catalog ha 35.11 fixed-mounted circuit-breaker switchgear type 8da and 8da

Upload: bajrica

Post on 24-Feb-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    1/63

    www.siemens.com/medium-voltage-switchgear

    Answers for infrastructure and cities.

    Fixed-Mounted Circuit-Breaker Switchgear

    Type 8DA and 8DB up to 40.5 kV, Gas-InsulatedMedium-Voltage Switchgear Catalog HA 35.11 2014

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    2/63

    R

    -HA35-170.tif

    R-HA35-171.tif

    R-HA35-132.tif

    R-HA35-172.tif

    ApplicationPublic power supplysystem

    Application Industry

    ApplicationOffshore and

    industry

    ApplicationTraction power supply

    R-HA35-174.tif

    R-HA35-173.tif

    2 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    3/63

    3Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Contents

    Application Page

    Versions, typical uses,ratings 4 and 5

    Requirements

    Features, safety, technology 6 and 7

    Technical data

    Electrical data 8 and 9Room planning 10 and 11Shipping data 12Classification 13

    Dimensions

    Front views, sections,floor openings, fixing points 14 to 25

    Product range

    Single-busbar panels 26 and 27Double-busbar panels 28 to 35

    Design

    Basic panel design 36 and 37Gas compartment scheme 38 and 39

    Components

    Vacuum circuit-breaker 40 and 41Three-position disconnector 42 and 43Control board 44Busbar, busbar components 45Current and voltage transformers 46 and 47Panel connection 48 and 49Panel connection (commercially availablecable plugs and bar connections) 50Indicating and measuring equipment 51 to 54

    Protection, control, measuring andmonitoring equipment 55ANSI design 56 to 59

    Standards

    Standards, specifications, guidelines 60 and 61

    First 8DA10 Year of manufacture 1982 62

    Fixed-Mounted Circuit-Breaker Switchgear

    Type 8DA and 8DB up to40.5 kV, Gas-InsulatedMedium-Voltage Switchgear

    Catalog HA 35.11 2014

    Invalid: Catalog HA 35.11 2012

    www.siemens.com/medium-voltage-switchgear

    The products and systems described in this catalogare manufactured and sold according to a certifiedmanagement system (acc. to ISO 9001, ISO 14001and BS OHSAS 18001).

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    4/63

    4 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Versions

    Application

    R-HA

    35-137.eps

    Circuit-breaker panel 8DA10 Circuit-breaker panel 8DB10 Circuit-breaker panel 8DA11/12

    R-HA

    35-136.eps

    R-HA

    35-135.eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    5/63

    5Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Typical uses, ratings

    Application

    Fixed-mounted circuit-breaker switchgear 8DA and 8DB isindoor, factory-assembled, type-tested, single-pole metal-enclosed, metal-clad, SF6-insulated switchgear for single-busbar and double-busbar applications, as well as fortraction power supply systems.

    It is used in transformer and switching substations, e.g., in: Power supply companies Power stations

    Cement industry

    Automobile industry

    Iron and steel works

    Rolling mills

    Mining industry

    Textile, paper and food industries

    Chemical industry

    Petroleum industry

    Pipeline installations

    Offshore installations Electrochemical plants

    Petrochemical plants

    Shipbuilding industry

    Diesel power plants

    Emergency power supply installations

    Lignite open-cast mines

    Traction power supply systems.

    1) 42 kV / 70 kV according to some national requirements2) 95 kV / 185 kV according to some nationa l requirement s

    Electrical data (maximum values) and dimensions

    Single-busbar and double-busbar switchgear

    Rated voltage kV 12 24 36 40.5

    Rated frequency Hz 50 / 60 50 / 60 50 / 60 50 / 60

    Rated short-durationpower-frequency

    withstand voltage kV 28 1) 50 70 85 2)Rated lightning impulsewithstand voltage kV 75 125 170 185

    Rated peakwithstand current kA 100/104 100/104 100/104 100/104

    Rated short-circuitmaking current kA 100/104 100/104 100/104 100/104

    Rated short-timewithstand current 3 s kA 40 40 40 40

    Rated short-circuitbreaking current kA 40 40 40 40

    Rated normal currentof the busbar A 5000 5000 5000 5000

    Rated normal currentof feeders A 2500 2500 2500 2500

    Width mm 600 600 600 600Depth Single busbar mm Double busbar mm

    16252665

    16252665

    16252665

    16252665

    Height Standard mm With high low-voltage

    compartment mm

    2350

    2700

    2350

    2700

    2350

    2700

    2350

    2700

    Single-pole and double-poletraction power supply switchgear

    Rated voltage kV 17.5 27.5

    Rated frequency Hz 16.7 50/60

    Rated short-durationpower-frequencywithstand voltage kV 50 95

    Rated lightning impulsewithstand voltage kV 125 200

    Rated peakwithstand current kA 80 80

    Rated short-circuitmaking current kA 80 80

    Rated short-timewithstand current 3 s kA 31.5 31.5

    Rated short-circuitbreaking current kA 31.5 31.5

    Rated normal currentof the busbar A 3150 3150

    Rated normal currentof feeders A 2500 2500

    Width mm 600 600

    Depth Single-pole traction

    switchgear mm Double-pole traction

    switchgear mm

    865

    1245

    865

    1245

    Height Standard mm With high low-voltage

    compartment mm

    2350

    2700

    2350

    2700

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    6/63

    6 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Requirements

    Environmental independence

    The enclosed high-voltage part of 8DA and 8DB switchgearis suitable for applications under aggressive ambientconditions, such as: Saline air

    Air humidity

    Dust

    Condensation.

    It is tight to ingress of foreign objects, such as: Dust

    Pollution

    Small animals.

    The application is independent of the site altitude.

    Compact design

    Thanks to the use of SF6insulation, compact dimensions arepossible.

    Thus:

    Existing switchgear rooms can be used effectively New constructions cost little

    Costly city-area space is saved.

    Maintenance-free design

    Switchgear housings designed as sealed pressure systems,maintenance-free switching devices and enclosed cableplugs ensure: Maximum supply reliability

    Personnel safety

    Sealed-for-life design according to IEC 62271-200(sealed pressure system)

    Reduced operating costs

    Cost-efficient investment.

    Innovation

    The use of digital secondary systems and combinedprotection and control devices ensures Clear integration in process control systems

    Flexible and highly simplified adaptation to new systemconditions and thus to cost-efficient operation.

    Service life

    Under normal operating conditions, the expected servicelife of gas-insulated switchgear 8DA and 8DB is at least35 years, probably 40 to 50 years, taking the tightness of

    the enclosed high-voltage part into account. The service lifeis limited by the maximum number of operat ing cycles ofthe switching devices installed: For circuit-breakers, according to the endurance class

    defined in IEC 62271-100

    For three-position disconnectors and earthing switches,according to the endurance class defined in IEC 62271-102.

    Personal safety

    Safe-to-touch and hermetically sealed primary enclosure

    All high-voltage parts including the cable terminations,busbars and voltage transformers are metal-enclosed

    Capacitive voltage detecting system to verify safe isolationfrom supply

    Operating mechanisms and auxiliary switches safely acces-sible outside the primary enclosure (switchgear housings)

    Due to the system design, operation is only possible withclosed switchgear enclosure

    Standard degree of protection IP 65 for all high-voltageparts of the primary circuit, IP 3XD for the switchgearenclosure according to IEC 60529

    High resistance to internal arcs by logical mechanicalinterlocks and tested switchgear enclosure

    Panels tested for resistance to internal faults up to 40 kA

    Logical mechanical interlocks prevent maloperation

    Make-proof earthing by means of the vacuum circuit-

    breaker.

    Security of operation

    Hermetically sealed primary enclosure independent ofenvironmental effects (pollution, humidity and smallanimals)

    Maintenance-free in an indoor environment according toIEC 62271-1

    Two-phase and three-phase short-circuits between theprimary conductors are excluded by the single-poleprimary enclosure

    In isolated or compensated systems, low-currentearth-fault currents are self-extinguishing

    Operating mechanisms of switching devices accessibleoutside the primary enclosure (switchgear housings)

    Metal-enclosed, plug-in inductive voltage transformersmounted outside the SF6switchgear housings

    Current transformers as ring-core current transformersmounted outside the SF6switchgear housings

    Complete switchgear interlocking system with logicalmechanical interlocks

    Bolted switchgear housings sealed for life

    Minimum fire load

    Option: Aseismic design.

    Reliability Type and routine-tested

    Standardized, NC production processes

    Quality assurance in accordance with DIN EN ISO 9001

    More than 70,000 switchgear panels of Siemens inoperation worldwide for many years.

    Features Safety

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    7/63

    7Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Technology

    Requirements

    General

    Single-pole enclosure of the primary part by modularswitchgear housings made of corrosion-resistantaluminum alloy

    Insulating gas SF6 Three-position disconnector as busbar disconnector and

    feeder earthing switch

    Make-proof earthing by means of the vacuum circuit-breaker

    Compact dimensions due to SF6insulation

    Hermetically bolted switchgear housings made ofcorrosion-resistant aluminum alloy

    Single-pole metal-enclosed, SF6-insulated busbars

    Cable connection with inside-cone plug-in system, or forconnection of gas-insulated and solid-insulated bars

    Wall-standing or free-standing arrangement

    Installation and extension of existing switchgear at bothends without modification of existing panels.

    Interlocks

    According to IEC 62271-200

    Logical mechanical interlocks prevent maloperation

    Three-position disconnector can only be operated withcircuit-breaker in OPEN position

    Circuit-breaker can only be operated with three-positiondisconnector in end position and operating lever removed

    Locking device for circuit-breaker

    Locking device for three-position disconnector

    Feeder earthed locking device

    Option: Electromagnetic interlocks.

    Modular design

    Replacement of the panel connection housings or thecircuit-breaker possible without interrupting busbaroperation

    Low-voltage compartment removable, plug-in bus wires

    Extension of double-busbar switchgear 8DB10 possiblewithout interrupting operation

    Option: Extension of single-busbar switchgear 8DA10possible without interrupting operation.

    Instrument transformers

    Current transformers not subjected to dielectric stress

    Metal-enclosed, plug-in and disconnectable voltagetransformers.

    Vacuum circuit-breaker

    Maintenance-free under normal ambient conditionsaccording to IEC 62271-1

    No relubrication or readjustment

    Vacuum interrupters sealed for life

    Up to 10,000 operating cycles (maintenance-free)

    Option: Up to 30,000 operating cycles(maintenance required).

    Secondary systems

    Customary protection, measuring and control equipment

    Option: Numerical multifunction protection relay withintegrated protection, control, communication, operatingand monitoring functions

    Can be integrated in process control systems.

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    8/63

    8 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Electrical data, filling pressure, temperature for single-busbar and double-busbar switchgear

    Technical data

    Commonelectricaldata, fillingpressure andtemperature

    Rated insulation level Rated voltage Ur kV 12 24 36 40.5

    Rated short-duration power-frequencywithstand voltage Ud: phase-to-earth, open contact gap kV across the isolating distance kV

    28 1)32 1)

    50 2)602)

    7080

    85 3)90 3)

    Rated lightning impulse withstand voltage Up: phase-to-earth, open contact gap kV

    across the isolating distance kV

    75

    85

    125

    145

    170

    195

    185 4)

    2204)

    Rated frequency fr Hz 50 / 60 50 / 60 50 / 60 50 / 60

    Rated normal current Ir for the busbar9)

    A A A A

    A A

    125020002500315040005000

    125020002500315040005000

    125020002500315040005000

    125020002500315040005000

    Rated filling level pre for the busbar 70 /120 kPa at 20 C

    Minimum functional level pme 50/ 100 kPa at 20 C

    Ambient air temperature 5 C to + 55 C

    Data of the switchgear panels

    Circuit-breakerpanel, discon-

    nector panel6)

    Rated normal current Ir9)

    A

    A

    A A A

    12501600

    200023002500

    12501600

    200023002500

    12501600

    200023002500

    12501600

    200023002500

    Rated short-time withstand current Ik tk= 3 s up to kA 40 40 40 40

    Rated peak withstand current Ip5) up to kA 100/104 100/104 100/104 100/104

    Rated short-circuit making current Ima5)

    up to kA 100/104 100/104 100/104 100/104

    Rated short-circuit breaking current Isc up to kA 40 40 40 40

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 10,000 operating cycles

    at rated short-circuit breaking current 50 breaking operations

    Rated filling level pre for feeders 70/ 120 kPa at 20 C

    Minimum functional level pme 50/ 100 kPa at 20 C

    Bus section-alizer, bus

    coupler7)

    Rated normal current Ir9)

    A A

    A A

    12502000

    23002500

    12502000

    23002500

    12502000

    23002500

    12502000

    23002500

    Rated short-time withstand current Ik tk= 3 s up to kA 40 40 40 40

    Rated peak withstand current Ip5) up to kA 100/104 100/104 100/104 100/104

    Rated short-circuit making current Ima5) up to kA 100/104 100/104 100/104 100/104

    Rated short-circuit breaking current Isc up to kA 40 40 40 40

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 10,000 operating cycles

    at rated short-circuit breaking current 50 breaking operations

    Rated filling level pre for feeders 70/ 120 kPa at 20 C

    Minimum functional level pme 50/ 100 kPa at 20 C

    Cable connec-tion panel,meteringpanel

    Rated normal current Ir8)9) A

    A A A

    1250160020002500

    1250160020002500

    1250160020002500

    1250160020002500

    Rated short-time withstand current Ik tk= 3 s up to kA 40 40 40 40

    Rated peak withstand current Ip5) up to kA 100/104 100/104 100/104 100/104

    Rated filling level pre for feeders 70/ 120 kPa at 20 C

    Minimum functional level pme 50/ 100 kPa at 20 C

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    9/63

    9Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Electrical data, filling pressure, temperature for single-poleand double-pole traction power supply switchgear

    Technical data

    Common electricaldata, fillingpressure andtemperature

    Rated insulation level Rated voltage Ur kV 17.5 27.5

    Nominal voltage according to IEC 60850/EN 50163 kV 15 25

    Rated short-duration power-frequencywithstand voltage Ud: phase-to-earth, open contact gap kV across the isolating distance kV

    5060

    95110

    Rated lightning impulse withstand voltage Up: phase-to-earth, open contact gap kV across the isolating distance kV

    125145

    200220 4)

    Rated frequency fr Hz 16.7 50/60

    Rated normal current Ir for the busbar9) A

    A A A

    1250200025003150

    1250200025003150

    Rated filling level pre for the busbar 70 /120 kPa at 20 C

    Minimum functional level pme 50/ 100 kPa at 20 C

    Ambient air temperature 5 C to +55 C

    Data of the switchgear panels

    Circuit-breakerpanel, disconnec-tor panel

    Rated normal current Ir9) A

    A A A A

    12501600200023002500

    12501600200023002500

    Rated short-time withstand current Ik tk= 3 s up to kA 31.5 31.5

    Rated peak withstand current Ip5) up to kA 80 80/82

    Rated short-circuit making current Ima5) up to kA 80 80/82

    Rated short-circuit breaking current Isc up to kA 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 20,000 operating cycles

    at rated short-circuit breaking current 50 breaking operations

    Rated filling level pre for feeders 70 /120 kPa at 20 C

    Minimum functional level pme 50/ 100 kPa at 20 C

    Bus sectionalizer Rated normal current Ir9) A

    A A

    A

    125020002300

    2500

    125020002300

    2500Rated short-time withstand current Ik tk= 3 s up to kA 31.5 31.5

    Rated peak withstand current Ip5) up to kA 80 80/82

    Rated short-circuit making current Ima5) up to kA 80 80/82

    Rated short-circuit breaking current Isc up to kA 31.5 31.5

    Electrical endurance ofvacuum circuit-breakers

    at rated normal current 20,000 operating cycles

    at rated short-circuit breaking current 50 breaking operations

    Rated filling level pre for feeders 70 /120 kPa at 20 C

    Minimum functional level pme 50/ 100 kPa at 20 C

    Footnotes for pages 8 and 9

    1) Higher values of the rated short-duration power-frequency withstand voltage available with:

    - 42 kV for phase-to-earth and open contact gap, as well as- 48 kV across the isolating distance

    2) Higher values of the rated short-duration power-frequency withstand voltage available with:- 65 kV for phase-to-earth and open contact gap, as well as- 75 kV across the isolating distance

    3) Higher values of the rated short-duration power-frequency withstand voltage available with:- 95 kV for phase-to-earth and open contact gap, as well as- 110 kV across the isolating distance

    4) Higher values of the rated lightning impulse withstand voltage available with:- 190 kV for phase-to-earth and open contact gap, as well as- 230 kV across the isolating distance

    5) Higher value applies to 60 Hz

    6) Disconnector panel available for single-busbar switchgear 8DA10

    7) Bus coupler available for double-busbar switchgear 8DB10

    8) Rated normal current Irfor cable connection panels9) Maximum permissible normal current dependent on ambient air temperature

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    10/63

    10 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Room planning

    Technical data

    Wall-standing arrangement (top view) Free-standing arrangement (top view)

    Room planning for single-busbar switchgear 8DA10

    Room planning for traction power supply switchgear 8DA12

    Room planning for traction power supply switchgear 8DA11

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    11/63

    11Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Switchgear installation

    Wall-standing arrangement without rear wall (IAC FL)

    Free-standing arrangement without rear wall (IAC FL)

    Free-standing arrangement with rear wall (IAC FLR).

    Room dimensions

    See dimension drawings above.Room height: 2900 mm.If there are any busbar components, the minimum roomheight may have to be higher.For switchable busbar components in 8DB10, free-standingarrangement is required.

    Door dimensions

    The door dimensions depend on the dimensions of theindividual panels (see pages 14 to 25).

    Switchgear fixing

    For floor openings and fixing points of the switchgear,see pages 14 to 25

    Foundations: Steel girder construction Steel-reinforced concrete with foundation rails,

    welded or bolted on.

    Panel dimensions

    See pages 14 to 25.

    * Depending on nationalrequirements

    ** Lateral wall distance 500 mm optionally required on the left

    or on the right

    *** Lateral minimum wall distance

    100 mm optionally possibleon the left or on the right

    Room planning

    Technical data

    Wall-standing arrangement (top view) Free-standing arrangement (top view)

    Room planning for double-busbar switchgear 8DB10

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    12/63

    12 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Shipping data

    Technical data

    Transport

    Single-busbar switchgear 8DA10and traction power supplyswitchgear 8DA11/12 is deliveredin transport units comprising upto four panels.

    Double-busbar switchgear8DB10 is delivered in transportunits comprising up to threepanels.Please observe the following: Transport facilities on site

    Transport dimensions andtransport weights

    Size of door openings inbuilding.

    Packing

    Means of transport: Truck

    Panels on pallets Open packing with PE

    protective foil.

    Means of transport: Ship andairplane

    Panels on pallets In closed crates with sealed

    upper and lower PE protectivefoil

    With desiccant bags With sealed wooden base Max. storage time: 6 months.

    Long-time packing Panels on pallets

    In closed crates with sealed,aluminum-coated PEprotective foil

    With desiccant bags With sealed wooden base Max. storage time: 12 months.

    1) Average values with LV compartment 850 mm depending on thedegree to which panels are equipped

    Transport dimensions, transport weights 1)

    Panel widths Transport dimensionsWidth x Height x Depth

    Transport weightwith packing

    Transport weightwithout packing

    mm mm mm mm approx. kg approx. kg

    Single-busbar switchgear 8DA10Means of transport: Truck

    1 600 1764 2550 1870 850 750

    2 600 1764 2550 1870 1700 1500

    3 600 2400 2550 1870 2550 2250

    4 600 2964 2550 1870 3400 3000

    Means of transport: Ship and airplane

    1 600 1764 2700 1888 850 750

    2 600 1764 2700 1888 1700 1500

    3 600 2400 2700 1888 2550 2250

    4 600 2964 2700 1888 3400 3000

    Double-busbar switchgear 8DB10

    Means of transport: Truck

    1 600 1870 2550 3124 1300 1200

    2 600 1870 2550 3124 2600 2400

    3 600 2416 2550 3124 3900 3600

    Means of transport: Ship and airplane

    1 600 1888 2850 3124 1300 1200

    2 600 1888 2850 3124 2600 2400

    3 600 2440 2850 3124 3900 3600

    Traction power supply switchgear 8DA11/12Means of transport: Truck

    1 600 1764 2550 1870 600 500

    2 600 1764 2550 1870 1200 1000

    3 600 2400 2550 1870 1800 1500

    4 600 2964 2550 1870 2400 2000

    Means of transport: Ship and airplane

    1 600 1764 2700 1888 600 500

    2 600 1764 2700 1888 1200 1000

    3 600 2400 2700 1888 1800 1500

    4 600 2964 2700 1888 2400 2000

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    13/63

    13Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Classification

    Technical data

    Classification of 8DA and 8DB switchgear according to IEC 62271-200

    Design and construction

    Partition class PM (metallic partition)

    Loss of service continuity category LSC 2

    Accessibility to compartments

    (enclosure)Busbar compartmentSwitching-device compartmentLow-voltage compartmentCable compartment

    Tool-basedTool-basedTool-basedTool-based

    Internal arc classification

    Designation of the internal arcclassification IACIAC class for:Wall-standing arrangementFree-standing arrangement

    IAC A FL 40 kA, 1 sIAC A FLR 40 kA, 1 s

    Type of accessibility A

    F L R

    Switchgear in closed electrical service location, accessfor authorized personnel only according to IEC 62271-200FrontLateralRear (for free-standing arrangement)

    Rated short-time withstand current 40 kA

    Rated duration of short-circuit 1 s

    Classification of 8DA and 8DB switchgear according to IEEE Std C37.20.7 -2007

    Internal arc classification

    Designation of the internal arcclassification IACIAC class for:Wall-standing arrangementFree-standing arrangement

    Type 1B 40 kA, 0.5 sType 2B 40 kA, 0.5 s

    Type of accessibility

    Type 1B Type 2B

    Switchgear in closed electrical service location,access for authorized personnel only according

    to IEEE Std C37.20.7-2007FrontFront, lateral, rear (for free-standing arrangement)

    Rated short-time withstand current 40 kA

    Rated duration of short-circuit 0.5 s

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    14/63

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    15/63

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    16/63

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    17/63

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    18/63

    18 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    DimensionsFront views, sections, floor openings, fixing points for 8DB10

    Circuit-breaker panel up to 2500 A

    Bus coupler up to 2500 A

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    19/63

    19Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    DimensionsFront views, sections, floor openings, fixing points for 8DB10

    Bus sectionalizer with panel connection up to 2500 A (busbar system 1 and 2)

    Bus sectionalizer up to 2500 A (busbar system 1 and 2)

    Legend and footnotes

    for pages 18 and 19

    1Fixing hole for26 mm x 45 mm

    2 Base frame

    3Floor opening forhigh-voltage cables

    4 Area for floor openings

    for control cables

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    20/63

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    21/63

    Front views, sections, floor openings, fixing points for 8DB10

    21Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Dimensions

    Legend and footnotes

    for pages 20 and 21

    1Fixing hole for26 mm x 45 mm

    2 Base frame

    3Floor opening forhigh-voltage cables

    4 Area for floor openings

    for control cables

    Cable connection panel up to 2500 A

    Bus sectionalizer up to 2500 A (busbar system 1 and 2)

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    22/63

    22 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Dimensions

    Metering panel

    Dummy panel

    Front views, sections, floor openings, fixing points for 8DB10

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    23/63

    23Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Dimensions

    Legend and footnotes

    for pages 22 and 23

    1Fixing hole for26 mm x 45 mm

    2 Base frame

    3Floor opening forhigh-voltage cables

    4 Area for floor openings

    for control cables

    Front views, sections, floor openings, fixing points for 8DB10 ANSI

    Example: Circuit-breaker panel

    with three-position disconnector

    at the feeder (option) up to

    2000 A

    Example: Circuit-breaker panel with

    disconnector bypass up to 2000 A

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    24/63

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    25/63

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    26/63

    26 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Single-busbar panels 8DA10

    Product range

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Plug-in voltagetransformer (directlyplugged or withcable connection)

    Voltage transformerwith or withoutthree-position dis-connector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-positiondisconnector

    Surge arrester

    Panel connectionwith inside-cone plugor bar connection

    Zero-sequencecurrent transformer

    Top-mounted bussectionalizer

    HA35-2679

    eps

    Circuit-breaker panel Disconnector panel

    Bus sectionalizer (2 panels)

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    27/63

    27Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Single-busbar panels 8DA10

    Product range

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Plug-in voltagetransformer (directlyplugged or withcable connection)

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-positiondisconnector

    Panel connectionwith inside-cone plugor bar connection

    HA35-2679

    eps

    Metering panel Cable connection panel

    Bus sectionalizer (2 panels)

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    28/63

    28 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Double-busbar panels 8DB10

    Product range

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Plug-in voltagetransformer (directlyplugged or withcable connection)

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-positiondisconnector

    Surge arrester

    Panel connectionwith inside-cone plugor bar connection

    Zero-sequencecurrent transformer

    Top-mountedbus sectionalizer

    HA35-2679

    eps

    Circuit-breaker panel Bus coupler

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    29/63

    29Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Double-busbar panels 8DB10

    Product range

    Three-positiondisconnector

    Plug-in voltagetransformer(directly plugged)

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-positiondisconnector

    Panel connectionwith inside-cone plugor bar connection

    HA35-2679

    eps

    Cable connection panelMetering panel

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    30/63

    Bus sectionalizer (busbar system 1 and 2)

    30 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Double-busbar panels 8DB10

    Product range

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-position

    disconnector

    Panel connectionwith inside-cone plugor bar connection

    Zero-sequencecurrent transformer

    HA35-2679

    eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    31/63

    Bus sectionalizer (busbar system 1)

    31Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Double-busbar panels 8DB10

    Product range

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-position

    disconnector

    HA35-2679

    eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    32/63

    Bus sectionalizer (busbar system 2)

    32 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Double-busbar panels 8DB10

    Product range

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-position

    disconnector

    HA35-2679

    eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    33/63

    Bus sectionalizer (busbar system 1 and 2)

    33Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Double-busbar panels 8DB10

    Product range

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-position

    disconnector

    HA35-2679

    eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    34/63

    34 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Double-busbar panels 8DB10

    Product range

    Bus sectionalizer (busbar system 1 and 2)

    Three-positiondisconnector

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-positiondisconnector

    HA3

    5-2679

    eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    35/63

    35Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Single-pole and double-pole single-busbar panels 8DA11/12

    Product range

    Single-pole circuit-breaker panel Double-pole circuit-breaker panel

    Three-positiondisconnector

    Vacuumcircuit-breaker

    Plug-in voltagetransformer (directlyplugged or withcable connection)

    Voltage transformerwith or withoutthree-positiondisconnector

    Current transformer

    Capacitive voltagedetecting system

    Busbar earthing switch

    and make-proof

    earthing switch

    Busbar connectionwith or withoutthree-positiondisconnector

    Surge arrester

    Panel connectionwith inside-cone plugor bar connection

    Zero-sequencecurrent transformer

    Top-mountedbus sectionalizer

    HA35-2679

    eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    36/63

    36 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Design

    Insulating system Switchgear housing filled with SF6gas Features of SF6gas: Non-toxic Odorless and colorless Non-inflammable Chemically neutral Heavier than air Electronegative (high-quality

    insulator) Pressure of the SF6gas in the

    switchgear housing dependent onthe electrical ratings (relativepressure at 20 C):

    Rated filling level: 70 kPa to 120 kPa Design pressure: 190 kPa Design temperature of the SF6gas:

    90 C Operating pressure of bursting disc:

    300 kPa

    Bursting pressure: 600 kPa Gas leakage rate: < 0.1 % per year.

    Panel design Factory-assembled, type-tested Single-pole metal-enclosed,

    metal-clad Hermetically bolted switchgear

    housings made of corrosion-resistant aluminum alloy

    Switchpanel poles arranged onebehind the other

    Maintenance-free in an indoor environ-ment (IEC 62271-1)

    Degree of protection

    IP 65 for all high-voltage parts ofthe primary circuit

    IP 3XD for the switchgear enclosure Option: IP 31D for the switchgear

    enclosure Option: IP 41 for the low-voltage

    compartment Vacuum circuit-breaker Three-position disconnector for

    disconnecting and earthing Make-proof earthing by means of

    the vacuum circuit-breaker Cable connection with inside-cone

    plug-in system according to

    EN 50 181 Wall-standing or free-standingarrangement

    Instrument transformers removable,as they are located outside the gascompartments

    Subframe, front cover, rear coverand end walls powder-coated incolor light basic (SN 700)

    Low-voltage compartment remov-able, plug-in bus wires

    Standardized production processesand certified quality and environ-mental management system accord-

    ing to ISO 9001 and ISO 14001.

    Panel design (examples)

    Legend for 8DA10 and

    8DB10

    1Low-voltagecompartment

    2Electronic control board,e.g. multifunctionprotection

    3Operating mechanismand interlock for three-position disconnector,as well as mechanicalposition indicatorsfor three-positiondisconnector andcircuit-breaker

    4Manometer for gasmonitoring of feeder

    gas compartments5Circuit-breaker operating

    mechanism6Voltage detecting system

    8DA10

    Panel for single-busbar switchgear

    8DB10

    Panel for double-busbar switchgear

    Basic panel design

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    37/63

    37Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Single-pole and double-pole design

    for AC traction power supply

    Typical uses

    Single-pole and double-pole panels8DA11/12 for the supply of over-

    head contact line sections in ACtraction power supply systems

    Double-pole panels 8DA12 forapplication in traction power supplysystems with autotransformers, e.g.for high-speed railway traffic.

    Panel design

    Panel design based on standardversion of single-busbar switchgear8DA10.

    8DA11

    Single-pole switchgear panel fortraction power supply.

    8DA12

    Double-pole switchgear panel fortraction power supply.

    Basic panel design

    Design

    Panel design (examples)

    Legend for 8DA11

    and 8DA12

    1Low-voltagecompartment

    2Electronic control board,e.g. multifunctionprotection

    3Operating mechanismand interlock for three-position disconnector,as well as mechanicalposition indicatorsfor three-positiondisconnector andcircuit-breaker

    4Manometer for gasmonitoring of feeder

    gas compartments5Circuit-breaker operating

    mechanism6Voltage detecting system

    8DA11

    Single-pole switchgear panel for traction power supply

    8DA12

    Double-pole switchgear panel for traction power supply

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    38/63

    Gas compartment scheme

    Sealed pressure system (accordingto IEC 62271-1)

    No refilling required throughoutthe entire service life

    Gas compartments distributed toseveral areas

    Gas pressure manometers arrangedat the switchgear front

    Gas pressure can be read with secu-rity even without auxiliary voltagesupply

    SF6gas filling equipment with non-return valve arranged at the switch-gear front beside the associatedgas pressure manometer

    Gas pressure manometers with twosignaling contacts for gas pres-

    sure too low / gas pressure too highindication

    Option: Gas pressure manometerswith three signaling contacts forgas pressure too low / very low andgas pressure too high indication

    Option: Gas pressure manometerswith temperature and pressurecompensation.

    Arrangement of gas compartments in 8DA10

    Single-busbar panel 8DA10

    Single-busbar switchgear 8DA10

    Gas-tight

    bushing

    Bushingpervious to gas

    Legend for 8DA10

    1 Busbar L1 (manometer B11)2 Busbar L2 (manometer B12)3 Busbar L3 (manometer B13)4 Circuit-breaker L1, L2, L3 (manometer B0)5 Top-mounted bus sectionalizer L1, L2, L3

    (manometer B16)

    38 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Gas compartment scheme of 8DA10

    Design

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    39/63

    Double-busbar panel 8DB10

    Double-busbar switchgear 8DB10

    Gas-tight

    bushing

    Bushingpervious to gas

    Arrangement of gas compartments in 8DB10

    Legend for 8DB10

    1 Busbar system 1, L1 (manometer B11)2 Busbar system 1, L2 (manometer B12)3 Busbar system 1, L3 (manometer B13)4 Busbar system 2, L1 (manometer B21)5 Busbar system 2, L2 (manometer B22)6 Busbar system 2, L3 (manometer B23)7 Three-position disconnector, busbar system 1, L1, L2, L3

    (manometer B1)8 Disconnector, busbar system 2, L1, L2, L3 (manometer B2)9 Circuit-breaker L1, L2, L3 (manometer B0)10 Top-mounted bus sectionalizer, busbar system 1, L1, L2, L3

    (manometer B16)11 Top-mounted bus sectionalizer, busbar system 2, L1, L2, L3

    (manometer B26)

    39Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    DesignGas compartment scheme of 8DB10

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    40/63

    40 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Features

    According to IEC 62271-100 (for standards, see page 60)

    Application in hermetically bolted switchgear housings inconformity with the system

    Vacuum interrupter in SF6-filled switchgear housing

    Maintenance-free for indoor installation according toIEC 62271-1

    Individual secondary equipment

    A metal bellows is used for gasketless separation betweenthe SF6insulation and the vacuum (already used withsuccess for over 2 million vacuum interrupters).

    Trip-free mechanism

    The vacuum circuit-breaker is fitted with a trip-freemechanism according to IEC 62271-100.

    Switching duties and operating mechanisms

    The switching duties of the vacuum circuit-breaker aredependent, among other factors, on its type of operating

    mechanism.Motor operating mechanism Motor-operating stored-energy mechanism For auto-reclosing (K) For synchronization and rapid load transfer (U)Further operating mechanism features Located outside the switchgear housings in the operating

    mechanism box and behind the control board

    Stored-energy spring mechanism for 10,000 operating cycles

    Optional:Stored-energy spring mechanism for 30,000 operating cycles.

    Operating mechanism functions

    Motor operating mechanism1)(M1 *)In the case of motor operating mechanism, the closing springis charged by means of a motor and latched in the chargedposition (spring charged indication is visible). Closing iseffected either by means of an ON pushbutton or a closingsolenoid. The closing spring is recharged automatically (forauto-reclosing).

    Endurance class of circuit-breaker

    Function Class Standard Property of 8DA and 8DB

    BREAKING M2 IEC 62271-100 10,000 times mechanically withoutmaintenance

    E2 IEC 62271-100 10,000 times rated normal currentwithout maintenance50 times short-circuit breakingcurrent without maintenance

    C2 IEC 62271-100 Very low probability of restrikes

    Operating times

    Closing time Closing solenoid < 95 ms

    Opening time 1stshunt release2ndshunt releaseUndervoltage release

    < 65 ms< 55 ms< 55 ms

    Arcing time at 50 Hz at 60 Hz

    < 15 ms< 12 ms

    Break time at 50 Hz 1stshunt release2ndshunt releaseUndervoltage release

    < 80 ms< 70 ms< 70 ms

    Dead time 300 msTotal charging time < 15 s

    Vacuum circuit-breaker

    Components

    Circuit-breaker operating mechanism 3AH49for 8DA and 8DB

    1 ON pushbutton2 Auxiliary switch S1

    3 Closing coil for CLOSE 4 Tripping coil for OPEN 5 OFF pushbutton

    6 Operating shaft for circuit-breaker 7 Opening spring 8 Operations counter 9 Position indicator for circuit-breaker10 Closing spring charged / not charged indicator11 Auxiliary switch12 Closing spring13 Gear with hand crank coupling14 Rating plate

    R-HA35

    -138.eps

    14

    12

    10

    11

    7

    8

    9

    132

    1

    34

    5

    6

    Abbreviations for switching duties:U = Synchronization and rapid load transferK = Auto-reclosing

    1) Motor rating at 24 V to 250 V DC: max. 650 W 110 V and 240 V AC: max. 850 VA* Item designation

    For further technical data and description of typicalapplications, please refer also to Catalog HG 11.04

    3AH4 Vacuum Circuit-Breakers

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    41/63

    41Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Vacuum circuit-breaker

    Components

    Secondary equipment

    The scope of the secondary equipment of the vacuumcircuit-breaker depends on the type of application and offersa wide range of possible variations, allowing almost everyrequirement to be satisfied.

    Closing solenoid Type 3AY15 10 (Y9 *)

    For electrical closing.

    Shunt releases

    Types: Standard: 3AY15 10 (Y1 *) Option: 3AX11 01 (Y2 *), with energy store

    Tripping by protection relay or electrical actuation.

    Undervoltage release

    Type 3AX11 03 (Y7 *)

    Comprising:

    Energy store and unlatching mechanism Electromagnetic system, which is permanently connected

    to voltage while the vacuum circuit-breaker is closed;tripping is initiated when this voltage drops

    Connection to voltage transformers possible.

    Anti-pumping

    Function: If constant CLOSE and OPEN commands arepresent at the vacuum circuit-breaker at the same time,the vacuum circuit-breaker will return to the open positionafter closing. It remains in this position until a new CLOSEcommand is given. In this manner, continuous closing andopening (= pumping) is avoided.

    Circuit-breaker tripping signal

    For electrical signaling (as pulse > 10 ms), e.g. to remotecontrol systems, in the case of automatic tripping(e.g. protection)

    Via limit switch (S6 *) and cutout switch (S7 *).

    Varistor module

    To limit overvoltages to approx. 500 V for protectiondevices (when inductive components are mounted in thevacuum circuit-breaker)

    For auxiliary voltages 60 V DC.

    Auxiliary switch Type 3SV9 (S1 *)

    Standard: 12 NO + 12 NC.

    Position switch

    Type 3SE4 (S4 *)

    For signaling closing spring charged.

    Mechanical interlock

    Mechanical interlocking to the three-position disconnector

    During operation of the three-position disconnector,the vacuum circuit-breaker cannot be operated.

    Operating cycle diagram

    Examples

    Electrical data (curve 1)

    Rated short-circuit breaking current 25 kARated normal current 1250 A

    Electrical data (curve 2)

    Rated short-circuit breaking current 31.5 kARated normal current 2000 A

    Rated operating sequences

    Rapid load transfer (U): O-t-CO-t-CO (t = 0.3 s, t = 3 min)Auto-reclosing (K): O-t-CO-t-CO (t = 0.3 s, t = 3 min)

    O = OPEN operationCO = CLOSE operation with subsequent OPEN operation at

    the shortest internal close-open time of the vacuumcircuit-breaker

    Possible release combinations

    Release1 2 3 4

    1st shunt release type type 3AY15 10 2ndshunt release type type 3AY11 01

    Undervoltage release type 3AX11 03

    Abbreviations: NO = normally open contactNC = normally closed contact * Item designation

    Electrical data (curve 3)

    Rated short-circuit breaking current 40 kARated normal current 2500 A

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    42/63

    42 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Features

    Rated normal currents up to 2500 A

    Up to 2000 operating cycles for the disconnector

    Option: Up to 3000 operating cycles for the disconnector

    Up to 1000 operating cycles for the earthing switch

    Option: Up to 2000 operating cycles for the earthing switch Operating shaft and contact blades with common centerof rotation and reliable switch position up to the operatingfront of the panel

    Gas-tight bushings separate the busbar and circuit-breakerhousings underneath the busbar disconnector contacts

    Cable connection and circuit-breaker housings can beremoved without interrupting busbar operation

    Maintenance-free.

    Switch positions

    CLOSED, OPEN, EARTHED or READY-TO-EARTH

    CLOSED: Contact blades connected with the busbar:

    Main circuit closed between busbar and circuit-breaker OPEN: Main circuit open between busbar and circuit-

    breaker: Test voltages for isolating distances are withstood

    READY-TO-EARTH: Contact blades connected with theearthing contact

    EARTHED: Feeder earthed and short-circuited by closingthe circuit-breaker.

    Operating mechanism

    Only permissible operations possible due to logicalmechanical interlocks

    Mechanically coupled position indicator

    Separate operating shafts for the DISCONNECTING,EARTHING and READY-TO-EARTH functions

    With manual operating mechanism

    Option: With motor operating mechanismMotor rating at 24 V to 250 V DC: max. 100 W 110 V to 240 V AC: max. 130 VA

    Same sense of rotation for the switching operations ofthe CLOSE or OPEN functions.

    Position indicators of 8DA10

    for three-position disconnectorand vacuum circuit-breaker

    Feeder OPEN

    Feeder CLOSED

    Feeder READY-TO-EARTH

    Feeder EARTHED

    ComponentsThree-position disconnector

    Endurance class of three-position disconnector

    Function Class Standard Property of 8DA and 8DB

    DISCONNECTING M1 IEC 62271-102 2000 times mechanical lywithout maintenance

    READY-TO-EARTH 1000 times mechanicallywithout maintenance

    EARTHING E2 1) IEC 62271-102 50 times rated short-circuit making current Imawithout maintenance

    Endurance class of make-proof earthing switch

    Function Class Standard Property of 8DA and 8DB

    EARTHING E1 IEC 62271-102 1000 times mechanicallywithout maintenance2 times rated short-circuit making current Imawithout maintenance

    1) By closing the circuit-breaker

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    43/63

    43Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Position indicators of 8DB10

    for three-position disconnectorand vacuum circuit-breaker

    Feeder OPEN

    Feeder busbar system 1 CLOSED

    Feeder busbar system 2 CLOSED

    Feeder READY-TO-EARTH

    Feeder EARTHED

    Three-position disconnector

    Components

    Interlocks

    Selection of permissible switchingoperations by means of a controlgate with mechanically interlockedvacuum circuit-breaker

    Selection of permissible switchingoperations in double-busbarswitchgear additionally by meansof a control gate with mechanicallyinterlocked vacuum circuit-breaker

    Corresponding operating shafts arenot released at the operating frontuntil they have been pre-selectedwith the control gate

    Operating lever cannot be removeduntil switching operation has beencompleted

    Circuit-breaker cannot be closed

    until the control gate is in neutralposition again

    Option: Switchgear interlockingsystem with electromechanicalinterlocks (mechanical interlockingfor manual operation remains).

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    44/63

    44 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Control board

    Components

    Features

    Mechanical control board below thelow-voltage compartment

    Actuations directly at the operatingmechanisms

    Mechanical position indicatorsintegrated in the switchgear front

    Unambiguous assignment ofactuating openings and controlelements to the correspondingposition indicators

    Ergonomic height of all controlelements.

    Interlocking

    Panel-internal mechanical interlocks

    Operation of three-position discon-nector (CLOSED, OPEN, EARTHED or

    READY-TO-EARTH) Vacuum circuit-breaker interlockedmechanically

    Control gate for opening the actuat-ing openings (with single-busbarsystems it can only be operated ifthe interrogation lever (4) is pusheddownwards)

    Actuating openings (2, 3 and 8)cannot be opened as long as thevacuum circuit-breaker is in CLOSEDposition

    Operating lever can be inserted

    when the actuating openings areopen

    Operating lever cannot be removedbefore the definite end positionof the disconnecting or earthingfunction is reached

    Feeder de-earthing is secured by thevacuum circuit-breaker

    electrically via the auxiliary switch mechanically through the lever (14)

    of the mechanical circuit-breakertripping block.

    A Operating mechanism of the three-position disconnector

    1 CLOSED/OPEN position indicator for disconnecting function of three-position disconnector2 Actuating opening for earthing function3 Actuating opening for disconnector function4 Interrogation lever

    5 CLOSED/OPEN position indicator for earthing function of three-position disconnector6 CLOSED/OPEN position indicator for vacuum circuit-breaker7 CLOSED/OPEN position indicator for 2nddisconnector in double-busbar systems8 Actuating opening for 2nddisconnector in double-busbar systems9 Control gate for selecting the three-position disconnector or the disconnector in double-

    busbar systems10 Control gate for opening the actuating openings (with single-busbar systems it can only be

    operated if the interrogation lever (4) is pushed downwards)

    Single-busbar panels 8DA10

    Double-busbar panels 8DB10

    B Operating mechanism of the vacuum circuit-breaker

    11 Mechanical ON pushbutton for vacuum circuit-breaker12 Actuating opening for manual charging of the circuit-breaker operating spring13 Mechanical OFF pushbutton for vacuum circuit-breaker14 Lever for locking the vacuum circuit-breaker against de-earthing15Circuit-breaker spring charged indicator16 CLOSED/OPEN position indicator for vacuum circuit-breaker

    17 Operations counter for vacuum circuit-breaker

    1

    42

    10

    10

    3

    11

    13

    14

    56

    12

    15

    16

    17

    A

    B

    R-HA35-139.eps

    15

    5

    1

    2

    63

    16

    17

    A

    B

    7

    8

    11

    13

    14

    9

    12

    R-HA35-140.eps

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    45/63

    45Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Busbar, busbar components

    Components

    Busbar features

    Single-pole enclosure withmodular switchgear housingsmade of corrosion-resistantaluminum alloy

    Continuous SF6insulation

    without plug-in connectionsor adapters

    No alteration of the insulat-ing medium throughout thecomplete busbar assembly

    Up to 4000 A with copper barconnection in one busbarhousing

    5000 A with copper barconnection in two busbarhousings (twin busbar).

    Design of busbar components

    The busbars of single-busbarswitchgear 8DA and double-busbar switchgear 8DB can beequipped with the followingbusbar components: Plug-in, metal-enclosed

    busbar voltage transformerswith or without three-posi-tion disconnector

    Busbar current transformers

    Busbar connection with cableplug, or with solid-insulated

    or gas-insulated bar connec-tion, with or without three-position disconnector

    Busbar earthing switch ormake-proof earthing switch

    Capacitive voltage detectingsystem according toIEC 61243-5 or IEC 61958

    Top-mounted bus sectional-izer for distribution into twobusbar sections without addi-tional switchgear panels andspace requirements.

    Busbar versions

    Busbar version up to 3150 A

    Example 8DA10Busbar version 4000 A

    Example 8DA10

    Busbar version 5000 A (twin busbar)

    Example 8DA10Busbar version 5000 A (twin busbar)

    Example 8DB10

    Busbar components

    Busbar connection with cable plug size S2

    or size S3Busbar connection with solid-

    insulated or gas-insulated bar

    Top-mounted bus sectionalizer

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    46/63

    46 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Current transformers

    Components

    Features

    According to IEC 61869-2

    Designed as ring-core currenttransformers, single-pole

    Free of dielectrically stressedcast-resin parts (due todesign)

    Insulation class E

    Inductive type

    Certifiable

    Climate-independent

    Secondary connection bymeans of a terminal strip inthe low-voltage compartmentof the panel

    Cast-resin insulated.

    Installation

    Arranged outside theprimary enclosure(switchgear housing).

    Current transformer installation (basic scheme)

    * Further electrical data on request

    Electrical data *

    Designation Type 4MC4

    Operating voltage max. 0.8 kV

    Rated short-duration power-frequency withstand voltage(winding test)

    3 kV

    Rated frequency 50 / 60 Hz

    Rated continuousthermal current

    max. 1.2 rated current(primary)

    Rated thermalshort-time current,max. 3 s

    max. 40 kA

    Rated current dynamic primary

    secondary

    unlimited40 A to2500 A1 A and 5 A

    Designation Type 4MC4

    Multiratio (secondary) 200 A 100 A

    to 2500 A 1250 A

    Core data accordingto rated primary current:Measuring core Rating Class Overcurrent

    factorProtection core Rating Class Overcurrent

    factor

    max. 3 cores

    2.5 VA to 30 VA0.2 to 1FS 5, FS 10

    2.5 VA to 30 VA5 P or 10 P10 to 30

    Permissible ambientair temperature

    max. 60 C

    Insulation class E

    Current transformers

    B Current transformer in bus sectionalizerand bus coupler (type 4MC4_40)

    C1Feeder current transformer(type 4MC4_90)

    C2Feeder current transformer(type 4MC4_40)

    D Feeder current transformer(type 4MC4_10)

    E Busbar current transformer(type 4MC4_40)

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    47/63

    47Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Voltage transformer installation (basic scheme)

    Voltage transformers

    Components

    Features

    According to IEC 61869-3

    Single-pole, plug-in design

    Connection system withplug-in contact accordingto EN 50181

    Inductive type

    Safe-to-touch due to metalenclosure

    Certifiable

    Climate-independent

    Secondary connection bymeans of plugs in the low-voltage compartment of thepanel

    Cast-resin insulated.

    Installation

    Arranged outside theprimary enclosure (switch-gear housing).

    Mounting locations

    On the busbar

    At the panel connectionhousing.

    Voltage transformer types

    Busbar voltage transformers4MT3 and 4MU4 Pluggable on the busbar with

    plug-in system according toEN 50181

    No separate metering panelrequired

    Option: Three-positiondisconnector for busbarvoltage transformer CLOSED OPEN EARTHED

    Option 4MU4: Repeat test at80 % of the rated short-duration power-frequencywithstand voltage possiblewith mounted voltage trans-

    former.

    Feeder voltage transformers4MT7 and 4MU3 Pluggable at the feeder with

    plug-in system according toEN 50181

    Connection of 4MT7 directly atthe panel connection housing

    Connection of 4MU3 viaflexible cable with plug sizeS2 at the panel connectionhousing, and metal-enclosed

    voltage transformer.

    Voltage transformers

    1Busbar voltage transformer 4MT32Feeder voltage transformer 4MT7

    (connection at panel connection

    housing)

    3Busbar voltage transformer 4MU4 with three-position disconnector

    4Feeder voltage transformer 4MU3 (not in the

    panel, connection via flexible cable with plugsize S2 at the panel connection housing, andmetal-enclosed voltage transformer)

    Electrical data (maximum values)

    Designation 4MT3 4MU4 4MT7 4MU3

    Rated voltage kV 24.0 40.5 40.5 40.5

    Rated short-durationpower-frequencywithstand voltage kV

    65 95 95 95

    Rated lightning impulsewithstand voltage kV

    125 200 200 200

    Rated voltage factor Un /8h = 1.9 Un /8h = 1.9 Un /8h = 1.9 Un /8h = 1.9

    Un /continuous= 1.2

    Un /continuous= 1.2

    Un /continuous= 1.2

    Un /continuous= 1.2

    Standard IEC IEC IEC IEC

    GOST GOST GOST GOST

    GB GB GB GB

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    48/63

    48 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2012

    Panel connection

    Components

    Features

    Bushings for plugs withinside-cone plug-in systemaccording to EN 50181

    Inside-cone plug-in system

    for plug sizes 2, 3 and 4 Single and multiple connec-

    tions possible per phase

    Connection of several cableswith different plug sizespossible per phase

    Connection of solid-insulatedor gas-insulated bar possible

    Connection of 4MT7 voltagetransformer plugged in at thepanel connection housingversion 3

    Connection of 4MU3 voltagetransformer via flexible cableand plug size 2 at the panelconnection housing

    For rated normal currents upto 2500 A.

    Surge arresters

    Pluggable via inside-coneplug-in system size 2 or 3

    Surge arresters recommendedif, at the same time,

    the cable system is directly

    connected to the overheadline,

    the protection zone of thesurge arrester at the endtower of the overhead linedoes not cover the switch-gear.

    Version 1

    S2

    1

    Version 2

    S3

    1

    Version 3

    S2 S3 4MT7 Solid-insulated

    barconnection

    1 1

    2

    3

    2

    3

    1 2

    1 1

    2 1 1 1

    2 1

    1 1 1

    1 1

    1 1

    2 1

    Legend

    1 Panel connection housing2 Subframeh Connection height of panel connection versions

    Panel connection of 8DA10, 8DB10 and 8DA11/12 for cable plugs and bar systems

    Switch-geartype

    Ratednormalcurrent

    [A]

    Standardsubframe

    Highsubframe

    Connection height of panel connection versions (mm)

    8DA10

    8DA118DA12

    up to 2300X 320 240 275

    X 540 460 495

    2500X -70 -150 -115

    X 150 70 105

    8DB10 up to 2500X 120 40 75

    X 540 460 495

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    49/63

    49Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2012

    Panel connection

    Components

    Panel connection of 8DA10, 8DB10 and 8DA11/12 for cable plugs and bar systems

    Version 7

    Gas-insulatedbar connection

    1

    Version 4

    S2 S3Solid-insulatedbar connection

    4

    5

    6

    4

    1 3

    1 4

    2 2

    2 3 3 1

    3 2

    4 1

    2 1

    1 1

    2 1

    1 1 1

    Version 5

    S2 S3 S4

    1

    1 1

    2 1

    1 1

    1 1 1

    2

    2 1

    Connection height of panel connection versions (mm)

    222 -15 294 327

    442 205 514 547

    -168 -405 96 -6352 -185 124 157

    22 -215 94 127

    442 205 514 547

    Version 6

    Solid-insulatedbar connection

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    50/63

    50 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Panel connection (commercially available cable plugs and bar connections)

    Components

    Busbar and panel connection (commercially available cable plugs)

    Cable type Cable sealing end Remark

    Make Type Size Diameter acrosscable insulationmm

    Conductorcross-sectionmm2

    Thermoplastic-insulated cables 12 kV according to IEC 60502-2Single-core cable orthree-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    nkt cables CPI 2 2 12.7 - 33.6 25 - 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special toolsCPI 3 3 21.2 - 45.6 185 - 630

    Pfisterer CONNEX 2 13.5 - 44.0 25 - 400 Insulation material silicone rubber,with metal housingCONNEX 3 15.5 - 55.0 35 - 800

    CONNEX 4 33.0 - 78.0 95 - 1600

    Sdkabel SEIK 14 2 13.0 - 40.6 25 - 300 Insulation material silicone rubber,with metal housingSEIK 15 3 19.3 - 50.6 120 - 630

    Tyco Electronics RPIT-321x 2 19.5 - 36.0 95 - 300 Insulation material silicone rubber,with metal housingRPIT-331x 3 26.0 - 50.0 240 - 630

    Thermoplastic-insulated cables 24 kV according to IEC 60502-2

    Single-core cable orthree-core cable,PE and XLPE-insulated,N2YSY (Cu) and

    N2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    nkt cables CPI 2 2 17.0 - 40.0 25 - 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special toolsCPI 3 3 21.2 - 45.6 95 - 630

    Pfisterer CONNEX 2 13.5 - 44.0 25 - 400 Insulation material silicone rubber,

    with metal housingCONNEX 3 15.5 - 55.0 35 - 800CONNEX 4 33.0 - 78.5 95 - 1600

    Sdkabel SEIK 24 2 13.0 - 40.6 25 - 300 Insulation material silicone rubber,with metal housingSEIK 25 3 19.3 - 50.6 50 - 630

    Tyco Electronics RPIT-521x 2 19.5 - 36.0 50 - 300 Insulation material silicone rubber,with metal housingRPIT-531x 3 26.0 - 50.0 150 - 630

    Thermoplastic-insulated cables 40.5 kVaccording to IEC 60502-2

    Single-core cable orthree-core cable,PE and XLPE-insulated,N2YSY (Cu) andN2XSY (Cu)orNA2YSY (Al) andNA2XSY (Al)

    nkt cables CPI 2 2 17.0 - 40.0 25 - 300 Insulation material silicone rubber, with or withoutmetal housing, installation without special toolsCPI 3 3 21.2 - 51.0 50 - 630

    Pfisterer CONNEX 2 13.5 - 44.0 25 - 400 Insulation material silicone rubber,with metal housingCONNEX 3 15.5 - 55.0 35 - 800

    CONNEX 4 33.0 - 78.5 95 - 1600

    Sdkabel SEIK 34 2 13.0 - 40.6 35 - 300 Insulation material silicone rubber,with metal housingSEIK 35 3 19.3 - 50.6 50 - 630

    Tyco Electronics RPIT-621x 2 19.5 - 36.0 50 - 185 Insulation material silicone rubber,with metal housingRPIT-631x 3 26.0 - 50.0 95 - 630

    Busbar and panel connection (commercially available bar systems)

    Bar type Bar connection Remark

    Make Type Conductor material Max. rated current

    Solid-insulated bar MGCMoser Glaser

    Duresca DE Copper, aluminum 2500 A Outer sheath made of polyamide (polyamide tube)

    Duresca DG Copper, aluminum 2500 A Outer sheath made of CrNi steel or aluminum(metal sheath)

    Preissinger ISOBUS MR Copper, aluminum 2500 A Outer sheath made of heat shrinkable tube; insulatedwith cast-resin impregnated paper bandage

    Ritz SIS Copper, aluminum 2500 A Outer sheath made of Raychem heatshrinkable tube

    Gas-insulated bar MGC Moser Glaser Gaslink Copper 2500 A Aluminum housing

    Preissinger ISOBUS MG Copper 2500 A Aluminum housingBusbar and panel connection (commercially available dummy plugs)

    Accessories Dummy plug Remark

    Make Type Size Rated voltage

    Inside-cone plug-insystem accordingto EN 50181

    nkt cables FPI 2 2 40.5 kV Insulation material silicone rubber,with metal housing

    FPI 3 3 40.5 kV

    PfistererBlindstecker

    2 40.5 kV Insulation material silicone rubber,with metal housing

    3 40.5 kV

    4 40.5 kV

    Sdkabel ISIK 14/24/34 2 12 / 24 / 40.5 kV Insulation material silicone rubber,with metal housing

    ISIK 15/25/35 3 12 / 24 / 40.5 kV

    Tyco Electronics RPIC-2 2 40.5 kV Insulation material silicone rubber,with metal housing

    RPIC-3 3 40.5 kV

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    51/63

    51Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Indicating and measuring equipment

    Components

    Symbols shown

    VOIS+, VOIS R+ CAPDIS-S1+ CAPDIS-S2+

    A0 CAPDIS-S2+: Operating voltage

    not present

    A1 Operating voltage present

    A2 Operating voltage not present

    For CAPDIS-S2+: Auxiliary power

    not present

    A3 Failure in phase L1, operating volt-

    age at L2 and L3 (for CAPDIS-Sx+

    also earth-fault indication)

    A4 Voltage (not operating voltage)

    present

    A5 Indication Test passed

    (lights up briefly)

    A6 Indication Test not passed

    (lights up briefly)

    A7 Overvoltage present

    (lights up permanently)

    A8 Indication ERROR, e.g.: in case

    of missing auxiliary voltage

    R-HA40

    -103

    eps

    Plug-in

    voltage

    indicator

    per phase at

    the panel front

    R-HA40-104 eps

    Integrated voltage indicator

    VOIS+, VOIS R+

    Integrated voltage detecting

    system CAPDIS-S1+, -S2+

    Indicators and detecting

    systems

    LRM system

    plugged in

    CAPDIS / VOIS

    installed

    Voltage indication

    via capacitive voltage divider (principle)

    C1 Capacitance integrated into bushing

    C2 Capacitance of the connection leads

    and the voltage indicator to earth

    ULE= UN / 3 during rated operation in the

    three-phase system

    U2 =UA= Voltage at the capacitive interface of

    the switchgear or at the voltage indicator

    R-HA35-154 eps R- HA 35 -155 eps

    A0

    A1

    A2

    A3

    A4

    A5

    A6

    A7

    A8

    Voltage detecting systems accordingto IEC 61243-5, IEC 62271-206 (WEGA ZERO) To verify safe isolation from supply LRM detecting systems with plug-in indicator with integrated indicator, type VOIS+,

    VOIS R+, WEGA ZERO

    with integrated indicator, with integratedrepeat test of the interface, with inte-grated function test, type CAPDIS-S1+,WEGA 1.2, WEGA 1.2 Vario, with inte-grated signaling relay, type CAPDIS-S2+,WEGA 2.2.

    Plug-in voltage indicator

    Verification of safe isolation from supplyphase by phase

    Indicator suitable for continuousoperation

    Measuring system and voltage indicatorcan be tested

    Voltage indicator flashes if high voltage ispresent.

    VOIS+, VOIS R+

    Integrated display, without auxiliarypower

    With indication A1 to A3 (see legend) Maintenance-free, repeat test required With integrated 3-phase LRM test socket

    for phase comparison With integrated signaling relay

    (only VOIS R+) Degree of protection IP54.

    Common features CAPDIS-Sx+

    Maintenance-free Integrated display, without auxiliary

    power Integrated repeat test of the interfaces

    (self-monitoring) With integrated function test (without

    auxiliary power) by pressing theDisplay-Test pushbutton

    Adjustable for different operatingvoltages (adjustable capacitance C2)

    With integrated 3-phase LRM test socketfor phase comparison

    With connectable signal-lead test With overvoltage monitoring and

    signaling (1.2 times operating voltage) Degree of protection IP54.

    CAPDIS-S1+

    Without auxiliary power With indication A1 to A7 (see legend) Without ready-for-service monitoring Without signaling relays (without auxiliary

    contacts).

    CAPDIS-S2+

    With indication A0 to A8 (see legend) Only by pressing the Test pushbutton:

    ERROR indication (A8), e.g. in case ofmissing auxiliary voltage

    With ready-for-service monitoring(auxiliary power required)

    With integrated signaling relay for signals(auxiliary power required).

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    52/63

    52 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    ComponentsIndicating and measuring equipment

    A0 For WEGA 2.2:Operating voltage not present,auxiliary power present, LCDilluminated

    A1 Operating voltage presentFor WEGA 2.2: Auxiliary powerpresent, LCD illuminated

    A2 Operating voltage not presentFor WEGA 2.2: Auxiliary power notpresent, LCD not illuminated

    A3 Failure in phase L1,operating voltage at L2 and L3For WEGA 2.2: Auxiliary powerpresent, LCD illuminated

    A4 Voltage present,current monitoring of couplingsection below limit valueFor WEGA 2.2: Auxiliary powerpresent, LCD illuminated

    A5 Indication Display-Test passedFor WEGA 2.2: Auxiliary powerpresent, LCD illuminated

    A6 For WEGA 2.2: LCD for missingauxiliary voltage is not illuminated

    Symbols shown

    LC display gray: not il luminatedLC display white: illuminated

    Integrated voltage indicator

    WEGA ZERO

    R-HA35-151.ep

    s

    Integrated voltage detecting system

    WEGA 1.2, WEGA 1.2 Vario

    R-HA35-152.aeps

    Integrated voltage detecting system

    WEGA 2.2

    R-HA35-153

    b.eps

    LRM systemplugged in

    WEGAinstalled

    Voltage indication

    via capacitive voltage divider (principle)

    C1 Capacitance integrated into bushing C2 Capacitance of the connection leads

    and the voltage indicator to earthULE= UN/ 3 during rated operation in the

    three-phase systemU2 = UA= Voltage at the capacitive interface of

    the switchgear or at the voltage indicator

    WEGA ZERO WEGA 1.2 WEGA 2.2

    WEGA 1.2 Vario

    WEGA ZERO

    Voltage detecting systemaccording to IEC 62271-206

    With indication A1 to A4(see legend)

    Maintenance-free

    With integrated 3-phase testsocket for phase comparison

    Degree of protection IP54.

    WEGA 1.2, WEGA 1.2 Vario

    Voltage detecting systemaccording to IEC 61243-5

    With indication A1 to A5(see legend)

    Maintenance-free

    Integrated repeat test of theinterface (self-monitoring)

    With integrated function test(without auxiliary power) bypressing the Display Testpushbutton

    With integrated 3-phaseLRM test socket for phasecomparison

    Without integrated signalingrelay

    Without auxiliary power

    Degree of protection IP54

    Adjustable for differentoperating voltages(adjustable capacitance C2)(only for WEGA 1.2 Vario).

    WEGA 2.2

    Voltage detecting systemaccording to IEC 61243-5

    With indication A0 to A6(see legend)

    Maintenance-free

    Integrated repeat test of theinterface (self-monitoring)

    With integrated function test

    (without auxiliary power) bypressing the Display Testpushbutton

    With integrated 3-phaseLRM test socket for phasecomparison

    With integrated signalingrelay (auxiliary powerrequired)

    Degree of protection IP54.

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    53/63

    53Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Indicating and measuring equipment

    Components

    R-HA40-059

    eps

    R-HA35-127.eps

    R-HA40-089.tif

    Phase comparison test units according to IEC 61243-5

    Verification of correctterminal-phase connections

    Verification of correct terminal-phase connections possible bymeans of a phase comparisontest unit (can be ordered

    separately) Safe-to-touch handling of the

    phase comparison test unitby inserting it into the capaci-tive taps (socket pairs) of theswitchgear.

    Phase comparison test unit

    make Kries, type CAP-Phase

    as combined test unit (HR and LRM) for: Voltage detection Repeat test Phase comparison Phase sequence test

    Self-testThe unit does not require a battery

    Phase comparison test unit

    make Horstmann, type ORION 3.1as combined test unit (HR and LRM) for: Phase comparison Interface testing at the switchgear Voltage detection Integrated self-test Indication via LED and acoustic alarm Phase sequence indicator

    R-HA35-127.eps

    Phase comparison test unit

    make Pfisterer, type EPV

    as combined test unit (HR and LRM) for:

    Voltage detection Phase comparison Interface test Integrated self-test Indication via LED

    Phase comparison test unit

    make Hachmann, type VisualPhase LCD

    as combined test unit (HR and LRM) for: Voltage detection with measured-value

    indication

    Interface test Low voltage detection Documentable repeat test Phase comparison with LED signal and

    measured-value indication Phase angle from 180 to +180 Phase sequence evaluation Frequency quality Complete self-test

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    54/63

    54 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Indicating and measuring equipment

    Components

    Ready-for-service indication

    Components Gas pressure manometers

    with two or three signalingcontacts for gas pressure too

    low / very low and gaspressure too high indication

    Simple, visual check of theready-for-service indicator byred/green indication areas

    Indication of gas pressure alsoguaranteed without auxiliaryvoltage supply

    SF6gas filling equipment withnon-return valve and boltedprotective cap arranged atthe switchgear front besidegas pressure manometer

    Option: Gas pressure mano-meters with temperature andpressure compensation.

    Low-voltage compartment

    For accommodation of protec-tion, control, measuring andmetering equipment

    Partitioned safe-to-touchfrom the high-voltage part ofthe panel

    Low-voltage compartment

    can be removed, bus wiresand control cables areplugged in

    Option: Higher low-voltagecompartment (1200 mminstead of 850 mm) possible.

    Gas pressure manometer (1)for circuit-breaker housing(arranged at the panel front)

    Gas monitoring for

    double-busbar switchgear

    8DB10

    Gas pressure manometers (3) forcircuit-breaker and disconnectorhousings (arranged at the panel front)

    Gas pressure manometers (2) forbusbar housings (arranged at thelateral switchgear termination)

    Gas pressure manometers (4) forbusbar housings (arranged at thelateral switchgear termination)

    R-HA35-145.eps

    R-H

    A35-147.eps

    R-HA35-146.eps

    R-HA35-148.eps

    1

    3

    2

    4

    Gas monitoring ofsingle-busbar switchgear8DA10

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    55/63

    55Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    Protection, control, measuring and monitoring equipment

    Components

    Overview of the device types of the SIPROTEC device series: SIPROTEC 5, SIPROTEC Compact and SIPROTEC 4

    SIPROTEC 5

    Overcurrent protection with PMU, control and power quality 7SJ82, 7SJ85

    Distance protection with PMU and control 7SA84, 7SA86, 7SA87

    Line differential protection with PMU and control 7SD84, 7SD86, 7SD87

    Combined line differential and distance protectionwith PMU and control

    7SL86, 7SL87

    Circuit-breaker management device with PMU and control 7VK87

    Overcurrent protection for lines 7SJ86

    Transformer protection with PMU, control, monitoring7UT857UT867UT87

    Motor protection with PMU 7SK82, 7SK85

    Central busbar protection 7SS85

    Bay controllers for control/interlocking tasks with PMU andmonitoring, optionally with protection funktions

    6MD85, 6MD86

    Digital fault recorder 7KE85

    SIPROTEC Compact

    Overcurrent protection 7SJ80, 7SJ81

    Motor protection 7SK80, 7SK81

    Voltage and frequency protection 7RW80

    Line differential protection 7SD80

    Distribution system controller 7SC80

    SIPROTEC 4

    Overcurrent protectionEASY 7SJ45/7SJ467SJ600, 7SJ601, 7SJ602

    7SJ61, 62, 63, 64

    Distance protection7SA522

    7SA6

    Line differential protection7SD600, 7SD610

    7SD52, 53

    Transformer differential protection 7UT612, 613, 63

    Busbar protection7SS60, 7SS522

    7SS52

    Generator and motor protection7UM61, 7UM62, 7VE6

    7UM518

    Accessories for generator and motor protection 7UW50; 7XR, 3PP, 7KG61, 7XT, 4NC

    Rapid changeover device 7VU683

    Bay controllers

    6MD61, 6MD63

    6MD662, 663, 664

    6MB525

    U/f relay 7RW600

    Transient earth-fault relay 7SN600

    Breaker failure protection 7SV600

    Automatic reclosing, synchrocheck 7VK61

    High-impedance protection 7VH60

    Protecting, controlling and monitoring are the basic require-ments placed on a complete bay controller across all tech-nology generations. The properties the user expects frommodern bay controllers are: multifunctionality, reliability,safety and communication capability.The increasing integration of many functions in one multi-

    functional device leads to an optimally supported engineer-

    ing process, IT security, service and testability, or simpleand safe operability of the devices and tools.On the following pages you will find functional descrip-tions for some selected devices. The low-voltage compart-ment can accommodate all customary protection, control,measuring and monitoring equipment available on the

    market:

  • 7/25/2019 Catalog HA 35.11 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DA

    56/63

    56 Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kV, Gas-Insulated Siemens HA 35.11 2014

    ComponentsANSI design

    Basic panel design

    Legend for 8DA10

    1Low-voltage compartment2Electronic control board,

    e.g. multifunction

    protection3Operating mechanism

    and interlock for three-position disconnector,as well as mechanicalposition indicatorsfor three-positiondisconnector and circuit-breaker

    4Manometer for gasmonitoring of feeder gascompartments

    5Circuit-breaker operatingmechanism

    6Voltage detecting system

    7Operating mechanism andinterlock for the three-position disconnector,as well as mechanicalposition indicator forthe three-positiondisconnector at the feeder

    Panel design Factory-assembled, type-tested

    according to IEC 62271 Single-pole metal-enclosed, metal-clad Hermetically bolted switchgear

    housings made of corrosion-resistantaluminum alloy

    Switchpanel poles arranged onebehind the other

    Maintenance-free in an indoorenvironment (IEC 62271-1)

    Cable connection with inside-coneplug-in system according to EN 50181

    Wall-standing or free-standingarrangement

    Subframe, front cover, rear cover andend walls powder-coated in colorlight basic (SN 700)

    Low-voltage compartmentremovable, plug-in bus wires

    Degree of protection IP 65 for all high-voltage parts of

    the primary circuit IP 3XD for the switchgear enclosure Option: IP 31D for the switchgear

    enclosure Option: IP 41 for the low-voltage

    compartment Vacuum circuit-breaker Three-position disconnector for

    disconnecting and earthing by meansof the circuit-breaker

    Make-proof earthing by means ofthe vacuum circuit-breaker

    Option: Three-position disconnector

    for disconnecting and earthing at thefeeder

    For further dimensions and productrange, see pages 14 to 35.

    Insulating system Switchgear housing filled with SF6gas Features of SF6gas: Non-toxic Odorless and colorless Non-inflammable Chemically neutral Heavier than air Electronegative (high-quality insulator) Pressure of the SF

    6

    gas in the switch-gear housing dependent on the electri-cal ratings (relative pressure at 20 C):Rated filling level: 70 kPa to 120 kPaGas leakage rate: < 0.1 % per year.

    Camera system

    Camera system for visual monitoringof the switch positions of the discon-nectors and earthing switches (seealso page 58).

    UL certification For 8DA and 8DB ANSI design options

    there is a UL or cUL certificat