canopen-lift shaft installation · the diagram shows plugs for zetadyn-fc. for other manufacturers...
TRANSCRIPT
CANopen-LiftShaft installation
W+W
AufzugkomponentenGmbH u. Co.KG
W+W
© W+W 09/2015 2
General information:The assembled cables and elements are used for the connection of differentcomponents of CANopen-Lift-products. It generally applies:- BUS length (main line): ≤ 200m (at baud-rate 250kBit/s)- Design the stub lines as short as possible: ≤ 6m- Stub lines shall not be longer than 60m in total. - Stub lines that are longer than 60m in total: With the prior consent of the control manufacturer a repeater or a second power supply may be needed.- At most 127 participants (nodes) at each BUS.- The main line has to be closed with a terminating resistor of 120Ω at both ends, to avoid reflexions. This is also necessary at very short cable lengths!More information about technics and suppliers see http://de.canopen-lift.org
CANopen-Lift, Technical information
Technical data connector systemSocket housing 4-pole (AMP):Operating temperature: -40° to +105°CFlammability: UL 94V-2RoHS compliantSocket contact:Maximum current: 9AMaximum voltage: 600V AC
Plug housing 4-pole (AMP):Operating temperature: -40° to +105°CFlammability: UL 94V-2RoHS compliantPlug contact:Maximum current: 9AMaximum voltage: 600V AC
Technical data cables:
Cable without sheathing:Lead insulation: PVCMaterial of conductor: Copper strand, bareConductor cross section: 0.75mm² or 1.5mm²Operating temperature: -5° to +70°C (permanently laid)Lead resistance: 26.0Ω/km (with 0.75mm²)Lead resistance: 13.3Ω/km (with 1.5mm²)Rated voltage: 500VTwisted pairs: black/red and blue/white
Sheathed cable:Material of sheathing*: PVC,type YI2 acc. to VDE 0207 Part 4Lead insulation*: PVC,type YM2 acc. to VDE 0207 Part 5Material of conductor: Copper strand, bareConductor cross section: 0.75mm² or 1.5mm²Diameter: 8.3mm (with 0.75mm²)Diameter: 10.1mm (with 1.5mm²)Operating temperature: -30° to + 80°C (permanently laid)Lead resistance: 26.0Ω/km (with 0.75mm²)Lead resistance: 13.3Ω/km (with 1.5mm²)Rated voltage: 500VTwisted pairs: black/red and blue/whiteReaction to fire*: self-extinguishing and flame-retardant acc. to IEC 60332-1LBS-free and silicone free (when manufacturing)*non halogen type:Material of sheathing + lead insulation: special non-halogen compoundReaction to fire: flame-retardant acc. to IEC 60332-1-2
Colour Functions
red 24V DC
black 0V
blue CAN_L
white CAN_H
Colour code for CANopen-Lift:
© W+W 09/2015 �
Art.nostandard
Art.nonon-halogen
Description
211�9 21150 BUS-Main line 1.5mm² 1m So/So
21101 21151 BUS-Main line 1.5mm² 2m So/So
21105 21152 BUS-Main line 1.5mm² �m So/So
21102 2115� BUS-Main line 1.5mm² 4m So/So
21140 21154 BUS-Main line 1.5mm² 5m So/So
2110� 21155 BUS-Main line 1.5mm² 7m So/So
21104 21156 BUS-Main line 1.5mm² 10m So/So
21120 21157 BUS-Main line (extension) 1.5mm² 5m Pl/So
21121 21158 BUS-Main line (extension) 1.5mm² 10m Pl/So
21122 21159 BUS-Main line (extension) 1.5mm² 20m Pl/So
2112� 21160 BUS-Main line (extension) 1.5mm² �0m Pl/So
21124 21161 BUS-Main line (extension) 1.5mm² 40m Pl/So
21125 21162 BUS-Main line (extension) 1.5mm² 50m Pl/So
Art.nostandard
Art.nonon-halogen
Description
21118 2116� BUS-Stub line 0.75mm² 1m Pl/So
21106 21164 BUS-Stub line 0.75mm² �m Pl/So
21107 21165 BUS-Stub line 0.75mm² 6m Pl/So
Art.nostandard
Art.nonon-halogen
Description
21119 21166 BUS-Stub line 0.75mm² 1m Pl/We
21108 21167 BUS-Stub line 0.75mm² �m Pl/We
21109 21168 BUS-Stub line 0.75mm² 6m Pl/We
21110 21169 BUS-Stub line 1.5mm² �m Pl/We
21111 21170 BUS-Stub line 1.5mm² 6m Pl/We
Art.nostandard
Art.nonon-halogen
Description
21100 N/A BUS-Line Y-adaptor 0.75mm² Pl/Pl/So 0.25
211�0 N/A BUS-Line Y-adaptor 0.75mm² Pl/Pl/So 0.80
CANopen-Lift, Assembled cablesMain line, sheathed cable, different lengths e.g. for the connection between the floors
Stub line, without sheathed (Y-Adaptor),e.g. for the tap of the landing panel, indicators, etc.
10cm
25cm
Stub line for buttons and indicators with AMP-plug
Stub line for buttons, indicators or other BUS-devices with screw terminals
Main line, sheathed cable, different lengths, e.g. for long ways to the shaft head/pit or for extension
80cmor
Socket Socket
SocketPlug
Plug Plug
Socket
SocketPlug
Plug Wire end sleeves
© W+W 09/2015 4
CANopen-Lift, Accessories
Transfer module for the hat rail, e.g. for the installation in the lift controlArt.no. Description
21114 BUS transfer module
BUS-Cable Art.no. Description
51450 BUS cable 2x2x0.75mm² sheathed
51429 BUS cable 2x2x1.5mm² sheathed
64009 BUS cable 2x2x0.75mm²
6�095 BUS cable 2x2x1.5mm²
10cm
Art.no. Description
21115 BUS terminating resistor 120Ohm So
Resistor is insulated with plastic material, 120Ω (±1%) / 0.6W
Art.no. Description
21117 BUS Adaptor Bu/D-Sub 9pol bp
Art.no. Description
21116 BUS-Stub line 0.75mm² �m Pl/Zetadyn �/4
Stub line sheathed 0.75mm² 3m with plug suitable for Ziehl-Abegg ZETADYN 4C and 3C
Art.no. Description
21129 BUS cable 0.75mm² �m So/AT40
Side 1: Plug 4-poleSide 2: Clamping connector 4-pole suitable for ZETADYN 4C / 3C
Art.no. Description
211�7 BUS repeater / distributor
The repeater generates a second main line in a CAN-system. This may be necessary for a group control or many stops.
Repeater / Distributor
Art.no. Description
21112 BUS-Adaptor line 0.75mm² 0.1m So/So
2111� BUS-Adaptor line 0.75mm² 0.1m Pl/Pl
Fastening fixtures 51114 Cable fixing dowels 6mm PU100
51126 Cable ties 200x4.5 PU100
Socket Socket
Plug Plug
Terminating resistor 120Ω in socket housing
Plug
Plug
Plug
Adaptor for wiring of BUS cable to absolute encoder of Böhnke+Partner
Screw terminals: Maximum cross section 2.5mm²Plug: 4-pole AMPElectric current In: Maximum 9ADimensions: LxWxH 83mm x 23mm x 58mm
Side 1: Socket 4-pole AMPSide 2: D-Sub 9pol suitable for absolute encoder of bp
Cable sheathed 0.75mm² 3m with plug suitable for door controller AT40
Side 1: Socket 4-poleSide 2: Plug 3-pole for door controller AT40The cable is connected directly to the transfer module.
© W+W 09/2015 5
Toothed belt mechanics set type-12Mechanics set for a running toothed belt. The encoder is at the shaft head room or at the shaft pit. Type-12 diameter of the encoder pulley Ø ≈ 80mmTechnical data:max. hoisting height: 40m max. rated speed 1.2m/s
Toothed belt mechanics set type-14AMechanics set for a streched belt. Encoder on the elevator car.Typ-14A diameter of the encoder pulley Ø ≈ 150mmTechnical data:max. hoisting height: 180m, max. rated speed 4m/s
Art.no. Description
52686 Mechanics set type-12 with AWG CANopen lift
Art.no. Description
52684 Mechanics set type-14A with AWG CANopen lift
Technical data absolute encoder:- Operating voltage: 10 - 32VDC- Output: CANopen LIFT CiA 417- Complete galvanic isolation- Multiturn technology: without battery and gear box- integrated terminating resistor 120Ω- Protection type AWG: IP67 (IP65 at the shaft inlet)- incl.10m supply line with AMP-socket for BUS connection
Toothed belt 5mm for type-12 and type-14A
CANopen-Lift, Shaft copying systems
Art.no. Length Art.no. Length Art.no. Length
9272 15m 9226 45m 9209 90m
922� 20m 9184 50m 9210 100m
9224 25m 9227 55m 9282 120m
9182 �0m 9185 60m 9256 140m
9225 �5m 9207 70m 92�0 160m
918� 40m 9208 80m 9266 200m
RMSRMS
Art.no. Description
on request ELGO LIMAX02 CiA417 CANopen with termination 120Ω
21189 ELGO fastening angle for LIMAX02
21190 ELGO magnetic tape AB20
21187 ELGO magnetic Tape Installation Kit RMS
21188 ELGO magnetic Tape Installation Kit RMS90
LIMAX 02 is an absolute measuring shaft information system that is used for positioning of lift cabins. The magnetic measurement principle is extremely robust. Dust, dirt and humidity do not aff ect the measurement in any way. Also, smoke and even higher temperatures have no infl uence on the measuring quality. Therefore, LIMAX02 is particularly suited for application in fi reman‘s lifts. Another advantage of the system is the simple and fl exible installation. Typical installation time will take less than an hour by a versed technician. Travel heights up to 260 metres and speeds up to 10m/s can be covered. The sensor head is always mounted at the car.
The magnetic band is suitable for all types of the sensor head LIMAX02. It is deli-vered cut to length (by metre) and commissioned in a special cardboard box. The maximum length available is 185m (longer lengths on demand).
© W+W 09/2015 6
-1
0
1
Ground rules:
- at most 127 BUS participants (nodes)- BUS length (main line): ≤ 200m- Stub lines as short as possible: ≤ 6m- Stub lines in total ≤ 60m* Stub line in total ≥ 60m: With the prior consent of the control manufacturer a repeater (see page16) or a second power supply may be needed.- Terminating resistor of 120Ω at both ends of the main line. At the BUS (blue/white) a resistance of approximately 60Ω has to be measurable.- The resistance can also be integrated into the last BUS participant.
Indication: Some BUS participants have an integrated terminating resistor, which cannot be switched off.
CANopen-Lift, general informationGenerally the topology of a BUS can be arranged freely. However some ground rules have to be respected.The following examples represent only a few of the many possibilites of arragement and can be modified or complemented as needed.
Control
FC
Highest landing
2.-n. landing
1. landing
Y-adaptor with separate stub line
The lift call button is close to the main line.
Stub line with wire end ferrules: For participants with screw terminals
Y-adaptor with 80cm outgoing line
Absolute encoder
Door controller
Lift panel
Control box on the car roof
Travelling cable
Frequency converter
Terminating resistor
The diagram shows plugs for Zetadyn-FC. For other manufacturers use a stub line with wire end ferrules or other plugs on request.
Stub line with socket (e.g. for lift panels manufactured by Schaefer )
To simplify matters, in all topologies only two conductors are shown.
* In rare cases it is necessary to use a repeater, even if the total stub line length is Σ<60m.
Assembling aid:Stub lines and their exits at the Y-adaptors are marked with blue plugs and sockets.Blue = stubWhite = main line
© W+W 09/2015 7
-1
0
1
CANopen-LiftMachine room above, absolute encoder on the car roof, control only with CAN 1
Art.no. 21100
Art.no. 21116Stub line 3m to the converter ZA
Y-adaptor
Travelling cable
Control
Machine room
Car
Highest landing
2.-n. landing
1. landing
FC
Transfer module CAN 1 in the control (not terminated)
Art.no. 21130Y-adaptor
Y-adaptor with 80cm outgoing line to the lift call button.
Door controller
Lift panel
Control box on the car roof
Absolute encoder on the car roof, terminated*
Art.no. 21115Terminating resistor
*If an absolute encoder without termination is used, this has to be effected in the cabin panel or the door controller.
Art.no. 21129Stub line 3m to the door controller AT40
The lift call button is close to the main line.
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
The diagram shows plugs for Zetadyn-FC. For other manufacturers use a stub line with wire end ferrules or other plugs on request.
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 8
CANopen-LiftMachine room above, absolute encoder in the pit, control only with CAN 1
Control box on the car roof
Art.no. 21100Y-adaptor
Absolute encoder in the pit (terminated)
Travelling cable
Lift panelterminated
Control
Machine room
CarArt.no. 21118 / 21106 / 21107Stub line 1m, 3m or 6m to the lift call button
Highest landing
2.-n. landing
1. landing
FC
Transfer module CAN 1 in the control (not terminated)
Door controller
Art.Nr. 21119 / 21108 / 21109Stub line 1m, 3m or 6m to the frequency converter
Art.no. 21129Stub line 3m to the door controller AT40
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
-1
0
1
© W+W 09/2015 9
CANopen-LiftControl below, frequency converter in the shaft head room, absolute
encoder on the car roof, control only with CAN 1
Head room
Highest landing
2.-n. landing
1. landingTravelling cable
Control
Transfer module CAN 1 in the control (not terminated)
Art.no. 21100Y-adaptor
Art.no. 21115Terminating resistor
Art.no. 21118 / 21106 / 21107Stub line 1m, 3m or 6m to the lift call button
FC
Car
Door controller
Lift panel
Control box on the car roof
Absolute encoder on the car roof (terminated*)
*If an absolute encoder without termination is used, this has to be effected in the cabin panel or the door controller.
Art.no. 21116Stub line 3m to the converter ZAThe diagram shows plugs for Zetadyn-FC. For other manufacturers use a stub line with wire end ferrules or other plugs on request.
Art.no. 21112Adaptor piece 20cm
Art.no. 21129Stub line 3m to the door controller AT40
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
-1
0
1
© W+W 09/2015 10
-1
0
1
CANopen-LiftControl below, frequency converter and absolute encoder in the shaft head
room, control only with CAN 1
Art.no. 21100
Art.no. 21116Stub line 3m to the converter ZA*
Y-adaptor
Art.no. 21112Adaptor piece 20cm
Absolute encoder in the shaft head room (terminated)
The lift call button is close to the cable duct or the main line.
Travelling cable
Head room
Control
Highest landing
2.-n. landing
1. landing
Art.no. 21130Y-adaptor
Y-adaptor with 80cm outgoing line to the lift call button.
Lift panelterminated
Car
Transfer module CAN 1 in the control (not terminated)
FC
Control box on the car roof
Door controller
Art.no. 21129Stub line 3m to the door controller AT40
The diagram shows plugs for Zetadyn-FC. For other manufacturers use a stub line with wire end ferrules or other plugs on request.
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 11
-1
0
1
CANopen-LiftMachine room above, absolute encoder on the car roof, control with CAN 1 and CAN 2
Art.no. 21130Y-adaptor
Y-adaptor with 80cm outgoing line to the lift call button.
Transfer module CAN 1 in the control (not terminated)
Travelling cable
Control
Machine room
Transfer module CAN 2 in the control (not terminated)
Art.no. 21115Terminating resistor
Highest landing
2.-n. landing
1. landing
The lift call button is close to the cable duct or the main line.
Car
FC
Door controller
Absolute encoder on the car roof (terminated*)
*If an absolute encoder without termination is used, this has to be effected in the cabin panel or the door controller.
Art.no. 21119 / 21108 / 21109Stub line 1m, 3m or 6m to the frequency converter
Control box on the car roof
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 12
-1
0
1
CANopen-LiftMachine room above, absolute encoder in the shaft head room, control with
CAN 1 and CAN 2
Art.no. 21100
Art.no. 21116Stub line 3m to the frequency converter
Y-adaptor
Absolute encoder in the shaft head room (terminated)
Transfer module CAN 2 in the control (not terminated)
Travelling cable
Lift panelterminated
Control
Machine room
Transfer module CAN 2 in the control (not terminated)
Car
Art.no. 21118 / 21106 / 21107Stub line 1m, 3m or 6m to the lift call button
Art.no. 21115Terminating resistor
Highest landing
2.-n. landing
1. landing
FC
Door controller
Art.no. 21129Stub line 3m to the door controller AT40
Control box for the car roof
The diagram shows plugs for Zetadyn-FU. For other manufacturers use a stub line with wire end ferrules or other plugs on request.
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 1�
-1
0
1
CANopen-LiftMachine room below, absolute encoder in the pit, control with CAN 1 and CAN2
Art.no. 21116Stub line 3m to the converter ZA
Absolute encoder in the pit (terminated)
Pit
Machine room
Travelling cable
Control
Transfer module CAN 1 in the control (not terminated)
Transfer module CAN 2 in the control (terminated)
Art.no. 21130Y-adaptor
Y-adaptor with 80cm outgoing line to the lift call button.
Highest landing
2.-n. landing
1. landing
Lift panelterminated
Car
Art.no. 21115Terminating resistor
FC
Control box for the car roof
Door controller
Art.no. 21129Stub line 3m to the door controller AT40
The diagram shows plugs for Zetadyn-FC. For other manufacturers use a stub line with wire end ferrules or other plugs on request.
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 14
-1
0
1
CANopen-LiftControl below, absolute encoder and frequency converter in the shaft head
room, control with CAN 1 and CAN 2
Art.no. 21116Stub line 3m to the converter ZA
Absolute encoder in the shaft head room (terminated)
Travelling cable
Control
Transfer module CAN 1 in the control (not terminated)
Transfer module CAN 2 in the control (terminated)
Lift panelterminated
Car
FC
Control box for the car roof
Door controller
Art.no. 21129Stub line 3m to the door controller AT40
Head room
Highest landing
2.-n. landing
1. landing
Art.no. 21100Y-adaptor
Art.no. 21118 / 21106 / 21107Stub line 1m, 3m or 6m to the lift call button
Art.no. 21120 - 21125Main line, available in:5m, 10m, 20m, 30m, 40m, 50m
Art.no. 21115Terminating resistor
The diagram shows plugs for Zetadyn-FC. For other manufacturers use a stub line with wire end ferrules or other plugs on request.
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 15
CANopen-Lift, group of 2, stub lines <60mGroup control, without repeaterOnly CAN 2 is shown. CAN 1 (absolute encoder, frequency converter, door controller, cabin panel, etc.) has to be laid separately for each lift. See also the previous examples.
Machine room
Highest landing
2.-n. landing
1. landing
Display lift 2,highest landing
Display lift 2,2.-n. landing
Display lift 1,highest landing
Display lift 1,2.-n. landing
Display lift 1,lowest landing
Lift call button group,2.-n. landing
Lift call button group,lowest landing
Lift call button group,highest landing
Display lift 2,lowest landing
Art.no. 21130Y-adaptor with 80cm outgoing line to the lift call button.
Art.no. 21139Main line 1m
Art.no. 21112Adaptor piece 20cm
Art.no. 21118 / 21106 / 21107Stub line 1m, 3m or 6m to the display
Art.no. 21115Terminating resistor
Control 12x transfer modules CAN 2 in the
control (not terminated)
Control 2Transfer module CAN 2 in the control (terminated)Group
connection*
* The group connection can be made with individual cables from the control manufacturers.
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 16
CANopen-Lift, group of 2, stub lines >60mGroup control, the repeater is located externally in the shaft. Only CAN 2 is shown.
Machine room
Highest landing
2.-n. landing
1. landing
Control 12x transfer modules CAN 2 in the
control (not terminated)
Display lift 2,highest landing
Display lift 2,2.-n. landing
Display lift 1,highest landing
Display lift 1,2.-n. landing
Display lift 1,lowest landing
Lift call button group,2.-n. landing
Lift call button group,lowest landing
Lift call button group,highest landing
Display lift 2,lowest landing
Art.no. 21130Y-adaptor with 80cm outgoing line to the lift call button.
Art.no. 21118 / 21106 / 21107Stub line 1m, 3m or 6m to the display
Art.no. 21137Repeater
Art.no. 21115Terminating resistor
Repater / distributor:The repater generates a second main line. For the second main line the following rules apply again:- BUS length (main line): ≤ 200m- Stub lines as short as possible: ≤ 6m- Terminating resistor of 120Ω at the ends of the main line.Important:The number of participants (nodes) in the whole CAN 2 is still limited to 127.
Mai
n lin
e 2
(ter
min
ated
)
Mai
n lin
e 1
Shaft head room
Control 2Transfer module CAN 2 in the control (terminated)Group
connection*
* The group connection can be made with individual cables from the control manufacturers.
Art.no. 21139 / 21101-05
Art.no. 21139Main line 1m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
Main line, available in:1m, 2m, 3m, 4m, 5m, 7m, 10m
© W+W 09/2015 17
CANopen-Lift, group of 3, stub lines >60mGroup control, the repeater is located externally in the shaft. Only CAN 2 is shown.
Machine room
Highest landing
2.-n. landing
1. landing
Control 1
Display lift 3,highest landing
Display lift 3,2.-n. landing
Display lift 1,highest landing
Display lift 1,2.-n.landing
Display lift 1,lowest landing
Lift call button group,2.-n. landing
Lift call button group,lowest landing
Lift call button group,highest landing
Display lift 3,lowest landing
Repeater
Mai
n lin
e 2
(ter
min
ated
)
Mai
n lin
e 1
Head room
Display lift 2,highest landing
Display lift 2,2.-n. landing
Display lift 2,lowest landing
Lift call button group,2.-n. landing
Lift call button group,lowest landing
Lift call button group,highest landing
Control 3Control 2
Groupconnection*
* The group connection can be made with individual cables from the control manufacturers.
Groupconnection*
(not terminated) (not terminated) (not terminated)
© W+W 09/2015 18
CANopen-Lift, group of 3, stub lines >60mGroup control, the repeater is located in the control. Only CAN 2 is shown.
Machine room
Highest landing
2.-n. landing
1. landing
Control 1
Display lift 3,highest landing
Display lift 3,2.-n. landing
Display lift 1,highest landing
Display lift 1,2.-n. landing
Display lift 1,lowest landing
Lift call button group,2.-n. landing
Lift call button group,lowest landing
Lift call button group,highest landing
Display lift 3,lowest landing
Display lift 2,highest landing
Display lift 2,2.-n. landing
Display lift 2,lowest landing
Lift call button group,2.-n. landing
Lift call button group,lowest landing
Lift call button group,highest landing
Control 3Control 2
Groupconnection*
* The group connection can be made with individual cables from the control manufacturers.
Groupconnection*
(not terminated)Output above an internal
repeater, terminated (not terminated)
Output
© W+W 09/2015 19
CANopen-Lift, notes
International representatives:
Errors and changes excepted.
Erkrather Straße 264-26640233 Düsseldorf
Germany
Phone: +49 (0)211-73848-183Fax: +49 (0)211-73848-90
e-mail: [email protected]: www.wwlift.de
Erkrather Straße 264-266
W+W
AufzugkomponentenGmbH u. Co.KG
W+W
Our off ers are exclusively addressed to the lift specialised trade.
© W+W 2015
Distribution AustriaHAIDER Steuerungstechnik GmbHBetriebsring 32483 EbreichsdorfPhone: +43 (0) 2254 / 747774Fax: +43 (0) 2254 / 747777www.haider-gmbh.atoffi [email protected]
Distribution BelgiumELVA AGNispert 5A4700 EupenPhone: +32 (0) 87 743 411Fax: +32 (0) 87 743 [email protected]
DistributionNetherlandsWITTUR BVRemmingweg 181332 BG AlmerePhone: +31 (0) 36-5495570Fax: +31 (0) [email protected]
Distribution Great BritainELEVATOR EQUIPMENT LIMITEDUnit 16, Abbey Court, Wallingford Rd.Leicester, LE4 5RDPhone: +44 (0) 116 266 2241Fax: +44 (0) 116 266 2242www.elevatorequipment.co.uk [email protected]
Distribution FranceBEAUVILLIER J.Pierre2 chemin du TeldesLe Butassin48340 Saint Germain du TeilPhone: +33 (0) 466 323 782Mobile: +33 (0) 608 895 [email protected]
Distribution SwitzerlandMASORA AGIndustriestr. 25d9524 ZuzwilPhone: +41 (0) 71 945 60 00Fax: +41 (0) 71 945 60 [email protected]
DistributionSweden, Norway, FinlandWITTUR Sweden ABDomnarvsgatan 35163 53 SpångaPhone: +46 (0) 8 564 755 40Fax: +46 (0) 8 564 755 [email protected]
DistributionSpain, Portugal CETEC COMPONENTES, S.L.Pol. Ind. San Lorenzo, Nave 548390 VizcayaPhone: +34 (0) 94 631 36 91Fax: +34 (0) 94 631 35 [email protected]