Power Transmission and Distribution Catalog HA 41.11 · 2007 Switchgear Type 8DH10 up to 24 kV, Gas-Insulated, Extendable Medium-Voltage Switchgear

Upload: doandang

Post on 01-May-2018

243 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Power Transmission and Distribution

Catalog HA 41.11 · 2007

Switchgear Type 8DH10up to 24 kV, Gas-Insulated, Extendable

Medium-Voltage Switchgear

Page 2: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

2 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

FeaturesPage

8DH10 switchgear is a factory-assembled, type-tested, three-pole,metal-enclosed, metal-clad single-busbar switchgear for in-door in-stallation:

• Up to 24 kV

• Feeder currents up to 630 A

• Busbar currents up to 1250 A

Typical uses

8DH10 switchgear is used – evenunder severe environmental con-ditions – for power distribution insecondary distribution systems,such as

Substations, customer transfersubstations, distribution sub-stations and switching substa-tions of power supply andpublic utilities

Industrial plants, such as:

• Wind power stations

• High-rise buildings

• Airports

• Lignite open-cast mines

• Underground railway stations

• Sewage treatment plants

• Port facilities

• Traction power supply systems

• Automobile industry

• Petroleum industry

• Chemical industry

• Cement industry

• Unit-type heating power stations

• Textile, paper and foodindustry

• Emergency power supplyinstallations

Modular design

• Individual panels and panelblocks can be freely combinedand extended – without gas workon site

• Low-voltage compartments canbe supplied in two overall heightsand are wired to the panel bymeans of plug-in connections

Reliability

• Type and routine-tested

• Standardized and manufacturedusing numerically controlledmachines

• More than 430,000 8DJ/8DHpanels in operation worldwidefor many years

Quality and environment

Quality and environmentalmanagement system acc. toDIN EN ISO 9001 andDIN EN ISO 14001

Personal safety

• Safe-to-touch and hermeticallysealed primary enclosure

• HV HRC fuses and cable sealingends are only accessible whenoutgoing feeders are earthed

• Operation only possible whenenclosure is closed

• Logical mechanical interlocking

• Capacitive voltage detecting sys-tem to verify safe isolation fromsupply

• Feeder earthing by means ofmake-proof earthing switches

Security of operation

• Hermetically sealed primaryenclosure independent ofenvironmental effects (such aspollution, humidity and small ani-mals) – sealed for life:

– Welded switchgear vessel– Welded-in bushings and operating

mechanism

• Operating mechanism partsmaintenance-free(IEC 60 694 / VDE 0670-1000)

• Operating mechanisms of switch-ing devices located outside theswitchgear vessel (primary enclo-sure)

• Switchgear interlocking systemwith logical mechanical interlocks

• Mechanical switch-positionindicators integrated in themimic diagram

Cost-efficiency

Extremely low “life-cycle costs”throughout the entire productservice life as a result of:

• Maintenance-free concept

• Climatic independence

• Minimum space requirements

• Maximum availability

Security of investment

Innovative developments, such as:

• Modular design

• Switchgear extension without gaswork on site

• Maintenance-free 3AH vacuumcircuit-breaker

• SIPROTEC protection device family

Application, Requirements

Features, typical uses 2 and 3

Technical Data

Electrical data, filling pressure,temperature 4 and 5

Switchgear installation, shipping data 6 and 7

Product Range

Product range overview 8 to 15

Design

Panel design 16 and 17

Components

3AH vacuum circuit-breaker 18 and 19

Three-position switch-disconnector 20

Busbars 21

Transformers 22 to 27

Cable connection 28

Low-voltage equipment 29

Dimensions

Individual panels, panel blocks 30 to 34

Metering panel combinations 33 and 35

Floor openings and fixing points 36 to 39

Cable connection examples 40

Standards, Transport, Notes

Standards, specifications, guidelines 41

Transport data, classification 42

Notes 43

For further information, please refer to

• Catalog HA 40.1: (Switchgear Type 8DJ and 8DH,General Part)

• Supplements to Catalogs HA 45.31/41.11

Invalid: Catalog HA 41.11 · 2006

Application, RequirementsContents

© Siemens AG 2007

The products and systems described in this catalog aremanufactured and sold according to certified qualityand enviromental management system (acc. ISO 9001and ISO 14001).(DQS Certificate Reg. No. DQS 003473 QM UM).The certificate is accepted in all IQNet countries.

Page 3: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 3

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technology

• Maintenance-free

• Climate-independent

• Partition class: Class PM(metallic partition)

• Three-pole primary enclosure,metal-enclosed

• Insulating gas SF6

• Welded switchgear vessel withoutseals, made of stainless steel,with welded-in bushings for elec-trical connections and mechanicalcomponents

• Three-position switch-discon-nector with load-break andmake-proof earthing function

• Cable connection for bushingswith outside cone

• Connection with cable plugs– In ring-main feeders and

circuit-breaker feeders withbolted contact (M16)

– In transformer feeders withplug-in contact

• Option: Connection with conven-tional cable sealing ends

– For thermoplastic-insulatedcables via elbow adapterAKE 20 / 630 (make Siemens)

– For paper-insulated mass-impregnated cables via commer-cially available adapter systems

• Easy installation

• Option: Pressure absorber system– Maintenance-free– For rated short-time withstand

current Ik � 20 kA– For single and multi-panel

combinations of 700 mm to2000 mm width (for panel typeME1 with max. 1 adjacent panel)

– With 300 mm high pressure ab-sorber duct below the switchgearand

– With 115 mm deep pressureabsorber duct for pressure reliefupwards

– With screwed-on cablecompartment cover

– Possible for switchgear with stand-ard cable compartment coverOption: Deeper cable compart-ment cover: 105 or 300 mm

– For overall height of switchgear,see page 6

– Option: Free-standing arrange-ment, for overall height ofswitchgear 2300 mm and withrear cover

For further information concerningthe pressure absorber system,please refer to page 39and to Catalog HA 40.1

Standards

See page 41

ExampleCustomer transfer switchgear

ApplicationCustomer transfer substation in anaccessible switchgear building(transformers, medium-voltage andlow-voltage in a factory-assembledbuilding)

ApplicationPower supply of high-rise buildings

R-H

A4

1-0

15

ep

s

R-H

A4

1-0

14

ep

s

R-H

A4

1-0

13

ae

ps

Application

Typical uses

Page 4: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

4 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical Data

Electrical data

Commonelectrical data

Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24

Rated short-dur. power-freq. withstand voltage Ud:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV

2023

28 1)

32 1)3639

3845

5060

Rated lightning impulse withstand voltage Up:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV

6070

75 1)

85 1)95110

95110

125145

Rated frequency fr 50/60 Hz

Rated normal current Ir2) for busbar (standard) up to A 630 630 630 630 630

for busbar (option) *) A 1250 1250 1250 1250 1250

Filling pressure,temperature,partition classandclassification

Rated filling level pre for insulation 150 kPa (absolute) at 20 °C

Min. functional level pme for insulation 130 kPa (absolute) at 20 °C

Ambient air temperature T 3) Panels without secondary equipment Class “Minus 25 indoor” (-25 to +70 °C 4))

Panels with secondary equipment, Classcircuit-breaker panels

“Minus 5 indoor” (-5 to +55 °C 4))

Partition class Class PM (metallic partition)

Loss of servicecontinuity category 5)

LSC (loss of service continuity) LSC 2

Panel data

Ring-main paneltype RK,bus sectionalizerpanel type LT2,cable paneltype K

Rated normal current Ir2) for feeder (for panel types RK ... and K ...) A 400, 630 400, 630 400, 630 400, 630 400, 630

for bus sectionalizer panel type LT2 A 400, 630 400, 630 400, 630 400, 630 400, 630

Rated short-timewithstand current Ik

for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20

for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20

Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50

Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50

Transformerpanel type TR

Rated normal current Ir2) for feeder 6) A 200 200 200 200 200

Rated short-timewithstand current Ik

for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20

for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20

Rated peak withstand current Ip6) up to kA 50 63 50 63 50 63 50 63 50

Rated short-circuit making current Ima6) up to kA 25 25 25 25 25 25 25 25 25

Reference dimension “e“ of the HV HRC fuse links mm 292 7) 292 442 442 442

Circuit-breakerpanel type LS,bus sectionalizertype LK/LT1

Rated normal current Ir2) for feeder (for panel types LS ...) A 400, 630 400, 630 400, 630 400, 630 400, 630

for bus sectionalizer panel type LT1 A 400, 630 400, 630 400, 630 400, 630 400, 630

Rated short-timewithstand current Ik

for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20

for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20

Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50

Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50

Rated short-circuit breaking current Isc8) up to kA 20 25 20 25 20 25 20 25 20

Electrical service life of3AH vacuum circuit-breakers

at rated normal current 10 000 operating cycles

at rated short-circuit breaking current 50 breaking operations

*) Not for billing meteringpanels type ME1

1) According to some national require-ments, higher values of the ratedshort-duration power-frequencywithstand voltage available forIk = 20 kA with:� 42 kV for phase-to-phase,

phase-to-earth and open contactgap as well as

� 48 kV across the isolating distanceHigher values of the rated lightingimpulse withstand voltage(for IK = 20 kA) :� 95 kV for phase-to-phase,

phase-to-earth and open contactgap as well as

� 110 kV across the isolatingdistance

2) The rated normal currents applyto ambient air temperatures ofmax. 40 °C. The 24-hour meanvalue is max. 35 °C (according toIEC 60 694 / VDE 0670-1000)

3) Operating conditions according toIEC 62 271-200.For application, see also pages2 and 41 (climate and ambientconditions)

4) Temperature range, reducednormal currents at ambient airtemperatures > +40 °C

5) Classification according toIEC 62 271-200 (see also page 42)

6) Depending on the HV HRC fuse link,observe the max. let-throughcurrent of the HV HRC fuse links

7) Extension tube (150 mm long)required additionally for fusemounting 442 mm

8) For the 3AH vacuum circuit-breaker

Page 5: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 5

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Electrical data

*) Not for billing meteringpanels type ME1

1) According to some national require-ments, higher values of the ratedshort-duration power-frequencywithstand voltage available forIk = 20 kA with:� 42 kV for phase-to-phase,

phase-to-earth and open contactgap as well as

� 48 kV across the isolating distanceHigher values of the ratedlighting impulse withstandvoltage (for Ik = 20 kA):� 95 kV for phase-to-phase,

phase-to-earth and open contactgap as well as

� 110 kV across the isolatingdistance

2) The rated normal currents applyto ambient air temperatures ofmax. 40 °C. The 24-hour meanvalue is max. 35 °C (according toIEC 60 694 / VDE 0670-1000)

3) Operating conditions according toIEC 62 271-200.For application, see also pages2 and 41 (climate and ambientconditions)

4) Temperature range, reducednormal currents at ambient airtemperatures > +40 °C

5) Classification according toIEC 62 271-200 (see also page 42)

Commonelectrical data

Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24

Rated short-dur. power-freq. withstand voltage Ud:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV

2023

28 1)

32 1)3639

3845

5060

Rated lightning impulse withstand voltage Up:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV

6070

75 1)

85 1)95110

95110

125145

Rated frequency fr 50/60 Hz

Rated normal current Ir2) for busbar (standard) up to A 630 630 630 630 630

for busbar (option) *) A 1250 1250 1250 1250 1250

Filling pressure,temperature,partition classandclassification

Rated filling level pre for insulation 150 kPa (absolute) at 20 °C

Min. functional level pme for insulation 130 kPa (absolute) at 20 °C

Ambient air temperature T 3) Panels without secondary equipment Class “Minus 25 indoor” (-25 to +70 °C 4))

Panels with secondary equipment, Classcircuit-breaker panels

“Minus 5 indoor” (-5 to +55 °C 4))

Partition class Class PM (metallic partition)

Loss of servicecontinuity category 5)

LSC (loss of service continuity) LSC 2

Panel data

Busbar earthingpaneltype SE,busbar voltagemetering paneltype MS1V/ME3

Rated short-timewithstand current Ik

for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20

for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20

Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50

Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50

Billing meteringpanelstypes ME1and ME2

Rated normal current Ir2) for transfer up to A 630 630 630 630 630

for feeder (T with cable panel as type ME1-K) up to A 630 630 630 630 630

for busbar metering up to A 630 630 630 630 630

Rated short-timewithstand current Ik

for switchgear with tk = 1 s up to kA – 25 20 25 20 25 20 25 20

for switchgear with tk = 3 s up to kA 20 – 20 – 20 – 20 – 20

Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50

Technical Data

Page 6: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

6 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Switchgear installation

Room planning

Switchgear installation

Wall-standing arrangement– Single row– Double row (for face-to-face

arrangement)Option: Free-standingarrangement

For room planning andswitchgear installation, pleasenote:– Floor openings: Dimensions

see pages 36 to 39– Direction of pressure relief

acc. to serial no. 13– Respective pressure relief

rooms

Room dimensions see oppositedimension drawings

Door dimensions

The door dimensions dependon the– Number of panels in a

transport unit– Design with or without

low-voltage compartment

Switchgear fastening

• For floor openings and fixingpoints of the switchgear,see pages 36 to 39

• Foundations:– Steel structure– Steel-reinforced concrete

Panel dimensions see p. 30 to 34

Weight

For details, please refer to page 7.

����

����

��

��������

���������

���

����

�� ���

���

�� ���

�����

���

����

��

��

���

��

��

��

��

Top view Top view

Side view Side view

����

���

����

����

����

���

���

���

������

���

���

����

�����

����

��

��

��

��

��

��

��

��

��

Cable basement

Switchgear room Switchgear room

Technical Data

Switchgear installation withstandard panels

Switchgear installation with rear-sidepressure absorber duct (option)

1 Relief opening

2 Opening (e.g. for ventilationas option)

3 Room height

4 Panel depth of the standardpanel (may be 15 mm deeperfor free-standing arrangement,depending on the panel design)

5 Control aisle �

6 Panel depth of panels withdeep cable compartmentcover

7 Deep cable compartmentcover

8 Standard cable compartmentcover

17 Depth of the pressure absorberduct behind the panel

18 Wall distance

19 End wall

20 Panel width

21 Width of the pressure absorber duct– 700 mm for panel combinations– Approx. 850 mm for metering

panels type ME1

22 Standard:Low-voltage compartmentfor circuit-breaker panels

Option:– Low-voltage compartment

for all other panel types or– Front cover

23 Relief outlet

9 Foundation

10 2nd cable for connection withof double T-plugs in conjunc-tion with larger floor openingand design with deep cablecompartment cover

11 Height of the cablebasement corresponding tothe cable bending radius

12 Cable

13 Direction of pressure relief

14 Floor openings:Dimensions see pages 34 to 37

15 Option:Pressure absorber duct

16 Base height of the pressureabsorber duct beneath thepanel

* Switchgear height for version withpressure absorber duct:– For wall-standing arrangement

W 1950 mm (panel combinationwithout metering panel ME1)W 2300 mm (for combinationwith metering panel ME1)

– For free-standing arrangementW 2300 mm (high end walls, rearwall and front covers, optionallow-voltage compartment)

** Installation conditions for internalarc classification acc. toIEC 62 271-200

*** Height of pressure absorber duct2100 mm with:– Wall-standing arrangement with

metering panel ME1– Free-standing arrangement for all

panel types

B Depending on nationalspecifications:– For extension/panel replacement:

Control aisle W 1000 mmrecommended (for GermanyW 800 mm)

Cable basement

Page 7: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 7

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical Data

Shipping data

Transport units for shipping (top view)

With individual panelor panel block

With combinations of different individualpanels and/or panel blocks(option: Panels bolted together and busbars mounted)

1 T1 = Depth of individualpanel or of panel block

2 Individual panel or panelblock, dimension B1 x T1

3 Transport unit,dimension B2 x T2

4 B3 = Overall width ofcombination of differentindividual panelsor panel blocks

5 B2 = Width of thetransport unit

1) The net weight and the grossweight depend on the extent towhich they are equipped (e.g. withcurrent transformers, motor oper-ating mechanism, deep cablecompartment cover) and aretherefore given as mean value

2) Sum of the net weights of indi-vidual panels and / or panel blocks

* Low-voltage compartment,600 mm high, weight approx.60 kg depending on the paneltype and on the extentto which it is equipped

** The weights depend on theweights of the mountedtransformers

*** Packing weight

Individual panel, panel blockor combinations thereoffor standard switchgear(without pressure relief duct)

TypeShort iden-tification B

current infuture

Panel or panel combination Transport unit (including packing) for standard panels (withoutpressure absorber system)

Width B1mm

Net weight 1)

approx. kgwithout / withLVC */ LVC*

Width B2m

Heightmwithout /withLVC */ LVC*

DepthT2 m

Volumem3

without /withLVC */ LVC*

Gross weight 1)

approx. kgwithout /withLVC */ LVC*

Transport of individual panels

Ring-main panel (standard) RK RK

RK1 RK1

350

500

150 / 210

180 / 240

0.70

0.70

1.60 / 2.20

1.60 / 2.20

1.10

1.10

1.23 / 1.69

1.23 / 1.69

210 / 270

240 / 300

RK2 RK1V 500 200 / 260 0.70 1.60 / 2.20 1.10 1.23 / 1.69 260 / 320

Cable panel (standard) K K 350 145 / 205 0.70 1.60 / 2.20 1.10 1.23 / 1.69 205 / 265

Transformer panel TR TR1 500 180 / 240 0.70 1.60 / 2.20 1.10 1.23 / 1.69 240 / 300

Circuit-breaker panel (standard) LS1 LS1

LS2 LS1V

500

500

– / 260

– / 380

0.70

0.70

– / 2.20

– / 2.20

1.10

1.10

– / 1.69

– / 1.69

– / 320

– / 440

Circuit-breaker panel BB LST1 LST1 500 280 / 340 0.70 1.60 / 2.20 1.10 1.23 / 1.69 320 / 380

Bus sectionalizer panel with circuit-breaker LT1 LK

LT1-V LKV

500

500

– / 280

– / 380

0.70

0.70

– / 2.20

– / 2.20

1.10

1.10

– / 1.69

– / 1.69

– / 340

– / 440

Bus sectionalizer panel with switch-disconnector LT2 LT 500 150 / 210 0.70 1.60 / 2.20 1.10 1.23 / 1.69 210 / 270

Busbar earthing panel

withvoltagetransformer

SE1 SE

SE2 SE1V

350

500

150 / 210

250 / 310

0.70

0.70

1.60 / 2.20

1.60 / 2.20

1.10

1.10

1.23 / 1.69

1.23 / 1.69

210 / 270

310 / 370

Busbar voltage metering panel ME3 MS1V 500 250 / 310 0.70 1.60 / 2.20 1.10 1.23 / 1.69 310 / 370

Billing metering with cast-resinpanels, insulated transformersair-insulated **

with combinedtransformers

ME1 ME1 850 250 / 310 1.08 1.60 / 2.20 1.10 1.90 / 2.61 310 / 370

ME2 ME2 600 390 / 450 1.08 1.60 / 2.20 1.10 1.90 / 2.61 450 / 510

Transport of panel blocks

Ring-main panel block R-B2

R-B3

700

1050

280 / 400

400 / 580

1.08

1.40

1.60 / 2.20

1.60 / 2.20

1.10

1.10

1.90 / 2.61

2.46 / 3.40

340 / 460

470 / 650

Transformer panel block T-B2

T-B3

1000

1500

320 / 440

480 / 660

1.40

2.03

1.60 / 2.20

1.60 / 2.20

1.10

1.10

2.46 / 3.40

3.57 / 4.91

390 / 510

560 / 740

Ring-main/transformer panel block RT-B2

2RT-B3

3RT-B4

700

1050

1400

300 / 420

450 / 630

580 / 820

1.08

1.40

2.03

1.60 / 2.20

1.60 / 2.20

1.60 / 2.20

1.10

1.10

1.10

1.90 / 2.61

2.46 / 3.40

3.57 / 4.91

360 / 480

520 / 700

660 / 900

Cable connection/transformer panel block KT-B2 700 300 / 420 1.08 1.60 / 2.20 1.10 1.90 / 2.61 360 / 480

Transport of combinations of different individual panels or panel blocks

Comprising– a number of individual panels or– 1 panel block or– a number of panel blocks or– individual panels with panel blocks

Overall width B3

� 850 mm

B2

1.08 1.60 / 2.20

T2

1.10 1.90 / 2.61 2) + 60***� 1200 mm 1.40 1.60 / 2.20 1.10 2.46 / 3.39 2) + 70***� 1800 mm 2.03 1.60 / 2.20 1.10 3.57 / 4.91 2) + 85***� 2350 mm 2.53 1.60 / 2.20 1.10 4.49 / 6.17 2) +100***

B Short identifications of the panels have been harmonized

BB Panel type LST1: Please refer to separate Catalog HA 45.31/41.11, Supplements to Catalogs HA 45.31/41.11

Page 8: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

8 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Technical Data

Product range overview

Legend for pages 8 and 9

* Short identifications of the panelshave been harmonized

** LV terminals as an option in the LVcompartment (compartment to beordered as an option)

� Three-position switch asthree-position switch-disconnector(switch-disconnectorCLOSED-OPEN-EARTHED)

BB Three-position switch asthree-position circuit-breaker(disconnecting circuit-breakerCLOSED-OPEN-EARTHED), seeSupplements to CatalogsHA 45.31/41.11-2007

1) The equipment applies to the entirepanel block, but it is located in thefirst feeder panel from the left

2) Low-voltage terminals arranged inthe low-voltage niche of thering-main or cable feeder

Product Range

Short identifications *

current in future

Individual panels

Panel blocks

Designation of theindividual panelsand panel blocks

Panelwidth

Type

Column no.

Ring-main panel 350 RK RK

500 RK1 RK1

500 RK2 RK1V

350 RK-U RK-U

500 RK1-U RK1-U

500 RK2-U RK1V-U

Cable panel without earthing switch 350 K K

350 K-U K-U

Cable panel with make-proof earthing switch 350 K K

350 K-U K-U

Transformer panel 500 TR TR1

500 TR-U TR1-U

Transformer panel with plug-in voltage transformers 500 TR-V TR1-V

500 TR/V TR1/V

Circuit-breaker panel 500 LS1 LS1

500 LS1-U LS1-U

Circuit-breaker panel with plug-in busbar voltage transformers 500 LS2 LS1V

500 LS2-U LS1V-U

Circuit-breaker panel (with disconnecting circuit-breaker) �� 500 LST1 LST1

Bus sectionalizer (with vacuum circuit-breaker) 500 LT1 LK

500 LT1-V LKV

Bus sectionalizer (with switch-disconnector) 500 LT2 LT

Busbar earthing panel 350 SE1 SE

500 SE2 SE1V

Busbar voltage metering panel 500 ME3 MS1V

Billing metering panel 850 ME1 ME1

850 ME1-K ME1-K

Billing metering panel for busbar connection 850 ME1-S ME1-S

cable connection 850 ME1-KS ME1-K

Billing metering panel with combined transformers 600 ME2 ME2

Ring-main panel block 700 R-B2

1050 R-B3

Transformer panel block 1000 T-B2

1500 T-B3

Ring-main/transformer panel block700 RT-B2

RK

T

1050 2RT-B3RK

T

1400 3RT-B4RK

T

Cable connection/transformer panel block(cable panel without make-proof earthing switch) 700 KT-B2

K

T

Cable connection/transformer panel block(cable panel with make-proof earthing switch) 700 KT-B2

K

T

Column no.

Page 9: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 9

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Ausstattungsmerkmale

Switchgear Type 8DH10 up to 24 kV, Gas-Insulated, Extendable

Product Range

Equipment features

Man

ualoper

atin

gm

echan

ismfo

r thre

e-posit

ion

switc

hB

)

Man

ualoper

atin

gm

echan

ismfo

r thre

e-posit

ion

circu

it-bre

aker

BB

)

Inte

rlock

for ca

bleco

mpar

tmen

t cove

r

Cable

com

partm

ent co

ver lo

cked

inpla

ce/sc

rew

edon

C-rail a

s cable

brack

et

Low

-volta

genich

eas

term

inal

com

p. above

the

operat

ing

mec

hanism

box

Low

-volta

gete

rmin

als in

the

operat

ing

mec

hanism

box **

Separ

ate

low

-volta

genich

eas

term

inal

com

partm

ent

Relea

seas

shunt re

leas

efo

r thre

e-posit

ion

switc

hB

) andB

B)

Mec

han. r

eady-

for-s

ervic

e indica

tor (e

.g. f

or switc

hing

device

s)

Signal

ling

switc

h(1

NO) for re

mote

elec

trica

l rea

dy-fo

r-ser

vice

indica

tion

Aux.sw

itch

for t

hree-

positio

nsw

itchB

) andB

B) : S

witc

h-disc

onnecto

r CLO

SED/

OPEN: 2

NO+

2NC, EART

HING

CLOSE

D/OPE

N: 2NO

+2NC; c

ircuit-

break

er

type LS

T CLOSE

D/OPE

N: 2NO

+2NC, E

ARTHIN

GCLO

SED/O

PEN: 2

NO+

2NC

Moto

r-ope

rat.

mec

han. f

. thre

e-po

s.sw

itchB

) and

BB

) (f.CLO

SED

and

OPEN)

Inte

rlock

incir

cuit-

break

erpan

elbet

wee

nth

ree-

positio

nsw

itchB

) and

vacu

umcir

cuit-

break

er

De-ea

rthin

glo

ck-o

ut for m

ake-

proof ea

rthin

gsw

itch

of thre

e-posit

ion

switc

hB

) and

BB

)

Closin

glo

ck-o

ut for th

ree-

positio

nsw

itchB

) and

BB

)

Lock

ing

device

for th

ree-

positio

nsw

itchB

) and

BB

)

Short-

circu

itor ea

rth-fa

ultin

dicato

r

Moto

r operat

ing

mec

hanism

for 3AH

vacu

umcir

cuit-

break

er

Relea

seas

curre

nt-tra

nsform

eroper

ated

rele

ase

Low

-volta

geco

mpar

tmen

t **)

Low

-volta

geco

ver

Mounte

dca

blecla

mps

Seco

ndary

equip

men

t

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

• Basic equipment

° Additional equipment(option), further additionalequipment on request

– Not available

• – • – • • – – – • ° ° ° – – ° ° ° – – ° ° ° °• – • – • • – – – • ° ° ° – – ° ° ° – – ° ° ° °• – • – • • – – – • ° ° ° – – ° ° ° – – ° ° ° °• – • – – • – – – • ° ° ° – – ° ° – – – ° ° – °• – • – – • – – – • ° ° ° – – ° ° – – – ° ° – °• – • – – • – – – • ° ° ° – – ° ° ° – – ° ° – °– – – • • • – – – • ° – – – – – – ° – – ° ° ° °– – – • – • – – – • ° – – – – – – – – – ° ° – °• – • – • • – – – • ° ° – – – – ° ° – – ° ° ° °• – • – – • – – – • ° ° – – – – ° – – – ° ° – °• – • – • – • – ° • ° ° ° – ° – ° – – – ° ° ° °• – • – – – • – ° • ° ° ° – ° – ° – – – ° ° – °• – • – • – • – ° • ° ° ° – ° – ° – – – ° ° ° °• – • – – – • – ° • ° ° ° – ° – ° – – – ° ° – °• – • – • – – – ° • ° ° ° ° – ° ° ° ° ° • – ° °• – • – – – – – ° • ° ° ° ° – ° ° – ° ° • – – °• – • – • – – – ° • ° ° ° ° – ° ° ° ° ° • – ° °• – • – – – – – ° • ° ° ° ° – ° ° – ° ° • – – °– • • – • • • – ° • ° • ° – ° ° ° ° – ° ° ° ° °• – – • – – – – ° • ° ° ° ° – – • – ° ° • – – °• – – • – – – – ° • ° ° ° ° – – • – ° ° • – – °• – – • – • – – – • ° ° ° – – – • – – – ° ° – °• – • – – • – – – • ° ° – – – – • – – – ° ° – °• – • – – • – – – • ° ° – – – – • – – – ° ° – °• – – • – • – – – • ° ° ° – – – ° – – – ° ° – °– – – • – – – • – – – – – – – – – – – – ° ° – °– – – • • – – • – – – – – – – – – – – – ° ° ° °– – – • – – – • – – – – – – – – – – – – ° ° – °– – – • • – – • – – – – – – – – – – – – ° ° ° °– – – • – – – – – – – – – – – – – – – – ° ° – °1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

• – • – • • – – – •1)

°1)

° ° – – – ° ° – – ° ° ° °• – • – • • – – – •1)

°1)

° ° – – – ° ° – – ° ° ° °• – • – • – – – ° •1)

°1)

° ° – ° – ° – – – ° ° ° °• – • – • – – – ° •1)

°1)

° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)

°1)

° ° – – ° ° ° – – ° ° ° °• – • – • 2) – – °

1) 1)

° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)

°1)

° ° – – ° ° ° – – ° ° ° °• – • – • 2) – – °

1) 1)

° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)

°1)

° ° – – ° ° ° – – ° ° ° °• – • – • 2) – – °

1) 1)

° ° – ° – ° – – – ° ° ° °– – – • • • – – – •1)

°1) – – – – – – ° – – ° ° ° °

• – – – • 2) – – ° 1)

1)

° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)

°1) ° – – – – ° ° – – ° ° ° °• – • – • 2) – – °

1) 1)

° ° – ° – ° – – – ° ° ° °

Page 10: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

10 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Ring-main panels

as feeder panels

Cable panels

as feeder panels

Transformer panels

as feeder panels

as transfer panels as transfer panels as transfer panels

����

����

����

�� �

����

����

���

�� �

����

����

����

�� �

����

����

����

�� �

����

����

���

�� �

Type RK-U350 mm wide

for transferto the right

����

����

����

�� �

Type RK *350 mm wide

with plug-insurgearresters *

����

����

����

�� �

��

Type RK *350 mm wide

for 2nd cable*

����

����

����

�� �

Type RK-U350 mm wide

for transferto the left

����

����

����

�� �

��

Type K *350 mm wide

for 2nd cable *

����

����

����

�� �

option

option

option

option

option

option

option

option

Type RK350 mm wide

����

����

����

�� �

Type K350 mm wide

����

����

����

�� �

Type K *350 mm wide

with plug-insurgearresters *

����

����

����

�� �

Type K-U350 mm wide

for transferto the right

����

����

����

�� �

Type K-U350 mm wide

for transferto the left

option

option

option

option

option

option

option

option

����

����

����

�� �

option

option

option

option

option

option

option

Type TR1-V B

500 mm wide

with plug-involtage trans-formers

Type TR1-U500 mm wide

for transferto the left

Type TR1500 mm wide

Type TR-V B

500 mm wide(105 mm deepercable compart-ment cover)

with plug-involtage trans-formers in-stead of cableconnection

Type TR1-U500 mm wide

for transferto the right

Product Range

Type RK1 1) 3)

500 mm wide HV HRC fuse

Capacitivevoltage detectingsystem

Cable (notincluded in thescope of supply)

2nd cable (notincluded in thescope of supply)

Plug-insurge arrester

Make-proofearthing switch

4MT8 plug-in voltagetransformer at thecable connection

Cable-type currenttransformer

��

Three-positionswitch-disconnector

4MT8 plug-in voltagetransformer at theconnection

Ring-main, cable and transformer panels as individual panels

HA

41

-22

78

ee

ps

Option:Type RK1 V 1) 2) 3)

500 mm wide

Option:Type RK1-U3)

Type RK1V-U2) 3)

500 mm wide

Option:Type RK1-U3)

Type RK1V-U2) 3)

500 mm wide

Footnotessee page 11

Page 11: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 11

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Ring-main, cable and transformer panels in panel blocks ��

Ring-main panel blocks

Designs and options for each panel, see page 10

Type R-B2700 mm wide

consisting of2 ring-main panels

RK RK

RK RK

����

����

���

��� Type R-B3

1050 mm wide

consisting of3 ring-main panels

Transformer panel blocks

Designs and options for each panel, see page 10

Type T-B21000 mm wide

consisting of2 transformer panels

TR TR

TR TRType T-B31500 mm wide

consisting of3 transformerpanels

Ring-main/transformer panel blocks

Designs and options for each panel, see page 10

Type RT-B2700 mm wide

consisting of1 ring-main panel and1 transformer panel

RK TR c

RK TR c

����

���

��

���

����

����

����

�� �

Type 2RT-B31050 mm wide

consisting of2 ring-main panels and1 transformer panel

Cable connection/transformer panel block

Designs and options for each panel, see page 10

Designs

• Busbar connection system for connection of individualpanels or panel blocks: Arranged in the left-hand panel of thepanel block (therefore extendable at a later date)

• Only either the left-hand or the right-hand panel of the panel blockcan be designed as a transfer panel with busbar connection

• Panel blocks are also available without a busbar connectionsystem (extendable at a later date only via the cable feeder)

TR

RK

RK RK

����

���

���

���

RK TR c

Type 3RT-B41400 mm wide

consisting of3 ring-main panelsand1 transformerpanel

Type KT-B2700 mm wide

consisting of1 cable connection panel1 transformer panel

K TR c

����

����

����

�� �

c A plug-in voltage transformer cannot be provided at the connection

Three-positionswitch-disconnector

HV HRC fuse

Capacitivevoltage detectingsystem

Cable (notincluded in thescope of supply)

����

����

����

�� �

����

���

���

���

RK

����

���

���

���

Product Range

Designs

• Busbar connection system for connection of individualpanels or panel blocks: Arranged in the left-hand panel of thepanel block (therefore extendable at a later date)

• Only either the left-hand or the right-hand panel of the panel blockcan be designed as a transfer panel with busbar connection

• Panel blocks are also available without a busbar connectionsystem (extendable at a later date only via the cable feeder)

HA

41

-22

78

ee

ps

B Deep cablecompartmentcover required

* Depending onthe make/type ofthe cableplug or arrester:Deep cablecompartmentcover required

** Cable-typecurrent trans-former on the2nd cable:For 300 mmdeeper cablecompartmentcover

1) Suitable forvoltagetransformertype 4MT8

2) Suitable forvoltagetransformertype 4MT3

3) Suitable forthree-phasecurrent trans-formers

Footnotesfrom page 10

BB Capacitive voltagedetecting system atthe busbar of thepanel blocks: Onlylocated once in thefirst panel of theblock!

Page 12: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

12 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

����

����

����

�� �

��

����

����

����

�� �

��

����

����

���

�� �

��

����

����

����

�� �

��

����

����

����

�� �

��

��

����

����

����

���

��

��

����

����

����

�� �

��

��

����

����

����

�� �

��

��

����

����

����

�� �

��

��

��

����

����

����

�� �

��

��

����

����

����

�� �

��

��

��

Circuit-breaker panels as individual panels ��

Circuit-breaker panels

as feeder panels

����

����

���

�� �

��

��

Type LS1500 mm wide

Basic panel

Type LS1 *500 mm wide

for 2nd cable *

Type LS1 *500 mm wide

with plug-insurge arresters orlimiters *

Type LS1 B

500 mm wide

with plug-involtage trans-formers �

as transfer panels

Type LS1-U500 mm wide

for transferto the right

option

option

option

option

option

option

option

option

Type LS1-U500 mm wide

for transferto the left

option

option

option

option

Circuit-breaker panels with plug-inbusbar voltage transformers

as feeder panels

Type LS1V/LS2500 mm wide

Basic panel

Type LS2 *500 mm wide

for 2nd cable *

Type LS1V/LS2 *500 mm wide

with plug-insurge arrestersor limiters *

Type LS1V/LS2 B

500 mm wide

with plug-involtage trans-formers B

as transfer panels

Type LS1V-U/LS2-U500 mm wide

for transferto the right

Type LS1V-U/LS2-U500 mm wide

for transferto the left

option

option

option

option

option

option

option

option option

option

option

option

Three-positionswitch-disconnector

Capacitivevoltage detectingsystem

Cable (notincluded in thescope of supply)

Vacuumcircuit-breaker

Cable-type currenttransformeron the cable

2nd cable (notincluded in thescope of supply)

Plug-insurge arresteror limiter

4MT3 plug-involtagetransformerat the busbar

4MT8 plug-in voltagetransformer at thecable connection

Product Range

HA

41

-22

78

ee

ps

option option option option

option option option option

Footnotessee page 13

4MC63... three-phase currenttransformer

��

��

Page 13: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 13

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

����

����

��

���

����

����

����

�� �

����

����

����

�� �

����

����

���

���

����

����

����

�� �

����

����

����

�� �

Bus sectionalizer with circuit-breaker, bus sectionalizer with switch-disconnector, busbar earthing panels andbusbar voltage metering panel as individual panels ��

option

option

Bus sectionalizerwith circuit-breaker

Type LK/LT1500 mm wide

with vacuumcircuit-breaker

option

option

Type LKV/LT1-V500 mm wide

with vacuumcircuit-breaker andplug-in voltagetransformers

option

option

Type LT2500 mm wide

Busbar earthingpanels

Type SE350 mm wide

Type SE1V/SE2500 mm wide

with plug-involtagetransformers

Busbar voltage meteringpanel

Type MS1V/ME3500 mm wide

Three-positionswitch-disconnector

Vacuumcircuit-breaker

4MT3 plug-involtagetransformerat the busbar

Cable-typecurrent trans-former on thescreened busbar

Make-proofearthing switch

Capacitivevoltage detec-ting system

4MT8 plug-involtagetransformerat the connection

Product Range

HA

41

-22

78

ee

ps

B Deep cablecompartmentcover required

BB Short identi-fications of thepanels havebeen harmo-nized

* Depending onthe make/type ofthe cableplug or arrester:Deep cablecompartmentcover required

** Cable-typecurrent trans-former on the2nd cable:For 300 mmdeeper cablecompartment

Footnotes frompage 12 and 13

Bus sectionalizerwith switch-disconnector

Page 14: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

14 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable��

����

����

����

��

��

��

option

Type ME1, 850 mm wide

for transfer to the right,transformer terminalsinterchanged

Billing metering panels(standard)

Billing metering panels as endpanels, for cable connection

Billing metering panels forbusbar connection

Cable (notincluded in thescope of supply)

Voltage trans-former, cast-resininsulated

Fixed earthingpoints for busbarearthing

Current trans-former, cast-resininsulated

Type ME1, 850 mm wide

for transfer to the right

����

����

����

�� �

��

�� ��

option

Type ME1-K, 850 mm wide

for transfer to the right

����

���

����

�� �

��

��

option

Type ME1-S, 850 mm wide

for busbar metering

����

���

����

�� �

��

��

��

option

Type ME1, 850 mm wide

for transfer to the right

Type ME1, 850 mm wide

for transfer to the right,transformer terminalsinterchanged

����

���

����

�� �

��

�� ��

option

Type ME1-K, 850 mm wide

for transfer to the right,transformer terminalsinterchanged

����

���

����

�� �

��

��

option

Type ME1-K, 850 mm wide

for transfer to the right

����

���

����

�� �

��

��

option

Type ME1-K, 850 mm wide

for transfer to the right,transformer terminalsinterchanged

����

���

����

�� �

��

��

option

Type ME1-S, 850 mm wide

for busbar metering,transformer terminalsinterchanged

����

���

����

�� �

����option

����

���

���

�� �

����option

Air-insulated metering panels as transfer panels

����

����

���

�� �

����

����

����

����

�� �

����

Type ME1-S, 850 mm wide

for busbar metering,transformer terminalsinterchanged

Type ME1-S, 850 mm wide

for busbar metering,transformer terminalsinterchanged

Scheme 1 Scheme 1 Scheme 1

Scheme 2Scheme 2Scheme 2

Scheme 3Scheme 3Scheme 3

Scheme 4Scheme 4Scheme 4

Note

Schemes 1 to 4 also feasiblefor transfer to the left

Note

Schemes 1 to 4 also feasiblefor transfer to the left

option

option

Voltage transformer,cast-resin insulatedor on request:

Voltage transformer,cast-resin insulated,with HV HRC fuse

P1 and P2are terminaldesignationsof the currenttransformer

Product Range

HA

41

-22

78

de

ps

1)

Page 15: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 15

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable��

����

���

����

��

��

��

Air-insulated metering panels as transfer panels

Billing metering panels as endpanels, for cable connection

Billing metering panelsas individual panels, for cableconnection

Type ME1-KS, 850 mm wide

for transfer to the right

option

Type ME1-KK, 850 mm wide

for cable connection

����

���

����

�� �

��

��

��

option

Type ME1-KS, 850 mm wide

for transfer to the right

����

����

����

�� �

��

��

��

option

Type ME1-KS, 850 mm wide

for transfer to the right,transformer terminalsinterchanged

����

����

����

�� �

��

��

��

option

Type ME1-KK, 850 mm wide

for cable connection,transformer terminalsinterchanged Cable (not

included in thescope of supply)

Fixed earthingpoints for busbarearthing

Current trans-former, cast-resininsulated

4MK plug-incombined voltagetransformer,metal-enclosed

Type ME1-KS, 850 mm wide

for transfer to the right,transformer terminalsinterchanged

4MK plug-incombined currenttransformer,metal-enclosed

Note

Schemes 1 to 4 also feasibleas left-hand end panelfor transfer to the left

Scheme 1

Scheme 2

Scheme 3

Scheme 4

Voltage transformer,cast-resin insulatedor on request:

Voltage transformer,cast-resin insulated,with HV HRC fuses

Type ME1-KK, 850 mm wide

for cable connection

Type ME1-KK, 850 mm wide

for cable connection,transformer terminalsinterchanged

P1 and P2are terminaldesignationsof the currenttransformer

Product Range

����

����

���

���

��

��

����

����

����

���

��� ����

��

��

����

���

���

���

����

��

��

����

���

���

���

����

��

��

����

����

����

���

��

��

����

����

����

��

��

��

����

����

����

��

��

��

����

����

���

��

��

��

Type ME2, 600 mm wide

for transfer to the right

Type ME2, 600 mm wide

for transfer to the right,transformer terminalsinterchanged

Type ME2, 600 mm wide

for transfer to the left

Type ME2, 600 mm wide

for transfer to the left,transformer terminalsinterchanged

* Mainly for connection tobus sectionalizer with switch-disconnectorLT1, LT1-V and LT2

option

option

option

option

Billing metering panels *with metal-enclosedcombined transformers

Scheme 1

Scheme 2

Scheme 3

Scheme 4

Scheme 1

Scheme 2

Scheme 3

Scheme 4

HA

41

-22

78

ee

ps

1)

��

Page 16: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

16 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Panel design (examples)

����

����

����

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

Ring-main panel Section Transformer panel Section

Billing metering panel, air-insulated Section

����

����

����

�����

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

����

����

����

��

��

��

��

��

��

��

��

��

��

Type RK Type TR

Type ME1

Design

Legend for pages 16 and 17

1 Option: Low-voltage compartment

2 Niche for customer-side low-voltage equipment,with hinged cover

3 Switch-position indicator for load-breakfunction “CLOSED – OPEN”

4 Switch-position indicator for earthingfunction “OPEN – EARTHED”

5 Ready-for-service indicator

6 Rating and type plate

7 Mimic diagram

8 Option: Short-circuit / earth-fault indicator

9 Sockets for voltage detecting system

10 Arrangement of the busbars

11 Feeder designation label

12 Option: Locking device for three-positionswitch-disconnector

13 Manual operation for the mechanism ofthe earthing function

14 Manual operation for the mechanism ofthe load-break function

15 Interlock of the cable compartment cover

16 Arrangement of the cable connections

17 Busbar system

18 Switchgear vessel filled with gas

19 Busbar connection

20 Pressure relief device

Page 17: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Siemens HA 41.11 · 2007 17

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Panel design (examples)

Circuit-breaker panel Section

����

����

����

����

��� ����

��

��

��

��

��

��

��

��

��

��

��

��

���������

��

��

��

��

��

��

��

��

��

��

��

��

��

Type LS1 (without voltage transformers)

����

����

����

��

��

��

��

��

��

Type LS2-V (with voltage transformers)

Design

21 Partition for busbar

22 Earthing busbar with earthing connection

23 Three-position switch-disconnector

24 Spring-operated mechanism

25 Bushing for cable plug with bolted contact (M16)

26 Option: Cable T-plug

27 Cable compartment cover

28 Cable compartment

29 Cable bracket

30 Earthing connection for earthing accessories

31 HV HRC fuse assembly, cover removed

32 Handle for replacing HV HRC fuse links

33 Interlock for HV HRC fuse assembly

34 Cover of the HV HRC fuse compartment

35 Spring-operated / stored-energy mechanism

36 Bushing for cable plug with plug-in contact

37 Cable elbow plug with plug-in contact

38 Switch-position indicator for load-break function“CLOSED – OPEN” and, if applicable,“HV HRC fuse tripped” or “shunt release tripped”

39 Cover for access to the busbar connection and tothe instrument transformers, screwed on

40 4MR voltage transformer

41 4MA7 current transformer

42 Cover to busbar connectioncompartment, screwed on

43 Option: SIPROTEC bay control unit

44 Low-voltage compartment (standard)

Vacuum circuit-breaker:

45 Opening for the hand crank– for closing with manual operating mechanism– for emergency operation with motor operating

mechanism

46 Operating mechanism box

47 Mechanical “ON” pushbutton (not supplied withspring-operated mechanism)

48 Mechanical “OFF” pushbutton

49 Operating cycle counter

50 “Spring charged” indicator

51 Vacuum interrupter

52 Switch-position indicator

53 Option: Interlock between vacuum circuit-breakerand three-position switch-disconnector

54 Option: Three-phase current transformer(protection transformer)

55 Cable-type current transformer

56 4MT3 plug-in voltage transformer at the busbar

57 Bushing for connection of plug-in voltage transformers

58 Plug-in connection according to EN 50181 /DIN EN 50181 as interface type “A”

59 Option: 4MT8 plug-in voltage transformer at the connection

60 Deep cable compartment cover

61 Wiring duct, removable, for control cables and/or bus wires

62 Cover screwed on

63 Option: Interlock between three-positionswitch-disconnector and circuit-breaker

Page 18: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

18 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Features

• According to IEC 62 271/VDE 0671-100(standards see page 41)

• Application of all 8DH10switchgear in hermeticallysealed vessel in conformitywith the system

• Climate-independent vacuuminterrupter poles in thegas-filled switchgear vessel

• Maintenance-free for indoorinstallation according toIEC 60 694/ VDE 0670-1000(standards see page 41)

• Individual secondary equipment

• A metal bellows is used forgasketless separation of theSF6-insulation and the operat-ing mechanism – as alreadyused with success for over100000 vacuum interrupters

Switching duties andoperating mechanisms

The switching duties of thevacuum circuit-breaker are de-pendent, among other factors, onits type of operating mechanism.Three operating mechanism ver-sions are available:

• Motor operating stored-energymechanism

– For auto-reclosing (K),– For synchronization and

rapid load transfer (U)

• Manual operating stored-energy mechanism

– For auto-reclosing (K)

• Manual spring-operated me-chanism (= spring CLOSED,stored-energy OPEN)

– Not for auto-reclosing (K)– For normal closing and– For storage of one opening

operation

Further operating mechanismfeatures

• Located outside the switch-gear vessel in the operatingmechanism box and behindthe control board

• Stored-energy springmechanism for 10000operating cycles

3AH vacuum circuit-breaker

Operating mechanismfunctions

Motor operating mechanism 1)

(M1 *)

In the case of the motor oper-ating mechanism, the closingspring is charged by means ofa motor and latched in thecharged position (the “springcharged” indication is visible).Closing is effected either bymeans of an ON pushbutton ora closing solenoid. The closingspring is recharged automati-cally (for auto-reclosing).

Manual operating stored-energy mechanism

The closing spring is chargedby means of the hand crank sup-plied until latching of the closinglatch is indicated(= “spring charged” indication).

Subsequently the vacuumcircuit-breaker can be closedeither manually or electricallyand the closing spring can berecharged manually. The “possi-bility to close” is thus storedonce more (for auto-reclosing).

Manual spring-operatedmechanism(= spring CLOSED, stored-energyOPEN)

The closing spring of the vacuumcircuit-breaker is charged bymeans of the hand crank sup-plied until the vacuum circuit-breaker closes. Subsequentlyeither manual or electrical open-ing is possible.

Vacuum circuit-breakers withspring-operated mechanism arenot suitable for auto-reclosing.

Trip-free mechanism

The vacuum circuit-breakeris fitted with a trip-freemechanism.

1) Motor rating at24 V to 220 V DC: 350 W110 V and 230 V AC:400 VA

2) With closing solenoid

* Item designation

For further technical data and description of typical applications,please refer also to Catalog HG 11.11 “3AH Vacuum Circuit-Breakers”

Components

CO = CLOSE operation with subsequentOPEN operation at the shortestinternal close-open time of thevacuum circuit-breaker

t = Dead time 0.3 s

t ‘ = Dead time 3 min

Abbreviations for switchingduties and applications:

U = Synchronization andrapid load transfer(make time � 90 ms)

K = Auto-reclosing

O = OPEN operation

Differentiation features between the vacuum circuit-breakersdepending on the operating mechanism version

Operatingmechanismversion

Motor operatingstored-energymechanism

Manualoperatingstored-energymechanism

Manual spring-operatedmechanism

Typical uses Utilitysubstationsand industrialplants

Classic transfersubstations andsubstationswithout auxiliaryvoltage supply

Simple utilitysubstations(circuit-breakeremployed astransformerswitch)

Mechanismfunction

Stored-energyCLOSED,stored-energyOPEN

Stored-energyCLOSED,stored-energyOPEN

SpringCLOSED,stored-energyOPEN

Mechanismoperation

With motor 1),manual (emer-gency) opera-tion at the panelincluding anti-pumping

With handcrank

With handcrank

Closing thevacuumcircuit-breaker

Electrically 2) ormechanically atthe panel withpushbutton

Mechanicallyat the panelwith push-button, option:electrically 2)

Mechanicallyat the panelwith handcrank (chargingprocess)

Closingsolenoid, e.g.for remoteelectricalclosing

Always provid-ed, with elec-trical signal“closing springcharged”

Option Without

Ratedoperatingsequence

O-t-COorO-t-CO-t’-CO

O-t-CO O or CO

Auto-reclosing (K)

Suitable (multi-ple auto-reclos-ing possible)

Suitable (onlywith closingsolenoid)

R-H

A4

1-0

16

ep

s

1

2

3

4

5

7

10

6

8

11

13

15

Operating mechanism of the vacuum circuit-breaker(for the legend, see page 19)

Page 19: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 19

Secondary equipment of the 3AH vacuum circuit-breaker

Circuit-breaker tripping signal(standard)

• For electrical signalling (as pulse> 10 ms), e.g. to remote controlsystems, in the case of automatictripping (e.g. protection)

• Via limit switch (S6 *) andcut-out switch (S7 *)

Varistor module

• To limit overvoltages to approx.500 V for protection devices(when inductive devices aremounted in the vacuum circuit-breaker)

• For auxiliary voltages W 60 V DC

Auxiliary switch

• Type 3SV9 (S1 *)

• Standard: 6 NO+6 NC, of which2 NO+2 NC+2 changeovercontacts are free 1)

• Option: 12 NO+12 NC, of which7 NO+4 NC+2 changeovercontacts are free 1)

Position switch

• Type 3SE4 (S4 *)

• For signalling “closing springcharged”

• Only in conjunction with stored-energy mechanisms

Mechanical interlocking

• Dependent on the type ofoperating mechanism

• Option: Switchgear interlockingwith the three-position switch-disconnector (option: Closinglock-out for the three-positionswitch-disconnector in circuit-breaker panels type LS and LT1)

• Option: Operating mechanismwith mechanical interlocking as

– Spring-operated mechanism:Hand crank opening is blocked

– Stored-energy mechanism withclosing solenoid (Y9 *) andpushbutton (S12 *): The push-button (S12 *) operated by themechanical interlock prevents acontinuous command to theclosing solenoid

• During operation of the three-position switch-disconnectorfrom CLOSED to OPEN:Vacuum circuit-breakercannot be closed.

����

����

�����

��

��

��

����

����

�����

��

��

��

��

��

��

The scope of the 3AH vacuumcircuit-breaker secondary equip-ment depends on the type of appli-cation and offers a wide range ofoptions, thus allowing even thehighest requirements to be satis-fied.

Closing solenoid

• Type 3AY15 10 (Y9 *)

• For electrical closing

Shunt releases

• Types:– Standard: 3AY15 10 (Y1 *)– Option: 3AX11 01 (Y2 *),

with energy store

• Tripping by protection device orelectrical operation

Current-transformeroperated release

• Type 3AX11 04 (Y6 *) for trip-ping pulse W 0.1 Ws in con-junction with suitable protec-tion systems, e.g. 7SJ4 protec-tion system, 4MC6.. transformerprotection system, SEG relay(other designs on request)

• Used where no externalauxiliary voltage is available,tripping by protection device

Undervoltage release

• Type 3AX11 03 (Y7 *)

• Comprising:– Energy store and unlatching

mechanism– Electromagnetic system which is

permanently connected to voltagewhile the vacuum circuit-breakeris closed; tripping is initiatedwhen this voltage drops

• Connection to voltage trans-formers possible

Anti-pumping (standard)(mechanical and electrical)

• Function: If constant CLOSE andOPEN commands are present atthe vacuum circuit-breaker atthe same time, the vacuum cir-cuit-breaker will return to theopen position after closing. Itremains in this position until anew CLOSE command is given.In this manner, continuous clos-ing and opening (= pumping) isavoided.

Basic equipment with manual spring-operated mechanism

Maximum equipment with motor operating stored-energy mechanism

Secondary equipment (view into the operating mechanism box)

1 Gear

2 Position switch (S4 *)

3 Closing spring

4 Motor (M1 *)

5 Operating cycle counter

6 “Closing spring charged” indicator

7 Closing solenoid (Y9 *)

8 Option: Auxiliary switch12 NO+12 NC

9 Auxiliary switch6 NO+6 NC (S1 *)

10 Circuit-breaker “CLOSED”

11 Circuit-breaker “OPEN”

12 Option: 2nd release

13 1st release (Y1 *)

14 Option: Mechanical inter-locking with interrogationof the three-positionswitch-disconnector

15 Operating rod with contactpressure springs

16 Interlocking to the three-position switch-disconnector

17 Actuation for closing thevacuum circuit-breaker

Abbreviations:NO = normally-open contactNC = normally-closed contact

1) For utilizationby thecustomer

* Itemdesignation

For further technical data and description of typical applications,please refer also to Catalog HG 11.11 “3AH Vacuum Circuit-Breakers”

Components

Page 20: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

20 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Three-position switch-disconnector

Features

• Switch positions: CLOSED –OPEN – EARTHED

• Switching functions asgeneral-purpose switch-disconnector (class E3)according to

– IEC 60 265-1/ VDE 0670-301– IEC 62 271-102/ VDE 0671-102

(standards see page 41)

• Designed as a multi-chamberswitch with the functions

– Switch-disconnector and– Make-proof earthing switch

• Operation via gas-tight welded-inmetal bellows at the front of theswitchgear vessel

Three-position switch-disconnector

1 Three-position switch-disconnector

2 Coupling linkage

3 Switchgear vessel

4 Operating mechanism rocker

5 Detachable lever mechanism

6 Operating lever inserted

����

����

�����

� � � �

Switch positions

Detachable lever mechanismwith three-position switch-disconnector

SF6 insulation

For further details, please refer toCatalog HA 40.1 “SwitchgearTypes 8DJ and 8DH for SecondaryDistribution Systems up to 24 kV,Gas-Insulated (General Part)”

R-H

A4

1-0

12

ep

s

EARTHED

OPEN

CLOSED

Components

Page 21: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 21

Busbars

Features

• Safe-to-touch as a result ofuse of metal covers

• Plug-in type

• Consisting of round-barcopper, insulated by means ofsilicone rubber

• Busbar joints with cross andend adapters, insulated bymeans of silicone rubber

• Insensitive to pollution andcondensation

• Switchgear extension orpanel replacement is possi-ble without gas work

• Special busbar connectionsto metering panels type ME1are possible. Connection tothe

– Cable connection bushingsof the adjacent panelor to the

– Busbar bushings

• Busbar arrangement in panelblocks within the switchgearvessel filled with gas

• Option screened busbar:– Field control by means of

electrically conductive layerson the silicone-rubberinsulation

– Installation of 4MC70 32current transformers is thuspossible

– Independent of the sitealtitude

• Option: Capacitive voltagedetecting system for thebusbar, refer also to theproduct range, pages 10to 15

����

����

�����

��

Insulated plug-in type busbarunscreened design

Top view

Busbar compartments over 2 panelswith busbar connections, busbar covers removed

R-H

A4

1-0

17

ae

ps

3

82

7

Busbar system

1 End adapter

2 Cross adapter

3 Busbar insulation of silicone rubber

4 Threaded bolt M12 / M16

5 Busbar, Cu, diameter 32 mm

6 Stopper

Switchgear vessel

7 Primary enclosure panel 1

8 Primary enclosure panel 2

9 Bushing

10 Capacitive tap at the bushings,earthed (standard)

Components

Page 22: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

22 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

4MT3 * and 4MT8 * plug-in voltage transformers for panel types LS, TR, SE and ME3

Common features

• According to IEC 60 044-2/ VDE 0414-2

• Designed as single-pole voltage trans-formers, plug-in type

• Inductive type

• Climate-independent

• Secondary connection by means ofplugs inside the panel

• Connection with plug-in contact

• Installation behind metallic cover

Features type 4MT3

• Inside-cone system, metal-coated

Features type 4MT8

• Outside-cone system, metal-enclosed

• For deep cable compartment cover

Installation

• Safe-to-touch arrangement due tometallic cover

• Arrangement on the switchgearvessel for busbar metering:

– 4MT3 voltage transformer for paneltypes LS1V/LS2, SE1V/SE2, MS1V/ME3and LKV/LT1

• Arrangement at the cable connection:– 4MT8 voltage transformer, pluggable

on screened cable T-plug, for paneltypes LS1-V, LS2-V and TR-V (deepcable compartment cover required)

– 4MT8 voltage transformer, directlypluggable via adapter on the bushingwith plug-in contact (interface type “A”),for panel type TR-V (deep cable com-partment cover required)

����

����

�����

R-H

A4

1-0

20

ep

sR

-HA

41

-01

9e

ps

R-H

A4

1-0

18

ae

ps

Panel sectiontype LS2-V

1 4MT3 * for the busbar

2 4MT8 * at the cable connection

4MT8 plug-in voltage transformermounted on cable T-plug (in panel type LS1-V)

4MT3 plug-involtagetransformer(for the busbar)

4MT8 plug-involtagetransformer(at the cableconnection)

Technical data4MT3 * and 4MT8 * voltage transformers

Primary data

Max. equipment operatingvoltage Um (= 1.2 x UN)

12 kV

Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud

3.3/ 3 kV at 10 kV

3.6� 3 kV at 20 kV4.8/ 3 kV at 20 kV5.0� 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3 kV at 20 kV

7.2/ 3 kV at 28 kV10.0/ 3 kV at 28 kV11.0/ 3 kV at 28 kV

Rated lightning impulsewithstand voltage Up

3.6 kV / 20 kV7.2 kV / 60 kV12 kV / 75 kV

Rated voltage factor (8 h) 1.9 x UN

Max. equipment operatingvoltage Um (= 1.2 x UN)

24 kV

Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud

13.8/ 3 kV at 38 kV15.0/ 3 kV at 38 kV

17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV

Rated lightning impulsewithstand voltage Up

17.5 kv / 95 kV24 kV / 125 kV

Rated voltage factor (8 h) 1.9 x UN

* Disassembly is necessary in order to perform voltage tests on the switchgear on site (max. 80 % Ud)

Make Type Combination

Euromold (K) 400 TB/G(K) 440 TB, AGT 10/20

yes

nkt cables ASTS 10/630,ASTS 20/630

yes

PrysmianKabel undSysteme

FMCTs-400, FMCTg-400 yes

Make Type Combination

Südkabel SEHDT (13/23) yes

Südkabel SET (12/24) on request

Cooper DT 400 P yes

Tyco Electronics RSTI�L56xx for:

• 35-300 mm2

(M12)

• > 300 mm2

(M16)

on request(add.measures)

on request

Combination of 4MT8 * voltage transformers with cable T-plugs (screened, without metal housing)

Components

Secondary data for 4MT3 voltage transformers

Rated voltage 100/ 3 V110/ 3 V (option)

Rated voltage forauxiliary winding (option)

100/3 V110/3 V (option)

Rated thermallimit current(measuring winding)

6 A

Rated long-time thermalcurrent (8 h)

4 A

Rating VA 25 15 60 100 150

Class 0.2 0.5 0.5 1 1

Secondary data for 4MT8 voltage transformers

Rated voltage 100/ 3 V110/ 3 V (option)

Rated voltage forauxiliary winding (option)

100/3 V110/3 V (option)

Rated thermallimit current(measuring winding)

4 A

Rated long-time thermalcurrent (8 h)

4 A

Rating VA 15 15 30 30 100

Class 0.2 0.5 0.5 1 3

Page 23: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 23

4MC63 three-phase current transformer for panel type LS

Features

• According to IEC 60 044-1/VDE 0414-1

• Designed as three-polering-core current transformer

• Free of dielectricallystressed cast-resin parts(due to design)

• Insulation class E

• Inductive type

• Climate-independent

• Secondary connection bymeans of a terminal stripinside the panel

Installation

• Arranged outside the switch-gear vessel on the bushingsof the cable connection

• Mounted at the factory

Other designs(option)

Three-phase current trans-former for protection equip-ment based on the current-transformer operation principle:

• 7SJ4x protection systemas definite-time overcurrentprotection

• Definite-time overcurrent pro-tection relay make SEG, typeWIP 1 or type WIC

Other values on request Other values on request

����

����

�����

R-H

A4

1-0

21

be

ps

R-H

A4

1-0

22

ep

s

4MC63 three-phasecurrent transformer

4MC63 three-phase current transformeron the bushings of the cable connection

Panel sectiontype LS1

1 4MC63 three-phasecurrent transformer

Technical data4MC63 10 three-phase current transformerfor IN � 150 A and ID = 630 A

Primary data

Max. equipment operatingvoltage Um

0.72 kV

Rated current IN A 150 100 75 50

Rated short-durationpower-frequency with-stand voltage (winding test)

3 kV

Rated thermal short-timewithstand current Ith

25 kA

Rated continuousthermal current ID

630 A

Transient overloadcurrent

1.5 x ID / 1 h

Rated peak withstandcurrent Idyn

unlimited

Secondary data

Rated current A 1 0.67 0.5 0.33

Rating VA 2.5 1.7 1.25 0.8

Rated current (option) 5 A

Current at ID 4.2 A

Protec- Classtion Overcurrent factorcore

10 P

10

4MC63 11 three-phase current transformerfor IN � 400 A and ID = 630 A

Primary data

Max. equipment operatingvoltage Um

0.72 kV

Rated current IN A 400 300 200

Rated short-durationpower-frequency with-stand voltage (winding test)

3 kV

Rated thermal short-timewithstand current Ith

25 kA

Rated continuousthermal current ID

630 A

Transient overloadcurrent

2 x ID / 0.5 h

Rated peak withstandcurrent Idyn

unlimited

Secondary data

Rated current A 1 0.75 0.5

Rating VA 4 3 2

Rated current (option) 5 A

Current at ID 1.575 A

Protec- Classtion Overcurrent factorcore

10 P

10

Components

Page 24: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

24 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

4MC70 33 and 4MC70 31 cable-type current transformers for panel types LS, RK and TR

Features

• According to IEC 60 044-1/VDE 0414-1

• Designed as single-pole ring-core current transformers

• Free of dielectrically stressedcast-resin parts (due to design)

• Insulation class E

• Inductive type

• Climate-independent

• Secondary connection bymeans of a terminal stripinside the panel

• Only for shielded cables

Installation

• 4MC70 33 cable-type currenttransformer for panel type LS

• 4MC70 31 cable-type currenttransformer for panel typesRK and TR

• Arranged outside the switch-gear vessel around the cableat the panel connection

• Transformers mounted on asupporting plate at the fac-tory; final assembly aroundthe cables on site

• For double cable: 300 mmdeeper cable compartmentcover

Other values on request

* Max. 230 mm, depending onthe core data of the 4MC70 33cable-type current transformer,overall heights 170 and 285 mm(observe floor openings on page 36)

����

����

�����

R-H

A4

1-0

23

ae

ps

R-H

A4

1-0

25

ep

s

4MC70 31 cable-typecurrent transformer

4MC70 33 cable-type current transformerfor the cables at the panel connection

Other values on request

Panel sectiontype LS1

Frontview

1 Cable-type current transformer2 Cable shield

Technical data4MC70 33 cable-type current transformer

Primary data

Max. equipment operatingvoltage Um

0.72 kV

Rated current IN 30 A to 600 A

Rated short-durationpower-frequency with-stand voltage (winding test)

3 kV

Rated thermal short-timewithstand current Ith

25 kA

Rated continuousthermal current ID

1.0 x IN

option: 1.2 x IN

Transient overloadcurrent

1.5 x ID / 1 h or2 x ID / 0.5 h

Rated peak withstandcurrent Idyn

unlimited

Secondary data

Rated current 1 A (option: 5 A)

Meas- Classuring Overcurrent factorcore

Rating

0.2 0.5 1

FS10 (option: FS5)

2.5 VA to 10 VA

Pro- Classtection Overcurrent factorcore

Rating

10 P 5 P

10 10

2.5 VA to 10 VA

Option: Secondary tap 1 : 2(e.g.150 A – 300 A)

Dimensions

Overall height H, mmdependent on thecore data

50 100 170 285

Outside diameter 145 mm

Inside diameter 55 mm

For cable diameter 50 mm

4MC70 31 cable-type current transformer

Primary data

Max. equipment operatingvoltage Um

0.72 kV

Rated current IN 50 A to 600 A

Rated short-durationpower-frequency with-stand voltage (winding test)

3 kV

Rated thermal short-timewithstand current Ith

25 kA

Rated continuousthermal current ID

1.0 x IN

option: 1.2 x IN

Transient overloadcurrent

1.5 x ID / 1 h or2 x ID / 0.5 h

Rated peak withstandcurrent Idyn

unlimited

Secondary data

Rated current 1 A (option: 5 A)

Meas- Classuring Overcurrent factorcore

Rating

1

FS5 (option: FS10)

2.5 VA to 10 VA

Option: Secondary tap 1 : 2

Dimensions

Overall height H 89 mm

Width x depth 85 mm x 114 mm

Inside diameter 40 mm

For cable diameter 36 mm

Components

4MC70 33 cable-typecurrent transformers,4 different overall heights

R-H

A4

1-0

24

ae

ps

Page 25: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 25

Features

• Used exclusively forscreened busbars

• Preferably in combinationwith panel type ME2

• According to IEC 60 044-1/VDE 0414-1

• Designed as single-polering-core current trans-formers

• Free of dielectricallystressed cast-resin parts (dueto design)

• Insulation class E

• Inductive type

• Climate-independent

• Secondary connection bymeans of a terminal stripinside the panel

Installation

• Arranged outside theswitchgear vessel only onthe screened busbars

• Installation of the bus-typecurrent transformers eitherbetween the panels or alter-natively

• Supplied loosely (includingthe busbar connections), ifthe mounting position of thebus-type current transformerslies at the joint of a transportunit

4MC70 32 bus-type current transformer,mounted on screened busbars, in some casesbetween the panels

����

����

����

R-H

A4

1-0

26

ae

ps

R-H

A4

1-0

27

ep

s

4MC70 32 bus-typecurrent transformer

Other values on request * On request

4MC70 32 bus-type current transformers for panel type LT (for screened busbars only)

Panel sectiontype LT1

1 4MC70 32 bus-typecurrent transformer

Technical data4MC70 32 bus-type current transformer

Primary data

Max. equipment operatingvoltage Um

0.72 kV

Rated current IN 200 A to 600 A

Rated short-durationpower-frequency with-stand voltage (winding test)

3 kV

Rated thermal short-timewithstand current Ith

25 kA

Rated continuousthermal current ID

1.0 x IN

option: 1.2 x IN

Transient overloadcurrent

1.5 x ID / 1 h or2 x ID / 0.5 h

Rated peak withstandcurrent Idyn

unlimited

Secondary data

Rated current 1 A (option: 5 A)

Meas- Classuring Overcurrent factorcore

Rating

0.2 0.5 1

FS10 (option: FS5)

2.5 VA to 10 VA

Pro- Classtection Overcurrent factorcore

Rating

10 P 5 P *

10 10

2.5 VA to 15 VA

Option: Secondary tap 1 : 2(e.g. 150 A – 300 A)

Dimensions

Overall width B,dependent on thecore data

80 mm 150 mm

Outside diameter 125 mm

Inside diameter 55 mm

Components

Page 26: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

26 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

4MA7 current transformers and 4MR voltage transformersfor air-insulated billing metering panels type ME1

Features

4MA7 current transformer

• According to IEC 60 044-1/VDE 0414-1

• Dimensions according toDIN 42600-8 (small design)

• Designed as single-poleindoor block-type currenttransformers

• Cast-resin insulated

• Insulation class E

• Secondary connection bymeans of screw-typeterminals

4MR voltage transformer

• According to IEC 60 044-2/VDE 0414-2

• Dimensions according toDIN 42600-9 (small design)

• Designed as indoorvoltage transformers:

– Type 4MR, single-pole– Option: Type 4MR, two-pole

• Cast-resin insulated

• Insulation class E

• Secondary connection bymeans of screw-typeterminals

Other values on request Other values on request

����

����

�����

R-H

A4

1-0

28

ep

s

4MR14 voltagetransformer

4MA7 currenttransformer

4MR voltage transformers and4MA7 current transformers installed inbilling metering panel type ME1

R-H

A4

1-0

29

ae

ps

R-H

A4

1-0

30

ae

ps

1 4MR voltage transformer2 4MA7 current transformer

Panel section type ME1

Technical data4MA7 single-pole current transformer

Primary data

Max. equipment operatingvoltage Um

12/ 24 kV17.5 kV

Rated short-durationpower-frequencywithstand voltage Ud

28/ 50 kV38 kV

Rated lightning impulsewithstand voltage Up

75/ 125 kV95 kV

Rated current IN 25 A to 600 A

Rated thermal short-timewithstand current Ith

up to 25 kA

Rated continuousthermal current ID

1.0 x IN

option: 1.2 x IN

Rated peak withstandcurrent Idyn

max. 2.5 x Ith

Secondary data

Rated current 1 A or 5 A

Meas- Classuring Overcurrent factorcore

Rating

0.2 0.5 1

FS5 or FS10

10 VA to 15 VA

Pro- Classtection Overcurrent factorcore

Rating

5 P or 10 P

10

5 VA to 15 VA

4MR single-pole voltage transformer

Primary data

Max. equipment operatingvoltage Um (= 1.2 x UN)

12 kV

Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud

3.3/ 3 kV at 10 kV

3.6/ 3 kV at 20 kV4.8/ 3 kV at 20 kV5.0/ 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3 kV at 20 kV

7.2/ 3 kV at 28 kV10.0/ 3 kV at 28 kV11.0/ 3 kV at 28 kV

Rated lightning impulsewithstand voltage Up

3.6 kV / 20 kV7.2 kV / 60 kV

12 kV / 75 kV

Rated voltagefactor (8 h)

1.9 x UN

Max. equipment operatingvoltage Um (= 1.2 x UN)

24 kV

Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud

13.8/ 3 kV at 38 kV15.0/ 3 kV at 38 kV

17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV

Rated lightning impulsewithstand voltage Up

17.5 kV / 95 kV24 kV / 125 kV

Rated voltagefactor (8 h)

1.9 x UN

Secondary data

Rated voltage 100/ 3 V110/ 3 V (option)120/ 3 V (option)

Rated voltage for auxiliarywinding (option)

100/3 V110/3 V (option)120/3 V (option)

Rating 20 VA 50 VA 100 VA

Class 0.2 0.5 1

Components

Page 27: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 27

4MK * metal-enclosed combined transformersfor billing metering panels type ME2

Features

• 4MK * combinedtransformer, comprising

– 4MK1 combined currenttransformer

– 4MK3 combined voltagetransformer

• According to IEC 60 044-3/VDE 0414-5

• Designed as indoor trans-formers, single-polecombination

• Metal-enclosed

• Insulation class E

• Inductive type

• Secondary connection bymeans of screw-typeterminals

Panel type ME2

• For combination withleft-hand panels

– As individual panels or– As panel blocks (on request)

• For combination withright-hand panels as endpanels or panel blocks

Other values on request Other values on request

����

����

�����

4MK combined transformers installed inbilling metering panel type ME2

R-H

A4

1-0

31

ae

ps

R-H

A4

1-0

32

ep

s

4MK combinedtransformer

1 4MK3combinedvoltagetransformer

2 4MK1combinedcurrenttransformer

1

2

Panel section type ME2

1 4MK3 combined voltagetransformer

2 4MK1 combined currenttransformer

* Available only as a combination ofcurrent and voltage transformers

Technical data4MK1 combined current transformer

Primary data

Max. equipmen+toperating voltage Um

12 kV 24 kV

Rated short-durationpower-frequencywithstand voltage Ud

28 kV 50 kV

Rated lightning impulsewithstand voltage Up

75 kV 125 kV

Rated current IN 50 A to 600 A

Rated thermal short-timewithstand current Ith

up to 25 kA

Rated continuousthermal current ID

1.0 x IN

option: 1.2 x IN

Rated peak withstandcurrent Idyn

max. 2.5 x Ith

Secondary data

Rated current 1 A or 5 A

Meas- Classuring Overcurrent factorcore

Rating

0.2 0.5 1

FS5 or FS10

10 VA to 15 VA

Pro- Classtection Overcurrent factorcore

Rating

10 P

10

5 VA or 15 VA

Secondary multiratio option

4MK3 combined voltage transformer

Primary data

Max. equipment operatingvoltage Um (= 1.2 x UN)

12 kV

Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud

3.3/ 3 kV at 10 kV

3.6/ 3 kV at 20 kV4.8/ 3 kV at 20 kV5.0/ 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3 kV at 20 kV

7.2/ 3 kV at 28 kV10.0/ 3 kV at 28 kV11.0/ 3 kV at 28 kV

Rated lightning impulsewithstand voltage Up

3.6 kV / 20 kV7.2 kV / 60 kV12 kV / 75 kV

Rated voltagefactor (8 h)

1.9 x UN

Max. equipment operatingvoltage Um (= 1.2 x UN)

24 kV

Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud

13.8/ 3 kV at 38 kV15.0/ 3 kV at 38 kV

17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV

Rated lightning impulsewithstand voltage Up

17.5 kV / 95 kV24 kV / 125 kV

Rated voltagefactor (8 h)

1.9 x UN

Secondary data

Rated voltage 100/ 3 V110/ 3 V (option)

Rated voltage for auxiliarywinding (option)

100/3 V110/3 V (option)

Rating 30 VA 75 VA 150 VA

Class 0.2 0.5 1

Components

Page 28: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

28 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Cable connection

Features

• Bushings with outside cone

• Uniform cable connectionheight 575 mm

• With cable bracket, e.g.type C40 according toDIN EN 50 024

• Access to the cable compart-ment only if the feeder hasbeen isolated and earthed

Special features

– In ring-main panels– In circuit-breaker panels– In cable panels:

• With bolted contact (M16)as interface type “C”according to EN 50181/DIN EN 50181

• For thermoplastic-insulated cables

• For paper-insulatedmass-impregnated cableswith adapter systems

• For conventional cablesealing ends via elbowadapter AKE 20/630(make Siemens)

• For cable T-plugs or cableelbow plugs with bolted con-tact (M 16)

• For connection cross-sections up to 300 mm²(standard)

• Cable routing downwards,cable connection at front

• For rated normal currents of400/630 A

– In transformer panels:

• With plug-in contact asinterface type “A”according to EN 50 181/DIN EN 50 181

• For cable elbow plugswith plug-in contact

• For thermoplastic-insulated cables

• For connection cross-sections up to 120 mm²

• For rated normal currentsof 200 A

Options

See figures on the right

* Cable plugs, cable sealing endsand cable clamps are notincluded in the scope of supply

Cable connections inring-main panels

1 Prepared for cableplugs with boltedcontact (M16)

2 Phase L1:Make Euromold,type K400 LB ascable elbow plug

3 Phase L2:Make Euromold,type K400 TB ascable T-plug

4 Phase L3:Make Euromold,type AGT 20/630 ascable T-plug

For options A, B, Cand E, see below

Cable connection · Examples

Cable plugs withbolted contact (M16)

Cable compartment, as-deliveredcondition *

L1 L2 L3 L3L2L1

Cable compartment,as-delivered condition *

Cable plugs withbolted contact (M16)

Cable connections incircuit-breaker panels

5 Prepared for cableplugs with boltedcontact (M16)

6 Phase L1:Elbow adapter,make Siemens,type AKE 20/630

7 Phase L2:Make Euromold,type K400 TB ascable T-plug

8 Phase L3:Make Euromold,type AGT 20/630 ascable T-plug

For options A, B, C,E and F, see below

L2L1L3L2L1

R-H

A4

1-0

33

ep

s

R-H

A4

1-0

34

ep

s

R-H

A4

1-0

35

ep

s

R-H

A4

1-0

36

ep

s

R-H

A4

1-0

37

ep

s

R-H

A4

1-0

38

ep

s

L3L2L1 L3L2L1

Cable elbow plugs withplug-in contact

Cable compartment,as-delivered condition *

Cable connections intransformer panels

9 Prepared for cableelbow plugs with plug-incontact

10 Phase L1:Make Euromold,type AWGL

11 Phase L2:Make Euromold,type K158 LR

12 Phase L3:Make Euromold,type AGW 20/250(with metal housing)

For options A, D and F,see below

Options

A Mounted cable clamps

B Short-circuit / earth-fault indicator

C Double cable connection withcorresponding cable plugs anddeep cable compartment cover

D Bushings as interface type “C” according toEN 50 181 / DIN EN 50 181 for cable plugs with bolted contact (M16)

E Suitable for connection of plug-in surge arresters in conjunction withcorresponding cable T-plugs

F Suitable for connection of 4MT8 metal-enclosed voltagetransformers in conjunction with corresponding cable T-plugs;deep cable compartment cover is required

L3

1

3

4

5

7

8

6

109

11

12

2

Components

Page 29: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 29

Low-voltage equipment

Low-voltage compartment *

• Overall height– Standard 600 mm– Option 900 mm

• Partitioned safe-to-touch fromthe high-voltage part of thepanel

• Installation on the panel:– Standard for circuit-breaker

panel type LS and bus section-alizer with switch-disconnectortype LT1

– Option for all other paneltypes, depending on thescope of the secondaryequipment

• For accommodation of protec-tion, control, measuring andmetering equipment, e. g.suitable for multifunction pro-tection device SIPROTEC 47SJ63

• Electronic control boardof the multifunction protec-tion device SIPROTEC 4 7SJ63with the following features:

1 User-programmable LEDswith application-specific label,for displaying any desiredprocess and equipment data

2 LCD for process andequipment data, e.g. for

– Measuring and meteringvalues

– Binary information on status ofswitchgear and switchingdevice

– Protection data– General indications– Alarms

3 Keys for navigation in themenus and for entering values

4 Four user-programmablefunction keys for frequentlyperformed actions

Low-voltage niche

• Only inside billing meteringpanels type ME1

• Option: For accommodation,e.g. of voltage transformer,m.c.b.s

Low-voltage cables

• Control cables of the panel tothe low-voltage compartmentare connected via multi-pole,coded module plug connectors

• Option: Plug-in bus wires frompanel to panel are routed inthe separate wiring duct onthe panel

* Door hinge on the left (standard)

Low-voltage compartment

Low-voltage compartmentof a circuit-breaker paneltype LS

Electronic control board withmultifunction protection deviceSIPROTEC 4 7SJ63

R-H

A4

1-0

41

ae

ps

R-H

A4

1-0

39

ae

ps

R-H

A4

1-0

40

ep

s

Open low-voltage compartmentwith (optional) equipment

Low-voltage niche

R-H

A4

1-0

42

ep

s

Low-voltage niche of abilling metering panel type ME1with open cover

1 Low-voltageniche

2 Equipment(option)

1 LEDs

2 LCD

3 Navigation keys

4 Function keys

1

2

3

1

4

2

Components

Page 30: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

30 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Ring-main, cable, transformer and circuit-breaker panels as individual panels

Cable panel type K:

1 Option: Earthing function

2 Interlock of cable compartment coverif earthing function is available

3 Cable compartment cover screwed on (without earthing function)

4 Cover screwed on

* Option:With low-voltage compartment

** Dependent on the type ofcable plug

*** Available mounting depthfor low-voltage equipment

**** Option: With highlow-voltage compartment 900 mm

Dimensions

����

����

����

�����������

���

���

���

���

���

���

�����

����

���

����

�����

����

��

���

����

����

���

��

Circuit-breaker paneltype LS1

����

����

����

����

��� �����������

���

���

���

���

���

���

�����

���

����

����

��

����

�����

����

��

���

Circuit-breaker paneltype LS1 V/LS2

����

����

���

����

���

����

��

��� �����������

���

���

���

���

���

���

����

�����

���

���

���

Ring-main paneltype RK

����

����

���

����

��� ��������

���

���

���

���

���

���

����

�����

���

���

����

��

���

��

���Cable paneltype K

����

����

� ��

����

��� ������������

���

���

���

���

���

���

���

����

��

���

��

����

�����

���

Transformer paneltype TR 1

Page 31: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 31

Ring-main, cable and transformer panels in panel blocks

Ring-mainpanel block type R-B2

Ring-mainpanel block type R-B3

Transformerpanel block type T-B2

Transformerpanel block type T-B3

Ring-main/transformerpanel block type RT-B2

Ring-main/transformerpanel block type 2RT-B3

Ring-main/transformerpanel block type 3RT-B4

Cable connection/transformerpanel block type KT-B2

Cable panel type K:

1 Option: Earthing function

2 Interlock of cable compartment coverif earthing function is available

3 Cable compartment cover screwed on(without earthing function)

4 Cover screwed on

* Option:With low-voltage compartment

Dimensions

����

����

����

���

��

���

����

�����

���

�� ��

����

����

����

���

������

����

�����

���

�� �� ��

����

����

����

���

��

����

����

�����

���

�� ��

���

����

���

�� �

����

����

����

�����

���

�� �� ��

����

����

����

���

��

���

����

�����

���

����

����

����

����

���

��

����

����

�����

���

�� �� ��

����

����

����

���

��

����

����

�����

���

�� �� �� ��

����

����

����

���

��

���

����

�����

���

���

Page 32: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

32 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

����

����

����

���

����

��

��

����

���

����

�����

���

������

���

���

���

���

���

����

����

����

������

���

���

���

���

���

����

���

����

��

���

��

����

�����

���

Bus sectionalizers with circuit-breakers, bus sectionalizers with switch-disconnectors andbusbar voltage metering panel as individual panels

1 Cover screwed on

* Option: With low-voltage compartment

*** Available mounting depth forlow-voltage equipment

**** Option: With highlow-voltage compartment 900 mm

Dimensions

Voltage meteringpanel type MS1V/ME3

Bus sectionalizer withswitch-disconnector type LT2

����

����

����

����

���

����

����

��� ������

���

���

���

���

���

�����

��

����

�����

����

��

Bus sectionalizer withcircuit-breaker type LK/LT1

����

����

����

������

���

���

���

���

���

�����

����

���

����

����

���

��

����

�����

����

��

Bus sectionalizer withcircuit-breaker type LKV/LT1

Page 33: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 33

����

����

���

������

���

���

���

���

���

���

����

��

��

����

���

����

�����

���

����

����

����

���

����

��

��

����

���

����

�����

���

������

���

���

���

���

���

����

����

� ��

������

��� ���

���

���

���

��

���

����

��

������

����

��

����

�����

���

Earthing paneltype SE

Earthing paneltype SE1V/SE2

Billing meteringpanel type ME2

Dimensions

* Option:With low-voltage compartment

1 Cover screwed on

* Option:With low-voltage compartment

*** Available mounting depthfor low-voltage equipment

1) Panel block on request

Metering panel combination

Billing metering panel type ME2 withindividual panel attached on the leftand panel block attached on the right(example)

Busbar earthing panelsas individual panels

Billing metering panel ME2 as individual panel andmetering panel combin. with billing metering panel

����

��

����

����

����

Only individualpanel or panel block, 1)

on the left

Billing meteringpanel

type ME2

Individual panelor panel block,on the right

Connectionat the busbar

Connectionat the busbar

Page 34: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

34 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

����

����

� ��

����

���

����

��

���

��

����

�����

���

������

���

���

���

���

���

��� ���

��

����

����

����

� ��

����

���

����

��

���

��

����

�����

���

������

���

��� ���

��

����

������

����

����

���

����

���

����

�����

���

��� ���

���

����

��

��

���

���

���

��� �

���

��

������

��� ���

����

����

� ��

����

���

����

��

���

��

����

�����

���

������

���

���

���

���

���

��� ����

���

��

Billing metering panels type ME1... as individual panels

Dimensions

1 Cover/cable compartment cover screwed on

* Option:With low-voltage compartment

** Dimension for cable routing: 323 mm for combination ofpanel type ME1-K with pressure absorber duct

Billing metering paneltype ME1

Billing metering paneltype ME1-K

Billing metering paneltype ME1-KS

Billing metering paneltype ME1-S

Page 35: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 35

Billing metering panels with individual panelsor panel blocks attached on the left and right (examples)

Connection inside the panel block:

* Only possible in the right-hand feeder

** Only possible in the left-hand feeder

Possible panel arrangements

The following types of individual panelsor panel blocks can be attached to billingmetering panels – on the right or left:

Possibility 1

• Types attached on the leftwith connection at the feeder

– Individual panel typeRK-U, K-U, TR-U, LS1-U or LS2-U

– Panel block typeR-B2 or R-B3 (in RK-U panel),T-B2 or T-B3 (in TR-U panel),RT-B2, 2RT-B3 or 3RT-B4 (in TR-U panel)or KT-B2 (in TR-U panel)

• Types attached on the rightwith connection at the busbar

– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT

– Panel block typeR-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4or KT-B2

Possibility 2

• Types attached on the leftwith connection at the busbar

– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT

– Panel blocks cannot be attached

• Types attached on the rightwith connection at the feeder

– Individual panel typeRK-U, K-U, TR-U, LS1-U or LS2-U

– Panel block typeR-B2 or R-B3 (in RK-U panel),T-B2 or T-B3 (in TR-U panel),RT-B2, 2RT-B3 or 3RT-B4 (in RK-U panel)or KT-B2 (in K-U panel)

Possibility 3

• Types attached on the leftwith connection at the busbar

– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT

– Panel blocks cannot be attached

• Types attached on the rightwith connection at the busbar

– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT

– Panel block typeR-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4or KT-B2

Metering panel combinations with billing metering panels type ME1...

Possiblity 1

Possiblity 2

Possiblity 3

���

����

!�

!�

!�!� !� !�

����

����

����

Billing meteringpanel

type ME1-S

Individual panelor panel block,on the right

Connectionat the busbar

Connectionat the busbar

Onlyindividual panel,

on the left

Dimensions

����

���

����

����

����

Individual panelor panel block,

on the left

Billing meteringpanel

type ME1

Individual panelor panel block,on the right

Connectionat the feeder *

Connectionat the busbar

����

���

!�

!�

!�!� !� !�

����

����

����

Onlyindividual panel,

on the left

Billing meteringpanel

type ME1

Individual panelor panel block,on the right

Connectionat the busbar

Connectionat the feeder **

Page 36: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

36 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Floor openings (dimensions in red) and fixing points

• For billing meteringpanels

– Type ME1– Type ME1-K– Type ME1-S– Type ME1-KS– Type ME1-KK

• For transformerpanel blocktype T-B2

• For ring-mainpanel blocktype R-B2

• For ring-main/transformerpanel blocktype RT-B2

• For cable connection/transformerpanel blocktype KT-B2

1 Wall distance

2 Fixing frame (base) of an individual panel or panel block

3 Floor opening for high-voltage cables (and, if applicable,control cables)

4 Fixing points

5 For 4MC70 33 cable-type current transformer with outside diameter145 mm for arrangement beneath the panel

6 Position of the incoming cables for metering panels type ME1...

7 Position of the incoming cables for the feeder

8 Overall panel depth

B Cutout in the fixing frame for extended floor opening forpanel with cable-type current transformers

Dimensions

• For billing meteringpanelstype ME2

• For circuit-breakerpanel types LS1 and LS2each with cable-typecurrent transformers

• For circuit-breaker panel typesLS1 and LS2 for ring-main pan-els type RK1 each without ca-ble-type current transformers

• For transformerpanels type TR1

• For bus sectionalizer with cir-cuit-breaker type LK and bussectionalizer with switch-dis-connector type LT

• For busbar earthingpanel type SE2

• For busbar voltagemetering panel type ME3

• For ring-main panelstype RK

• For cable panelstype K

• For busbar earthingpaneltype SE

Standard (for special versions, see pages 38 and 39)

����

����

����

���

����

���

���

��

���

��

��

���

���

���

���

���

����

��

��

���

���

���

���"���

���"��� �

����

�����

For individual panels

����

���

���

� �������

���

��

���

��

��

����

���

���

���

�����

���

���

��

��

���

�����

��

���

������������

���

���"���

���"��� �

��

��

���

���

���

For panel blocks

�������

����

��

���

��

��

���

���

���

���

���

����

��

��

���

���

����

����

����

���

�����

��

��

������������

���

���"���

���"��� �

��

��

���

���

���

For panel block

�����

��

��

���

��

��

���

���

���

���

����

��

��

������

����

����

����

���"���

���"��� �

���

For individual panels

�������

���

���

��

���

��

��

���

���

���

���

���

����

��

���

���

���

���

��

��

����

����

����

���

���

���

�� ���

���"���

���"��� �

���

For individual panels

�������

���

���

��

���

��

��

���

���

���

���

���

����

��

��

������

����

����

���

���

���"���

���"��� �

��

���

���

���

For individual panels

�������

���

���

��

���

��

��

���

���

���

���

���

����

�� ���

����

����

����

���

���"���

���"���

��

��

���

��� ��

���

For individual panels

Page 37: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 37

Floor openings (dimensions in red) and fixing points

• For trans-formerpanel blocktype T-B3

• For ring-main/transformerpanel blocktype 3RT-B4

• For ring-mainpanel blocktype R-B3

• For ring-main/transformerpanel blocktype 2RT-B3

Dimensions

1 Wall distance

2 Fixing frame (base) of an individual panel or panel block

3 Floor opening for high-voltage cables (and, if applicable, control cables)

4 Fixing points

7 Position of the incoming cables for the feeder

8 Overall panel depth (including cable compartment cover)

9 Fixing support

B Cutout in the fixing frame for extended floor opening forpanel with cable-type current transformers

� ��� ��� ���� ���

���

����

���

����

#��

� $%"&���

Example for fixingpanels on the floor

� ��� ��� ���� ���

����

���

����

����"���

Detail “A”

���

�������

����

��

���

��

��

���

���

���

���

���

����

��

��

����

���

����

����

����

���

�����

�����

��

������������

���

������

���

���"���

���"��� �

���� ����

���

��� ��

For panel block

���

����

���

���

� �������

����

��

���

��

��

���

���

���

���

���

����

��

��

����

���

�����

��� ��� ����� ��

������������

���

������

���

������

���

���"���

���"��� �

��������

���

��� ��

����

For panel block

���

���

���

����

���

���

� �������

����

��

���

����

���

���

���

���

���

����

��

��

���

���

�����

�����

���

������������

���

������

���

���"���

���"��� �

��������

��

For panel blocks

Page 38: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

38 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Floor openings (dimensions in red) and fixing points

Dimensions

• For ring-main panelstype RK

• For cable panelstype K

Legends and footnotes see page 39Special versions

• For ring-main panelstype RK

• For cable panelstype K

• For ring-main panelstype RK1

• For circuit-breaker panelstype LS1 and LS2

• For ring-main panelstype RK

• For cable panelstype K

• For ring-main panelstype RK1

• For circuit-breaker panelstype LS1 and LS2

• For ring-main panelstype RK

• For cable panelstype K

For individual panels with double cable connection (panel depth 1075 mm), 300 mm deeper cable compartment cover

• For ring-main panelstype RK1

• For circuit-breaker panelstype LS1 and LS2

�������

���

���

��

���

��

��

���

���

���

���

���

����

���

����

����

����

���

���

��

��

�����

���

���

�����

���"���

���"���

��� ��

���

For individual panels with cable-type current transformersor surge arresters

��

���

���

��

���

��

��

���

���

���

���

����

�� ���

����

����

����

���

���"���

���"���

��

��� ��

����

���

���

���

���

���

�������

���

���

���

���

��

��

���

���

���

���

���

����

�� �������

����

����

���

���"���

���"���

���

���

��

����

��

���

���

For individual panels with double cable connection (panel depth 880 mm), 105 mm deeper cable compartment cover

�������

���

���

���

����

��

��

���

���

���

��

���

����

���

����

����

����

���

��

���

���

����

���

���"���

���"���

��

��

���

���

����

���

��

���

���

��

���

��

��

���

���

���

����

����

�� �������

����

����

���

���"���

���"���

��

��� ��

����

���

���

���

For individual panels with double cable connection or surge arresters make Tyco Electronics, type RDA 24(panel depth 775 mm), standard or 25 mm deeper cable compartment cover

���

��

���

���

�������

���

���

���

���

��

��

���

���

���

���

���

����

�� �������

����

����

���

���"���

���"���

���

���

��

���

����

�������

���

���

���

����

��

��

���

���

���

��

���

����

���

����

����

����

���

��

���

���

���

���

����

���"���

���"���

��

��

���

���

����

Page 39: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 39

Special versions in combination with pressure absorber system

• For ring-main panelstype RK and RK1

• For cable panelstype K

• For circuit-breaker panelstype LS1 and LS2

• For transformer panelstype TR

• For ring-main panelstype RK and RK1

• For cable panelstype K

• For circuit-breaker panelstype LS1 and LS2

• For ring-main panelstype RK and RK1

• For cable panelstype K

• For circuit-breaker panelstype LS1 and LS2

• For ring-main panelstype RK and RK1

• For cable panelstype K

• For circuit-breaker panelstype LS1 and LS2

• For transformer panelstype TR, however connec-tion with bolted contact(M16)

Dimensions

Floor openings (dimensions in red) and fixing points

1 Wall distance

2 Fixing frame (base) of an individual panel orpanel block

3 Floor opening for high-voltage cables (and, ifapplicable, control cables)

4 Fixing points

7 Position of the incoming cables for the feeder

8 Overall panel depth (including cable compartment cover)

10 Position of 2nd cable

11 For surge arrester

12 For cable-type currenttransformers with outsidediameter up to 90 mm

13 Pressure absorber duct

14 Front edge of base of the pressure absorber system

15 Front edge of panel without cable compartment cover

* Dependent on the type of cable plug employed

** For panel types RK, K and LS

*** For panel types TR, connection with plug-in contact

� Cutout in the fixing frame for extended floor openingfor panel with cable-type current transformers

��

�����

���

���

��

���

���

���

����

����

����

��� �

����

���

���

���"��� �

����

���

���

���

����

��

���

����� ���

For individual panels with single cable connection

��

���

���

���

���"��� �

���

��

��

���

���

������

����

���

���

����

��

���

���

���

���

���

����

���

����� ���

For individual panels with double cable connectionstandard or 25 mm deepercable compartment cover

����

���

����

���

���

��

���

���

�������

����

����

��� �

����

���"��� �

���

���

����

���

��� ��

��

��

���

����

����� ���

For individual panels with double cable connection300 mm deeper cable compartment cover

��

���

���

���

���"��� �

���

��

����

���

��

����

����

����

���

���

��

���

���

���

���

���

� ���

��

���

����� ���

For individual panels with double cable connection105 mm deeper cable compartment cover

Page 40: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

40 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

1 Elbow adapter, make Siemens,type AKE 20/630 withconventional cable sealing end,make Lovink Enertech, type IAE 20

2 Cable T-plug, make Euromold,type (K)400 TB/G

3 Cable T-plug, make Euromold,type (K)400 TB/G

4 Cable T-plug, make Euromold,type (K)400 TB/G as 2nd cable(option: Cable elbow plugtype (K)400 LB/G);always same make required

5 Surge arrester,make Euromold,type 300 SA-5 or 300 SA-10

6 Cable plug,make Euromold,type 430 TB

7 Cable plug,make Tyco Electronics,type RICS 5139

8 Surge arrester,make Tyco Electronics,type RDA 21 (for type RDA 24,a floor opening of 635 mminstead of 610 mm is required)

9 Cable T-plug,make Südkabel,type SET (12/24)

and

10 Surge arrester,make Südkabel,type MUT (13/23)

or:

9 Cable connector,make nkt cables, type AB 24-630

and

10 Surge arrester,make nkt cables, type ASA 24-5

11 Cable T-plug, make Euromold,type (K)400 TB/G

12 Surge arrester, e.g.make Euromold,type 400 Pbor similar designs

13 Busbar systemfor billing metering paneltype ME1

14 Cable T-plug,make nkt cables, type CB 24-630

15 Coupling connector,make nkt cables, type CC 24-630

16 Cable T-plug,make Euromold, type (K)400 TB/G

17 4MT8 plug-in voltage transformer

18 Cable T-plug,make Südkabel,type SET 24

19 Coupling insert,make Südkabel,type KU 23.2

Cable connection examples in ring-main, cable and circuit-breaker panels(non-binding examples, for further examples see Catalog HA 40.1)

Dimensions

����

����

����

������ �

���

�����

������

���

����

�� �

����

�� ���

������

���

������

������

���� ��

����

����

����

���

�����

���

�������

������

����

����

����

���

������

�����

������

���

����

����

���

��

���

�� ���

������

����������

������

����

����

����

���

��

��

���

���

������

����

����

����

���

��������

����

���

���������

���

��

����

����

����

��

���

������

�����

������

�����

����

�� �

�����

�� ���

������

���

������

������������

����

�� �

�����

�� ��� ��

���

������

���� ������

Cable connection withsurge arresters

Connection incircuit-breaker panel

Cable connection inring-main panel

Standard cable compartment coverStandard cable compartment cover

Standard cable compartment coverStandard cable compartment cover Standard cable compartment cover

25 mm deepercable compartment cover

105 mm deepercable compartment cover

150 mm deepercable compartment cover

150 mm deepercable compartment cover

300 mm deeper cable compartmentcover for double cable connection

* Max. mounting spacefor cable plugs

** Dependent on the typeof cable plug

*** Dimension for bushing asinterface type “C” withbolted contact (M16)

**** Mounting depth forcombination of cable T-plugand surge arrester

����

���

���

������

������

� ��

�����

���

�����

Standard cable compartment cover

Page 41: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 41

Overview of standards (July 2007)

Standards

Standards, specifications, guidelines

IEC standard VDE standard EN standard

Switchgear 8DH10 IEC 60 694 VDE 0670-1000 EN 60 694

IEC 62 271-200 VDE 0671-200 EN 62 271-200

Switching devices Circuit-breaker IEC 62 271-100 VDE 0671-100 EN 62 271-100

Disconnector andearthing switch

IEC 62 271-102 VDE 0671-102 EN 62 271-102

Switch-disconnector IEC 60 265-1 VDE 0670-301 EN 60 265-1

Switch-disconnector /fuse combination

IEC 62 271-105 VDE 0671-105 EN 62 271-105

HV HRC fuses IEC 60 282-1 VDE 0670-4 EN 60 282

Voltage detecting systems IEC 61 243-5 VDE 0682-415 EN 61 243-5

Degree of protection – IEC 60 529 VDE 0470-1 EN 60 529

Insulation – IEC 60 071 VDE 0111 EN 60 071

Instrument transformers Current transformers IEC 60 044-1 VDE 0414-1 EN 60 044-1

Voltage transformers IEC 60 044-2 VDE 0414-2 EN 60 044-2

Combined transformers IEC 60 044-3 VDE 0414-5 EN 60 044-3

Installation – IEC 61 936-1 VDE 0101 –

Standards

The 8DH10 switchgearcomplies with the relevantstandards and specificationsapplicable at the time oftype tests.

In accordance with theharmonization agreementreached by the countries of theEuropean Community, theirnational specificationsconform to the IEC standard.

Dielectric strength

See also Catalog HA 40.1“Standards”.

Terms

“Make-proof earthing switches”are earthing switches withshort-circuit making capacityaccording to IEC 62 271-102/VDE 0671-102.

Protection against solid for-eign objects, electric shockand ingress of water

The switchgear types 8DH10fulfill acc. to the standards

the following degrees of pro-tection (for explanations re-garding the degrees of protec-tion, please refer to Catalog HA40.1, page 38)

Climate and ambientconditions

8DH10 switchgear types arefully enclosed and insensitive toclimatic conditions.

• Climatic tests fulfilled inaccordance with IEC 60 932(report)

• All medium-voltage devices(except for HV HRC fuses)are installed in a gas-tight,welded stainless steelswitchgear vessel which isfilled with SF6 gas

• Live parts outside the switch-gear vessel are provided withsingle-pole enclosure

• At no point can creepagecurrents flow from high-voltage potentials to earth

• Operating mechanism partswhich are functionally impor-tant are made of corrosion-proof materials

• Bearings in operating mech-anisms are designed as dry-type bearings and do notrequire lubrication

• Suitable instrument trans-former designs

• Plug-in busbar system,insulated or screened

• Operating conditions accord-ing to IEC 62 271-200,among other, relative airhumility: 95 %(24-hour mean value)

• Metering panel ME1(air-insulated) according toIEC 60 694: “Normal operat-ing conditions”

Type of service location

8DH10 switchgear can beused as indoor installations inaccordance with IEC 61 936(Power installations exceeding1 kV AC) and VDE 0101:

• Outside lockable electricalservice locations at placeswhich are not accessible tothe public. Enclosures ofswitchgear can only beremoved with tools.

• Inside lockable electricalservice locations. A lockableelectrical service location is aplace outdoors or indoors thatis reserved exclusively forhousing electrical equipmentand which is kept under lockand key. Access is restrictedto authorized personnel andpersons who have been prop-erly instructed in electricalengineering. Untrained orunskilled persons may onlyenter under the supervision ofauthorized personnel or prop-erly instructed persons.

Internal arc classification(option)

The possibility of arc faults ingas-insulated switchgear type8DH is improbable and a merefraction of that typical of earlierswitchgear types, due to:

• Use of gas-filled switchgearcompartments

• Use of suitable switchingdevices such as three-position switches with make-proof earthing switch

• Logical mechanical interlocks

• Use of metal-coated voltagetransformers and three-phasering-core current transformers.

Optionally, switchgear type8DH can be designed with in-ternal arc classification:

• Internal arc classification IAC

• Type of accessibility A(for authorized personnelonly)

• Accessible sides– Side F (front)– Side L (lateral)– Side R (rear) as an option for

switchgear with pressureabsorber

• Arc test current up to 21 kA /1 s

IEC 60 694 VDE 0670-1000DIN EN 60 694

IEC 62 271-200

VDE 0671-200

IEC 60 529 DIN EN 60 529

Degree ofprotection

Type ofprotection

IP 2X(standard)

Live parts under highvoltage in switchgearwith HV HRC fuses

Degree ofprotection

Type ofprotection

IP 3X(option)

Enclosure of live partsunder high voltage inswitchgear withlocking device

IP 3XD(on request)

Live parts under highvoltage in switchgearwith locking device

IP 65 Live parts under highvoltage in switchgearwithout HV HRC fuses

Page 42: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

42 Siemens HA 41.11 · 2007

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Standards, Transport

Transport

8DH10 switchgear is deliveredin transport units containingindividual panels or severalpanels.

The following must be noted:

• Transport facilities on site

• Transport dimensions andweights

• Size of door openings inbuilding

Packing

Place of destination insideGermany or other Europeancountries

• Means of transport:Rail and truck

• Type of packing:– Panels on open pallets– Open packing with PE

protective foil

Place of destination overseas

• Means of transport:Ship

• Type of packing:– Panels on open pallets– In closed crates with sealed

upper and lower PE protectivefoil

– With desiccant bags– With sealed wooden base– Max. storage time: 6 months

Transport data, classification

Classification of 8DH10 switchgear according to IEC 62 271-200

Design and construction

Partition class PM (metallic partition)

Loss of service continuity category 1)

Panels– With HV HRC fuses– Without HV HRC fuses

LSC 2ALSC 2B

Accessibility to compartments(enclosure)

– Busbar compartment– Switching-device compartment– Low-voltage compartment– Cable compartment 2)

– Panel without HV HRC fuses– Panel with HV HRC fuses (TR…)– Panel type K– Panel without cable connection

(e.g. type RK-U, LS1-U)

Access option

– Tool-based– Non-accessible– Tool-based

– Interlock-controlled– Interlock-controlled– Tool-based– Interlock-controlled and tool-based

Internal arc classification (option)

Designation ofinternal arc classification IACfor

– Wall-standing arrangement (standard)– Free-standing arrangement (option)

Rated voltage 7.2 kV to 24 kV

IAC A FL 21 kA, 1 sIAC A FLR 21 kA, 1 s

Type of accessibility A

– F– L– R

Switchgear in closed electrical service location,access “for authorized personnel only“ (acc. to IEC 62 271-200)FrontLateralRear (for free-standing arrangement)

Arc test current Up to 21 kA

Test duration 1 s

1) The loss of service continuitycategory is always refered to thecomplete switchgear, i.e. the panelwith the lowest category definesthe loss of service continuitycategory of the completeswitchgear.

2) For 8DH10 switchgear withpressure absorber:Access to cable compartment istool-based and interlock-controlled.For metering panels type ME1... :Access to cable compartment istool-based.

Page 43: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable

Siemens HA 41.11 · 2007 43

Responsible for

Technical contents:Christoph MaulSiemens AG, Dept. PTD M 2 PPMErlangen

General editing:Gabriele PollokSiemens AG, Dept. PTD CC MErlangen

Notes

If not stated otherwise on theindividual pages of this catalog,we reserve the right to includemodifications, especiallyregarding the stated values,dimensions and weights.

Drawings are not binding.

All product designations usedare trademarks or productnames of Siemens AG or othersuppliers.

If not stated otherwise, alldimensions in this catalog aregiven in mm.

Page 44: CatalogHA41.11·2007 Switchgear Type 8DH10 up to 24 kV, … · 6 SiemensHA 41.11 · 2007 SwitchgearType8DH10,upto24kV,Gas-Insulated,Extendable Switchgear installation Room planning

For questions concerning

Power Transmission and Distribution:

You can contact our Customer Support

Center 24 hours a day, 365 days a year.

Tel.: +49 180/524 70 00

Fax: +49 180/524 24 71

(Charges depending on provider)

E-Mail: [email protected]

www.siemens.com/energy-support

Siemens AG

Power Transmission and Distribution

Medium Voltage Division

Postfach 32 40

91050 Erlangen

Germany

www.siemens.com/

medium-voltage-switchgear

Subject to change without noticeOrder No.: E50001-K1441-A101-A7-7600Printed in GermanyDispo 31606KG 10.07 7.0 40 En102773 6101/6487

The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.

The required features should therefore be specified in each individual case at the time of closing the contract.