cascade_control_se665

Upload: nurulfarihahmohdzulkefle

Post on 08-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/7/2019 Cascade_Control_SE665

    1/20

    EXPERIMENT 6

    Cascade Control

    6.1 Objective

    (i) To demonstrate the characteristics of On/Off control

    (ii) To demonstrate the characteristics of PID control

    (iii) To demonstrate the characteristics of Proportional Band, Integral Action and Derivative Action

    on a cascade process control loop.

    (iv) To demonstrate the characteristics of cascade control

    6.2 Introduction

    TheCascade Control Modulehas been designed for students demonstration and to give them

    better understanding on how open and closed tank level measurement and level control is done,

    and to provide them with a hands on experience on manipulating various control parameters

    using a microprocessor based controller. It can be coupled with a flow metering loop to enable

    cascade control studies. The equipment consists of industrial grade instrumentation to exhibit a

    realistic working environment of a true level process using various types of measuring

    instruments and control strategy.

    The equipment is self contained and constructed on an epoxy coated mild steel frame with four

    lockable castor wheels. The pumps, tanks, instrumentation and valves are strategically located

  • 8/7/2019 Cascade_Control_SE665

    2/20

    p p g y

    6.2.1 Process Description

    The SOLTEQ Model: SE 665 Cascade Control Trainer is a water process. Water from the sump

    tank, T-601 is pumped by P-601 to the level tank, T-602. There are two discharge possibilities

    from the T-602 back to the T-601. One is known as the self-regulatory mode using gravity flow

    for the water to return to the sump tank. The other is the non self-regulatory mode, using a

    pump P-602 to drain the water from the tank.

    6.2.2 Control Strategy

    Various types of instrumentations are installed in the process. There are two PID control loops in

    the process controller that controls the process, namely FIC-601 and LIC-603. There is a switch

    at the local control panel, which allows selection of either flow control or level control or a

    combination of the two, called the flow/level cascade control.

    6.2.3 Level Control Loop

    The level transmitter LT-603 feed the signal to LIC-603, which controls the valve FCV-601.

    6.2.4 Flow Control Loop

    The orifice flow transmitter FT-601 feed the signal to FIC-601, which controls the valve FCV-601.

  • 8/7/2019 Cascade_Control_SE665

    3/20

    6.2.6 Experimental Capabilities

    PID Single Loop Flow Control

    PID Single Loop Level Control

    Self-Regulating

    Non Self-Regulating

    On/Off Control

    PID Level and Flow Cascade Control

    Table 6.1 Instrument function and capabilities

    No. Instrument Tag No. Description Range

    1 PID ControllerFIC-601

    LIC-603

    Microprocessor based PID

    controller, controlling level / flow-

    2 RecorderLR-603

    FR-603

    Continuous 2-pen chart

    recorder-

    3Orifice D/P

    TransmitterFT-601

    Primary flow measurement

    device giving 4 20 mA output0 100 LPM

    4 D/P Transmitter LT-603Level measurement using

    differential pressure.

    0-

    1000mmH2O

    5 Control Valve FCV-601

    1 inch globe type valve with

    Cv=4.8, linear characteristic

    with I/P positioner and I/P1 100%

  • 8/7/2019 Cascade_Control_SE665

    4/20

    11 RotameterFI-601

    FI-602

    Flowrate measurement forwaterFlowrate measurement for air

    0 100 LPM

    0 6 LPM

    12 Pressure Indicator

    PI-601

    PI-602

    PI-603

    Dial gauge pressure indicator at

    location.

    0 4 bar

    0 4 bar

    0 4 bar

    13 Side GlassSG-601

    SG-602

    Observation of water level in

    tanks.-

    6.3 Process Control

    Student may refer to section 0.3.1 for theory of process control

    6.3.1 On/Off Control

    Student may refer to section 0.3.2 for theory of On/Off Control

    6.3.2 Proportional Control

    Student may refer to section 0.3.3 for theory of proportional control

    6.3.3 Integral Control

    Student may refer to section 0.3.4 for theory of integral control

    6.3.4 PID Control

  • 8/7/2019 Cascade_Control_SE665

    5/20

    6.4 Procedure

    Table 6.2 Start up procedure

    STEP ACTION REMARKS

    1

    Ensure that all valves are set according to Flow Control Initial

    Valves Position outlined in Table 1

    Table 1:Flow Control Initial Valve Positions

    Open CloseHV612 HV611HV614 HV613HV615 HV616

    HV617 HV618HV620

    2 Fill in Sump Tank T-601 with water to about 80% full.

    3 Switch on the panel.

    4Set the Control Mode switch to Flowto engage the Flow

    control loop.

    5 Switch on Pump P-601

    6 Put the Controller FIC-601 into manual mode, then set theoutput to 100%.

  • 8/7/2019 Cascade_Control_SE665

    6/20

    3Tune the output gradually so that the flow measurement

    matches the set point at 50%.

    4Turn on the recorder, then put the control loop into "auto"

    mode.

    5Stimulate load change by closing HV615 for 3 seconds, then

    open HV615 back.

    6Once the measurement stabilizes, turn off the recorder. Put

    the control loop back into "manual" mode.

    7Tune the output gradually so that the flow measurement

    matches the set point at 50%.

    8Turn on the recorder, then put the control loop into "auto"

    mode.

    9Stimulate a set point change by increasing the set point to

    75%.

    10Observe the response. Once the response stabilizes, turn off

    the recorder. Put the control loop back into "manual" mode.

    11

    With the I and D values maintained, repeat step 2 to step 10with the following PB values

  • 8/7/2019 Cascade_Control_SE665

    7/20

    4Turn on the recorder, then put the control loop into "auto"

    mode.

    5Stimulate load change by closing HV615 for 3 seconds, then open

    HV615 back.

    6Once the measurement stabilizes, turn off the recorder. Put the

    control loop back into "manual" mode.

    7Tune the output gradually so that the flow measurement matches

    the set point at 50%.

    8 Turn on the recorder, then put the control loop into "auto" mode.

    9 Stimulate a set point change by increasing the set point to 75%.

    10Once the measurement stabilizes, turn off the recorder. Put the

    control loop back into "manual" mode.

    11

    With the PB and D values maintained, repeat step 2 to step 10 withthe following I values

    I

    15

    62

    Table 6.5 PID Flow Control

  • 8/7/2019 Cascade_Control_SE665

    8/20

    5Stimulate load change by closing HV615 for 3 seconds, then

    open HV615 back.

    6Once the measurement stabilizes, turn off the recorder. Put

    the control loop back into "manual" mode.

    7Tune the output gradually so that the flow measurement

    matches the set point at 50%.

    8Turn on the recorder, then put the control loop into "auto"

    mode.

    9Stimulate a set point change by increasing the set point to

    75%.

    10 Once the measurement stabilizes, turn off the recorder. Putthe control loop back into "manual" mode.

    11

    With the PB and I values maintained, repeat step 2 to step 10with the following D values

    D

    510

    Table 6.6 PI Flow Control Loop Tuning

    STEP ACTION REMARKS

  • 8/7/2019 Cascade_Control_SE665

    9/20

    values are as follows: -

    PB

    100252

    5

    Determine the natural period using the following method

    Natural Period, min60SpeedTrend

    DT

    Where D = Distance in mm between successive crests or

    valleys

    6

    Set the Integral Time to the Natural period, repeat Step 3 and

    6. The period of oscillation should increase by 40%. If the

    period is longer than this, increase the integral time. If the

    period is shorter than this, decrease the Integral time.

    7Finally, adjust (increase) the PB until the desire degree of

    damping is achieved

    6.4 Level Process Control

    The Level Experiments can be run either in Self-Regulating mode or Non-Self-Regulating mode.

    The Procedure of experiments in sections 3B to 6B are based on self-regulating (Flow Under

    Head) operation mode.

  • 8/7/2019 Cascade_Control_SE665

    10/20

    Table 6.7 Self-Regulating (Flow Under Head)

    STEP ACTION REMARKS

    1

    Ensure that all valves are set according to Level Control

    Initial Valve Positions (Self-Regulating) outlined in Table 2.

    Table 2: Level Control Initial Valve Positions (Self-

    Regulating)

    Open Close

    HV612 HV611

    HV614 HV613HV615 HV616HV619 HV618

    HV620 HV621HV624 HV622

    HV623HV625

    2 Fill in Sump Tank T-601.

    3 Switch on the panel

    4Set the Control Mode switch to Levelto engage the level

    control loop.

    5 Switch on Pump P-601.

    6 Align the mark on the HV620 handle to about 45o.

    7 Y d d h i

  • 8/7/2019 Cascade_Control_SE665

    11/20

    Table 6.8 Non-Self-Regulating (Pump Discharge)

    STEP ACTION REMARKS

    1

    Ensure that all valves are set according to Level Control

    Initial Valve Positions (Non-Self-Regulating) outlined in Table

    3

    Table 3: Level Control Initial Valve Positions (Non-Self-

    Regulating)

    Open CloseHV612 HV611HV614 HV613HV615 HV616

    HV621 HV618HV622 HV623

    HV626 (30o) HV625

    2 Fill in Sump Tank T-601.

    3 Switch on the panel

    4Set the Control Mode switch to Levelto engage the level

    control loop.

    5 Switch on Pump P-601.

    6 You are now ready to proceed to the experiment.

  • 8/7/2019 Cascade_Control_SE665

    12/20

    4Turn on the recorder, then put the control loop into "auto"

    mode.

    5

    Stimulate load change by opening HV620 fully for 20

    seconds. (Be careful not to empty the tank during the

    process) and restore it to its original position.

    6Once the measurement stabilizes, turn off the recorder. Put

    the control loop back into "Manual" mode.

    7Tune the output gradually so that the level measurement

    matches the set point at 50%.

    8Turn on the recorder, then put the control loop into "auto"

    mode.

    9

    Stimulate a set point change by increasing the set point to

    75%.

    10Once the measurement stabilizes, turn off the recorder. Putthe control loop back into "Manual" mode.

    Table 6.10 Proportional only Level Control

    STEP ACTION REMARKS

    Enter PB value of 100, I value of 1000 seconds, and D value

  • 8/7/2019 Cascade_Control_SE665

    13/20

    6Once the measurement stabilizes, turn off the recorder. Put

    the control loop back into "Manual" mode.

    7Tune the output gradually so that the level measurement

    matches the set point at 50%.

    8Turn on the recorder, then put the control loop into "auto"

    mode.

    9Stimulate a set point change by increasing the set point to

    75%.

    10Once the measurement stabilizes, turn off the recorder. Put

    the control loop back into "Manual" mode

    11

    With the I and D values maintained, repeat step 8 to step 16with the following PB values

    PB

    1062s

    Table 6.11 Proportional and Integral Level Control

    STEP ACTION REMARKS

    1

    Enter PB value of 100, I value of 60 seconds, and D value of

    0 second

  • 8/7/2019 Cascade_Control_SE665

    14/20

    7Tune the output gradually so that the level measurement

    matches the set point at 50%.

    8Turn on the recorder, then put the control loop into "auto"

    mode.

    9Stimulate a set point change by increasing the set point to

    75%.

    10 Once the measurement stabilizes, turn off the recorder.

    11

    With the PB and D values maintained, repeat step 8 to step16 with the following I values

    I

    30155

    Table 6.12 PID Level Control

    STEP ACTION REMARKS

    1

    Enter PB value of 100, I value of 6 seconds, and D value of 0

    second.

    2Put the control loop into "manual" mode, then adjust the set

  • 8/7/2019 Cascade_Control_SE665

    15/20

    7Tune the output gradually so that the level measurement

    matches the set point at 50%.

    8Turn on the recorder, then put the control loop into "auto"

    mode.

    9Stimulate a set point change by increasing the set point to

    75%.

    10Once measurement stabilizes, turn off the recorder. Put the

    control loop back into "Manual" mode.

    11

    With the PB and I values maintained, repeat step 2 to step 10with the following D values

    D

    1

    61230

    60

    Table 6.13 PID Level Control Loop Tuning

    STEP ACTION REMARKS

    1

    Enter a PB value of 100, I value of 1000 seconds and D

    value of 0 second. (Setting the I to its maximum and D to its

    minimum providing proportional only control)

  • 8/7/2019 Cascade_Control_SE665

    16/20

    5

    Determine the natural period using the following method:

    Natural Period, min60TrendSpeed

    DT

    Where D = Distance in mm between successive crests or valle

    6

    Maintain the PB value. Set I to 0.4T and D to 0.15T. Repeat

    Step 2 and 4 and observe the response. There should be a

    25% decrease in period. If the new period of oscillation is

    shorter than this, reduce derivative time, if the period is

    longer increase integral time.

    7Finally, adjust (increase) the PB until the desire degree of

    damping is achieved

    LEVEL AND FLOW CASCADE PROCESS CONTROL

    Table 6.14 Start-Up Procedure

    STEP ACTION REMARKS

    1

    Ensure that all valves are set according to Level and Flow

    Cascade Control Initial Valve Position outlined in Table 4.

    Table 4:Cascade Control Initial Valve Positions

    Open Close

    HV612 HV611HV614 HV613

  • 8/7/2019 Cascade_Control_SE665

    17/20

    5 Switch on Pump P-601.

    6Put the Controller FIC-601 into manual mode, then set the

    output to 100%.

    7 Adjust HV618 to set flow measurement FT-601 to 100%.

    8 You are now ready to proceed to the experiment.

    Table 6.15 PID Level and Flow Cascade Control

    STEP ACTION REMARKS

    1Enter PID values as obtained in Level loop tuning.

    2 Enter PI values as obtained in Flow loop tuning.

    3

    Put the control loop into "Manual" mode. Adjust the output of

    the controller gradually so that the level of tank matches the

    set point of 50%.

    4

    Turn on the recorder, and then put the control loop into

    "Auto" mode. Wait until measurement settle down and

  • 8/7/2019 Cascade_Control_SE665

    18/20

    9Wait until the measurement stabilizes, then turn off the recorder. Put

    the control loop back into manual mode.

    10Compare the cascade chart with the chart obtained from Level PID

    experiments.

    Appendix

    A ] FLOW CONTROL TUNING

    P CONTROL PI CONTROL PID CONTROL

    P 50 100 209.1 209.1 209.1 209.1 209.1 209.1 209.1

    I 9999 9999 9999 2.4 7.9 20.9 2.4 2.4 2.4

    D 0 0 0 0 0 0 2.0 4.0 5.0

    B ] LEVEL CONTROL TUNING

    P CONTROL PI CONTROL PID CONTROL

    P 6.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6 16.6I 9999 9999 9999 5.6 13.6 25.6 13.6 13.6 13.6

  • 8/7/2019 Cascade_Control_SE665

    19/20

    Piping and Instrumentation Diagram

  • 8/7/2019 Cascade_Control_SE665

    20/20