CARLYLE 104 MM SCREW COMPRESSORS

06N CARLYLE SEMI-HERMETIC COMPRESSORS

132

CARLYLE REFRIGERATION COMPRESSORS

GENERAL NOTES on Refrigeration Screw Compressors 05T & 06TCompressors are shipped with service valves attached to the compressor pallet and have blankoff pads bolted over service valve open-ings. Alternate suction and discharge service valves are available.

All 06T screw compressors are suitable for across-the-line or part winding start. Customer is required to hook up terminal plate for appli-cable voltage. Wiring diagrams and jumpers are included in the compressor terminal box. Compressor part number on nameplate is the same as the package ordering number.

All 05T and 06T compressors:a. Are dehydrated and have a dry air holding charge.b. Have no oil charge. Oil must be added to fill the entire oil system from the oil solenoid at compressor back to the oil separator.

Carlyle requires the following accessories to protect both 05T and 06T compressors:- oil separator - oil level switch- oil filter housing - reverse rotation protection switch- oil pressure differential switch - Carlyle Electronic Module- high pressure switch - low pressure switch

The 06T Compressor further requires:- C-Flange - coupling

06T screw compressors provided WITHOUT motor overcurrent protection, which MUST be supplied by the customer. Heinemann cali-brated circuit breakers specifically selected for each motor and voltage are a required accessory. All 06T compressor models are UL and CSA approved. The use of authorized overcurrent protection is part of UL recognition.

All 06T compressors are provided with a 5K thermistor installed in the compressor motor to monitor the motor temperature. The CEM is required with each 06T to monitor this thermistor.

All compressors are painted green.

133

CARLYLE REFRIGERATION COMPRESSORS

05T (74 mm) SCREW COMPRESSOR

Design Duty: Commercial RefrigerationQualified For: HCFC Refrigeration Duty

HFC Refrigeration DutyR-22/407C Water Cooled DutyR-134a Air Cooled Duty

Capacities:cfm @ 60 Hz 33 39 44 49 54 65 78 88 m3 /hr @ 50 Hz

Economizer: Optional on all modelsVi: Dual Vi Option

Configuration: Open DriveCheck Valve: Integral

Oil Filter: ExternalMotor Type: External

P3036

134

CARLYLE REFRIGERATION COMPRESSORS

OPEN DRIVE MODELS - For All Temperature Ranges With Service Valves

NOTE: APPLICATION LIMITS.R-134a - Medium temperature

- Air ConditionR-22 - Low temperature

- Medium temperature- Air Conditioning

R-404A/R-507 - Low temperature- Medium temperature

ACCESSORIES FOR 05T MODELS

05T COUPLING PACKAGE

05T C-FLANGE PACKAGE

MODEL NO.DISPLACEMENT (CFM)

MOTOR HP

APPROX.SHIP. WEIGHT

(kg)1750 RPM

Motor (4 pole)3500 RPM

Motor (2 pole)05TRQ033Z3EA-A00 33 65 N/A 9105TRQ039Z3EA-A00 39 78 N/A 9105TRQ044Z3EA-A00 44 88 N/A 9105TRQ048Z3EA-A00 48 N/A N/A 9105TRQ054Z3EA-A00 54 N/A N/A 91

COUPLINGPKG

MOTOR SHAFTDIAMETER

(in.)

4 POLE MOTOR1750 Rpm @ 60 Hz1450 Rpm @ 50 Hz

2 POLE MOTOR3500 Rpm @ 60 Hz3000 Rpm @ 50 Hz

APPROX.SHIP. WT

(kg)Hp NEMA Frame Size Hp NEMA Frame Size

8TA0868B 1 5/8 15, 20 254TC, 256TC 30 286TC 5

8TA0869B 1 7/8 25, 30 284TC, 286TC40, 5060, 75

324TSC, 326TSC,364TSC, 365TSC

5

8TA0870B 2 1/8 40, 50 324TC, 326TC N/A N/A 5

C-FLANGEPKG

4 POLE MOTOR1750 Rpm @ 60 Hz1450 Rpm @ 50 Hz

2 POLE MOTOR3500 Rpm @ 60 Hz3000 Rpm @ 50 Hz

APPROX.SHIP. WT

(kg)Hp NEMA Frame Size Hp NEMA Frame Size

0TA092915, 20,35, 30

254TC, 256TC,284TC, 286TC

N/A N/A 25

0TA0930 25, 30 284TC, 286TCN/A

60, 75N/A 25

0TA0931 N/A N/A40, 5060, 75

286TC, 324TSC,226TSC, 364TSC,

365TSC25

135

CARLYLE REFRIGERATION COMPRESSORS

06T SCREW COMPRESSOR

†Economized (°F).

06T Model Number Significance

CAPACITY (Btu/Hr) @ 60 HzRefrigerant R-22 R-507/404A R-22 R-507/404A R-134aConditions† -25/110/65 -25/110/65 20/110/65 20/110/65 45/130/65

06T**033 51,000 70,900 131,500 143,100 127,90006T**039 62,700 86,100 161,000 175,000 156,80006T**044 72,100 98,900 182,800 199,000 177,70006T**048 80,100 11,000 203,100 221,100 194,30006T**054 91,900 126,100 233,100 253,700 222,80006T**065 113,900 156,400 292,500 318,400 284,10006T**078 140,200 192,000 354,300 385,700 342,40006T**088 159,800 218,700 400,900 436,300 387,500

P3035

136

CARLYLE REFRIGERATION COMPRESSORS

COMPRESSOR PHYSICAL DIMENSIONS

P3031 P3032

P3033

137

CARLYLE REFRIGERATION COMPRESSORS

LOW TEMPERATURE DUTY - Semi-Hermetic With Service Valves

NOTE: APPLICATION LIMITS.R-134a - Medium temperature

- Air ConditioningR-22 - Low temperature

R-404A/R-507 - Low temperature

06TRK model satisfactory for use on high temp, medium temp and low temp applications.

MODEL NO.VOLTAGE3 PHASE MOTOR

HP

APPROX.SHIP. WEIGHT

(kg)60 HZ 50 HZ06TRC033B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-15 166

06TRD039B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-20 172

06TRD044B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-20 172

06TRE048B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-25 177

06TRE054B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-25 177

06TRF065B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-30 181

06TRG078B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-35 184

06TRH088B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-40 184

06TRK108B2EA-A00NOTE: 50Hz Applications Only

n/a 400 50 186

138

CARLYLE REFRIGERATION COMPRESSORS

MEDIUM/HIGH TEMPERATURE DUTY - Semi-Hermetic With Service Valves

NOTE: APPLICATION LIMITS.R-22 - Low temperature

- Air Conditioning (High Temperature)

R-404A/R-507 - Medium temperature

MODEL NO.VOLTAGE3 PHASE MOTOR

HP

APPROX.SHIP. WEIGHT

(kg)60 HZ 50 HZ06TAD033B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-20 164

06TAE039B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-25 171

06TAF044B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-30 171

06TAF048B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-30 176

06TAG054B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-35 176

06TAG065B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-35 180

06TAH078B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-40 182

06TAK088B2EA-A00 F2EA-A00 C2EA-A00

460208/230

575

400200

-50 187

139

CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES

05T/06T REFRIGERATION COMPRESSOR ACCESSORIESELECTRONIC PHASE MONITOR (REVERSE ROTATION PROTECTION)

(See Notes Below)

NOTES:1. Protects screw compressor from reverse rotation by monitoring 3-phase input power to compressor motor. Will not allow compressor to start if

sequence is incorrect.2. This phase monitor will not operate with a variable speed drive inverter.3. May be used in place of reverse rotation switch; (1) per compressor.

RUBBER ISOLATION MOUNTS

(1 Package Per Compressor Recommended)

MUFFLERS

(1 Per Compressor Required)

OIL SEPARATORS

(1 Per Rack Required)

NOTES:1. Oil Separators supplied with multiple sight glasses to view oil level.2. Oil Separators has adapter fitting at bottom to connect KH13LB004 Oil Level Float Switch.

PART NO. QTY/PKG WEIGHT (kg) USAGEP251-0090 1 1.5 ALL 05/6T compressors

PART NO. QTY/PKG WEIGHT (kg) USAGEKA75KR002 4 0.5 ALL 05/6T compressors

PART NO. QTY/PKG WEIGHT (kg) INLET/OUT LENGTH USAGE

LM10HH162 1 3 1-5/8” 9-3/4″ All 05/6T compressor

PART NO. MOUNTING LINE SIZE (0. WT (kg) DIA. USAGEKH31ZZ340KH31ZZ212

VERTICALVERTICAL

2-1/8″2-5/8″

66120

12″14″

Single Comp.Multiple Comp.

140

CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES

05T/06T REFRIGERATION COMPRESSOR ACCESSORIESOIL LEVEL SWITCH

(1 Per Oil Separator Required)

NOTE:1. Protects compressor against loss of oil in Oil Separator. Screws into bottom.

HEATER FOR OIL SEPARATOR / OIL RESERVOIR

(2 Per Oil Separator Recommended)

NOTE:1. Heater applied to oil separator to keep refrigerant from accumulating in it during off cycles.

See application guide for application requirements.

AIR-COOLED OIL COOLERS

(See Application Guide for Requirements)

OIL FILTER HOUSING ASSEMBLY

(2 Per Rack Required)

NOTES:1. Oil Housing which allows replacement of filter cartridge.2. Filter Housing assembly includes (1) 3 micron filter cartridge.3. (2) per rack recommended.

PART NO. QTY/PKG WEIGHT (kg) USAGEHK13LB004 1 0.5 On vertical oil separators

PART NO. QTY/PKG WEIGHT (kg)ELECTRICAL CHARACTERISTICS

VOLTS WATTSHK38KN007 1 0.5 115/230 500

PART NO.NO. OF COMPS.

@ LOADWEIGHT (kg)

ELECTRICAL CHARACTERISTICSVOLTS/1 PH HZ

KH51ZZ181 2 23 115/230 V - 1 PH 60/50 HZKH51ZZ182 3 57 115/230 V - 1 PH 60/50 HZKH51ZZ183 4 91 115/230 V - 1 PH 60/50 HZKH51ZZ184 5 98 115/230 V - 1 PH 60/50 HZ

PART NO. QTY/PKG WEIGHT (kg) CONNECTION TYPE USAGEKH18MG002 1 4 7/8″ Sweat All 05/6T Compressors

141

CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES

05T/06T REFRIGERATION COMPRESSOR ACCESSORIESOIL FILTER CARTRIDGE

NOTE:1. Carlyle recommends (3) cartridges be left at the job site per oil filter housing. Several changeouts will be necessary before the system is free of

contaminant. If the job is a remodel, more changeouts may be necessary.2. Each cartridge is supplied with (1) filter housing O ring.

PART NO. QTY/PKG WEIGHT (kg) USAGEKH39MG002 1 0.5 Replacement Cartridge for KH18MG002 housing

DESUPERHEATING

(1 Per Compressor for R-22 <-32° C & R-404A/R507 <-43C SST Systems)

PART NO. QTY/PKG WEIGHT (kg) SIZE USAGEEA02ZD001 1 1 1 ton

All 05/6TCompressors

EA02ZD002 1 1 1.5 tonEA02ZD030 1 1 2 tonEA02ZD050 1 1 3 tonEA02ZD100 1 1 5 ton

SOLENOID COILS - FOR UNLOADING AND Vi CONTROL

(1 Per 06TA Compressor Required)

(2 Per 05/6TR Compressor Required)

NOTES:1. Solenoid Coil operates either capacity control unloading mechanism or variable volume (Vi) control.2. 06TR Models require (2) per compressor, 06TA models require (1) per compressor.

PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE

EF19ZE120 1 0.5 120-1-50/60All 05/6T Compressors

EF19ZE240 1 0.5 208/240-1-50/60EF19ZE024 1 0.5 24-1-50/60

CARLYLE ELECTRONIC MODULE (CEM)

(1 Per Compressor Required)

NOTES:1. Module uses (2) 5K Thermistors, (1) embedded in motor windings and (1) strapped on discharge line (thermistor purchased separately.)2. The modules control motors and discharge cooling and acts as a safety for overheating protection.

PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGE

3TA0796B 1 0.5120/240-1-60100/200-1-50

All 05/6T Compressors

142

CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES

05T/06T REFRIGERATION COMPRESSOR ACCESSORIES5K THERMISTOR

(1 Per Compressor Required)

NOTE: One required per compressor for use with CEM to monitor discharge temperature.

PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGEHH79NZ065 1 0.5 115/240-1-60 All 05/6T Compressors

MOTOR COOLING VALVES

(1 Per Compressor Required)

NOTE: Used for motor and discharge gas cooling of screw compressors.

PART NO. QTY/PKG WEIGHT (kg) EVRP SIZE USAGEEF28BZ007 1 0.5 1.4 All 05/6T Compressors

SOLENOID COILS FOR MOTOR COOLING VALVES

(1 Per Compressor Required)

PART NO. QTY/PKG WEIGHT (kg) ELECTRICAL USAGEP510-XV120D 1 0.5 120-1-50/60

All 05/6T CompressorsP510-XV208D 1 0.5 208/240-1-50/60P510-XV024D 1 0.5 24-1-50/60

REVERSE ROTATION PROTECTION SWITCH

(1 Per Compressor Required)

NOTE: Protects screw compressor from reverse rotation.

PART NO. QTY/PKG WEIGHT (kg) USAGEHK01CB002 1 1 All 05/6T Compressors

143

CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES

05T/06T REFRIGERATION COMPRESSOR ACCESSORIESOIL PRESSURE DIFFERENTIAL SWITCH(1 Per Compressor Required)

NOTES:1. Senses oil differential between discharge pressure and oil feed to the compressor.2. Switch setting is for cutout when differential pressure above (45 psid) and has a 30 second time delay.

PART NO. QTY/PKG WEIGHT (kg) CONNECTIONVOLTAGE

INPUTUSAGE

HK06ZB006 1 2 1/4″ FLARE 115 or 230 ALL 05/6T compressors

OIL FILTER DIFFERENTIAL SWITCH

(1 Per Oil System Recommended)

NOTES:1. Senses oil differential across filters.2. Switch setting is for cutout when differential pressure exceeds 45 psid and has a 30 second time delay.

PART NO. QTY/PKG WEIGHT (KG) CONNECTIONVOLTAGE

INPUTUSAGE

HK06CA051 1 2 1/4″ FLARE 115 or 230 ALL 05/6T compressors

SUCTION AND DISCHARGE SERVICE VALVE PACKAGES

NOTES:1. (2) 06TA660001 packages are supplied with each compressor.2. All service Valve are 4 bolt, 2-1/2″ square bolt spacing. Service Valve Package contains (1) service valve (1) gasket, and (4) metric hex

head cap screws (M12 x 1,75 x 60mm).3. These Service Valve packages (except 06TA68005) are the same as the respective 06D/E packages except the mounting bolts have

metric threads.

PART NO. SIZE ODF QTY/PKG WEIGHT (kg) USAGE06TA660001 1-5/8″ 1 2

ALL 05/6T compressors05T/06T 65, 78, 88 CFM

06TA660002 1-3/8″ 1 206TA660003 1-1/8″ 1 206TA680005 1-5/8″ 1 2

ECONOMIZER SERVICE VALVE

(See Notes Below)

NOTES:1. (1) 06TA660004 package is supplied with each compressor.2. All Economizer Service Valve contain (1) Rotalock * valve, (1) O-ring, (1) seal, and (1) connection fitting.

PART NO. SIZE ODF QTY/PKG WEIGHT (kg) USAGE06TA660004 7/8″ 1 2 ALL 05/6T compressors

144

CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES

06T REFRIGERATION COMPRESSOR ACCESSORIESCALIBRATED CIRCUIT BREAKERS

(1 Per 06T Compressor)

NOTES:1. Circuit breaker selections are based on across-the-line start.2. Overcurrent protection required per General Note.3. Heinemann circuit breaker not required with 05T compressor.

COMPRESSORMODULE USAGE

VOLTAGE3 PHASE

QTY/PKG WEIGHT (kg) CIRCUIT BREAKER

06TRC033B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

222

HH83XA463HH83XB356HH83XA460

06TRD039B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

222

HH83XA424HH83XB336HH83XA461

06TRD044B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

222

HH83XA424HH83XB336HH83XA461

06TRE048B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

232

HH83XA426HH83XC509HH83XA469

06TRE054B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

232

HH83XA426HH83XC509HH83XA469

06TRF065B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

232

HH83XA474HH83XC573HH83XB617

06TRG078B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

232

HH83XA476HH83XC574HH83XB618

06TRH088B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

232

HH83XA476HH83XC575HH83XB619

06TRK108B2EA-A00 400-3-50 1 2 HH83XA477

145

CARLYLE REFRIGERATION COMPRESSOR ACCESSORIES

06T REFRIGERATION COMPRESSOR ACCESSORIESCALIBRATED CIRCUIT BREAKERS

(1 Per 06T Compressor)

*These breakers are supplied without compression lugs. Customer must provide connectors or use our Power Terminal Parts Connectors for HH83XB Circuit Breakers shown below.

NOTES:1. Circuit breakers selections are based on across-the-line start.2. Overcurrent protection required per General Note.3. Heinemann circuit breaker not required with 05T compressor.

COMPRESSORMODULE USAGE

VOLTAGE3 PHASE

QTY/PKG WEIGHT (kg) CIRCUIT BREAKER

06TAD033B2EA-A00 F2EA-A00

C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-60

1

44

4

HH83XA424HH83XB336* or

HH83XB625HH83XA461

06TAE039B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

444

HH83XA426HH83XC509HH83XA469

06TAF044B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

444

HH83XA425HH83XC539HH83XA430

06TAF048B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

444

HH83XA425HH83XC539HH83XA430

06TAG054B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

444

HH83XA547HH83XC532HH83XA453

06TAG065B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

464

HH83XA475HH83XC574HH83XB618

06TAH078B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

464

HH83XA476HH83XC575HH83XB619

06TAK088B2EA-A00 F2EA-A00 C2EA-A00

460-3-60 & 400-3-50230-3-60 & 200-3-50

575-3-601

464

HH83XA477HH83XC576HH83XB610

POWER TERMINAL PARTS CONNECTORS FOR HH83XB CIRCUIT BREAKER

HH83XB series circuit breakers require customer supplied power wire connections at circuit breaker.Kit includes ring terminal, cap screws and lock washers. Not required for XA, XC, C or B series circuit breakers.

PART NO. USAGE SHIP WEIGHT (kg)06EA660152 #1 - #2 Wire 0.506EA660153 #4 Wire 0.5

TERMINAL PARTS PACKAGES

Package Contents: (6) Ring Terminal to connect power wiring to compressor terminal studs, plus (3) spare (2-hole) jumper bars.

PART NO. QTY/PKG WEIGHT (kg) USE WITH USAGE06EA900132 1 0.5 #6 Wire

All 06TCompressors

06EA900102 1 0.5 #4 Wire06EA900112 1 0.5 #2 Wire06EA900122 1 0.5 #1/0 Wire

146

CARLYLE REFRIGERATION COMPRESSORS

GUIDE TO 06D PART NUMBERING SYSTEM:NOTES:1. SPECIAL ORDER SERVICE COMPRESSORS FOR BRYANT

MAY BE PROCESSED AS “9” NAMEPLATED “6” (8TH DIGIT). 2. SERVICE MODELS WITH “C” IN THE 10th DIGIT REPLACE ALL

“A”, “C” AND “E” ORIGINAL EQUIPMENT MODELS AND “D” SERVICE MODELS REPLACE “8” & “F” MODELS. TERMINAL BOXES AND OVERLOADS ARE TO BE RE-USED OR REPLACED IF DAMAGED.

3. “09” IN THE 11TH & 12TH DIGITS HAS BEEN USED IN THE PAST FOR 400-3-50 MOTORS AND IS NO LONGER USED, SO AS TO AVOID CONFUSION IN SERVICE THESE DIGITS ARE TO BE LEFT ON THIS CHART BUT ARE NOT TO BE RE-USED.

PRODUCT SERIES

UN

LO

AD

ER

VA

RIA

TIO

NS

MO

TOR

SIZ

E

CF

MD

ISP

LA

CE

ME

NT

KE

Y N

UM

BE

R

VARIABLES

EL

EC

TR

ICA

LC

HA

RA

CT

ER

IST

ICVA

RIA

TIO

NS

FU

TU

RE

DE

SIG

NVA

RIA

BL

ES

PAC

KA

GIN

GVA

RIA

TIO

NS

SU

CT

ION

VA

LU

E &

M.E

.

CO

VE

R O

RIE

NTA

TIO

N

VO

RE

LO

AD

S &

INT

ER

NA

L

TH

ER

MO

STA

T

MODEL 0 6 D A 3 1 6 0 0 A 3 2 0 0

VARIABLE DIGIT I 2 3 4 5 6 7 8 9 10 11 12 13 14

13THDIGIT

FUTURE DESIGNVARIABLES

0 ORIGINAL DESIGN A/C & REFRIG.1 2ND GENERATION REFRIG,

CPRSR. W/NEW VALVE PLATE2 MED. RANGE A/C CPRSR. WITH

REFRIG. CHARACTERISTICS3 LOW CLEARANCE VOLUME4 SUCTION CUT-OFF

ELECTRIC UNLOADERS1 STEP

5 OILLESS67

14TH DIGIT

PACKAGING VARIATIONS

0SERVICE UNIT SINGLE PACK - BASE UNIT UNPACKAGES

ISINGLE PACK - DOMESTIC LESS SERVICE VALVE

2 MULTI-PACK - DOMESTIC3 EXPORT - I UNIT4 MULTI-PACK5 PALLETIZED6 GOVERNMENT PACK

7SINGLE PACK - DOMESTIC WITH SERVICE VALVE

8MATCHED COMPONENTS - CONSISTS OF SEPARATE EXPORT PACKAGE PIECES

9DOMESTIC MULTI-PACK & MCMINNVILLE

1ST, 2ND, 3RD DIGITSSIGNIFY 06D HERMETICRECIP. COMPRESSOR

4TH DIGIT UNLOADER VARIABLE

LETTER

STANDARD

SERVICE

BOTH

DESCRIPTION

A X NO HOT GAS BY-PASS UNLOADERSB X ELECTRIC UNLOADERS 1 STEPC X 2 STEPD X PRESSURE UNLOADERS 1 STEPE X 2 STEPF X SUCTION CUT-OFF

ELECTRIC UNLOADERS1 STEP

G X 2STEPM X MED. TEMPERATURE, REPLACES

ALL “A’s” IN SERVICEN X 2 SHAVED HDS. - SPECIAL ORDERR X REFRIGERATIONW X AIC - 2 PLUGGED HDS. REPLACES

ALL C&E SERVICE SPEC. ORDERSX X 1 PLUGGED HEAD - REPLACES ALL

B, C, D & E PROD. MODELS INSERVICE

Y X REFR. - 2 PLUGGED HDS. SERVICE SPEC. ORDER

S X HI-EFF SERVICE MOD. w/I BLOCKED UNLD’R HD - REPLACES F, G, H & J

H X SUCTON CUT-OFF PRES-SURE UNLOADERS!

1 STEPJ X 2 STEP

5TH DIGITVARIABLE

MOTOR SIZES2 CYL 4 CYL 6 CYL

0 3 HP1 2 HP 5 HP2 24 LBFT3 5 HP 27 LBFT4 31/2 HP5 51/2 HP 38 LBFT67 5 HP 20 LBFT8 3 HP 20 LBFT 24 LBFT9

10THDIGIT

OVERLOAD & T’STAT. VARIABLE SEE NOTE 2EXTL.

OVLDS.INTL.T’RAT.

DESCRIPTION

A YES YESB YES NOC NO YESD NO NOE YES YES 1ST OVERLOAD VARIATIONF YES NO 1ST OVERLOAD VARIATIONG YES YES MANUAL RESET OVERLOADST NO YES TECUMSEH SERVICE MODELS

9THDIGIT

SUCTION SERVICE VALVE VARIABLESLOC. OF VALVE M.E.COV. DESC. VALVE ORIENTATION

A MOTOR END 2 BOLT 30°B MOTOR END 4 BOLT 30°C MOTOR END 2 BOLT 90°D MOTOR END 4 BOLT 90° OR 180°E MOTOR END 2 BOLT 150°F PUMP END PLAIN 270°G PUMP END PLAIN 225°

270° 90°

180°

8THDIGIT

KEY NO. SIGNIFICANCE

0 PROD. MOD. W/T-BOX1 PKG. CPRSR. & CONTROL BOX2 OEM A/C CPRSR.3 TYLER MODELS4 TECUMSEH OEM MODELS5 FUTURE USE6 REMAN. SERVICE CPRSR.7 NEWMAN SERVICE GPRSR.6 SPECIAL ORDER ONLY9 SERV. SPEC. OR SEE NOTE 1

6TH & 7THDIGITS

CRANKCASEASSEMBLY

NO.

CYLBORE

CFM07 6D20-249 1-13/1608 6D23-249 209 6D23-249 213 6D48-249 216 6D48-249 218 6D48-249 220 6D48-249 224 6D68-259 228 6D75-249 237 6D75-249 2

11TH& 12THDIGITS

ELECTRICALCHARACTERISTICS

VOLTS-PHASE-HERTZ

START

00 XL01 575 - 3 - 60 XL02 200 - 1 - 60 XL03 230 - 1 - 60 XL04 200 - 3 - 60 XL05 230 - 3 - 60 XL06 400/460 - 3 - 50/60 XL07 230 - 1 - 50 XL08 220 - 3 - 50 XL09 SEE NOTE 3 XL10 230 - 2 - 60 XL11 480 - 3 - 60 XL12 2081230 - 3 - 60 XL13 380 - 3 - 60 XL14 200 - 3 - 60 P/W15 230 - 3 - 60 P/W18 220 - 3 - 50 P/W19 230/460 - 3 - 60 XL21 575 - 3 - 60 XL26 400/460 - 3 - 50/60 XL31 575 - 3 - 60 XL32 208/230 - 3 - 60 XL36 400/460 - 3 - 50/60 XL38 415 - 3 - 50 P/W39 415 - 3 - 50 XL33 208/230 - 1 - 60 XL34 220 - 3 - 50 XL

147

CARLYLE REFRIGERATION COMPRESSORS

06D REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSORAPPLICATION DATA

P912

For mounting configuration, dimensions and weight refer to outline drawings on previous pages.

MODELNO.

HPNO.OF

CYL.

CFM@

1750RPM

SUCTION TEMP. RANGE*(°F)

*Condensing temperature range 80° to 120° F.

CAPACITY (000 BTUH)-25° SST110° SCT65° SGT

0° SC

20° SST120° SCT65° SGT

0° SC

15° SST110° SCT65° SGT

0° SC

40° SST120° SCT60° SGT

0° SCR-502 R-12 R-22 R-502 R-502 R-12/R134a R-22

06DR109 2 2 8.7 -40 to 0**

**Cylinder Head Cooling Fan is required to operate at minimum suction temperatures.

-10 to 40 - 9.9 - 14.6/ - -06DM808 3 2 8.0 -10 to 40 - -10 to 50 - 23.1 - 35.606DR013 3 4 13.1 -40 to 0** -10 to 40 - 11.7 - 22.7/19.5 -06DM313 5 4 13.1 -10 to 40 -10 to 40 -10 to 50 - 35.1 20.4/ - 55.606DR316 5 4 15.9 -40 to 10** -10 to 40 - 16.2 - 29.1/26.9 -06DM316 5 4 15.9 -10 to 40 -10 to 40 -10 to 50 - 45.0 26.6/ - 69.006DR718 5 4 18.3 -40 to 10** -10 to 40 - 20.4 - 33.7/31.9 -06DR820 6-1/2 4 20.0 -40 to 40** -10 to 40 -10 to 50 22.3 - 37.4/35.6 92.506DR724 6-1/2 6 23.9 -40 to 40** -10 to 40 -10 to 50 25.6 - 43.7/40.1 109.606DR228 7-1/2 6 28.0 -40 to 40** -10 to 40 -10 to 50 31.0 - 51.3/49.2 128.206DR337 10 6 37.1 -40 to 10** -10 to 40 - 42.7 - 69.3/67.7 -06DM337 10 6 37.1 -10 to 30 -10 to 40 -10 to 35 - 111.1 65.6/ - 165.9

06D COMPRESSOR DATA - SINGLE PHASEMED. TEMP - NO UNLOADING

COMPRESSORMODEL NO.

VOLT HP CFMOIL

CHG.PINTS

MAX.WATTS

MAX.RLA

MTA LRA

2 CYLINDER... MEDIUM TEMP ... 60 HZ 06DM8086-0350 230 3 8 3.5 2800 17.0 22.0 70.006DM1096-0350 230 2 8.7 3.5 2800 12.5 15.6 50.04 CYLINDER... MEDIUM TEMP ... 60 HZ 06DM3136-0350 230 5 13.1 5 6600 28.0 35.0 100.006DM3166-0350 230 5 15.9 5 6600 28.0 35.0 100.006DM3186-0350 230 5 18.3 7 6600 28.0 35.0 100.006DM5186-0350 230 5.5 18.3 7 7700 36.8 46.0 148.006DM7186-0350 230 5 18.3 7 6600 28.0 35.0 100.0

148

CARLYLE REFRIGERATION COMPRESSORS

06D COMPRESSOR DATA - THREE PHASEMED. TEMP. - NO UNLOADING

COMPRESSORMODEL NO.

VOLT HP CFMOIL

CHG.PINTS

MAX.WATTS

MAX.RLA*

*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower RLA values.

MTA LRA

2 CYLINDER... MEDIUM TEMP ... 60 HZ 06DM8086-3150 575 3 8 3.5 4,100 5.6 7.0 28.406DM8086-3250 208/230 3 8 3.5 4,100 14.0 17.4 71.006DM8086-3650 460 3 8 3.5 4,100 7.0 8.7 35.52 CYLINDER... MEDIUM TEMP ... 50 HZ 06DM8086-3650 400 3 6.7 3.5 3,400 7.0 8.7 35.54 CYLINDER... MEDIUM TEMP ... 60 HZ 06DM3136-3150 575 5 13.1 5 6,250 8.6 10.8 40.006DM3136-3250 208/230 5 13.1 5 6,250 21.5 27.0 100.006DM3136-3650 460 5 13.1 5 6,250 10.8 13.5 50.006DM3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.006DM3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.006DM3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.04 CYLINDER...MEDIUM TEMP ... 60 HZ06DM3136-3650 400 5 11 5 5,200 10.8 13.5 50.006DM3166-3650 400 5 13 5 5,200 10.8 13.5 50.06 CYLINDER...MEDIUM TEMP ... 60 HZ06DM3376-3150 575 10 37.1 10 16,500 17.9 25.0 91.006DM3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.006DM3376-3250 208.230 10 37.1 10 16,500 44.3 62.0 228.06 CYLINDER...MEDIUM TEMP ... 50 HZ06DM3376-3650 400 8 31.0 10 13,700 22.1 31.0 114.0

06D COMPRESSOR DATA - SINGLE PHASELOW TEMP REFRIGERATION

COMPRESSORMODEL NO.

VOLT HP CFMOIL

CHG.PINTS

MAX.WATTS

MAX.RLA*

MTA LRA

2 CYLINDER... LOW TEMP REFRIGERATION ... 60 HZ 06DR1096-3350 208/230-1 2 8.7 3.5 3,400 17.0 24.0 110.04 CYLINDER... LOW TEMP REFRIGERATION ... 60 HZ 06DR0136-3350 208/230-1 3 13.1 5 4,800 23.3 32.6 100.006DR3166-3350 208/230-1 5 15.9 5 6,400 28.6 40.0 150.006DR7186-3350 208/230-1 5 18.3 7 6,400 28.6 40.0 150.0

149

CARLYLE REFRIGERATION COMPRESSORS

06D COMPRESSOR DATA - THREE PHASELOW TEMP REFRIGERATION

COMPRESSORMODEL NO.

VOLT HP CFMOIL

CHG.PINTS

MAX.WATTS

MAX.RLA*

*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower RLA values.

MTA LRA

2 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ 06DR1096-3150 575 2 8.7 3.5 3,100 3.1 4.4 21.306DR1096-3250 280/230 2 8.7 3.5 3,100 8.8 12.1 53.306DR1096-3650 460 2 8.7 3.5 3,100 3.8 5.5 26.62 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ 06DR109-3650 400 2 7.5 3.5 2,600 3.8 5.5 26.64 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ 06DR0136-3150 575 3 13.1 5 4,300 5.6 7.0 28.406DR0136-3250 208/230 3 13.1 5 4,300 14.0 17.4 71.006DR0136-3650 460 3 13.1 5 4,300 7.0 8.7 35.506DR3166-3150 575 5 15.9 5 6,250 8.6 10.8 40.006DR3166-3250 208/230 5 15.9 5 6,250 21.5 27.0 100.006DR3166-3650 460 5 15.9 5 6,250 10.8 13.5 50.006DR7186-3150 575 5 18.3 7 6,250 8.6 10.8 40.006DR7186-3250 208/230 5 18.3 7 6,250 21.5 27.0 100.006DR7186-3650 460 5 18.3 7 6,250 10.8 13.5 50.006DR8206-3150 575 6.5 20 7 9,800 12.6 17.6 64.006DR8206-3250 208/230 6.5 20 7 9,800 31.5 44.0 160.006DR8206-3650 460 6.5 20 7 9,800 15.7 22.0 80.04 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ06DR013-3650 400 3 11 5 3,400 7.0 8.7 35.506DR316-3650 400 5 13 5 5,200 10.8 13.5 50.006DR718-3650 400 5 15 7 5,200 10.8 13.5 50.006DR820-3650 400 6.5 16.7 7 8,200 31.5 44.0 160.06 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ 06DR7246-3150 575 6.5 23.9 10 9,800 12.6 17.6 64.006DR7246-3250 208/230 6.5 23.9 10 9,800 31.5 44.0 160.006DR7246-3650 460 6.5 23.9 10 9,800 15.7 22.0 80.006DR2286-3150 575 7.5 28 10 12,800 15.9 22.2 79.006DR2286-3250 208/230 7.5 28 10 12,800 39.7 55.5 198.006DR2286-3650 460 7.5 28 10 12,800 19.9 27.8 99.006DR3376-3150 575 10 37.1 10 1,6500 17.9 25.0 91.006DR3376-3250 208/230 10 37.1 10 16,500 44.3 62.0 228.006DR3376-3650 460 10 37.1 10 16,500 22.1 31.0 114.06 CYLINDER... LOW TEMP. REFRIGERATION ... 50 HZ 06DR724-3650 400 6.7 20 10 8,200 15.7 22.0 80.006DR228-3650 400 8 23.3 10 10,700 19.9 27.8 99.006DR337-3650 400 9 31 10 13,700 22.1 31.0 114.0

150

CARLYLE REFRIGERATION COMPRESSORS

REQUIRED CIRCUIT BREAKERS: 06D ... 60 HZ (REF. DUTY)

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06DR1096-3100 HH83XB49806DR1096-3200 HH83XB49206DR1096-3600 HH83XB49506DR0136-3100 HH83XB49606DR0136-3200 HH83XB49006DR0136-3600 HH83XB49406DR3166-3100 HH83XB49706DR3166-3200 HH83XB41506DR3166-3600 HH83XB44306DR7186-3100 HH83XB49706DR7186-3200 HH83XB41506DR7186-3600 HH83XB44306DR8206-3100 HH83XB45006DR8206-3200 HH83XB30606DR8206-3600 HH83XB41906DR7246-3100 HH83XB45006DR7246-3200 HH83XB30606DR7246-3600 HH83XB41906DR2286-3100 HH83XB419

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06DR2286-3200 HH83XB30706DR2286-3600 HH83XB43806DR3376-3100 HH83XB45106DR3376-3200 HH83XB30506DR3376-3600 HH83XB45206DM8086-0300 HH83XB48006DM1096-0300 HH83XB48106DM8096-0300 HH32XB48006DM3136-0300 HH83XB48306DM3166-0300 HH83XB48306DM3186-0300 HH83XB48306DM5186-0300 HH83XB48406DM7186-0300 HH83XB48306DM8086-3200 HH83XB49006DM8086-3600 HH83XB49406DM3136-3100 HH83XB49706DM3136-3200 HH83XB31606DM3136-3600 HH83XB44306DM3166-3100 HH83XB497

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06DM3166-3200 HH83XB31606DM3166-3600 HH83XB44306DM8186-0100 HH83XB45006DM8186-0600 HH83XB41906DM8186-1200 HH83XB30606DM8246-0100 HH83XB41906DM8246-0600 HH83XB40006DM8246-1200 HH83XB42306DM3376-3100 HH83XB45106DM3376-3600 HH83XB45206DM3376-3200 HH83XB30506DM3376-1400 HH83XE63006DM3376-1500 HH83XE60406DM5376-0100 HH83XB44006DM5376-0600 HH83XB42206DM5376-1200 HH83XB31106DM5376-1400 HH83XE63306DM5376-1500 HH83XE643

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06DR109-3600 HH83XB49506DR013-3600 HH83XB49406DR316-3600 HH83XB44306DR718-3600 HH83XB41506DR820-3600 HH83XB419

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06DR724-3600 HH83XB41906DR228-3600 HH83XB43806DR337-3600 HH83XB45206DM808-3600 HH83XB49406DM313-3600 HH83XB443

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06DM316-3600 HH83XB44306DM818-0600 HH83XB41906DM824-0600 HH83XB40006DM337-3600 HH83XB45206DM537-0600 HH83XB422

REQUIRED CIRCUIT BREAKERS: 06D ... 50 HZ

151

CARLYLE REFRIGERATION COMPRESSORS

REQUIRED ACCESSORIES - 06DOPTIONAL ACCESSORIES

COMPRESSOR MODEL NO.

TERMINAL BOX KIT

SUCTION SERVICE

VALVE KIT

ALTERNATE SUCTION SERVICE

VALVE KIT

DISCHARGE SERVICE

VALVE KIT

ALTERNATE DISCHARGE

SERVICE VALVE KIT

SUSPENSION KIT MOUNTING PLATE KIT

06DR109 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058 06EA660096- - 06DA660061

013 06DA660078 06DA660064 - 06DA660056 316 06DA660064 - 06DA660056 718 06DA660065 06EA660090 06DA660056 820 06DA660065 06EA660090 06DA660056 724 06DA660065 06EA660090 06DA660062 06DA660064 06DA660057 228 06EA660090 - 06DA660062 06DA660064 06DA660057 337 06EA660090 - 06DA660062 06DA660064 06DA660057 06DM808 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058

- - 06DA660061 809 06DA660061 - 06DA660058 ( )313 06DA660078 06DA660064 - 06DA660056 ( )316 06DA660078 06DA660062 06DA660064 06DA660056 518 06DA660078 06DA660064 - 06DA660061 - 06DA660056 06EA660096 ( )818 06DA660064 - 06DA660061 - 06DA660056 06D( )724 06DA660063** 06DA660065** 06DA660062 06DA660064 06DA660057

- 06EA660090** - -06DA660064* - - -

( )824 06DA660063** 06DA660065** 06DA660062 06DA660064- 06EA660090** - -

06DA660064* - - - ( )337 06DA660065 06EA660090 06DA660064 -

* -- 2 BOLT ** -- 4 BOLT

• KIT CONSISTS OF:SERVICE VALVE, GASKET AND BOLTS

NOTE: Service Valve contained in kits cannot be ordered separately.

P419

NR= Not Required.NA = Vendor part number available upon request.

VALVESIZE(in.)

VALVEMOUNTING

(BOLT HOLECENTER-IN)

MUELLER - SERVICE VALVE HENRY - SERVICE VALVEADAPTER/TAILPIECE

P/N

KITP/N

VALVEP/N

CAPP/N

ADAPTER/TAILPIECE

P/N

KITP/N

VALVEP/N

CAPP/N

5/8 FLARE 2 BOLT (1-5/8) NR 06DA660059 EN26AA211 EN99ZA001 - - - -5/8 SWEAT 2 BOLT (1-5/8) NR 06DA660060 EN32AA250 EN99ZA001 - - - -

7/8 SWEAT2-BOLT (1 -5/8)

NR06DA660061 EN07AA271

EN99ZA006NR

06DA660061 EN07AA271NA

2 BOLT (1 -3/4) 06DA660062 EN07AA284 06DA660062 EN07AA2842 BOLT (2-3/4) EN99ZC027 - EN07AA390 - - - -

1-1/8 SWEAT4 BOLT (2-1/2) NR 06DA660063 EN07EA033

EN99ZA006NR

06DA660063 EN07EA033

EN99ZA0132 BOLT (1 -3/4) 06DA660064 EN07AA348 06DA660064 EN07AA3482 BOLT (2-3/4) EN99ZC033 - EN07AA395 NA - EN07EC341

1-3/8 SWEAT 4 BOLT (2-1/2) NR 06DA660065 EN07EA039 EN99ZA006 NR - - -

1-5/8 SWEAT4 BOLT (2-1/2) NR 06EA660090 EN07EA041 EN99ZA006 NR 06EA60090 EN07EA041

EN99ZA013NR - EN13HA045 NA NA - EN13HA045

2-1/8 SWEAT 4 BOLT (3-1/16) EM99AA516- EM13FE051

EN99ZA009 EP29VC540 06EA660091 EM13FE051 EN99ZA022- EM13FA516

2-5/8 SWEAT 4 BOLT (3-1/16) EM99AA518 - EM13FA518 - - - - -3-1/8 SWEAT 4 BOLT (3-7/8) EM99AA520 - EM13FA520 EN99ZA011 EP29VC660 - EM13FE520 EN99ZA0184-1/8 SWEAT 4 BOLT (4-13/16) NA - EM13FA524 NA NA - EM13FES24 EN99ZA025

COMPRESSOR SERVICE VALVE KITS BY VALVE SIZE

152

CARLYLE REFRIGERATION COMPRESSORS

GUIDE TO 06E PART NUMBERING SYSTEM:

PRODUCTSERIES

DE

SIG

N V

AR

IAB

LE

S

US

AG

E

SIZE

EL

EC

TR

ICA

LC

HA

RA

CT

ER

IST

ICS

FU

TU

RE

DE

SIG

N

MO

DE

L A

ND

PAC

KA

GIN

G

CFM CPRSRS

HOM.H.P. CPRSR UNITS

MODEL 0 6 E A 1 5 0 3 4 0DIGIT 1 2 3 4 5 6 7 8 9 10

1ST, 2HD, 3RD DIGITSO6E HERMETIC COMPRESSOR

9TH DIGIT SERVICE DESIGN VARIABLE1 THERMOTECTOR PROTECTION OLD STYLE

CRANKCASE2 NEW MANUFACTURE SERVICE COMPRESSOR3 FUTURE USE4 REMANUFACTURED SERVICE COMPRESSOR

LOW TEMP5 OLD STYLE CRANKCASE ROBERTSHAW SEN-

SORS & TAPPED CYL. HDS. MOTOR PROTEC-TION KIT REQ’D. FOR THERMOTECTOR APPLICATION

6 REMANUFACTURED SERVICE COMPRESSOR7 REMANUFACTUREO SERVICE COMPRESSOR

MED. TEMP.

9TH DIGIT PROD. DESIGN VARIABLE0 OEM MODEL1 ELECTRICAL REDESIGN23 FIRST REDESIGN

LONG STROKE CRANKCASE4 SECOND DESIGN

ROBERTSHAW MOTOR PROTECTION56 CPRSR. MODEL LESS MOTOR PROTECTION7 MEDIUM TEMP. ROBERTSHAW MOTOR PRO-

TECTION89 CEMAK MODEL

10TH DIGIT PACKAGING0 MODEL

NO.4

MULTI PACK EXP

1SINGLE PACK

LESS VALVE

5PALLETIZED LESS VALVE

2 MULTI PACK DOM 7 PALLETIZED WITH VALVE3

SINGLE PACKWITH VALVE

9 MULTI PACK MC MINN

SYMBOLS:

= SAMPLE PART NO. 06E215O36ONOTES:4. 220-3-60 UNIT DESIGNED FOR USE ON 198 to 242 V

380-3-60 342 418 V575-3-60 518 660 V460-3-60 414 529 V230-3-60 198 264 V230-3-50 198 264 V400-3-50 342 457 V200-3-60 180 229 V

5. RVS HD CPRSR -- ORIGINAL DESIGN NO. 4TH DIGIT A, B, C, D, CRF9TH DIGIT

REDESIGN NO. 4TH DIGIT F, J, K. L OR N9TH DIGIT SAME AS STANDARD

5TH DIGIT USAGE0 LIGHT DUTY CPRSR. OR

CPRSR. UNIT TONNAGE56

1 MEDIUM DUTY CPRSR. 72 HEAVY DUTY CPRSR. 8 SPECIAL ORDER3 OILLESS 94

6TH & 7TH DIGIT COMPRESSOR SIZENO. STD. LONG STROKE LONG STROKE SHORTCYL. PROD. STD. CLEARANCE HI CLEARANCE STROKE

4 50 CFM 66 CFM 60 CFM --6 75 CFM 99 CFM -- 65 CFM

COMPRESSOR UNITS (CAC USAGE)NO

CYL.STD. PROD. CPRSR. LONG STROKE CPRSR.

4 22 (NOM TONS) --6 33 (NOM TONS) 44 (NOM TONS)

8TH DIGIT ELECT1 575 - 3 - 602 200 - 1 - 603 208/230/460 - 3 - 604 200 - 3 - 605 230 - 3 - 606 400 - 3 - 50

460 -3 - 607 230 - 1 - 508 230 - 3 - 509 220/380 - 3 - 600 208/230 - 3 - 60A 415 - 3 - 50

4TH DIGIT 4TH DIGIT UHLDADER VARIABLESUCTION CUTOFF

UNLOADINGLETTER

STANDARD

SERVICE

BOTH

DESCRIPTION

A X NO UNLOADERS

2 B X ONE UNLOADER - ELECTRIC

3 C X TWO UNLOADERS - ELECTRIC

4 D X ONE UNLOADER - PRESSURE

5 E X TWO UNLOADERS - PRESSURE

F X NO UNLOADERS

RE

VE

RS

ED

HE

AD

6 C

YL

.

SE

E N

OT

E 26 J X ONE UNLOADER - ELECTRIC

7 K X TWO UNLOADERS - ELECTRIC

8 L X ONE UNLOADER - PRESSURE

9 N X TWO UNLOADERS - PRESSURE

G X NO UNLOADERS - PRESSURE

CP

RS

R W

ITH

CO

NT

BO

X

US

ED

BY

CA

CF

OR

UN

ITSP X ONE UNLOADER - ELECTRIC

U X TWO UNLOADERS - ELECTRIC

V X ONE UNLOADER - PRESSURE

W X TWO UNLOADERS - PRESSURE

M X MEDIUM TEMP. - NO UNLOADERS

R X REFRIGERATION - NO UNLOADERS

T XSERVICE CMPRSR. w/(1) BLOCKED SUCTION CUT-OFF UNLOADER HEAD

REPLACES 2, 3,4, 5, 6, 7, 8 & 9

X XSERVICE COMPRESSOR - AIR CONDITION.

REPLACES A, B,C, D, E, F J, K, L & N

Y X SVC. CPRSR. - REFRIG. REPLACES R

153

CARLYLE REFRIGERATION COMPRESSORS

06E REFRIGERATION AND MEDIUM TEMPERATURE DUTY COMPRESSORAPPLICATION DATA

P52

For mounting configuration, dimensions and weight refer to outline drawings on previous pages.

MODELNO.

HPNO.OF

CYL.

CFM@

1750RPM

SUCTION TEMP. RANGE*(°F)

*Condensing temperature range 80° to 120° F.

CAPACITY (000 BTUH)

-25° SST110° SCT65° SGT

0° SC

20° SST120° SCT

65° SGT0° SC

15° SST110° SCT65° SGT

0° SC

40° SST120° SCT60° SGT

0° SC

R-502 R-12 R-22 R-502 R-502 R-12 R-2206EY150 15 4 50.3 -40 to 10** -10 to 40 - 54.5 - 92.1 -06EZ150 15 4 50.3 -10 to 40 -10 to 40 -10 to 40 - 139.0 82.6 219.706EY166 20 4 66.0 -40 to 10** -10 to 40 - 68.0 - 109.0 -06EZ266 25 4 66.0 -10 to 40 - -10 to 50 - 180.0 - 277.006EY165 20 6 65.0 -40 to 10** -10 to 40 - 68.3 - 121.7 -06EY175 20 6 75.4 -40 to 1**

**Cylinder Head Cooling Fan is required to operate at minimum suction temperatures.

-10 to 40 - 78.6 - 135.7 -06EZ175 25 6 75.4 -10 to 40 -10 to 40 -10 to 50 - 207.5 121.0 323.806EY099 30 6 99.0 -40 to 10** -10 to 40 - 104.0 - 172.4 -06EZ199 35 6 99.0 -10 to 40 -10 to 40 -10 to 50 - 280.0 163.4 422.6

154

CARLYLE REFRIGERATION COMPRESSORS

06E COMPRESSOR DATA - THREE PHASELOW TEMP. & MED. TEMP. REFRIGERATION

COMPRESSORMODEL NO.

VOLT HP CFMOIL

CHG.PINTS

MAX.WATTS

MAX.RLA*

*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower RLA values.

MTA LRA

4 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ 06EY150-140 575 15 50.3 14 22,000 31 38 9806EY150-340 208-230/460 15 50.3 14 22,000 72/36 90/45 283/14206EY166-140 575 20 66 14 25,300 36 45 12006EY166-340 208-230/460 20 66 14 25,300 87/44 108/54 345/17306EY166-640 ** 460 20 66 14 25,300 45 56 150

4 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ06EY150-340 200/400 15 41.7 14 18,300 72/36 90/45 283/14206EY166-340 200/400 20 55 14 28,000 87/44 108/54 345/17306EY166-640 ** 400 20 55 14 28,000 45 56 150

6 CYLINDER... LOW TEMP. REFRIGERATION ... 60 HZ 06EY165-140 575 20 65 19 25,300 36 45 12006EY165-340 208-230/460 20 65 19 25,300 87/44 108/54 345/17306EY165-640 ** 460 20 65 19 25,300 44 54 17306EY175-140 575 20 75.4 19 25,300 36 45 12006EY175-340 208-230/460 20 75.4 19 25,300 87/44 108/54 345/17306EY175-640 ** 460 20 75.4 19 25,300 45 56 15006EY099-140 575 30 99 19 39,100 52 65 17606EY099-340 208-230/460 30 99 19 39,100 135/68 168/84 506/25306EY099-640 ** 460 30 99 19 39,100 65 81 220

6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ06EY165-340 200/400 20 54 19 21,100 87/44 108/54 345/17306EY165-640 ** 400 20 54 19 21,100 44 54 17306EY175-340 200/400 20 62.5 19 21,100 87/44 108/54 345/17306EY175-640 ** 400 20 62.5 19 21,100 45 56 15006EY099-340 200/400 30 82.5 19 32,600 135/68 168/84 506/25306EY099-640 ** 400 30 82.5 19 32,600 65 81 220

4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ 06EZ150-170 575 15 50.3 14 22,000 31 38 9806EZ150-370 208-230/460 15 50.3 14 22,000 72/36 90/45 283/14206EZ266-170 575 25 66 14 33,600 46 57 16406EZ266-370 208-230/460 25 66 14 33,600 112/56 140/170 446/22306EZ266-670 ** 460 25 66 14 33,600 57 71 205

4 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ06EZ150-370 200/400 15 41.7 14 18,300 72/36 90/45 283/14206EZ266-370 200/400 25 55 14 28,000 112/56 140/170 446/22306EZ266-670 ** 400 25 55 14 28,000 57 71 205

6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 60 HZ 06EZ175-170 575 25 75.4 19 33,600 46 57 16406EZ175-370 208-230/460 25 75.4 19 33,600 112/56 140/70 446/22306EZ175-670 ** 460 25 75.4 19 33,600 57 71 20506EZ199-170 575 35 99 19 47,600 65 82 21206EZ199-370 208-230/460 35 99 19 47,600 155/77 193/96 610/30506EZ199-670 ** 460 35 99 19 47,600 82 102 265

6 CYLINDER ... MEDIUM TEMP. REFRIGERATION ... 50 HZ06EZ175-370 200/400 25 62.5 19 28,000 112/56 140/170 446/22306EZ175-670 ** 400 25 62.5 19 28,000 57 71 20506EZ199-370 200/400 35 82.5 19 39,700 155/77 193/96 610/30506EZ199-670 ** 400 35 82.5 19 39,700 82 102 265

**Order the discrete 400/460-3-50/60 volt compressor for part wind start applications only. When ordering, place the letters PW after the model num-ber, (i.e., 06EX299660PW).

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

155

CARLYLE REFRIGERATION COMPRESSORS

REQUIRED CIRCUIT BREAKERS: 06E ... 60 HZ

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06EY150-140 HH83XA460

06EY150-340HH83XE633†

HH83XB360††HH83XA463†††

06EY166-140 HH83XA461

06EY166-340HH83XE622†

HH83XB336††HH83XA424†††

06EY166-640 HH83XE62606EY165-140 HH83XA461

06EY165-340HH83XE622†

HH83XB336††HH83XB437†††

06EY165-640 HH83XE626

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06EY175-140 HH83XA461

06EY175-340HH83XE622†

HH83XB336††HH83XA424†††

06EY175-640 HH83XE62606EY099-140 HH83XA430

06EY099-340HH83XE652†

HH83XC439††HH83XA425†††

06EY099-640 HH83XE64206EZ150-170 HH83XA460

06EZ150-370HH83XE633†

HH83XB356††HH83XA463†††

06EZ266-170 HH83XA469

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N

06EZ266-370HH83XE621†

HH83XC409††HH83XA426†††

06EZ266-670 HH83XE63006EZ175-170 HH83XA469

06EZ175-370HH83XE621†

HH83XC409††HH83XA426†††

06EZ175-670 HH83XE63006EZ199-170 HH83XA453

06EZ199-370HH83XE609†

HH83XC432††HH83XA547†††

06EZ199-670 HH83XE623

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N

06EY150-340HH83XE633†

HH83XB360††HH83XA463†††

06EY166-340HH83XE622†

HH83XB336††HH83XA424†††

06EY166-640 HH83XE626

06EY165-340HH83XE622†

HH83XB336††HH83XB437†††

06EY165-640 HH83XE626

06EY175-340HH83XE622†

HH83XB336††HH83XA424†††

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06EY175-640* HH83XE626

06EY099-340HH83XE652†

HH83XC439††HH83XA425†††

06EY099-640 HH83XE642

06EZ150-370HH83XE633†

HH83XB356††HH83XA463†††

06EZ266-370HH83XE621†

HH83XC409††HH83XA426†††

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06EZ266-670 HH83XE630

06EZ175-370HH83XE621†

HH83XC409††HH83XA426†††

06EZ175-670 HH83XE630

06EZ199-370HH83XE609†

HH83XC432††HH83XA547†††

06EZ199-670 HH83XE623

REQUIRED CIRCUIT BREAKERS: 06E ... 50 HZ

NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.†This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.

††This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.†††This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

156

CARLYLE REFRIGERATION COMPRESSORS

REQUIRED ACCESSORIES - 06E

OPTIONAL ACCESSORIES

COMPRESSOR MODEL NO.

TERMINAL BOX KIT

SUCTION SERVICE

VALVE KIT

ALTERNATE SUCTION SERVICE

VALVE KIT

DISCHARGE SERVICE

VALVE KIT

ALTERNATE DISCHARGE

SERVICE VALVE KIT

SUSPENSION KIT

MOUNTING PLATE KIT

06EY150 06EA660095 06EA660091 - 06DA660064 - 06EA660089 06EA660096 166 - 06DA660064 - 175 - 06DA660065 06EA660090 099 - 06DA660065 06EA660090 06EZ150 - 06DA660064 - 266 - 06DA660064 - 175 - 06DA660065 06EA660090 199 - 06DA660065 06EA660090

157

VALVES

COMPRESSOR SERVICE VALVE KITS BY VALVE SIZE

• KIT CONSISTS OF:SERVICE VALVE, GASKET AND BOLTS

NOTE: Service Valve contained in kits cannot be ordered separately.

P419

NR= Not Required.NA = Vender part number available upon request.

VALVESIZE(in.)

VALVEMOUNTING

(BOLT HOLECENTER-IN)

MUELLER - SERVICE VALVE HENRY - SERVICE VALVEADAPTER/TAILPIECE

P/N

KITP/N

VALVEP/N

CAPP/N

ADAPTER/TAILPIECE

P/N

KITP/N

VALVEP/N

CAPP/N

5/8 FLARE 2 BOLT (1-5/8) NR 06DA660059 EN26AA211 EN99ZA001 - - - -5/8 SWEAT 2 BOLT (1-5/8) NR 06DA660060 EN32AA250 EN99ZA001 - - - -

7/8 SWEAT2-BOLT (1 -5/8)

NR06DA660061 EN07AA271

EN99ZA006NR

06DA660061 EN07AA271NA

2 BOLT (1 -3/4) 06DA660062 EN07AA284 06DA660062 EN07AA284

2 BOLT (2-3/4) EN99ZC027 - EN07AA390 - - - -

1-1/8 SWEAT4 BOLT (2-1/2) NR 06DA660063 EN07EA033

EN99ZA006NR

06DA660063 EN07EA033

EN99ZA0132 BOLT (1 -3/4) 06DA660064 EN07AA348 06DA660064 EN07AA348

2 BOLT (2-3/4) EN99ZC033 - EN07AA395 NA - EN07EC341

1-3/8 SWEAT 4 BOLT (2-1/2) NR 06DA660065 EN07EA039 EN99ZA006 NR - - -

1-5/8 SWEAT4 BOLT (2-1/2) NR 06EA660090 EN07EA041 EN99ZA006 NR 06EA60090 EN07EA041

EN99ZA013NR - EN13HA045 NA NA - EN13HA045

2-1/8 SWEAT 4 BOLT (3-1/16) EM99AA516- EM13FE051

EN99ZA009 EP29VC540 06EA660091 EM13FE051 EN99ZA022- EM13FA516

2-5/8 SWEAT 4 BOLT (3-1/16) EM99AA518 - EM13FA518 - - - - -3-1/8 SWEAT 4 BOLT (3-7/8) EM99AA520 - EM13FA520 EN99ZA011 EP29VC660 - EM13FE520 EN99ZA018

4-1/8 SWEAT 4 BOLT (4-13/16) NA - EM13FA524 NA NA - EM13FES24 EN99ZA025

158

CARLYLE REFRIGERATION COMPRESSORS

TOTALINE COMPRESSOR OILS - FOR CARLYLE AND TOTALINE COMPRESSORS

COMPRESSOR MODEL

REFRIGERANT R-12, R-22 (L & H TEMP.)

REFRIGERANT R-507, R-404A

(MED. TEMP)

REFRIGERANT R-507, R-404A (LOW. TEMP

REFRIGERANT R-134A(M & H TEMP)

OIL MODELTOTALINE PART NO.

OIL MODELTOTALINE PART NO.

OIL MODELTOTALINE PART NO.

OIL MODELTOTALINE PART NO.

Carlyle 06D, E semi-hermetic

Zerol 150P903-2001P903-2005P903-2025

SW68P903-1001P903-1025P903-1005

E68(Do not use SW-68 for Low Temp)

P903-1725P903-1701P903-1705

SW68P903-1001P903-1025P903-1005

RO 15 P903-0101P903-0105P903-0155

Carlyle 5F/H open Zerol 150P903-2001P903-2005P903-2025

SW68P903-1001P903-1025P903-1005

E68(Do not use SW-68 for Low Temp)

P903-1725P903-1701P903-1705

SW 68P903-1001P903-1025P903-1005

RO 15 P903-0101P903-0105P903-0155

Carlyle 05T/06T Screw (74)

E-100 P903-1501P903-1505P903-1525

E-100 P903-1501P903-1505P903-1525

E-100 P903-1501P903-1505P903-1525

E-100 P903-1501P903-1505P903-1525

Carlyle 06N Screw(104 mm Global Chiller)

N/A N/A N/A N/A N/A N/A SW-220(R-134a Only)

P903-1201P903-1225P903-1205

Millennium ScrollTechnologies

Zerol 150 P903-2001P903-2005P903-2025

N/A N/A N/A N/A Mobil Arctic 68 Model now obsolete

159

OILS

TOTALINE OILSVACUUM PUMP OIL

A highly purified purpose vacuum pump oil that cleans and lubricates. The quart bottle (9.5 liters) has a convenient flip-top-cap.

P894

P/N SIZEP903-0632 1 QT (.95 liters)P903-0601 1 GAL (3.8 litersP903-0605 5 GAL (18.9 liters)P903-0655 55 GAL (208.2 liters)

MINERAL REFRIGERATION OILS

POLYOL-ESTER OILS

This is a refined oil used specifically for air conditioning and refrigera-tion. The low moisture content means less failure. A non-foaming, wax-free oil to prevent plugged cap-illaries and sticking expansion valves. OEM approved by most manufacturers.

P/N SIZE VISCOSITYP903-0101 1 GAL (3.8 liters) 150P903-0105 5 GAL (18.9 liters) 150P903-0155 55 GAL (208.2 liters) 150P903-0201 1 GAL (3.8 liters) 300P903-0205 5 GAL (18.9 liters) 300P903-0255 55 GAL (208.2 liters) 300P903-0301 1 GAL (3.8 liters) 500P903-0305 5 GAL (18.9 liters) 500P903-0355 55 GAL (208.2 liters) 500

P893

P/N SIZE TYPEP903-1025 1 QT (,95 liters) SW68P903-1001 1 GAL (3.8 liters) SW68P903-1005 5 GAL (18.9 liters) SW68P903-1125 1 QT (.95 liters) SW32P903-1101 1 GAL (3.8 liters) SW32P903-1105 5 GAL (18.9 liters) SW32P903-1225 1 QT (,95 liters) SW220P903-1201 1 GAL (3.8 liters SW220P903-1205 5 GAL (18.9 liters) SW220

P1544

These environmentally friendly products are specifically formu-lated to use with the non-CFC refrigerant R-134a. The base flu-ids have been engineered to be totally miscible with R134a over a very wide temperature range while maintaining excellent lubri-cating properties.

The Z-Series are high quality synthetic Alkylbenzene Refrigera-tion fluids for us with HCFC, CFC and ammonia refrigerants in refrigeration and air conditioning applications.

Due to superior miscibility, Totaline Z-Series lubricants are excel-lent for systems utilizing environmentally sound refrigerants MP39, MP60, HP80 or HP81. Totaline Z-Series are superior products for all R-22, R-123 and R-502 Systems, particularly at low temperatures.

Z-200TD is formulated with a unique additive package providing extreme pressure (EP) lubricity and foam control at operating conditions.

P/N SIZE TYPEP903-2025 1 QT (,95 liters) Z-150P903-2001 1 GAL (3.8 liters) Z-150P903-2005 5 GAL (18.9 liters) Z-150P903-2125 1 QT (.95 liters) Z-200TDP903-2101 1 GAL (3.8 liters) Z-200TDP903-2105 5 GAL (18.9 liters) Z-200TDP903-2225 1 QT (.95 liters) Z-300P903-2201 1 GAL (3.8 liters Z-300P903-2205 5 GAL (18.9 liters) Z-300

ALKYLBENZENE REFRIGERATION OILS

P1545

160

CARLYLE REFRIGERATION COMPRESSORS

06CY REFRIGERATION DUTY COMPRESSOR APPLICATION DATA

P53

CARLYLE COMPOUND COOLINGTM ...An innovative approach to low temperature refrigeration from Carlyle.

TWO-STAGE COMPRESSION IN A SINGLE COMPRESSOR USES R-22 WITH THE EFFICIENCY AND RELIABILITY OF R-502

• LOW COMPRESSION RATIOS• TWO-STAGE BOOSTER

PERFORMANCE

• SAME CAPACITIES AS R-502 COMPRESSORS

• EASY APPLICATION OF SUBCOOLING

• SUBCOOLING CONTROL ALLOWS CONSTANT CAPACITY OVER A WIDE OPERATING RANGE

• CONSTANT CAPACITY REDUCES STRESS RESULTING FROM SHORT CYCLING

• IDENTICAL OIL CONTROL TO R-502 RACK SYSTEMS

• LOW OIL CIRCULATION RATES

• SIMILAR DIMENSIONS TO OTHER CARLYLE MODELS FOR EASY FIT

HOW COMPOUND COOLINGTM WORKSA variation of the two-stage booster system, the internally compounded compressor has both the high and low stages built into one compressor body. In this arrangement, compression is accomplished in two stages, safely and economically.

All nine Compound Cooling models have six cylinders. Four cylinders, acting as the low stage, “boost” the suction pressure from the refrigeration load to the intermediate pressure. The remaining two cylinders, acting as the high stage, complete the compression to normal condensing temperatures. The result is lower internal losses and a compressor that delivers more capacity in the same dis-placement. The lower losses also produce operating efficiencies that are substantially higher than the competition.

For mounting configuration, dimen-sions and weight refer to outline drawings on following page.

MODEL NO. HPNO.OF

CYL.

CFM@

RPM

SUCTION TEMP. RANGE*(DEGREES °F)

R-22

*Condensing temperature range 60° to 130° F Cylinder Head Cooling Fans recommended for all applications.

R-22 CAPACITY(000 BTUH)

OILCHARGE(PINTS)

-25° SST110° SCT65° SGT

40° LIQUID06CY016 5.0 6 16 -40 to -15 17.6 1006CY018 5.0 6 18 -40 to -15 22.6 1006CY124 6.5 6 24 -40 to -15 24.6 1006CY228 7.5 6 28 -40 to -15 29.5 1006CY337 10.0 6 37 -40 to -15 39.9 1006CY550 15.0 6 50 -40 to -15 56.3 1906CY665 20.0 6 65 -40 to -15 71.4 1906CY675 20.0 6 75 -40 to -15 80.6 1906CY899 30.0 6 99 -40 to -15 103.4 19

161

CARLYLE REFRIGERATION COMPRESSORS

06CY OUTLINE DRAWINGSNOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.

06CC COMPRESSORS

* 4 FIRST STAGE, 2 SECOND STAGE.

06CY016 06CY018 06CY228 06CY337MOTOR HORSEPOWER 5 5 7.5 10

NO. OF CYLINDERS 6* 6* 6* 6*BORE AND STROKE (in.) 2.0 x 2.0 x 2.0 x 1.47 2.0 x 1.94DISPLACEMENT CFM AT 1750 RPM 16 18 28 37OIL, CHARGE, PINTS CPP33-2 10 10 10 10DRY WEIGHT LESS SERVICE VALVES 340 LBS 340 LBS 340 LBS 345 LBS

06CC COMPRESSORS

* 4 FIRST STAGE, 2 SECOND STAGE.

06CY550 06CY665 06CY675 06CY899MOTOR HORSEPOWER 15.0 20.0 50.0 30.0NO. OF CYLINDERS 6* 6* 6* 6*BORE AND STROKE (in.) 2.69 x 2.16 2.69 x 1.96 2.69 x 2.19 2.69 x 2.87DISPLACEMENT CFM AT 1750 RPM 50 65 75 99OIL, CHARGE, PINTS CPP33-2 19 19 19 19

DRY WEIGHT LESS SERVICE VALVES 545 LBS 555 LBS 555 LBS 580 LBS

162

CARLYLE REFRIGERATION COMPRESSORS

06CY COMPRESSOR DATA - THREE PHASELOW TEMP. REFRIGERATION - COMPOUND COOLING™ MODELS

COMPRESSORMODEL NO.

VOLT HP CFMOIL

CHG.PINTS

MAX.WATTS

MAX.RLA*

*This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lower RLA values.

MTA LRA

6 CYLINDER ... LOW TEMP. REFRIGERATION ... 60 HZ06CY016-D103 208/230 5.0 16 10 4,600 19.3 27.0 10006CY016-G103 460 5.0 16 10 4,600 9.6 13.5 50.006CY016-J103 575 5.0 16 10 4,600 7.7 10.8 40.006CY018-DI03 208/230 5.0 18 10 5,000 19.3 27.0 10006CY018-G103 460 5.0 18 10 5,000 9.6 13.5 50.006CY018-J103 575 5.0 18 10 5,000 7.7 10.8 40.006CY124-D103 208/230 6.5 24 10 6,500 23.6 33.0 16006CY124-G103 460 6.5 24 10 6,500 11.8 16.5 80.006CY124-J103 575 6.5 24 10 6,500 9.4 13.2 64.006CY228-D103 208/230 7.5 28 10 7,600 29.7 41.6 19806CY228-G103 460 7.5 28 10 7,600 14.9 20.9 99.006CY228-J103 575 7.5 28 10 7,600 11.9 16.7 79.006CY337-D103 208/230 10 37 10 10,000 33.2 46.5 228.006CY337-G103 460 10 37 10 10,000 16.6 23.3 114.006CY337-J103 575 10 37 10 10,000 13.4 18.8 91.006CY550-E103 208-230/460 15 50 19 13,000 37.1/18.6 52/26 283/14206CY550-F103 460 15 50 19 13,000 18.6 26.0 14206CY550-J103 575 15 50 19 13,000 15.0 21.0 98.006CY665-E103 208-230/460 20 65 19 16,800 60.7/30.0 85/42 345/17306CY665-F103 460 20 65 19 16,800 30.0 42.0 17306CY665-J103 575 20 65 19 16,800 23.6 33.0 12006CY675-E103 208-230/460 20 75 19 19,000 60.7/30.0 85/42 345/17306CY675-F103 460 20 75 19 19,000 30.0 42.0 17306CY675-J103 575 20 75 19 19,000 26.4 33.0 12006CY899-E103 208-230/460 30 99 19 26,000 92.9/46.4 130/65 506/25306CY899-F103 460 30 99 19 26,000 46.4 65.0 25306CY899-J103 575 30 99 19 26,000 37.1 52.0 175

6 CYLINDER ... LOW TEMP. REFRIGERATION ... 50 HZ06CY016-G103 400 5 13.2 10 3,800 9.6 13.5 50.006CY018-G103 400 5 15.0 10 4,200 9.6 13.5 50.006CY124-G103 400 6.5 20.0 10 5,400 11.8 16.5 80.006CY228-G103 400 7.5 23.3 10 6,300 14.9 20.9 99.006CY337-G103 400 10 30.8 10 8,300 16.6 23.3 114.006CY550-E103 200/400 15 41.7 19 11,000 37.1/18.6 52.0/26.0 283/14206CY550-F103 400 15 41.7 19 11,000 18.6 26.0 14206CY665-E103 200/400 20 54 19 14,000 60.7/30.0 85.0/42.0 345/17306CY665-F103 400 20 54 19 14,000 30.0 42.0 17306CY675-E103 200/400 20 62.5 19 14,000 60.7/30.0 85.0/42.0 345/17306CY675-F103 400 20 62.5 19 14,000 30.0 42.0 17306CY899-E103 200/400 30 82.5 19 2,1700 92.9/46.4 130/65.0 506/25306CY899-F103 400 30 82.5 19 21,700 46.4 65.0 253

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

163

CARLYLE REFRIGERATION COMPRESSORS

REQUIRED CIRCUIT BREAKERS: 06CY ... 60 HZ

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N

06CY550-E100HH83XB560††

HH83XB548†††06CY550-F100 HH83XB54806CY550-J100 HH83XB547

06CY665-E100HH83XB376††

HH83XB447†††

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N06CY665-F100 HH83XB44706CY665-J100 HH83XB555

06CY675-E100HH83XB376††

HH83XB559†††06CY675-F100 HH83XB55906CY675-J100 HH83XB430

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N

06CY899-E100HH83XB346††

HH83XB402†††06CY899-F100 HH83XB40206CY899-J100 HH83XB437

REQUIRED CIRCUIT BREAKERS: 06CY ... 50 HZ

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N

06CY550-E100HH83XB560††HH83XB548†††

06CY550-F100 HH83XB548

06CY665-E100HH83XB376††HH83XB447†††

06CY665-F100 HH83XB447

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N

06CY675-E100HH83XB376††

HH83XB559†††06CY675-F100 HH83XB559

COMPRESSORMODEL NO.

CIRCUITBREAKERS

P/N

06CY899-E100HH83XB346††

HH83XB402†††06CY899-F100 HH83XB402

NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.†This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.

††This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.†††This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).

Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

164

CARLYLE REFRIGERATION COMPRESSORS

REQUIRED ACCESSORIES - 06CY

REQUIRED ACCESSORIES - 06CY OPTIONAL ACCESSORIES

COMPRESSORMODEL NO.

SUCTIONSERVICE

VALVE KITP/N

ALTERNATESUCTIONSERVICE

VALVE KITP/N

DISCHARGESERVICE

VALVE KITP/N

ALTERNATEDISCHARGE

SERVICEVALVE KIT

P/N

SUSPENSIONKITP/N

MOUNTINGPLATE KIT

P/N

06CY016 06DA660063 06DA660065 06DA660062 06DA660064 06DA660057 06EA66009606EA660090 - -

06CY018 06DA660065 06EA660090 06DA660062 06DA66006406DA660063 - -

06CY124 06DA660065 06EA660090 06DA660062 06DA660064

06DA660063 - -

06CY228 06DA660065 06EA660090 06DA660062 06DA660064

06DA660063 - -

06CY337 06DA660090 06EA660065 06DA660064 06DA66006206DA660063 - -

06CY550 06EA660090 - 06DA660065 06EA660090 06EA66008906CY665 06EA660090 - 06DA660065 06EA66009006CY675 06EA660090 - 06DA660065 06EA66009006CY899 06EA660090 - 06DA660065 06EA660090

165

HERMETIC REFRIGERATION COMPRESSORS

COPELAND AFTERMARKET REFRIGERATION COMPRESSORS

P6 P7

60 Hertz Nominal Performance ±5% After 72 Run-InConditions (°F) Evap/Cond/Return Gas/Liquid/Ambient

Amperage RatingsR404A/507 Extended Med Temp. 20/120/40/120/95 °F -10/120/40/120/95 °F

Copeland P/N HP Volt/Phase CFM BTUH WATTS AMPS EER BTUHWATT

SAMPS EER RLA LRA MCC

RS43C1E-CAA-958 0.5 115-1 113 4,170 944 10.6 4.4 1,720 600 7.2 2.9 10.1 51 14.2

RS43C1E-IAA-958 0.5 115-1 113 4,170 944 10.6 4.4 1,720 596 8.1 2.9 10.1 51 14.2

RS43C1E-CAV-958 0.5 208/230-1 113 4,170 944 5.6 4.4 1,720 600 4.3 2.9 5.4 24.1 7.5

RS43C1E-IAV-958 0.5 208/230-1 113 4,170 944 5.6 4.4 1,720 600 4.3 2.9 5.7 24.1 8

RS64C1E-CAA-958 0.75 115-1 162 6,460 1470 12.9 4.4 2,860 1050 9.3 2.7 15.2 59 21.2

RS64C1E-IAA-958 0.75 115-1 162 6,460 1470 12.9 4.4 2,860 1050 9.3 2.7 17.5 76.7 24.5

RS64C1E-PAA-958 0.75 115-1 162 6,460 1470 12.9 4.4 2,860 1050 9.3 2.7 15.2 59 21.2

RS64C1E-CAV-958 0.75 208/230-1 162 6,450 1460 6.4 4.4 2,860 1050 4.6 2.7 7.7 37 10.8

RS64C1E-IAV-958 0.75 208/230-1 162 6,450 1460 8.6 4.4 2,860 1050 6.2 2.7 9.2 45 12.9

RS97C1E-CAA-959 1.5 115-1 245 9,590 1940 19.4 4.9 3,820 1250 14.4 3.1 19.6 95 29

RS97C1E-CAV-959 1.5 208/230-1 245 9,590 1940 9.7 4.9 3,820 1250 7.2 3.1 11 51 15.4

RS97C1E-TFC-959 1.5 208/230-1 245 9,400 1890 6.3 5 3,750 1210 4.7 3.1 7 35 9.8

CS12K6E-PFV-970 2 208/230-1 320 12,000 1930 8.8 6.2 3,990 1120 5.4 3.6 10.9 56 15.3

CS12K6E-PFJ-970 2 265-1 320 12,000 1930 7.6 6.2 3,990 1120 4.7 3.6 10.9 55 15.2

CS12K6E-TF5-970 2 208/230-3 320 11,700 1860 5.8 6.3 3,830 1090 3.6 3.5 7.5 51 10.5

CS14K6E-PFV-970 2.5 208/230-1 350 14,100 2280 10.3 6.2 5,440 1420 6.6 3.8 12.4 61 17.4

CS14K6E-PFJ-970 2.5 265-1 350 14,100 2280 8.9 6.2 5,440 1420 5.7 3.8 12.5 58 17.5

CS14K6E-TF5-970 2.5 208/230-3 350 13,800 2210 6.9 6.2 5,330 1370 4.5 3.9 9.1 55 12.8

CS14K6E-TFD-970 2.5 208/230-3 350 13,800 2210 3.4 6.2 5,330 1370 2.2 3.9 4.7 28 6.6

CS20K6E-PFV-970 3 208/230-1 535 20,000 3120 14.9 6.4 7,050 1850 10 3.8 18.6 96 26

CS20K6E-TF5-970 3 208/230-3 535 19,600 3030 10 6.5 6,910 1800 6.7 3.8 11.4 75 16

CS20K6E-TFD-970 3 460-3 535 19,600 3030 5 6.5 6,910 1800 3.4 3.8 5.1 40 7.1

CS27K3E-PFV-970 4 208/230-1 665 26,500 4420 20.3 6 9,370 4460 12.2 3.8 23.9 95.4 33.5

CS27K3E-TF5-970 4 208/230-3 665 26,000 4290 13.1 6.1 9,070 2495 8.1 3.6 15.6 82 21.4

CS27K3E-TFD-970 4 460-3 665 26,000 4290 6.6 6.1 9,070 2495 4.1 3.6 8.5 41 11.8

CS33K3E-PFV-970 5 2230/230-1 756 31,600 5290 25.3 6 11,500 3070 15.8 3.8 30.7 125 43

CS33K3E-TF5-970 5 208/230-3 756 31,200 5190 15.2 6 11,700 2920 9.9 4 20.7 90 29

CS33K3E-TFD-970 5 380/460-3 756 31,200 5190 7.6 6 11,700 2920 5 4 9.9 45 13.8

166

HERMETIC REFRIGERATION COMPRESSORS

COPELAND AFTERMARKET REFRIGERATION COMPRESSORS (cont)

60 Hertz Nominal Performance Conditions (°F): Evap/Cond/Return Gas/Liquid/Ambient

Amperage Ratings*R-22 High Temp. 45/130/65/95 °F 20/120/65/120/95 °F

Copeland P/N HP Volt/Phase CFM BTUH WATTS AMPS EER BTUH WATTS AMPS EER RLA LRA MCCJRF4-0050-IAA-958 0.5 115-1 113 7,360 1090 13 6.8 4320 850 11.6 5.1 13.6 71 19

JRF4-0050-IAV-958 0.5 208/230-1 113 7,360 1090 7 6.8 4320 850 5.8 5.1 6.4 34 9

RRGA-0100-PAA-950 1 115-1 161 10,800 1390 12.6 7.8 6170 1050 9.8 5.9 13.2 60 18.5

RRGA-0100-PAV-950 1 208/230-1 161 10,800 1390 6.3 7.8 6170 1050 4.9 5.9 6 33.5 8.4

CRA1-0150-PFV-970 1.5 208/230-1 242.5 16,960 1870 8.3 9.1 9430 1430 6 6.6 10.8 48 15.1

CRA1-0150-TF5-970 1.5 208/230-1 242.5 17,190 1810 5.8 9.5 9690 1350 5 7.2 9.3 58 13

CRA1-0150-TFC-970 1.5 208/230-1 242.5 17,190 1810 2.9 9.5 9690 1350 3 7.2 4.1 17.4 5.7

REK3-0125-PFV-959 1.25 115-1 174.7 12,500 1440 6 8.7 7090 1110 5.1 6.4 7 34.2 9.8

REK3-0125-TFC-959 1.25 208/230-1 174.7 12,400 1370 3.8 9.1 7370 1020 3.1 7.2 4.7 31 6.6

RSE4-0075-IAA-958 0.75 115-1 135 8,620 1250 15.2 6.9 5060 940 13.2 5.4 14.3 66.3 20

RSE4-0075-IAV-958 0.75 208/230-1 135 8,620 1250 15.2 6.9 5060 940 6.6 5.4 7.1 35.5 10

R-22 Medium Temp. 20/120/40/120/95 °F 0/110/40/110/95 °FCopeland P/N HP Volt / Phase CFM BTUH WATTS AMPS EER BTUH WATTS AMPS EER RLA LRA MCC

RSE4-0075-IAA-958 0.75 115-1 135.3 4770 930 6.5 5.1 2630 690 5.8 3.8 14.3 66.3 20

RSE4-0075-IAV-958 0.75 208/230-1 135.3 4770 930 3.3 5.1 2630 690 2.9 3.8 7.1 35.5 10

RSN6-0075-IAA-958 0.75 115-1 162.4 6200 1190 15 5.2 3680 870 13 4.2 14.3 66.3 20

RSN6-0075-IAV-958 0.75 208/230-1 162.4 6200 1190 7.5 5.2 3680 870 6.5 4.2 6.9 45 9.6

RSL2-0101-CAA-959 1 115-1 244.5 9620 1760 18.2 5.5 5500 1300 14.8 4.2 18 78 25.2

RSL2-0101-CAV-959 1 208/230-1 244.5 9620 1760 9.1 5.5 5500 1300 7.4 4.2 10.4 51 14.5

Copeland Compressor Family SeriesEither a number or a letter

established for eachproduct model.

Compressor nominal capacity at ratingconditions to twosignificant digits.

X X X X X X E - X X X - X X X

Compressor Motor TypesPhase Description Code 1 Capacitor Run - Capacitor Start C 1 Induction Run - Capacitor Start I 1 Capacitor Run - Permanent P Split Capacitor 3 Three Phase T

Bill of Material*(See Opposite Page)

Code Description R = High Temperature S = Medium Temperature F = Low Temperature T = Two Speed

CapacityMultiplierC = 100

K = 1000

Model VariationA number or letter,

assigned to indicatedifferent modeltypes within any

one family series.

Compressor Motor ProtectionType Protection CodeExternal Thermal Protection -One Protector (Line Break) AUse with Contactor InternalInherent Protection -One Protector (Line Break) FUse with Contactor

Electrical Codes60 Hz 50 Hz Codes115-1 - A208/230-3 200/220-3 C460-3 380/420-3 D575-3 550-3 E265-1 220/240-1 J - 380/420-3 M208/230-1 200-1 V - 220/240-1 Z200/230-3 200/240-3 5

Indicatescompressors with polyolester oil.

Comp. Motor RatingNominal (HP) Code 1/2 0050 3/4 0075 1 0100 1-1/4 0125 1-1/2 0150 1-3/4 0175 2 0200 2-1/4 0225 2-3/4 0275 3 0275 3-1/2 0350 4 0400 4-1/2 0450 5 0500 7-1/2 7500 9 0900 10 1000 12 1200

Nomenclature

167

HERMETIC REFRIGERATION COMPRESSORS

BILL OF MATERIAL INFORMATION

xxxx-xxxx-xxx- The last 3 digits of any model is a unique bill of material.

xxxx-xxxx-xxx- xx’sexamples: -959 or -970

Wholesaler service compressors used to replaces the above bills of material in most situations which include oil, protector, terminal box cover, and mounting parts in a single carton.

The Second Digit xxxx-xxxx-xxx-x x Rotalock connection(s) or a valve welded on the suction side. xxxx-xxxx-xxx-x x Sweat connections with terminal flag kit, no electrical components.

Copeland “CR” Compressors primarilyThe Third Digit xxxx-xxxx-xxx-xx No electrical components with the compressor.

xxxx-xxxx-xxx-xx Electrical components mounted. xxxx-xxxx-xxx-xx Electrical components remote, in the box with the service compressor.