Catalog for Wires & Cables
A M A RESOURCES, INC.Marketing Office
4000 Ponce De Leon Boulevard Suite 470 Coral Gables, FL 33146
T. (786)509-6433F. (305) 777-0449
Executive Office
AMA ASIA HOLDINGS, LIMITEDRoom 2802, 28/F., China Resources Building
No.26 Harbour RoadWanchai, Hong Kong
T. 852-2815-8380
Catalog
Company introduction ................................................................ l
Certificates .................................................................................. 2
Bare Copper Conductor .............................................................. 3
PVC insulated wire ..................................................................... 4
I PVC insulated wire .............................................................. 4
II PVC insulated flexible wire ................................................. 8
Plastic insulated control cabl'e .................................................. 11
r PVC insulated control cable ............................................... 11
Il XLPE insulated control cable ............................................ 26
Computer cable ......................................................................... 31
Plastics insulated power cable ................................................... 38
I PVC insulated power cable ................................................ 38
0 XLPE Insulated Power Cable ............................................ 53
Low Smoke Halogen Free(LSHF) Cable ............................................. 88
Packaging and shipping ............................................................. 105
A M A RESOURCES
1
AMA Resources, Inc.; (Allied Mines of Argentina) was established in 2003 as a Junior Mining Exploration Company, and has since then performed exploration on several deposits which have proven to contain important copper, silver, vanadium, gallium and Lanthanum mineral reserves.
The company owns several measured reserves of Surface Based Red Bed Oxide Malachite Copper that contain over 55 million tons of copper ore at 0.37% cupric or 300 million pounds of metal copper once processed. Additionally, the company has established relationships with several local mine owners with properties which have been previously explored and proven to contain mineral below the 50 million ton minimum requirement which the large mining companies look to acquire. Some of these deposits and proven mines have substantial mineral ranging between 10 million and 30 million tons with grades ranging from 1.20% cu., to 5%. The total tonnage of the combined deposits and mines is well above one billion tons. AMA contractually has right of first refusal to purchase the mineral and the license to process the mineral.
AMA Resources today counts with offices in Hong Kong, Buenos Aires and Neuquén, Republic of Argentina, Montevideo, Uruguay, Republic of Malta and Miami, USA.
The company has three divisions:ExplorationCopper Concentrate ProductionCopper Wire, Cable, Piping, Cathode Trading and Sales
The above was achieved over years of negotiations in order to establish solid strategic alliances with Chinese end users, technology transfer attainment, machinery supplied, end product quid pro quo arrangements in exchange for future copper concentrate production and agency agreements with Chinese, Chilean and Peruvian toll smelters and refiners.
Our company is able to supply over 1,200 copper wire and cable products on order and over 500 sizes and gages of piping.The company strongly believes that in order to
maintain future high level development and brand prestige, returning customer good
quality products with reasonable prices and service levels and that this attitude starts at
home; thus we must continue to develop our already successful social commitment
and management philosophy. We believe this pragmatically innovative spirit will result
in continuous cooperation and harmony, taking our win-win ideology into the next level.
COMPANY INTRODUCTION
A M A RESOURCES
2
CERTIFICATES
ISO 9001 : 2006 STANDARDISO14001 : 2004 STANDARDISO 18001 : 2007 STANDARD
A M A RESOURCES
3
1. Usage Soft drawn copper conductors are used for grounding electrical systems, where
high conductivity and flexibility is required.
2. Applicable standard IEC:60228, Class 2
3. Performance and parameters See table 1
Table 1
Nominal
section
mm²
Number/diameter
of core
mm
Maximum
outer
diameter
mm
Reference
weight
kg/km
Copper
Conductor
resistance at
20
/km
Copper
Standard
Package
M+/-5
1.5 7/0.52 1.6 13.5 12.1 10000
2.5 7/0.62 1.9 22.5 7.41 9000
4 7/0.85 2.4 36.0 4.61 5000
6 7/1.04 3.0 54.0 3.08 8000
10 7/1.35 4.0 90.0 1.83 9000
16 7/1.70 5.0 144.0 1.15 5000
25 7/2.04 6.3 225.0 0.727 3600
35 7/2.52 7.4 315.0 0.524 2500
50 19/1.78 8.8 450.0 0.387 2500
70 19/2.14 10.6 630.0 0.268 2400
95 19/2.52 12.4 855.0 0.193 2500
120 37/2.03 14.0 1080.0 0.153 2500
150 37/2.25 15.5 1350.0 0.124 2000
185 37/2.52 17.4 1665.0 0.099 1000
240 61/2.25 20.0 2160.0 0.075 1000
300 61/2.48 22.3 2700.0 0.061 1000
400 61/2.81 25.3 3600.0 0.047 500
500 61/3.18 28.6 4450.0 0.037 500
Product Figure
Conductor
BARE COPPER CONDUCTOR
A M A RESOURCES
4
1. Usage The cable is used for fixed wiring of power device with the rated AC voltage
450/750V.
2. Applicable standard IEC60227
3.Working temperature BV-90 model not more than 90 .others not more than 70
installation temperature not lower than 0 .
4. Model and Name See table 1
Table 1
Model Name
BV Copper core PVC insulation power line
BVV Copper core PVC insulation PVC sheathed round power wire
BV-90 Copper core heat-resistance 90 PVC insulation power wire
PVC INSULATED WIRE
I PVC INSULATED WIRE CLASS 1 & 2
A M A RESOURCES
5
5.Performance and parameters See table 2-3
Table2: BV-90 450/750
Nominal
section
mm²
Number/diameter
of core
mm
Maximum
outer
diameter
mm
Reference weight
kg/km
Conductor resistance at
20
/km
Copper Aluminum Aluminum Copper
1.5 A 1/1.38 3.3 20.3 12.1
1.5 B 7/0.52 3.5 21.6 12.1
2.5 A 1/1.78 3.9 31.6 17 11.8 7.41
2.5 B 7/0.62 4.2 34.8 7.41
4 A 1/2.55 4.4 47.1 22 7.39 4.61
4 B 7/0.85 4.8 50.3 4.61
6 A 1/2.76 4.8 50.3 29 4.91 3.08
6 B 7/1.04 5.4 71.2 3.08
10 7/1.35 7.0 119 62 3.08 1.83
16 7/1.70 8.0 179 78 1.91 1.15
25 7/2.04 10.0 281 118 1.20 0.727
35 7/2.52 11.5 381 156 0.868 0.524
50 19/1.78 13.0 521 215 0.641 0.387
70 19/2.14 15.0 734 282 0.443 0.268
95 19/2.52 17.5 962 385 0.320 0.193
120 37/2.03 19.0 1180 431 0.253 0.153
150 37/2.25 21.0 1470 539 0.206 0.124
185 37/2.52 23.5 1810 666 0.164 0.0991
240 61/2.25 26.5 2350 857 0.125 0.0754
Product Figure
Conductor
Insulation
A M A RESOURCES
6
Table3 BVV 300/500V
Nominal section
mm²
Number/diameter of
core
mm
Maximum outer
diameter
mm
Reference weight
kg/km
2×1.5 A 2×1/1.38 9.8 109 2×1.5(B) 2×7/0.52 10.5 123
2×2.5 A 2×1/1.78 11.5 157
2×2.5(B) 2×7/0.68 12.0 172
2×4 A 2×1/2.25 12.5 205
2×4(B) 2×7/0.85 13.0 222
2×6 A 2×1/2.76 13.5 265
2×6 B 2×7/1.04 14.5 286
2×10 2×7/1.35 18.0 471
3×1.5 A 3×1/1.38 10.5 136
3×1.5(B) 3×7/0.52 11.0 146
3×2.5 A 3×1/1.78 12.0 190
3×2.5(B) 3×7/0.68 12.5 207
3×4 A 3×1/2.25 13.0 252
3×4(B) 3×7/0.85 14.0 272
3×6 A 3×1/2.76 14.5 344
3×10 3×7/1.35 19.0 574
4×1.5 A 4×1/1.38 11.5 164
4×1.5(B) 4×7/0.52 12.0 174
4×2.5 A 4×1/1.78 13.5 252
4×2.5(B) 4×7/0.68 14.5 321
4×4 A 4×1/2.25 15.5 346
4×4(B) 4×7/0.85 17.5 370
4×6 A 4×1/2.76 16.0 439
4×6 B 4×7/1.04 17.5 470
5×1.5 A 5×1/1.38 12.0 192
5×1.5(B) 5×7/0.52 12.5 205
5×2.5 A 5×1/1.78 14.0 272
5×2.5(B) 5×7/0.68 14.5 292
5×4 A 5×1/2.25 16.0 379
5×4(B) 5×7/0.85 17.0 418
5×6 A 5×1/2.76 17.5 518
5×6 B 5×7/1.04 18.5 550
4*10 4×/71.35 23.2 891
4*16 4×7/1.70 26.0 1175
4*25 4×7/2.12 30.5 1998
4*35 4×7/2.52 34.8 2585
5*10 5×7/1.35 21.7 776
5*16 5×7/1.70 24.5 1093
5*25 5×7/2.12 28.6 1602
5*35 5×7/2.52 31.2 2073
A M A RESOURCES
7
Product Figure
Table 4 BVR 450/750V
Nominal
section
mm²
Number/diameter
of core
mm
Maximum
outer
diameter
mm
Reference
weight
kg/km
Conductor resistance at 20
/km
2.5 19/0.41 4.2 34.7 7.41
4 19/0.52 4.8 51.4 4.61
6 19/0.64 5.6 73.6 3.08
10 49/0.52 7.6 129 1.83
16 49/0.64 8.8 186 1.15
25 98/0.58 11.0 306 0.727
35 133/0.58 12.5 403 0.524
50 133/0.68 14.5 553 0.387
70 189/0.68 16.5 764 0.268
Product Figure
Softer copper conductor
Insulation
Conductor
Insulation
Filler
Sheath
A M A RESOURCES
8
1.Usage This product is fitted for domestic electrical appliances with ac rated voltage
450/750V and below, smaller size motorized tools, instruments of various meters and
motorized lighting installations.
2.Applicable standard IEC60227
3. Working temperature Not more than90 for RV-90 model, the others not more than 70 .
4.Model and name See table 1
Table1
Model Name
RV Copper core PVC insulation jointed flexible wire
RVV Copper core PVC insulation PVC sheathed round joint flexible wire
RV-90 Copper core heat-resistance 90 PVC insulation joint flexible wire
5.Performance and parameters(RV) See table 2-4
Table 2 RV 300/500V
Nominal section
mm²
Number/diameter of core
mm
Maximum outer diameter
mm
Reference weight
kg/km
0.3 16/0.15 2.3 6.4
0.4 23/0.15 2.5 8.1
0.5 16/0.2 2.6 9.1
0.75 24/0.2 2.8 12.2
1.0 32/0.2 3.0 15.1
II PVC INSULATED FLEXIBLE WIRE
A M A RESOURCES
9
Table 3 RV 450/750V
Nominal section
mm²
Number/diameter of core
mm
Maximum outer diameter
mm
Reference weight
kg/km
1.5 30/0.25 3.5 21.4
2.5 49/0.25 4.2 24.5
4 56/0.30 4.8 51.8
6 84/0.30 6.4 74.1
10 84/0.30 8.0 124
Table 4 RV-90 300/500V
Nominal section
mm²
Number/diameter of core
mm
Maximum outer diameter
mm
Reference weight
kg/km
0.5 16/0.2 2.4 10.2
0.75 24/0.2 3.0 13.5
1.0 32/0.2 3.2 16.4
1.5 30/0.25 3.5 21.4
2.5 49/0.25 4.2 34.5
Product Figure:
Softer copper conductor
Insulation
A M A RESOURCES
10
6. Performance and parameters(RVV) See table 5
Table 5 RVV 300/500V
Nominal section
mm²
Number/diameter of core
mm
Maximum outer diameter
mm
Reference weight
kg/km
2×0.75 2×24/0.20 7.6 50
2×1.0 2×32/0.20 7.8 58
2×1.5 2×30/0.25 8.8 75
2×2.5 2×49/0.25 11.0 120
3×0.75 2×24/0.20 8.0 63
3×1.0 2×32/0.20 8.4 74
3×1.5 2×30/0.25 9.6 102
3×2.5 2×49/0.25 11.5 162
4×0.75 2×24/0.20 8.6 79
4×1.0 2×32/0.20 9.2 97
4×1.5 2×30/0.25 11.0 133
4×2.5 2×49/0.25 12.5 204
5×0.75 2×24/0.20 9.4 97
5×1.0 2×32/0.20 11.0 115
5×1.5 2×30/0.25 12.0 158
5×2.5 2×49/0.25 14.0 249
Product Figure:
Insulation
Filler
Wrapping layer
Sheath
Softer copper conductor
A M A RESOURCES
11
1.Usage The product is suitable for control supervisory circuit and protection circuit with
AC rated voltage up to and including 450/750V. It can be installed in doors, trenches, ducts
and etc.
2.Applicable standard IEC60502 \ IEC60092-376
3.Using feature:
Rated voltage: U0/U 450/750V
Operating temp PVC low-smoke low-halogen PVC insulated not more than 70 .
Mini ambient temp: installation 0 .
Mini bending radius:
6 times of the cable diameter non-armored cable or shielded flexible cable .
10 times of the cable diameter armored cable or Cu-tape shielded cable .
PLASTICS INSULATED CONTROL CABLE
I PVC INSULATED CONTROL CABLE
A M A RESOURCES
12
4.Main technical index See table 1
Table 1
Item Technical Index
Conductor
DC
resistance
20
Section
mm²0.75 1.0 1.5 2.5 4 6 10.0
Conductor
AB
Type 24.5 24.8 18.1 18.2 12.1 12.2 7.41 7.56 4.61 4.7 3.08 3.11 1.83 1.84
R
Type 26 26.7 19.5 20.0 13.3 13.7 7.98 8.21 7.98 8.21 4.95 5.09 3.30 3.39
Test
voltage Test voltage3000V/5min
General
Flame-
retardant
As National standard IEC60332
5.Model and name See table 2
Table 2
Model Name Application places
KVV Cu-core PVC insulated sheathed control
cable Fixed laying indoors trench and conduits
KVVP Cu-core PVC insulated sheathed copper
wire braiding shielded control cable
Fixed laying indoors trench and conduits with
screening needs
KVVP2 Cu-core PVC insulated sheathed Cu-
tape shielded control cable
Fixed laying indoors trench and conduits with
screening needs
KVV22 Cu-core PVC insulated sheathed steel-
tape armored control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
A M A RESOURCES
13
Model Name Application places
KVV32 Cu-core PVC insulated sheathed fine
steel-wire armored control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
KVVR Cu-core PVC insulated sheathed control
flexible cable It is insulated in the buildings and can be moved
KVVRP Cu-core PVC insulated sheathed copper
wire braiding shielded control flexible cable
It is insulated in the buildings and required to be
moved freely
ZR-KVV Cu-core PVC insulated sheathed flame-
resistance control cable Fixed laying indoors trench and conduits
ZR-KVVP
Cu-core PVC insulated sheathed copper
wire braiding shielded flame-resistance
control cable
Fixed laying indoors trench and conduits with
screening needs
ZR-KVVP2
Cu-core PVC insulated sheathed Cu-
tape shielded flame-resistance control
cable
Fixed laying indoors trench and conduits with
screening needs
ZR-KVV22
Cu-core PVC insulated sheathed steel-
tape armored flame-resistance control
cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
ZR-KVV32
Cu-core PVC insulated sheathed fine
steel-wire armored flame-resistance control
cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
ZR-KVVR Cu-core PVC insulated sheathed flame-
resistance control flexible cable It is insulated in the buildings and can be moved
ZR-KVVRP
Cu-core PVC insulated sheathed copper
wire braiding shielded flame-resistance
control flexible cable
It is insulated in the buildings and required to be
moved freely
DZR-
KVDVD
Cu-core low-smoke low-halogen PVC
insulated sheathed low-smoke low-
halogen flame-resistance control cable
Fixed laying indoors trench and conduits
DZR-
KVDVDP
Cu-core low-smoke low-halogen PVC
insulated sheathed copper wire braiding
shielded low-smoke low-halogen flame-
resistance control cable
Fixed laying indoors trench and conduits with
screening needs
DZR-
KVDVDP2
Cu-core low-smoke low-halogen PVC
insulated sheathed Cu-tape shielded
low-smoke low-halogen flame-resistance
control cable
Fixed laying indoors trench and conduits with
screening needs
A M A RESOURCES
14
Model Name Application places
DZR-
KVDVD22
Cu-core low-smoke low-halogen PVC
insulated sheathed steel-tape armored
low-smoke low-halogen flame-resistance
control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
DZR-
KVDVD32
Cu-core low-smoke low-halogen PVC
insulated sheathed fine steel-wire
armored low-smoke low-halogen flame-
resistance control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
DZR-
KVDVDR
Cu-core low-smoke low-halogen PVC
insulated sheathed low-smoke low-
halogen flame-resistance control flexible
cable
It is insulated in the buildings and can be moved
DZR-
KVDVDRP
Cu-core low-smoke low-halogen PVC
insulated sheathed copper wire braiding
shielded low-smoke low-halogen flame-
resistance control flexible cable
It is insulated in the buildings and required to be
moved freely
ZH-
ZRKVVP
Cu-core PVC insulated sheathed copper
wire braiding shielded flame-resistance
fire-resistance control cable
Fixed laying indoors trench and conduits with
screening needs
ZH-
ZRKVVP2
Cu-core PVC insulated sheathed Cu-
tape shielded flame-resistance fire-
resistance control cable
Fixed laying indoors trench and conduits with
screening needs
ZH-
ZRKVV22
Cu-core PVC insulated sheathed steel-
tape armored flame-resistance fire-
resistance control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
ZH-
ZRKVV32
Cu-core PVC insulated sheathed fine
steel-wire armored flame-resistance fire-
resistance control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
ZH-
ZRKVVR
Cu-core PVC insulated sheathed flame-
resistance fire-resistance control flexible
cable
It is insulated in the buildings and can be moved
ZH-
ZRKVVRP
Cu-core PVC insulated sheathed copper
wire braiding shielded flame-resistance
fire-resistance control flexible cable
It is insulated in the buildings and required to be
moved freely
ZH-
DZRKVDV
D
Cu-core low-smoke low-halogen PVC
insulated sheathed low-smoke low-
halogen flame-resistance fire-resistance
control cable
Fixed laying indoors trench and conduits
15
Model Name Application places
ZH-
DZRKVDV
DP
Cu-core low-smoke low-halogen PVC
insulated sheathed copper wire braiding
shielded low-smoke low-halogen flame-
resistance fire-resistance control cable
Fixed laying indoors trench and conduits with
screening needs
ZH-
DZRKVDV
DP2
Cu-core low-smoke low-halogen PVC
insulated sheathed Cu-tape shielded
low-smoke low-halogen flame-resistance
fire-resistance control cable
Fixed laying indoors trench and conduits with
screening needs
ZH-DZRKV
DVD22
Cu-core low-smoke low-halogen PVC
insulated sheathed steel-tape armored
low-smoke low-halogen flame-resistance
fire-resistance control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
ZH-
DZRKVDV
D53
Cu-core low-smoke low-halogen PVC
insulated sheathed and corrugated steel
armoring made of single longitudinal tape
wrapping low-smoke low-halogen flame-
resistance fire-resistance control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
ZH-
DZRKVDV
D32
Cu-core low-smoke low-halogen PVC
insulated sheathed fine steel-wire
armored low-smoke low-halogen flame-
resistance fire-resistance control cable
Fixed laying indoors trench and conduits with
capability of bearing considerable mechanical
force
ZH-
DZRKVDV
DR
Cu-core low-smoke low-halogen PVC
insulated sheathed low-smoke low-
halogen flame-resistance fire-resistance
control flexible cable
It is insulated in the buildings and can be moved
A M A RESOURCES
A M A RESOURCES
16
Model Name Application places
ZH-
DZRKVDV
DRP
Cu-core low-smoke low-halogen PVC
insulated sheathed copper wire braiding
shielded low-smoke low-halogen flame-
resistance fire-resistance control flexible
cable
It is insulated in the buildings and required to be
moved freely
6. Model explanation Table 3
-
Specifications
Heat-proof degree
Shielding material
Armoring material
Multi strand material
Sheath material
Insulating material
Series code
Flame-retardant code
Fire-resistance code
Table 3
Item Code Explanation
Fire-resistance code NH Fire-resistance
Flame-retardant code /
ZR
Non-flame-retardant to be omitted
Flame-retardant
Series code K Control cable
Insulating material V
VD
PVC
Low-smoke Low-halogen PVC
Sheath material V
VD
PVC
Low-smoke Low-halogen PVC
A M A RESOURCES
17
Conductor type
A
B
R
Single strand conductor
Stranding conductor
Multi-strand stranding conductor
Shielding material
/
P
P2
Non-shielded to be omitted
Cu wire
Cu tape
Armoring material 22 Steel tape armored
32 Fine steel tape armored
7.Cable construction data See table 4-5
Table 4
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
2×0.75 A 1/0.97 8.0 63
2×0.75 B 7/0.37 8.4 9.8 72 91
2×1.0 A 1/1.13 8.4 71
2×1.0 B 7/0.43 8.8 10.5 79 102
2×1.5 A 1/1.38 9.4 89
2×1.5 B 7/0.52 10.0 11.5 96 125
2×2.5 A 1/1.78 10.5 120
2×2.5 B 7/0.68 11.5 12.5 133 171
2×4 A 1/2.25 11.5 160
2×4 B 7/0.85 12.5 14.5 173 218
2×6 A 1/2.76 12.5 206
2×6 B 7/1.04 14.0 16.0 228 280
2×10 B 7/1.35 17.5 19.0 360 436
3×0.75 A 1/0.97 8.4 77
3×0.75 B 7/0.37 8.8 10.5 89 98
A M A RESOURCES
18
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
3×1.0 A 1/1.13 8.8 90
3×1.0 B 7/0.43 9.2 10.5 99 126
3×1.5 A 1/1.38 9.8 111
3×1.5 B 7/0.52 10.5 12.0 126 163
3×2.5 A 1/1.78 11.0 165
3×2.5 B 7/0.68 12.0 13.5 182 216
3×4 A 1/2.25 12.5 212
3×4 B 7/0.85 13.5 15.5 239 294
3×6 A 1/2.76 14.5 308
3×6 B 7/1.04 15.0 17.0 326 380
3×10 B 7/1.35 18.5 20.0 485 564
4×0.75 A 1/0.97 9.0 91
4×0.75 B 7/0.37 9.8 11.0 103 128
4×1.0 A 1/1.13 9.8 105
4×1.0 B 7/0.43 10.0 11.5 119 146
4×1.5 A 1/1.38 10.5 139
4×1.5 B 7/0.52 11.5 12.5 158 187
4×2.5 A 1/1.78 12.0 198
4×2.5 B 7/0.68 13.0 15.0 222 286
4×4 A 1/2.25 14.0 290
4×4 B 7/0.85 15.0 16.5 321 370
4×6 A 1/2.76 15.0 380
4×6 B 7/1.04 16.5 18.0 406 458
4×10 B 7/1.35 20.0 22.0 615 690
5×0.75 A 1/0.97 9.6 110
5×0.75 B 7/0.37 10.5 11.5 124 146
5×1.0 A 1/1.13 10.0 128
5×1.0 B 7/0.43 11.0 12.0 149 169
A M A RESOURCES
19
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
5×1.5 A 1/1.38 11.5 170
5×1.5 B 7/0.52 12.5 13.5 196 228
5×2.5 A 1/1.78 14.0 262
5×2.5 B 7/0.68 14.5 16.5 280 331
5×4 A 1/2.25 15.0 350
5×4 B 7/0.85 16.5 18.0 362 423
5×6 A 1/2.76 16.5 472
5×6 B 7/1.04 18.0 19.5 496 552
5×10 B 7/1.35 22.5 24.0 786 882
7×0.75 A 1/0.97 10.5 132
7×0.75 B 7/0.37 11.0 12.5 149 178
7×1.0 A 1/1.13 11.0 156
7×1.0 B 7/0.43 11.5 13.0 174 206
7×1.5 A 1/1.38 12.5 211
7×1.5 B 7/0.52 13.5 15.0 232 281
7×2.5 A 1/1.78 15.0 337
7×2.5 B 7/0.68 16.0 17.5 363 419
7×4 A 1/2.25 16.5 456
7×4 B 7/0.85 17.5 19.0 478 542
7×6 A 1/2.76 18.0 618
7×6 B 7/1.04 19.5 21.0 636 709
7×10 B 7/1.35 24.0 26.0 1046 1144
8×0.75 A 1/0.97 11.5 154
8×0.75 B 7/0.37 12.0 13.5 176 208
8×1.0 A 1/1.13 12.0 186
8×1.0 B 7/0.43 13.0 15.0 199 242
8×1.5 A 1/1.38 14.5 264
8×1.5 B 7/0.52 15.5 17.0 275 329
20
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
8×2.5 A 1/1.78 16.5 281
8×2.5 B 7/0.68 17.5 19.0 316 386
8×4 A 1/2.25 18.0 524
8×4 B 7/0.85 19.5 21.5 559 623
8×6 A 1/2.76 20.0 716
8×6 B 7/1.04 22.0 24.0 743 826
8×10 B 7/1.35 27.5 29.0 1205 1307
10×0.75 A 1/0.97 12.5 181
10×0.75 B 7/0.37 13.5 16.0 196 272
10×1.0 A 1/1.13 14.0 242
10×1.0 B 7/0.43 15.0 16.0 261 309
10×1.5 A 1/1.38 16.0 329
10×1.5 B 7/0.52 17.0 18.5 348 402
10×2.5 A 1/1.78 18.5 468
10×2.5 B 7/0.68 19.5 21.5 496 578
10×4 A 1/2.25 20.5 656
10×4 B 7/0.85 22.5 24.0 683 783
10×6 A 1/2.76 22.5 888
10×6 B 7/1.04 25.0 27.5 908 1049
10×10 B 7/1.35 30.5 32.5 1506 1627
12×0.75 A 1/0.97 13.5 230
12×0.75 B 7/0.37 14.5 16.0 248 296
12×1.0 A 1/1.13 14.5 276
12×1.0 B 7/0.43 15.5 17.0 291 345
12×1.5 A 1/1.38 16.5 362
12×1.5 B 7/0.52 17.5 19.0 383 453
12×2.5 A 1/1.78 19.0 537
12×2.5 B 7/0.68 20.5 22.5 569 664
A M A RESOURCES
A M A RESOURCES
21
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
12×4 A 1/2.25 21.5 753
12×4 B 7/0.85 23.0 25.0 789 885
12×6 A 1/2.76 23.5 1017
12×6 B 7/1.04 26.0 27.0 1065 1196
14×0.75 A 1/0.97 14.5 259
14×0.75 B 7/0.37 15.0 17.0 272 333
14×1.0 A 1/1.13 15.0 298
14×1.0 B 7/0.43 16.0 17.5 328 390
14×1.5 A 1/1.38 17.0 413
14×1.5 B 7/0.52 18.5 20.0 439 508
14×2.5 A 1/1.78 19.5 606
14×2.5 B 7/0.68 21.5 23.5 647 743
14×4 A 1/2.25 22.5 859
14×4 B 7/0.85 24.5 26.0 905 999
14×6 A 1/2.76 24.5 1186
14×6 B 7/1.04 27.0 29.0 1217 1356
16×0.75 A 1/0.97 15.0 287
16×0.75 B 7/0.37 16.0 17.5 299 365
16×1.0 A 1/1.13 16.5 341
16×1.0 B 7/0.43 17.0 18.5 363 429
16×1.5 A 1/1.38 18.0 460
16×1.5 B 7/0.52 19.5 21.0 484 568
16×2.5 A 1/1.78 21.0 699
16×2.5 B 7/0.68 23.0 24.5 756 845
19×0.75 A 1/0.97 15.5 327
19×0.75 B 7/0.37 16.5 18.0 353 413
19×1.0 A 1/1.13 16.5 392
19×1.0 B 7/0.43 17.5 19.0 418 482
A M A RESOURCES
22
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
KVV
ZR-KVV
ZR-KVDVD
KVVP
ZR-KVVP
DZR-
KVDVDP
19×1.5 A 1/1.38 18.0 535
19×1.5 B 7/0.52 19.5 22.5 562 653
19×2.5 A 1/1.78 19.0 806
19×2.5 B 7/0.68 20.5 25.5 842 967
Note
1. The cable with 61#cores can be supplied, but not listed in the table
2. Maximum outer diameter of armored cable is 4mm larger than that of non-
armored one. Maximum outer diameter of Cu-tape shielded cable is 2mm
larger than that of non-Cu-tape shielded one.
Table 5
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVVR
ZR-KVVR
DZR-
KVDVDR
KVVRP
ZR-KVVRP
DZR-
KVDVDRP
KVVR
ZR-KVVR
DZR-
KVDVDR
KVVRP
ZR-
KVVRP
DZR-
KVDVDRP
4×0.5 R 16/0.20 9.0 10.5 84 109
4×0.75 R 24/0.20 9.4 11.0 108 137
4×1.0 R 32/0.20 10.0 11.5 123 159
4×1.5 R 30/0.25 11.5 12.5 164 198
4×2.5 R 50/0.25 13.0 15.0 231 289
5×0.5 R 16/0.20 9.6 11.0 110 138
5×0.75 R 24/0.20 10.5 11.5 120 153
5×1.0 R 32/0.20 11.0 12.0 154 187
5×1.5 R 30/0.25 12.0 13.5 208 249
5×2.5 R 50/0.25 14.5 16.0 293 348
A M A RESOURCES
23
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVVR
ZR-KVVR
DZR-
KVDVDR
KVVRP
ZR-KVVRP
DZR-
KVDVDRP
KVVR
ZR-KVVR
DZR-
KVDVDR
KVVRP
ZR-
KVVRP
DZR-
KVDVDRP
7×0.5 R 16/0.20 10.5 11.5 122 158
7×0.75 R 24/0.20 11.0 12.5 154 192
7×1.0 R 32/0.20 11.5 13.0 182 222
7×1.5 R 30/0.25 13.0 15.0 241 287
7×2.5 R 50/0.25 16.0 17.5 382 432
8×0.5 R 16/0.20 11.5 13.0 142 184
8×0.75 R 24/0.20 12.0 13.5 184 226
8×1.0 R 32/0.20 13.0 15.0 208 252
8×1.5 R 30/0.25 15.0 17.0 296 343
8×2.5 R 50/0.25 17.5 19.0 438 398
10×0.5 R 16/0.20 12.5 14.5 168 213
10×0.75 R 24/0.20 13.5 15.5 207 254
10×1.0 R 32/0.20 15.0 16.5 264 318
10×1.5 R 30/0.25 17.0 18.5 365 424
10×2.5 R 50/0.25 19.5 21.0 524 596
12×0.5 R 16/0.20 13.0 15.0 186 233
12×0.75 R 24/0.20 14.5 16.0 259 308
12×1.0 R 32/0.20 15.5 17.0 314 366
12×1.5 R 30/0.25 17.5 19.0 398 457
12×2.5 R 50/0.25 20.5 22.5 597 689
14×0.5 R 16/0.20 13.5 16.0 215 267
14×0.75 R 24/0.20 15.0 16.5 293 349
14×1.0 R 32/0.20 16.0 17.5 351 415
14×1.5 R 30/0.25 18.0 20.0 464 536
14×2.5 R 50/0.25 21.0 23.0 661 757
A M A RESOURCES
24
Core No. ×
nominal
section
mm
Conductor Max outer diameter
mm
Calculated weight
kg/km
Type
Numbers/
diameter
mm
KVVR
ZR-KVVR
DZR-
KVDVDR
KVVRP
ZR-KVVRP
DZR-
KVDVDRP
KVVR
ZR-KVVR
DZR-
KVDVDR
KVVRP
ZR-
KVVRP
DZR-
KVDVDRP
16×0.5 R 16/0.20 15.0 16.5 251 308
16×0.75 R 24/0.20 16.0 17.5 312 375
16×1.0 R 32/0.20 17.0 18.5 378 452
16×1.5 R 30/0.25 19.0 20.5 497 582
16×2.5 R 50/0.25 23.0 24.5 789 886
19×0.5 R 16/0.20 15.5 17.0 292 368
19×0.75 R 24/0.20 16.5 18.0 367 448
19×1.0 R 32/0.20 17.5 19.0 429 514
19×1.5 R 30/0.25 20.0 22.0 584 669
19×2.5 R 50/0.25 24.0 25.5 893 982
Note:
The cable with 61#cores can be supplied, but not listed in the table
Product Figures
Conductor
Insulation
Wrapping
Shield
Sheath
A M A RESOURCES
26
1.Usage The product is suitable for control supervisory circuit and protection circuit with
AC rated voltage up to and including 450/750V. It can be installed in doors, trenches, ducts
and etc.
2.Applicable standard IEC60502\ IEC60092-376
3.Using feature: Rated voltage: U0/U 450/750V.
4. Operating temp XLPE insulated not more than 90 , Radiation XLPE insulated not more
than 105 .
5. Mini bending radius:
1 6 times of the cable diameter non-armored cable or shielded flexible cable .
2 10 times of the cable diameter armored cable or Cu-tape shielded cable .
6.Main technical index See table 1
II XLPE INSULATED CONTROL CABLE
A M A RESOURCES
27
Table 1
Item Technical Index
Conductor
DC
resistance
20
Section
mm²0.75 1.0 1.5 2.5 4 6 10.0
Conductor
AB
Type 24.5 24.8 18.1 18.2 12.1 12.2 7.41 7.56 4.61 4.7 3.08 3.11 1.83 1.84
R
Type 26 26.7 19.5 20.0 13.3 13.7 7.98 8.21 7.98 8.21 4.95 5.09 3.30 3.39
Test
voltage Test voltage3000V/5min
Flame-
retardant
feature
Low-smoke low halogen
flame-retardant
Flame-retardant material oxygen index 30
Zero emission of halogen acid gas 100
Light penetration 30%
Smoke density Dm 200
7.Model explanation Table2
-
Specifications
Shielding material
Armoring material
Multi strand material
Sheath material
Insulating material
Series code
Flame-retardant code
Fire-resistance code
A M A RESOURCES
28
Table2
Item Code Explanation
Fire-resistance code NH Fire-resistance
Flame-retardant code
/
ZR
WZR
Non-flame-retardant to be omitted
Flame-retardant
low-smoke non-halogen flame-retardant
Series code K Control cable
Insulating material YJ XLPE
Sheath material
V
VD
E
PVC
Low-smoke Low-halogen PVC
Polyethylene
Conductor type
A
B
R
Single strand conductor
Stranding conductor
Multi-strand stranding conductor
Shielding material
/
P
P1
P2
Non-shielded to be omitted
Cu wire
Tinned Cu wire
Cu tape
Armoring material 22
32
Steel tape armored
Fine steel tape armored
8.Model and Name See table 3
Table 3
Model Name Application places
KYJV Cu-core XLPE insulated PVC sheathed control
cable
Fixed laying indoors trench and
conduits
KYJVP Cu-core XLPE insulated PVC sheathed copper
wire braiding shielded control cable
Fixed laying indoors trench and
conduits with screening needs
A M A RESOURCES
29
Model Name Application places
KYJVP2 Cu-core XLPE insulated PVC sheathed Cu-tape
shielded control cable
Fixed laying indoors trench and
conduits with screening needs
KYJV22 Cu-core XLPE insulated PVC sheathed steel-tape
armored control cable
Fixed laying indoors trench and
conduits with capability of bearing
considerable mechanical force
KYJV32 Cu-core XLPE insulated PVC sheathed fine steel-
wire armored control cable
Fixed laying indoors trench and
conduits with capability of bearing
considerable mechanical force
KYJVR Cu-core XLPE insulated PVC sheathed control
flexible cable
It is insulated in the buildings and can be
moved
KYJVRP Cu-core XLPE insulated PVC sheathed copper
wire braiding shielded control flexible cable
It is insulated in the buildings and
required to be moved freely
WZR-
KYJEP
Cu-core XLPE insulated polythene sheathed
copper wire braiding shielded low-smoke non-
halogen flame-resistance control cable
Fixed laying indoors trench and
conduits with screening needs
WZR-
KYJEP2
Cu-core XLPE insulated polythene sheathed Cu-
tape shielded low-smoke non-halogen flame-
resistance control cable
Fixed laying indoors trench and
conduits with screening needs
WZR-
KYJE22
Cu-core XLPE insulated polythene sheathed steel-
tape armored low-smoke non-halogen flame-
resistance control cable
Fixed laying indoors trench and
conduits with capability of bearing
considerable mechanical force
WZR-
KYJE32
Cu-core XLPE insulated polyethylene sheathed
fine steel-wire armored low-smoke non-halogen
flame-resistance control cable
Fixed laying indoors trench and
conduits with capability of bearing
considerable mechanical force
WZR-
KYJER
Cu-core XLPE insulated polyethylene sheathed
low-smoke non-halogen flame-resistance control
flexible cable
It is insulated in the buildings and can be
moved
WZR-KYJE
Cu-core radiation XLPE insulated polyethylene
sheathed low-smoke non-halogen flame-
resistance control cable
Fixed laying indoors trench and
conduits
WZR-
KYJEP
Cu-core radiation XLPE insulated polyethylene
sheathed copper wire braiding shielded low-smoke
non-halogen flame-resistance control cable
Fixed laying indoors trench and
conduits with screening needs
WZR-
KYJEP2
Cu-core radiation XLPE insulated polyethylene
sheathed Cu-tape shielded low-smoke non-
halogen flame-resistance control cable
Fixed laying indoors trench and
conduits with screening needs
A M A RESOURCES
30
Model Name Application places
WZR-
KYJE22
Cu-core radiation XLPE insulated polyethylene
sheathed steel-tape armored low-smoke non-
halogen flame-resistance control cable
Fixed laying indoors trench and
conduits with capability of bearing
considerable mechanical force
WZR-
KYJE32
Cu-core radiation XLPE insulated polyethylene
sheathed fine steel-wire armored low-smoke non-
halogen flame-resistance control cable
Fixed laying indoors trench and
conduits with capability of bearing
considerable mechanical force
WZR-
KYJER
Cu-core radiation XLPE insulated polyethylene
sheathed low-smoke non-halogen flame-
resistance control flexible cable
It is insulated in the buildings and can be
moved
WZR-
KYJERP
Cu-core radiation XLPE insulated polyethylene
sheathed copper wire braiding shielded low-smoke
non-halogen flame-resistance control flexible cable
It is insulated in the buildings and
required to be moved freely
NH-
WZRKYJEP
Cu-core XLPE insulated polyethylene sheathed
copper wire braiding shielded low-smoke non-
halogen flame-resistance control cable
Fixed laying indoors trench and
conduits with screening needs
Product Figure
9.Delivery length
Minimum delivery length is 500m for Non-armored cable 200m for armored cable short
length more than 30m can be delivered but not exceeding 10% of the total. Special
requirement needs to be discussed between the supplier and the buyer if required.
Conductor
Insulation
Wrapping laver
Inner sheath
Armour
Sheath
A M A RESOURCES
31
1.Usage It is used as signal transmission and connection of checking appliances of
distribution system computer system and automatic system of power-generating metallurgy
petroleum chemistry.
2.Applicable standard IEC60092-376
4. Operating temp Normal model 70 .
5. Mini ambient temp Fixed installation -40 Not-fixed installation 15 .
6. Mini bending radius: Non-armored cable 10 times diameter of the cable. Armored cable
12 times diameter of the cable.
7. Main Technical Index See table 1
Table1
Item Unit Technical index
PE insulation PVC insulation
20
insulation
Between any core
M .km
5000
Between any individual
screen 1
Operating
capacitance
Type3
pf/m
75
Type1 and 2 90
Capacitance Imbalance 1kHz pf/m 1
Inductance
resistance
0.75 mm²
1.0 mm²
1.5 mm²
20
25
35
20
25
35
Shield control coefficient 0.01 0.01
Test voltage V/1min 1000 1000
COMPUTER CABLE
FLAME RETARDANT COMPUTER CABLE
A M A RESOURCES
32
8. Model and Name See table2
Table2
Model Name
ZR-DJYPV Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded flame-
retardant computer cable
ZR-DJYPV22 Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded steel
tape armored flame-retardant computer cable
ZR-DJYPV32 Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded fine
steel wire armored flame-retardant computer cable
ZR-DJYPVP Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded and
general shielded flame-retardant computer cable
ZR-DJYP2V Cu core PE insulated PVC sheathed paired with Cu tape shielded flame-retardant
computer cable
ZR-DJYP2VP2 Cu core PE insulated PVC sheathed paired with Cu tape shielded and general shielded
flame-retardant computer cable
ZR-JHDJYP3V Cu core PE insulated PVC sheathed paired with Al foil/plastic film compound shielded
flame-retardant computer cable
ZR-DJYP3VP3 Cu core PE insulated PVC sheathed paired with Al foil/plastic film compound shielded
and general shielded flame-retardant computer cable
DZR-DJYPV Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded low-
smoke low-halogen flame-retardant computer cable
DZR-DJYPV22 Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded steel
tape armored low-smoke low-halogen flame-retardant computer cable
DZR-DJYPV32 Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded fine
steel wire armored low-smoke low-halogen flame-retardant computer cable
DZR-DJYPVP Cu core PE insulated PVC sheathed paired with tinned Cu wire braided shielded and
general shielded low-smoke low-halogen flame-retardant computer cable
DZR-DJYP2V Cu core PE insulated PVC sheathed paired with Cu tape shielded low-smoke low-
halogen flame-retardant computer cable
DZR-DJYP2VP2 Cu core PE insulated PVC sheathed paired with Cu tape shielded and general shielded
low-smoke low-halogen flame-retardant computer cable
DZR-DJYP3V Cu core PE insulated PVC sheathed paired with Al foil/plastic film compound shielded
low-smoke low-halogen flame-retardant computer cable
DZR-DJYP3VP3 Cu core PE insulated PVC sheathed paired with Al foil/plastic film compound shielded
and general shielded low-smoke low-halogen flame-retardant computer cable
A M A RESOURCES
33
9. Model explanation Table3
/
Conductor type
Specifications
Bundle flame-retardant
General shielding material
Armoring material
Sheath material
Paired shielding material
Insulating material
Series code
Flame-retardant
Table 3
Item Code Explanation
Flame-retardant code
ZR
ZR/
DZR
Flame-retardant
Bundle flame-retardant
Low-smoke low-halogen flame-retardant
Series code DJ For computer and electric appliance
Insulating material Y
V
PE
PVC
Shielding material
P
P2
P3
A
Tinned Cu wire braided
Copper tape
Al foil/polymer film compound
With polymer-coated Al tape bond inner shield
Sheathing material Y
V
PE
PVC
Armoring material
22
32
Steel tape armored
Steel wire armored
With corrugated steel armoring made of single longitudinal tape
wrapping
Specifications
Unit core noose conductor section
Pairs 1 2
Unit core noose 2 3
Conductor section 0.75 1.0 1.5 mm²
A M A RESOURCES
34
10. Cable construction data See table 4
Table 4
Pair×unit
core
×nominal
section
mm²
Max out diameter of cable
mm
ZR-DJYPV
ZR-DJYPV
DZR-
DJYPV
ZR-
DJYP2V
ZR-
JDJYP2V
DZR-
JHDJYP2V
ZR-
DJYP2VP2
ZR-
DJYP2VP2
DZR-
DJYP2VP2
ZR-DJYP3V
ZR-
JHDJYP3V
DZR-
JHDJYP3V
ZR-
DJYP3VP3
ZR-
DJYP3VP3
DZR-
DJYP3VP3
ZR-
DJYPV22 32
ZR-
DJYPV22 32
DZR-
DJYPV22 32
ZR-
DJYPVP
ZR-
DJYPVP
DZR-
DJYPVP
1×2×0.75 8.4 8.4 9.3 8.4 9.3 11.6 9.5
2×2×0.75 14.8 14.8 15.7 14.8 15.7 18.0 15.9
3×2×0.75 15.6 15.6 16.5 15.6 16.5 18.8 16.7
4×2×0.75 17.0 17.0 17.9 17.0 17.9 20.2 18.1
5×2×0.75 18.8 18.8 19.7 18.8 19.7 22.0 19.9
6×2×0.75 21.2 21.2 22.1 21.2 22.1 24.4 22.3
7×2×0.75 21.2 21.2 22.1 21.2 22.1 24.4 22.3
8×2×0.75 22.2 22.2 23.1 22.2 23.1 25.4 23.3
9×2×0.75 26.0 26.0 26.9 26.0 26.9 29.2 27.3
10×2×0.75 26.0 26.0 26.9 26.0 26.9 29.2 27.3
12×2×0.75 27.1 27.1 27.9 27.1 27.9 30.2 28.3
14×2×0.75 28.4 28.4 29.3 28.4 29.3 31.6 29.7
16×2×0.75 30.4 30.4 31.3 30.4 31.3 33.6 31.7
19×2×0.75 32.0 32.0 32.9 32.0 32.9 35.2 33.3
1×3×0.75 8.8 8.8 9.7 8.8 9.7 12.0 9.9
3×3×0.75 16.5 16.5 17.4 16.5 17.4 19.7 17.6
4×3×0.75 18.2 18.2 19.1 18.2 19.1 21.4 19.3
5×3×0.75 19.9 19.9 20.8 19.9 20.8 23.1 21.0
6×3×0.75 22.0 22.0 22.9 22.0 22.9 25.2 23.3
7×3×0.75 22.0 22.0 22.9 22.0 22.9 25.2 23.3
8×3×0.75 23.7 23.7 24.6 23.7 24.6 26.9 25.0
10×3×0.75 28.2 28.2 29.1 28.2 29.1 31.4 29.3
A M A RESOURCES
35
Pair×unit
core
×nominal
section
mm²
Max out diameter of cable
mm
ZR-DJYPV
ZR-DJYPV
DZR-
DJYPV
ZR-
DJYP2V
ZR-
JDJYP2V
DZR-
JHDJYP2V
ZR-
DJYP2VP2
ZR-
DJYP2VP2
DZR-
DJYP2VP2
ZR-DJYP3V
ZR-
JHDJYP3V
DZR-
JHDJYP3V
ZR-
DJYP3VP3
ZR-
DJYP3VP3
DZR-
DJYP3VP3
ZR-
DJYPV22 32
ZR-
DJYPV22 32
DZR-
DJYPV22 32
ZR-
DJYPVP
ZR-
DJYPVP
DZR-
DJYPVP
12×3×0.75 29.1 29.1 30.0 29.1 30.0 32.3 30.3
14×3×0.75 30.6 30.6 31.5 30.6 31.5 33.8 31.9
1×2×1.0 8.8 8.8 9.7 8.8 9.7 12.0 9.9
2×2×1.0 15.8 15.8 16.7 15.8 16.7 19.0 16.9
3×2×1.0 16.5 16.5 17.4 16.5 17.4 19.7 17.6
4×2×1.0 18.2 18.2 19.1 18.2 19.1 21.4 19.3
5×2×1.0 19.9 19.9 20.8 19.9 20.8 23.1 21.0
6×2×1.0 22.0 22.0 22.9 22.0 22.9 25.2 23.3
7×2×1.0 22.0 22.0 22.9 22.0 22.9 25.2 23.3
8×2×1.0 23.7 23.7 24.6 23.7 24.6 26.9 25.0
9×2×1.0 28.2 28.2 29.1 28.2 29.1 31.4 29.3
10×2×1.0 28.2 28.2 29.1 28.2 29.1 31.4 29.3
12×2×1.0 29.1 29.1 30.0 29.1 30.0 32.3 30.3
14×2×1.0 30.6 30.6 31.5 30.6 31.5 33.8 31.9
16×2×1.0 32.7 32.7 33.6 32.7 33.6 35.9 34.0
19×2×1.0 34.8 34.8 35.7 34.8 35.7 37.6 35.7
1×3×1.0 9.2 9.2 10.1 9.2 10.1 12.4 10.3
3×3×1.0 18.0 18.0 18.9 18.0 18.9 20.8 18.7
4×3×1.0 19.6 19.6 20.5 19.6 20.5 22.4 20.3
5×3×1.0 21.3 21.3 22.2 21.3 22.2 24.5 22.6
6×3×1.0 23.2 23.2 24.1 23.2 24.1 26.4 24.5
7×3×1.0 23.2 23.2 24.1 23.2 24.1 26.4 24.5
8×3×1.0 25.1 25.1 26.0 25.1 26.0 28.3 26.4
10×3×1.0 29.8 29.8 30.7 29.8 30.7 33.0 31.1
12×3×1.0 30.8 30.8 31.7 30.8 31.7 34.0 32.1
A M A RESOURCES
36
Pair×unit
core
×nominal
section
mm²
Max out diameter of cable
mm
ZR-DJYPV
ZR-DJYPV
DZR-
DJYPV
ZR-
DJYP2V
ZR-
JDJYP2V
DZR-
JHDJYP2V
ZR-
DJYP2VP2
ZR-
DJYP2VP2
DZR-
DJYP2VP2
ZR-DJYP3V
ZR-
JHDJYP3V
DZR-
JHDJYP3V
ZR-
DJYP3VP3
ZR-
DJYP3VP3
DZR-
DJYP3VP3
ZR-
DJYPV22 32
ZR-
DJYPV22 32
DZR-
DJYPV22 32
ZR-
DJYPVP
ZR-
DJYPVP
DZR-
DJYPVP
14×3×1.0 32.8 32.8 33.7 32.8 33.7 36.0 34.1
1×2×1.5 10.0 10.0 11.1 10.0 11.1 12.4 11.3
2×2×1.5 17.7 17.7 18.6 17.7 18.6 20.9 18.8
3×2×1.5 18.7 18.7 19.6 18.7 19.6 21.9 19.8
4×2×1.5 20.7 20.7 21.6 20.7 21.6 23.9 21.8
5×2×1.5 22.6 22.6 23.5 22.6 23.5 25.8 23.9
6×2×1.5 24.7 24.7 25.6 24.7 25.6 27.9 26.0
7×2×1.5 24.7 24.7 25.6 24.7 25.6 27.9 26.0
8×2×1.5 27.3 27.3 28.2 27.3 28.2 30.5 28.6
9×2×1.5 32.0 32.0 32.9 32.0 32.9 35.2 33.3
10×2×1.5 32.0 32.0 32.9 32.0 32.9 35.2 33.3
12×2×1.5 33.4 33.4 34.3 33.4 34.3 36.6 34.7
14×2×1.5 35.2 35.2 36.1 35.2 36.1 38.4 36.5
16×2×1.5 37.7 37.7 38.6 37.7 38.6 40.9 39.0
19×2×1.5 39.8 39.8 40.7 39.8 40.7 43.0 41.1
1×3×1.5 10.6 10.6 11.5 10.6 11.5 13.8 11.7
3×3×1.5 19.5 19.5 20.4 19.5 20.4 22.9 20.8
4×3×1.5 22.0 22.0 22.9 22.0 22.9 25.2 23.3
5×3×1.5 24.0 24.0 24.9 24.0 24.9 27.2 25.3
6×3×1.5 26.6 26.6 27.5 26.6 27.5 29.8 27.9
7×3×1.5 26.6 26.6 27.5 26.6 27.5 29.8 27.9
8×3×1.5 28.8 28.8 29.7 28.8 29.7 32.0 30.1
10×3×1.5 34.2 34.2 35.1 34.2 35.1 37.4 35.5
12×3×1.5 35.9 35.9 36.8 35.9 36.8 39.4 37.2
14×3×1.5 38.2 38.2 39.1 38.2 39.1 41.0 39.1
A M A RESOURCES
37
Product Figure
Note
The cable with 61#cores can be supplied but not listed in the table
means the type of flame retardant power cable.
added to the original type of cable means the type of fireproof cable. Intrinsically
after it.
11. Delivery length
Minimum delivery length is 1000m for Non-armored cable 10-pair and below 500m for
the one more than 10-pair. Minimum delivery length is 1000m for armored cable 8-pair and
below, 500m for the one more than 8-pair. Short length more than 50m can be delivered, but
not exceeding 6% of total. Special requirement needs be discussed between the supplier and
the buyer if required.
Conductor
Insulation
Wrapping layer
Shield
Filler
Wrapping layer
Sheath
Shield
A M A RESOURCES
38
1.Usage This cable is suitable to be installed in transmission distribution lines with rated
voltage up to and including 10kV.
2.Applicable standard IEC60502
3.Using feature Max continuous operating temperature of conductor is 70 .
Max short circuit conductor temperature max 5 sec is 160 .
The ambient temperature should not be below 0 .When the cable is
installed Min bending diameter is double to that of testing usage cylinder..
4.Main technical index See table 1
Table 1
Item Technical index
Test voltage 3500V/5min
Test voltage
Applicable
standard IEC60502
Flame-retardant
feature
General flame-retardant Applicable standard IEC60502
Low-smoke low halogen
flame-retardant
Flame-retardant material oxygen index 30
Zero emission of halogen acid gas 100
Light penetration 30%
Smoke density Dm 200
PLASTICS INSULATED POWER CABLE
I PVC INSULATED POWER CABLE
A M A RESOURCES
39
5.Model and name See table 2
Table2
Model Name
Cu Al
VV VLV PVC insulated PVC sheathed power cable
VY VLY PVC insulated PE sheathed power cable
VV22 VLV22 PVC insulated steel-tape armored PVC sheathed power cable
VV32 VLV32 PVC insulated fine steel-wire armored PVC sheathed power cable
VV42 VLV42 PVC insulated steel-wire armored PVC sheathed power cable
ZR-VV ZR-VLV PVC insulated PVC sheathed flame-resistance power cable
ZR-VV22 ZR-VLV22 PVC insulated steel-tape armored PVC sheathed flame-resistance
power cable
ZR-VV32 ZR-VLV32 PVC insulated fine steel-wire armored PVC sheathed flame-resistance
power cable
ZR-VV42 ZR-VLV42 PVC insulated steel-wire armored PVC sheathed flame-resistance
power cable
VVF VLVF PVC insulated NBR sheathed power cable
VVF-22 VLVF-22 PVC insulated steel-tape armored NBR sheathed power cable
VVF-32 VLVF-32 PVC insulated fine steel-wire armored NBR sheathed power cable
VVF-42 VLVF-42 PVC insulated steel-wire armored NBR sheathed power cable
ZR-VV ZR-VLV PVC insulated PVC sheathed flame-resistance power cable
A M A RESOURCES
40
Model Name
Cu Al
ZR-VV22 ZR-VLV22 PVC insulated steel-tape armored PVC sheathed flame-resistance
power cable
ZR-VV32 ZR-VLV32 PVC insulated fine steel-wire armored PVC sheathed flame-resistance
power cable
ZR-VV42 ZR-VLV42 PVC insulated steel-wire armored PVC sheathed flame-resistance
power cable
ZR-VVF ZR-VLVF PVC insulated NBR sheathed flame-resistance power cable
ZR-VVF-22 ZR-VLVF-22 PVC insulated steel-tape armored NBR sheathed flame-resistance
power cable
ZR-VVF-32 ZR-VLVF-32 PVC insulated fine steel-wire armored NBR sheathed flame-resistance
power cable
ZR-VVF-42 ZR-VLVF-42 PVC insulated steel-wire armored NBR sheathed flame-resistance
power cable
DZR-VV DZR-VLV PVC insulated PVC sheathed low-smoke low halogen flame-resistance
power cable
DZR-VV22 DZR-VLV22 PVC insulated steel-tape armored PVC sheathed low-smoke low
halogen flame-resistance power cable
DZR-VV32 DZR-VLV32 PVC insulated fine steel-wire armored PVC sheathed low-smoke low
halogen flame-resistance power cable
DZR-VV42 DZR-VLV42 PVC insulated steel-wire armored PVC sheathed low-smoke low
halogen flame-resistance power cable
DZR-VVF DZR-VLVF PVC insulated NBR sheathed low-smoke low halogen flame-resistance
power cable
DZR-VVF-22 DZR-VLVF-22 PVC insulated steel-tape armored NBR sheathed low-smoke low
halogen flame-resistance power cable
DZR-VVF-32 DZR-VLVF-32 PVC insulated fine steel-wire armored NBR sheathed low-smoke low
halogen flame-resistance power cable
DZR-VVF-42 DZR-VLVF-42 PVC insulated steel-wire armored NBR sheathed low-smoke low
halogen flame-resistance power cable
A M A RESOURCES
41
6. Specifications See table 3
Table 3
Model
No of cores
Rated voltage
(kV)
0.6/1 1.8/3
Copper core Aluminum core Nominal cross-section
mm²
VV VY VV22 VLV VLY VLV22 1 1.5-800 10-800
VV VY VV22 VLV VLY VLV22 2 1.5-185 10-185
VV VY VV22 VV32 VV42 VLV VLY VLV22 VLV32 VLV42 3 1.5-300 10-300
VV VY VV22 VLV VLY VLV22 3+1 4-300 10-300
VV VY VV22 VLV VLY VLV22 4 4-185 4-185
VV VY VV22 VV32 VV42 VLV VLY VLV22 VLV32 VLV42 4+1 3+2 5 2.5-240
Note
Single core cable armored material should be non-magnetic or reducing magnetic
loss structure.
Flame-resistance and NBR sheathed cable is similar to non-flame-resistance PVC
sheathed cable in specifications and construction data.
7. DC resistance conductor See table 4
Table 4
Nominal cross-
section
mm²
Max DC resistance at 20
/km
Nominal cross-
section
mm²
Max DC resistance at 20
/km
Copper core Aluminum core Copper core Aluminum core
1.5 12.1 - 95 0.193 0.320
2.5 7.41 12.1 120 0.153 0.253
4 4.61 7.41 150 0.124 0.206
6 3.08 4.61 185 0.0991 0.164
10 1.83 3.08 240 0.0754 0.125
16 1.15 1.91 300 0.0601 0.100
25 0.727 1.20 400 0.0470 0.0778
35 0.524 0.868 630 0.0283 0.0469
50 0.387 0.641 800 0.0221 0.0367
70 0.268 0.443
A M A RESOURCES
42
8.Cable construction data See table 5-6
Table 5 Rated voltage 0.6/1kV PVC insulated power cable
Core No.×
nominal
section
mm
Max outer diameter
mm
Calculated weight
kg/km
VV
VY
VLV
VLY
VV22
VLV22
VV32
VLV32 VV VY VLV VLY VV22 53 VLV22 53 VV32 VLV32
1×1.5 6.4 - - 55 45 46 36
1×2.5 6.8 - - 68 57 52 42
1×4 7.8 - - 93 79 68 55
1×6 8.4 - - 117 102 79 65
1×10 9.1 13.8 - 161 145 98 82 299 236
1×16 10.6 15.3 - 233 214 134 114 384 285
1×25 12.4 17.1 - 343 319 186 161 515 357
1×35 13.5 18.2 - 445 419 226 201 630 412
1×50 15.3 20.0 587 557 291 262 791 496
1×70 17.1 21.8 - 799 766 372 339 1027 600
1×95 19.4 24.1 - 1080 1042 488 449 1334 742
1×120 21.4 25.7 - 1337 1293 589 544 1603 854
1×150 23.2 27.7 - 1628 1578 708 659 1913 933
1×185 25.8 30.0 - 2029 1971 875 817 2336 1182
1×240 29.1 33.3 - 2634 2564 1118 1048 2970 1454
1×300 32.1 36.4 - 3286 3204 1378 1296 3651 1742
1×400 35.8 40.0 4148 4052 1716 1620 4547 2115
1×500 10.0 44.2 - 5330 5217 2166 2053 5774 2610
1×630 11.6 48.7 - 6874 6741 2717 2584 7360 3204
2×1.5 10.5 - - 126 106 107 87
2×2.5 11.3 - - 157 134 126 104
2×4 13.1 15.7 - 224 198 174 148 369 319
2×6 14.1 16.9 - 281 252 211 182 437 369
2×10 15.7 18.3 - 382 371 256 245 557 430
2×16 18.8 19.8 - 559 520 358 320 764 544
2×25 19.2 21.4 - 669 634 359 323 855 564
A M A RESOURCES
43
Core No.×
nominal
section
mm
Max outer diameter
mm
Calculated weight
kg/km
VV
VY
VLV
VLY
VV22
VLV22
VV32
VLV32 VV VY VLV VLY VV22 53 VLV22 53 VV32 VLV32
2×35 19.5 21.5 - 901 860 465 424 1086 650
2×50 22.2 24.4 - 1237 1188 614 567 1453 830
2×70 24.4 27.9 - 1646 1590 775 719 2148 1277
2×95 27.7 31.1 - 2192 2125 1010 943 2763 1581
2×120 30.1 33.5 - 2699 2622 1206 1129 3302 1809
2×150 33.3 36.9 - 3350 3261 1484 1394 4038 2172
2×185 35.7 39.9 4160 4104 1814 1757 5144 2737
3×1.5 11.0 - 149 127 121 100
3×2.5 11.8 - 189 166 142 120
3×4 13.8 16.4 17.6 268 240 194 167 421 347 570 465
3×6 15.1 17.6 19.7 341 310 236 205 507 404 700 654
3×10 16.6 19.1 23.0 492 456 303 267 666 484 1163 1017
3×16 19.9 22.5 25.0 731 687 431 388 948 649 1427 1263
3×25 21.2 22.8 26.4 1004 958 536 491 1200 733 1809 1362
3×35 23.2 25.2 28.2 1314 1264 659 609 1535 881 2174 1980
3×50 26.8 30.2 32.9 1821 1762 886 827 2376 1036 2979 2736
3×70 30.0 33.4 35.7 2443 2369 1134 1080 3045 1738 3739 3469
3×95 34.5 37.9 39.7 3267 3179 1491 1403 3968 2191 4760 4452
3×120 37.6 41.0 44.2 4021 3721 1781 1481 4776 2537 6074 5709
3×150 41.3 44.9 47.6 5006 4889 2198 2108 5857 3049 7118 6719
3×185 45.9 49.3 51.3 6136 5996 2584 2543 7075 3822 8485 8047
3×240 51.8 55.2 57.3 7868 7698 3389 3216 8911 4432 10623 10096
3×300 52.1 56.1 58.0 9792 9578 4032 3818 11233 5473 12902 12375
3×4+1×2.5 14.4 17.0 21.1 309 279 200 170 469 379 660 537
3×6+1×4 16.0 18.4 23.2 400 367 271 236 574 446 1062 922
3×10+1×6 17.6 20.2 25.8 564 527 341 303 755 531 1284 1128
3×16+1×10 21.0 23.6 29.6 835 789 472 427 1062 700 1596 1420
3×25+1×16 24.2 26.2 32.8 1228 1175 661 616 1459 892 2024 1837
3×35+1×16 26.5 28.5 35.1 1541 1483 787 729 1788 1034 3352 3091
A M A RESOURCES
44
Core No.×
nominal
section
mm
Max outer diameter
mm
Calculated weight
kg/km
VV
VY
VLV
VLY
VV22
VLV22
VV32
VLV32 VV VY VLV VLY VV22 53 VLV22 53 VV32 VLV32
3×50+1×25 30.2 33.6 40.1 2146 2075 1053 982 2755 1662 4218 3927
3×70+1×35 34.3 37.7 44.3 2864 2780 1335 1251 3653 2034 5793 5435
3×95+1×50 39.2 42.6 49.4 3804 3698 1730 1624 4611 2538 5895 6507
3×120+1×70 42.2 45.6 52.1 4809 4545 2140 2020 5647 2978 7924 7504
3×150+1×70 43.7 47.7 54.2 5820 5679 2594 2450 6786 3557 7952 9440
3×185+1×95 45.6 49.5 56.0 7238 7070 3190 3022 8296 4246 9572 9710
3×240+1×12
0
51.9 55.9 62.4 9295 9056 4028 3824 10445 5213 11960 11405
3×300+1×15
0
56.9 61.0 67.5 11395 11365 4689 4448 12878 6172 14373 13818
4×4 14.9 17.5 - 334 302 235 204 500 401
4×6 16.3 18.7 - 430 396 278 244 607 458
4×10 18.1 20.7 - 607 596 356 319 807 554
4×16 21.8 24.4 26.7 909 861 510 462 1150 751 1659 1480
4×25 25.1 27.1 28.3 1300 1245 678 623 1536 914 2164 1970
4×35 27.5 29.7 31.3 1709 1649 838 778 1988 1117 2850 2634
4×50 31.3 34.5 35.5 2372 2299 1127 1054 2031 1776 3608 3341
4×70 35.8 39.2 39.0 3208 3115 1466 1373 3932 2190 4609 4307
4×95 40.7 44.3 45.5 4280 4170 1916 1824 5120 2757 6403 5025
4×120 44.0 47.4 48.5 5294 5164 2308 2178 6260 3214 7550 7141
4×150 49.2 52.6 52.2 6581 6428 2848 2696 7581 3848 8889 8442
4×185 54.4 57.8 57.7 8073 7891 3469 3287 9168 4564 10797 10265
3×4+2×2.5 16.0 18.0 22.0 336 336 229 229 529 422 743 606
3×6+2×4 17.0 19.0 23.0 456 420 292 256 679 515 1256 1091
3×10+2×6 20.0 22.0 26.0 661 618 390 347 912 641 1548 1358
3×16+2×10 23.0 25.0 27.0 960 909 524 473 1250 814 1882 1667
3×25+2×16 26.0 28.0 30.0 1408 1349 419 660 1742 1053 2410 2193
3×35+2×16 28.0 30.0 32.0 1715 1651 845 781 2089 1198 3670 3571
3×50+2×25 33.0 35.0 37.0 2444 2362 1164 1082 3252 1972 4983 4636
3×70+2×35 34.0 37.0 38.0 3170 3082 1406 1319 3979 2215 6314 5927
3×95+2×50 38.0 41.0 42.0 4359 4249 1903 1793 5283 2827 7885 7473
A M A RESOURCES
45
Core No.×
nominal
section
mm
Max outer diameter
mm
Calculated weight
kg/km
VV
VY
VLV
VLY
VV22
VLV22
VV32
VLV32 VV VY VLV VLY VV22 53 VLV22 53 VV32 VLV32
3×120+2×70 41.0 45.0 46.0 5488 5360 2324 2196 6502 3338 9086 8641
3×150+2×70 44.0 48.0 49.0 6421 6276 2703 2558 7512 3794 10063 8814
3×185+2×95 50.0 53.0 54.0 7887 7713 3198 3024 9103 4414 10508 9974
4×4+1×2.5 16.0 18.0 22.0 360 330 246 213 561 444 613 499
4×6+1×4 18.0 20.0 24.0 479 442 303 266 698 522 1293 1123
4×10+1×6 21.0 23.0 27.0 715 670 417 372 974 676 1658 1455
4×16+1×10 24.0 26.0 28.0 1028 975 555 502 1324 851 1955 1768
4×25+1×16 27.0 29.0 31.0 1517 1456 787 726 1861 1113 2579 2346
4×35+1×16 29.0 31.0 33.0 1923 1853 932 862 2299 1308 4307 3974
4×50+1×25 34.0 37.0 38.0 2727 2639 1289 1201 3570 2132 5475 5093
4×70+1×35 35.0 38.0 39.0 3501 3404 1518 1421 4529 2546 7196 6755
4×95+1×50 40.0 43.0 44.0 4782 4661 2039 1918 5763 3020 8603 8153
4×120+1×70 44.0 47.0 48.0 5970 5828 2487 2346 7041 3558 9838 9357
4×150+1×70 48.0 51.0 52.0 7207 7043 2983 2819 8377 4153 11223 9830
4×185+1×95 53.0 56.0 57.0 8916 8722 3676 3479 10207 4964 11788 11188
5×4 16.0 18.0 22.0 387 353 262 228 592 467 870 708
5×6 18.0 20.0 24.0 505 467 317 279 728 540 1350 1173
5×10 21.0 23.0 27.0 772 725 446 399 1053 727 1796 1576
5×16 24.0 26.0 28.0 1095 1041 584 530 1400 889 2114 1876
5×25 28.0 30.0 32.0 1788 1725 980 917 1983 1175 2750 2502
5×35 31.0 34.0 36.0 2141 2066 1030 955 2901 1790 5453 5031
5×50 32.0 35.0 37.0 2901 2817 1304 1219 3695 2098 5677 5282
5×70 37.0 40.0 41.0 3888 3783 1684 1579 4790 2588 7610 7143
5×95 42.0 45.0 46.0 5281 5150 2251 2120 6310 3280 9425 8932
5×120 45.0 49.0 50.0 6513 6361 2709 2557 7630 3826 10665 10143
5×150 50.0 54.0 55.0 8039 7859 3310 3130 9316 4587 12486 10937
5×185 56.0 59.0 60.0 9875 9663 4080 3868 11239 5444 12983 12323
A M A RESOURCES
46
Table 6 Rated voltage 1.8/3kV PVC insulated power cable
Core No.×
nominal section
mm
Max outer
diameter
mm
Calculated weight
kg/km
VV
VY
VLV
VLY
VV22
VLV22 VV VY VLV VLY VV22 53 VLV22 53
1×10 12.6 16.2 290 268 229 207 516 455
1×16 13.5 17.1 364 340 268 244 606 509
1×25 15.5 20.1 505 477 345 317 822 661
1×35 16.6 21.2 622 592 400 370 960 738
1×50 18.0 22.6 769 736 466 435 1132 831
1×70 20.8 24.4 1049 999 614 564 1404 969
1×95 22.7 26.3 1342 1287 739 684 1729 1125
1×120 24.3 27.9 1614 1555 852 793 2028 1266
1×150 25.8 29.4 1906 1843 969 907 2346 1409
1×185 27.7 31.3 2300 2232 1125 1057 2771 1596
1×240 30.3 34.7 2901 2826 1357 1282 3661 2117
1×300 33.2 38.6 3562 3479 1625 1543 4472 2536
1×400 36.5 41.9 4455 4364 1977 1886 5456 2979
1×500 41.1 45.5 5596 5469 2473 2346 6606 3483
1×630 45.3 50.9 7127 6986 332 2891 8373 4277
2×10 21.5 25.6 604 552 493 431 1004 883
2×16 23.4 27.4 758 701 564 508 1192 998
A M A RESOURCES
47
Core No.×
nominal section
mm
Max outer
diameter
mm
Calculated weight
kg/km
VV
VY
VLV
VLY
VV22
VLV22 VV VY VLV VLY VV22 53 VLV22 53
2×25 23.9 28.0 961 906 649 594 1387 1075
2×35 24.3 29.2 1182 1123 750 691 1834 1402
2×50 25.9 31.8 1455 1392 870 807 2215 1630
2×70 28.3 34.2 1906 1837 1059 990 2734 1887
2×95 31.8 36.6 2529 2433 1357 1260 3359 2186
2×120 33.8 39.6 3047 2944 1564 1461 4012 2529
2×150 35.8 41.6 3601 3491 1799 1669 4621 2799
2×185 37.3 43.1 4224 4114 1988 1858 5244 2988
3×10 22.7 26.8 769 714 587 533 1191 1009
3×16 24.7 28.8 986 926 696 636 1444 1154
3×25 25.3 30.1 1324 1263 855 794 2001 1532
3×35 27.1 33.0 1647 1581 999 933 2441 1792
3×50 29.2 35.0 2048 1976 1171 1099 2899 2021
3×70 32.9 37.8 2783 2682 1512 1412 3643 2372
3×95 36.0 40.9 3614 3504 1856 1745 4555 2796
3×120 38.6 44.4 4378 4259 2153 2034 5477 3252
3×150 42.1 46.9 5288 5133 2556 2401 6368 3636
3×185 44.9 50.0 6411 6245 2979 2813 7565 4133
A M A RESOURCES
48
Core No.×
nominal section
mm
Max outer
diameter
mm
Calculated weight
kg/km
VV
VY
VLV
VLY
VV22
VLV22 VV VY VLV VLY VV22 53 VLV22 53
3×240 49.1 53.9 8115 7933 3611 3428 9374 4872
3×300 53.7 59.5 9971 9770 4343 4142 11477 5849
4×4 21.7 25.7 626 574 528 476 1029 931
4×6 22.9 26.9 733 678 587 532 1158 1012
4×10 24.8 28.8 935 875 692 632 1394 1152
4×16 26.0 31.9 1217 1151 830 764 1939 1551
4×25 26.8 32.7 1656 1591 1031 965 2441 1816
4×35 29.2 34.9 2082 2011 1218 1146 2929 2065
4×50 32.4 37.3 2679 2580 1509 1410 3526 2356
4×70 36.0 40.8 3569 3459 1875 1765 4507 2813
4×95 39.7 45.5 4668 4545 2323 2200 5797 3452
4×120 43.7 48.5 5771 5610 2805 2643 6894 3928
4×150 46.6 51.5 6865 6692 3222 3050 9063 4421
4×185 50.3 55.2 8358 8171 3782 3595 9652 5075
Installation condition Running in air the ambient temperature is 30 .Max permissible
continuous operating temperature of conductor is 70 . Buried directly in the ground
Temperature of ground is15 Thermal resistivity of ground is 1.2 .m/w Buried depth is
0.5m Max allowed continuous operating temperature of conductor is 70 ..
A M A RESOURCES
49
9. Current Rating See table 7-9
Table 7 The permissible continuous operating current rating of 0.6/1kV PVC insulated without
armoring power cables
Nominal
cross
section
area
(mm²)
In air
A
In the ground
A
Single-core BI-core Trio-core 3+1 -
core Single-core BI-core Trio-core
3+1 -
core
Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
1.5 24 - 20 - 17 - - - 34 - 27 - 22
2.5 32 25 28 21 23 18 46 35 35 28 30 23
4 45 34 36 29 31 24 28 22 61 47 47 36 39 31 37 28
6 56 43 47 36 39 31 38 28 75 58 58 45 49 38 46 36
10 80 61 66 51 56 43 51 50 105 81 80 62 68 52 61 47
16 106 83 89 69 76 59 68 53 138 106 105 82 89 69 80 61
25 143 111 117 91 102 78 92 71 180 138 133 104 107 83 106 82
35 175 133 143 111 122 94 115 89 218 169 164 127 131 101 130 101
50 223 170 180 138 154 122 144 111 265 196 201 159 159 123 161 124
70 265 207 217 170 191 148 178 136 310 239 244 186 195 150 194 148
95 329 254 233 180 218 168 369 283 231 178 231 177
120 382 297 270 207 253 195 416 323 262 201 263 204
150 445 339 313 244 297 228 474 364 300 231 303 233
185 519 392 360 281 344 163 530 408 337 262 340 263
240 609 472 429 334 617 474 390 301
300 705 546 477 376 700 530 451 355
400 832 641 820 629
500 965 753 929 710
630 1134 880 1060 813
A M A RESOURCES
50
Table 8 The permissible continuous operating current rating of 0.6/1kV PVC insulated with
armoring power cables
Nominal
cross
section
area
(mm²)
In air
A
In the ground
A
Single-core BI-core Trio-core 3+1 -
core Single-core BI-core Trio-core
3+1 -
core
Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
4 - 37 37 29 32 24 29 23 - - 45 35 38 29 36 27
6 48 48 37 40 32 39 29 56 43 47 37 46 36
10 82 67 67 52 57 45 52 40 101 78 77 59 65 50 61 47
16 111 91 91 70 77 60 70 54 132 104 102 79 87 66 81 62
25 143 122 122 92 102 80 94 73 175 132 125 97 109 84 106 82
35 175 143 143 111 122 95 119 92 212 164 148 115 130 100 134 103
50 223 180 180 138 154 122 149 115 260 201 181 140 160 123 163 125
70 276 217 217 170 191 148 184 141 307 238 220 170 195 150 196 151
95 334 233 180 226 174 371 286 229 150 234 181
120 387 270 207 260 201 424 339 262 176 267 206
150 445 313 244 301 231 483 375 299 201 301 231
185 509 360 281 345 266 541 419 334 229 338 261
240 615 424 334 636 493 386 298
300 700 477 371 721 557 445 350
400 832 838 547
500 970 955 743
630 1124 1093 987
A M A RESOURCES
51
Table 9 The permissible continuous operating current rating of 1.8/3kV PVC insulated with
armoring power cables
Nominal cross section area
(mm²)
In air
A
In the ground
A
Single-core Trio-core Single-core Trio-core
Cu Al Cu Al Cu Al Cu Al
16 - 90 68 - 97 74
25 118 89 125 95
35 143 108 151 114
50 195 143 173 130 193 147 178 136
70 244 180 217 164 236 180 219 168
95 302 221 266 201 282 215 264 201
120 348 255 308 233 319 244 299 230
150 395 290 351 265 357 273 336 257
185 453 337 403 305 401 309 379 292
240 532 399 474 361 269 357 436 338
300 607 458 540 413 513 402 488 381
10.The correct coefficients of current rating at different ambient temperatures
See table 10
Table 10
Ambient temperature In air In the ground
15 1.21 1.0
20 1.14 0.95
25 1.08 0.90
30 1.00 0.85
35 0.94 0.78
40 0.86 0.71
45 0.77 -
A M A RESOURCES
52
11. The correct coefficients of ground thermal resistivity See table 11
Table11
Thermal resistivity .m/w 0.6 0.8 1.0 1.2 1.4 1.6 2.0
Coefficient 1.17 1.08 1.00 0.94 0.89 0.84 0.77
12.Delivery length
The delivery length of cables should not be less than 100m. It is permitted to supply short
cable not shorter than 30m but overall length should not be more than 10% of the total length.
Special requirement needs be discussed between the supplier and the buyer if required.
A M A RESOURCES
53
1.Applicable standard IEC60502
2.Using feature The ambient temperature should not be below 0 when the cable
installed.There is no limit in drop.
3.The min bending radius 20 D+d ±5% to single core 15 D+d ±5% to three cores cable
D is the overall diameter of cable d is the of diameter conductor .
4.Max operating temperature of cables: PVC sheathed power cable 90 PE sheathed
power cable 80 .
5.Max continuous conductor operating temperature XLPE insulated not more than 90
radiation XLPE insulated not more than 105 Max short circuit conductor temperature is
250 max 5sec
6.The operating conditions:
One or two single-core cable is not permitted to install in steel tube.
II XLPE INSULATED POWER CABLE
A M A RESOURCES
54
Table 1
Item Technical index
Test voltage As National standardIEC60502
Insulation
resistance As National standard 6
Flame-retardant
feature
Low-smoke low halogen flame-
retardant
Flame-retardant material oxygen
index30
Zero emission of halogen acid gas
100
Light penetration 30%
Smoke density Dm 200
Fire-resistance characteristics As National standard IEC60331
7.Model and name See table 2
Table 2
Model Name Application places
Cu Al
YJV YJLV XLPE insulated PVC sheathed
power cable Suitable for indoor channels
conduits and cable grooves It
cannot bear mechanical stress, but
can endure common pulling force.
Suitable for installing under ground YJY YJLY XLPE insulated PE sheathed
power cable
YJV22 YJLV22
XLPE insulated steel-tape
armored PVC sheathed power
cable It can bear mechanical stress, but
cannot endure large pulling force
YJV23 YJLV23
XLPE insulated steel-tape
armored PE sheathed power
cable
A M A RESOURCES
55
Model Name Application places
Cu Al
YJV32 YJLV32
XLPE insulated fine steel-wire
armored PVC sheathed power
cable It can be laid in water and high
dropped earth it cannot endure large
pulling force
YJV33 YJLV33
XLPE insulated fine steel-wire
armored PE sheathed power
cable
YJV42 YJLV42
XLPE insulated steel-wire
armored PVC sheathed power
cable It can be laid in water and high
dropped earth it cannot endure much
large pulling force
YJV43 YJLV43
Radiation XLPE insulated steel-
wire armored PE sheathed
power cable
ZA-YJV ZR-YJLV XLPE insulated PVC sheathed
flame-resistance power cable
Suitable for indoor, channels conduits,
and cable grooves, It cannot bear
mechanical stress. But can endure
common pulling force. Suitable for
installed under ground
ZR-YJV22 ZR-YJLV22
XLPE insulated steel-tape
armored PVC sheathed flame-
resistance power cable
It can bear mechanical stress, but
cannot endure large pulling force
ZR-YJV32 ZR-YJLV32
XLPE insulated fine steel-wire
armored PVC sheathed flame-
resistance power cable
It can be laid in water and high
dropped earth it cannot endure large
pulling force
ZR-YJV42 ZR-YJLV42
XLPE insulated steel-wire
armored PVC sheathed flame-
resistance power cable
It can be laid in water and high
dropped earth it cannot endure much
large pulling force
WDZ-YJV WDZ-YJLV
XLPE insulated PVC sheathed
low-smoke low-halogen flame-
resistance power cable
Suitable for indoor channels
conduits and cable grooves It
cannot bear mechanical stress, but
can endure common pulling force.
Suitable for installing under ground
A M A RESOURCES
56
Model Name Application places
Cu Al
WDZ-YJV22 WDZ-
YJLV22
XLPE insulated steel-tape
armored PVC sheathed power
cable
It can bear mechanical stress, but
cannot endure large pulling force
WDZ-YJV32 WDZ-
YJLV32
XLPE insulated fine steel-wire
armored PVC sheathed power
cable
It can be laid in water and high
dropped earth it cannot endure large
pulling force
WDZ-YJV42 WDZ-
YJLV42
XLPE insulated steel-wire
armored PVC sheathed power
cable
It can be laid in water and high
dropped earth it cannot endure much
large pulling force
N-YJV N-YJLVXLPE insulated PVC sheathed
fire-resistance power cable
Suitable for indoor channels
conduits and cable grooves It
cannot bear mechanical stress, but
can endure common pulling force.
Suitable for installing under ground
N-YJV22 N-YJLV22
XLPE insulated steel-tape
armored PVC sheathed fire-
resistance power cable
It can bear mechanical stress, but
cannot endure large pulling force
N-YJV32 N-YJLV32
XLPE insulated fine steel-wire
armored PVC sheathed fire-
resistance power cable
It can be laid in water and high
dropped earth it cannot endure large
pulling force
N-YJV42 N-YJLV42
XLPE insulated steel-wire
armored PVC sheathed fire-
resistance power cable
It can be laid in water and high
dropped earth it cannot endure much
large pulling force
N-ZRYJV N-ZRYJLV
XLPE insulated PVC sheathed
flame-resistance fire-resistance
power cable
Suitable for indoor channels
conduits and cable grooves It
cannot bear mechanical stress, but
can endure common pulling force.
Suitable for installing under ground
N-ZJV22 NH-YJLV22
XLPE insulated steel-tape
armored PVC sheathed flame-
resistance fire-resistance power
cable
It can bear mechanical stress, but
cannot endure large pulling force
N-YJV32 N-YJLV32
XLPE insulated fine steel-wire
armored PVC sheathed flame-
resistance fire-resistance power
cable
It can be laid in water and high
dropped earth it cannot endure large
pulling force
A M A RESOURCES
57
Model Name Application places
Cu Al
N-YJV42 N-YJLV42
XLPE insulated steel-wire
armored PVC sheathed flame-
resistance fire-resistance power
cable
It can be laid in water and high
dropped earth it cannot endure much
large pulling force
Table 3
Model NO. of
cores
Rated voltage
(kV)
0.6/1 1.8/3 3.6/6-6/6 6/10-
8.7/10
8.7/15-
12/20
18/20-
26/35
Cu Al Nominal cross-section
(mm²)
YJV YJLV
1
1.5-800 10-800 25-1200 25-1200 35-1200 50-1200
YJY YJLY 2.5-1000 10-1000 25-1200 25-1200 35-1200 50-1200
YJV32 YJLV32 10-1000 10-1000 25-1200 25-1200 35-1200 50-1200
YJV33 YJLV33 10-1000 10-1000 25-1200 25-1200 35-1200 50-1200
YJV42 YJLV42 10-1000 10-1000 25-1200 25-1200 35-1200 50-1200
YJV43 YJLV43 10-1000 10-1000 25-1200 25-1200 35-1200 50-1200
YJV YJLV
3
1.5-300 10-800 25-1200 25-300 35-300
YJY YJLY 4-300 10-1000 25-300 25-300 35-300
YJV22 YJLV22 4-300 10-1000 25-300 25-300 35-300
YJV23 YJLV23 4-300 10-1000 25-300 25-300 35-300
YJV32 YJLV32 4-300 10-1000 25-300 25-300 35-300
YJV33 YJLV33 4-300 10-1000 25-300 25-300 35-300
YJV42 YJLV42 4-300 10-1000 25-300 25-300 35-300
YJV43 YJLV43 4-300 10-1000 25-300 25-300 35-300
YJV YJLV
3+1
4
5
1.5-300
YJV22 YJLV22 4-300
YJV32 YJLV32 4-300
YJV42 YJLV42 4-300
Note Single core cable armored material should be non-magnetic or reducing magnetic loss
structure
Rated voltage of Radiation XLPE insulated power cable is up to and inducing 8.7/10kV.
A M A RESOURCES
58
8. Cable construction data See table 4
Table 4 0.6/1 kV Single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
diameter
of cable
Approx.
weight
Max DC
resistance
at20Test
voltage
Resistance
of insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
1×1.5 0.7 1.5 5.8 53 12.
1 3.5 1.10 25 35
1×2.5 0.7 1.5 6.2 68 53 7.4
1
12.
1 3.5 0.916 30 25 45 35
1×4 0.7 1.5 6.7 87 64 4.6
1
7.4
1 3.5 0.757 45 35 60 50
1×6 0.7 1.5 7.2 110 73 3.0
8
4.6
1 3.5 0.645 55 45 70 60
1×10 0.7 1.5 8.0 115 95 1.8
3
3.0
8 3.5 0.523 75 60 95 75
1×16 0.7 1.5 8.9 220 120 1.1
5
1.9
1 3.5 0.431 100 80 125 100
1×25 0.9 1.5 10.4 345 190 0.7
27
1.2
0 3.5 0.414 140 115 160 130
1×35 0.9 1.5 11.5 424 207 0.5
24
0.8
68 3.5 0.379 175 140 190 150
1×50 1.0 1.5 13.0 555 245 0.3
87
0.6
41 3.5 0.355 210 170 225 180
1×70 1.1 1.5 14.0 770 336 0.2
68
0.4
43 3.5 0.335 270 215 280 225
1×95 1.1 1.5 16.4 104
0 455
0.1
93
0.3
20 3.5 0.290 340 275 335 270
A M A RESOURCES
59
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
diameter
of cable
Approx.
weight
Max DC
resistance
at20Test
voltage
Resistance
of insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
1×120 1.2 1.5 17.8 129
0 550
0.1
53
0.2
53 3.5 0.282 400 320 380 305
1×150 1.4 2.0 20.6 159
0 650
0.1
24
0.2
06 3.5 0.294 460 370 425 340
1×185 1.6 2.0 22.5 194
4 804
0.0
091
0.1
64 3.5 0.303 530 415 480 375
1×240 1.7 2.0 24.9 251
0
102
1
0.0
754
0.1
25 3.5 0.283 625 490 555 435
1×300 1.8 2.5 27.3 307
6
123
8
0.0
601
0.1
00 3.5 0.263 720 565 630 495
1×400 2.0 2.5 34.1 364
2
145
5
0.0
470
0.0
08 3.5 0.243 815 840 705 555
Product pictures
Conductor
Insulation
Sheath
A M A RESOURCES
60
Table 5 0.6/1 kV 3 core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.-
diameter
of cable
Approx.-
weight
Max. DC
resistance
at20
Test
voltage
Resistance
of insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm Kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×1.5 0.7 1.5 9.8 145 12.
1 3.5 1.10 25 30
3×2.5 0.7 1.5 10.7 185 140 7.4
1
12.
1 3.5 0.916 30 25 35 30
3×4 0.7 1.5 11.8 250 175 4.6
1
7.4
1 3.5 0.757 40 30 50 40
3×6 0.7 1.5 12.9 320 210 3.0
8
4.6
1 3.5 0.645 50 40 60 45
3×10 0.7 1.5 14.6 450 260 1.8
3
3.0
8 3.5 0.523 65 50 80 60
3×16 0.7 1.5 16.5 640 340 1.1
5
1.9
1 3.5 0.431 85 65 100 80
3×25 0.9 2.0 20.8 940 470 0.7
27
1.2
0 3.5 0.414 115 90 130 100
3×35 0.9 2.0 23.2 126
0 600
0.5
24
0.8
68 3.5 0.379 145 110 155 120
3×50 1.0 2.0 25.4 167
0 730
0.3
87
0.6
41 3.5 0.355 175 130 185 140
3×70 1.1 2.0 29.9 228
0 970
0.2
68
0.4
43 3.5 0.335 220 170 225 175
A M A RESOURCES
61
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.-
diameter
of cable
Approx.-
weight
Max. DC
resistance
at20
Test
voltage
Resistance
of insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm Kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×95 1.1 2.0 33.3 302
0
124
0
0.1
93
0.3
20 3.5 0.290 270 205 270 210
3×120 1.2 2.5 37.8 379
5
154
0
0.1
53
0.2
53 3.5 0.282 315 240 305 235
3×150 1.4 2.5 41.7 475
0
194
0
0.1
24
0.2
06 3.5 0.294 360 275 345 265
3×185 1.6 2.5 44.6 565
4
224
8
0.0
091
0.1
64 3.5 0.303 420 320 390 301
3×240 1.7 2.5 50.1 724
3
272
3
0.0
754
0.1
25 3.5 0.283 500 385 455 355
3×300 1.8 3.0 55.6 883
2
321
8
0.0
601
0.1
00 3.5 0.263 580 460 520 409
3×400 2.0 3.0 61.6 104
21
369
3
0.0
470
0.0
08 3.5 0.243 640 515 585 463
Product Figure
Conductor
Insulation
Filler
Wrapping layer
Sheath
A M A RESOURCES
62
Table6 0.6/1kV 3+1 core XLPE insulated PVC sheathed power cable
Nominal
cross-section
of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.-
Diameter.
of cable
Approx.-
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×4+1×2.5 0.7 1.5 12.5 236 180 4.6
1
7.4
1 3.5 0.757 40 30 55 45
3×6+1×4 0.7 1.5 13.7 316 210 3.0
8
4.6
1 3.5 0.645 50 40 65 55
3×10+1×6 0.7 1.5 15.4 460 380 1.8
3
3.0
8 3.5 0.523 70 55 90 70
3×16+1×1
0 0.7 1.5 17.5 679 575
1.1
5
1.9
1 3.5 0.431 90 70 110 90
3×25+1×1
6 0.9 2.0 23.8
136
8
0.7
27
1.2
0 3.5 0.414 130
10
5 150 120
3×35+1×1
6 0.9 2.0 23.8
156
8 821
0.5
24
0.8
68 3.5 0.379 165
13
0 185 140
3×50+1×2
5 1.0 2.0 27.4
190
1
114
1
0.3
87
0.6
41 3.5 0.355 200
16
0 210 170
3×70+1×3
5 1.1 2.0 31.0
258
5
146
3
0.2
68
0.4
43 3.5 0.335 285
20
3 265 203
3×95+1×5
0 1.1 2.5 35.8
371
8
223
1
0.1
93
0.3
20 3.5 0.290 320
25
5 315 250
3×120+1×
70 1.2 2.5 39.7
444
3
266
5
0.1
53
0.2
53 3.5 0.282 380
30
0 360 285
A M A RESOURCES
63
Nominal
cross-section
of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.-
Diameter.
of cable
Approx.-
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×150+1×
70 1.4 2.5 42.9
532
6
319
0
0.1
24
0.2
06 3.5 0.294 440
35
0 400 320
3×185+95 1.6 3.0 47.4 662
8
384
2
0.0
091
0.1
64 3.5 0.303 505
49
0 435 350
3×240+1×
120 1.7 3.0 52.7
850
1
500
1
0.0
754
0.1
25 3.5 0.283 603
47
1 524 415
3×300+1×
150 1.8 3.5 58.0
103
20
567
9
0.0
601
0.1
00 3.5 0.263 700
54
5 605 465
3×400+1×
185 2.0 3.5 63.5
121
39
718
5
0.0
470
0.0
08 3.5 0.243 795
61
0 675 525
Product Figure
Conductor
Insulation
Filler
Wrapping layer
Sheath
A M A RESOURCES
64
Table 7 0.6/1kV 4 cores XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductor
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.-
Diameter.
of cable
Approx.-
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm Kg/
km
kg/
km
/
km
/
km kV M .km A A A A
4×1.5 0.7 1.5 10.6 139 84 12.
1 3.5 1.10 21 26
4×2.5 0.7 1.5 11.5 150 107 7.4
1
12.
1 3.5 0.916 28 21 35 26
4×4 0.7 1.5 12.8 253 151 4.6
1
7.4
1 3.5 0.757 37 28 46 27
4×6 0.7 1.5 14.0 337 198 3.0
8
4.6
1 3.5 0.645 47 37 56 46
4×10 0.7 1.5 15.9 501 291 1.8
3
3.0
8 3.5 0.523 64 49 76 59
4×16 0.7 2.0 19.1 778 455 1.1
5
1.9
1 3.5 0.431 84 64 98 78
4×25 0.9 2.0 22.7 116
0 696
0.7
27
1.2
0 3.5 0.414 115 87 126 98
4×35 0.9 2.0 25.4 155
4 905
0.5
24
0.8
68 3.5 0.379 141
12
0 152 130
4×50 1.0 2.0 29.0 214
8
123
5
0.3
87
0.6
41 3.5 0.355 172
15
1 181 161
4×70 1.1 2.5 32.9 292
8
164
0
0.2
68
0.4
43 3.5 0.335 218
18
3 222 192
4×95 1.1 2.5 37.7 359
4
229
4
0.1
93
0.3
20 3.5 0.290 269
23
8 267 234
A M A RESOURCES
65
Nominal
cross-
section of
conductor
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.-
Diameter.
of cable
Approx.-
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm Kg/
km
kg/
km
/
km
/
km kV M .km A A A A
4×120 1.2 2.5 41.7 492
5
266
5
0.1
53
0.2
53 3.5 0.282 313
28
5 305 276
4×150 1.4 2.5 47.6 632
6
361
8
0.1
24
0.2
06 3.5 0.294 359
32
8 344 318
4×185 1.6 2.5 50.6 756
2
439
5
0.0
091
0.1
64 3.5 0.303 405
37
5 383 351
4×240 1.7 2.5 56.4966
0
560
3
0.0
754
0.1
25 3.5 0.283 451
40
5 442 391
4×300 1.8 3.5 62.2 117
58
658
5
0.0
601
0.1
00 3.5 0.263 491
42
2 461 392
4×400 2.0 3.5 68.0 138
36
778
4
0.0
470
0.0
08 3.5 0.243 543
46
5 500 425
Product Figure
Conductor
Insulation
Filler
Wrapping layer
Sheath
A M A RESOURCES
66
Table8 0.6/1kV 3 cores XLPE insulated steel-tape armored PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×1.5 0.7 1.5 13.0 273 12.
1 3.5 1.10 21 26
3×2.5 0.7 1.5 13.9 321 208 7.4
1
12.
1 3.5 0.916 28 24 35 30
3×4 0.7 1.5 15.0 390 254 4.6
1
7.4
1 3.5 0.757 37 32 46 39
3×6 0.7 1.5 16.1 471 344 3.0
8
4.6
1 3.5 0.645 47 41 56 48
3×10 0.7 1.5 17.8 622 404 1.8
3
3.0
8 3.5 0.523 64 55 76 65
3×16 0.7 2.0 21.5 100
5 650
1.1
5
1.9
1 3.5 0.431 84 70 98 80
3×25 0.9 2.0 24.8 137
1 891
0.7
27
1.2
0 3.5 0.414 115 96 126 105
3×35 0.9 2.0 27.2 172
4
112
1
0.5
24
0.8
68 3.5 0.379 141 118 152 186
3×50 1.0 2.0 30.4 224
7
157
3
0.3
87
0.6
41 3.5 0.355 172 144 181 152
3×70 1.1 2.5 35.3 302
3
196
5
0.2
68
0.4
43 3.5 0.335 218 183 222 186
3×95 1.1 2.5 38.7 382
5
248
6
0.1
93
0.3
20 3.5 0.290 269 243 267 224
A M A RESOURCES
67
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×120 1.2 2.5 42.2 464
2
301
7
0.1
53
0.2
53 3.5 0.282 313 263 305 256
3×150 1.4 3.0 47.5 576
7
374
9
0.1
24
0.2
06 3.5 0.294 359 302 344 289
3×185 1.6 3.0 52.8 689
2
448
0
0.0
091
0.1
64 3.5 0.303 405 340 383 321
3×240 1.7 3.0 58.1 801
7
521
5
0.0
754
0.1
25 3.5 0.283 451 378 442 355
3×300 1.8 3.5 63.4 914
2
594
6
0.0
601
0.1
00 3.5 0.263 491 417 461 387
3×400 2.0 3.5 68.7 102
87
667
3
0.0
470
0.0
08 3.5 0.243 543 456 500 420
Table 9 0.6/1kV 3+1 core XLPE insulated steel-tape armored PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×4+1×2.
5 0.7 1.5 15.7 443 288
4.6
1
7.4
1 3.5 0.757 37 32 46 39
3×6+1×4 0.7 1.5 16.9 531 372 3.0
8
4.6
1 3.5 0.645 47 37 56 46
3×10+1×
6 0.7 2.0 19.6 741 519
1.8
3
3.0
8 3.5 0.523 64 47 76 56
A M A RESOURCES
68
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
3×16+1×
10 0.7 2.0 22.5
113
5 795
1.1
5
1.9
1 3.5 0.431 84 64 98 76
3×25+1×
16 0.9 2.0 25.8
155
6
108
9
0.7
27
1.2
0 3.5 0.414 115 84 126 98
3×35+1×
16 0.9 2.0 27.8
189
6
132
7
0.5
24
0.8
68 3.5 0.379 141 115 152 126
3×50+1×
25 1.0 2.0 31.4
251
8
176
3
0.3
87
0.6
41 3.5 0.355 172
14
1 181 152
3×70+1×
35 1.1 2.5 36.4
339
3
237
5
0.2
68
0.4
43 3.5 0.335 218
17
2 222 181
3×95+1×
50 1.1 2.5 40.2
434
9
304
4
0.1
93
0.3
20 3.5 0.290 269
21
8 267 222
3×120+1
×70 1.2 3.0 44.1
536
5
375
6
0.1
53
0.2
53 3.5 0.282 313
26
9 305 267
3×150+1
×70 1.4 3.0 48.7
646
8
452
8
0.1
24
0.2
06 3.5 0.294 359
31
3 344 305
3×185+9
5 1.6 3.0 53.3
757
1
529
9
0.0
091
0.1
64 3.5 0.303 405
35
9 383 344
3×240+1
×120 1.7 3.0 58.9
867
4
607
2
0.0
754
0.1
25 3.5 0.283 451
40
5 429 383
3×300+1
×150 1.8 3.5 63.5
977
7
684
4
0.0
601
0.1
00 3.5 0.263 497
45
1 475 429
3×400+1
×185 2.0 3.5 69.1
108
80
761
6
0.0
470
0.0
08 3.5 0.243 543
49
7 521 475
A M A RESOURCES
69
Table 10 0.6/1kV 4 cores XLPE insulated steel-tape armored PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
2Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
4×1.5 0.7 1.5 13.8 307 209 12.
1 3.5 1.10 21 19 26 22
4×2.5 0.7 1.5 14.7 367 250 7.4
1
12.
1 3.5 0.916 28 21 35 26
4×4 0.7 1.5 16.0 454 309 4.6
1
7.4
1 3.5 0.757 37 28 46 35
4×6 0.7 1.5 17.2 557 379 3.0
8
4.6
1 3.5 0.645 47 37 56 46
4×10 0.7 2.0 20.1 791 538 1.8
3
3.0
8 3.5 0.523 64 47 76 56
4×16 0.7 2.0 23.1 121
0 823
1.1
5
1.9
1 3.5 0.431 84 64 98 76
4×25 0.9 2.0 26.7 167
2
113
4
0.7
27
1.2
0 3.5 0.414 115 84 126 98
4×35 0.9 2.0 29.4 212
7
144
6
0.5
24
0.8
68 3.5 0.379 141 115 152 126
A M A RESOURCES
70
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
2Max. DC
resistance
at20Test
voltage
Resistance
of
insulation
Current rating
Cu Al Cu Al In air In earth
Cu Al Cu Al
mm² mm mm mm kg/
km
kg/
km
/
km
/
km kV M .km A A A A
4×50 1.0 2.0 33.0 280
2
190
6
0.3
87
0.6
41 3.5 0.355 172 141 181 152
4×70 1.1 2.5 38.3 378
5
257
4
0.2
68
0.4
43 3.5 0.335 218 172 222 181
4×95 1.1 2.5 42.1 482
9
328
4
0.1
93
0.3
20 3.5 0.290 269 218 267 222
4×120 1.2 3.0 47.4 603
3
410
3
0.1
53
0.2
53 3.5 0.282 313 269 305 267
4×150 1.4 3.0 52.2 735
6
500
2
0.1
24
0.2
06 3.5 0.294 359 313 344 305
4×185 1.6 3.0 57.0 867
9
590
2
0.0
091
0.1
64 3.5 0.303 405 359 383 344
4×240 1.7 3.0 61.8 100
02
680
2
0.0
754
0.1
25 3.5 0.283 451 405 442 383
4×300 1.8 3.5 66.6 123
25
838
1
0.0
601
0.1
00 3.5 0.263 497 451 461 422
4×400 2.0 3.5 71.4 146
48
996
1
0.0
470
0.0
08 3.5 0.243 543 497 500 461
A M A RESOURCES
71
Table 11 3.6/6kV single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA kA
1×25 2.8 1.8 19.0 617 459 0.7
27
1.2
00 165 130 160 120 3.7 2.4
1.0
8 3.8
1×35 2.5 1.8 20.0 736 515 0.5
24
0.8
68 205 155 190 145 5.2 3.4
1.0
7 3.5
1×50 2.5 1.8 22.0 903 587 0.3
87
0.6
41 245 190 225 175 7.3 4.8
1.0
7 3.5
1×70 2.5 1.8 23.0 112
9 687
0.2
68
0.4
43 305 235 275 215
10.
2 6.7
1.0
7 3.5
1×95 2.5 1.8 25.0 140
7 807
0.1
93
0.3
20 370 290 330 255
13.
8 9.7
1.0
7 5.4
1×120 2.5 1.8 26.0 167
6 918
0.1
53
0.2
53 430 335 375 290
17.
4
11.
4
1.0
7 5.4
1×150 2.5 1.8 28.0 199
0
104
3
0.1
24
0.2
06 490 380 425 330
21.
7
14.
2
1.0
7 5.4
1×185 2.5 1.9 30.0 235
8
119
0
0.0
991
0.1
64 560 435 480 370
26.
7
17.
5
1.0
6 7.5
1×240 2.8 1.9 32.0 293
5
142
0
0.0
754
0.1
25665 515 555 435
34.
6
22.
6
1.2
47.5
1×300 2.8 2.0 35.0 364
8
175
4
0.0
601
0.1
00 765 595 630 490
43.
1
28.
2
1.2
4 7.5
1×400 3.0 2.1 39.0 467
5
214
9
0.0
470
0.0
778 890 695 725 565
57.
4
37.
6
1.2
4 7.5
1×500 3.2 2.2 41.0 570
2
254
4
0.0
366
0.0
605
103
0 810 825 650
71.
7
47.
0
1.2
4 7.5
A M A RESOURCES
72
Table12 3.6/6kV 3 cores XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×25 2.8 2.1 39.0 188
8
141
4
0.7
27
1.2
00 120 90 125 100 3.69 2.42 2.96
3×35 2.5 2.2 41.0 228
7
162
4
0.5
24
0.8
68 140 110 155 120 5.15 3.37 2.96
3×50 2.5 2.3 44.0 278
3
183
6
0.3
87
0.6
41 165 130 180 140 7.31 4.79 2.96
3×70 2.5 2.4 48.0 355
1
222
5
0.2
68
0.4
43 210 165 220 170 10.2 6.68 2.96
3×95 2.5 2.5 52.0 448
3
268
3
0.1
93
0.3
20 255 200 265 210 13.8 9.68 2.96
3×120 2.5 2.6 55.0 533
8
306
5
0.1
53
0.2
53 290 225 300 235 17.4 11.4 2.96
3×150 2.5 2.8 59.0 627
9
343
8
0.1
24
0.2
06 330 255 340 260
21.7
7 14.2 2.96
3×185 2.5 2.9 62.0 756
5
406
1
0.0
991
0.1
64 375 295 380 300 26.7 17.5 2.96
3×240 2.8 3.0 68.0 930
4
485
8
0.0
754
0.1
25 435 345 435 345 34.6 22.6 3.3
3×300 2.8 3.1 74.0 113
71
568
9
0.0
601
0.1
00 495 390 485 390 43.1 28.2 3.3
3×400 3.0 3.2 76.0 134
38
652
0
0.0
470
0.0
778 555 435 535 435 57.4 37.6 3.3
3×500 3.2 3.3 78.0 155
05
735
1
0.0
366
0.0
605 615 480 585 480 71.7 47.0 3.3
A M A RESOURCES
73
Table13 3.6/6kV 3 cores XLPE insulated steel-tape armored PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×25 2.8 2.3 44.0 282
9
235
5
0.7
27
1.2
00 120 90 125 100 3.69 2.42 2.96
3×35 2.5 2.3 46.0 330
1
263
8
0.5
24
0.8
68 140 110 155 120 5.15 3.37 2.96
3×50 2.5 2.4 49.0 385
5
290
8
0.3
87
0.6
41 165 130 180 140 7.31 4.79 2.96
3×70 2.5 2.5 53.0 484
5
351
9
0.2
68
0.4
43 210 165 220 170 10.2 6.68 2.96
3×95 2.5 2.7 57.0 579
7
399
8
0.1
93
0.3
20 255 200 265 210 13.8 9.68 2.96
3×120 2.5 2.8 60.0 673
5
446
2
0.1
53
0.2
53 290 225 300 235 17.4 11.4 2.96
3×150 2.5 2.9 64.0 792
4
508
3
0.1
24
0.2
06 330 255 340 260
21.7
7 14.2 2.96
3×185 2.5 3.0 68.0 921
6
571
2
0.0
991
0.1
64 375 295 380 300 26.7 17.5 2.96
3×240 2.8 3.2 74.0 112
36
669
0
0.0
754
0.1
25 435 345 435 345 34.6 22.6 3.3
3×300 2.8 3.5 81.0 144
37
875
5
0.0
601
0.1
00 495 390 485 390 43.1 28.2 3.3
3×400 3.0 3.7 84.0 176
83
108
20
0.0
470
0.0
778 555 435 535 435 57.4 37.6 3.3
3×500 3.2 4.0 87.0 208
39
128
85
0.0
366
0.0
605 615 480 585 480 71.7 47.0 3.3
A M A RESOURCES
74
Table14 6/6kV 6/10kV single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA kA
1×25 3.4 1.8 21.0 685 52
7
0.7
27
1.2
00
16
5130 160
12
0 3.7 2.4 1.08 3.8
1×35 3.4 1.8 22.0 807 58
6
0.5
24
0.8
68
20
5155 190
14
5 5.2 3.4 1.07 3.5
1×50 3.4 1.8 23.0 977 66
1
0.3
87
0.6
41
24
5190 225
17
5 7.3 4.8 1.07 3.5
1×70 3.4 1.8 25.0 120
7
76
5
0.2
68
0.4
43
30
5235 275
21
5
10.
2 6.7 1.07 3.5
1×95 3.4 1.8 27.0 148
9
88
9
0.1
93
0.3
20
37
0290 330
25
5
13.
8 9.7 1.07 5.4
1×120 3.4 1.9 28.0 176
2
10
02
0.1
53
0.2
53
43
0335 375
29
0
17.
4
11.
4 1.07 5.4
1×150 3.4 1.9 30.0 208
0
11
33
0.1
24
0.2
06
49
0380 425
33
0
21.
7
14.
2 1.07 5.4
1×185 3.4 2.0 32.0 245
3
12
85
0.0
991
0.1
64
56
0435 480
37
0
26.
7
17.
5 1.06 7.5
1×240 3.4 2.1 34.0 310
0
15
84
0.0
754
0.1
25
66
5515 555
43
5
34.
6
22.
6 1.24 7.5
1×300 3.4 2.1 36.0 372
3
18
29
0.0
601
0.1
00
76
5595 630
49
0
43.
1
28.
2 1.24 7.5
1×400 3.4 2.3 40.0 472
8
22
03
0.0
470
0.0
778
89
0695 725
56
5
57.
4
37.
6 1.24 7.5
1×500 3.4 2.4 42.0 573
3
25
77
0.0
366
0.0
605
10
30810 825
65
0
71.
7
47.
01.24 7.5
A M A RESOURCES
75
Table15 6/6 6/10 kV 3 cores XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulatio
n
Thick-
ness
of
sheath
Approx
.dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×25 3.4 2.3 43.0 213
2
235
5
0.7
27
1.2
00 120 90 125 100 3.69 2.42 2.96
3×35 3.4 2.3 45.0 249
1
263
8
0.5
24
0.8
68 140 110 155 120 5.15 3.37 2.96
3×50 3.4 2.4 48.0 309
1
290
8
0.3
87
0.6
41 165 130 180 140 7.31 4.79 2.96
3×70 3.4 2.6 52.0 388
4
351
9
0.2
68
0.4
43 210 165 220 170 10.2 6.68 2.96
3×95 3.4 2.7 56.0 477
8
399
8
0.1
93
0.3
20 255 200 265 210 13.8 9.68 2.96
3×120 3.4 2.8 59.0 559
5
446
2
0.1
53
0.2
53 290 225 300 235 17.4 11.4 2.96
3×150 3.4 2.9 63.0 673
2
508
3
0.1
24
0.2
06 330 255 340 260
21.7
7 14.2 2.96
3×185 3.4 3.0 66.0 795
4
571
2
0.0
991
0.1
64 375 295 380 300 26.7 17.5 2.96
3×240 3.4 3.2 77.0 972
9
669
0
0.0
754
0.1
25 435 345 435 345 34.6 22.6 3.3
3×300 3.4 3.3 77.0 118
55
875
5
0.0
601
0.1
00 495 390 485 390 43.1 28.2 3.3
3×400 3.4 3.4 79.0 139
80
108
20
0.0
470
0.0
778 555 435 535 435 57.4 37.6 3.3
3×500 3.4 3.5 81.0 161
07
128
85
0.0
366
0.0
605 615 480 585 480 71.7 47.0 3.3
A M A RESOURCES
76
Table16 6/6kV 6/10kV 3 cores XLPE insulated steel-tape armored PVC sheathed power
cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×25 3.4 2.4 48.0 319
0
271
6
0.7
27
1.2
00 120 90 125 100 3.69 2.42 2.96
3×35 3.4 2.5 50.0 373
1
305
8
0.5
24
0.8
68 140 110 155 120 5.15 3.37 2.96
3×50 3.4 2.6 53.0 439
6
344
9
0.3
87
0.6
41 165 130 180 140 7.31 4.79 2.96
3×70 3.4 2.7 57.0 519
8
387
2
0.2
68
0.4
43 210 165 220 170 10.2 6.68 2.96
3×95 3.4 2.9 62.0 635
0
455
1
0.1
93
0.3
20 255 200 265 210 13.8 9.68 2.96
3×120 3.4 3.0 65.0 725
7
498
4
0.1
53
0.2
53 290 225 300 235 17.4 11.4 2.96
3×150 3.4 3.1 69.0 838
3
554
2
0.1
24
0.2
06 330 255 340 260
21.7
7 14.2 2.96
3×185 3.4 3.2 72.0 974
1
623
7
0.0
991
0.1
64 375 295 380 300 26.7 17.5 2.96
3×240 3.4 3.3 78.0 118
54
730
9
0.0
754
0.1
25435 345 435 345 34.6 22.6 3.3
3×300 3.4 3.4 84.0 148
61
917
8
0.0
601
0.1
00 495 390 485 390 43.1 28.2 3.3
3×400 3.4 3.5 90.0 178
68
110
47
0.0
470
0.0
778 555 435 535 435 57.4 37.6 3.3
3×500 3.4 3.6 96.0 198
75
129
16
0.0
366
0.0
605 615 480 585 480 71.7 47.0 3.3
A M A RESOURCES
77
Table 17 8.7/10kV 8.7/15kV single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA kA
1×25 4.5 1.8 23.0 775 617 0.7
27
1.2
00 165 130 160
12
0 3.7 2.4
1.0
9 3.5
1×35 4.5 1.8 24.0 899 678 0.5
24
0.8
68 205 155 190
14
5 5.2 3.4
1.0
9 3.5
1×50 4.5 1.8 26.0 107
3 757
0.3
87
0.6
41 245 190 225
17
5 7.3 4.8
1.0
9 3.5
1×70 4.5 1.8 27.0 130
8 866
0.2
68
0.4
43 305 235 275
21
5
10.
2 6.7
1.0
9 3.5
1×95 4.5 1.8 29.0 159
6 996
0.1
93
0.3
20 370 290 330
25
5
13.
8 9.7
1.0
9 5.5
1×120 4.5 1.9 30.0 187
4
111
6
0.1
53
0.2
53 430 335 375
29
0
17.
4
11.
41.3 5.5
1×150 4.5 1.9 32.0 219
4
125
0
0.1
24
0.2
06 490 380 425
33
0
21.
7
14.
21.3 5.5
1×185 4.5 2.0 34.0 264
9
148
1
0.0
991
0.1
64 560 435 480
37
0
26.
7
17.
51.3 7.7
1×240 4.5 2.1 36.0 323
4
171
9
0.0
754
0.1
25665 515 555
43
5
34.
6
22.
61.3 7.7
1×300 4.5 2.1 38.0 386
5
197
1
0.0
601
0.1
00 765 595 630
49
0
43.
1
28.
21.3 7.6
1×400 4.5 2.3 42.0 483
0
235
4
0.0
470
0.0
778 890 695 725
56
5
57.
4
37.
61.3 7.6
1×500 4.5 2.4 44.0 579
5
237
3
0.0
366
0.0
605
103
0 810 825
65
0
71.
7
47.
01.3 7.6
A M A RESOURCES
78
Table 18 8.7/10kV 8.7/15kV 3 cores XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×25 4.5 2.4 48.0 248
6
210
2
0.7
27
1.2
00 120 90 125 100
3.6
9 2.42 2.96
3×35 4.5 2.5 50.0 296
3
230
0
0.5
24
0.8
68 140 110 155 120
5.1
5 3.37 2.96
3×50 4.5 2.6 53.0 348
1
253
4
0.3
87
0.6
41 165 130 180 140
7.3
1 4.79 2.96
3×70 4.5 2.7 57.0 403
6
291
1
0.2
68
0.4
43 210 165 220 170
10.
2 6.68 2.96
3×95 4.5 2.8 61.0 514
7
334
8
0.1
93
0.3
20 255 200 265 210
13.
8 9.68 2.96
3×120 4.5 2.9 64.0 611
6
384
3
0.1
53
0.2
53 290 225 300 235
17.
4 11.4 2.96
3×150 4.5 3.1 68.0 718
7
434
6
0.1
24
0.2
06 330 255 340 260
21.
77 14.2 2.96
3×185 4.5 3.2 72.0 837
9
487
4
0.0
991
0.1
64 375 295 380 300
26.
7 17.5 2.96
3×240 4.5 3.3 77.0 103
91
584
5
0.0
754
0.1
25 435 345 435 345
34.
6 22.6 3.3
3×300 4.5 3.5 82.0 123
36
665
3
0.0
601
0.1
00 495 390 485 390
43.
1 28.2 3.3
3×400 4.5 3.6 87.0 142
81
745
9
0.0
470
0.0
778 555 435 535 435
57.
4 37.6 3.3
3×500 4.5 3.8 92.0 162
26
826
5
0.0
366
0.0
605 615 480 585 480
71.
7 47.0 3.3
A M A RESOURCES
79
Table19 8.7/10kV 8.7/15kV 3 cores XLPE insulated steel-tape armored PVC sheathed power
cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km km km A A A A kA kA kA
3×25 4.5 2.6 53.0 379
6
332
3
0.7
27
1.2
00 120 90 125 100
3.6
9 2.42 2.96
3×35 4.5 2.6 56.0 425
2
358
9
0.5
24
0.8
68 140 110 155 120
5.1
5 3.37 2.96
3×50 4.5 2.8 59.0 482
9
388
1
0.3
87
0.6
41 165 130 180 140
7.3
1 4.79 2.96
3×70 4.5 2.9 63.0 583
4
450
8
0.2
68
0.4
43 210 165 220 170
10.
2 6.68 2.96
3×95 4.5 3.0 67.0 688
5
508
5
0.1
93
0.3
20 255 200 265 210
13.
8 9.68 2.96
3×120 4.5 3.1 70.0 780
7
553
4
0.1
53
0.2
53 290 225 300 235
17.
4 11.4 2.96
3×150 4.5 3.2 74.0 899
5
615
4
0.1
24
0.2
06 330 255 340 260
21.
77 14.2 2.96
3×185 4.5 3.3 78.0 104
93
698
9
0.0
991
0.1
64 375 295 380 300
26.
7 17.5 2.96
3×240 4.5 3.6 84.0 133
81
883
5
0.0
754
0.1
25 435 345 435 345
34.
6 22.6 3.3
3×300 4.5 3.7 89.0 155
64
988
1
0.0
601
0.1
00 495 390 485 390
43.
1 28.2 3.3
3×400 4.5 3.8 94.0 177
47
109
27
0.0
470
0.0
778 555 435 535 435
57.
4 37.6 3.3
3×500 4.5 4.0 99.0 199
30
119
73
0.0
366
0.0
605615 480 585 480
71.
747.0 3.3
A M A RESOURCES
80
Table20 12/20kV single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section
of con-
ductors
Thick-
ness of
insulation
Thick-
ness
of
sheath
Appro
x.dia.
of
cable
Approx.-
weight
Max. DC
resistanc
e at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA kA
1×35 5.5 1.8 26.0 990 769 0.5
24
0.8
68 205
15
5 190 145 5.2 3.4 1.09 3.5
1×50 5.5 1.8 28.0 116
0 851
0.3
87
0.6
41 245
19
0 225 175 7.3 4.8 1.09 3.5
1×70 5.5 1.9 29.0 140
7 965
0.2
68
0.4
43 305
23
5 275 215
10.
2 6.7 1.09 3.5
1×95 5.5 1.9 31.0 170
0
110
0
0.1
93
0.3
20 370
29
0 330 255
13.
8 9.7 1.09 5.5
1×120 5.5 2.0 33.0 198
2
122
4
0.1
53
0.2
53 425
33
5 375 290
17.
4
11.
4 1.3 5.5
1×150 5.5 2.0 34.0 238
3
143
6
0.1
24
0.2
06 485
38
0 425 330
21.
7
14.
2 1.3 5.5
1×185 5.5 2.1 36.0 277
1
160
3
0.0
991
0.1
64 555
43
5 480 370
26.
7
17.
5 1.3 7.7
1×240 5.5 2.1 38.0 336
3
184
8
0.0
754
0.1
25 660
51
5 555 435
34.
6
22.
6 1.3 7.7
1×300 5.5 2.2 41.0 400
0
210
6
0.0
601
0.1
00 745
59
5 630 490
43.
1
28.
2 1.3 7.6
1×400 5.5 2.3 44.0 502
4
249
8
0.0
470
0.0
778 870
69
5 725 565
57.
4
37.
6 1.3 7.6
1×500 5.5 2.4 45.0 604
8
289
0
0.0
366
0.0
605
100
0
81
0 825 650
71.
7
47.
0 1.3 7.6
A M A RESOURCES
81
Table21 12/20kV 3 cores XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×35 5.5 2.4 50.0 296
3
230
0
0.5
24
0.8
68 140 110 155 120
5.1
5 3.37 2.96
3×50 5.5 2.8 53.0 348
1
253
4
0.3
87
0.6
41 165 130 180 140
7.3
1 4.79 2.96
3×70 5.5 2.9 57.0 403
6
291
1
0.2
68
0.4
43 210 165 220 170
10.
2 6.68 2.96
3×95 5.5 3.0 61.0 514
7
334
8
0.1
93
0.3
20 255 200 265 210
13.
8 9.68 2.96
3×120 5.5 3.1 64.0 611
6
384
3
0.1
53
0.2
53 290 225 300 235
17.
4 11.4 2.96
3×150 5.5 3.2 68.0 718
7
434
6
0.1
24
0.2
06 330 255 340 260
21.
77 14.2 2.96
3×185 5.5 3.3 72.0 839
7
487
4
0.0
991
0.1
64 375 295 380 300
26.
7 17.5 2.96
3×240 5.5 3.5 77.0 103
91
584
5
0.0
754
0.1
25 435 345 435 345
34.
6 22.6 3.3
3×300 5.5 3.6 82.0 123
36
665
3
0.0
601
0.1
00 495 390 485 390
43.
1 28.2 3.3
3×400 5.5 3.7 87.0 142
81
745
9
0.0
470
0.0
778 555 435 535 435
57.
4 37.6 3.3
3×500 5.5 3.8 92.0 162
26
826
5
0.0
366
0.0
605 615 480 585 480
71.
7 47.0 3.3
A M A RESOURCES
82
Table22 12/20kV 3 cores XLPE insulated steel-tape armored PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×35 5.5 2.8 60.0 465
9
399
7
0.5
24
0.8
68 140 110 155 120
5.1
5 3.37 2.96
3×50 5.5 2.9 63.0 543
0
448
2
0.3
87
0.6
41 165 130 180 140
7.3
1 4.79 2.96
3×70 5.5 3.0 68.0 632
7
500
1
0.2
68
0.4
43 210 165 220 170
10.
2 6.68 2.96
3×95 5.5 3.2 72.0 744
6
564
6
0.1
93
0.3
20 255 200 265 210
13.
8 9.68 2.96
3×120 5.5 3.3 75.0 838
2
610
9
0.1
53
0.2
53 290 225 300 235
17.
4 11.4 2.96
3×150 5.5 3.4 79.0 990
6
686
5
0.1
24
0.2
06 330 255 340 260
21.
77 14.2 2.96
3×185 5.5 3.5 83.0 119
54
845
0
0.0
991
0.1
64 375 295 380 300
26.
7 17.5 2.96
3×240 5.5 3.7 89.0 140
27
918
1
0.0
754
0.1
25 435 345 435 345
34.
6 22.6 3.3
3×300 5.5 3.9 94.0 164
37
107
55
0.0
601
0.1
00 495 390 485 390
43.
1 28.2 3.3
3×400 5.5 4.0 99.0 188
47
120
29
0.0
470
0.0
778 555 435 535 435
57.
4 37.6 3.3
3×500 5.5 4.2 104.0 212
57
133
03
0.0
366
0.0
605 615 480 585 480
71.
7 47.0 3.3
A M A RESOURCES
83
Table23 18/20kV 18/30kV single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA kA
1×50 8.0 2.0 33.0 142
6
111
0
0.3
87
0.6
41 245 190 225 175 7.3 4.8 1.3 3.6
1×70 8.0 2.0 35.0 175
2
131
0
0.2
68
0.4
43 305 235 275 215
10.
2 6.7 1.3 3.6
1×95 8.0 2.1 36.0 206
2
146
2
0.1
93
0.3
20 370 285 330 255
13.
8 9.7 1.3 5.6
1×120 8.0 2.1 38.0 235
8
160
0
0.1
53
0.2
53 425 330 375 290
17.
4
11.
4 1.3 5.6
1×150 8.0 2.2 40.0. 269
9
175
2
0.1
24
0.2
06 485 375 425 330
21.
7
14.
2 1.3 5.6
1×185 8.0 2.2 41.0 310
0
193
2
0.0
991
0.1
64 555 430 480 370
26.
7
17.
5 1.3 7.7
1×240 8.0 2.3 44.0 370
9
219
4
0.0
754
0.1
25 660 505 555 435
34.
6
22.
6 1.3 7.7
1×300 8.0 2.4 45.0 436
4
247
0
0.0
601
0.1
00 745 580 630 490
43.
1
28.
2 1.3 7.6
1×400 8.0 2.5 49.0 551
7
299
1
0.0
470
0.0
778 870 680 725 565
57.
4
37.
6 1.3 7.6
1×500 8.0 2.5 51.0 667
0
351
2
0.0
366
0.0
605
100
0 790 825 645
71.
7
47.
0 1.3 7.6
A M A RESOURCES
84
Table24 21/35kV single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA kA
1×50 9.3 2.1 36.0 165
2
133
6
0.3
87
0.6
41 245 190 225 175 7.3 4.8 1.3 3.6
1×70 9.3 2.1 37.0 191
3
147
1
0.2
68
0.4
43 305 235 275 215
10.
2 6.7 1.3 3.6
1×95 9.3 2.2 39.0 222
9
163
0
0.1
93
0.3
20 370 290 330 255
13.
8 9.7 1.3 5.6
1×120 9.3 2.2 41.0 253
1
177
3
0.1
53
0.2
53 425 335 375 290
17.
4
11.
4 1.3 5.6
1×150 9.3 2.3 42.0 287
8
193
1
0.1
24
0.2
06 485 380 425 330
21.
7
14.
2 1.3 5.5
1×185 9.3 2.3 44.0 328
5
211
7
0.0
991
0.1
64 555 435 480 370
26.
7
17.
5 1.3 7.8
1×240 9.3 2.4 46.0 390
4
238
8
0.0
754
0.1
25 660 515 555 435
34.
6
22.
6 1.3 7.7
1×300 9.3 2.5 49.0 456
8
267
4
0.0
601
0.1
00 745 595 630 490
43.
1
28.
2 1.3 7.7
1×400 9.3 2.6 52.0 573
7
321
2
0.0
470
0.0
778 870 695 725 565
57.
4
37.
6 1.3 7.7
1×500 9.3 2.7 54.0 690
0
375
0
0.0
366
0.0
605
100
0 810 825 650
71.
7
47.
0 1.3 7.7
A M A RESOURCES
85
Table25 26/35kV single core XLPE insulated PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al
In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu
tape
Cu
tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA kA
1×50 10.5 2.2 38.0 180
3
148
7
0.3
87
0.6
41 245 190 225 175 7.3 4.8 1.3 3.6
1×70 10.5 2.2 40.0 207
0
162
8
0.2
68
0.4
43 305 235 275 215
10.
2 6.7 1.3 3.6
1×95 10.5 2.3 42.0 239
3
179
3
0.1
93
0.3
20 370 290 330 255
13.
8 9.7 1.3 5.6
1×120 10.5 2.3 43.0 269
9
194
2
0.1
53
0.2
53 425 335 375 290
17.
4
11.
4 1.3 5.6
1×150 10.5 2.4 45.0 305
2
210
4
0.1
24
0.2
06 485 380 425 330
21.
7
14.
2 1.3 5.6
1×185 10.5 2.4 47.0 346
5
229
4
0.0
991
0.1
64 555 435 480 370
26.
7
17.
5 1.3 7.7
1×240 10.5 2.5 49.0 409
2
257
7
0.0
754
0.1
25 660 515 555 435
34.
6
22.
6 1.3 7.7
1×300 10.5 2.6 51.0 486
7
298
2
0.0
601
0.1
00 745 595 630 490
43.
1
28.
2 1.3 7.6
1×400 10.5 2.7 55.0 594
9
342
4
0.0
470
0.0
778 870 695 725 565
57.
4
37.
6 1.3 7.6
1×500 10.5 2.8 57.0 700
0
386
6
0.0
366
0.0
605
100
0 810 825 650
71.
7
47.
0 1.3 7.6
A M A RESOURCES
86
Table26 26/35kV 3 cores XLPE insulated steel-tape armored PVC sheathed power cable
Nominal
cross-
section of
conductors
Thick-
ness of
insulation
Thick-
ness of
sheath
Approx.
dia. of
cable
Approx.-
weight
Max. DC
resistance
at20
Current rating Short circuit current
Cu Al Cu Al In air In earth Conductor Screen
Cu Al Cu Al Cu Al Cu tape
mm² mm mm mm kg/
km
kg/
km
/
km
/
km A A A A kA kA kA
3×50 10.5 3.7 90.0 968
7
882
1
0.3
87
0.6
41 190 145 185 140
7.3
1
4.7
9 2.96
3×70 10.5 3.9 95.0 102
83
953
3
0.2
68
0.4
43 240 180 225 170
10.
2
6.6
8 2.96
3×95 10.5 4.0 98.0 120
74
103
79
0.1
93
0.3
20 288 220 275 210
13.
8
9.6
8 2.96
3×120 10.5 4.2 102.0 132
67
111
33
0.1
53
0.2
53 335 260 315 240
17.
4
11.
4 2.96
3×150 10.5 4.3 106.0 146
59
119
80
0.1
24
0.2
06 380 295 350 270
21.
77
14.
2 2.96
3×185 10.5 4.5 110.0 162
26
129
22
0.0
991
0.1
64 437 335 401 305
26.
7
17.
5 2.96
3×240 10.5 4.6 115.0 185
07
142
22
0.0
754
0.1
25 510 398 465 360
34.
6
22.
6 3.3
3×300 10.5 4.8 120.0 208
66
155
44
0.0
601
0.1
00 580 455 525 410
43.
1
28.
2 3.3
A M A RESOURCES
87
Product pictures
Note Single core cable armored material should be non-magnetic or reducing
magnetic loss structure
9. Delivery length
The delivery length of cable shall not be less than 100m. The tolerance of length must
be less than ±0.5%. Any delivery length is permitted under the agreement.
The terminal of cable must be shut fasten. The length of cable out of reel must be
more them 300mm.
Conductor
Conductor screen
Insulation
Insulation screen
Metallic screen
Filler
Wrapping layer
Inner sheath
Armour
Sheath
A M A RESOURCES
88
Section8Low Smoke Halogen Free(LSHF) Cable
Ⅰ FD/LSHF Insulated Copper Cable(1 core)
Specification:■Lighting control and low voltage power system cable■Cable type: CU/FD/LSHF 450/750V LSHF 90℃■Single core copper conductor LSHF insulated
Scope:■Single core with copper conductors, with LSHF insulated. Cables are rated up to450/750V in lower voltage power system and conform to IEC60502, IEC60754,IEC60332.■Application: These cables have been designed for buildings and equipments wheretheir internal environment has LSHF requirements.
Operating Characteristics:■Rated voltage: 0.45/0.75 kV, maximum operating voltage should be less than 1.0 kV.■Maximum rated temperature of cable conductor is 90℃ during long running process.When a short circuit occurs, cable conductor does not exceed 250 ℃, with durationless 5 sec.■Minimum working environment temperature is minus 20℃.■The environmental temperature should be above 0℃ when installing cable.■ Minimum bending radius should be10 times less than cable diameter.
Cable Structure:■Conductor: Cable conductor is made by T2 copper rods in which pure copperoccupies 99.95%, the surface should be clean, no oil stain, no metal burr or sharpedge which may break insulation and sheath, and no bulge or rupture.■Insulation:Insulation adopts LSHF materials, Average insulation thickness conformsto IEC60502 Average insulation thickness should not be less than nominal value, andany measured value should not be less than 90% of the nominal value. Theeccentricity ratio of any section [(maximum measured thickness - minimum measuredthickness) / maximum measured thickness] should not be more than 10%.
Cable identification:The signs on the finished cable should be consistent and legible. It should be easy torecognize and possesses Rub-off resistance. The sheath surface should have thesecontents as follow for each finished cable.■ The length should marked every one meter■ Manufacturer’s name,■Model number■Voltage grade
A M A RESOURCES
89
Section8
■Meters maker
Testing:Cable should pass the testing and inspection which include following detail beforedelivery■ Conductor structure and conductor resistance■Average insulation thickness and thinnest insulation thickness■Insulation resistance and withstand voltage test■Flame retardant test, smoke density test, halogen content test
Packing:These cables are packed in cable reels or in cable rolls and should be sealed safely atboth ends.Cable reels or cable rolls should indicate plate number, cable type, specification,length, gross weight, rolling direction and other considerations.Product quality inspection certificate should go along with each cable delivery. Testreport should be submitted to the interested party through the appropriate way.
Drawing:
Technical Data(1core)(parts)
Description Unit Proposed Data
Number of core andcross-section area
No.*mm2 1C*2.5 1C*4 1C*6 1C*10 1C*16
Manufacturer / Anhui Deyuan Cable Group Co., Ltd.
Conductor
LSHF
Insulation
A M A RESOURCES
90
Section8
Type / CU/FD/LSHF
Standards / IEC60502, IEC60754, IEC60332
Rated voltage v Less than 750
Conductor
Material Concentric-lay-round stranded annealed copper wire
Resistivity at 20 ℃ Ω-mm2/m ≤0.017241
Conductivity at 20℃ % IACS 100
Number anddiameter of wire
No./mm 1/1.78 1/2.24 1/2.76 7/1.35 7/1.70
Diameter ofconductor
mm 1.78 2.24 2.76 4.05 5.1
Max. DC conductorresistance at 20℃
Ω/km 7.41 4.61 3.08 1.83 1.15
Insulation
Material / LSHF
Average thickness mm 0.7 0.7 0.7 0.7 0.7
Min. insulationresistance at 90℃
MΩ-km 0.916 0.757 0.645 0.523 0.444
Overall diameter mm 3.18 3.84 4.36 6.05 7.10
Cable weight KG/KM 27.58 41.52 60.83 100.48 155.54
Withstand ACvoltage(5min.)
KV 2.5
Light transmittance % ≥60
PH value >4.3
Halogen content mg/g <5
Standard packing / 100M/C 100M/C 100M/C 100M/C 100M/C
A M A RESOURCES
91
Section8
Ⅱ FR/LSHF Insulated Copper Cable(1 core)
Specification:■Lighting control and low voltage power system cable■Cable type :CU/MTP/LSHF 0.45/0.75kv 90℃■Single core copper conductor fire-resistant mica tape wrapped LSHF insulated.
Scope:■Single core with copper conductors, with mica tape wrapped and LSHF insulated.Cables are rated up to 450/750V in lower voltage power system and conform toIEC60502, IEC60332,IEC60754, IEC60331.■These cables have been designed for sites with big passenger flow such as hospital,subway, school and supermarket, which have special requirements for LSHF as wellas maintaining power in the flame for more than 90 minutes.
Operating Characteristics:■Rated voltage: 0.45/0.75 kV, maximum operating voltage should be less than 1.0kV.■Maximum rated temperature of cable conductor is 90℃ during long runningprocess. When a short circuit occurs, cable conductor does not exceed 250 ℃ , withduration less 5 sec.■Minimum working environment temperature is minus 20 ℃.■The environmental temperature should be above 0 ℃ when installing cable.■Minimum bending radius should be10 times less than cable diameter.
Cable Structure:■ Conductor: Cable conductor is made by T2 copper rods in which pure copperoccupies 99.95%, the surface should be clean, no oil stain, no metal burr or sharpedge which may break insulation and sheath, no bulge or rupture.■ Fire-resistant layer is made of gold mica tape with double sides, the coverage rateshould not be less than 25%.■ Insulation : Insulation adopts LSHF materials, Average insulation thicknessconforms to IEC60502 and should not be less than nominal value, any measured valueshould not be less than 90% of the nominal value. The eccentricity ratio of any section[(maximum measured thickness - minimum measured thickness) / maximummeasured thickness] should not be more than 10%.
Cable identification:
A M A RESOURCES
92
Section8
The signs on the finished cable should be consistent and legible. It should be easy torecognize and possesses Rub-off resistance. The sheath surface should have thesecontents as follow for each finished cable.■The length should marked every one meter■ Manufacturer’s name,■Model number■Voltage grade■Meters maker
Testing:Cable should pass the testing and inspection which include following detail beforedelivery■ Conductor structure and conductor resistance■Average insulation thickness and thinnest insulation thickness■Insulation resistance and withstand voltage test■Flame retardant test, smoke density test, halogen content test and Fire-resistant test
Packing:These cables are packed in cable reels or in cable rolls and should be sealed safely atboth ends.Cable reels or cable rolls should indicate plate number, cable type, specification,length, gross weight, rolling direction and other considerations.Product quality inspection certificate should go along with each cable delivery. Testreport should be submitted to the interested party through the appropriate way.
Drawing:
Technical data(1core)(parts)
Conductor
Fire-resistant
layer
LSHF Insulation
A M A RESOURCES
93
Section8
Description Unit Proposed Data
Number of coreand cross-section
area
No.*mm2 1C*2.5 1C*4 1C*6 1C*10 1C*16
Manufacturer / Anhui Deyuan Cable Group Co., Ltd.
Type / CU/FR/LSHF
Standards / IEC60502, IEC60754, IEC60331, IEC60332
Rated voltage v Less than 750
Conductor
Material / Concentric-lay-round stranded annealed copper wire
Resistivity at20 ℃
Ω-mm2/m
≤0.017241
Conductivity at20℃
% IACS 100
Number anddiameter of wire
No./mm 1/1.78 1/2.24 1/2.76 7/1.35 7/1.70
Diameter ofconductor
mm 1.78 2.24 2.76 4.05 5.1
Max. DCconductor
resistance at 20℃Ω/km 7.41 4.61 3.08 1.83 1.15
Fire-resistant layer
Gold mica tape layer 2
Insulation
Material / LSHF
Average thickness mm 0.7 0.7 0.7 0.7 0.7
Min. insulationresistance at 90℃
MΩ·km 0.916 0.757 0.645 0.523 0.444
Overall diameter mm 3.98 4.64 5.16 7.45 8.5
Cable weight KG/KM 37.23 54.86 76.07 131.2 191.45
Withstand ACvoltage(5min.)
KV 2.5
A M A RESOURCES
94
Section8
Ⅲ FD/XLPE Insulated LSHF Sheath Copper Cable(4
core)
Specification:■Lighting control and low voltage power system cable■Cable type :CU/FD/XLPE/LSHF 0.6/1KV LSHF 90℃■Multi cores copper conductor XLPE insulated LSHF Sheath.
Scope:■Multi cores with copper conductors, with mica tape wrapped and LSHF insulated.Cables are rated up to 600/1000V in lower voltage power system and conform toIEC60502, IEC60332,IEC60754.■These cables have been designed for sites with big passenger flow such as hospital,subway, school and supermarket, which have special requirements for LSHF andFlame retardant
Operating Characteristics:■Rated voltage: 0.6/1.0kV, maximum operating voltage should be less than 1.2 kV.■Maximum rated temperature of cable conductor is 90℃ during long runningprocess. When a short circuit occurs, cable conductor does not exceed 250 ℃ , withduration less 5 sec.■ Minimum working environment temperature is minus 20 ℃.■Environmental temperature should be above 0 ℃ when installing cable.■Minimum bending radius should be15 times less than cable diameter.
Cable Structure:
Lighttransmittance
% ≥60
pH value >4.3
Halogen content mg/g <5
Standard packing / 100M/C 100M/C 100M/C 100M/C 100M/C
A M A RESOURCES
95
Section8
■ Conductor: Cable conductor is made by T2 copper rods in which pure copperoccupies 99.95%, the surface should be clean, no oil stain, no metal burr or sharpedge which may break insulation and sheath, no bulge or rupture.■ Insulation : Insulation adopts XLPE materials, Average insulation thicknessconforms to IEC60502 and should not be less than nominal value, any measured valueshould not be less than 90% of the nominal value. The eccentricity ratio of any section[(maximum measured thickness - minimum measured thickness) / maximummeasured thickness] should not be more than 10%.■ Filler: Cable should be filled with soft non-absorbent material whose operatingtemperature is in accordance with related cable. Moreover, the material of filler is notallowed to harm insulation.■ Sheath: Cable outer sheath adopts LSHF material whose rated operatingtemperature is in accordance with related cable. Average sheath thickness should notbe less than nominal value and any measured value should not be less than 90% of thenominal value. Out of roundness of cable diameter should not be more than 15%.
Cable identification:The signs on the finished cable should be consistent and legible. It should be easy torecognize and possesses Rub-off resistance. The sheath surface should have thesecontents as follow for each finished cable.■The length should marked every one meter■Manufacturer’s name,■Model number■Voltage grade■ Meters maker
Testing:Cable should pass the testing and inspection which include following detail beforedelivery■ Conductor structure and conductor resistance■Average insulation thickness and thinnest insulation thickness■Insulation resistance and withstand voltage test■Flame retardant test, smoke density test, halogen content test and Fire-resistant test
Packing:These cables are packed in cable reels or in cable rolls and should be sealed safely atboth ends.Cable reels or cable rolls should indicate plate number, cable type, specification,length, gross weight, rolling direction and other considerations.Product quality inspection certificate should go along with each cable delivery. Testreport should be submitted to the interested party through the appropriate way.
A M A RESOURCES
96
Section8
Drawing:
Technical data (4Cores)(parts)
Description Unit Proposed Data
Number of coreand
cross-sectionarea
No.*mm2 4C*6 4C*16 4C*25 4C*35 4C*50 4C*150 4C*240 4C*300
Manufacturer / Anhui Deyuan Cable Group Co., Ltd.
Type / CU/FD/XLPE/LSHF
Standards / IEC60502,IEC60754,IEC60332
Rated voltage V Less than 1000
Conductor
Material / Concentric-lay-round stranded annealed copper wire
Resistivity at20 ℃
Ω-mm2/m
≤0.017241
Conductivity at20℃
% IACS 100
Number anddiameter of wire
No./mm1/2.76
7/1.70 7/2.12 7/2.5210/2.52
24/2.52
37/ 2.52 48/ 2.52
Diameter ofconductor
mm 2.76 5.1 6.36 7.62 9.65 14.48 16.89 19.68
Conductor
Insulation
Filler
Sheath
A M A RESOURCES
97
Section8
Ⅳ FR/XLPE Insulated LSHF Sheath Copper Cable(4
core)
Specification:■0.6/1KV low voltage power system cable■Cable type : CU//MTP/XLPE/LSHF 0.6/1KV LSHF 90℃
Max. DCconductorresistance at
20℃
Ω/km 3.08 1.15 0.727 0.524 0.387 0.153 0.0991 0.0754
Insulation
Material / XLPE
Averagethickness
mm 0.7 0.7 0.9 0.9 1.0 1.2 1.6 1.7
Min. insulationresistance at
90℃MΩ·km 0.645 0.444 0/431 0.379 0.355 0.645 0.444 0.431
Sheath
Material / LSHF
Averagethickness
mm 1.8 1.8 1.8 1.8 1.9 2.5 3.0 3.3
Overalldiameter
mm 17.0 22.0 25.5 28.5 29.5 46.0 57.0 62.0
Cable weight KG/KM 337 778 1160 1554 2148 6300 9700 11800
Withstand ACvoltage(5min.)
KV 3.5
Lighttransmittance
% ≥60
PH value >4.3
Halogen content mg/g <5
Standardpacking
/2000M/R
1500M/R
1500M/R
1000M/R
1000M/R
600M/R
400M/R300M/R
A M A RESOURCES
98
Section8
■Multi cores copper conductor fire-resistant mica tape wrapped XLPE insulatedLSHF Sheath.
Scope:■Multi cores with copper conductors, with mica tape wrapped, XLPE insulated andLSHF Sheath. Cables are rated up to 600/1000V in lower voltage power system andconform to IEC60502, IEC60331 and IEC60332,IEC60754■These cables have been designed for sites with big passenger flow such as hospital,subway, school and supermarket, which have special requirements for LSHF and Fireresistant.
Operating Characteristics:■Rated voltage: 0.6/1.0kV, maximum operating voltage should be less than 1.2 kV.■Maximum rated temperature of cable conductor is 90 ℃ during long runningprocess. When a short circuit occurs, cable conductor does not exceed 250 ℃ , withduration less 5 sec.■ Minimum working environment temperature is minus 20 ℃.■ Environmental temperature should be above 0 ℃ when installing cable.■Minimum bending radius should be 15 times less than cable diameter.
Cable Structure:■Conductor: Cable conductor is made by T2 copper rods in which pure copperoccupies 99.95%, the surface should be clean, no oil stain, no metal burr or sharpedge which may break insulation and sheath, no bulge or rupture.■ Fire-resistant layer is made of gold mica tape with double sides, the coverage rateshould not be less than 25%.■Insulation:Insulation adopts XLPE materials, Average insulation thickness conformsto IEC60502 and should not be less than nominal value, any measured value shouldnot be less than 90% of the nominal value. The eccentricity ratio of any section[(maximum measured thickness - minimum measured thickness) / maximummeasured thickness] should not be more than 10%.■Filler: Cable should be filled with soft non-absorbent material whose operatingtemperature is in accordance with related cable. Moreover, the material of filler is notallowed to harm insulation.■Sheath: Cable outer sheath adopts LSHF material whose rated operating temperatureis in accordance with related cable. Average sheath thickness should not be less thannominal value and any measured value should not be less than 90% of the nominalvalue. Out of roundness of cable diameter should not be more than 15%.Cable identification:The signs on the finished cable should be consistent and legible. It should be easy torecognize and possesses Rub-off resistance. The sheath surface should have thesecontents as follow for each finished cable.■The length should marked every one meter■Manufacturer’s name,
A M A RESOURCES
99
Section8
■ Model number■Voltage grade■Meters maker
Testing:Cable should pass the testing and inspection which include following detail beforedelivery■Conductor structure and conductor resistance■Average insulation thickness and thinnest insulation thickness■Insulation resistance and withstand voltage test■Flame retardant test, smoke density test, halogen content test and fire-resistant test
Packing:These cables are packed in cable reels or in cable rolls and should be sealed safely atboth ends.Cable reels or cable rolls should indicate plate number, cable type, specification,length, gross weight, rolling direction and other considerations.Product quality inspection certificate should go along with each cable delivery. Testreport should be submitted to the interested party through the appropriate way.
Drawing:
Technical data (4Cores)(parts)
Description Unit Proposed
Number ofcore and
cross-sectionarea
No.*mm2 4C*6 4C*10 4C*16 4C*25 4C*35 4C*50 4C*70 4C*120 4C*150
Manufacturer
/ Anhui Deyuan Cable Group Co., Ltd.
ConductorFire-resistantlayerInsulationFillerSheath
A M A RESOURCES
100
Section8
Type / CU/MTP/XLPE/LSHFStandards / IEC60502, IEC60754,IEC60331,IEC60332Ratedvoltage
V Less than 1000
Conductor
Material / Concentric-lay-round stranded annealed copper wire
Resistivity at20 ℃
Ω-mm2
/m≤0.017241
Conductivityat 20℃
%IACS
100
Number anddiameter of
wire
No./mm
1/2.76
7/1.35 7/1.70 7/2.12 7/2.5210/2.52
14/2.52
24/ 2.52 30/ 2.52
Diameter ofconductor
mm 2.76 4.05 5.1 6.36 7.62 9.65 10.65 16.89 19.68
Max. DCconductorresistance at
20℃
Ω/km 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.0991 0.0754
Fire-resistant layer
Gold micatape
layer 2
Insulation
Material / XLPEAveragethickness
mm 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.2 1.4
Min.insulationresistance at
90℃
MΩ·km
0.645 0.523 0.444 0/431 0.379 0.355 0.916 0.645 0.523
Sheath
Material / LSHF
Averagethickness
mm 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.3 2.5
Overalldiameter
mm 18.6 21.5 24.5 28.5 31.3 31.5 34.5 43 47.5
Cable weightKG/KM
345 530 810 1022 1357 1792 1414 5050 6400
WithstandAC
voltage(5min.)
KV 3.5
A M A RESOURCES
101
Section8
Ⅴ THW/LSHF Copper CableSpecification:■Lighting control and low voltage power system cable■Cable type: CU/THW/LSHF 450/750V LSHF 90℃■Single core copper conductor LSHF insulated
Scope:■Single core with copper conductors, with LSHF insulated. Cables are rated up to450/750V in lower voltage power system and conform to IEC60502, IEC60754,IEC60332.■Application: These cables have been designed for buildings and equipments wheretheir internal environment has LSHF requirements.
Operating Characteristics:■Rated voltage: 0.45/0.75 kV, maximum operating voltage should be less than 1.0 kV.■Maximum rated temperature of cable conductor is 90℃ during long running process.When a short circuit occurs, cable conductor does not exceed 250 ℃, with durationless 5 sec.■Minimum working environment temperature is minus 20℃.■The environmental temperature should be above 0℃ when installing cable.■ Minimum bending radius should be10 times less than cable diameter.
Lighttransmittanc
e% ≥60
pH value >4.3Halogencontent
mg/g <5
Standardpacking
/2000M/R
2000M/R
1600M/R
1300M/R
1100M/R
1000M/R
6000M/R
700M/R
6000M/R
A M A RESOURCES
102
Section8
Cable Structure:■Conductor: Cable conductor is made by T2 copper rods in which pure copperoccupies 99.95%, the surface should be clean, no oil stain, no metal burr or sharpedge which may break insulation and sheath, and no bulge or rupture.■Insulation:Insulation adopts LSHF materials, Average insulation thickness conformsto IEC60502 Average insulation thickness should not be less than nominal value, andany measured value should not be less than 90% of the nominal value. Theeccentricity ratio of any section [(maximum measured thickness - minimum measuredthickness) / maximum measured thickness] should not be more than 10%.
Cable identification:The signs on the finished cable should be consistent and legible. It should be easy torecognize and possesses Rub-off resistance. The sheath surface should have thesecontents as follow for each finished cable.■ The length should marked every one meter■ Manufacturer’s name,■Model number■Voltage grade■Meters maker
Testing:Cable should pass the testing and inspection which include following detail beforedelivery■ Conductor structure and conductor resistance■Average insulation thickness and thinnest insulation thickness■Insulation resistance and withstand voltage test■Flame retardant test, smoke density test, halogen content test
Packing:These cables are packed in cable reels or in cable rolls and should be sealed safely atboth ends.Cable reels or cable rolls should indicate plate number, cable type, specification,length, gross weight, rolling direction and other considerations.Product quality inspection certificate should go along with each cable delivery. Testreport should be submitted to the interested party through the appropriate way.
Drawing:
Conductor
LSHF
Insulation
A M A RESOURCES
103
Section8
Technical data (parts)
Description
Unit Proposed Data
Numberof coreand
cross-section area
No.*mm2 1C*2.5 1C*4 1C*6 1C*10 1C*16 1C*25 1C*50 1C*70
Manufacturer
/ Anhui Deyuan Cable Group Co., Ltd.
Type / CU/FD/LSHF
Standards / IEC60502, IEC60754, IEC60332
Ratedvoltage
v Less than 750
Conductor
Material Concentric-lay-round stranded annealed copper wire
Resistivityat 20 ℃
Ω-mm2/m
≤0.017241
Conductivity at20℃
% IACS 100
Numberand
diameterof wire
No./mm 1/1.78 1/2.24 1/2.76 7/1.35 7/1.70 7/2.1210/2.52
14/2.52
Diameterof
conductormm 1.78 2.24 2.76 4.05 5.1 6.36 9.65 10.65
Max. DCconductorresistanceat 20℃
Ω/km 7.41 4.61 3.08 1.83 1.15 0.727 0.387 0.268
Insulation
Material / LSHF
Average mm 0.7 0.7 0.7 0.7 0.7 0.9 1.0 1.1
A M A RESOURCES
104
Section8
thickness
Min.insulationresistanceat 90℃
MΩ-km 0.916 0.757 0.645 0.523 0.444 0/431 0.355 0.916
Overalldiameter
mm 3.18 3.84 4.36 6.05 7.10 8.16 11.65 12.85
Cableweight
KG/KM 27 41 60 100 155 260 510 690
WithstandAC
voltage(5min.)
KV 2.5
Lighttransmitta
nce% ≥60
PH value >4.3
Halogencontent
mg/g <5
Standardpacking
/ 100M/C 100M/C 100M/C 100M/C 100M/C 100M/C100M/C
100M/C
A M A RESOURCES
88
Requirements for cables loading un loading and transportation
A.Unloading cables with a forklift
B.Unloading cables with a crane
C.Unloading cables with sted cable and a gang boaed
D.After loading,steed cable must be used to tie four comers
E.Rou the drum in the arrow direction for at most 5 metres
PACKAGING & SHIPPING