cables and conduit fittings b

21
1. Cable Gland for Armoured Cable DAC Series B2/ 21 2. Cable Gland for Non-Armoured Cable DNA Series B3/ 21 3. Cable Gland for Non-Armoured Cable DNAF Series B4/ 21 4. Barrier Cable Gland for Armoured Cable DACB Series B5/ 21 5. Barrier Cable Gland for Non-Armoured Cable DNAB Series B6/ 21 6. Barrier Cable Gland for Non-Armoured Cable DNAFB Series B7/ 21 7. Conductor Bushing DCB Series B8/ 21 8. Accessories for Cable Glands B9/ 21 Lock Nut LNB Series Earth Tag DET Series Shroud SPV Series Gasket Ring GK Series 9. Stopping Plug DSP Series B10/ 21 10. Reducer and Adaptor (Enlarger) DRH, DAT Series B11/ 21 11. Union and Elbow Union DUN, DUNL Series B14/ 21 12. Sealing Fitting DYS, DYK, DYD Series B15/ 21 13. Sealing Compound and Fiber SCF-ALLCO ® B16/ 21 14. Sealing Compound SCFR B17/ 21 (Resin, Hardener and Fiber) 15. Flexible Coupling DFC Series B18/ 21 16. Drain Fitting DDF Series B19/ 21 17. Clamp and Back clamp CL, CLB Series B20/ 21 18. Bracket Clamp BC Series B20/ 21 19. PG1 Premium Grade B21/ 21 Performance Grease CABLES AND CONDUIT FITTINGS B We reserve the right to make alterations to the technical data, weights, dimensions, designs and products available without notice. The illustrations cannot be considered binding.

Upload: others

Post on 06-May-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CABLES AND CONDUIT FITTINGS B

1. Cable Gland for Armoured Cable DAC Series B2/ 21

2. Cable Gland for Non-Armoured Cable DNA Series B3/ 21

3. Cable Gland for Non-Armoured Cable DNAF Series B4/ 21

4. Barrier Cable Gland for Armoured Cable DACB Series B5/ 21

5. Barrier Cable Gland for Non-Armoured Cable DNAB Series B6/ 21

6. Barrier Cable Gland for Non-Armoured Cable DNAFB Series B7/ 21

7. Conductor Bushing DCB Series B8/ 21

8. Accessories for Cable Glands B9/ 21 Lock Nut LNB Series Earth Tag DET Series Shroud SPV Series Gasket Ring GK Series

9. Stopping Plug DSP Series B10/ 21

10. Reducer and Adaptor (Enlarger) DRH, DAT Series B11/ 21

11. Union and Elbow Union DUN, DUNL Series B14/ 21

12. Sealing Fitting DYS, DYK, DYD Series B15/ 21

13. Sealing Compound and Fiber SCF-ALLCO® B16/ 21

14. Sealing Compound SCFR B17/ 21

(Resin, Hardener and Fiber)

15. Flexible Coupling DFC Series B18/ 21

16. Drain Fitting DDF Series B19/ 21

17. Clamp and Back clamp CL, CLB Series B20/ 21

18. Bracket Clamp BC Series B20/ 21

19. PG1 Premium Grade B21/ 21

Performance Grease

CABLES AND CONDUIT FITTINGS B

We reserve the right to make alterations to the technical data, weights, dimensions, designs and products available without notice. The illustrations cannot be considered binding.

Page 2: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B2/21

B

The DAC cable glands are suitable for used in zone 1, 2 and zone 21, 22 hazardous areas to enable direct insertion of SWA-steel wire armoured cable into Ex d equipment or enclosure.

Cable Fitting: Cable Gland for Armoured Cable, DAC Series

Application

Body, gland nut : Brass (Nickel-plated brass as option)Thread seal : Nylon (PA6) (For metric threads only)

Technical Data

DAC / - -Series Body Threads Option

S Small NI Nickel-M Medium platedL Large brass

Thread seal

Body(Entry thread)

Neoprene innersealing ring

Clamping cone-A

Inner gland nut

Neoprene outersealing ring

End cap

Outer gland nut

Sealing washer

Clamping cone-B

Bush sleeve

Flameproof/ Increased Safety and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Cat. No.Entries Threads

(Male)Cable Diameter Armour

WireDia.

Dimension in mm. Approx.Weight(kgs.)

ShroudRef.Inner 'd1' Outer 'd2'

l a AcrossCorners

AcrossFlatsMetric NPT Min - Max Min - Max

DAC/S -M0 - M16x1.5 -3.0-8.6 6.0-13.4 0.9 65.0 15.0 26.5 24.0 0.13 SPV-24DAC/S -M1 - M20x1.5 -

DAC/S -N1 - - 1/2” 65.0 19.8 26.5 24.0DAC/M -M1 - M20x1.5 - 6.1-11.9 9.5-16.0 0.9/1.25 65.0 15.0 26.5 24.0 0.14 SPV-24DAC/M -N1 - - 1/2” 65.0 19.8 26.5 24.0DAC/L -M1 - M20x1.5 -

6.5-14.3 12.5-20.9 0.9/1.2573.0 15.0 35.0 31.75 0.20

SPV-31DAC/S -M2 - M25x1.5 - 0.26DAC/L -N1 - - 1/2” 73.0 19.8 35.0 31.75 0.20DAC/S -N2 - - 3/4” 73.0 20.1 35.0 31.75 0.26DAC/M -M2 - M25x1.5 -

11.1-20.2 16.9-26.2 1.25/1.681.0 15.0 42.0 38.1 0.37

SPV-38DAC/S -M3 - M32x1.5 -DAC/M -N2 - - 3/4” 81.0 20.1 42.0 38.1 0.39DAC/S -N3 - - 1” 81.0 25.0 42.0 38.1DAC/M -M3 - M32x1.5 -

17.0-26.5 22.0-31.9 1.6/2.092.0 15.0 49.0 44.4 0.60

SPV-44DAC/S -M4 - M40x1.5 - 0.65DAC/M -N3 - - 1” 92.0 25.0 49.0 44.4 0.60DAC/S -N4 - - 1-1/4” 92.0 25.6 49.0 44.4 0.65DAC/M -M4 - M40x1.5 -

22.0-32.5 26.0-38.5 1.6/2.096.0 15.0 56.0 50.8

0.80 SPV-50DAC/S -M5 - M50x1.5 -DAC/M -N4 - - 1-1/4” 96.0 25.6 56.0 56.0DAC/S -N5 - - 1-1/2” 96.0 26.0 56.0 56.0DAC/M -M5 - M50x1.5 29.5-38.1 35.0-46.8 1.8/2.5 98.0 15.0 63.0 57.1 0.90 SPV-57DAC/M -N5 - 1-1/2” 98.0 26.0 63.0 57.1DAC/L -M5 - M50x1.5 -

35.6-44.0 38.0-50.1 1.8/2.598.0 15.0 70.0 63.5

1.00 SPV-63DAC/S -M6 - M63x1.5 -DAC/L -N5 - - 1-1/2” 98.0 26.0 70.0 63.5DAC/S -N6 - - 2” 98.0 26.9 70.0 63.5DAC/M -M6S - M63x1.5 -

39.0-44.0 47.0-55.0 1.8/2.599.0 15.0 84.0 76.2

1.35 SPV-76DAC/S -M7S - M75x1.5 -DAC/M -N6S - - 2” 99.0 26.9 84.0 76.2DAC/S -N7S - - 2-1/2” 99.0 39.9 84.0 76.2DAC/M -M6L - M63x1.5 -

44.1-54.0 55.1-65.0 1.8/2.599.0 15.0 84.0 76.2

1.35 SPV-76DAC/S -M7L - M75x1.5 -DAC/M -N6L - - 2” 99.0 26.9 84.0 76.2DAC/S -N7L - - 2-1/2” 99.0 39.9 84.0 76.2

Ordering Requirements

Catalogue Number Logic

Brass Nickel-plated brass

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db eb IIC Gb Ex tb IIIC Db IP66Certificate TÜV CY 18 ATEX 0206101 UT Rating Temperature class of enclosure to which will be connected.Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -20oC to +75oCIndex of Protection IP66

Note: Cables for fixed installations shall have flame propagation characteristics which enable them to withstand the tests according to IEC 60332-1-2 or IEC 60332-3-22.

Page 3: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B3/21

B

Thread seal

Body(Entry thread)

Neoprene innersealing ring

Gland nut

Sealing washer

Cable Fitting: Cable Gland for Non-Armoured Cable, DNA Series

Flameproof/ Increased Safety and Dust protection by enclosureZone 1 & 2 _ 21 & 22

The DNA cable glands are suitable for used in zone 1, 2 and zone 21, 22 hazardous areas to enable direct insertion of normal non-armoured cable into Ex d equipment or enclosure.

Application

Body, gland nut : Brass (Nickel-plated brass as option)Thread seal : Nylon (PA6) (For metric threads only)

DNA / - -Series Body Threads Option

S Small NI Nickel-M Medium platedL Large brass

Cat. No.Entries Threads

(Male)Cable Dia.Outer ‘d’

Dimension in mm. Approx.Weight(kgs.)

ShroudRef.l a Across

CornersAcrossFlatsMetric NPT Min - Max

DNA/S -M0 - M16x1.5 -3.0-8.6 25.0 15.0 26.5 24.0 0.06

SPV-24DNA/S -M1 - M20x1.5 - 0.07DNA/S -N1 - - 1/2” 25.0 19.8 26.5 24.0 0.07DNA/M -M1 - M20x1.5 - 6.1-11.9 25.0 15.0 26.5 24.0 0.07 SPV-24DNA/M -N1 - - 1/2” 25.0 19.8 26.5 24.0 0.07DNA/L -M1 - M20x1.5 -

6.5-14.326.0 15.0 35.0 31.75 0.09

SPV-31DNA/S -M2 - M25x1.5 - 0.11DNA/L -N1 - - 1/2” 26.0 19.8 35.0 31.75 0.08DNA/S -N2 - - 3/4” 26.0 20.1 35.0 31.75 0.12DNA/M -M2 - M25x1.5 -

11.1-20.233.0 15.0 42.0 38.1 0.14

SPV-38DNA/S -M3 - M32x1.5 - 0.18DNA/M -N2 - - 3/4” 33.0 20.1 42.0 38.1 0.14DNA/S -N3 - - 1” 33.0 25.0 42.0 38.1 0.21DNA/M -M3 - M32x1.5 -

17.0-26.534.0 15.0 49.0 44.4 0.19

SPV-44DNA/S -M4 - M40x1.5 - 0.25DNA/M -N3 - - 1” 34.0 25.0 49.0 44.4 0.19DNA/S -N4 - - 1-1/4” 34.0 25.6 49.0 44.4 0.31DNA/M -M4 - M40x1.5 -

22.0-32.538.0 15.0 56.0 50.8 0.26

SPV-50DNA/S -M5 - M50x1.5 - 0.38DNA/M -N4 - - 1-1/4” 38.0 25.6 56.0 50.8 0.30DNA/S -N5 - - 1-1/2” 38.0 26.0 56.0 50.8 0.41DNA/M -M5 - M50x1.5 29.5-38.1 38.0 15.0 63.0 57.1 0.36 SPV-57DNA/M -N5 - 1-1/2” 38.0 26.0 63.0 57.1 0.37DNA/L -M5 - M50x1.5 -

35.6-44.040.0 15.0 70.0 63.5 0.44

SPV-63DNA/S -M6 - M63x1.5 - 0.65DNA/L -N5 - - 1-1/2” 40.0 26.0 70.0 63.5 0.47DNA/S -N6 - - 2” 40.0 26.9 70.0 63.5 0.67DNA/M -M6S - M63x1.5 -

39.0-44.040.0 15.0 84.0 76.2 0.49

SPV-76DNA/S -M7S - M75x1.5 - 0.76DNA/M -N6S - - 2” 40.0 26.9 84.0 76.2 0.52DNA/S -N7S - - 2-1/2” 40.0 39.9 84.0 76.2 0.95DNA/M -M6L - M63x1.5 -

44.1-54.040.0 15.0 84.0 76.2 0.49

SPV-76DNA/S -M7L - M75x1.5 - 0.76DNA/M -N6L - - 2” 40.0 26.9 84.0 76.2 0.52DNA/S -N7L - - 2-1/2” 40.0 39.9 84.0 76.2 0.95

Ordering Requirements

Catalogue Number Logic

Brass Nickel-plated brass

Note: Cables for fixed installations shall have flame propagation characteristics which enable them to withstand the tests according to IEC 60332-1-2 or IEC 60332-3-22.

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db eb IIC Gb Ex tb IIIC Db IP66Certificate TÜV CY 18 ATEX 0206101 UT Rating Temperature class of enclosure to which will be connected.Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -20oC to +75oCIndex of Protection IP66

Technical Data

Page 4: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B4/21

B

Thread seal

Body(Entry thread)

Neoprene innersealing ring

Gland nutFemale Threads

ended

Sealing washer

Cable Fitting: Cable Gland for Non-Armoured Cable, DNAF Series (Female threads ended)

Flameproof/ Increased Safety and Dust protection by enclosureZone 1 & 2 _ 21 & 22

The DNAF cable glands are suitable for used in zone 1, 2 and zone 21, 22 hazardous areas to enable direct insertion of normal non-armoured cable into Ex d equipment or enclo-sure. The gland nut is provided with female threads ended.

Application

Body, gland nut : Brass (Nickel-plated brass as option)Thread seal : Nylon (PA6) (For metric threads only)

DNAF / - -Series Body Threads Option

S Small NI Nickel-M Medium platedL Large brass

Cat. No.Entries Threads

(Male)Cable Dia.Outer ‘d’

ThreadsEnded

(Female)

Dimension in mm. Approx.Weight(kgs.)l a Across

CornersAcrossFlatsMetric NPT Min - Max NPT

DNAF/S -M0N1 - M16x1.5 -3.0-8.6 1/2” 38.5 15.0 26.5 24.0 0.08

DNAF/S -M1N1 - M20x1.5 - 0.10DNAF/S -N1 - - 1/2” 41.5 19.8 26.5 24.0 0.11DNAF/M -M1N1 - M20x1.5 - 6.1-11.9 1/2” 38.5 15.0 26.5 24.0 0.10DNAF/M -N1 - - 1/2” 41.5 19.8 26.5 24.0 0.10DNAF/L -M1N1 - M20x1.5 -

6.5-14.3

1/2” 39.5 15.0 35.0 31.75 0.11DNAF/S -M2N2 - M25x1.5 - 3/4” 0.16DNAF/L -N1 - - 1/2” 1/2” 42.5 19.8 35.0 31.75 0.12DNAF/S -N2 - - 3/4” 3/4” 42.5 20.1 35.0 31.75 0.17DNAF/M -M2N2 - M25x1.5 -

11.1-20.2

3/4” 46.5 15.0 42.0 38.1 0.17DNAF/S -M3N3 - M32x1.5 - 1” 0.23DNAF/M -N2 - - 3/4” 3/4” 49.5 20.1 42.0 38.1 0.25DNAF/S -N3 - - 1” 1” 54.5 25.0 42.0 38.1 0.28DNAF/M -M3N3 - M32x1.5 -

17.0-26.5

1” 47.5 15.0 49.0 44.4 0.23DNAF/S -M4N4 - M40x1.5 - 1-1/4” 0.31DNAF/M -N3 - - 1” 1” 55.5 25.0 49.0 44.4 0.25DNAF/S -N4 - - 1-1/4” 1-1/4” 55.5 25.6 49.0 44.4 0.40DNAF/M -M4N4 - M40x1.5 -

22.0-32.5

1-1/4” 51.0 15.0 56.0 50.8 0.30DNAF/S -M5N5 - M50x1.5 - 1-1/2” 63.0 57.1 0.45DNAF/M -N4 - - 1-1/4” 1-1/4” 59.0 25.6 56.0 50.8 0.37DNAF/S -N5 - - 1-1/2” 1-1/2” 59.0 26.0 63.0 57.1 0.49DNAF/M -M5N5 - M50x1.5 29.5-38.1 1-1/2” 51.0 15.0 63.0 57.1 0.42DNAF/M -N5 - 1-1/2” 59.0 26.0 63.0 57.1 0.46DNAF/L -M5N5 - M50x1.5 -

35.6-44.0

1-1/2” 51.0 15.0 70.0 63.5 0.48DNAF/S -M6N6 - M63x1.5 - 2” 52.0 15.0 77.0 70.0 0.72DNAF/L -N5 - - 1-1/2” 1-1/2” 60.0 26.0 70.0 63.5 0.60DNAF/S -N6 - - 2” 2” 60.0 26.9 77.0 70.0 0.80DNAF/M -M6N6S - M63x1.5 -

39.0-44.0

2” 52.0 15.0 84.0 76.2 0.63DNAF/S -M7N7S - M75x1.5 - 2-1/2” 52.0 15.0 99.0 88.9 1.00DNAF/M -N6S - - 2” 2” 60.0 26.9 84.0 76.2 0.84DNAF/S -N7S - - 2-1/2” 2-1/2” 72.0 39.9 99.0 88.9 1.56DNAF/M -M6N6L - M63x1.5 -

44.1-54.0

2” 52.0 15.0 84.0 76.2 0.63DNAF/S -M7N7L - M75x1.5 - 2-1/2” 52.0 15.0 99.0 88.9 1.00DNAF/M -N6L - - 2” 2” 60.0 26.9 84.0 76.2 0.84DNAF/S -N7L - - 2-1/2” 2-1/2” 72.0 39.9 99.0 88.9 1.56

Ordering Requirements

Catalogue Number Logic

Brass Nickel-plated brass

Note: Cables for fixed installations shall have flame propagation characteristics which enable them to withstand the tests according to IEC 60332-1-2 or IEC 60332-3-22.

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db eb IIC Gb Ex tb IIIC Db IP66Certificate TÜV CY 18 ATEX 0206101 UT Rating Temperature class of enclosure to which will be connected.Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -20oC to +75oCIndex of Protection IP66

Technical Data

Page 5: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B5/21

B

Cable Fitting: Barrier Cable Glandfor Armoured Cable, DACB Series

Flameproof/ Increased Safety and Dust protection by enclosureZone 1 & 2 _ 21 & 22

The DACB cable glands are suitable for used to direct insertion of SWA-steel wire armoured cable into Ex db equipment or enclosure.

Application

Body, gland nut : BrassThread seal : Nylon (PA6) (For metric threads only)Seal : Epoxy barrier compound

Technical Data

DACB / - -Series Body Threads Option

S Small NI Nickel-M Medium platedL Large brass

Thread seal

Body(Entry thread)

Neoprene innersealing ring

Clamping cone-A

Inner gland nut

Neoprene outersealing ring

End cap

Outer gland nut

Sealing washer

Clamping cone-B

Bush sleeve

Cat. No.Entries Threads

(Male)Cable Diameter Armour

WireDia.

Dimension in mm. Approx.Weight(kgs.)

Inner 'd1' Outer 'd2'l a Across

CornersAcrossFlatsMetric NPT Min - Max Min - Max

DACB/S -M0 - M16x1.5 -3.0-8.6 6.0-13.4 0.9 65.0 15.0 26.5 24.0 0.13DACB/S -M1 - M20x1.5 -

DACB/S -N1 - - 1/2” 65.0 19.8 26.5 24.0DACB/M -M1 - M20x1.5 - 6.1-11.9 9.5-16.0 0.9/1.25 65.0 15.0 26.5 24.0 0.14DACB/M -N1 - - 1/2” 65.0 19.8 26.5 24.0DACB/L -M1 - M20x1.5 -

6.5-14.3 12.5-20.9 0.9/1.2573.0 15.0 35.0 31.75 0.20

DACB/S -M2 - M25x1.5 - 0.26DACB/L -N1 - - 1/2” 73.0 19.8 35.0 31.75 0.20DACB/S -N2 - - 3/4” 73.0 20.1 35.0 31.75 0.26DACB/M -M2 - M25x1.5 -

11.1-20.2 16.9-26.2 1.25/1.681.0 15.0 42.0 38.1 0.37DACB/S -M3 - M32x1.5 -

DACB/M -N2 - - 3/4” 81.0 20.1 42.0 38.1 0.39DACB/S -N3 - - 1” 81.0 25.0 42.0 38.1DACB/M -M3 - M32x1.5 -

17.0-26.5 22.0-31.9 1.6/2.092.0 15.0 49.0 44.4 0.60

DACB/S -M4 - M40x1.5 - 0.65DACB/M -N3 - - 1” 92.0 25.0 49.0 44.4 0.60DACB/S -N4 - - 1-1/4” 92.0 25.6 49.0 44.4 0.65DACB/M -M4 - M40x1.5 -

22.0-32.5 26.0-38.5 1.6/2.096.0 15.0 56.0 50.8

0.80DACB/S -M5 - M50x1.5 -DACB/M -N4 - - 1-1/4” 96.0 25.6 56.0 56.0DACB/S -N5 - - 1-1/2” 96.0 26.0 56.0 56.0DACB/M -M5 - M50x1.5 29.5-38.1 35.0-46.8 1.8/2.5 98.0 15.0 63.0 57.1 0.90DACB/M -N5 - 1-1/2” 98.0 26.0 63.0 57.1DACB/L -M5 - M50x1.5 -

35.6-44.0 38.0-50.1 1.8/2.598.0 15.0 70.0 63.5

1.00DACB/S -M6 - M63x1.5 -DACB/L -N5 - - 1-1/2” 98.0 26.0 70.0 63.5DACB/S -N6 - - 2” 98.0 26.9 70.0 63.5DACB/M -M6S - M63x1.5 -

39.0-44.0 47.0-55.0 1.8/2.599.0 15.0 84.0 76.2

1.35DACB/S -M7S - M75x1.5 -DACB/M -N6S - - 2” 99.0 26.9 84.0 76.2DACB/S -N7S - - 2-1/2” 99.0 39.9 84.0 76.2DACB/M -M6L - M63x1.5 -

44.1-54.0 55.1-65.0 1.8/2.599.0 15.0 84.0 76.2

1.35DACB/S -M7L - M75x1.5 -DACB/M -N6L - - 2” 99.0 26.9 84.0 76.2DACB/S -N7L - - 2-1/2” 99.0 39.9 84.0 76.2

Ordering Requirements

Catalogue Number Logic

Brass Nickel-plated brass

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db eb IIC Gb Ex tb IIIC Db IP66T Rating Temperature class of enclosure to which will be connected.Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -40oC to +75oCIndex of Protection IP66

Note: Cables for fixed installations shall have flame propagation characteristics which enable them to withstand the tests according to IEC 60332-1-2 or IEC 60332-3-22.

Compound tube

Nickel-plated brass

Page 6: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B6/21

B

Cable Fitting: Barrier Cable Glandfor Non-Armoured Cable, DNAB Series

Flameproof/ Increased Safety and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Thread seal

Body(Entry thread)

Neoprene innersealing ring

Gland nut

Sealing washer

The DNAB cable glands are suitable for used to direct insertion of normal non-armoured cable into Ex db equipment or enclosure.

Application

Body, gland nut : BrassThread seal : Nylon (PA6) (For metric threads only)Seal : Epoxy barrier compound

DNAB / - -Series Body Threads Option

S Small NI Nickel-M Medium platedL Large brass

Cat. No.Entries Threads

(Male)Cable Dia.Outer ‘d’

Dimension in mm. Approx.Weight(kgs.)l a Across

CornersAcrossFlatsMetric NPT Min - Max

DNAB/S -M0 - M16x1.5 -3.0-8.6 25.0 15.0 26.5 24.0 0.06

DNAB/S -M1 - M20x1.5 - 0.07DNAB/S -N1 - - 1/2” 25.0 19.8 26.5 24.0 0.07DNAB/M -M1 - M20x1.5 - 6.1-11.9 25.0 15.0 26.5 24.0 0.07DNAB/M -N1 - - 1/2” 25.0 19.8 26.5 24.0 0.07DNAB/L -M1 - M20x1.5 -

6.5-14.326.0 15.0 35.0 31.75 0.09

DNAB/S -M2 - M25x1.5 - 0.11DNAB/L -N1 - - 1/2” 26.0 19.8 35.0 31.75 0.08DNAB/S -N2 - - 3/4” 26.0 20.1 35.0 31.75 0.12DNAB/M -M2 - M25x1.5 -

11.1-20.233.0 15.0 42.0 38.1 0.14

DNAB/S -M3 - M32x1.5 - 0.18DNAB/M -N2 - - 3/4” 33.0 20.1 42.0 38.1 0.14DNAB/S -N3 - - 1” 33.0 25.0 42.0 38.1 0.21DNAB/M -M3 - M32x1.5 -

17.0-26.534.0 15.0 49.0 44.4 0.19

DNAB/S -M4 - M40x1.5 - 0.25DNAB/M -N3 - - 1” 34.0 25.0 49.0 44.4 0.19DNAB/S -N4 - - 1-1/4” 34.0 25.6 49.0 44.4 0.31DNAB/M -M4 - M40x1.5 -

22.0-32.538.0 15.0 56.0 50.8 0.26

DNAB/S -M5 - M50x1.5 - 0.38DNAB/M -N4 - - 1-1/4” 38.0 25.6 56.0 50.8 0.30DNAB/S -N5 - - 1-1/2” 38.0 26.0 56.0 50.8 0.41DNAB/M -M5 - M50x1.5 29.5-38.1 38.0 15.0 63.0 57.1 0.36DNAB/M -N5 - 1-1/2” 38.0 26.0 63.0 57.1 0.37DNAB/L -M5 - M50x1.5 -

35.6-44.040.0 15.0 70.0 63.5 0.44

DNAB/S -M6 - M63x1.5 - 0.65DNAB/L -N5 - - 1-1/2” 40.0 26.0 70.0 63.5 0.47DNAB/S -N6 - - 2” 40.0 26.9 70.0 63.5 0.67DNAB/M -M6S - M63x1.5 -

39.0-44.040.0 15.0 84.0 76.2 0.49

DNAB/S -M7S - M75x1.5 - 0.76DNAB/M -N6S - - 2” 40.0 26.9 84.0 76.2 0.52DNAB/S -N7S - - 2-1/2” 40.0 39.9 84.0 76.2 0.95DNAB/M -M6L - M63x1.5 -

44.1-54.040.0 15.0 84.0 76.2 0.49

DNAB/S -M7L - M75x1.5 - 0.76DNAB/M -N6L - - 2” 40.0 26.9 84.0 76.2 0.52DNAB/S -N7L - - 2-1/2” 40.0 39.9 84.0 76.2 0.95

Ordering Requirements

Catalogue Number Logic

Brass Nickel-plated brass

Note: Cables for fixed installations shall have flame propagation characteristics which enable them to withstand the tests according to IEC 60332-1-2 or IEC 60332-3-22.

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db eb IIC Gb Ex tb IIIC Db IP66T Rating Temperature class of enclosure to which will be connected.Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -40oC to +75oCIndex of Protection IP66

Technical Data

Compound tube

(Entry thread)

Compound tube

Page 7: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B7/21

B

Cable Fitting: Barrier Cable Glandfor Non-Armoured Cable, DNAFB Series

Flameproof/ Increased Safety and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Thread seal

Body(Entry thread)

Neoprene innersealing ring

Gland nutFemale Threads

ended

Sealing washer

The DNAFB cable glands are suitable for used to insertion of normal non-armoured cable into Ex db equipment or enclo-sure. The gland nut is provided with female threads ended.

Application

Body, gland nut : BrassThread seal : Nylon (PA6) (For metric threads only)Seal : Epoxy barrier compound

DNAFB / - -Series Body Threads Option

S Small NI Nickel-M Medium platedL Large brass

Cat. No.Entries Threads

(Male)Cable Dia.Outer ‘d’

ThreadsEnded

(Female)

Dimension in mm. Approx.Weight(kgs.)l a Across

CornersAcrossFlatsMetric NPT Min - Max NPT

DNAFB/S -M0N1 - M16x1.5 -3.0-8.6 1/2” 38.5 15.0 26.5 24.0 0.08

DNAFB/S -M1N1 - M20x1.5 - 0.10DNAFB/S -N1 - - 1/2” 41.5 19.8 26.5 24.0 0.11DNAFB/M -M1N1 - M20x1.5 - 6.1-11.9 1/2” 38.5 15.0 26.5 24.0 0.10DNAFB/M -N1 - - 1/2” 41.5 19.8 26.5 24.0 0.10DNAFB/L -M1N1 - M20x1.5 -

6.5-14.3

1/2” 39.5 15.0 35.0 31.75 0.11DNAFB/S -M2N2 - M25x1.5 - 3/4” 0.16DNAFB/L -N1 - - 1/2” 1/2” 42.5 19.8 35.0 31.75 0.12DNAFB/S -N2 - - 3/4” 3/4” 42.5 20.1 35.0 31.75 0.17DNAFB/M -M2N2 - M25x1.5 -

11.1-20.2

3/4” 46.5 15.0 42.0 38.1 0.17DNAFB/S -M3N3 - M32x1.5 - 1” 0.23DNAFB/M -N2 - - 3/4” 3/4” 49.5 20.1 42.0 38.1 0.25DNAFB/S -N3 - - 1” 1” 54.5 25.0 42.0 38.1 0.28DNAFB/M -M3N3 - M32x1.5 -

17.0-26.5

1” 47.5 15.0 49.0 44.4 0.23DNAFB/S -M4N4 - M40x1.5 - 1-1/4” 0.31DNAFB/M -N3 - - 1” 1” 55.5 25.0 49.0 44.4 0.25DNAFB/S -N4 - - 1-1/4” 1-1/4” 55.5 25.6 49.0 44.4 0.40DNAFB/M -M4N4 - M40x1.5 -

22.0-32.5

1-1/4” 51.0 15.0 56.0 50.8 0.30DNAFB/S -M5N5 - M50x1.5 - 1-1/2” 63.0 57.1 0.45DNAFB/M -N4 - - 1-1/4” 1-1/4” 59.0 25.6 56.0 50.8 0.37DNAFB/S -N5 - - 1-1/2” 1-1/2” 59.0 26.0 63.0 57.1 0.49DNAFB/M -M5N5 - M50x1.5 29.5-38.1 1-1/2” 51.0 15.0 63.0 57.1 0.42DNAFB/M -N5 - 1-1/2” 59.0 26.0 63.0 57.1 0.46DNAFB/L -M5N5 - M50x1.5 -

35.6-44.0

1-1/2” 51.0 15.0 70.0 63.5 0.48DNAFB/S -M6N6 - M63x1.5 - 2” 52.0 15.0 77.0 70.0 0.72DNAFB/L -N5 - - 1-1/2” 1-1/2” 60.0 26.0 70.0 63.5 0.60DNAFB/S -N6 - - 2” 2” 60.0 26.9 77.0 70.0 0.80DNAFB/M -M6N6S - M63x1.5 -

39.0-44.0

2” 52.0 15.0 84.0 76.2 0.63DNAFB/S -M7N7S - M75x1.5 - 2-1/2” 52.0 15.0 99.0 88.9 1.00DNAFB/M -N6S - - 2” 2” 60.0 26.9 84.0 76.2 0.84DNAFB/S -N7S - - 2-1/2” 2-1/2” 72.0 39.9 99.0 88.9 1.56DNAFB/M -M6N6L - M63x1.5 -

44.1-54.0

2” 52.0 15.0 84.0 76.2 0.63DNAFB/S -M7N7L - M75x1.5 - 2-1/2” 52.0 15.0 99.0 88.9 1.00DNAFB/M -N6L - - 2” 2” 60.0 26.9 84.0 76.2 0.84DNAFB/S -N7L - - 2-1/2” 2-1/2” 72.0 39.9 99.0 88.9 1.56

Ordering Requirements

Catalogue Number Logic

Brass Nickel-plated brass

Note: Cables for fixed installations shall have flame propagation characteristics which enable them to withstand the tests according to IEC 60332-1-2 or IEC 60332-3-22.

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db eb IIC Gb Ex tb IIIC Db IP66T Rating Temperature class of enclosure to which will be connected.Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -40oC to +75oCIndex of Protection IP66

Technical Data

Compound tube

(Entry thread)

Compound tube

Page 8: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B8/21

B

Cable Fitting: Conductor Bushing,DCB Series

Flameproof/ Increased Safety and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db eb IIC Gb Ex tb IIIC Db IP66T Rating Temperature class of enclosure to which will be connected.Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -40oC to +105oCIndex of Protection IP66

Technical DataThe conductor bushing are used to provide the wire connection between flameproof enclosures and increased safety enclosures.

Application

Body : Brass (Nickel-plated brass as option)Seal : Polyurethane cast resin

Voltage : up to 750V.Ampere : up to 200A.Conductor : 1.5mm.2 up to 70mm.2

Strand copper wire (H07V2-K)Conductor length : 500/500mm. (Ex db/ Ex eb)

Electrical Rating

Cat. No.

ConductorSize

Rated Operational

Current at 40oC

RatedOperational

Voltage

ConductorQuantity

EntryThreads

Dimension in mm.

Øa b c Ød e f g(mm.2) (A.) (V.) (core) (Metric)DCB 04 1X -M0 -

1.5mm.2 16A. 450/750V.

4 cores M16x1.5 24.5 22.0 20.0 14.0 15.0 5.0 M10x1.5DCB 06 1X -M2 - 6 cores M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5DCB 12 1X -M3 - 12 cores M32x1.5 42.0 38.1 20.0 30.0 15.0 5.0 M25x1.5DCB 34 1X -M4 - 34 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 48 1X -M5 - 48 cores M50x1.5 56.0 50.8 20.0 48.0 15.0 5.0 M42x1.5DCB 03 2X -M0 -

2.5mm.2 23A. 450/750V.

3 cores M16x1.5 24.5 22.0 20.0 14.0 15.0 5.0 M10x1.5DCB 04 2X -M2 - 4 cores M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5DCB 10 2X -M3 - 10 cores M32x1.5 42.0 38.1 30.0 20.0 15.0 5.0 M25x1.5DCB 22 2X -M4 - 22 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 34 2X -M5 - 34 cores M50x1.5 56.0 50.8 20.0 48.0 15.0 5.0 M42x1.5DCB 01 4X -M0 -

4.0mm.2 31A. 450/750V.

1 core M16x1.5 24.5 22.0 20.0 14.0 15.0 5.0 M10x1.5DCB 03 4X -M2 - 3 cores M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5DCB 06 4X -M3 - 6 cores M32x1.5 42.0 38.1 20.0 30.0 15.0 5.0 M25x1.5DCB 16 4X -M4 - 16 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 01 6X -M0 -

6.0mm.2 40A. 450/750V.

1 core M16x1.5 24.5 22.0 20.0 14.0 15.0 5.0 M10x1.5DCB 03 6X -M2 - 3 cores M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5DCB 06 6X -M3 - 6 cores M32x1.5 42.0 38.1 20.0 30.0 15.0 5.0 M25x1.5DCB 10 6X -M4 - 10 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 01 10 -M2 -

10.0mm.2 58A. 450/750V.1 core M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5

DCB 03 10 -M3 - 3 cores M32x1.5 42.0 38.1 20.0 30.0 15.0 5.0 M25x1.5DCB 06 10 -M4 - 6 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 01 16 -M2 -

16.0mm.2 75A. 450/750V.1 core M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5

DCB 03 16 -M3 - 3 cores M32x1.5 42.0 38.1 20.0 30.0 15.0 5.0 M25x1.5DCB 06 16 -M4 - 6 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 01 25 -M2 -

25.0mm.2 98A. 450/750V.1 core M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5

DCB 03 25 -M4 - 3 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 04 25 -M5 - 4 cores M50x1.5 56.0 50.8 20.0 48.0 15.0 5.0 M42x1.5DCB 01 35 -M2 -

35.0mm.2 124A. 450/750V.1 core M25x1.5 35.0 31.75 20.0 23.0 15.0 5.0 M18x1.5

DCB 03 35 -M4 - 3 cores M40x1.5 49.0 44.4 20.0 38.0 15.0 5.0 M32x1.5DCB 04 35 -M5 - 4 cores M50x1.5 56.0 50.8 20.0 48.0 15.0 5.0 M42x1.5DCB 01 50 -M3 - 50.0mm.2 163A. 450/750V. 1 core M32x1.5 42.0 38.1 20.0 30.0 15.0 5.0 M25x1.5DCB 03 50 -M5 - 3 cores M50x1.5 56.0 50.8 20.0 48.0 15.0 5.0 M42x1.5DCB 01 70 -M3 - 70.0mm.2 200A. 450/750V. 1 core M32x1.5 42.0 38.1 20.0 30.0 15.0 5.0 M25x1.5

Ordering Requirements

DCB - -Series Number of Core Conductor Size Threads Option

01 1 core 12 12 cores 1X 1.5mm.2 16 16.0mm.2 M0 M16x1.5 NI Nickel-03 3 cores 22 22 cores 2X 2.5mm.2 25 25.0mm.2 M2 M25x1.5 plated04 4 cores 34 34 cores 4X 4.0mm.2 35 35.0mm.2 M3 M32x1.5 brass06 6 cores 48 48 cores 6X 6.0mm.2 50 50.0mm.2 M4 M40x1.510 10 cores 10 10.0mm.2 70 70.0mm.2 M5 M50x1.5

Catalogue Number Logic

Rated Conduc

Series Number of Core Conductor Size Thread01 1 core 1 1X 1.5mm.2 16 16.0mm.2 M0 M16x03 3 cores 2 25 0mm 2 M2 M25x04 4 cores06 6 cores10 10 cores

tity Threads

c Ød e f g

M10x1 5

x1.5 bx1.5x1.5

ctor Entry Dimension in mm.

12 12 cores 1X 1.5mm22 22 cores 2X 2.5mm.2 25 25.0mm.34 34 cores 4X 4.0mm.2 35 35.0mm.2 M3 M32x48 48 cores 6X 6.0mm.2 50 50.0mm.2 M4 M40x

10 10.0mm.2 70 70.0mm.2 M5 M50x

Page 9: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B9/21

B

NPT threads are also available upon request.

Cable Fitting: Accessories for Cable Glands, Lock Nut/ Earth Tag/ Shroud/ Entries Thread Seal

Lock nuts are used to secure the cable gland body to the gland plate or the enclosure which are less thick. Material : Brass (Nickel-plated is available upon request)

Lock Nut

Earth tags are installed between the cable gland and equipment to provide an earth/ bond connection. Material : Brass (Nickel-plated is available upon request)

Earth Tag

The shrouds are used to minimise the risk of dirt or foreign substances gathering on the cable gland body. Material : PVC DIP moulded (black)

Shroud

Entries thread seal are used between the cable gland and enclosure interface to maintain the ingress protection rating of equipment. Material : Nylon (PA6)

Entries Thread Seal

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Cat. No.Dimension in mm.

a b øc ød øe fSPV-24 74.0 50.0 24.5 28.1 3.0 1.8SPV-31 77.0 55.0 32.5 36.1 6.5 1.8SPV-38 85.0 60.0 39.5 43.1 11.1 1.8SPV-44 91.0 65.0 46.0 49.6 17.0 1.8SPV-50 96.0 70.0 53.0 56.6 22.0 1.8SPV-57 99.0 75.0 60.0 63.6 29.5 1.8SPV-63 101.0 80.0 66.5 70.1 35.6 1.8SPV-70 57.0 80.0 73.5 77.1 35.6 1.8SPV-76 102.0 85.0 79.5 83.1 39.0 1.8SPV-88 55.0 85.0 94.5 98.1 39.0 1.8

Cat. No.Dimension in mm.

øa øb c d e Thk.DET-0 16.5 6.75 30.0 36.5 22.0 1.5DET-1 21.5 7.0 33.0 39.6 27.0 1.5DET-2 26.5 10.5 36.0 44.5 38.0 1.5DET-3 33.0 12.2 41.0 51.0 44.0 1.5DET-4 41.5 13.5 44.5 60.0 50.0 1.5DET-5 51.0 13.5 58.0 80.0 63.0 1.5DET-6 64.0 13.5 67.0 86.0 76.0 1.5DET-7 76.0 13.5 73.0 94.0 89.0 1.5DET-8 91.0 13.5 84.5 103.0 101.0 2.5DET-9 101.0 13.5 96.0 114.0 114.0 2.5DET-10 113.0 13.5 108.0 126.0 127.0 2.5

Cat. No.Dimension in mm. Approx. Weight

(kgs.)øa øbGK-0 22.0 16.0 0.001GK-1 27.0 21.5 0.001GK-2 32.0 26.6 0.001GK-3 39.0 33.0 0.002GK-4 47.5 41.5 0.002GK-5 58.0 50.0 0.002GK-6 71.0 63.0 0.002GK-7 84.0 75.0 0.003GK-8 101.0 91.0 0.003GK-9 113.0 101.0 0.004GK-10 126.0 114.0 0.004

Cat. No. Gland SizeDimension in mm. Approx.

Weight(kgs.)

AcrossCorners

AcrossFlats

Thk.'t'

LNB-M16 M16x1.5 22.0 24.5 5.0 0.012LNB-M20 M20x1.5 27.0 30.0 5.0 0.014LNB-M25 M25x1.5 31.0 34.0 5.0 0.016LNB-M32 M32x1.5 38.1 42.0 7.0 0.028LNB-M40 M40x1.5 50.8 56.0 7.0 0.036LNB-M50 M50x1.5 63.5 70.0 7.0 0.058LNB-M63 M63x1.5 76.2 84.0 7.0 0.090LNB-M75 M75x1.5 89.0 99.0 10.0 0.101LNB-N1 1/2” NPT 27.0 30.0 5.0 0.156LNB-N2 3/4” NPT 31.0 34.0 5.0 0.015LNB-N3 1” NPT 38.1 42.0 7.0 0.026LNB-N4 1-1/4” NPT 50.8 56.0 7.0 0.053LNB-N5 1-1/2” NPT 63.5 70.0 7.0 0.058LNB-N6 2” NPT 76.2 84.0 7.0 0.106LNB-N7 2-1/2” NPT 89.0 99.0 10.0 0.138

Ordering Requirements

Ordering Requirements

Ordering Requirements

Ordering Requirements

the cable gland body.Material : PVC DIP moulded (black)

Page 10: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B10/21

B

Metric threads

NPT threads

The DSP stopping plugs are used for sealing or closing unused threaded entries of flameproof enclosure.

Application

Body : Aluminium or BrassThread seal : Nylon (PA6) (For metric threads only)

Conduit Fitting: Stopping Plug, DSP Series

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Metric threads

NPT threads

Technical DataHazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex d IIC Gb Ex tb IIIC Db IP66Certificate LCIE 13 ATEX 3046 U

IECEx LCIE 13.0028UConformity to Standards EN 60079-0:2012, EN 60079-1:2007, EN 60079-31:2009

IEC 60079-0:2011, IEC 60079-1:2007-04,IEC 60079-31:2008

Ambient Temperature -20oC to +75oCIndex of Protection IP66

Cat. No.EntriesThread(Male)

Dimension in mm. Approx. Weight (kgs.)

a b c d Aluminium BrassDSP-M0 - M16x1.5 20.0 5.0 25.0 10.0 0.011 0.035DSP-M1 - M20x1.5 20.0 5.0 30.5 10.0 0.019 0.059DSP-M2 - M25x1.5 20.0 5.0 36.0 10.0 0.030 0.092DSP-M3 - M32x1.5 20.0 5.0 42.5 16.0 0.044 0.132DSP-M4 - M40x1.5 20.0 5.0 51.0 16.0 0.070 0.222DSP-M5 - M50x1.5 20.0 5.0 59.0 16.0 0.107 0.341DSP-M6 - M63x1.5 20.0 5.0 72.0 16.0 0.172 0.550DSP-M7 - M75x1.5 20.0 5.0 84.0 16.0 0.241 0.774DSP-M8 - M80x2.0 25.0 5.0 89.0 24.0 0.330 1.058DSP-M9 - M90x2.0 25.0 5.0 99.0 24.0 0.421 1.350DSP-M10 - M100x2.0 25.0 5.0 109.0 24.0 0.523 1.677

Cat. No.EntriesThread(Male)

Dimension in mm. Approx. Weight (kgs.)

a b c Aluminium BrassDSP-N1 - 1/2” NPT 19.85 21.96 10.0 0.012 0.043DSP-N2 - 3/4” NPT 20.15 27.29 10.0 0.024 0.078DSP-N3 - 1” NPT 25.01 34.16 16.0 0.046 0.144DSP-N4 - 1-1/4” NPT 25.62 42.92 16.0 0.083 0.259DSP-N5 - 1-1/2” NPT 26.04 49.02 16.0 0.112 0.349DSP-N6 - 2” NPT 26.88 61.08 16.0 0.187 0.628DSP-N7 - 2-1/2” NPT 39.91 74.11 24.0 0.421 1.350DSP-N8 - 3” NPT 41.50 89.99 24.0 0.663 1.124DSP-N9 - 3-1/2” NPT 42.77 102.69 24.0 0.901 2.890DSP-N10 - 4” NPT 44.04 115.39 24.0 1.181 3.784

DSP - -

Series Entries threads Material Option (Brass only)M Metric threads A Aluminium NI Nickel-plated brassN NPT threads B Brass

Ordering Requirements and Dimension

Catalogue Number Logic

Metric threads

NPT threads

Brass

Brass Nickel-plated brass

Nickel-plated brass

Page 11: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B11/21

B

Conduit Fitting: Reducer and Adaptor (Enlarger), DRH and DAT Series

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Reducer and Adaptor are provided a means of attachment between dissimilar thread types or thread sizes.

Application

Body : BrassEntry thread seal : Aramid fiber (For metric threads only)

Brass : Nickel-plated is available upon request

Option

add option (- ) to Cat. No. (Brass only)e.g. DAT-M13-NI (Nickel-plated brass)

Ordering

Selection Chart for Reducer and Adaptor (Enlarger)

Technical Data

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex d IIC Gb Ex tb IIIC Db IP66Certificate LCIE 13 ATEX 3046 U

IECEx LCIE 13.0028UConformity to Standards EN 60079-0:2012, EN 60079-1:2007, EN 60079-31:2009

IEC 60079-0:2011, IEC 60079-1:2007-04,IEC 60079-31:2008

Ambient Temperature -20oC to +75oCIndex of Protection IP66

Page 12: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B12/21

B

Conduit Fitting: Reducer, DRH Series

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Ordering Requirements and Dimension

NPT threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDRH-N21 3/4” NPT

1/2” NPT18.4 20.15

15.032.15 31.0 30.0

DRH-N311” NPT 24.0 25.01 37.01 38.1 42.0

DRH-N32 3/4” NPTDRH-N41

1-1/4” NPT1/2” NPT

31.0 25.6115.0

39.92 44.4 49.0DRH-N42 3/4” NPTDRH-N43 1” NPT 17.0DRH-N52

1-1/2” NPT3/4” NPT

37.0 26.0415.0

40.04 57.1 63.0DRH-N53 1” NPT 17.0DRH-N54 1-1/4” NPT 17.5DRH-N63

2” NPT1” NPT

49.0 26.8717.0

40.87 70.0 77.0DRH-N64 1-1/4” NPT17.5

DRH-N65 1-1/2” NPTDRH-N74

2-1/2” NPT1-1/4” NPT

60.0 39.9117.5

56.91 76.2 84.0DRH-N75 1-1/2” NPTDRH-N76 2” NPT 18.0DRH-N85

3” NPT1-1/2” NPT

74.0 41.4917.5

61.49 101.0 112.0DRH-N86 2” NPT 18.0DRH-N87 2-1/2” NPT 24.0DRH-N96

3-1/2” NPT2” NPT

86.0 42.7618.0 62.76

114.0 126.0DRH-N97 2-1/2” NPT 24.0 68.76DRH-N98 3” NPT 26.0 70.76DRH-N107

4” NPT2-1/2” NPT

96.070.04 24.0

70.04120.0 134.0DRH-N108 3” NPT

72.0426.0

DRH-N109 3-1/2” NPT 27.5 72.04

Metric threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDRH-M10 M20x1.5 M16x1.5 14.0

15.0 15.0 27.022.0 24.5

DRH-M20M20x1.5

M16x1.517.0 27.0 30.0

DRH-M21 M20x1.5DRH-M30

M32x1.5M16x1.5

24.0 15.0 15.0 27.0 38.1 42.0DRH-M31 M20x1.5DRH-M32 M25x1.5DRH-M41

M40x1.5M20x1.5

32.0 15.0 15.0 29.0 44.4 49.0DRH-M42 M25x1.5DRH-M43 M32x1.5DRH-M52

M50x1.5M25x1.5

42.0 15.0 15.0 29.0 57.1 63.0DRH-M53 M32x1.5DRH-M54 M40x1.5DRH-M63

M63x1.5M32x1.5

55.0 15.0 15.0 29.0 70.0 77.0DRH-M64 M40x1.5DRH-M65 M50x1.5DRH-M74

M75x1.5M40x1.5

67.0 15.0 15.0 32.0 76.2 84.0DRH-M75 M50x1.5DRH-M76 M63x1.5DRH-M85

M90x2.0M50x1.5

78.0 20.0 15.0 40.0 101.0 112.0DRH-M86 M63x1.5DRH-M87 M75x1.5DRH-M96

M100x2.0M63x1.5

88.0 20.015.0 40.0

114.0 126.0DRH-M97 M75x1.5DRH-M98 M90x2.0 20.0 42.0

Metric/NPT threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDRH-MN21 M25x1.5 1/2” NPT 17.0

15.0 15.0 27.027.0 30.0

DRH-MN31M32x1.5 24.0 38.1 42.0

DRH-MN32 3/4” NPTDRH-MN41

M40x1.51/2” NPT

32.0 15.0 15.0 29.0 44.4 49.0DRH-MN42 3/4” NPTDRH-MN43 1” NPTDRH-MN52

M50x1.53/4” NPT

42.0 15.015.0

29.0 57.1 63.0DRH-MN53 1” NPT 17.0DRH-MN54 1-1/4” NPT 17.5DRH-MN63

M63x1.51” NPT

55.0 15.017.0

29.0 70.0 77.0DRH-MN64 1-1/4” NPT17.5

DRH-MN65 1-1/2” NPTDRH-MN74

M75x1.51-1/4” NPT

67.0 15.017.5

32.0 76.2 84.0DRH-MN75 1-1/2” NPTDRH-MN76 2” NPT 18.0DRH-MN85

M90x2.01-1/2” NPT

78.0 20.017.5

40.0101.0 112.0DRH-MN86 2” NPT 18.0

DRH-MN87 2-1/2” NPT 24.0 46.0DRH-MN96

M100x2.02” NPT

88.0 20.018.0 40.0

114.0 126.0DRH-MN97 2-1/2” NPT 24.0 46.0DRH-MN98 3” NPT 26.0 48.0

NPT/Metric threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDRH-NM10 1/2” NPT

M16x1.514.0 19.85

15.031.85 24.0 26.5

DRH-NM203/4” NPT 18.0 20.15 32.15 31.0 34.0

DRH-NM21 M20x1.5DRH-NM30

1” NPTM16x1.5

24.0 25.0 15.0 37.0 38.1 42.0DRH-NM31 M20x1.5DRH-NM32 M25x1.5DRH-NM41

1-1/4” NPTM20x1.5

31.0 25.61 15.0 39.61 44.4 49.0DRH-NM42 M25x1.5DRH-NM43 M32x1.5DRH-NM52

1-1/2” NPTM25x1.5

37.0 26.04 15.0 40.04 57.1 63.0DRH-NM53 M32x1.5DRH-NM54 M40x1.5DRH-NM63

2” NPTM32x1.5

49.0 26.87 15.0 40.87 70.0 77.0DRH-NM64 M40x1.5DRH-NM65 M50x1.5DRH-NM74

2-1/2” NPTM40x1.5

60.0 39.9 15.0 56.9 76.2 84.0DRH-NM75 M50x1.5DRH-NM76 M63x1.5DRH-NM85

3” NPTM50x1.5

74.0 41.49 15.0 61.49 101.0 112.0DRH-NM86 M63x1.5DRH-NM87 M75x1.5DRH-NM96

3-1/2” NPTM63x1.5

86.0 42.7615.0 62.76

114.0 126.0DRH-NM97 M75x1.5DRH-NM98 M90x2.0 20.0 64.76DRH-NM107

4” NPTM75x1.5

96.0 44.0315.0 64.03

120.0 134.0DRH-NM108 M90x2.020.0 66.03

DRH-NM109 M100x2.0

Page 13: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B13/21

B

Conduit Fitting: Adaptor (Enlarger), DAT Series

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Ordering Requirements and Dimension

NPT threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDAT-N12

1/2” NPT3/4” NPT

14.0 19.8515.0 40.85 38.1 42.0

DAT-N13 1” NPT17.0

42.85 44.4 49.0DAT-N14 1-1/4” NPT 43.35 50.8 56.0DAT-N23

3/4” NPT1” NPT

18.0 20.1517.0 43.15 44.4 49.0

DAT-N24 1-1/4” NPT17.5 43.65

50.8 56.0DAT-N25 1-1/2” NPT 57.1 63.0DAT-N34

1” NPT1-1/4” NPT

24.0 25.017.5 48.5

50.8 56.0DAT-N35 1-1/2” NPT 57.1 63.0DAT-N36 2” NPT 18.0 49.0 76.2 84.0DAT-N45

1-1/4” NPT1-1/2” NPT

31.0 25.6117.5 49.11 57.1 63.0

DAT-N46 2” NPT 18.049.61

76.2 84.0DAT-N47 2-1/2” NPT 24.0 89.0 99.0DAT-N56

1-1/2” NPT2” NPT

37.0 26.0418.0

50.0476.2 84.0

DAT-N57 2-1/2” NPT 24.0 89.0 99.0DAT-N58 3” NPT 26.0 114.0 126.0DAT-N67

2” NPT2-1/2” NPT

49.0 26.8724.0

59.8789.0 99.0

DAT-N68 3” NPT 26.0114.0 126.0

DAT-N69 3-1/2” NPT 27.5 62.37DAT-N78

2-1/2” NPT3” NPT

60.0 39.926.0 72.9

114.0 126.0DAT-N79 3-1/2” NPT 27.5 75.4DAT-N710 4” NPT 28.0 75.9 127.0 140.0DAT-N89

3” NPT3-1/2” NPT

74.041.49

27.5 76.99 114.0 126.0DAT-N810

4” NPT 28.077.49

127.0 140.0DAT-N910 3-1/2” NPT 86.0 78.76

NPT/Metric threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDAT-NM11

1/2” NPTM20 x 1.5

14.0 19.85 15.038.85

27.0 30.0DAT-NM12 M25 x 1.5 38.1 42.0DAT-NM13 M32 x 1.5 40.85 44.4 49.0DAT-NM22

3/4” NPTM25 x 1.5

18.0 20.15 15.039.15 38.1 42.0

DAT-NM23 M32 x 1.541.15

44.4 49.0DAT-NM24 M40 x 1.5 50.8 56.0DAT-NM33

1” NPTM32 x 1.5

24.0 25.0 15.0 46.044.4 49.0

DAT-NM34 M40 x 1.5 50.8 56.0DAT-NM35 M50 x 1.5 63.5 70.0DAT-NM44

1-1/4” NPTM40 x 1.5

31.0 25.61 15.0 46.6150.8 56.0

DAT-NM45 M50 x 1.5 63.5 70.0DAT-NM46 M63 x 1.5 76.2 84.0DAT-NM55

1-1/2” NPTM50 x 1.5

37.0 26.04 15.0 47.0463.5 70.0

DAT-NM56 M63 x 1.5 76.2 84.0DAT-NM57 M75 x 1.5 89.0 99.0DAT-NM66

2” NPTM63 x 1.5

49.0 26.8715.0 47.87

76.2 84.0DAT-NM67 M75 x 1.5 89.0 99.0DAT-NM68 M90 x 2.0 20.0 54.87 101.0 112.0DAT-NM77

2-1/2” NPTM75 x 1.5

60.0 39.915.0 60.9 89.0 99.0

DAT-NM78 M90 x 2.020.0 67.9

101.0 112.0DAT-NM79 M100 x 2.0 120.0 134.0DAT-NM88

3” NPTM90 x 2.0

74.0 41.4920.0

69.49101.0 112.0

DAT-NM89M100 x 2.0 120.0 134.0

DAT-NM99 3-1/2” NPT 86.0 42.76 70.76

Metric threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDAT-M01

M16 x 1.5M20 x 1.5

10.0 15.0 15.034.0

31.0 34.0DAT-M02 M25 x 1.5 38.1 42.0DAT-M03 M32 x 1.5 36.0 44.4 49.0DAT-M12

M20 x 1.5M25 x 1.5

14.0 15.0 15.034.0 38.1 42.0

DAT-M13 M32 x 1.536.0

44.4 49.0DAT-M14 M40 x 1.5 50.8 56.0DAT-M23

M25 x 1.5M32 x 1.5

17.0 15.0 15.0 36.044.4 49.0

DAT-M24 M40 x 1.5 50.8 56.0DAT-M25 M50 x 1.5 63.5 70.0DAT-M34

M32 x 1.5M40 x 1.5

24.0 15.0 15.0 36.050.8 56.0

DAT-M35 M50 x 1.5 63.5 70.0DAT-M36 M63 x 1.5 76.2 84.0DAT-M45

M40 x 1.5M50 x 1.5

32.0 15.0 15.0 36.063.5 70.0

DAT-M46 M63 x 1.5 76.2 84.0DAT-M47 M75 x 1.5 89.0 99.0DAT-M56

M50 x 1.5M63 x 1.5

42.0 15.015.0 36.0

76.2 84.0DAT-M57 M75 x 1.5 89.0 99.0DAT-M58 M90 x 2.0 20.0 43.0 101.0 112.0DAT-M67

M63 x 1.5M75 x 1.5

55.0 15.015.0 36.0 89.0 99.0

DAT-M68 M90 x 2.020.0 43.0

101.0 112.0DAT-M69 M100 x 2.0 120.0 134.0DAT-M78

M75 x 1.5M90 x 2.0

67.0 15.020.0

43.0101.0 112.0

DAT-M79M100 x 2.0 120.0 134.0

DAT-M89 M90 x 1.5 78.0 20.0 48.0

Metric/NPT threads

Cat. No.Entries Thread Dimension in mm.

D1 (Male) D2 (Female) a b c d e fDAT-MN01

M16 x 1.51/2” NPT

10.0 15.015.0 34.0

31.0 34.0DAT-MN02 3/4” NPT 38.1 42.0DAT-MN03 1” NPT 17.0 38.0 44.5 49.0DAT-MN11

M20 x 1.51/2” NPT

14.0 15.015.0 34.0

31.0 34.0DAT-MN12 3/4” NPT 38.1 42.0DAT-MN13 1” NPT 17.0 38.0 44.5 49.0DAT-MN22

M25 x 1.53/4” NPT

17.0 15.015.0 34.0 38.1 42.0

DAT-MN23 1” NPT 17.0 38.0 44.5 49.0DAT-MN24 1-1/4” NPT 17.5 38.5 50.8 56.0DAT-MN33

M32 x 1.51” NPT

24.0 15.017.0 38.0 44.5 49.0

DAT-MN34 1-1/4” NPT17.5 38.5

50.8 56.0DAT-MN35 1-1/2” NPT 57.1 63.0DAT-MN44

M40 x 1.51-1/4” NPT

32.0 15.017.5 38.5

50.8 56.0DAT-MN45 1-1/2” NPT 57.1 63.0DAT-MN46 2” NPT 18.0 39.0 76.2 84.0DAT-MN55

M50 x 1.51-1/2” NPT

42.0 15.017.5 38.5

76.2 84.0DAT-MN56 2” NPT 18.0 39.0DAT-MN57 2-1/2” NPT 24.0 45.0 89.0 99.0DAT-MN66

M63 x 1.52” NPT

55.0 15.018.0 39.0

89.0 99.0DAT-MN67 2-1/2” NPT 24.0 45.0DAT-MN68 3” NPT 26.0 47.0 114.0 126.0DAT-MN77

M75 x 1.52-1/2” NPT

67.0 15.024.0 45.0 89.0 99.0

DAT-MN78 3” NPT 26.0 47.0114.0 126.0

DAT-MN79 3-1/2” NPT 27.5 48.5DAT-MN88

M90 x 2.03” NPT

78.0 20.026.0 52.0

114.0 126.0DAT-MN89 3-1/2” NPT 27.5 53.5DAT-MN810 4” NPT 28.0 54.0 127.0 140.0DAT-MN99

M100 x 2.03-1/2” NPT

88.0 20.027.5 53.5 114.0 126.0

DAT-MN910 4” NPT 28.0 54.0 127.0 140.0

Page 14: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B14/21

B

* The DUNL elbow unions are used for connecting conduit to enclosure in angle position. (1-male and 1-female threaded)

DUN-1 to DUN-3 DUN-4 to DUN-10 DUNL-1 to DUNL-3

Conduit Fitting: Union and Elbow Union, DUN and DUNL Series

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

The DUN union and DUNL elbow union are used in a conduit system to connect between two conduits or the conduit to fitting for zone 1, 2 and zone 21, 22 hazardous areas.

Application

Body material : Marine grade copper-free aluminium alloy with polyester powder coated, RAL 7032 (Grey)

Ordering Requirements and Dimension

DUN-1 to DUN-3

DUN-4 to DUN-10

DUNL-1 to DUNL-3

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db IIC Gb Ex tb IIIC Db IP65Certificate TÜV CY 16 ATEX 0205742 UConformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-31:2014Ambeint Temperature -20oC to +75oCIndex of Protection IP65

Technical Data

Cat. No. Entries Thread(Female)

Dimension in mm. Approx.Weight(kgs.)a Ø b Ø c

UnionDUN-1 Ø1/2” NPT 47.0 31.0 48.0 0.098DUN-2 Ø3/4” NPT 47.0 37.8 51.0 0.101DUN-3 Ø1” NPT 55.0 43.3 58.0 0.131DUN-4 Ø1-1/4” NPT 52.5 64.0 76.0 0.289DUN-5 Ø1-1/2” NPT 60.0 75.0 86.0 0.395DUN-6 Ø2” NPT 66.0 90.0 104.0 0.655DUN-7 Ø2-1/2” NPT 80.0 107.0 120.0 0.819DUN-8 Ø3” NPT 89.0 132.0 142.0 1.442DUN-9 Ø3-1/2” NPT 89.0 136.0 158.0 1.681DUN-10 Ø4” NPT 99.0 160.0 176.0 1.842

90o Elbow Union*DUNL-1 Ø1/2” NPT 74.0 48.0 59.0 0.184DUNL-2 Ø3/4” NPT 74.0 51.0 67.0 0.207DUNL-3 Ø1” NPT 98.0 58.0 75.0 0.354

Page 15: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B15/21

B

Turning radius with cover or plug removed Turning radius with drain fitting removed

DYS DYK

Conduit Fitting: Sealing Fitting, DYS/ DYK/ DYD Series

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

The sealing fittings are used in a conduit system for zone 1, 2 and zone 21, 22 hazardous areas, to prevent the passage of gases, vapors or flames from one portion of the electrical installation to another through the conduit. DYS series for sealing in vertical position. DYK series for sealing in horizontal position. DYD series for sealing in vertical position and provide

continuous water drain path.

Application

Body material : Marine grade copper-free aluminium alloy with polyester powder coated, RAL 7032 (Grey)

Ordering Requirements and DimensionDYS

DYK

DYD

Technical Data

Cat. No. Entries Thread(Female)

Dimension in mm. Approx.Weight(kgs.)a Ø b Turning

RadiusVertical position

DYS 1 Ø1/2” NPT 87.0 32.0 45.0 0.156DYS 2 Ø3/4” NPT 96.0 38.0 54.5 0.237DYS 3 Ø1” NPT 107.0 45.0 63.0 0.365DYS 4 Ø1-1/4” NPT 120.0 58.0 77.5 0.601DYS 5 Ø1-1/2” NPT 138.0 63.0 88.5 0.655DYS 6 Ø2” NPT 157.0 76.0 105.0 1.210DYS 7 Ø2-1/2” NPT 185.0 90.0 124.0 1.707DYS 8 Ø3” NPT 217.0 106.0 146.0 2.436DYS 9 Ø3-1/2” NPT 258.0 132.0 181.5 4.999DYS 10 Ø4” NPT 260.0 133.0 183.0 4.430

Horizontal positionDYK 1 Ø1/2” NPT 87.5 32.0 31.0 0.149DYK 2 Ø3/4” NPT 99.5 40.0 33.5 0.211DYK 3 Ø1” NPT 103.0 45.0 37.5 0.319DYK 4 Ø1-1/4” NPT 130.0 58.0 51.0 0.644DYK 5 Ø1-1/2” NPT 138.0 65.0 54.5 0.705DYK 6 Ø2” NPT 152.0 76.0 60.0 0.963DYK 7 Ø2-1/2” NPT 174.0 88.0 69.0 1.258DYK 8 Ø3” NPT 196.0 104.0 77.0 1.806DYK 9 Ø3-1/2” NPT 241.0 129.0 89.5 3.295DYK 10 Ø4” NPT 242.0 134.0 92.0 3.652

Vertical position with drainDYD 1 Ø1/2” NPT 87.0 32.0 45.5 0.250DYD 2 Ø3/4” NPT 96.0 38.0 52.0 0.335DYD 3 Ø1” NPT 107.0 45.0 61.5 0.347

DYD

Hazardous Area Gas Dust

Zones 1 & 2 21 & 22

Equipment Group/Category II 2G II 2D

Symbol of Protection Ex db IIC Gb Ex tb IIIC Db IP66

T Rating Temperature class of enclosure to which will be connected.

Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-31:2014

Ambeint Temperature -20oC to +75oC

Index of Protection IP66

Page 16: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B16/21

B

Caution : Do not mix more than it can be poured within 10 minutes after adding water. Use cold water, warm water increases speed of setting. Partical of previous mixing or dirt may spoil the seal.

Depth of sealing compound should be equal to the trade size of conduit, having a minimum of 5/8 inch thickness. Close the plug immediately after pouring.

SCF - ALLCO® Sealing Compound For seal forming between and around each electrical

conductor inside of sealing fitting to restrict the passage of gases, vapors and flames.

SCF - ALLCO® Sealing Fiber Forms a positive dam to hold sealing compound in the

sealing fitting.

SCF - ALLCO® Sealing Compound is water soluble powder that can be easily mixed and poured. Mix 2 parts by volume of SCF -ALLCO® Sealing Compound with 1 part of clean water in a completely clean container. Stir it immediately and thoroughly then pour this compound into the sealing fitting. Compound will harden in 60 minutes then form a secure non-shrinking, acids, water and oil resistant seal.

SCF - ALLCO® Sealing Fiber is a rope type asbestos fiber that easy to form a dam and non-flammable.

Conduit Fitting: Sealing Compound and Fiber

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

Application

SCF - ALLCO® Sealing Compound and Sealing Fiber are packed together in standard package 454 g. (1 lb.).

Note : SCF - ALLCO® Sealing Compound and Fiber are approved for use only with ALLOY sealing fittings.

Packing

Feature

Vertical seal Horizontal seal Vertical seal and water drain

Hazardous Area Gas DustZones 1 & 2 21 & 22Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-14:2013Ambeint Temperature -20oC to +75oC

Technical Data

Page 17: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B17/21

B

Conduit Fitting: Sealing Compound(Resin, Hardener and Fiber)

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

SCFR-R100 Resin and SCFR-H100 Hardener SCFR-R100 Resin and SCFR-H100 Hardener are

certified for use in connection to the sealing fittings type DYS, DYK and/or DYD, therefore the sealing compound and the sealing fittings can be sold only coupled and never separately. The sealing must be done properly to prevent passage of gas, vapours or flames through the pipe system.

SCFR-F100 Fiber The Fiber is inserted into the sealing fittings to avoid

that the resin runs into the pipe below.

Application

The SCFR-R100 Resin and SCFR-H100 Hardener is an exclusive product of Alloy’s. Its chemical composition has been improved after many sealing tests, carried out with the cooperation of ATEX accredited testing laboratory.

Feature

SCFR-R100Resin

Hazardous Area Gas DustZones 1 & 2 21 & 22Conformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-14:2013Ambeint Temperature -20oC to +75oC

Technical Data

Gram Required per Fitting

FittingCat. No.

CavityVolume(cm3)

SealingCompound

Weight(gram)

Sealing CompoundMix Ratio (by weight)

100:13Fiber

Weight(gram)SCFR-R100

(Resin)SCFR-H100(Hardener)

DYK 1 25.30 49.2 gram 43.5 gram 5.7 g. 2.0 gramDYK 2 35.90 69.8 gram 61.8 gram 8.0 g. 4.0 gramDYK 3 43.20 84.0 gram 74.3 gram 9.7 g. 6.4 gramDYK 4 115.90 318.2 gram 281.6 gram 41.2 g. 12.2 gramDYK 5 163.70 358.6 gram 317.4 gram 36.6 g. 17.2 gramDYK 6 255.20 496.1 gram 439.0 gram 57.1 g. 32.0 gramDYK 7 394.10 766.1 gram 678.0 gram 88.1 g. 60.8 gramDYK 8 697.70 1356.4 gram 1200.4 gram 156.0 g. 106.4 gramDYK 9 1447.80 2814.5 gram 2490.8 gram 323.7 g. 199.4 gramDYK 10 1627.60 3164.0 gram 2800.1 gram 363.9 g. 200.0 gram

DYD 1 21.45 34.7 gram 30.7 gram 4.0 gram 1.0 gramDYD 2 41.03 66.5 gram 58.9 gram 7.6 gram 2.0 gramDYD 3 67.76 109.8 gram 97.2 gram 12.6 gram 3.2 gram

SCFR-H100Hardener

SCFR-F100Fiber

FittingCat. No.

CavityVolume(cm3)

SealingCompound

Weight(gram)

Sealing CompoundMix Ratio (by weight)

100:13Fiber

Weight(gram)SCFR-R100

(Resin)SCFR-H100(Hardener)

DYS 1 19.50 37.9 gram 33.5 gram 4.4 gram 1.0 gramDYS 2 37.30 72.5 gram 64.2 gram 8.3 gram 2.0 gramDYS 3 61.60 119.8 gram 106.0 gram 13.8 gram 3.2 gramDYS 4 117.20 227.9 gram 201.7 gram 26.2 gram 6.1 gramDYS 5 165.00 320.8 gram 283.9 gram 36.9 gram 8.6 gramDYS 6 305.30 593.5 gram 525.2 gram 68.3 gram 16.0 gramDYS 7 580.70 1128.8 gram 999.0 gram 129.8 gram 30.4 gramDYS 8 1015.00 1973.2 gram 1746.3 gram 226.9 gram 53.2 gramDYS 9 1903.40 3700.2 gram 3274.7 gram 425.5 gram 99.7 gramDYS 10 1910.00 3713.0 gram 3286.0 gram 427.0 gram 100.0 gram

Page 18: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B18/21

B

Conduit Fitting: Flexible Coupling, DFC Series

FlameproofZone 1 & 2 _ 21 & 22

The DFC flexible couplings are used in a conduit system for zone 1, 2 and zone 21, 22 hazardous areas to isolate conduit from vibration or movement of con-

nected equipment. accomplish difficult bends in place of rigid conduit.

Application

Inner flexible tube : Stainless steelOuter wire braid : Stainless steelMale threaded fiitting : Nickel-plated brass

with union (DUN series)

Option

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db IIC Gb Ex tb IIIC Db IP65Certificate TÜV CY 16 ATEX 0205741 UConformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-31:2014Ambeint Temperature -20oC to +75oCIndex of Protection IP65

Technical Data

Cat. No. EntriesThread (Male)

‘Ød1’

Dimension in mm.

300mm.Flexible length

600mm.Flexible length

900mm.Flexible length

1,200mm.Flexible length Ød2 a b c d e

DFC-130 DFC-160 DFC-190 DFC-1120 Ø1/2” NPT 15.0 41.35 19.85 8.0 35.0 38.0DFC-230 DFC-260 DFC-290 DFC-2120 Ø3/4” NPT 20.0 41.65 20.15 8.0 37.0 40.0DFC-330 DFC-360 DFC-390 DFC-3120 Ø1” NPT 26.0 50.0 25.0 8.0 42.0 46.0DFC-430 DFC-460 DFC-490 DFC-4120 Ø1-1/4” NPT 35.0 50.61 25.61 8.0 56.0 61.0DFC-530 DFC-560 DFC-590 DFC-5120 Ø1-1/2” NPT 40.0 51.04 26.04 8.0 60.0 65.0DFC-630 DFC-660 DFC-690 DFC-6120 Ø2” NPT 52.0 51.87 26.87 8.0 75.0 81.0_ DFC-760 DFC-790 DFC-7120 Ø2-1/2” NPT 62.0 85.90 39.90 11.0 107.0 115.0_ DFC-860 DFC-890 DFC-8120 Ø3” NPT 77.0 87.49 41.49 11.0 125.0 135.0_ DFC-960 DFC-990 DFC-9120 Ø3-1/2” NPT 88.0 93.76 42.76 11.0 165.0 178.0_ DFC-1060 DFC-1090 DFC-10120 Ø4” NPT 102.0 95.03 44.03 11.0 175.0 185.0

Ordering Requirements and Dimension

Page 19: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B19/21

B

Approx. Weight ; 0.080 kgs.

Conduit Fitting: Drain Fitting, DDF Series

Flameproof and Dust protection by enclosureZone 1 & 2 _ 21 & 22

The DDF drain fitting is installed at bottom of enclosure or conduit fitting to drain water formed by condensation.

Application

Body material : Stainless steelSize : 1/2 inch NPT or M20x1.5

Technical Data

Catalogue Number Logic

DDF -

Series Entries threadsM1 M20x1.5N1 1/2" NPT

Hazardous Area Gas DustZones 1 & 2 21 & 22Equipment Group/Category II 2G II 2DSymbol of Protection Ex db IIC Gb Ex tb IIIC Db IP66Certificate TÜV CY 20 ATEX 0206299 UConformity to Standards EN 60079-0:2012+A11:2013, EN 60079-1:2014,

EN 60079-7:2015, EN 60079-31:2014Ambeint Temperature -20oC to +75oCIndex of Protection IP66

Page 20: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020B20/21

B CL clamp

CLB back clamp

Conduit Fitting: Clamp and Back Clamp/ Bracket Clamp, CL and CLB/ BC Series

CL clamps and CLB back clamps are used for fixing the rigid steel conduit (RSC), intermediate metal conduit (IMC) or cable in dry, wet or corrosive locations. CL clamps are used for fixing the conduit or cable

running on surface. CLB back clamps are used with CL clamps to provide

space between conduit and surface.

Application

Body material : Marine grade copper-free aluminium alloy with polyester powder coated, RAL 7032 (Grey)Standard size : 1/2 to 4 inches conduit size

Ordering Requirements and Dimension

Clamp and Back Clamp

Backet Clamp

BC bracket clamps are used for supporting and fixing the rigid steel conduit (RSC), intermediate metal conduit (IMC) or cable in dry, wet or corrosive location.

Application

Body material : Marine grade copper-free aluminium alloy with polyester powder coated, RAL 7032 (Grey)Screw and washer : Stainless steel

Ordering Requirements and Dimension

FlameproofZone 1 & 2 _ 21 & 22

Cat. No.Conduit

Size(inch)

Dimension in mm.

a b c d e f g h i j ø k

BC 1 1/2" 18.0 24.0 72.0 60.0 61.0 30.0 45.0 45.0 14.0 14.0 12.0BC 2 3/4" 23.0 30.0 83.0 60.0 76.0 30.0 50.0 57.0 14.0 14.0 12.0BC 3 1" 30.0 36.0 83.0 60.0 80.0 30.0 50.0 57.0 14.0 14.0 12.0BC 4 1-1/4" 38.0 46.0 111.0 60.0 84.0 30.0 65.0 57.0 14.0 14.0 12.0BC 5 1-1/2" 44.0 52.0 111.0 60.0 87.0 30.0 65.0 57.0 14.0 14.0 12.0BC 6 2" 56.0 63.0 145.0 72.0 124.0 36.0 80.0 87.0 17.0 17.0 14.0BC 7 2-1/2" 69.0 76.0 145.0 72.0 131.0 36.0 80.0 87.0 17.0 17.0 14.0BC 8 3" 84.0 92.0 187.0 90.0 167.0 45.0 100.0 115.0 20.0 20.0 14.0BC 9 3-1/2" 96.0 106.0 187.0 90.0 173.0 45.0 100.0 115.0 20.0 20.0 14.0BC 10 4" 109.0 120.0 187.0 90.0 179.0 45.0 100.0 115.0 20.0 20.0 14.0

Cat. No. ConduitSize

(inch)

Dimension in mm.

Clamps BackClamps a b c d e f g h ø i

CL 1 CLB 1 1/2" 20.0 19.0 30.0 22.0 10.0 8.0 70.0 16.0 6.0CL 2 CLB 2 3/4" 25.0 23.0 33.0 22.0 11.0 8.0 77.0 16.0 6.0CL 3 CLB 3 1" 31.0 28.0 39.0 24.0 12.0 10.0 85.0 16.0 7.0CL 4 CLB 4 1-1/4" 40.0 35.0 47.0 28.0 14.0 10.0 98.0 25.0 8.0CL 5 CLB 5 1-1/2" 44.0 38.0 54.0 28.0 14.0 10.0 105.0 25.0 8.0CL 6 CLB 6 2" 58.0 47.0 68.0 35.0 14.0 12.0 127.0 29.0 8.0CL 7 CLB 7 2-1/2" 73.0 52.0 86.0 35.0 16.0 12.0 145.0 31.0 8.0CL 8 CLB 8 3" 87.0 60.0 102.0 35.0 16.0 13.0 160.0 35.0 8.0CL 9 CLB 9 3-1/2" 97.0 66.0 113.0 35.0 16.0 13.0 182.0 35.0 8.0CL 10 CLB 10 4" 105.0 70.0 120.0 35.0 21.0 13.0 188.0 35.0 8.0

Page 21: CABLES AND CONDUIT FITTINGS B

Visit our website at www.alloyindustry.comor contact us at +66 (0) 2434 3688 © June 2020 B21/21

B

PG1 Premium Grade Performance Grease

Protect Flameproof Joint Against Corrosion

For use Ex-equipments’ joints. Resulting in easy-to-open rust-free surface.

Application

Exclusive for Alloy Industry’s Ex-equipments. Withstands extreme pressure and temperrature

(max. at 190°C continuously) Suitable for high vibration locations. Oxidation resistant

Feature