    CASCADE DESIGNPresented By:

    SHAEEZ USMAN ABDULLA

    ROLL NO: 10

    M1 AEI

    1

  • 7/28/2019 Cascade Design

    2/24

    INTRODUCTION

    Cascade Control

    Cascade control has a multi-loop structure, where the output of the

    controller in the outer loop (the primary or master) is the set point

    of a controller in the inner loop (the secondary or slave).

    2

  • 7/28/2019 Cascade Design

    3/24

    In the cascade configuration the process is divided into two parts and

    therefore two controllers are used, but only one process variable(m) is

    manipulated.

    3

    INTRODUCTION

  • 7/28/2019 Cascade Design

    4/24

    The primary controller maintains the primary variable y1 at its set point

    by adjusting the set point r2 of the secondary controller. The secondary

    controller, in turn, responds both to set point r2 and to the secondary

    controlled variable y2. This secondary controlled variable also affects

    the primary process and therefore the primary controlled variable (y1),hence the loop is closed.

    4

    INTRODUCTION

  • 7/28/2019 Cascade Design

    5/24

    Cascade control is advantageous on applications where1) P1 process has a large dead time or time lag

    2) Time delays in the P2 part of the process are smaller.

    3) The main disturbance is in the secondary loop. This is becausewith the cascade configuration, the correction of the inner

    disturbance di occurs as soon as the secondary sensor (y2) detects

    that upset.

    5

    INTRODUCTION

  • 7/28/2019 Cascade Design

    6/24

    6

    INTRODUCTION

    Cascade System Advantages

    1) Disturbances that are affecting the secondary variable can be

    corrected by the secondary controller before their influence is felt

    by the primary variable.

    2) reduces the phase lag seen by the primary controller, resulting in

    increased speed of response.

  • 7/28/2019 Cascade Design

    7/24

    7

    COMPONENTS OF THE CASCADE LOOPThe primary or outer control loop of a cascade system is designed only

    after the secondary loop has already been designed. This is because

    the characteristics of the slave loop have an effect on the master loop.

  • 7/28/2019 Cascade Design

    8/24

    The Secondary Loop

    Ideally, the secondary variable should be so selected as to split the

    process time delays approximately in half. This means that the

    secondary loop should be closed around half of the total time lags in

    the process.

    8

    COMPONENTS OF THE CASCADE LOOP

  • 7/28/2019 Cascade Design

    9/24

    The Secondary Loop

    To demonstrate this need, consider two extreme cases:

    1) If the secondary variable responded instantly to the manipulated

    variable (no time delay in the secondary loop), the secondary

    controller would accomplish nothing.

    2) If the secondary loop was closed around the entire process, the

    primary controller would have no function.

    9

    COMPONENTS OF THE CASCADE LOOP

  • 7/28/2019 Cascade Design

    10/24

    10

    COMPONENTS OF THE CASCADE LOOPThe Secondary Loop

    Therefore, the dynamic elements of the process should be

    distributed as equitably as possible between the two controllers.

    When most of the process dynamics are enclosed in the secondary

    loop, that can cause problems. Although the response of the

    secondary loop is faster than the open loop configuration, in which

    a secondary controller does not even exist , its dynamic gain is also

    higher, as indicated by the damped oscillation.

  • 7/28/2019 Cascade Design

    11/24

    11

    COMPONENTS OF THE CASCADE LOOPSecondary Control Variables

    The most common types of secondary control variables:

    Valve Position Control (Positioner) :- Friction produces hysteresis

    between the action of the control signal and its effect on the valve

    position.

    Flow Control :- A cascade flow loop can overcome the effects of

    valve hysteresis.

    Temperature Control :- The most commonly accepted configuration

    has the reactor temperature controlled by manipulating the coolanttemperature in cascade.

  • 7/28/2019 Cascade Design

    12/24

    Speed Control of a DC Motor

    The current can reach high peaks during the start-up and shut-down

    phases. Therefore it is usual to apply cascade control with the

    armature current as the secondary variable. Saturation applied at the

    current set point (reference value) limits the maximum value of thecurrent.

    12

    CASCADE APPLICATION EXAMPLES

  • 7/28/2019 Cascade Design

    13/24

    13

    CASCADE APPLICATION EXAMPLES

    Room Temperature Control

    The variation in steam pressure can be the main source of upsets. The

    secondary variable is the inlet air temperature measured immediately

    after the heat exchanger, as the disturbances in the steam pressure

    affect it much sooner than they affect the room temperature

  • 7/28/2019 Cascade Design

    14/24

    The process controlled by a cascade system is shown

    14

    CASCADE CONTROLLER DESIGN EXAMPLE

  • 7/28/2019 Cascade Design

    15/24

    First design a single-series PID controller, with feedback taken from the

    output signal y1. Design objectives are stability and good reference

    signal (set point) tracking properties characterized by zero steady-state

    error and about 60 of the phase margin to keep the overshoot below

    10%, when a step change is introduced in the set point.

    15

    CASCADE CONTROLLER DESIGN EXAMPLE

  • 7/28/2019 Cascade Design

    16/24

    Cascade Controller System Design

    Design a cascade control system with feedback taken from the primary

    and secondary (outer and inner) controlled variables (process outputs)

    y1 and y2, respectively. Both control loops have to be stable. The design

    objectives for tracking the set point (reference signal) are the same asbefore. Fast response is also required to any upsets in the secondary

    loop or measurement.

    16

    CASCADE CONTROLLER DESIGN EXAMPLE

  • 7/28/2019 Cascade Design

    17/24

    17

    CASCADE CONTROLLER DESIGN EXAMPLECascade Controller System Design

    The inner (secondary) controller can be proportional only.

    Transfer function of the inner closed loop between signals y2 and u1

    is

  • 7/28/2019 Cascade Design

    18/24

    18

    CASCADE CONTROLLER DESIGN EXAMPLECascade Controller System Design

    In the primary (outer) loop a PI controller is used, which will be

    responsible for accurate steady-state tracking of a step change in

    the set point (reference signal). The transfer function of the

    controller is

  • 7/28/2019 Cascade Design

    19/24

    19

    CASCADE CONTROLLER DESIGN EXAMPLESimulation Results

    The set-point (reference signal) change is a unit step that occurs at a

    time point of 10 sec. A unit step inner disturbance is added at a time

    point of 250 sec.

    response to upsets

    set-point (reference

    signal) tracking

  • 7/28/2019 Cascade Design

    20/24

    20

    CASCADE CONTROLLER DESIGN EXAMPLESimulation Results

    Effect of model parameter uncertainties in cases of the single loop and

    the cascade system.

  • 7/28/2019 Cascade Design

    21/24

    21

    CASCADE CONTROLLER DESIGN EXAMPLESimulation Results

    Controlled variable responses of the single-loop and cascade control

    systems, assuming all dynamic parameters (time constants) of the

    process and its gain are both at their highest values.

  • 7/28/2019 Cascade Design

    22/24

    Cascade loops consist of two or more controllers in series and have

    only a single, independently adjustable set point, that of the

    primary (master) controller. The main value of having secondary

    (slave) controllers is that they act as the first line of defense against

    disturbances, preventing these upsets from entering and upsettingthe primary process.

    In order for the cascade loop to be effective, it should be more

    responsive (faster) than the master. Some rules of thumb suggest

    that the slaves time constant should be under 1/4 to 1/10 that of

    the master loop and the slaves period of oscillation should beunder 1/2 to 1/3 that of the master loop.

    22

    SUMMARY

  • 7/28/2019 Cascade Design

    23/24

    The goal is to distribute the time constants more-or-less evenly

    between the inner (slave or secondary) and outer (master or

    primary) loops, while making sure that the largest time constant is

    not placed within the inner loop.

    23

    SUMMARY

  • 7/28/2019 Cascade Design

    24/24

    Bela G. Liptak, Bila G. Liptak,Instrument Engineers' Handbook, Volume

    2: Process Control And Optimization, 4th Edition, Crc Press, Sep 2005.

    24

    REFERENCE