case model - daikin · since the "troubleshooting flow chart" in the skyair servic e...

18
1 / 18 August, 20, 2008 Reliable technology ensures maximum customer satisfaction. M-08003 Since the "Troubleshooting Flow Chart" in the SkyAir Service Manual had errors in the description of the Error Code "E9", we make a correction to these errors as below. [Detail of Correction] In the description of the Error Code "E9" in the Troubleshooting Flow Chart, we made errors in describing the measuring point of and the criteria for the resistance of electronic expansion valve coil. The measuring point and criteria vary with the types of electronic expansion valve. Referring to the table shown below and the attached information. Type A Measuring point Criteria Applicable model Type B Measuring point Criteria Applicable model 1 - 5 27~37RZP125~140D 1 - 5 40~50RZQ(S)100~140C7 RZQ(S)71~125B7 · 8 · 9 RZQ100~140K(A) RZQ71F · 90C · 100F RQ71F, RQ100~160K RZQ100~160P 2 - 5 3 - 5 3 - 5 2 - 6 4 - 5 4 - 6 Type C Measuring point Criteria Applicable model Type D Measuring point Criteria Applicable model 1 - 6 40~50RZQ(S)71C7 RZQ71KA 1 - 6 40~50RZQ71C7 RZQS71C7 RZQ71D RZP71~100D R(Y)42 · 71~140LU 2 - 6 3 - 6 3 - 6 2 - 5 4 - 6 4 - 5 Type E Measuring point Criteria Applicable model 1 - 2 135~165RZQ200C7 RZQ250C7 4 - 2 3 - 5 6 - 5 Case Model RZQ(S)71~140B · C · F · K(A) RZQ200C7 · 250C7 RZP71~140D RQ71F, RQ100~160K R42LU · R71~140LU RZQ100~160P Correction of SkyAir Service Manual

Upload: tranhuong

Post on 11-Jul-2018

261 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

1 / 18

August, 20, 2008

Reliable technology ensures maximum customer satisfaction. M-08003

Since the "Troubleshooting Flow Chart" in the SkyAir Service Manual had errors in the description of the Error Code "E9", we make a correction to these errors as below.

[Detail of Correction]In the description of the Error Code "E9" in the Troubleshooting Flow Chart, we made errors in describing the measuring point of and the criteria for the resistance of electronic expansion valve coil.The measuring point and criteria vary with the types of electronic expansion valve. Referring to the table shown below and the attached information.

Type A Measuring point

Criteria Applicable modelType B Measuring

pointCriteria Applicable model

1 - 5

27~37Ω RZP125~140D

1 - 5

40~50Ω

RZQ(S)100~140C7RZQ(S)71~125B7 · 8 · 9RZQ100~140K(A)RZQ71F · 90C · 100FRQ71F, RQ100~160KRZQ100~160P

2 - 5 3 - 5

3 - 5 2 - 6

4 - 5 4 - 6

Type C Measuring point

Criteria Applicable modelType D Measuring

pointCriteria Applicable model

1 - 6

40~50Ω RZQ(S)71C7RZQ71KA

1 - 6

40~50Ω

RZQ71C7RZQS71C7RZQ71DRZP71~100DR(Y)42 · 71~140LU

2 - 6 3 - 6

3 - 6 2 - 5

4 - 6 4 - 5

Type E Measuring point

Criteria Applicable model

1 - 2

135~165Ω RZQ200C7RZQ250C7

4 - 2

3 - 5

6 - 5

Case

Model

RZQ(S)71~140B · C · F · K(A)RZQ200C7 · 250C7RZP71~140DRQ71F, RQ100~160KR42LU · R71~140LURZQ100~160P

Correction of SkyAir Service Manual

Page 2: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

2 / 18[Corresponding Service Manuals]

Product No. Issue datePage

describing E9Applicable models

Information attached for replacement

1Si20-502Pocket manual

03/2005 P. 54 RZP71~140D Attachment

2Si20-701Pocket manual

09/2007 P. 424 ALL models Attachment

3 Si21-204 03/2003 P. 206 R71~140LU Attachment

4 Si25-110 04/2002 P. 157 RZP71~140D Attachment

5 Si25-601 07/2006 P. 146 RZQ125 · 140K Attachment

6 SiAU25-401 09/2004 P. 186 RZQ90C Attachment

7 SiAU28-605 02/2007 P. 124 RZQ100~160P Attachment

8 SiAU28-606 01/2007 P. 232 RZQ71F, 90C, 100F Attachment

9 SiAU28-703 11/2007 P. 180 RZQ71F, 100~160K Attachment

10 SiAU28-704 02/2008 P. 174 RQ71F, 100~160K Attachment

11 SiBE26-701 05/2007 P. 129 RZQ200 · 250C Attachment

12 SiBE27-702 06/2007 P. 198RZQ71B9, RZQS71, 100B7RZQ100~140C7, RZQS125 · 140C7RZQ100~140B8

Attachment

13 SiBE28-804 05/2008 P. 190RZQ(S)71C7V1BRZQ(S)100~140C7V1B

Attachment

14 SiTH21-804 01/2008 P. 110 R42LU Attachment

15 SiTW28-802 07/2008 P. 180RZQ71KARZQ100~140KA

Attachment

Page 3: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

3 / 18

RZP71~100D

RZP125~140D

1

2

3

4

5

6

Measuring point1 - 63 - 62 - 54 - 5

(White)

(Yellow)

(Orange)

(Blue)

(Brown)

(Red)

Criteria40~50Ω

or 27~37Ω.

1

2

3

4

5

Measuring point1 - 52 - 53 - 54 - 5

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

Criteria27~37Ω

Attachment

Page 4: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

4 / 18

or 27~37Ω.

Go on to the next page.

Attachment

1

2

3

4

5

6

Measuring point1 - 63 - 62 - 54 - 5

(White)

(Yellow)

(Orange)

(Blue)

(Brown)

(Red)

Criteria40~50Ω

RZP - D

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

RZQ71F · 90C · 100FRZQ(S)71~140B7 · 8 · 9

Criteria40~50Ω

Criteria40~50Ω

1

2

3

4

5

6

Measuring point1 - 63 - 62 - 54 - 5

White

Yellow

Orange

Blue

Brown

Red

R(Y) - LU

RZP125~140D

1

2

3

4

5

Measuring point1 - 52 - 53 - 54 - 5

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

Criteria27~37Ω

Page 5: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

5 / 18

1

2

3

4

5

6

Measuring point1 - 62 - 63 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)COM(+)

Criteria40~50Ω

Criteria40~50Ω

Criteria135~165Ω

Continued from the previous page.

RZQ(S)71C7

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

Measuring point1 - 24 - 23 - 56 - 5

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

RZQ71~125B9

RZQ200, 250C

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RZQ(S)100~140C7

1 2 3(Blue) (Brown) (Orange)

(Yellow) (Red) (White)4 5 6

*1. Measure the resistance between each pin of connector and make sure that the resistance ranges between 135 and 165Ω.

Page 6: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

6 / 18

1

2

3

4

5

6

Measuring point1(WHT) - 6(RED)3(ORG) - 6(RED)2(YLW) - 5(BRN)4(BLU) - 5(BRN)

(White)

(Yellow)

(Orange)

(Blue)

(Brown)

(Red)

LU Series

Attachment

Page 7: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

7 / 18

Attachment

RZP71~100D

RZP125~140D

1

2

3

4

5

6

Measuring point1 - 63 - 62 - 54 - 5

(White)

(Yellow)

(Orange)

(Blue)

(Brown)

(Red)

Criteria40~50Ω

1

2

3

4

5

Measuring point1 - 52 - 53 - 54 - 5

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

Criteria27~37Ω

or 27~37Ω.

Page 8: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

8 / 18

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RZQ125 · 140K

Attachment

between 40~50Ω.

Page 9: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

9 / 18

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RZQ90C

Attachment

Page 10: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

10 / 18

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RZQ100~160P

Attachment

Page 11: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

11 / 18

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RZQ71F, 90C,100F

Attachment

Page 12: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

12 / 18

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RZQ71FRZQ100~160K

Attachment

Page 13: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

13 / 18

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RQ71FRQ100~160K

Attachment

Page 14: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

14 / 18

Measuring point1 - 24 - 23 - 56 - 5

RZQ200, 250C

1 2 3(Blue) (Brown) (Orange)

(Yellow) (Red) (White)4 5 6

Attachment

Page 15: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

15 / 18

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

RZQ100~140C7RZQS125 · 140C7RZQ71B9, RZQS71 · 100B7RZQ100~140B8

Attachment

Page 16: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

16 / 18

RZQ100~140C7V1BRZQS100~140C7V1B

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

1

2

3

4

5

6

Measuring point1 - 62 - 63 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

Criteria40~50Ω

RZQ71C7V1BRZQS71C7V1B

COM(+)

Attachment

Page 17: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

17 / 18Attachment

Measuring pins1(WHT) - 6(RED)3(ORG) - 6(RED)2(YLW) - 5(BRN)4(BLU) - 5(BRN)

- LU

R42LU

Page 18: Case Model - Daikin · Since the "Troubleshooting Flow Chart" in the SkyAir Servic e Manual had errors in the ... [Corresponding Service Manuals] Product No. Issue date Page

18 / 18Attachment

RZQ100 · 125 · 140KA

1

2

3

4

5

6

Measuring point1 - 53 - 52 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

(White)

Criteria40~50Ω

1

2

3

4

5

6

Measuring point1 - 62 - 63 - 64 - 6

(Orange)

(Red)

(Yellow)

(Black)

(Gray)

Criteria40~50Ω

RZQ71KA

COM(+)