPH-JB001M HE67908QPH-JB001M

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

3 m HE67908QPH-JB003M HE67908QPH-JB003M

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

20 m HE67908QPH-JB020M HE67908QPH-JB020M

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

50 m HE67908QPH-JB050M HE67908QPH-JB050M

Cable Management Solutions for Brocade High-Density Port Blades36 53-1003738-02

Page 37: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Type Description Length R&M P/N (Type B Polarity Assemblies part numbers listed below)

Device (QSFP) to Device(QSFP) (both MTP ends non-pinned)

Device (QSFP) to Patch Panel(non-pinned to pinned)

Patch Panel to Patch Panel(both MTP ends pinned)

QSFP-QSFP

OM4 – QSFP (MTP) to QSFP(MTP) optical cable

2 m KFA-C3777329001 KFA-C3777361001 KFA-C3777393001

QSFP-QSFP

OM4 – QSFP (MTP) to QSFP(MTP) optical cable

3 m KFA-C3777337001 KFA-C3777369001 KFA-C3777401001

QSFP-QSFP

OM4 – QSFP (MTP) to QSFP(MTP) optical cable

20 m KFA-C3777345001 KFA-C3777377001 KFA-C3748339001

QSFP-QSFP

OM4 – QSFP (MTP) to QSFP(MTP) optical cable

50 m KFA-C3777353001 KFA-C3777385001 KFA-C3748383001

Device (QSFP) to Device(SFP+) or Patch Panel toDevice (SFP+) (non-pinned toLC)

QSFP-4xSFP

OM4 – QSFP (MTP) to 4SFP+ (LC) optical fiber

2 m KFA-C3777425001

QSFP-4xSFP

OM4 – QSFP (MTP) to 4SFP+ (LC) optical fiber

3 m KFA-C3777433001

QSFP-4xSFP

OM4 – QSFP (MTP) to 4SFP+ (LC) optical fiber

20 m KFA-C3777441001

QSFP-4xSFP

OM4 – QSFP (MTP) to 4SFP+ (LC) optical fiber

50 m KFA-C3777449001

Type Description Length Amphenol P/N Methode P/N

QSFP-QSFP OM4 - QSFP (MTP) to QSFP (MTP)optical cable

1 m 943-99609-10001 FT-30020DD123D 12371C001M

QSFP-QSFP OM4 - QSFP (MTP) to QSFP (MTP)optical cable

3 m 943-99609-10003 FT-30020DD123D 12371C003M

QSFP-QSFP OM4 - QSFP (MTP) to QSFP (MTP)optical cable

20 m 943-99609-10020 FT-30020DD123D 12371C020M

QSFP-QSFP OM4 - QSFP (MTP) to QSFP (MTP)optical cable

50 m 943-99609-10050 FT-30020DD123D 12371C050M

QSFP-4xSFP OM4 - QSFP (MTP) to 4 SFP+ (LC) opticalcable

1 m 943-99402-10001 FH-30000BD121Y 01570C001M

QSFP-4xSFP OM4 - QSFP (MTP) to 4 SFP+ (LC) opticalcable

3 m 943-99402-10003 FH-30000BD121Y 01570C003M

QSFP-4xSFP OM4 - QSFP (MTP) to 4 SFP+ (LC) opticalcable

20 m 943-99402-10020 FH-30000BD121Y 01570C020M

QSFP-4xSFP OM4 - QSFP (MTP) to 4 SFP+ (LC) opticalcable

50 m 943-99402-10050 FH-30000BD121Y 01570C050M

NOTEAdditional pinning/polarity configurations are available. For design assistance, contact themanufacturer.

Type Description Length Molex P/N TE Connectivity P/N Wave2Wave P/N

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

1 m 106283-7001 MPB-NCNCJ40001M-NN 50-8120P-1M

Patch Cables for QSFP Connections

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 37

Page 38: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Type Description Length Molex P/N TE Connectivity P/N Wave2Wave P/N

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

3 m 106283-7003 MPB-NCNCJ40003M-NN 50-8120P-3M

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

20 m 106283-7020 MPB-NCNCJ400020M-NN 50-8120P-20M

QSFP-QSFP

OM4 - QSFP (MTP) to QSFP(MTP) optical cable

50 m 106283-7050 MPB-NCNCJ400050M-NN 50-8120P-50M

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

1 m 106283-5401 MPS-NCLCJ40001M-NC 51-8080P-1M

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

3 m 106283-5403 MPS-NCLCJ40003M-NC 51-8080P-3M

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

20 m 106283-5407 MPS-NCLCJ400020M-NC 51-8080P-20M

QSFP-4xSFP

OM4 - QSFP (MTP) to 4 SFP+(LC) optical cable

50 m 106283-TBD MPS-NCLCJ400050M-NC 51-8080P-50M

NOTEVerify the appropriate cable number and description with the cable manufacturer before placing an order.

Patch PanelsVendor Type Rack Unit Number of Ports Part Number

CommScope MPO-MPO 1U Up to 3 x 24 MPO panel adapters 760136473

Vendor Corning

Bill of Materials for Figure 8 on page 18

Item Number Part Number Description

1 JE6E608QE8-NBxxxF EDGE8 (OM4), MTP (non-pinned) to MTP (non-pinned) Jumper, TIA-568 Type-B.

2 EDGE8-CP32-V3 EDGE8 32-Fiber MTP Adapter (4 port).

EDGE8 32-Fiber MTP Adapter.

3 GE5E508QPNDDUxxxF EDGE8 Solution Trunk Cable, 50 µm multimode (OM4), MTP Connector (pinned) toMTP Connector (pinned), 8 Fibers, with 33/33 inch legs, pulling grip one side, xxx ft.

NOTETrunks are available in fiber counts from 8 to 288fibers.

4 HE67908QPH-KBxxxF EDGE8, 8-fiber Harness, 50 µm multimode (OM4), MTP(non-pinned) to LCUniboot, xxx ft., 24-in. LC legs.

Vendor Corning

Bill of Materials for Figure 9 on page 18

Item Number Part Number Description

1 JE6E608QE8-NAxxxF EDGE8, 8-Fiber MTP Jumper, (OM4), MTP (non-pinned) to MTP (non-pinned),TIA-568 Type-A polarity, xxx ft.

2 EDGE8-CP32-V3 EDGE8, 32-Fiber MTP Adapter Panel, 50 µm multimode (OM4/OM3); mounts inEDGE8 Housings (example: EDGE8-02U).

Patch Panels

Cable Management Solutions for Brocade High-Density Port Blades38 53-1003738-02

Page 39: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Vendor Corning

Bill of Materials for Figure 9 on page 18

Item Number Part Number Description

NOTEPanels are available in 4 ports.

3 GE5E508QPNDDUxxxF EDGE8 Solutions Trunk Cable, 50 µm multimode (OM4), MTP Connector (pinned)to MTP Connector (pinned), 8 Fibers, 33/33 inch legs, pulling grip one side, xxx ft.

NOTETrunks are available in fiber counts from 8 to 288fibers.

4 ECM-UM08-05-E6Q-ULL EDGE8 Solutions Ultra Low Loss (OM4) Module, 8 F, LC Duplex to MTP (non-pinned).

5 797902QD120xxxF Pretium EDGE® Solutions Jumper, 2 F, LC Uniboot to LC Uniboot, Riser, 50 µmmultimode (OM4), xxx ft.

Vendor Type Rack Unit Number of Ports Part Number

Data Center Systems Enclosure: 10U x 8 Slot x 15.5" D ECOModular Enclosure 1-4, 9-12 Overlay

10U Up to 512 7510-0101-010

MTP/MPO-LC Panel: 10U-8 64-ChannelBlack LC-Quad ECO Modular AdapterPanel FC16-64 QSFP 0-15/FC 00-63

10U 64 7110-0118-000

Modular Cassette: 10U-8 64-ChannelBlack LC-Quad OM4 ECO ModularCassette FC16-64 QSFP 0-15/FC00-63

10U 64 7310 0105-000

Vendor Type Rack Unit Number of Ports Part Number

Methode MPO-MPO Conversion Patch Panel (frontand rear wire managers, blank couplerplates and mounting rails)

2U Up to 64 (MTP) QS-108111000

MTP 2 x 1 MTP—Harness Kit DCX8510-8 Chassis

N/A 8 QSFP ports(1 blade)

QCB-120144

MTP 2 x 1 MTP—Harness Kit DCX8510-4 Chassis (1&2, bottom 2 blades/slots)

N/A 8 QSFP ports(1 blade)

QCB-220244

MTP 2 x 1 MTP—Harness Kit DCX8510-4 Chassis (3&4, top 2 blades/slots)

N/A 8 QSFP ports(1 blade)

QCB-220344

Vendor Description Rack Unit Number of Ports Part Number

R&M

Netscale Housing, accepting 20 modulesor cassettes

3U 828644

Netscale Housing, accepting 5 modules orcassettes

1U 828643

Rear Cabling Manager (one per module orcassette)

827348

LC-to-MTP module, OM4 18 832182

LC-to-MTP module, OM4, inteliPhycompatible

12 832181

Patch Panels

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 39

Page 40: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Vendor Description Rack Unit Number of Ports Part Number

MTP cassette 18 832192

MTP cassette, inteliPhy compatible 12 832191

inteliPhy sensor bar for one individualNetscale module or cassette

824369

Control unit PCU 824370

RFID clips for LC jumpers, 10 pair 827357

Vendor Type Rack Unit Number of Ports Part Number

Wave2Wave MPO-MPO Conversion Patch Panel 1U 5 slots 69EVO-1U00-5v2 1U00-5v2

MPO-MPO Conversion Patch Panel (frontand rear wire managers, blank couplerplates and mounting rails)

2U 14 slots 69EVO-1U00-5v2 1U00-5v2

Custom Director TrunksVendor Type Rack Unit Number of Ports Part Number

Data Center Systems Trunk: 64-Fiber DCX FC16-64 0-31OM4 Plenum Trunk LC-MTPf xxx Feet

N/A 32 ports TB1964F5-3236-XXXF

Trunk: 64-Fiber DCX FC16-64 32-63OM4 Plenum Trunk LC-MTPf xxx Feet

N/A 32 ports TB2064F5-3236-XXXF

Velcro Cable WrapsUse Velcro-based tie wraps instead of plastic zip ties or metal tie wraps. Over-tightening plastic zip ties or metal tie wraps can causesheathing and can overstress the patch cables, causing signal loss and impacting performance. Velcro cable ties come in a roll or inpredetermined lengths. Bundle groups of relevant cables with Velcro cable ties as you install the cables, which will help you identifycables later and facilitate better overall cable management.

LabelersLabelers are used to print sticky labels for devices and cables. Here are some considerations when you choose a hand-held labeler:

• The labeler should be capable of operating with batteries.

• The labeler can print labels on smooth, textured, flat, and curved surfaces.

• The actual label material should resist solvents, chemicals, and moisture.

• Labels are durable and resist fading.

• Adhesive should be long-lasting.

If you choose a labeler with bundled software, install it on a client workstation. You can then customize labels, print labels in batches, andstore the formats for future printing.

Custom Director Trunks

Cable Management Solutions for Brocade High-Density Port Blades40 53-1003738-02

Page 41: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Appendix E: FC16-64 SupportedConnection Distances

Connection Type Speed Multimode Max Distance Comments

OM3 OM4

QSFP<>QSFP (0-dB connector loss) 16 Gbps 100 m 125 m Assumes point-to-point connection withoutpatch panel.

QSFP<>SFP (1-dB connector loss) 16 Gbps 66 m 100 m 1 dB represents the maximum likely signalloss from a breakout cable.

QSFP<>SFP (1.5-dB connector loss) 8 Gbps 150 m 190 m Uses industry-standard figure for 1.5-dBsignal loss with a patch panel.

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 41

Page 42: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Appendix F: Cable Management andPatch Panel VendorsAmphenol

Phone: 1-510-209-6831

www.amphenol.com

www.cablesondemand.com

CommScope

Phone: 1-800-344-0223

E-mail: mailto://[email protected]

http://www.commscope.com/Product-Catalog/#market-enterprise

Corning

Phone: 1-800-743-2671

www.corning.com/opcomm

Data Center Systems

Phone: 1-972-620-4997

E-mail: mailto://[email protected]

http://datacentersys.com

Methode Data Solutions Group

Phone: 1-888-446-9175

E-mail: mailto://[email protected]

www.methode-datasolutions.com

Molex

Phone: 1-800-833-3557

E-mail: mailto://[email protected]

E-mail for quotes outside the U.S.: mailto://[email protected]

www.arrow.com (contact your local branch if you are already an Arrow customer)

R&M

Phone: 1-408-945-6626

E-mail: mailto://[email protected]

https://www.rdm.com/usa_en/Markets/Data-Center

TE Connectivity

Phone: 1-800-342-5267

E-mail: mailto://[email protected]

Cable Management Solutions for Brocade High-Density Port Blades42 53-1003738-02

Page 43: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

http://www.te.com/

Wave2Wave Solution Corporation

Phone: 1-877-223-2296

E-mail: mailto://[email protected]

www.wave-2-wave.com

Cable Management Solutions for Brocade High-Density Port Blades53-1003738-02 43

Page 44: Cable Management Solutions for Brocade High-Density … · Cross-Connect Structured Cabling Options ... Brocade DCX 8510 and X6 ... To help ensure a complete solution, Brocade partners

Appendix G: Reference Materials• High-Density Fiber Adapter Panel Shelf Instructions(CommScope Part Number:860499748)

• TIA-568-C.0—Generic Telecommunications Cabling for Customer Premises

• TIA-568-C.3—Optical Fiber Cabling Components Standard

Cable Management Solutions for Brocade High-Density Port Blades44 53-1003738-02