catalogo de plcs idec
DESCRIPTION
CATALO DE PLC IDECTRANSCRIPT
Section
J
Selection Guide...................................J-2
MicroSmart PLCs
• CPU Modules . . . . . . . . . . . . . . . . .J-3• Expansion Modules . . . . . . . . . . .J-10• Dimensions and Specifications . .J-16
OpenNet Controller
• ONC . . . . . . . . . . . . . . . . . . . . . . .J-23• Interbus. . . . . . . . . . . . . . . . . . . . .J-51• DeviceNet. . . . . . . . . . . . . . . . . . .J-61• LONWorks . . . . . . . . . . . . . . . . . .J-71
Original Micro PLCs
• Micro
3
and Micro
3
C. . . . . . . . . . .J-81
Other PLCs
• Micro-1. . . . . . . . . . . . . . . . . . . . .J-99• FA2J . . . . . . . . . . . . . . . . . . . . . .J-101• FA3S. . . . . . . . . . . . . . . . . . . . . .J-103
Programming Software
• WindLDR™ . . . . . . . . . . . . . . . .J-105
Program
mable Logic Controllers
Programmable Logic Controllers
Selection Guide
J-2
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
IDEC, a pioneer in the micro-PLC market, is proud to offer so many quality micro programmable logic controllers, from the original Micro-1 to the brand new MicroSmart series. Not all information about our older PLCs has been included in this catalog. Please refer to previous catalogs or call IDEC Technical Support with any questions.
Series Appearance Specifications Page
MicroSmart
2 types of CPU modules4 types of Expansion modules J-3
ONC
Available with SX5 Smart I/O modules to communicate with Interbus, DeviceNet, and LONWorks
J-23
Micro
3
and Micro
3
C
J-81
Micro-1
The original micro-PLC J-99
FA2J
Flat-Pak Modular J-101
FA3S
J-103
WindLDR
Software for programming all of IDEC’s PLCs J-105
Selection Guide
NEW!
NEW!
Programmable Logic Controllers
MicroSmart Series
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-3
J
CE Certified
The Next Generation of PLC
Key features of the MicroSmart series include:
• 10, 16, or 24 I/O All-in-one type CPU modules with Sink/Source DC input and Relay Output
• 20 I/O Slim type CPU modules with Sink/Source DC input and Transistor Sink or Source Output
• 20 I/O Slim type CPU modules with Sink/Source DC input and Relay Output with high-speed Transistor Sink or Source Output
• 40 I/OSlim type CPU module with Sink/Source DC input and Transistor Sink or Source Output
• DC Input, Relay Output, Transistor Output, Combination I/O and Analog I/O expansion modules available
• 24 I/O All-in-one CPU expandable to 88 I/O points; 20 I/O slim types expandable up to 148 or 244 I/O; 40 I/O slim type expandable up to 264 I/O points
• Standard RS232 port, optional plug-in RS485/RS232 port• Optional memory cartridge or real-time clock and calendar
cartridge• Data link to other MicroSmart modules, PLCs, PCs or HG
series operator interfaces• UL1604 approved for Class 1–Div. 2 hazardous locations• Compact size
UL ListedFile No. E211795
MicroSmart
CPU MODULES
INPUTMODULES
COMBINATION I/O MODULES
OUTPUT MODULES
Programmable Logic Controllers
MicroSmart Series
J-4
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Part Numbers: MicroSmart
Item Description Part Number
CPU modules
10 I/O All-in-one Type
FC4A-C10R2
16 I/O All-in-one Type
FC4A-C16R2
24 I/O All-in-one Type
FC4A-C24R2
20 I/O Slim Type, Transistor Sink Output
FC4A-D20KS
20 I/O Slim Type, Transistor Source Output
FC4A-D20S3
20 I/O Slim Type, Relay Sink Output
FC4A-D20RK1
20 I/O Slim Type, Relay Source Output
FC4A-D20RS1
40 I/O Slim Type, Transistor Sink Output
FC4A-D40K3
40 I/O Slim Type, Transistor Source Output
FC4A-D40S3
Input Modules
8-point 24V DC Input, Removable Terminal Block
FC4A-N08B1
16-point 24V DC Input, Removable Terminal Block
FC4A-N16B1
16-point 24V DC Input, MIL Connector
FC4A-N16B3
32-point 24V DC Input, MIL Connector
FC4A-N32B3
Output Modules
8-point Relay Output, Removable Terminal Block
FC4A-R081
16-point Relay Output, Removable Terminal Block
FC4A-R161
8-point Transistor Sink Output, Removable Terminal Block
FC4A-T08K1
8-point Transistor Source Output, Removable Terminal Block
FC4A-T08S1
16-point Transistor Sink Output, MIL Connector
FC4A-T16K3
16-point Transistor Source Output, MIL Connector
FC4A-T16S3
32-point Transistor Sink Output, MIL Connector
FC4A-T32K3
32-point Transistor Source Output, MIL Connector
FC4A-T32S3
Combination I/O Modules4-point 24V DC Input, 4-point Relay Output
FC4A-M08BR1
16-point 24V DC Input, 8-point Relay Output
FC4A-M24BR2
Analog I/O Modules
2-point DC Input, 1-point DC Output
FC4A-L03A1
2-point Thermocouple Resistance Input, 1-point DC Output
FC4A-L03AP1
2-point DC Input
FC4A-J2A1
1-point DC Output
FC4A-K1A1
Programming Software WindLDR 4.10
FC9Y-LP2CDW
HMI Module For displaying and changing required operands
FC4A-PH1
HMI Base Module For mounting HMI module with Slim type CPU module
FC4A-HPH1
ANALOG MODULES HMI MODULE MEMORY CARTRIDGE
CLOCK CARTRIDGE
COMMUNICATION ADAPTERS
Programmable Logic Controllers
MicroSmart Series
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-5
J
Part Numbers: MicroSmart Options
Description Part Number
RS232C Communication Adapter (mini DIN type)
FC4A-PC1
RS485 Communication Adapter (mini DIN type)
FC4A-PC2
RS485 Communication Adapter (screw terminal type)
FC4A-PC3
RS232C Communicator Adapter for Slim Type CPU (mini DIN type)
FC4A-HPC1
RS485 Communication Adapter for Slim Type CPU (mini DIN type)
FC4A-HPC2
RS485 Communication Adapter for Slim Type CPU (terminal block type)
FC4A-HPC3
Clock Cartridge
FC4A-PT1
Memory Cartridge (32KB)
FC4A-PM32
RS232C/RS485 Converter (modem connectable)
FC2A-MD1
26-position Connector Socket, MIL Connector for Slim Type CPU (package quantity: 2)
FC4A-PMC26P
26-position Connector Socket, MIL Connector for I/O Modules (package quantity: 2)
FC4A-PMC20P
10-position Terminal Blocks for I/O Modules (package quantity: 2)
FC4A-PMT10P
11-position Terminal Blocks for I/O Modules (package quantity: 2)
FC4A-PMT11P
13-position Terminal Blocks for Slim Type CPU Modules FC4A-D20RK1 and FC4A-D20RS1 (package quantity: 2)
FC4A-PMT13P
16-position Terminal Blocks for Slim Type CPU Module FC4A-D20RK1 (package quantity: 2)
FC4A-PMTK16P
16-position Terminal Blocks for Slim Type CPU Module FC4A-D20RS1 (package quantity: 2)
FC4A-PMTS16P
Analog Voltage Input Cable - 1m (3.28 ft)
FC4A-PMAC2P
Computer LInk Cable 4C - 3m (9.84 ft.)
FC4A-KC4C
Modem Cable 1C - 3m (9.84 ft.)
FC2A-KM1C
RS232C Cable (4-wire) - 1.5m (4.92 ft.)
HD9Z-C52
PLC to IDEC’s HG series Connection Cable - 3m (9.84 ft.) (for 2nd RS232 port only)
HG9Z-XC183
User Communication Cable 1C - 2.4m (7.87 ft.)
FC2A-KP1C
O/I Communication Cable IC - 5m (16.4 ft)
FC4A-KC1C
O/I Communication Cable 2C - 5m (16.4 ft)
FC4A-KC2C
Direct Mounting Strips (package quantity: 2)
FC4A-PSP1P
35mm DIN Rails (aluminum, 1m)
BNDN1000BAA1000
Mounting Clips
BNL6
Screwdriver (3.5)
FC9Z-SD1
Screwdriver (2.5)
FC9Z-SD2
14-point input switch simulator
FC4A-DS824-SW14
9-point input switch simulator
FC4A-DS824-SW9
6-point input switch simulator
FC4A-DS824-SW6
I/O Cables
20-wireShielded 2 m FC9Z-H200A20
Non-shielded 2 m FC9Z-H200B20
26-wireShielded 2 m FC9Z-H200A26
Non-shielded 2 m FC9Z-H200B26
MicroSmart Starter Kit with FC4A-C10R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual
MM-SMART-10
MicroSmart Starter Kit with FC4A-C16R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual
MM-SMART-16
MicroSmart Starter Kit with FC4A-C24R2, WindLDR 4.10, cables, simulator switch, screwdrivers, manual
MM-SMART-24
Programmable Logic Controllers
MicroSmart Series
J-6
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
* CPU module power consumption includes 250 mA sensor power.** CPU module (including 250 mA sensor power) + 4 I/O modules# CPU module + 7 I/O modules
Communication Port 1 Specifications
FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20K3FC4A-D20S3
FC4A-D20RK1FC4A-D20RS1
FC4A-D40KSFC4A-D40S3
CPU
Gen
eral
Spe
cific
atio
ns
Rated Voltage
100-240V AC 24V DC
Allowable Range
85-264V AC 20.4 to 26.4V DC (including ripple)
Rated Frequency
50/60 Hz (47-63 Hz) —
Maximum Input Current
0.25A (85V AC) 0.30A (85V AC) 0.45A (85V AC) ** 0.56A (26.4V DC) # 0.70A (26.4V DC) #
Max. Power Consumption
30VA/264V AC *20VA/100V AC
31VA/264V AC *22VA/100V AC
40VA/264V AC **33VA/100V AC 15W/26.4V DC # 19W/26.4V DC #
Allowable Momentary Power Interruption
20 msec maximum, Level PS-2 (IEC61131) 10 msec (at 24V DC)
Dielectric Strength
Between power and terminal: 1500V AC, 1 minBetween I/O and terminal: 1500V AC, 1 min
Between power and terminal: 500V AC, 1 minBetween I/O and terminal: 1500V AC, 1 min
Insulation Resistance
Between power and terminal: 10 m
Ω
(min), 500V DCBetween I/O and terminal: 10 m
Ω
(min), 500V DCBetween power and terminal: 10 m
Ω
(min)Between I/O and terminal: 10 m
Ω
(min)
Noise Resistance
AC power terminal: 1.5 kV, 50ns to 1µsI/O terminal (coupling clamp): 1.5 kV, 50ns to 1µs
DC power terminals: 1.0 kV, 50 nsec to 1µsecI/O terminals (coupling clamp): 1.5 kV, 50 nsec to 1µsec
Inrush Current
35A max. 35A max. 40A max. 50A maximum (24V DC)
Power Supply Wire UL1015, AWG22, UL1007, AWG18
Operating Temperature 0 to 55°C
Storage Temperature –25 to +70°C
Operating Humidity 30-95% Level RH1 (no condensation)
Altitude Operation: 0 to 2,000m (0 to 6,595 ft)Transport: 0 to 3,000m (0 to 9.840 ft)
Pollution Degree 2 (IEC60664)
Corrosion Immunity Free from corrosive gases
Degree of Protection IP20
Ground Grounding resistance 100Ω maximum
Vibration Resistance DIN rail mounted: 10 to 57Hz / amplitutde 0.075mm, 57 to 150Hz / acceleration 9.8m/s2 (1G)Direct mounted: 2 to 25Hz / amplitude 1.6mm, 25 to 100Hz / acceleration 39.2m/s2 (4B) in each of 3 axes
Shock Resistance 15G, 11ms, 3 shocks in each of 3 axes
Standards EIA RS232C
Maximum Baud Rate 19200 bps
Maintenance Communication Possible
User Communication Possible
Modem Communication Not possible
Data Link Communication Not possible
Cable Special Cables: FC2A-KC4C, FC2A-KP1C, FC4A-KC1C, FC4A-KC2C
Isolation between Internal Circuit and Communication Port Not isolated
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-7
J
FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20K3FC4A-D20S3
FC4A-D20RK1FC4A-D20RS1
FC4A-D40KSFC4A-D40S3
CPU
Fun
ctio
n Sp
ecifi
catio
ns
Control System Stored program system
Instruction words35 basic instructions
38 advanced 40 advanced 46 advanced 53 advanced 70 advanced
Program Capacity 4,800 bytes(800 steps)
15,000 bytes(2,500 steps)
27,000 bytes(4,500 steps)
27,000 bytes(4,500 steps)
31,200 bytes(5,200 steps)
Calculated 6 bytes per step
User ProgramStorage Internal EEPROM, Memory cartridge (option: EEPROM)
Processing Time Basic instruction: 1.65 msec (1000 steps); END processing: 0.64 msec (does not include expansion I/O service, clock function processing, data link processing and interrupt processing)
Expandable I/O Modules – – 4 modules 7 modules
RAM Backup
Backup Data: Internal relay, shift register, counter, data registerBackup Duration: Approx. 30 days (typical) at 25° C after backup battery fully chargedBattery: Lithium secondary batteryCharging Time: Approx. 15 hours for charging from 0% to 90% of full chargeBattery Life: 5 yearsReplaceability: Impossible to replace battery
I/O Points 6 input, 4 output 9 input, 7 output 14 input, 10 outputExpansion: 64 I/O
12 input, 8 outputExpansion: 128 I/O
12 intput, 8 outputExpansion: 224 I/O
24 input, 16 outputExpansion: 224 I/)
Internal Relay 256 1024
Shift Register 64 128
Data Register 400 1300
Expansion Data Register — 6000
Counter 32 100
Timer (1-sec, 100-msec, 10-msec, 1-msec)
32 100
Self-Diagnostic Function
Power failure check, watchdog timer, data link connection, user program EEPROM sum check, timer/counter preset value sum check, user program RAM sum check, keep data, user program syntax, user program writing, CPU module, clock IC, I/O bus initialize, user program execution
Input Filter 3 to 15 msec (1-msec increments)
Catch Input/Interrupt Input 4 input (I2 through I5) Minimum turn on pulse width: 40 µsec maximum Minimum turn off pulse width: 150 µsec maximum
High-Speed Counter
Total 4 points: Single/two-phase selectable: 20kHz (1 point)Single-phase: 5kHz (3 points)
Total 4 points: Single/two-phase selectable: 20kHz (2 points)Single-phase: 5kHz (2 points)
Counting Range 0 to 65535 (16 bits), Operation Mode: Rotary encoder mode and adding counter mode
AnalogPotentiometer
1 point 2 points 1 point
Data Range: 0 to 255
Analog Voltage Input — 1 point, 0 to 10V DC Input Voltage Range, approx. 100kΩ Input
Impedance, data range 0-255 (8 bit)
Pulse Output — 2 points, max. frequency 20kHz
Sensor PowerSupply
24V DC (+10% to -15%), 250 mA, no overload detectionIsolated from the internal circuit —
Port 1 RS232C Maintenance Communication, User Communication, Modem Communication
Port 2 (optional) — Possible: RS232C or RS485 (Maintenance communication, data link)
Clock Function (optional) Possible
Select either clock or memory cartridge
PossibleYear, month, day, day of week, hour, minute, second
Memory Cartridge (optional) Possible
HMI Module (optional) Possible Possible using HMI Base Module
Programmable Logic Controllers MicroSmart Series
J-8 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
DC Input Specifications for CPU modules
FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20K3FC4A-D20S3
FC4A-D20RK1FC4A-D20RS1
FC4A-D40KSFC4A-D40S3
Rated Input Voltage 24V DC (both sink and source)
Allowable Range 20.4 to 28.8V DC 20.4 to 26.4V DC
Rated Input Current I0, I1: 11mA, I2 to I7, I10 to I15: 7mA I0, I1, I6, I7: 5mA/point, I2 to I5, I10 to I27: 7mA/point
Input Impedance I0, I1: 2.1kΩ, I2 to I7, I10 to I15: 3.4kΩ I0, I1, I6, I7: 5.7kΩ, I2 to I5, I10 to I27: 3.4kΩ
OFF/ON TimeOFF/ON I0 to I5: 35µsec + Filter Value
I6, I7, I10 to I15: 40µsec + Filter ValueI0 to I7: 35µsec + Filter ValueI10 to I27: 40µsec + Filter Value
ON/OFF I0, I1: 45µsec + Filter ValueI2 to I7, I10 to I15: 150µsec + Filter Value
I0, I1, I6, I7: 45µsec + Filter ValueI2 to I5, I10 to I27: 150µsec + Filter Value
Input Points 6 inputs6/1 common
9 inputs9/1 common
14 inputs 14/1 common
12 inputs12/1 common
12 inputs12/1 common
24 inputs,12/1 common
ConnectorOn Mother Board —
FL26A2MA (Oki Electric Cable)
MC1.5/13-G-3.81BK(Phoenix Contact)
FL26A2MA(Oki Electric Cable)
Insertion/Removal Durability — 100 times minimum
Isolation Between input terminals: Not isolatedInternal circuit: Photocoupler isolated
Input Type Type 1 (IEC61131)
External Load for I/O Interconnection Not needed
Signal Determination Method Static
Effect of Improper Input Connection Both sinking and sourcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused.
Cable Length 3m (9.84 ft)
Relay Output Specifications for CPU modules
FC4A-C10R2 FC4A-C16R2 FC4A-C24R2 FC4A-D20RK1FC4A-D20RS1
Output Points 4 points 7 points 10 points 8 points
Output Points per Common
COM0 3 points 4 points 4 points 2 points(transistor output)
COM1 1 point 2 points 4 points 3 points
COM2 – 1 point 1 point 2 points
COM3 – – 1 point 1 point
Type of Output 1NO
Maximum Load Current 1 point 2A
Common 8A
Minimum Switching Load 0.1mA, 0.1V DC (reference value)
Initial Contact Resistance 30mΩ maximum
Electrical Life 100,000 operations (rated load) @ 1,800 operations/hr
Mechanical Life 200,000 operations (no load) @ 18,000 operations/hr
Rated Load Current (resistive/inductive) 240V AC/2A, 24V DC/2A (30V DC / 2A)
Dielectric StrengthBetween output and terminals: 1500V AC, 1 minute
Between output terminals and internal circuit: 1500V AC, 1 minuteBetween output terminals (COMs): 1500 V AC, 1 minute
Connector
On Mother Board — MC1.5/16-G-3.81BK
(Phoenix Contact)
Insertion/Removal Durability
— 100 times minimum
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-9
J
Transistor Sink and Source Output Specifications for CPU modules
FC4A-D20K3FC4A-D20S3
FC4A-D20RK1FC4A-D20RS1
FC4A-D40K3FC4A-D40S3
Output Points and Common Line 8 points, 8/1 common 2 points, 2/1 common 16 points, 8/1 common
Type of Output FC4A-D20K3/D20RK1/D40K3 = Sink OutputFC4A-D20S3/D20RS1/D40S3 = Source Output
Rated Load Voltage 24V DC
Operating Load Voltage Range 20.4 to 28.8V DC
Rated Load Current 0.3A per output point
Maximum Load Current 1A per common line
Voltage Drop (ON Voltage) 1V maximum (voltage between COM and output terminals when output is on)
Inrush Current 1A maximum
Leakage Current 0.1 mA maximum
Clamping Voltage 39V±1V
Maximum Lamp Load 8W
Inductive Load L/R = 10ms (28.8V DC, 1Hz)
External Current Draw 100mA maximum, 24V DC (power voltage at the +V or -V terminal)
Isolation Between output terminal and internal circuit: Photocoupler isolatedBetween output terminals: Not isolated
ConnectorOn Mother Board FL26A2MA
(Oki Electric Cable)MC1.5/16-G-3.81BK(Phoenix Contact)
FL26A2MA(Oki Electric Cable)
Insertion/Removal Durability 100 times minimum
Output DelayTurn ON time 5 µs (Q0, Q1), 300 µs max (Q2 to Q7, Q10 to Q17)
Turn OFF time 5 µs (Q0, Q1), 300 µs max (Q2 to Q7, Q10 to Q17)
Programmable Logic Controllers MicroSmart Series
J-10 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
DC Input Module Specifications
Relay Output Module Specifications
FC4A-N08B1 FC4A-N16B1 FC4A-N16B3 FC4A-N32B3
Input Points 8 points (8/1 common) 16 points (16/1 common) 32 points (16/1 common)
Rated Input Voltage 24V DC sink/source input signal
Input Voltage Range 20.4 to 28.8V DC
Rated Input Current 7mA/point (24V DC) 5mA/point (24V DC)
Input Impedance 3.4 kΩ 4.4 kΩ
Input Delay Time (24V DC) ON time: 4 msecOFF time: 4 msec
Isolation Between input terminals: Not isolatedInternal circuit: Photocoupler isolated
External Load for I/O Interconnection Not needed
Signal Determination Method Static
Effect of Improper Input Connection Both sinking and courcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused.
Cable Length 3m (9.84 ft) in compliance with electromagnetic immunity
ConnectorOn Mother Board MC1.5/10-G-3.81BK (Phoenix contact) FL20A2MA (Oki Electric Cable)
Insertion/Removal Durability 100 times minimum
Internal Current Draw
All Inputs ON 25 mA (5V DC)0 mA (24V DC)
40 mA (5V DC)0 mA (24V DC)
35 mA (5V DC)0 mA (24V DC)
65 mA (5V DC)0 mA (24V DC)
All Inputs OFF 5 mA (5V DC)0 mA (24V DC)
5 mA (5V DC)0 mA (24V DC)
5 mA (5V DC)0 mA (24V DC)
10 mA (5V DC)0 mA (24V DC)
Weight 85g 100g 65g 100g
FC4A-R08B1 FC4A-R16B1
Output Points and Common Lines 8 points (4/1 common) 16 points (8/1 common)
Output Type 1NO
Maximum Load Currentper point 2A
per common 7A 8A
Minimum Switching Load 0.1 mA/0.1V DC (reference value)
Initial Contact Resistance 30 mΩ maximum
Electrical Life 100,000 operations minimum(rated load 1,800 operations/hour)
Mechanical Life 20,000,000 operations minimum(no load 18,000 operations/hour)
Rated Load (resistive/inductive) 240V AC/2A, 30V DC/2A
Dielectric StrengthBetween output and terminals: 1500V AC, 1 minute
Between output terminals and internal circuit: 1500V AC, 1 minuteBetween output terminals (COMs): 1500 V AC, 1 minute
ConnectorOn Mother Board MC1.5/11-G-3.81BK
(Phoenix contact)MC1.5/10-G-3.81BK(Phoenix contact)
Insertion/Removal Durability 100 times minimum
Internal Current DrawAll Inputs ON 30 mA (5V DC)
40 mA (24V DC)45 mA (5V DC)
75 mA (24V DC)
All Inputs OFF 5 mA (5V DC)0 mA (24V DC)
5 mA (5V DC)0 mA (24V DC)
Weight 110g 145g
Specifications — Expansion Modules
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-11
J
Transistor Output Module Specifications
FC4A-T08K1FC4A-T08S1
FC4A-T16K3FC4A-T16S3
FC4A-T32K3FC4A-T32S3
Output Points 8 points (8/1 common) 16 points (16/1 common) 32 points (16/1 common)
Output Type FC4A-TK: Transistor sink outputFC4A-TS: Transistor source output
Rated Load Voltage 24V DC
Operating Load Voltage Range 20.4 to 28.8V DC
Rated Load Current 0.3A per output point (at 28.8V DC) 0.1A per output point (at 28.8V DC)
Maximum Load Currentper point 0.36A (at28.8V DC) 0.12A (at 28.8V DC)
per common 3A (at 28.8V DC) 1A (at 28.8V DC)
Voltage Drop (ON Voltage) 1V maximum (between COM and output terminals when output is on)
Inrush Current 1A maximum
Leakage Current 0.1A maximum
Clamping Voltage 39V ± 1V
Maximum Clamping Load 8W
Inductive Load L/R = 10 msec (DC 28.8V, 1Hz)
External Current Draw FC4A-TK: 100mA maximum, 24V DC (power voltage at the +V)FC4A-TS: 100mA maximum, 24V DC (power voltage at the -V)
Isolation Between output terminal and internal circuit: Photocoupler isolatedBetween output terminals: Not isolated
Connector
Type (on Mother Board)
MC1.5/10-G-3.81BK (Phoenix contact) FL20A2MA (Oki Electric Cable)
Insertion/Removal Durability 100 times minimum
Internal Current DrawAll Inputs ON 10mA (5V DC)
20mA (24V DC)10mA (5V DC)
40mA (24V DC)20mA (5V DC)
70mA (24V DC)
All Inputs OFF 5mA (5V DC)0mA (24V DC)
5mA (5V DC)0mA (24V DC)
10mA (5V DC)0mA (24V DC)
Output DelayTurn ON time 300µsec maximum
Turn OFF time 300µsec maximum
Weight 85g 70g 105g
Programmable Logic Controllers MicroSmart Series
J-12 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Combination I/O Module Specifications
FC4A-M08BR1 FC4A-M24BR2
DC
Inpu
t Spe
cific
atio
ns
Input Points 4 points (4/1 common) 16 points (16/1 common)
Rated Input Voltage 24V DC sink/source input signal
Input Voltage Range 20.4 to 28.8V DC
Range Input Current 7 mA/point (24V DC)
Input Impedance 3.4 kΩ
Turn ON Time 4 msec (24V DC)
Turn OFF Time 4 msec (24V DC)
Isolation Between input terminals: Not isolatedInternal circuit: Photocoupler isolated
External Load for I/O Interconnection Not needed
Signal Determination Method Static
Effect of Improper Input Connection Both sinking and sourcing input signals can be connected. If any input exceeding the rated value is applied, permanent damage may be caused.
Cable Length 3m (9.84 ft) in compliance with electromagnetic immunity
Rela
y O
utpu
t Spe
cific
atio
ns
Output Points 4 points (4/1 common) 8 points (8/1 common)
Output Type 1NO
Maximum Load Currentper point 2A
per common 7A
Minimum Switching Load 0.1 mA/0.1V DC (reference value)
Initial Contact Resistance 30 mΩ maximum
Electrical Life 100,000 operations minimum (rated load 1,800 operations/hour)
Mechanical Life 20,000,000 operations minimum (no load 18,000 operations/hour)
Rated Load (resistive/inductive) 240V AC/2A, 30V DC/2A
Dielectric StrengthBetween output and or terminals: 1,500V AC, 1 minute
Between output terminal and internal circuit: 1,500V AC, 1 minuteBetween output terminal (COMs): 1,500V AC, 1 minute
Connectoron Mother Board MC1.5/11-G-3.81BK
(Phoenix contact)Input: F6018-17P (Fujicon)
Output: F6018-11P (Fujicon)
Insertion/Removal Durability 100 times minimum —
Internal Current DrawAll Inputs ON 25 mA (5V DC)
20 mA (24V DC)65 mA (5V DC)
45 mA (24V DC)
All Inputs OFF 5 mA (5V DC)0 mA (24V DC)
10 mA (5V DC)0 mA (24V DC)
Weight 95g 140g
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-13
J
Analog I/O Module Specifications
Analog Output Specifications
FC4A-L03A1 FC4A-L03AP1 FC4A-J2A1 FC4A-K1A1
Input Points 2 2 2 —
Input Signal TypeVoltage Input (0 to 10V DC)Current Input
(4 to 20 mA DC)
Thermocouple Resistance
Thermometer
Voltage Input (0 to 10V DC)Current Input
(4 to 20 mA DC)—
Output Points 1 1 — 1
Output Signal TypeVoltage Output(0 to 10V DC)
Current Output (4 to 20 mA DC)
Voltage Output (0 to 10V DC)
Current Output (4 to 20 mA DC)
—Voltage Output (0 to 10V DC)
Current Output (4 to 20 mA DC)
Rated Power Voltage 24V DC
Allowable Voltage Range 20.4 to 28.8V DC
ConnectorOn Mother Board MC1.5/11-G-3.81BK (Phoenix contact)
Insertion/Removal Durability 100 times minimum
Internal Current Draw
Internal Power 50 mA (5V DC)0 mA (24V DC)
50 mA (5V DC)0 mA (24V DC)
50 mA (5V DC)0 mA (24V DC)
50 mA (5V DC)0 mA (24V DC)
External Power 40 mA (24V DC) 40 mA (24V DC) 40 mA (24V DC) 40 mA (24V DC)
Weight 85g
FC4A-L03A1, FC4A-L03AP1, FC4A-K1A1
Output Signal Type Voltage Output Current Output
Output Range 0 to 10V DC 4 to 20 mA DC
Load Impedance 2 kΩ minimum 300Ω maximum
Applicable Load Type Resistive load
Setting Time 20 msec
Total Output System Transfer Time 20 msec + 1 scan time
Output Error
Maximum Error at 25°C ±0.2% of full scale
Temperature Coefficient ±0.015% of full scale/°C
Repeatabliity after Stabilization Time ±0.5% of full scale
Output Voltage Drop ±1% of full scale —
Non-lineality ±0.2% of full scale
Output Ripple 1 LSB maximum
Overshoot 0%
Total Error ±1% of full scale
Data
Digital Resolution 4096 increments (12 bits)
Output Value of LSB 2.5 mV 4 µA
Data Type in Application Program 0 to 4095 (12-bit data); -32768 to 32767 (optional range designation)See note on page J-14
Monotonicity Yes
Current Loop Open — Detectable (See note on page J-14)
Noise
Maximum Termporary Deviation during Electrical Noise Tests ±3% max. when a 500V clamp is applied to the power and I/O wiring
Cable Twisted pair shielded cable recommended for inproved noise immunity
Crosstalk No crosstalk because of 1 channel output
Dielectric Strength 500V between output and power circuit
Type of Protection Photocoupler between output and internal circuit
Effect of Improper Output Connection No damage
Selection of Analog Output Signal Type Using software programming
Calibration or Verification to Maintain Rated Accuracy Impossible (approx. 10 years)
Programmable Logic Controllers MicroSmart Series
J-14 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Analog Input Specifications
FC4A-L03A1, FC4A-J2A1, FC4A-L03AP1 FC4A-L03AP1 only
Input Signal Type Voltage Input Current Input Thermocouple Resistance Thermometer
Input Range 0 to 10V DC 4 to 20 mA DCType K (0 to 1300°C)Type J (0 to 1200°C)Type T (0 to 400°C)
Pt 100 3-wire type(-100 to 500°C)
Input Impedance 1 MΩ minimum 10Ω 1 MΩ minimum 1 MΩ minimum
Allowable Conductor Resistance — — — 200Ω maximum
Input Detection Current — — — 1.0 mA maximum
Sample Duration Time 16 msec maximum 50 msec maximum
Sample Repetition Time 16 msec maximum 50 msec maximum
Total Input System Transfer Time 32 msec + 1 scan time * 100 msec + 1 scan time *
Type of Input Single-ended input Differential input
Operating Mode Self scan
Conversion Method ∑∆ type ADC
Input Error
Maximum Error at 25°C ±0.2% of full scale±0.2% of full scale plus
reference junction compensa-tion accuracy (±4°C maximum)
±0.2% of full scale
Temperature Coefficient ±0.006% of full scale / °C
Repeatabliity after Stabilization Time ±0.5% of full sclae
Non-lineality ±0.2% of full scale
Maximum Error ±1% of full scale
Data
Digital Resoltuion 4096 increments (12 bits)
Input Value of LSB 2.5 mV 4 µA K: 0.325°C; J: 0.300°C; T: 0.100°C 0.15°C
Data Type in Application Program 0 to 4095 (12-bit data); -32768 to 32767 (optional range designation) **
Monotonicity Yes
Input Data Out of Range Detectable #
NoiseResistance
Maximum Termporary Deviation duringElectrical Noise Tests
±3% maximum when a 500V clamp voltage is applied to the power and I/O wiring Accuracy is not assured when noise is applied
Common Mode Characteristics Common mode reject ratio (CMRR): -50 dB
Common Mode Voltage 16V DC
Input Filter No
Cable Twisted pair shielded cable recommended for improved noise immunity —
Crosstalk 2 LSB maximum
Dielectric Strength 500V between input and power circuit
Type of Protection Photocoupler between input and internal circuit
Effect of Improper Input Connection No damage
Maximum Permanent Allowed Overload (No damage) 13V DC 40 mA DC —
Selection of Analog Input Signal Type Using software programming
Calibration or Verification to Maintain Rated Accuracy Impossible (approx. 10 years)
NOTES FOR ANALOG EXPANSION UNITS:* Total input system transfer time = Sample repetition time x 2 + 1 scan time** The 12-bit data (0 to 4095) processed in the analog I/O module can be linear-converted to a value between -32768 and 32767. Select the optional
range designations and analog I/O data minumum and maximum values by using data registers allocated to analog I/O modules.# When an error is detected, a corresponding error code is sorted to a data register allocated to analog I/O operating status.
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-15
J
Communication Adapter and Communication Module Specifications
Optional HMI Module Specifications
Optional Memory Cartridge Specificaions
Optional Clock Cartridge Specificaions
FC4A-PC1FC4A-HPC1
FC4A-PC2FC4A-HPC2
FC4A-PC3FC4A-HPC3
Standards EIA RS232C EIA RS485 EIA RS485
Maximum Baud Rate 19200 bps 19200 bps Computer link: 19200 bpsData link: 38400 bps
Maintenance Communication Possible Possible Possible
User Communication Possible Impossible Impossible
Modem Communication Possible Impossible Impossible
Data Link Communication Impossible Impossible Possible
Maximum Cable Length Use FC2A-KC4C, FC2A-KM1C, FC4A-KC1C, FC4A-KC2C Use FC2A-KP1C 200m
Quantity of Slave Stations — — 31
Isolation between Internal Circuit and Communication Port Not isolated
Recommended Cable for RS485 — Twisted-piar shielded cable with a minimum core wire of 0.3 mm2
Conductor Resistance — 85 Ω/km maximum
Shield Resistance — 20Ω/km maximum
FC4A-PH1
Power Voltage 5V DC (supplied from the CPU module)
Internal Current Draw 200mA DC
Weight 20g
FC4A-PM32
Memory Type EEPROM
Accessible Memory Capacity 32 KB
Hardware for Storing Data CPU module
Software for Storing Data WindLDR
Quantity of Store Programs One user program can be stored on one memory cartridge
FC4A-PT1
Accuracy ±30 sec/month (typical) at 25°C
Backup Duration Approx. 30 days (typical) at 25°C after backup battery fully charged
Battery Lithium secondary battery
Charging Time Approx. 10 hours for charging from 0% to 90% of full charge
Replaceability Impossible to replace battery
Programmable Logic Controllers MicroSmart Series
J-16 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
CPU Modules:
Expansion Modules:
Dimensions
90.0
4.5*
80.0 70.0
FC4A-C10R2, FC4A-C16R2
95.0
90.0
70.0
FC4A-C24R2
35.4
90.0
70.011.3
FC4A-D20K3, FC4A-D20S3
47.5
90.0
70.014.6
FC4A-D20RK1, FC4A-D20RS1
47.5
90.0
70.011.3
FC4A-D40K3, FC4A-D40S3
70.014.623.53.8
90.0
4.5*
FC4A-N08B1, FC4A-T08K1, FC4A-M08BR1,FC4A-L03AP1, FC4A-K1A1, FC4A-R081FC4A-T08S1, FC4A-L03A1, FC4A-J2A1
70.014.623.53.8
90.0
FC4A-N16B1, FC4A-R161
70.01.039.13.8
90.0
FC4A-M24BR2
70.011.317.63.8
90.0
FC4A-N16B3, FC4A-T16K3, FC4A-T16S3
70.011.329.73.8
90.0
FC4A-N32B3, FC4A-T32K3, FC4A-T32S3
70.0
4.5*
90.0
22.5 13.9
FC4A-HPC1, FC4A-HPC2, FC4A-HPC3
71.0
90.0
38.0 13.9
FC4A-HPH1
95.0
DIN RailBNL6P Mounting Clip
23.5 23.5 9.09.0
90.0
45.0
35.0
4.5*
EXAMPLE: This figure illustrates a system setup with the FC4A-C24R2 All-in-one type CPU, an 8-point relay output module, and a 16-point DC input module, mounted on a 35mm DIN rail using BNL6P mounting clips.
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-17
J
CPU Modules:
Expansion Modules:
Mounting Hole Layout
90.0
83.0
68.0
80.0
FC4A-C10R2FC4A-C16R2
90.0
83.0
83.0
95.0
2-ø4.3
FC4A-C24R2
103.
090
.0
35.424.1
3.0
2-ø4.3
FC4A-C20K3FC4A-D20S3
90.0
103.
0
47.524.1
2-ø4.3
3.0
FC4A-C20RK1, FC4A-D40K3FC4A-C20RS1, FC4A-D40S3
23.56.3
3.0
90.0
103.
0
2-ø4.3
FC4A-N08B1, FC4A-N16B1, FC4A-R081, FC4A-R161, FC4A-T08K1, FC4A-T08S1, FC4A-M08BR1, FC4A-L03A1 FC4A-L03AP1, FC4A-J2A1, FC4A-K1A1
90.0
103.
0
17.66.3 2-ø4.3
3.0
FC4A-N16B3FC4A-T16K3FC4A-T16S3
29.76.3
3.0
90.0
103.
0
2-ø4.3
FC4A-N32B3FC4A-T32K3FC4A-T32S3
22.54.8
3.0
90.0
103.
0
2-ø4.339.16.3
3.0
90.0
103.
0
2-ø4.3
FC4A-M24BR2FC4A-HP1CFC4A-HPC2FC4A-HPC3
38.020.3
3.0
90.0
103.
0
2-ø4.3
FC4A-HPH1
23.5 23.5 23.512.3
15.3 23.5 23.5 23.583.03.0 3.0 3.0 3.0
103.
0
83.0
10-ø4.3
41.8
3.0 3.0 3.0 3.03.0
41.8 17.6 17.6 29.7
103.
0
17.6 17.6 29.7
EXAMPLE:Mounting hole layout for FC4A-C24R2 and 23.5mm-wide I/O modules.
EXAMPLE:Mounting hole layout for, from left, FC4A-HPH1, FC4A-D20K3, FC4A-N16B3, FC4A-N32B3, and FC4A-M24R2 modules.
Programmable Logic Controllers MicroSmart Series
J-18 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
I/O Usage Limits
All-in-one Type CPU Modules:
Input Internal Circuits
Usage Limits
Input Voltage (V DC)
28.8V26.4V24.0V
0 50% 100%
Ambient temperature 55°C
Input Voltage (V DC)
28.8V
26.4V
0 50% 100%
Ambient temperature 55°C
I/O Simultaneous ON Ratio (%)
Ambient temperature 45°C
Input Voltage (V DC)
28.8V26.4V24.0V
0 50% 100%
Ambient temperature 30°C
Input Voltage (V DC)
28.8V26.4V24.0V
0 50% 100%
Input Voltage (V DC)
28.8V26.4V24.0V
0 50% 100%
Ambient temperature 55°C
Ambient temperature 45°C
Input Voltage (V DC)
28.8V26.4V24.0V
0 50% 100%
Input Voltage (V DC)
28.8V
26.4V
0 50% 100%
Ambient temperature 45°C
Ambient temperature
55°C
Ambient temperature
55°C
Ambient temperature
55°C
Ambient temperature
55°C
Ambient temperature
55°C
Ambient temperature
55°C
Ambient temperature
55°C
I/O Simultaneous ON Ratio (%)
Input Voltage (V DC)
26.4V
24.0V
0 50% 100%
Ambient temperature 40°C
I/O Simultaneous ON Ratio (%)
I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%)
I/O Simultaneous ON Ratio (%) I/O Simultaneous ON Ratio (%)
Input Voltage (V DC)
26.4V
24.0V
0 50% 100%
Ambient temperature 40°C
Input Voltage (V DC)
28.8V
26.4V
0 50% 100%
Ambient temperature 45°C
I/O Simultaneous ON Ratio (%)
Input Voltage (V DC)
26.4V
24.0V
0 50% 100%
Ambient temperature 55°C
Slim Type CPU Modules:
Input Usage Limits
When using at an operating ambient temperature above 40°C, reduce the input voltage or the quantity of I/O points that turn on simultaneously.
Internal Circuits
Inte
rnal
Circ
uit
Input1.8 kΩ
I0, I1
COM
ALL-IN-ONE TYPE
Inte
rnal
Circ
uit
COM
Input3.3 kΩ
I2 to I15
Inte
rnal
Circ
uit
Input4.7 kΩ
I0, I1, I6, I7
COM
SLIM TYPE
Inte
rnal
Circ
uit
COM
Input3.3 kΩ
I2 to I5 and I10 to I27
SINK OUTPUT
InternalCircuit
+V
Output
COM(-)
InternalCircuit
-V
Output
COM(+)SOURCE OUTPUT
Output Internal Circuit (Slim Type)
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-19
J
Input Internal Circuits (Expansion Modules) Output Internal Circuits
Analog I/O Module
Inte
rnal
Circ
uit
COM
Input3.3 kΩ
FC4A-N081, FC4A-N16B1
Inte
rnal
Circ
uit
COM
Input4.3 kΩ
FC4A-N16B3, FC4A-N32B3
Inte
rnal
Circ
uit
COM
Input3.3 kΩ
FC4A-M08BR1, FC4A-M24BR2
InternalCircuit
+V
Output
COM(-)
FC4A-T08K1, FC4A-T16K3, FC4A-T32K3
InternalCircuit
-V
Output
COM(+)
FC4A-T08S1, FC4A-T16S3, FC4A-T32S3
+
-
Out
put C
ircui
t
NC(A)1 kΩ
15 MΩ
+ (B')
- (B)
1 kΩ
1 kΩ10 Ω
+V2 +V1
- V1
Mul
tiple
xer
Input Data
InputSelectionSignal
Input Circuit
Output Circuit
Programmable Logic Controllers MicroSmart Series
J-20 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Basic Instruction List
Symbol Function Qty. of Bytes
LOD Stores intermediate results and reads contact status 6
LODN Stores intermediate results and reads inverted contact status 6
OUT Outputs the result of bit logical operation 6
OUTN Outputs the inverted result of bit logical operation 6
SET Sets output, internal relay, or shift register bit 6
RST Resets output, internal relay, or shift register bit 6
AND Series connection of NO contact 4
ANDN Series connection of NC contact 4
OR Parallel connection of NO contact 4
ORN Parallel connection of NC contact 4
AND • LOD Series connection of circuit blocks 5
OR • LOD Parallel connection of circuit blocks 5
BPS Saves the result of bit logical operation temporarily 5
BRD Reads the result of bit logical operation which was saved temporarily 3
BPP Restores the result of bit logical operation which was saved temporarily 2
TML Subracting 1-sec timer (0 to 65535 sec) 4
TIM Subtracting 100-msec timer (0 to 6553.5 sec) 4
TMH Subtracting 10-msec timer (0 to 655.35 sec) 4
TMS Subtracting 1-msec timer (0 to 65.535 sec) 4
CNT Adding counter (0 to 65535) 4
CDP Dual pulse reversible counter (0 to 65535) 4
CUD Up/down selection reversible counter (0 to 65535) 4
CC= Equal to comparison of counter current value 7
CC≥ Greater than or equal to comparison of counter current value 7
DC= Equal to comparison of data register value 8
DC≥ Greater than or equal to comparison of data register value 8
SFR Forward shift register 6
SFRN Reverse shift register 6
SOTU Rising-edge differentiation output 5
SOTD Falling-edge differentiation output 5
JMP Jumps a designated program area 4
JEND Ends a jump instruciton 4
MCS Starts a master control 4
MCR Ends a master control 4
END Ends a program 2
Programming Instructions
Programmable Logic Controllers MicroSmart Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-21
J
Advanced Instruction List
Function Qty. of Bytes
All-in-one Type Slim Type
Symbol FC4A-C10R2
FC4A-C16R2
FC4A-C24R2
FC4A-D20K3FC4A-D20S3
FC4A-D20RK1FC4A-D20RS1FC4A-D40K3FC4A-D40S3
NOP No Operation 2
MOV Move 16
MOVN Move Not 16
IMOV Indirect Move 24-28
IMOVN Indirect Move Not 24-28
IBMV Indirect Bit Move 24 — — — —
IBMVN Indirect Bit Move Not 24 — — — —
BMOV Block Move 18 — — — —
CMP= Compare Equal To 20
CMO<> Compare Unequal To 20
CMP< Compare Less Than 20
CMP> Compare Greater Than 20
CMP<= Compare Less Than or Equal To 20
CMP>= Compare Greater Than or Equal To 20
ICMP>= Interval Compare Greater Than or Equal To 22 — — — —
ADD Addition 20
SUB Subtraction 20
MUL Multiplication 20
DIV Division 20
ANDW AND Word 20
ORW OR Word 20
XORW Exclusive OR Word 20
SFTL Shift Left 12
SFTR Shift Right 12
BCDLS BCD Left Shift 14 — — — —
WSFT Word Shift 18 — — — —
ROTL Rotate Left 12
ROTR Rotate Right 12
HTOB Hex to BCD 14
HTOA Hex to ASCII 18
BTOH BCD to Hex 14
BTOA BCD to ASCII 18
ATOH ASCII to Hex 18
ATOB ASCII to BCD 18
ENCO Encode 16 — — — —
DECO Decode 16 — — — —
TXD1 Transmit 1 21-819
TXD2 Transmit 2 21-819 —
Not applicable to previously released CPU modules FC4A-C10R2B, FC4A-C16R2B, or FC4A-C24R2B. Applicable only to newer MicroSmart All-in-one-type CPU modules.
Programmable Logic Controllers MicroSmart Series
J-22 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Advanced Instruction List, continued
Function Qty. of Bytes
All-in-one Type Slim Type
Symbol FC4A-C10R2
FC4A-C16R2
FC4A-C24R2
FC4A-D20K3FC4A-D20S3
FC4A-D20RK1FC4A-D20RS1FC4A-D40K3FC4A-D40S3
RXD1 Receive 1 21-819
RXD2 Receive 2 21-819 —
LABEL Label 8
LJMP Label Jump 10
LCAL Label Call 10
LRET Label Return 6
ROOT Root 14
DISP Display 16 — —
DGRD Digital Read 20 — —
WKTBL Week Table 13-89
WKTIM Week Timer 24
PULS1 Pulse Output 1 12 — — —
PULS2 Pulse Output 2 12 — — —
PWM1 Pulse Width Modulation 1 24 — — —
PWM2 Pulse Width Modulation 2 24 — — —
RAMP Ramp Pulse Output 14 — — —
ZRN1 Zero Return 1 18 — — — —
ZRN2 Zero Return 2 18 — — — —
XYFS XY Format Set 24-124 — —
CVXTY Convert X to Y 18 — —
CVYTX Convery Y to X 18 — —
PID PID Control 26 — —
IOREF I/O Refresh 16
BCNT Bit Count 18 — — — —
ALT Alternate Output 10 — — — —
DTML 1-sec Dual Timer 22 — — — —
DTIM 100-msec Dual Timer 22 — — — —
DTMH 10-msec Dual Timer 22 — — — —
DTMS 1-msec Dual Timer 22 — — — —
TTIM Teaching Timer 10 — — — —
DI Disable Interrupt 8 — — — —
EI Enable Interrupt 8 — — — —
Not applicable to previously released CPU modules FC4A-C10R2B, FC4A-C16R2B, or FC4A-C24R2B. Applicable only to newer MicroSmart All-in-one-type CPU modules.
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-23
J Hardware Features
•Digital I/O- 8, 16, and 32 point cards- 224 inputs and outputs, 480 with expansion power supply
•Analog I/O- up to 42 analog inputs or 14 analog outputs- 0-5V, 0-10V, ±5V, ±10V, 4-20mA
•Built-In Communications Ports- 2 RS232 (programming port, ASCII, printer and modem ready)- 1 RS485 (programming port and data link)
•Build-in High-Speed Counter- 1 channel, 10kHz, 16-bit resolution
•Memory- 16K words (8K steps) user program capacity- Flash miniature memory card slot (FC3A-CP2KM/SM only)
•Realtime Calendar/Clock, Y2K compliant•Password Protection•PID Algorithm
•Networking ONC capable of communicating with various standard networks:
• DeviceNet • INTERBUS • LONWORKS
•Programming Software; WindLDR® 4.10 • Programs all IDEC PLCs• Windows-based (compatible with Windows 3.10, 3.11,
Win 95, Win-98, Win-2000, or Win-NT 4.0)
•Programming Instructions• Transmit/Receive• Built-in X/Y Conversion • Sub-Routine Call/Return for Modular Programming• Square Root• 16- and 32-bit Math, Add, Sub, Mult, Div• Data Conversion to/from Dec, Hex, BCD, ASCII• Block Move• Summation• Averaging• Day of Week Program Scheduling
•Built-in Hayes "AT" command set for modem dialup/pager applications
OpenNet Controller(without memory card connector)
OpenNet Controller
FC3A-CP2KFC3A-CP2S
FC3A-CP2KMFC3A-CP2SM
Flash memory card ready
CPU
s
FC3A-CP2K High-speed counter sink output, no memory card connector
FC3A-CP2KM High-speed counter sink output with memory card connector
FC3A-CP2S High-speed counter source output, no memory card connector
FC3A-CP2SM High-speed counter source output with memory card connector
Elec
tric
al S
peci
ficat
ions
Rated Voltage 24V DC (19-30V DC, including ripple)
Maximum Input Current 1.5A at 24V DC
Reverse Polarity Protection Prevents damage if incorrectly wired.
Operating Temperature 0 to +55°C
Storage Temperature -25 to +70°C
Relative Humidity 30 to 95% (non-condensing)
Vibration Resistance10 to 57 Hz, amplitude 0.075mm 57 to 150 Hz 9.8 m/sec2 10 sweep cycles/axis (IEC 1131)
Shock Resistance 147 m/sec2, 11 ms3 shocks each in 3 axes (IEC 1131)
Dielectric Strength Between power terminal and FG: 500V AC, 1 minBetween I/O terminal and FG: 1500V AC, 1 min
Ground Grounding resistance 100Ω (maximum)
Mounting Style 35mm DIN rail
OpenNet Controller(with memory card connector)
CE Certified
UL ListedFile No. E102342
Programmable Logic Controllers ONC Series
J-24 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
PS5R Power Supply
PS5R
-D24 Wattage & Current Ratings 50W, 2.1A
Rating UL 508 listed
Mounting DIN rail mountable
Standard ONC CPU
Gen
eral
ON
C Sp
ecifi
catio
ns
Available Instructions 37 basic, 65 advanced (PID, square root, subroutine calls, etc.)
User Program Capacity 16K words flash memory
Memory (Miniature Card) 2, 4 and 8MB; 5V type
Average Scan Time 1 ms or greater
Input 224 points (I0-I277)
Output 224 points (Q0-Q277)
Total I/O Points Using expansion power supply: 480 I/O points
Internal Relay 2048 (M0-M2557)
Special Internal Relay 192 (M8000-M8237)
Shift Register 256 (R0-R255)
Timer 256 (T0-T255; 1-sec, 100-msec, 10-msec, 1-msec)
Counter 256 (C0-C255; adding, dual pulse reversible, up/down selection reversible)
Data Register 8000 (D0-D7999)
Link Register 256 master (L1000 - L1317), 168 slave (L100 - L127, L200 - L227, ......, L700 - L727)
Remote I/O 512 points
Real-Time Calendar/Clock Runtime Yes (Y2K complaint)
Program Protection Yes (password protected)
External Run/Stop Control Yes
Power Failure Protection Yes
Self-Diagnostics Yes
Auto Start Function Yes
Powered by IDEC’s PS5R Series 50W Power Supply
The eighth slot must be expansion power supply module. (Above photo is only an example of the range of available modules.)
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-25
J
Part Numbers: OpenNet Controller
Item Description Part Number
CPU Modules
High-speed counter, source output type,No memory card available FC3A-CP2K
High-speed counter, source output type,With memory card connector FC3A-CP2KM
High-speed counter, sink output type,No memory card available FC3A-CP2S
High-speed counter, sink output type,With memory card connector FC3A-CP2SM
Input Modules
DC Input
16 points 24V DC input, sink/source compatible, terminal block FC3A-N16B1
16 points 24V DC input, sink/source compatible,nylon connector (10P*2) FC3A-N16B3
32 points 24V DC input, sink/source compatible,nylon connector (10P*2) FC3A-N32B4
32 points 24V DC input, sink/source compatible,FUJITSU connector FC3A-N32B5
AC Input 8 points 100V AC input, terminal block FC3A-N08A11
Analog Input 6 channels, 4-20mA,selectable by DIP sw, terminal block FC3A-AD1261
Output Modules
Analog Output 2 channels, 4-20mA, selectable by DIP sw, terminal block FC3A-DA1221
Relay Output16 points relay output, terminal block FC3A-R161
16 points relay output, nylon connector (5P*4) FC3A-R162
Transistor Output
16 points transistor output sink, terminal block FC3A-T16K1
16 points transistor output sink, nylon connector FC3A-T16K3
16 points transistor output protect source, terminal block FC3A-T16P1
32 points transistor output sink, nylon connector FC3A-T32K4
32 points transistor output sink, FUJITSU connector FC3A-T32K5
Expansion Module Expansion power supply FC3A-EA1
Programmable Logic Controllers ONC Series
J-26 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Part Numbers: SX/IO
For Use With Description Part Number
INTERBUS
DC-16 Inputs, Source SX5S-SBN16S
DC-16 Inputs, Sink SX5S-SBN16K
Relay Output, 8 points SX5S-SBR08
Transistor Output, 16 points SX5S-SBT16K
Transistor Output, 16 points, Protect Source SX5S-SBT16P
DC-8 points Source Input / Transistor 8 points SInk Output SX5S-SBM16K
DC-8 points Sink Input / Transistor 8 points Protect Source Output SX5S-SBM16P
DEVICENET
DC-16 Inputs, Source SX5D-SBN16S
DC-16 Inputs, Sink SX5D-SBN16K
Relay Output, 8 points SX5D-SBR08
Transistor Output, 16 points SX5D-SBT16K
Transistor Output, 16 points, Protect Source SX5D-SBT16P
DC-8 points Source Input / Transistor 8 points SInk Output SX5D-SBM16K
DC-8 points Sink Input / Transistor 8 points Protect Source Output SX5D-SBM16P
LONWORKS
DC-16 Inputs, Source SX5L-SBN16S
DC-16 Inputs, Sink SX5L-SBN16K
Relay Output, 8 points SX5L-SBR08
Transistor Output, 16 points SX5L-SBT16K
Transistor Output, 16 points, Protect Source SX5L-SBT16P
DC-8 points Source Input / Transistor 8 points SInk Output SX5L-SBM16K
DC-8 points Sink Input / Transistor 8 points Protect Source Output SX5L-SBM16P
Common Unit
Upper terminal block for SX5*-SBN16*, -SBT16*, -SBM16* SX9Z-SS1
Lower terminal block for SX5*-SBN16*, -SBT16* SX9Z-SS2
Lower terminal block for SX5*-SBN16* SX9Z-SS3
Lower terminal block for SX5*-SBN16* SX9Z-SS4
Lower terminal block for SX5*-SBN16* SX9Z-SS5
SX5D (DeviceNet connector), comes with mounting screws SX9Z-CN5G2
SX5L (LON connector), comes with mounting screws SX9Z-CN22
LonWorks slave interface module FC3A-SX5LS1
ONC Remote I/O Master module FC3A-SX5SM1
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-27
J
01234567891011121314151617
Computer Link Cable 4CFC2A-KC4C3m (9.84 ft.) long
D-sub 9-pin Female Connector
RS232C Port 1 or Port 2
01234567891011121314151617RS232C/RS485 Converter
FC2A-MD1
1st Unit
2nd Unit
32nd Unit
RS232C CableHD9Z-C521.5m (4.92 ft.) long
01234567891011121314151617
01234567891011121314151617
Twist-pair Shielded Cable
D-sub 9-pin Female Connector
RS485
OpenNet Controller, Networking & Applications
Printer
Barcode Reader
Modem
PC CommunicationThe ONC is programmed by our intuitive WindLDR™3.0 software -use RS232 or RS485 ports -upload, download and monitor programs
Data Link - Superiority in NetworkingConnect up to 32 ONC, Micro3, FA Series PLCs orthe HG Series operator interface on the data link network.
Communication FlexibilityEasy connections to any R232C equipmentthrough the user defined RS232C port 1 or 2.Built-in Hayes “AT” command set for directmodem dialup and pager applications.
Computer Link - Power & VersatilityConnect 32 ONCs on a 1:N computer link system.Upload, download, monitor, and update data.
For RS485 programming, use FC2A-KC6C cable.
Communication Selector DIP Switch
Master Station Slave Station 1 Slave Station 2
HG SeriesOperatorInterface
01234567891011121314151617
01234567891011121314151617
Slave Station 31
01234567891011121314151617
AB
GR
S485
CO
MA
BZ
HS
CO
UT
+24V
0V
POWER
RUN
ERROR
HSC OUT
12
3
O N
DIPSwitch
Programmable Logic Controllers ONC Series
J-28 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
INTERBUS DeviceNet LONWORKS
Expansion Connector
(1) Module ID(5) Status LED
(3) Connector 1
(4) Connector 2
Expansion Connector
(1) Module ID(4) Status LED
(2) FG Terminal
(2) DIP Switch
(3) Connector
Expansion Connector
(1) Module ID(5) Status LED
(3) Service Request
(4) Connector
SERVIOSE
REQUESI
NETWORK
(2) FG Terminal
V.24
Inte
rfac
eR
EMO
TE O
UT
idec
REM
OTE
IN
REM
OTE
OU
T
idec idec
NOH/LDR1DR0
NA5NA4NA3
NA2NA1NA0
idec
SERVICEREQUPST
NET WORK
INTERBUS
DeviceNet
LONWORKS
INTERBUS
Remote I/OMaster Module
CPUModule
SX5S Communication Terminals
OpenNet Interface Modules I/O Modules
AB
GR
S485
CO
MA
BZ
HS
CO
UT
+24V0V
Remote I/O
REM
OTE
OU
TR
EMO
TE I
NR
EMO
TE O
UT
REM
OTE
IN
Remote I/O
REM
OTE
OU
TR
EMO
TE I
NR
EMO
TE O
UT
REM
OTE
IN
POWER
RUN
ERROR
HSC OUT
Network Communication SystemThe ONC offers versatility and power with the unique capabilityto inferface with standard networks such as INTERBUS,DeviceNet and LONWORKS.
OpenNet Interface Modules
Add 8 or 16 I/O points to theremote I/O network with a simpleconnection: SX5S communicationterminals offer a simple and lowcost method of system expan-sion.
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-29
J
Spec
ifica
tions
Analog Type Input Output
Point Per Card 6 Points 2 PointsPart Number FC3A-AD1261 FC3A-DA1221Connector Type Phoenix Contact Phoenix Contact
Input Signal 0-10V DC, ±10V DC, 0-5V DC, ±5V DC, 4-20mA
0-10V DC, ±10V DC, 0-5V DC, ±5V DC, 4-20mA
Resolution 12 bits 12 bitsRange 0-4000 counts 0-4000 countsInput Error ±0.6% of full scale @ 25°C NAOutput Error NA ±0.6% of full scale @ 25°C Conversion Time 3ms per point NASettling Time NA 3ms
Input Impedance Voltage: 1 MΩ minimumCurrent: 250Ω NA
Output Load Impedance NA Voltage=2 kΩ minimum
(Current=250Ω, 300Ω max.)Internal Current Draw 120mA@24V DC 120mA@24V DC
Analog Input and Output Modules
Analog Input ModuleFC3A-AD1261
Key features include:• One card handles 5 different signal types,
[±5V, ±10V, 0-5V, 0-10V, or 4-20mA], switch selectable
• Input module has 6 inputs per card, 7 cards per CPU, 42 analog input points maximum
• Output module has 2 outputs per card, 7 cards per CPU, 14 analog output points maximum
• 12-bit resolution, 0-4000 counts, count range divides evenly• Fast input scan, 3ms + 1 scan time• I/O error ±0.6% full scale @25°C• Convenient input termination, Phoenix Contact type connector
Analog Input Module Analog Output Module
Voltage Input
COM
+V
250Ω
+
–
–V
Differential
Current Input
Amplifier
Voltage Output
COM
+V
–V
Current Output
Analog Output ModuleFC3A-DA1221
Type of Protection
Programmable Logic Controllers ONC Series
J-30 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Terminal No. Channel Name
1
Channel 0
+V (voltage)
2 +I (current)
3 COM (-V, -I)
4
Channel 1
+V (voltage)
5 +I (current)
6 COM (-V, -I)
7
Channel 2
+V (voltage)
8 +I (current)
9 COM (-V, -I)
10
Channel 3
+V (voltage)
11 +I (current)
12 COM (-V, -I)
13
Channel 4
+V (voltage)
14 +I (current)
15 COM (-V, -I)
16
Channel 5
+V (voltage)
17 +I (current)
18 COM (-V, -I)
19 — NC
20 — NC
FC3A-AD1261 Analog Input Module Terminal Arrangement
6-Channel - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)
FC3A-DA1221 Analog Output Module Terminal Arrangement
2-Channel - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal
No. Channel Rotary Switch Position Name
1
Channel 0
0Voltage Output (0 to 10V)
2 COM (GND)
31
Voltage Output (±10V)
4 COM (GND)
52
Voltage Output (0 to 5V)
6 COM (GND)
73
Voltage Output (±5V)
8 COM (GND)
94
Current Output (4 to 20mA)
10 COM (GND)
11
Channel 1
0Voltage Output (0 to 10V)
12 COM (GND)
131
Voltage Output (±10V)
14 COM (GND)
152
Voltage Output (0 to 5V)
16 COM (GND)
173
Voltage Output (±5V)
18 COM (GND)
194
Current Output (4 to 20mA)
20 COM (GND)
PCW
A/D
D/A
PCW
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-31
J
16-Point DC Input Modules
Input Type DC Sink/Source
16-P
oint
DC
Part Number FC3A-N16B1 FC3A-N16B3Connector Type Phoenix Contact NylonInput Voltage Range 19-30V DC 19-30V DCRated Input Voltage 24V DC 24V DCCurrent Per Point 7mA 7mAInternal Current - all inputs ON 40mA 40mAInput Impedance 3.4kΩ 3.4kΩOn/Off Voltage 15/5V DC 15/5V DCOn/Off Time 20/120µs 20/120µs
Key features include:• One card handles sink (NPN) or source (PNP)
type input signals• 16 points per card, 7 cards local, 8 cards expansion,
15 cards max. per CPU• 19-30V DC input voltage range• Software selectable input filtering, 0-32 msec• High-speed catch inputs, first 8 points user definable,
pulse detection within 20-120µsec range• Termination connector
-FC3A-N16B1 - removable Phoenix Contact type-FC3A-N16B3 - removable Nylon type
Input Operating RangeThe input operating range of the Type 1 (EN61131) input module is shown below:
Input Internal Circuit
Transition
OFF AreaInpu
t Vo
ltage
(V
DC
)
30
15
5
01.5 8.8
Input Current (mA)
ON Area
Area
74.4
24
COM
Inte
rnal
Circ
uit
Input
DC Input ModuleFC3A-N16B1
DC Input ModuleFC3A-N16B3
Programmable Logic Controllers ONC Series
J-32 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Terminal No. Name
1 COM
2 COM
3 I0
4 I1
5 I2
6 I3
7 I4
8 I5
9 I6
10 I7
11 COM
12 COM
13 I10
14 I11
15 I12
16 I13
17 I14
18 I15
19 I16
20 I17
Terminal No. CN1
1 COM
2 COM
3 I0
4 I1
5 I2
6 I3
7 I4
8 I5
9 I6
10 I7
Terminal No. CN2
1 COM
2 COM
3 I10
4 I11
5 I12
6 I13
7 I14
8 I15
9 I16
10 I17
FC3A-N16B1 Input Module Terminal Arrangement
16-Point DC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)
FC3A-N16B3 Input Module Terminal Arrangement
16-Point DC - Nylon Connector TypeApplicable Connectors: VHR-10N (J.S.T. Mfg.)
SVH-21T-P1.1 (J.S.T. Mfg.)
012345671011121314151617
DCIN
012345671011121314151617
CN2
CN1 DCIN
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-33
J
Key features include:• One card handles sink (NPN) or source (PNP) type input signals• 32 points per card, 7 cards local, 8 cards expansion,
15 cards max. per CPU• 20-28V DC input voltage range• Software selectable input filtering, 0-32 msec• High-speed catch inputs, first 8 points user definable,
pulse detection within 20-120µsec range• Termination connector
-FC3A-N32B4 - removable Nylon type-FC3A-N32B5 - removable Fujitsu type
32-Point DC Input Modules
Input Type DC Sink/Source
32-P
oint
DC
Part Number FC3A-N32B4 FC3A-N32B5Connector Type Nylon FujitsuInput Voltage Range 20-28V DC 20-28V DCRated Input Voltage 24V DC 24V DCCurrent Per Point 5mA 5mAInternal Current-all inputs ON 50mA 50mA
Input Impedance 4.7kΩ 4.7kΩOn/Off Voltage 15/5V DC 15/5V DCOn/Off Time 20/120µs 20/120µs
Input Operating RangeThe input operating range of the Type 1 (EN61131) input module is shown below:
Input Internal Circuit
Transition
OFF AreaInpu
t Vo
ltage
(V
DC
)
27.6
15
5
01 5.4
Input Current (mA)
ON Area
Area
4.94.4
24
COM
Inte
rnal
Circ
uit
Input
DC Input ModuleFC3A-N32B4
DC Input ModuleFC3A-N32B5
Programmable Logic Controllers ONC Series
J-34 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Terminal No. CN1 CN2
18 I0 I20
17 I1 I21
16 I2 I22
15 I3 I23
14 I4 I24
13 I5 I25
12 I6 I26
11 I7 I27
10 I10 I30
9 I11 I31
8 I12 I32
7 I13 I33
6 I14 I34
5 I15 I35
4 I16 I36
3 I17 I37
2 COM COM
1 COM COM
Terminal No. Name
B20 I0
B19 I1
B18 I2
B17 I3
B16 I4
B15 I5
B14 I6
B13 I7
B12 I10
B11 I11
B10 I12
B9 I13
B8 I14
B7 I15
B6 I16
B5 I17
B4 NC
B3 NC
B2 COM
B1 COM
Terminal No. Name
A20 I20
A19 I21
A18 I22
A17 I23
A16 I24
A15 I25
A14 I26
A13 I27
A12 I30
A11 I31
A10 I32
A9 I33
A8 I34
A7 I35
A6 I36
A5 I37
A4 NC
A3 NC
A2 NC
A1 NC
FC3A-N32B5 Input Module Terminal Arrangement
32-Point DC - Fujitsu Connector TypeApplicable Connector: FCN-367J040-AU (Fujitsu)
FC3A-N32B4 Input Module Terminal Arrangement
32-Point DC - Nylon Connector TypeApplicable Connectors: H18-SHF-AA (J.S.T. Mfg.)
SHF-001T-0.8BS (J.S.T. Mfg.)
01234567
CN1
CN2
101112131415161720212223242526273031323334353637
DCIN
01234567101112131415161720212223242526273031323334353637
DCIN
FOR MODULE FC3A-N32B5 ONLY:
Accessory Part No.
RIbbon Cable FC3A-KUSA1
Breakout ModulesBX1D-T40A
BX1D-S40A
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-35
J
Key features include:• 8 points per card, 7 cards local, 8 cards expansion,
15 cards max. per CPU• 100-120V AC rated input voltage• 85-132V AC input voltage range• On/off detection set at 20ms• Convenient termination connector, removable Phoenix Contact type
8-Point AC Input Module
Input Type AC
8-Po
int A
C
Part Number FC3A-N08A11Connector Type Phoenix ContactInput Voltage Range 85-132V ACRated Input Voltage 100-120V ACCurrent Per Point 8mAInternal Current - all inputs ON 30mAInput Impedance 12kΩ (60Hz)On/Off Voltage 79/20V ACOn/Off Time 20ms
Input Operating RangeThe input operating range of the Type 1 (EN61131) input module is shown below:
Input Internal Circuit
Transition
OFF AreaInpu
t Vo
ltage
(V
AC)
132
79
20
01.6 11
Input Current (mA)
ON Area
Area
8.36.5
100
COMIn
tern
al C
ircui
t
Input
AC Input ModuleFC3A-N08A11
Programmable Logic Controllers ONC Series
J-36 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Terminal No. Name
1 COM0
2 I0
3 COM1
4 I1
5 COM2
6 I2
7 COM3
8 I3
9 COM4
10 I4
11 COM5
12 I5
13 COM6
14 I6
15 COM7
16 I7
17 NC
18 NC
19 NC
20 NC
FC3A-N08A11 Input Module Terminal Arrangement
8-Point AC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)
0
ACIN
1234567
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-37
J
Key features include:• 16 points per card, 4 points per common,
15 cards max. per CPU• Outputs rated 240V AC/2A or 24V DC/2A• Turn On/Off delay 6-10ms• 20,000,000 operations per relay minimum• Termination connector
-FC3A-R161 - removable Phoenix Contact type-FC3A-R162 - removable Nylon type
16-Point Relay Output Modules
Output Type Relay Output
16-P
oint
Rel
ay
Part Number FC3A-R161 FC3A-R162Connector Type Phoenix Contact NylonRated Output Voltage 240V AC/24V DC 240V AC/24V DCRated Current Per Point 2A 2AInternal Current - all inputs ON 170mA 170mA
On/Off Time 6/10ms 6/10ms
Output Delay
Command
Output Status
OFF delay: 10 msec maximumChatter: 6 msec maximumON delay: 6 msec maximum
Relay Output ModuleFC3A-R162
Relay Output ModuleFC3A-R161
Programmable Logic Controllers ONC Series
J-38 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Terminal No. Name
1 COM0
2 Q0
3 Q1
4 Q2
5 Q3
6 COM1
7 Q4
8 Q5
9 Q6
10 Q7
11 COM2
12 Q10
13 Q11
14 Q12
15 Q13
16 COM3
17 Q14
18 Q15
19 Q16
20 Q17
Terminal No. CN1
1 COM0
2 Q0
3 Q1
4 Q2
5 Q3
Terminal No. CN2
1 COM1
2 Q4
3 Q5
4 Q6
5 Q7
Terminal No. CN3
1 COM2
2 Q10
3 Q11
4 Q12
5 Q13
Terminal No. CN1
1 COM3
2 Q14
3 Q15
4 Q16
5 Q17
FC3A-R162 Output Module Terminal Arrangement
16-Point Relay - Nylon Connector TypeApplicable Connectors: VHR-5N (J.S.T. Mfg.)
SVH-21T-P1.1 (J.S.T. Mfg.)
FC3A-R161 Output Module Terminal Arrangement
16-Point Relay - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)
0
RyOUT
12345671011121314151617
01234567
CN1
CN2
CN3
CN4
RyOUT
1011121314151617
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-39
J
Key features include:• 16 transistor sink outputs per card, 15 cards max. per CPU• Outputs rated 19-30V DC/0.5A• Turn On/Off delay 500µsec max.• Opto-isolated outputs• Termination connector
-FC3A-T16K1 - removable Phoenix Contact type-FC3A-T16K3 - removable Nylon type
16-Point DC Sink Output Modules
Output Type DC Sink
16-P
oint
DC
Part Number FC3A-T16K1 FC3A-T16K3Connector Type Phoenix Contact NylonRated Output Voltage 19-30V DC 19-30V DCRated Current Per Point 500mA@ 24V DC 500mA@ 24V DCInternal Current - all inputs ON 60mA 60mA
On/Off Time 500/500µs 500/500µs
DC Sink Output ModuleFC3A-T16K1
DC Sink Output ModuleFC3A-T16K3
Output Delay Output Internal Circuit
Command
Output Status
ON delay 500 µsec maximum
+V
Output
Inte
rnal
Circ
uit
COM (–)
OFF delay 500 µsec maximum
Programmable Logic Controllers ONC Series
J-40 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
FC3A-T16K3 Sink Output Module Terminal Arrangement
16-Point DC - Nylon Connector TypeApplicable Connectors: VHR-10N (J.S.T. Mfg.)
SVH-21T-P1.1 (J.S.T. Mfg.)
FC3A-T16K1 Sink Output Module Terminal Arrangement
16-Point DC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact) Terminal No. Name
1 Q0
2 Q1
3 Q2
4 Q3
5 Q4
6 Q5
7 Q6
8 Q7
9 COM(-)
10 +V
11 Q10
12 Q11
13 Q12
14 Q13
15 Q14
16 Q15
17 Q16
18 Q17
19 COM(-)
20 +V
Terminal No. CN1
1 Q0
2 Q1
3 Q2
4 Q3
5 Q4
6 Q5
7 Q6
8 Q7
9 COM(-)
10 +V
Terminal No. CN2
1 Q10
2 Q11
3 Q12
4 Q13
5 Q14
6 Q15
7 Q16
8 Q17
9 COM(-)
10 +V
0
TrOUT
12345671011121314151617
01234567
CN2
CN1 TrOUT
1011121314151617
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-41
J
16-Point DC Protect Source Output Module
Protect Source Output ModuleFC3A-T16P1
Key features include:• 16 transistor protect source outputs per card, 15 cards max. per CPU• Outputs rated 19-30V DC/0.5A• Turn On/Off delay 500µsec max.• Opto-isolated outputs• Termination connector, removable Phoenix Contact type
Output Type DC Source
16-P
oint
DC
Part Number FC3A-T16P1Connector Type Phoenix ContactRated Output Voltage 19-30V DCRated Current Per Point 500mA @ 24V DCInternal Current - all inputs ON 70mAOn/Off Time 500µs/500µs
Output Delay Output Internal Circuit
Command
Output Status
ON delay 500 µsec maximum
COM (+)
Output
–V
Overload
Out
put
Prot
ect
Dev
ice
Signal
Inte
rnal
Circ
uit
OFF delay 500 µsec maximum
Programmable Logic Controllers ONC Series
J-42 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
FC3A-T16P1 Protect Source Output Module Terminal Arrange-
ment
16-Point DC - Screw Terminal TypeApplicable Connector: SMSTB2.5/20-ST-5.08 (Phoenix Contact)
Terminal No. Name
1 Q0
2 Q1
3 Q2
4 Q3
5 Q4
6 Q5
7 Q6
8 Q7
9 COM(+)
10 -V
11 Q10
12 Q11
13 Q12
14 Q13
15 Q14
16 Q15
17 Q16
18 Q17
19 COM(+)
20 -V
0
TrOUT
12345671011121314151617
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-43
J
Key features include:• 32 transistor sink outputs per card, 15 cards max. per CPU• Outputs rated 20.4-27.6V DC/0.1A• Turn On/Off delay 500µsec max. • Opto-isolated outputs• Termination connector
-FC3A-T32K4 - removable Nylon type-FC3A-T32K5 - removable Fujitsu type
32-Point DC Sink Output Modules
Output Type DC Sink
32-P
oint
DC
Part Number FC3A-T32K4 FC3A-T32K5Connector Type Nylon FujitsuRated Output Voltage 20.4-27.6V DC 20.4-27.6V DCRated Current Per Point 100mA@24V DC 100mA@24V DCInternal Current - all inputs ON 90mA 90mA
On/Off Time 500/500µs 500/500µs
Output Delay Output Internal Circuit
Command
Output Status
ON delay 500 µsec maximum
+V
Output
Inte
rnal
Circ
uit
COM (–)
DC Sink Output ModuleFC3A-T32K4
DC Sink Output ModuleFC3A-T32K5
OFF delay 500 µsec maximum
Programmable Logic Controllers ONC Series
J-44 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Terminal No. CN1 CN2
18 Q0 Q20
17 Q1 Q21
16 Q2 Q22
15 Q3 Q23
14 Q4 Q24
13 Q5 Q25
12 Q6 Q26
11 Q7 Q27
10 Q10 Q30
9 Q11 Q31
8 Q12 Q32
7 Q13 Q33
6 Q14 Q34
5 Q15 Q35
4 Q16 Q36
3 Q17 Q37
2 COM(-) COM(-)
1 +V +V
Terminal No. Name
B20 Q0
B19 Q1
B18 Q2
B17 Q3
B16 Q4
B15 Q5
B14 Q6
B13 Q7
B12 Q10
B11 Q11
B10 Q12
B9 Q13
B8 Q14
B7 Q15
B6 Q16
B5 Q17
B4 NC
B3 NC
B2 +V
B1 +V
Terminal No. Name
A20 Q20
A19 Q21
A18 Q22
A17 Q23
A16 Q24
A15 Q25
A14 Q26
A13 Q27
A12 Q30
A11 Q31
A10 Q32
A9 Q33
A8 Q34
A7 Q35
A6 Q36
A5 Q37
A4 NC
A3 NC
A2 COM(-)
A1 COM(-)
FC3A-T32K5 Sink Output Module Terminal Arrangement
32-Point DC - Fujitsu Connector TypeApplicable Connector: FCN-367J040-AU (Fujitsu)
FC3A-T32K4 Sink Output Module Terminal Arrangement
32-Point DC - Nylon Connector TypeApplicable Connectors: H18-SHF-AA (J.S.T. Mfg.)
SHF-001T-0.8BS (J.S.T. Mfg.)
01234567
CN1
CN2
TrOUT
101112131415161720212223242526273031323334353637
01234567101112131415161720212223242526273031323334353637
TrOUT
Programmable Logic Controllers ONC Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-45
J
Key features include:• Expands the ONC from 224 up to 480 I/O points• Increases I/O and functional modules by 8• Comes with a cable connector and contacts• Simple, easy and convenient mounting• Install in the 8 slot only
Expansion Power Supply Module
Specifications
Expa
nsio
n Po
wer
Sup
ply
Part Number FC3A-EA1Connector Type Nylon - 5 pinInput Voltage Range 19 - 30V DC (including ripple)Rated Input Voltage 24V DCInternal Current 30mA
Momentary Power Interruption 10 msec (24V DC), Level PS-2 (EN61131)
Power Supply Wiring
1: NC
2: NC
3: 24V DC (red)
4: 0V (blue)
5: FG (green)
Ground
Fuse– +Power Voltage: 24V DCInrush Current: 50A
(same power source for CPU)
Connector
Expansion Power Supply ModuleFC3A-EA1
Programmable Logic Controllers ONC Series
J-46 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
FC3A-EA1 Expansion Power Supply Module Mounting Position
Mount the expansion power supply module in the eighth slot.
7 modules (I/O and functional)Expansion Power Supply Module
8 modules (I/O and functional)
A maximum of 7 functional modules can be mounted in any of 15 slots
CPU Module
Mount the expansion power supply module only in the eighth slot, otherwise correct allocation of I/O and link register numbers may not occur.
Programmable Logic Controllers SX5 Smart I/O
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-47
J
UL/c-UL ListedFile No. E102542
SX5 Series Smart I/O (General Information)
SX5 Communication Terminals
Bus I/O Type Specifications Part No.
INTERBUS
DC Input16-point source input (24V DC) SX5S-SBN16S16-point sink input (24V DC) SX5S-SBN16K
Relay Output 8-point relay output (240V AC/24V DC, 5A) SX5S-SBR08
Transistor Output16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) SX5S-SBT16K16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) SX5S-SBT16P
DC inputTransistor Output
8-point source input (24V DC)8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) SX5S-SBM16K
8-point sink input (24V DC)8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) SX5S-SBM16P
DeviceNet
DC Input16-point source input (24V DC) SX5D-SBN16S16-point sink input (24V DC) SX5D-SBN16K
Relay Output 8-point relay output (240V AC/24V DC, 5A) SX5D-SBR08
Transistor Output16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) SX5D-SBT16K16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) SX5D-SBT16P
DC InputTransistor Output
8-point source input (24V DC)8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) SX5D-SBM16K
8-point sink input (24V DC)8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) SX5D-SBM16P
LonWorks
DC Input16-point source input (24V DC) SX5L-SBN16S16-point sink input (24V DC) SX5L-SBN16K
Relay Output 8-point relay output (240V AC/24V DC, 5A) SX5L-SBR08
Transistor Output16-point transistor sink output (24V DC, 0.5A/point, 6.0A/common) SX5L-SBT16K16-point transistor protect source output (24V DC, 0.5A/point, 6.0A/common) SX5L-SBT16P
DC InputTransistor Output
8-point source input (24V DC)8-point transistor sink output (24V DC, 0.5A/point, 4.0A/common) SX5L-SBM16K
8-point sink input (24V DC)8-point transistor protect source output (24V DC, 0.5A/point, 4.0A/common) SX5L-SBM16P
DeviceNet™ and LONWORKS® are trademarks of ODVA and Echelon, USA, respectively.
Key features:• INTERBUS I/O compatible with IDEC ONC remote I/O• Removable terminal blocks for easy maintenance• Finger-safe spring-up screw terminals• Compact body 75 × 132 × 48 mm• Mounting on a 35-mm-wide DIN rail or on a panel surface• Both inputs and outputs are available in sink or source types.
Relay outputs are also available.• The source output is protected against overload.
Designed to communicate with major industrial networks: INTERBUS, DeviceNet™ and LONWORKS®.
Programmable Logic Controllers SX5 Smart I/O
J-48 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Options (For INTERBUS, DeviceNet, and LONWORKS)
• One upper and one lower terminal blocks are supplied with every SX5 communication terminal.
Option (For DeviceNet)
• One network connector and connector mounting screws are supplied with every SX5D communication terminal.
Option (For LONWORKS)
• One network connector and connector mounting screws are supplied with every SX5L communication terminal.
Name Part No. RemarksTerminal Block 1 SX9Z-SS1 Upper terminal block for SX5*-SBN16*, -SBT16*, -SBM16*Terminal Block 2 SX9Z-SS2 Lower terminal block for SX5*-SBN16*, SBT16*Terminal Block 3 SX9Z-SS3 Lower terminal block for SX5*-SBM16*Terminal Block 4 SX9Z-SS4 Upper terminal block for SX5*-SBR08Terminal Block 5 SX9Z-SS5 Lower terminal block for SX5*-SBR08
DIN RailAluminum (1m) BNDN1000 35-mm-wide DIN rail available in US and Canada marketsSteel (1m) BAP1000 35-mm-wide DIN rail available in other than US and Canada marketsAluminum (1m) BAA1000 35-mm-wide DIN rail available in other than US and Canada markets
Mounting Clip BNL5 Used on DIN rail to fasten SX5 communication terminals
Name Part No. RemarksSX5D Network Connector SX9Z-CN5G2 Mounting screws are attached
Name Part No. RemarksSX5L Network Connector SX9Z-CN22 Mounting screws are attached
General Specifications
I/O Terminals
Rated Pow er Voltage 2 4 V D C
Allow a b le Vo l tage Range 19 to 30V DC ( including 5% r ipple)
IsolationI/O – Control Circuit Not isolated
Control Circuit – C o m m . Interface
I N T E R B U S , DeviceNet,PhotocouplerL O N W O R K S :Transformer coupl ing
Insulat ion Resistance Between pow er terminals and ground:1 0 0 MΩ min imum (500V DC megger )
Dielectr ic Strength
B e t ween pow er terminals and ground:1 0 0 0 V AC , 1 minuteB e t ween relay outputs and other l ive par ts: 2000V AC , 1 minute
Vibration Res is tance
Damage L im i ts Ampl i tude: 0.35 mm, 10 to 55 Hz
O p e rat ing Extremes(relay output)
Ampl i tude: 0.35 mm, 10 to 55 Hz(contact opening ≤ 1 msec when energ ized)
S h o ck Res is tance
Damage L im i ts 294 m/sec 2, 11 m/sec, sine half-wave pulse
O p e rat ing Extremes(relay output)
59 m/sec2 (in the direction of relay contact move-ment )98 m/sec2 (in other 5 directions)
O p e rating Te m p e r ature 0 to +55°C
O p e rat ing Humidi ty 30 to 90% RH (non-condens ing)
Storage Te m p e r ature –20 to +75°C
Storage Humid i ty 30 to 90% RH (non-condens ing)
Moun t ing Snap-on mount on 35-mm DIN railP anel-mount wi th M4 screw s
W eight (approx.) 2 8 0 g
Terminal Style R e m o va b le
Rated Insulat ion Voltage 2 5 0 V
Terminal Screw M3 (center to center : 7 .62 mm)
Number o f Poles 1 0
Rated Operat ing Current 7 A
Damage L im i ts 100 inser t ion/removal cycles
Finger Protect ion Yes
Network Status Indicators• INTERBUS
• DeviceNet
• LonWorks
Indicator Status DescriptionU L G r e e n O N P ow er ON
R C G r e e n O N Remote- in cable connected correct ly
B A G r e e nFlash Ready for transmit t ing data
O N Transmit t ing data
E R R e d O N Module error (available on protect output module only; pro-tect ion is reset when over load is removed)
R D R e d O N Remote-ou t cable disabled or network error
Indicator Status Description
P O W— O F F P ow er OFF
G r e e n O N P ow er ON
M N S
— O F F P ow er OFF o r Dup_MAC_ID test not completed
G r e e nFlash Nor mal opera t ion (communication not established)
O N Nor mal opera t ion (communicat ion established)
R e dFlash Minor fault ( temporary network error)
O N Cr itical fault
IO
— O F F I/O inactive ( c o m m unication not established)
G r e e nFlash I/O idle ( c o m m unicat ion established)
O N I/O active
R e d O N I/O error or communication interrup ted
Indicator Status DescriptionP O W G r e e n O N P ow er ON
R U N G r e e n O N Nor mal operation
E R R R e d O N C o m m unication error
I /O R e d O N I / O c o m munication error
S E R YellowO N Appl icat ion program not configured
F lash N e t w ork management no t configured
Programmable Logic Controllers SX5 Smart I/O
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-49
J
Wiring SX5D and SX5L Cable Connector
• For wiring the communication cable connector on the SX5D and SX5L, use a cable of 24 AWG to 14 AWG (0.2 to 2.5 mm2). Strip the cable 7 mm from the end as shown below. Each communication terminal can accommodate up to two cables.
• When connecting two cables to one terminal, use cables of 24 AWG to 16 AWG (0.2 to 1.5 mm2).
• Do not solder the cable end for connection.• Tighten terminal screws on the communication cable connec-
tor to a torque of 0.5 to 0.6 N-m.• Tighten mounting screws on the communication cable con-
nector to a torque of 0.3 to 0.5 N-m.
7 mm
Terminal SymbolsSX5*-SBR08SX5*-SBM16*SX5*-SBN16*/SBT16* 7
7C3
+++
–––
000
11
C0
C5 C6 C7C4
221
33
C1
442
55
C2
663
157
804
91
1025
113
1246
135
1467
+ –POWER
+ –POWER
+ –POWERSX5*-SBR08
SX5*-SBM16*SX5*-SBN16*/SBT16*
Insertion Pin PositionsWhen purchasing terminal blocks separately, set the insertion pins asshown below.
SX5 Type No. Terminal Block Type No. Pin Positions
SX5*-SBN16*Upper SX9Z-SS1 B D F H
Lower SX9Z-SS2 A C E G
SX5*-SBR08 Upper SX9Z-SS4 B D E G
Lower SX9Z-SS5 A C F H
SX5*-SBT16*Upper SX9Z-SS1 B C E G
Lower SX9Z-SS2 A D F H
SX5*-SBM16*Upper SX9Z-SS1 B C F H
Lower SX9Z-SS3 A D E G
HE F GA B C D
A B C D E F G H
Dimensions
19m
m (
0.75
in)
3.6m
m (0
.14i
n)75
mm
(2.
95in
)132mm (5.24in) 19.3mm
48mm (1.89in)
(0.76in)
Safety Precautions• Turn power off to the SX5 communication terminals before start-
ing installation, removal, wiring, maintenance, and inspection of the SX5. Failure to turn power off may cause electrical shocks or fire hazard.
• Wire the SX5 correctly. Improper wiring may cause malfunction, abnormal heat, and fire hazard.
• Use wires of a proper size to meet voltage and current require-ments of the SX5. Tighten the terminal screws to a proper tighten-ing torque. A loose screw may cause abnormal heat and fire hazard. Check periodically to see if the screws are tightened securely.
• All SX5 communication terminals are manufactured under IDEC’s rigorous quality control system, but users must add a backup or fail safe provision to the control system using a SX5 communica-tion terminal in applications where heavy damage or personal injury might result should the SX5 fail.
Mounting Hole Layout (Top view)
4.5mm (0.18 in)
33mm
50m
m m
in.
0.5+–100mm 0.5+–
60m
m0.
5+ –
(3.94in ± 0.05) (1.3in ± 0.05)
(2.3
6in
± 0.
05)
(1.9
7 in
min
)
SX5 Series Smart I/O (General Information)
Programmable Logic Controllers SX5 Smart I/O
J-50 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Input/Output Requirements
• When connecting DC two-wire sensors to the SX5, the sensors must meet the following specifications. Operating voltage: 12 to 24V DCLeakage current: 1 mA maximumResidual voltage: 6V maximumON output current: 5.5 mA minimum (at 24V DC)
The sensor must have an ON output current of 4 mA at the minimum. If the sensor does not meet this lower limit, connect a bleeder resis-tor as shown below. But if the residual voltage is 6V or less, the sen-sor can still be used although the ON output may be less than 3.5 mA.
• Use the following formula for calculating the bleeder resistance if needed.
Vcc: Power voltage
I: Lower limit of DC two-wire sensor ON output (mA)• Do not apply a DC power voltage to the output circuit without con-
necting a load, otherwise internal elements will be damaged (except for the protect source output type).
• When an overload or short circuit occurs, the protect source output shuts down the output immediately to protect the internal elements from permanent damage. When the cause of the overload or short cir-cuit is removed, the SX5 will restore normal operation automatically.
• When the capacity of main power supply is small, the overcurrent protection of the main supply may reduce power supply to the SX5, then the SX5 will stop operation, causing a network error.
• When using the relay output in environments where extraneous noises exist or inductive loads are switched frequently, generating high reverse emf, connect contact protection elements to the output terminals and across the load as shown below.
Response Time• The response time of the SX5 system varies greatly depending on
such factors as the quantity of modules and cable length. The accu-rate response time can be confirmed on the actual network system.
Terminators• DeviceNet and LONWORKS networks require terminators. For details
about the terminators, see publications on DeviceNet or LONWORKS, or consult IDEC.
+ – Input
DC two-wire
Source Input Type
R
I
sensor
+ – Input
Sink Input Type
R
I
DC two-wire sensor
R (kΩ)Vcc 6–
I 4–-------------------=
Varistor System
SX5*-SBR08 SX5*-SBR08
LoadC0
OUT0
Load
OUT0
C0
• For both AC and DC power voltages • For DC power voltage only
+
–
Diode and Zener Diode System
LoadPower
LoadPower
Operating InstructionsInstallation and Wiring (All SX5 Modules)
• Turn power off to the SX5 before installing or removing the con-nector or the detachable terminal block.
• Tighten the terminal screws to a torque of 0.6 to 1.0 N-m.• When mounting the SX5 on a panel, tighten the mounting screws
to a torque of 1.0 to 1.3 N-m. Recommended mounting screw: M4• When mounting the SX5 on a 35-mm-wide DIN rail, put the SX5
on the DIN rail and press the SX5 towards the rail to lock. To remove, pull out the latch from the bottom of the module using a screwdriver and release the SX5. To re-attach, push back the latch into place and snap on the SX5 again.
• The upper-right mounting hole has a FG terminal. Connect the FG terminal and control box. Use a wire of 4 mm2 at the minimum to connect the relay terminal block with the safety ground. When mounting on a 35-mm-wide DIN rail, a steel DIN rail is recom-mended for easy grounding.
Mounting on Steel DIN Rail (Recommended)• A metal grounding clip is provided on the back of the SX5S and
SX5L to contact with a DIN rail. When mounting the SX5 on a steel DIN rail, the metal grounding clip comes in electrical contact with the DIN rail. Connect the DIN rail to a proper ground.
Mounting on Aluminum DIN Rail• The upper-right mounting hole has a FG terminal. When mounting
the SX5 on an aluminum DIN rail, connect the FG terminal to the panel using the attached M4 screw and nut, and connect the panel to a proper ground.
Panel Mounting• When mounting the SX5 on a panel surface, attach a crimping
terminal of a grounding wire to the FG terminal on the upper-right mounting hole of the SX5, and insert a screw through the mount-ing hole. Connect the grounding wire to the panel and connect the panel to a proper ground.
• Note: For secure electrical connection, remove coating from the grounding area on the panel.
Terminal Block• The SX5 uses detachable terminal blocks. To remove and attach
the terminal block, follow the procedures below.• To remove the terminal block, squeeze both latches on top of the
block inward to unlock the block from the socket.• To reattach the terminal block, place the block in the socket with
the latches opened and press the block until it bottoms in the socket, then the latches snap outward to lock the terminal block.
• Insertion pins are positioned on the base of the terminal block and inside the socket to prevent insertion of invalid blocks into the socket. The pins are keyed to ensure correct matching of block and socket, and prevent swapping of upper and lower blocks.
• When the block does not fit into the socket properly, check to see if the pin positions on the block agree with the pin-slot arrange-ment in the socket. If the pins and the pin slots are in matching positions, check for any chips and obstacles in the socket.
• When cutting cables or wires, keep the SX5 out of the way to pre-vent ingress of wire chips and fragments.
• When wiring the screw terminals using crimping terminals, use crimping terminals of the dimensions shown below. Each screw terminal can accommodate up to two crimping terminals.
• Note: Spade crimping terminals can also be used.
ø3.2 min.
3.0 max. 5.2 min.
6 max.
(Dimensions are in mm)
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-51
J
16-PointTransistor Input Modules (INTERBUS)
Input Type Part Number
Source SX5S-SBN16SSink SX5S-SBN16K
DC Input Type
Part No. SX5S–SBN16S SX5S–SBN16KInput Type DC source input DC sink inputInput Logic Active Low Active HighInput Points 16 points
Input TypeNo-voltage input (2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)
No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)
Rated Input Voltage 24V DCInput Voltage Range 0 to the power voltageTurn ON Voltage 6V maximum 10V minimumTurn OFF Voltage 10V minimum 6V maximumInput Current 6 mA/24V DC 6 mA/24V DCCommon 1 commonCurrent Draw 200 mA 200 mA
Communication Speed and Distance
Bus Baud Rate Transmission Distance
INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)
Communication Cable
Bus Network I/F Connector (on the module) Cable
INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female
INTERBUS cable
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS2)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 8 IN81 IN1 9 IN92 IN2 10 IN103 IN3 11 IN114 IN4 12 IN125 IN5 13 IN136 IN6 14 IN147 IN7 15 IN15
Communication Configuration
Type No. ID Code Station Type Data Length Data Address
SX5S-SBN16SSX5S-SBN16K 02hex Remote Bus Station with
Digital Inputs1 word(16 inputs)
Byte 1
7 0
Byte 0
15 8
Key features include:• Communicate with INTERBUS network• 16-point input modules (sink/source)• Removable terminal blocks• Use as remote I/O on ONC
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
J-52 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
DC Power
ContactSwitch
ContactSwitch
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
++
–Blue (White)
IN0Black (White)
Brown (Red)
Network
Brown (Black)IN1
Blue (Black)
IN14
IN15
ControlCircuit
DC3-wireSensorNPN
Output
DC2-wireSensor
CommunicationInterface
–
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
ContactSwitch
ContactSwitch
++
––
Brown (Red)
Blue (Black)
IN0Black (White)
IN1
Brown (White)
Blue (Black)
IN15
IN14CommunicationInterface
ControlCircuit
DCPower
Network
DC3-wireSensor
PNPOutput
DC2-wireSensor
16-Point Source Input
16-Point Sink Input
Wiring INTERBUS Cable
• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.
• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.
• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically.
• INTERBUS Cable Connector Pinouts
• Stripping and Clamping Cable Ends
• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-
rately.• Master and slave stations may be powered up in any order. But, if a
slave station is not powered up while the master is in preparation for transmission, a network error will result.
• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the mas-ter station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance.
• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the
INTERBUS CLUB.
16
9 5
/DO 6DO 1/DI 7DI 2COM 3
95
Housing
GreenYellowPinkGray
Brown
6 /DO1 DO7 /DI2 DI3 COM
HousingSolderedSide
SolderedSide
Bridge pins 5 and 9 inside the housing of the male connector.
1 6
95
D-sub 9-pin Male Connector
D-sub 9-pin Female Connector
3 8
20
First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.
Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.
SX5S-SBN16K
SX5S-SBN16S
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-53
J
8-Point Relay Output Module (INTERBUS)
Output Type Part Number
Relay Output SX5S-SBR08
Key features include:• Communicate with INTERBUS network• 8-point relay output module• Handles current up to 5A per point• Removable terminal blocks• Use as remote I/O on ONC
Communication Speed and Distance
Bus Baud Rate Transmission Distance
INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)
Communication Cable
Bus Network I/F Connector (on the module) Cable
INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female
INTERBUS cable
Terminal Arrangement
Upper Terminal Block (SX9Z-SS4)
Lower Terminal Block (SX9Z-SS5)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 4 OUT4
C0 COM0 C4 COM41 OUT1 5 OUT5
C1 COM1 C5 COM52 OUT2 6 OUT6
C2 COM2 C6 COM63 OUT3 7 OUT7
C3 COM3 C7 COM7
Communication Configuration
Type No. ID Code Station Type Data Length Data Address
SX5S-SBR08 01hex Remote Bus Station with Digital Outputs
1 word(8 outputs)
Byte 1
7 0 Unused
Relay Output Type
Rated Relay Contact
Part No. SX5S–SBR08Output Type Relay outputOutput Points 8 pointsOutput Type 1NO relay contactRated Load Voltage 250V AC, 24V DCMaximum Load Current 5A/point Commons/Current 8 commons/5ACurrent Draw 140 mABuilt-in Relay PCB mount, not replaceable
Maximum Applicable Voltage 250V AC, 125V DCMaximum Current 5ARated Load (resistive load) 250V AC/5A, 24V DC/5AMinimum Applicable Load 1V DC / 1mA
LifeMechanical 20,000,000 operations minimum
(18,000 operations/hour)
Electrical See Electrical Life Curve on next page (1,800 operations/hour)
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
J-54 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Load PowerPilotLight
Load Power
Solenoid
PilotLight
Load Power
Load Power
Solenoid
++
Network
OUT1COM1
COM7OUT7
OUT0COM0
COM6OUT6
ControlCircuit
CommunicationInterface
DCPower
––
8-Point Relay Output Wiring INTERBUS Cable
• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.
• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.
• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plat-ing. Connect the cable shield with the connector housing electrically.
• INTERBUS Cable Connector Pinouts
• Stripping and Clamping Cable Ends
• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-
rately.• Master and slave stations may be powered up in any order. But, if a slave
station is not powered up while the master is in preparation for transmis-sion, a network error will result.
• Causes of network errors include disconnection or short-circuit of the net-work cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power volt-age, faulty transmission line, incorrect cable, and transmission longer than the rated distance.
• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the
INTERBUS CLUB.
16
9 5
/DO 6DO 1/DI 7DI 2COM 3
95
Housing
GreenYellowPinkGray
Brown
6 /DO1 DO7 /DI2 DI3 COM
HousingSolderedSide
SolderedSide
Bridge pins 5 and 9 inside the housing of the male connector.
1 6
95
D-sub 9-pin Male Connector
D-sub 9-pin Female Connector
3 8
20
First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.
Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.
Reference Data Electrical Life Curve: Relay in SX5S-SBR08
Note 1: AC/DC Resistive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%
Note 2: AC Inductive Load
Note 3: DC Inductive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%Time constant: L/R =15 msec
Line MakingCurrent
BreakingCurrent Frequency Duty
Ratio
Solid 10 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 1800 operations/h40%
Dashed 5 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 300 operations/h
100
500
50
10
0.05 0.1 1 2 3 50.2 0.3 0.5
110V ACInductive
220V ACInductive
220V AC Resistive110V AC Resistive
AC Load
Life
(x
1000
0 op
erat
ions
)
Load Current (A)
100
500
50
10
0.05 0.1 1 2 3 50.2 0.3 0.5
110V DCInductive
24V DC Resistive
48V DC Resistive
24V DC Inductive
Load Current (A)
110 DC Resistive
Life
(x
1000
0 op
erat
ions
)
48V DC Inductive
DC Load
SX5S-SBR08
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-55
J
16-Point Transistor Output Modules (INTERBUS)
Key features include:• Communicate with INTERBUS network• 16-point transistor output modules (sink/source)• The source output is protected against overload• Removable terminal blocks• Use as remote I/O on ONC
Transistor Output Type
Part No. SX5S–SBT16K SX5S–SBT16P
Output Type Sink output Protect source output
Output Points 16 points
Output Type N-channel MOS open drain
P-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 3 to 30V DC 19 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/6A
Short-circuit Protection No Yes
Current Draw 155 mA 180 mA
Communication Speed and Distance
Bus Baud Rate Transmission Distance
INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)
Communication Cable
Bus Network I/F Connector (on the module) Cable
INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female
INTERBUS cable
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS2)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 8 OUT81 OUT1 9 OUT92 OUT2 10 OUT103 OUT3 11 OUT114 OUT4 12 OUT125 OUT5 13 OUT136 OUT6 14 OUT147 OUT7 15 OUT15
Communication Configuration
Part No. ID Code Station Type Data Length Data Address
SX5S-SBT16KSX5S-SBT16P 01hex Remote Bus Station with
Digital Outputs1 word(16 outputs)
Byte 1
7 0
Byte 0
15 8
Output Type Part Number
Sink SX5S-SBT16KSource SX5S-SBT16P
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
J-56 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Wiring INTERBUS Cable
• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.
• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.
• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electri-cally.
• INTERBUS Cable Connector Pinouts
• Stripping and Clamping Cable Ends
• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-
rately.• Master and slave stations may be powered up in any order. But, if a
slave station is not powered up while the master is in preparation for transmission, a network error will result.
• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the mas-ter station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance.
• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the
INTERBUS CLUB.
16
9 5
/DO 6DO 1/DI 7DI 2COM 3
95
Housing
GreenYellowPinkGray
Brown
6 /DO1 DO7 /DI2 DI3 COM
HousingSolderedSide
SolderedSide
Bridge pins 5 and 9 inside the housing of the male connector.
1 6
95
D-sub 9-pin Male Connector
D-sub 9-pin Female Connector
3 8
20
First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.
Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.
16-Point Transistor Sink Output
16-Point Transistor Protect Source Output
Relay
PilotLight
++
––
OUT15
ControlCircuit
Pro
tect
ion
Circ
uit
Pro
tect
ion
Circ
uit
DCPower
CommunicationInterface
Network
OUT0
SX5S-SBT16P
• SX5*-SBT16K
Relay
PilotLight
Relay
++
––
OUT0
OUT1
DCPower
ControlCircuit
CommunicationInterface
Network
OUT15
SX5S-SBT16K
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-57
J
8-Point Source Input & 8-Point Transistor Sink Output Module (INTERBUS)
Key features include:• Communicate with INTERBUS network• 8-point source input and 8-point sink output module• Removable terminal blocks• Use as remote I/O on ONC
Communication Speed and Distance
Bus Baud Rate Transmission Distance
INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)
Communication Cable
Bus Network I/F Connector (on the module) Cable
INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female
INTERBUS cable
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS3)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7
Communication Configuration
Type No. ID Code Station Type Data Length Data Address
SX5S-SBM16K 03hex Remote Bus Station with Digital I/Os
1 byte(8 in / 8 out) Byte 0 (Output)
7 0
Byte 0 (Input)
7 0
Input/Output Type Part Number
Source Input/Sink Output SX5S-SBM16K
DC Input / Transistor Sink Output Type
Part No. SX5S–SBM16KI/O Type Source input / sink output
InputInput Logic Active Low
Input Points 8 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
ON Voltage 6V maximum
OFF Voltage 10V minimum
Input Current 6 mA/24V DC
Common 1 common
OutputOutput Points 8 points
Output Type N-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 3 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/4A
Short-circuit Protection No
Current Draw 180 mA
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
J-58 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
DC Power
ContactSwitch
ContactSwitch
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
++
–Blue (White)
IN0Black (White)
Brown (Red)
Network
Brown (Black)IN1
Blue (Black)
IN6
IN7
ControlCircuit
DC3-wireSensorNPN
Output
DC2-wireSensor
CommunicationInterface
–
Wiring INTERBUS Cable
• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.
• Turn power off before wiring the INTERBUS cable. Make sure of correct wiring before turning power on.
• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electri-cally.
• INTERBUS Cable Connector Pinouts
• Stripping and Clamping Cable Ends
• Leave open the remote out connector at the last station in the network.• Supply power to each slave station or to each group of stations sepa-
rately.• Master and slave stations may be powered up in any order. But, if a
slave station is not powered up while the master is in preparation for transmission, a network error will result.
• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the mas-ter station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmission longer than the rated distance.
• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by the
16
9 5
/DO 6DO 1/DI 7DI 2COM 3
95
Housing
GreenYellowPinkGray
Brown
6 /DO1 DO7 /DI2 DI3 COM
HousingSolderedSide
SolderedSide
Bridge pins 5 and 9 inside the housing of the male connector.
1 6
95
D-sub 9-pin Male Connector
D-sub 9-pin Female Connector
3 8
20
First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.
Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.
8-Point Source Input
8-Point Transistor Sink Output
Relay
PilotLight
Relay
++
––
OUT0
OUT1
DCPower
ControlCircuit
CommunicationInterface
Network
OUT7
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-59
J
8-Point Sink Input & 8-Point Transistor Source Output Module (INTERBUS)
Key features include:• Communicate with INTERBUS network• 8-point sink input and 8-point source output module• Removable terminal blocks• Use as remote I/O on ONC• Source output short circuit and overload protected
Communication Speed and Distance
Bus Baud Rate Transmission Distance
INTERBUS 500 kbps 400m (between slaves)12.8 km (total length)
Communication Cable
Bus Network I/F Connector (on the module) Cable
INTERBUS9-pin D-sub connectorRemote-in: MaleRemote-out: Female
INTERBUS cable
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS3)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7
Communication Configuration
Type No. ID Code Station Type Data Length Data Address
SX5S-SBM16P 03hex Remote Bus Station with Digital I/Os
1 byte(8 in / 8 out) Byte 0 (Output)
7 0
Byte 0 (Input)
7 0
Input/Output Type Part Number
Sink Input/Source Output SX5S-SBM16P
DC Input / Transistor Source Output Type
Part No. SX5S–SBM16PI/O Type Sink input / protect source output
InputInput Logic Active High
Input Points 8 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
ON Voltage 10V minimum
OFF Voltage 6V maximum
Input Current 6 mA/24V DC
Common 1 common
OutputOutput Points 8 points
Output Type P-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 19 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/4A
Short-circuit Protection Yes
Current Draw 180 mA
Programmable Logic Controllers SX5 Smart I/O (INTERBUS)
J-60 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Wiring INTERBUS Cable
• Do not install the INTERBUS cable in parallel with or close to motor lines. Keep the INTERBUS cable away from noise sources.
• Turn power off before wiring the INTERBUS cable. Make sure of cor-rect wiring before turning power on.
• Use a special INTERBUS cable and connect the cable as shown below. Use D-sub connectors made of metal or made of plastic with metallic plating. Connect the cable shield with the connector housing electrically.
• INTERBUS Cable Connector Pinouts
• Stripping and Clamping Cable Ends
• Leave open the remote out connector at the last station in the net-work.
• Supply power to each slave station or to each group of stations sepa-rately.
• Master and slave stations may be powered up in any order. But, if a slave station is not powered up while the master is in preparation for transmission, a network error will result.
• Causes of network errors include disconnection or short-circuit of the network cable, strong external noise, invalid command sent to the master station, momentary power voltage drop below the minimum power voltage, faulty transmission line, incorrect cable, and transmis-sion longer than the rated distance.
• When a network error occurs, all outputs are turned off.• For further information on INTERBUS, read documents published by
the INTERBUS CLUB.
16
9 5
/DO 6DO 1/DI 7DI 2COM 3
95
Housing
GreenYellowPinkGray
Brown
6 /DO1 DO7 /DI2 DI3 COM
HousingSolderedSide
SolderedSide
Bridge pins 5 and 9 inside the housing of the male connector.
1 6
95
D-sub 9-pin Male Connector
D-sub 9-pin Female Connector
3 8
20
First, strip the cable sheath 20 mm from both ends of the cable and shorten the braided screen by 12 mm.Bare the core ends 3 mm.
Next, place the braided screen evenly around the cable sheath.Clamp the shield under the cable grip in the connector housing for conduc-tive connection with the housing.
8-Point Sink Input
8-Point Transistor Protect Source Output
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
ContactSwitch
ContactSwitch
++
––
Brown (Red)
Blue (Black)
IN0Black (White)
IN1
Brown (White)
Blue (Black)
IN7
IN6CommunicationInterface
ControlCircuit
DCPower
Network
DC3-wireSensor
PNPOutput
DC2-wireSensor
Relay
PilotLight
++
––
OUT7
ControlCircuit
Pro
tect
ion
Circ
uit
Pro
tect
ion
Circ
uit
DCPower
CommunicationInterface
Network
OUT0
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-61
J
16-Point Transistor Input Modules (DeviceNet)
Input Type Part Number
Source SX5D-SBN16SSink SX5D-SBN16K
Key features include:• Communicate with DeviceNet network• 16-point input module (sink/source)• Removable terminal blocks
DC Input Type
Part No. SX5D–SBN16S SX5D–SBN16KInput Type DC source input DC sink input
Input Logic Active Low Active High
Input Points 16 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)
No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
Turn ON Voltage 6V maximum 10V minimum
Turn OFF Voltage 10V minimum 6V maximum
Input Current 6 mA/24V DC 6 mA/24V DC
Common 1 common
Current Draw 190 mA 170 mA
Communication Speed and Distance
Bus Transmission RateTransmission Distance
Thick Cable Thin Cable
DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m
Communication Cable
Bus Network I/F Connector (on the module) Cable
DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU
DeviceNet cable
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS2)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 8 IN81 IN1 9 IN92 IN2 10 IN103 IN3 11 IN114 IN4 12 IN125 IN5 13 IN136 IN6 14 IN147 IN7 15 IN15
Communication Configuration
[Baud Rate Selection][Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1
125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON
Output/Load H/LLOAD OFF OFFHOLD ON
System Reserve NOFixed to OFF(Selection Prohibited) ON
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
J-62 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
DC Power
ContactSwitch
ContactSwitch
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
++
–Blue (White)
IN0Black (White)
Brown (Red)
Network
Brown (Black)IN1
Blue (Black)
IN14
IN15
ControlCircuit
DC3-wireSensorNPN
Output
DC2-wireSensor
CommunicationInterface
–3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
ContactSwitch
ContactSwitch
++
––
Brown (Red)
Blue (Black)
IN0Black (White)
IN1
Brown (White)
Blue (Black)
IN15
IN14CommunicationInterface
ControlCircuit
DCPower
Network
DC3-wireSensor
PNPOutput
DC2-wireSensor
16-Point Source Input 16-Point Sink Input
Wiring DeviceNet Cable
• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.
• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of
matching colors.• DeviceNet Cable
Cable Part No. MakerThick Cable 1485C-P1A50
Rockwell AutomationThin Cable 1485C-P1-C150
Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5
0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON
1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON
2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON
3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON
4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON
5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON
6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON
7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON
8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON
9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON
15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON
23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON
24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON
25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON
26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON
27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON
28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON
29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON
30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON
31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON
SX5D-SBN16S SX5D-SBN16K
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-63
J
8-Point Relay Output Module (DeviceNet)
Output Type Part Number
Relay Output SX5D-SBR08
Key features include:• Communicate with DeviceNet network• 8-point relay output module• Handles current up to 5A per point• Removable terminal blocks
Terminal Arrangement
Upper Terminal Block (SX9Z-SS4)
Lower Terminal Block (SX9Z-SS5)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 4 OUT4
C0 COM0 C4 COM41 OUT1 5 OUT5
C1 COM1 C5 COM52 OUT2 6 OUT6
C2 COM2 C6 COM63 OUT3 7 OUT7
C3 COM3 C7 COM7
Communication Speed and Distance
Bus Transmission RateTransmission Distance
Thick Cable Thin Cable
DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m
Communication Cable
Bus Network I/F Connector (on the module) Cable
DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU
DeviceNet cable
Communication Configuration
[Baud Rate Selection]
[Output Hold or Load Off][System Reserve]
Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON
Output/Load H/LLOAD OFF OFFHOLD ON
System Reserve NOFixed to OFF(Selection Prohibited) ON
Relay Output Type
Rated Relay Contact
Part No. SX5D–SBR08Output Type Relay outputOutput Points 8 pointsOutput Type 1NO relay contactRated Load Voltage 250V AC, 24V DCMaximum Load Current 5A/point Commons/Current 8 commons/5ACurrent Draw 120 mABuilt-in Relay PCB mount, not replaceable
Maximum Applicable Voltage 250V AC, 125V DCMaximum Current 5ARated Load (resistive load) 250V AC/5A, 24V DC/5AMinimum Applicable Load 1V DC / 1mA
LifeMechanical 20,000,000 operations minimum
(18,000 operations/hour)
Electrical See Electrical Life Curve on next page (1,800 operations/hour)
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
J-64 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Wiring DeviceNet Cable
• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.
• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of
matching colors.• DeviceNet Cable
Cable Type No. MakerThick Cable 1485C-P1A50
Rockwell AutomationThin Cable 1485C-P1-C150
8-Point Relay Output
Load PowerPilotLight
Load Power
Solenoid
PilotLight
Load Power
Load Power
Solenoid
++
Network
OUT1COM1
COM7OUT7
OUT0COM0
COM6OUT6
ControlCircuit
CommunicationInterface
DCPower
––
Reference Data
Electrical Life Curve: Relay in SX5D-SBR08
Note 1: AC/DC Resistive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%
Note 2: AC Inductive Load
Note 3: DC Inductive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%Time constant: L/R =15 msec
Line MakingCurrent
BreakingCurrent Frequency Duty
RatioSolid 10 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 1800 operations/h
40%Dashed 5 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 300 operations/h
100
500
50
10
0.05 0.1 1 2 3 50.2 0.3 0.5
110V ACInductive
220V ACInductive
220V AC Resistive110V AC Resistive
AC Load
Life
(x
1000
0 op
erat
ions
)
Load Current (A)
100
500
50
10
0.05 0.1 1 2 3 50.2 0.3 0.5
110V DCInductive
24V DC Resistive
48V DC Resistive
24V DC Inductive
Load Current (A)
110 DC Resistive
Life
(x
1000
0 op
erat
ions
)
48V DC Inductive
DC Load
Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5
0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON
1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON
2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON
3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON
4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON
5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON
6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON
7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON
8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON
9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON
15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON
23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON
24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON
25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON
26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON
27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON
28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON
29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON
30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON
31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON
SX5D-SBR08
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-65
J
Communication Speed and Distance
Bus Transmission RateTransmission Distance
Thick Cable Thin Cable
DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m
Communication Cable
Bus Network I/F Connector (on the module) Cable
DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU
DeviceNet cable
Communication Configuration
[Baud Rate Selection] [Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON
Output/Load H/LLOAD OFF OFFHOLD ON
System Reserve NOFixed to OFF(Selection Prohibited) ON
16-Point Transistor Output Modules (DeviceNet)
Key features include:• Communicate with DeviceNet network• 16-point transistor output module (sink/source)• Removable terminal blocks• Source output short circuit and overload protected
Transistor Output Type
Part No. SX5D–SBT16K SX5D–SBT16P
Output Type Sink output Protect source output
Output Points 16 points
Output Type N-channel MOS open drain
P-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 3 to 30V DC 19 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/6A
Short-circuit Protection No Yes
Current Draw 70 mA 100 mA
Terminal Arrangement
•
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS2)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 8 OUT81 OUT1 9 OUT92 OUT2 10 OUT103 OUT3 11 OUT114 OUT4 12 OUT125 OUT5 13 OUT136 OUT6 14 OUT147 OUT7 15 OUT15
Output Type Part Number
Sink SX5D-SBT16KSource SX5D-SBT16P
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
J-66 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Wiring DeviceNet Cable
• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.
• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of
matching colors.• DeviceNet Cable
Cable Type No. MakerThick Cable 1485C-P1A50
Rockwell AutomationThin Cable 1485C-P1-C150
16-Point Transistor Sink Output
Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5
0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON
1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON
2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON
3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON
4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON
5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON
6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON
7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON
8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON
9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON
15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON
23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON
24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON
25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON
26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON
27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON
28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON
29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON
30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON
31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON
16-Point Transistor Protect Source Output
SX5D-SBT16K SX5D-SBT16P
Relay
PilotLight
++
––
OUT15
ControlCircuit
Pro
tect
ion
Circ
uit
Pro
tect
ion
Circ
uit
DCPower
CommunicationInterface
Network
OUT0
Relay
PilotLight
Relay
++
––
OUT0
OUT1
DCPower
ControlCircuit
CommunicationInterface
Network
OUT15
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-67
J
Communication Speed and Distance
Bus Transmission RateTransmission Distance
Thick Cable Thin Cable
DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m
Communication Cable
Bus Network I/F Connector (on the module) Cable
DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU
DeviceNet cable
Communication Configuration
[Baud Rate Selection]
[Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON(Selection Prohibited) ON ON
Output/Load H/LLOAD OFF OFFHOLD ON
System Reserve NOFixed to OFF(Selection Prohibited) ON
8-Point Source Input & 8-Point Transistor Sink Output Module (DeviceNet)
Key features include:• Communicate with DeviceNet network• 8-point source input and 8-point sink output module• Removable terminal blocks
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS3)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7
DC Input / Transistor Sink Output Type
Part No. SX5D–SBM16KI/O Type Source input / sink output
InputInput Logic Active Low
Input Points 8 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
ON Voltage 6V maximum
OFF Voltage 10V minimum
Input Current 6 mA/24V DC
Common 1 common
OutputOutput Points 8 points
Output Type N-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 3 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/4A
Short-circuit Protection No
Current Draw 130 mA
Input/Output Type Part Number
Source Input/Sink Output SX5D-SBM16K
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
J-68 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Wiring DeviceNet Cable
• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.
• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of
matching colors.• DeviceNet Cable
Cable Type No. MakerThick Cable 1485C-P1A50
Rockwell AutomationThin Cable 1485C-P1-C150
8-Point Source Input 8-Point Transistor Sink Output
DC Power
ContactSwitch
ContactSwitch
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
++
–Blue (White)
IN0Black (White)
Brown (Red)
Network
Brown (Black)IN1
Blue (Black)
IN6
IN7
ControlCircuit
DC3-wireSensorNPN
Output
DC2-wireSensor
CommunicationInterface
–
Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5
0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON
1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON
2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON
3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON
4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON
5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON
6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON
7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON
8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON
9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON
15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON
23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON
24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON
25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON
26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON
27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON
28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON
29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON
30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON
31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON
Relay
PilotLight
Relay
++
––
OUT0
OUT1
DCPower
ControlCircuit
CommunicationInterface
Network
OUT7
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-69
J
8-Point Sink Input & 8-Point Transistor Source Output Module (DeviceNet)
Key features include:• Communicate with DeviceNet network• 8-point sink input and 8-point source output module• Removable terminal blocks• Source output short circuit and overload protected
DC Input / Transistor Source Output Type
Part No. SX5D–SBM16PI/O Type Sink input / protect source output
InputInput Logic Active High
Input Points 8 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
ON Voltage 10V minimum
OFF Voltage 6V maximum
Input Current 6 mA/24V DC
Common 1 common
OutputOutput Points 8 points
Output Type P-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 19 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/4A
Short-circuit Protection Yes
Current Draw 140 mA
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS3)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7
Input/Output Type Part Number
Sink Input/Source Output SX5D-SBM16P
Communication Speed and Distance
Bus Transmission RateTransmission Distance
Thick Cable Thin Cable
DeviceNet125k baud 500m 100m250k baud 250m 100m500k baud 100m 100m
Communication Cable
Bus Network I/F Connector (on the module) Cable
DeviceNetPhoenix Contact5-pin connector MSTBV2.5/5-GF-5.08AU
DeviceNet cable
Communication Configuration
[Baud Rate Selection]
[Output Hold or Load Off] [System Reserve]Baud Rate DR0 DR1125 kbps OFF OFF250 kbps ON OFF500 kbps OFF ON
(Selection Prohibited) ON ON
Output/Load H/LLOAD OFF OFF
HOLD ON
System Reserve NOFixed to OFF
(Selection Prohibited) ON
Programmable Logic Controllers SX5 Smart I/O (DeviceNet)
J-70 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Wiring DeviceNet Cable
• DeviceNet requires two power voltages; one for communication and the other for internal circuit and load.
• Use a special DeviceNet cable for connecting to the DeviceNet network.• Connect the core wires of the cable to terminals identified by labels of
matching colors.• DeviceNet Cable
Cable Type No. MakerThick Cable 1485C-P1A50
Rockwell AutomationThin Cable 1485C-P1-C150
Node Address SelectionNode Address NA0 NA1 NA2 NA3 NA4 NA5 Node Address NA0 NA1 NA2 NA3 NA4 NA5
0 OFF OFF OFF OFF OFF OFF 32 OFF OFF OFF OFF OFF ON
1 ON OFF OFF OFF OFF OFF 33 ON OFF OFF OFF OFF ON
2 OFF ON OFF OFF OFF OFF 34 OFF ON OFF OFF OFF ON
3 ON ON OFF OFF OFF OFF 35 ON ON OFF OFF OFF ON
4 OFF OFF ON OFF OFF OFF 36 OFF OFF ON OFF OFF ON
5 ON OFF ON OFF OFF OFF 37 ON OFF ON OFF OFF ON
6 OFF ON ON OFF OFF OFF 38 OFF ON ON OFF OFF ON
7 ON ON ON OFF OFF OFF 39 ON ON ON OFF OFF ON
8 OFF OFF OFF ON OFF OFF 40 OFF OFF OFF ON OFF ON
9 ON OFF OFF ON OFF OFF 41 ON OFF OFF ON OFF ON
10 OFF ON OFF ON OFF OFF 42 OFF ON OFF ON OFF ON
11 ON ON OFF ON OFF OFF 43 ON ON OFF ON OFF ON
12 OFF OFF ON ON OFF OFF 44 OFF OFF ON ON OFF ON
13 ON OFF ON ON OFF OFF 45 ON OFF ON ON OFF ON
14 OFF ON ON ON OFF OFF 46 OFF ON ON ON OFF ON
15 ON ON ON ON OFF OFF 47 ON ON ON ON OFF ON
16 OFF OFF OFF OFF ON OFF 48 OFF OFF OFF OFF ON ON
17 ON OFF OFF OFF ON OFF 49 ON OFF OFF OFF ON ON
18 OFF ON OFF OFF ON OFF 50 OFF ON OFF OFF ON ON
19 ON ON OFF OFF ON OFF 51 ON ON OFF OFF ON ON
20 OFF OFF ON OFF ON OFF 52 OFF OFF ON OFF ON ON
21 ON OFF ON OFF ON OFF 53 ON OFF ON OFF ON ON
22 OFF ON ON OFF ON OFF 54 OFF ON ON OFF ON ON
23 ON ON ON OFF ON OFF 55 ON ON ON OFF ON ON
24 OFF OFF OFF ON ON OFF 56 OFF OFF OFF ON ON ON
25 ON OFF OFF ON ON OFF 57 ON OFF OFF ON ON ON
26 OFF ON OFF ON ON OFF 58 OFF ON OFF ON ON ON
27 ON ON OFF ON ON OFF 59 ON ON OFF ON ON ON
28 OFF OFF ON ON ON OFF 60 OFF OFF ON ON ON ON
29 ON OFF ON ON ON OFF 61 ON OFF ON ON ON ON
30 OFF ON ON ON ON OFF 62 OFF ON ON ON ON ON
31 ON ON ON ON ON OFF 63 ON ON ON ON ON ON
8-Point Sink Input
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
ContactSwitch
ContactSwitch
++
––
Brown (Red)
Blue (Black)
IN0Black (White)
IN1
Brown (White)
Blue (Black)
IN7
IN6CommunicationInterface
ControlCircuit
DCPower
Network
DC3-wireSensorPNP
Output
DC2-wireSensor
8-Point Transistor Protect Source Output
Relay
PilotLight
++
––
OUT7
ControlCircuit
Pro
tect
ion
Circ
uit
Pro
tect
ion
Circ
uit
DCPower
CommunicationInterface
Network
OUT0
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-71
J
Input Type Part Number
Source SX5L-SBN16SSink SX5L-SBN16K
Key features include:• Communicate with LONWORKS network• 16-point transistor input module (sink/source)• Removable terminal blocks
DC Input Type
Part No. SX5L–SBN16S SX5L–SBN16KInput Type DC source input DC sink input
Input Logic Active Low Active High
Input Points 16 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)
No-voltage input (2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
Turn ON Voltage 6V maximum 10V minimum
Turn OFF Voltage 10V minimum 6V maximum
Input Current 6 mA/24V DC 6 mA/24V DC
Common 1 common
Current Draw 150 mA 130 mA
Communication Speed and Distance
Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).
Bus Baud Rate Transmission Distance
LonWorks 78 kbps 500m (total length) 400m (between nodes)
Communication Cable
Bus Network I/F Connector (on the module) Cable
LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08
Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS2)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 8 IN81 IN1 9 IN92 IN2 10 IN103 IN3 11 IN114 IN4 12 IN125 IN5 13 IN136 IN6 14 IN147 IN7 15 IN15
Communication Configuration
All SX5L Modules:• The application program of the LonWorks is installed in the Neuron
chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-
msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs
also go off.• The SX5L does not use SNVT.
SX5L-SBN16S/SX5L-SBT16K:• Output network variables are updated only at the transition of the
input status. (When all inputs are off at power-up, network variables are not updated.)
• When nv_update_fails is TRUE(1) while using the data acknowl-edged service (ACKD), the ERR LED goes on.
• The ERR LED goes off when nv_update_succeeds is TRUE(1).(When an attempt to send network variables fails, resending does not occur until the input changes status.
continued
16-Point Transistor Input Modules (LONWORKS)
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
J-72 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Communication Configuration Continued
• When modifying the application program, please consult IDEC.
SX5L-SBN16SSX5L-SBN16K
8
15Input
InputOutput
0
7
nv_o8[1]
nv_o16
nv_o8[0]Input to SX5L
Network Variables
Input to SX5L
Wiring LONWORKS Cable
• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.
• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.
• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.
• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.
DC Power
ContactSwitch
ContactSwitch
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
++
–Blue (White)
IN0Black (White)
Brown (Red)
Network
Brown (Black)IN1
Blue (Black)
IN14
IN15
ControlCircuit
DC3-wireSensorNPN
Output
DC2-wireSensor
CommunicationInterface
–
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
ContactSwitch
ContactSwitch
++
––
Brown (Red)
Blue (Black)
IN0Black (White)
IN1
Brown (White)
Blue (Black)
IN15
IN14CommunicationInterface
ControlCircuit
DCPower
Network
DC3-wireSensor
PNPOutput
DC2-wireSensor
16-Point Source Input
16-Point Sink Input
SX5L-SBN16S
SX5L-SBN16K
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-73
J
8-Point Relay Output Module (LONWORKS)
Output Type Part Number
Relay Output SX5L-SBR08
Key features include:• Communicate with LONWORKS network• 8-point relay output module• Handles current up to 5A per point• Removable terminal blocks
Relay Output Type
Rated Relay Contact
Part No. SX5L–SBR08Output Type Relay output
Output Points 8 points
Output Type 1NO relay contact
Rated Load Voltage 250V AC, 24V DC
Maximum Load Current 5A/point
Commons/Current 8 commons/5A
Current Draw 80 mA
Built-in Relay PCB mount, not replaceable
Maximum Applicable Voltage 250V AC, 125V DC
Maximum Current 5A
Rated Load (resistive load) 250V AC/5A, 24V DC/5A
Minimum Applicable Load 1V DC / 1mA
LifeMechanical 20,000,000 operations minimum
(18,000 operations/ hour)
Electrical See Electrical Life Curve on next page (1,800 operations/ hour)
Terminal Arrangement
Upper Terminal Block (SX9Z-SS4)
Lower Terminal Block (SX9Z-SS5)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 4 OUT4
C0 COM0 C4 COM41 OUT1 5 OUT5
C1 COM1 C5 COM52 OUT2 6 OUT6
C2 COM2 C6 COM63 OUT3 7 OUT7
C3 COM3 C7 COM7
Communication Speed and Distance
Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).
Bus Baud Rate Transmission Distance
LonWorks 78 kbps 500m (total length) 400m (between nodes)
Communication Cable
Bus Network I/F Connector (on the module) Cable
LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08
Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2
Communication Configuration
All SX5L Modules:• The application program of the LonWorks is installed in the Neuron
chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-
msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs
also go off.• The SX5L does not use SNVT.
SX5L-SBR08:• Output is updated only when input network variables are received.
(At power-up to the network, all outputs remain off until initial com-munication starts.)
• When modifying the application program, please consult IDEC.
SX5L-SBR08
Output0
7nv_i8[0]
Input Network Variable
Output from SX5L
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
J-74 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Wiring LONWORKS Cable
• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.
• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.
• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.
• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.
8-Point Relay Output
Load PowerPilotLight
Load Power
Solenoid
PilotLight
Load Power
Load Power
Solenoid
++
Network
OUT1COM1
COM7OUT7
OUT0COM0
COM6OUT6
ControlCircuit
CommunicationInterface
DCPower
––
Reference Data Electrical Life Curve: Relay in SX5L-SBR08
Note 1: AC/DC Resistive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%
Note 2: AC Inductive Load
Note 3: DC Inductive LoadOperating frequency: 1800 operations/hourDuty ratio: 40%Time constant: L/R =15 msec
Line MakingCurrent
BreakingCurrent Frequency Duty
RatioSolid 10 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 1800 operations/h
40%Dashed 5 I, cos θ = 0.7 I, cos θ = 0.3 to 0.4 300 operations/h
100
500
50
10
0.05 0.1 1 2 3 50.2 0.3 0.5
110V ACInductive
220V ACInductive
220V AC Resistive110V AC Resistive
AC Load
Life
(x
1000
0 op
erat
ions
)
Load Current (A)
100
500
50
10
0.05 0.1 1 2 3 50.2 0.3 0.5
110V DCInductive
24V DC Resistive
48V DC Resistive
24V DC Inductive
Load Current (A)
110 DC Resistive
Life
(x
1000
0 op
erat
ions
)
48V DC Inductive
DC Load
SX5L-SBR08
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-75
J
Key features include:• Communicate with LONWORKS network• 16-point transistor output module (sink/source)• Removable terminal blocks• Source output short circuit and overload protected
Transistor Output Type
Part No. SX5L–SBT16K SX5L–SBT16P
Output Type Sink output Protect source output
Output Points 16 points
Output Type N-channel MOS open drain
P-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 3 to 30V DC 19 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/6A
Short-circuit Protection No Yes
Current Draw 30 mA 60 mA
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS2)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 OUT0 8 OUT81 OUT1 9 OUT92 OUT2 10 OUT103 OUT3 11 OUT114 OUT4 12 OUT125 OUT5 13 OUT136 OUT6 14 OUT147 OUT7 15 OUT15
Output Type Part Number
Sink SX5L-SBT16KSource SX5L-SBT16P
16-Point Transistor Output Modules (LONWORKS)
Communication Speed and Distance
Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).
Bus Baud Rate Transmission Distance
LonWorks 78 kbps 500m (total length) 400m (between nodes)
Communication Cable
Bus Network I/F Connector (on the module) Cable
LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08
Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2
Communication Configuration
All SX5L Modules:• The application program of the LonWorks is installed in the Neuron
chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-
msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs
also go off.• The SX5L does not use SNVT.
SX5L-SBT16P/SX5L-SBT16K:• Output is updated only when input network variables are received.
(At power-up to the network, all outputs remain off until initial com-munication starts.)
continued
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
J-76 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Communication Configuration continued
• When modifying the application program, please consult IDEC.
Output from SX5L
SX5L-SBT16KSX5L-SBT16P
Output
Output0
7
8
15
Input
nv_i8[1]
nv_i16
nv_i8[0]
Network Variables
Output from SX5L
Wiring LONWORKS Cable
• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.
• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.
• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.
• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.
16-Point Transistor Sink Output
Relay
PilotLight
++
––
OUT15
ControlCircuit
Pro
tect
ion
Circ
uit
Pro
tect
ion
Circ
uit
DCPower
CommunicationInterface
Network
OUT0
16-Point Transistor Protect Source Output
SX5L-SBT16K
SX5L-SBT16P
Relay
PilotLight
Relay
++
––
OUT0
OUT1
DCPower
ControlCircuit
CommunicationInterface
Network
OUT15
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-77
J
8-Point Source Input & 8-Point Transistor Sink Output Module (LONWORKS)
Key features include:• Communicate with LONWORKS network• 8-point source input and 8-point sink output module • Removable terminal blocks
DC Input / Transistor Sink Output Type
Part No. SX5L–SBM16KI/O Type Source input / sink output
InputInput Logic Active Low
Input Points 8 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire NPN sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
ON Voltage 6V maximum
OFF Voltage 10V minimum
Input Current 6 mA/24V DC
Common 1 common
OutputOutput Points 8 points
Output Type N-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 3 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/4A
Short-circuit Protection No
Current Draw 95 mA
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS3)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7
Input/Output Type Part Number
Source Input/Sink Output SX5L-SBM16K
Communication Speed and Distance
Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).
Bus Baud Rate Transmission Distance
LonWorks 78 kbps 500m (total length) 400m (between nodes)
Communication Cable
Bus Network I/F Connector (on the module) Cable
LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08
Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2
Communication Configuration
All SX5L Modules:• The application program of the LonWorks is installed in the Neuron
chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-
msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs
also go off.• The SX5L does not use SNVT.
SX5L-SBM16K (inputs):• Output network variables are updated only at the transition of the
input status. (When all inputs are off at power-up, network variables are not updated.)
• When nv_update_fails is TRUE(1) while using the data acknowl-edged service (ACKD), the ERR LED goes on.
• The ERR LED goes off when nv_update_succeeds is TRUE(1).(When an attempt to send network variables fails, resending does not occur until the input changes status.
continued
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
J-78 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
8-Point Source Input
DC Power
ContactSwitch
ContactSwitch
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
++
–Blue (White)
IN0Black (White)
Brown (Red)
Network
Brown (Black)IN1
Blue (Black)
IN6
IN7
ControlCircuit
DC3-wireSensorNPN
Output
DC2-wireSensor
CommunicationInterface
–
8-Point Transistor Sink Output
Relay
PilotLight
Relay
++
––
OUT0
OUT1
DCPower
ControlCircuit
CommunicationInterface
Network
OUT7
Communication Configuration ContinuedSX5L-SBM16K (outputs):
• Output is updated only when input network variables are received.(At power-up to the network, all outputs remain off until initial commu-nication starts.)
• When modifying the application program, please consult IDEC.
SX5L-SBM16K
Output
Input0
7
0
7
nv_o8[0]
nv_i8[0]
Output Network Variable
Input Network Variable
Input to SX5L
Output from SX5L
Wiring LONWORKS Cable
• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.
• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.
• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.
• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-79
J
Communication Speed and Distance
Note: The transmission distances represent the values when using Level 4, 22 AWG cables (free topology).
Bus Baud Rate Transmission Distance
LonWorks 78 kbps 500m (total length) 400m (between nodes)
Communication Cable
Bus Network I/F Connector (on the module) Cable
LonWorksPhoenix Contact2-pin connectorMSTBV2.5/2-GF-5.08
Single twisted-pair cableAWG24 to 140.2 to 2.5 mm2
Communication Configuration
All SX5L Modules:• The application program of the LonWorks is installed in the Neuron
chip of the SX5L module.• When wink is executed, the RUN LED flashes for 3 seconds in 500-
msec increments.• In the off-line mode, the RUN and ERR LEDs go off and all outputs
also go off.• The SX5L does not use SNVT.
SX5L-SBM16P (inputs):• Output network variables are updated only at the transition of the
input status. (When all inputs are off at power-up, network variables are not updated.)
• When nv_update_fails is TRUE(1) while using the data acknowl-edged service (ACKD), the ERR LED goes on.
• The ERR LED goes off when nv_update_succeeds is TRUE(1).(When an attempt to send network variables fails, resending does not occur until the input changes status.
continued
Key features include:• Communicate with LONWORKS network• 8-point sink input and 8-point source output module • Removable terminal blocks• Source output short circuit and overload protected
DC Input / Transistor Source Output Type
Part No. SX5L–SBM16PI/O Type Sink input / protect source output
InputInput Logic Active High
Input Points 8 points
Input TypeNo-voltage input
(2-wire DC sensor, 3-wire PNP sensor, no-voltage contact)
Rated Input Voltage 24V DC
Input Voltage Range 0 to the power voltage
ON Voltage 10V minimum
OFF Voltage 6V maximum
Input Current 6 mA/24V DC
Common 1 common
OutputOutput Points 8 points
Output Type P-channel MOS open drain
Rated Load Voltage 24V DC
Load Voltage Range 19 to 30V DC
Maximum Load Current 0.5A/point
Commons/Current 1 common/4A
Short-circuit Protection Yes
Current Draw 100 mA
Terminal Arrangement
Upper Terminal Block (SX9Z-SS1)
Lower Terminal Block (SX9Z-SS3)
Symbol Signal Symbol Signal+ COM (+) + POWER (+)– COM (–) – POWER (–)0 IN0 0 OUT01 IN1 1 OUT12 IN2 2 OUT23 IN3 3 OUT34 IN4 4 OUT45 IN5 5 OUT56 IN6 6 OUT67 IN7 7 OUT7
Input/Output Type Sink Input/Source Output
Part Number SX5L-SBM16P
8-Point Sink Input & 8-Point Transistor Source Output Module (LONWORKS)
Programmable Logic Controllers SX5 Smart I/O (LONWORKS)
J-80 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
8-Point Sink Input
8-Point Transistor Protect Source Output
3.8 kΩ
3.8 kΩ
3.8 kΩ
3.8 kΩ
ContactSwitch
ContactSwitch
++
––
Brown (Red)
Blue (Black)
IN0Black (White)
IN1
Brown (White)
Blue (Black)
IN7
IN6CommunicationInterface
ControlCircuit
DCPower
Network
DC3-wireSensor
PNPOutput
DC2-wireSensor
Relay
PilotLight
++
––
OUT7
ControlCircuit
Pro
tect
ion
Circ
uit
Pro
tect
ion
Circ
uit
DCPower
CommunicationInterface
Network
OUT0
Communication Configuration ContinuedSX5L-SBM16P (outputs):
• Output is updated only when input network variables are received.(At power-up to the network, all outputs remain off until initial commu-nication starts.)
• When modifying the application program, please consult IDEC.
SX5L-SBM16P
Output
Input0
7
0
7
nv_o8[0]
nv_i8[0]
Output Network Variable
Input Network Variable
Input to SX5L
Output from SX5L
Wiring LONWORKS Cable
• Turn power off before wiring the SX5L to the LonWorks network. Make sure wiring is correct before turning power on. Supply power to each slave station or to each group of stations separately.
• The LONWORKS network uses a twisted-pair cable. The connector has no polarity and the core wires of the twisted-pair cable can be con-nected to either terminal of the connector.
• The LONWORKS network requires network management to enable communication between nodes, including the SX5L.
• The network management requires an XIF extension. For your XIF extension, find your XIF No., printed on the side of the SX5 module or on the shipping package. The network management is not completed successfully without the XIF extension.
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-81
J
CE CertifiedEMC ApprovedFile No. B950913332312
The Benchmark for Micro-PLCs
Key features of the Micro3 include:• Built-in communications and networking• Input/output analog capability• User program password protection• Catch input, pulse output• Real-time clock and calendar available• Built-in power supply for sensors• Arithmetic, comparison, and Boolean computation• High-speed: 400µ/100 steps, 10kHz
The True Micro PLC Ambassador
Key features of the Micro3C include:• All the features of the Micro3
• Talks both ASCII and binary• Equipped with two serial ports, RS232 and RS485• Capable of connecting to dial-up modem, serial printer,
and bar code reader• Up to 500 data registers• Handles a wide range of analog input signals• Comes with an easy reset button• Available in 2 sizes: 16- and 24-I/O with relay output
UL ListedFile No. E102542
CSA CertifiedFile No. LR66809
Micro3C
Micro3
CE CertifiedEMC ApprovedFile No. B950913332312
UL ListedFile No. E102542
CSA CertifiedFile No. LR66809
Programmable Logic Controllers Micro3 Series
J-82 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Standard Mode High-Speed ModeG
ener
al S
peci
ficat
ions
Program Capacity 1012 steps 100 steps (approximately)
Processing 2.9ms/1k steps (average) 400µs/100 steps (average)
Internal Relay 232 points 40 points
Data Register Micro3: 100 pointsMicro3C: 500 points
32 points
Control Data Register 10 points —
Counter/Timer 32 points total 16 points total
Shift Register 64 points 32 points
Communication Channel
Data link channel: RS485Baud rate: 19,200 bps (fixed)Cable length: 656' (200m) (maximum)Data link: 6 slave stations (maximum)Expansion: 1 unit (maximum)
—
Programming channel: complies with EIA RS485 (Micro3)/RS232 (Micro3C) standardsBaud rate: 1,200/2,400/4,800/9,600/19,200 bps (selectable); Extension: 16.4' (5m) (maximum)
Instructions Micro3: 22 basic, 33 advancedMicro3C: 22 basic, 35 advanced
Memory EEPROM
I/O See configurations shown on page J-85
Catch Input Relays 8 points
Special Internal Relay 16 points
Power Failure Protection Internal relay, shift register, counter, data register; backup time, lithium battery fully charged— With clock: 30 days at 25°C (approximately); Without clock: 50 days at 25°C (approximately)
Self-Diagnostic Function CPU error (WDT), user program CRC error, user program sum check error, communication error, sensor power overload, transistor output overload
Catch Input 8 points; Minimum detectable pulse width (when hard filter is set to 10); Input I0 ON pulse = 28µs,OFF pulse = 30µs; Inputs I1 to I7 ON pulse = 37µs, OFF pulse = 120µs (depending on input filter settings)
Input Filter Function(DC input type only)
Normal input: 0ms, 3ms, 7ms, 10ms; Catch input: Input I0 ON pulse = 4 to 616µs, OFF pulse = 6 to 618µs; Input I1 to I7 ON pulse = 20 to 625µs, OFF pulse = 120 to 618µs
High-Speed Counter 1 point, single-phase, 10kHz (maximum), 32 bits
Analog Potentiometer Micro3: 1 point (10-point), 2 points (16-, 24-point)Micro3C: 1 point only
Pulse Output 1 channel, frequency/PWM output (not available in Micro3C)
Real Time Clock Clock accuracy ±30s/month (maximum) at 25°C (typical); year, month, day, hour, minute, second
Sensor Power Supply 24V ±3.6V DC, 150mA (maximum) including input current, overload detected
.
AC Power DC Power
Elec
tric
al S
peci
ficat
ions
Rated Power Range 100 to 240V AC, 50/60Hz (85 to 264V) 24V DC (19 to 30V DC)
Power Consumption Approximately 30VA (240V AC) Approximately 14W (24V DC)
Inrush Current 40A (maximum)
Power Disruption 25ms (momentary disruption) allowed
Dielectric StrengthBetween power terminal and ground: 2,000V AC, 1 minute
Between power terminal and ground: 1,500V AC, 1 minute
Between I/O terminal and ground: 1,500V AC, 1 minute
Temperature Operating: 0 to 60°C, Storage: –20 to +70°C
Operating Humidity 45 to 85% RH (avoid condensation)
Vibration Resistance 5 to 55Hz, 6G, 2 hours in each of 3 axes
Shock Resistance 30G, 3 shocks in each of 3 axes
Noise Resistance Between power terminal and ground: 1.3kV, 1µs; Between I/O terminal and ground: 1kV, 1µs (with noise simulator) — complies with IEC1131-2
Insulation Resistance Between power or I/O terminal and ground: 10MΩ (minimum), 500V DC
Ground Resistance 100Ω (maximum)
Micro3C only available in 16 I/O or 24
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-83
J
Part Numbers: Micro3
Item Part Number Description Remarks
100 to 240V AC50/60HzPowerMicro3 CPU
Output: Relay240V AC, 2A30V DC, 2A
FC2A-CA16A1 16 I/O: 9 inputs and 7 outputs Inputs: 120V AC (85-132V AC) 50/60Hz(housing = 24 I/O size)
FC2A-C10A1FC2A-C16A1FC2A-C24A1
10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs
Inputs: 24V DC sink/source
Only the 16- and 24-I/O unitshave real-time clock/calendar
Output:Transistor Sink24V DC, 0.5A
FC2A-C10B1FC2A-C16B1FC2A-C24B1
10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs
24V DCPowerMicro3 CPU
Output: Relay240V AC, 2A30V DC, 2A
FC2A-C10A4FC2A-C16A4FC2A-C24A4
10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs
Output:Transistor Sink24V DC, 0.5A
FC2A-C10B4FC2A-C16B4FC2A-C24B4
10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs
Output:Transistor Source24V DC, 0.5A
FC2A-C10D4FC2A-C16D4FC2A-C24D4
10 I/O: 6 inputs and 4 outputs16 I/O: 9 inputs and 7 outputs24 I/O: 14 inputs and 10 outputs
Programming Starter Kits
MM-MICRO1MM-MICRO3-10MM-MICRO3-16MM-MICRO3-24MM-MICRO3C-16MM-MICRO3C-24MM-Cables
Micro-1 PLC, WindLDR, computer link cableMicro3 10 I/O, WindLDR, computer link cable, input switch simulatorMicro3 16 I/O, WindLDR, computer link cable, input switch simulatorMicro3 24 I/O, WindLDR, computer link cable, input switch simulatorMicro3C 16 I/O, WindLDR, computer link cable, input switch simulatorMicro3C 24 I/O, WindLDR, computer link cable, input switch simulatorWindLDR, 3 computer link cables for Micro-1, Micro3 and Micro3C
Program Loader FC2A-HL1EC Program loader with cable
Loader Cable FC2A-KL1FC2A-KL2
6.56' (2m) long16.4' (5m) long Connects program loader to Micro3
Loader Adaptor PSR-GA05005 5V power supply adaptor for using program loader when not connected to CPU
Computer Link Cable FC2A-KC2 Connects Micro3 or loader to PC (1:1 link), 6.56' (2m)
Memory Card FC2A-MC1 Used with program loader to store user programs in SRAM memory
Expansion Cable FC2A-KE1 Close proximity Micro3 link expansion, 9.84" (250mm) long
1:N Computer Link Interface Unit FC2A-LC1 One required to connect each Micro3 in a 1:N computer link system (all connected to one central RS232C/RS485 converter)
1:N Computer Link Interface Cable FC2A-KC3 One required to connect each Micro3 in a 1:N computer link system(connected to each interface unit), 32.8' (10m) long
1:N RS232C/RS485 Converter HD9Z-T11 One required to connect all Micro3 units in a 1:N computer link system
1:N RS232C/RS485 Converter HD9Z-T11-DS783One required to connect all Micro3 units in a 1:N computer link system;Additionally, the DS783 should be used in applications requiring PC to Micro3
communications via modem
1:N PC Cable HD9Z-C52 Connects RS232C/RS485 converter to PC in a 1:N computer link system, 4.92' (1.5m) long (D-sub 9-pin female computer connector)
Analog Input Unit
FC2A-AD1FC2A-AD2FC2A-AD3FC2A-AD4FC2A-AD5
0 to 5V0 to 10V±5V4 to 20mA±10V
Converts analog signals to digital andsends to input I0 of Micro3
(not for use with AC input type units)
Analog Output Unit
FC2A-DA1FC2A-DA2FC2A-DA3FC2A-DA4FC2A-DA5
0 to 5V0 to 10V±5V4 to 20mA±10V
Converts digital (PWM) signal from output Q0 of Micro3 to analog(not for use with relay output type units)
Analog Timer Unit PFA-1U11 For fine adjustment of analog timer preset value
Input SwitchesFC2A-SW6FC2A-SW9FC2A-SW14
Input simulator switches (6) for 10 I/O Micro3sInput simulator switches (9) for 16 I/O Micro3sInput simulator switches (14) for 24 I/O Micro3s
WindLDR™ WINDLDR Windows-based application software, performs ladder programming and monitors all IDEC PLCs including the Micro series, FA series, and Open NET controllers.
Programmable Logic Controllers Micro3 Series
J-84 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Optional Item Part Number DescriptionLoader Cable (2m) FC2A-KL3C Connects basic unit (loader port) and program loader
Loader Cable (2m) FC2A-KL4C Connects basic unit (data link terminal) and program loaderModem Cable (3m) FC2A-KM1C Connects basic unit (loader port) and modem (1:1 communications)PC Interface Cable (3m) FC2A-KC4C Connects basic unit (loader port) and PC (1:1 communications)PC Interface Cable (2m) FC2A-KC6C Connects basic unit (data link terminal) and PC (1:1 communications)User Communication Cable (2.4m) FC2A-KP1C Connects basic unit (loader port) and user’s equipmentPC Connect Cable (5m) HG9Z-XC183 Connects basic unit (loader port) and Micro O/I™Memory Card (RAM) FC2A-MC1 Memory to store user’s programs (64K)AC Adaptor PSR-GA05005 Connects basic unit (data link terminal) and program loader/PCExpansion Cable (25cm) FC2A-KE1 Connects basic unit and expansion function unit1:N Link Adaptor FC2A- MD1 Connects basic unit (data link terminal) and PCRS232C Cable (4 lines, 1.5m) HD9Z-C52 Connects link adaptor and PC (1:N communications), D-sub 9-pin
WindLDR™ WINDLDRWindows-based application software, performs ladder programmingand monitors IDEC’s Micro-1, Micro3, and Micro3C PLCs
Part Numbers: Micro3C
Item Part Number DescriptionAC Power
(100 to 240V AC, 50/60Hz power supply)FC2A-C24A1C 24 I/O (14 in, 10 out)
FC2A-C16A1C Base units:Input (24V DC sink/source)Relay output (240V AC/30V DC, 2A)
16 I/O (9 in, 7 out)
DC Power(24V DC, 19 to 30V DC)
FC2A-C24A4C 24 I/O (14 in, 10 out)
FC2A-C16A4C 16 I/O (9 in, 7 out)
Program Loader FC2A-HL1EC Version 2.0+; also compatible with Micro3C
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-85
J
A data link network is simple to set up. No special cables or junctions arerequired. Just wire up to 6 Micro3s or Micro3Cs in a bus configuration, over atotal distance of 656’ (200m).
Using a built-in data link, the master initiates communication automati-cally—no special programming is required. Values from 2 read registers and2 write registers are exchanged between the master and each slave.
Data link channel 19200, RS485 is fixed.
3. The expansion link and data link cannot be used concurrently.
6 Inputs4 Outputs
9 Inputs7 Outputs
12 Inputs8 Outputs
14 Inputs10 Outputs
15 Inputs11 Outputs
18 Inputs14 Outputs
20 Inputs14 Outputs
23 Inputs17 Outputs
28 Inputs20 Outputs
10
16
20
24
26
32
34
40
48
9 Inputs7 Outputs
16
14 Inputs10 Outputs
24
32
48
40
Master:
Slave #1 Slave #2 Slave #3
Slave #6 Slave #5 Slave #4
Slave #1 Slave #2 Slave #3
Slave #6 Slave #5 Slave #4
Master
Micro3 I/O Expansion
18 Inputs14 Outputs
28 Inputs20 Outputs
23 Inputs17 Outputs
2. These Micro3 expansions listed are examples. You may create your owncombinations as well.
FA3S
1. These Micro3C expansions listedare examples. You may createyour own combinations as well.
Micro3 and Micro3C Link with FA3S Master
A high-performance FA3S CPU an PF3S-SIF4 interface module can managedata transfer with up to 6 Micro3s. Two interface modules can be used witheach FA3S CP12 or CP13, making it possible to network up to 12 Micro3stotal.
Using a built-in data link, the master initiates communication automaticallywhen executing a network communication program. Values from 2 read regis-ters and 2 write registers are exchanged between the master and each slave.
Micro3C I/O Expansion Micro3 and Micro3C Data Link
Programmable Logic Controllers Micro3 Series
J-86 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
RS232 Cable
WindLDR combines the logic of ladder programming with theintuitive approach of a Windows environment. IDEC providesthe ideal PLC programming and monitoring solution.
IDEC’s WindLDR™ includes all the advantages of our CLIPand CUBIQ software, plus a Window-based, graphic inter-face. With extensive new features such as an icon-driventoolbar, on-line help, cross reference cut and paste, programcompass, line dialog screens, and debugging tools.
At an enticingly low price, there is no question—WindLDR isthe solution.
Currently, WindLDR supports the programming configurationfor IDEC’s Micro series. WindLDR is the bridge between olderapplications’ software/hardware and future generations ofIDEC PLCs.
Computer Link 1:1 Communication
Computer Link 1:N Communication (Micro3 only)
WindLDR™ Software Solution — One Application for All PLCs
Computer Link CableFC2A-KC27.87’ (2m) long To RS232C Port
The Micro3 and Micro3C can be programmed from a PC usingWindLDR ladder programming software. A computer linkcable is required to connect the PC’s RS232 serial port withthe Micro’s programming port.
A network of Micro3s can be set up for programming and monitoringwith WindLDR. The network can also be used for supervisory controland data acquisition (SCADA). Up to 32 Micro3s can be networks witha PC as the master. Each Micro3 should be programmed with a spe-cific device number in FUN9. FUN9 can be set with a program loaderor with a PC in 1:1 mode running WindLDR.
Slave #1 Slave #2
N ≤ 32
Link InterfaceFC2A-LC1
Link CableFC2A-KC3
AC Adaptor
RS232C/RS485ConverterHD9Z-T11
Slave #3 Slave #N
Tag Name Editor Advanced InstructionsMultiplication (MUL)
Computer Link CableFC2A-KC4C
9.84’ (3m) long
To RS232C Port To Loader Port(RS232C)
D-sub 9-pinFemale Connector
HD9Z-C52
or 24V DC P/S
Programming Port
Micro3
RS485
Built-inRS232/RS485
Converter
Micro3C
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-87
J
1st UnitFunction selector switch: 0
Protocol selector switch: 2, 3, or 4
RS232C/RS485 Converter FC2A-MD1(H x W x D)
5.92” x 4.33” x 1.34”(132 x 110 x 34mm)
RS232C CableHD9Z-C52
4.92’ (1.5m) long
D-sub 9-pin Female
Connector
To RS232C PortTo RS232C Port
–+24V DC or AC Adapter (9V DC, 350 mA)
Shielded twisted pair cable 656’ (200m) maximum
D-sub 25-pin Male
Connector
A B SG
2nd UnitFunction selector switch: 0
Protocol selector switch: 2, 3, or 4
A B SG
Nth Unit (N≤32)Function selector switch: 0
Protocol selector switch: 2, 3, or 4
A B SG
3rd UnitFunction selector switch: 0
Protocol selector switch: 2, 3, or 4
A B SG
1
T2
A3
B4
SG5
FG6
+7
–
SD
RD
POWER
DC IN
RS485SERIAL PORT
POWER SUPPLY24V DC
RS
232C
SE
RIA
L P
OR
T
RS232C/RS485CONVERTER
Type FC2A-MD1
Computer Link 1:N Communication (Micro3C only)
To set up a 1:N computer link system, connect your PC to the RS232C/RS485converter using RS232C cable HD9Z-C52. Connect the RS232C/RS485 con-verter to Micro3C units using shielded twisted pair cables.
Supply power to the RS232C/RS485 converter by connecting a 24V DC sourceto terminals 6 and 7 or by plugging an AC adapter to the DC IN jack.
Programmable Logic Controllers Micro3 Series
J-88 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Micro3CMicro3
Micro3 programs can be created or modified withthe hand held program loader. The loader programsin Boolean commands and displays four lines. It canbe programmed by using a PC or off line with a 5volt adaptor (PSR-GA05005). The loader also can beused to monitor and change all internal registersincluding timers and counters. An optional SRAMmemory card can also be used with the loader tostore up to 31 programs with alphanumeric filenames.
Spec
ifica
tions
Display 4 lines × 16 charactersBack-lit LCD with auto turn-off
Program Key 35 keys
Control Switch RUN/STOP for Micro operation
Power Supply From Micro through loader cable;From AC adaptor (5 to 6.5V DC, 4W) during off-line programming
Power Consumption 1.5W
Connection to Micro3 Loader cable FC2A-KL1, 6.56' (2m) or FC2A-KL2, 16.4' (5m)
Connection to Micro3C Loader cable to RS232 loader port FC2A-KL3C
Connection to Micro3C Loader cable to RS485 data link port FC2A-KL4C
Power Failure Protection Approximately 1 hour at 25°C
User Program Storage SRAM memory card stores up to 31 programs
Operating Temperature 0 to 50°C
Weight Approximately 300g
Dimensions (HxWxD) 7.283" × 3.740" × 1.181" (185 × 95 × 30mm)
FC2A-MC1Optional memory cardstores up to 31 programs
ProgramLoader
Program Loader
Program Loader Cables for Micro3 and Micro3C
Micro3C
AC Adapter (output: 5V DC)The loader cable 4C is not sup-plied with an AC adapter, which
must be prepared by the user
With Loader CableFC2A-KL1 (2m)FC2A-KL2 (5m)
With Loader Cable 3CFC2A-KL3C
The loader cable 3C has anRS232C/RS458 converter
in the middle
With Loader Cable 4CFC2A-KL4C
The loader cable 4Chas a power supply box in the middle
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-89
J
•
To connect a modem to the loader port on the Micro3C, use the modem cableFC2A-KM1C. Set the protocol selector switch to 1 or 3 to select user protocolfor the loader port.
Cable Connector Pinouts
Pin Description
1 FG Frame Ground
2 TDX Transmit Data
3 RXD Receive Data
4 RTS Request to Send
5 –– ––
6 –– ––
7 SG Signal Ground
8 DCD Data Carrier Detect
20 DTR Data Terminal Ready
To connect equipment with an RS232C communication port to the loader porton the Micro3C, use the user communication cable FC2A-KP1C. One end of theuser end communication cable 1C is not provided with a connector. It can beterminated with a proper connector to plug in to communicate with theRS232C port.
When the protocol selector switch is set to 1 or 3, the Micro3C can communi-cate with RS232C equipment through the loader port using the user protocol.When the protocol selector switch is set to 0, 2, or 4, the Micro3C can commu-nicate through the loader port using the loader protocol.
Cable Connector Pinouts
Pin Description AWG # # Color
1 RTS Request to Send 28 Black
2 DTR Data Terminal Ready 28 Yellow
3 TDX Transmit Data 28 Blue
4 RXD Receive Data 28 Green
5 DSR Data Set Ready 28 Brown
6 SG Signal Ground 28 Gray
7 SG Signal Ground 26 Red
8 NC No Connection 26 White
Cover –– Shield –– ––
Twisted
Twisted
•
Modem Cable FC2A-KM1C
9.84’ (3m) long
To RS232C Port
D-sub 25=pinMale Connector
To Loader Port(RS232C)
Modem
RS232C EquipmentUser Communication Cable FC2A-KP1C7.78’ (2.4m) long
To Loader Port(RS232C)
To RS232C Port
Attach a proper connector to the open end referring tothe cable connector pinouts
Micro3C: Connecting the Modem through the Loader Port
Micro3C: Connecting RS232C Equipment through the Loader Port
Micro3C
Micro3C
Programmable Logic Controllers Micro3 Series
J-90 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
The system setup demonstrates a program to send data to a printerusing the user communication TXD (transmit) instruction. Serialprinters used in this example are Seiko Electronic’s DPU-201GSand Citizen’s iDP3110 printers.
System Setup Protocol Selector SwitchSet to 1 or 3 to select user protocol
for the loader port
User Communication Cable 1CFC2A-KP1C
7.87’ (2.4m) long
Attach a connector to the open end of the usercommunication cable 1C referring to the cableconnector pinouts shown below
Cable Connections for Seiko Electronic’s DPU201GS
Mini DIN Connector Pinouts
Description Color Pin
Shield –– Cover
NC No Connection Black 1
NC No Connection Yellow 2
TXD Transmit Data Blue 3
NC No Connection Green 4
DSR Data Set Ready Brown 5
SG Signal Ground Gray 6
SG Signal Ground Red 7
NC No Connection White 8
D-Sub 9-pin Connector Pinouts
Pin Description
1 NC No Connection
2 NC No Connection
3 DATA Receive Data
4 NC No Connection
5 GND Ground
6 NC No Connection
7 NC No Connection
8 BUSY Busy Signal
9 NC No Connection
••
•
Micro3C: User Communication TXD
To RS232C Port
To Loader Port(RS232C)
Printer3
7 0 126
5 4
Micro3C
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-91
J
DC Input AC Input (Micro3 only)
Inpu
t Spe
cific
atio
ns
Rated Input Voltage(allowable range)
24V DC(19 to 30V DC)
100 to 120V AC(85 to 132V AC)
Rated Input Current 7mA (input I/0: 13mA) 10mA/point
Input Impedance 3.3kΩ (input I/0: 1.8kΩ) 13kΩ
On/Off Current On: 2.5mA (minimum) at 11V DCOff: 1.2mA (maximum)
On: 4mA (minimum) at 79V AC Off: 2mA (maximum)
On/Off Voltage On: 11V DC (minimum)Off: 5V DC (maximum)
On: 79V AC (minimum)Off: 20V AC (maximum)
On/Off Time Depends on input filter setting (see note) On: 20ms (maximum)Off: 20ms (maximum)
Rela
y O
utpu
t Spe
cific
atio
ns Configuration
10 I/O(Micro3 only)
4 outputs: Independent NO = 1 point, Common NO = 3 points
16 I/O7 outputs: Independent NO = 1 pointCommon NO = 2 points + 4 points
24 I/O10 outputs: Independent NO = 2 pointsCommon NO = 4 points + 4 points
AC in(Micro3 only)
7 outputs: Independent NO = 3 pointsCommon NO = 4 points
Switching CapacityIndependent contact: 240V AC or 30V DC, 2A (resistive load)Common contact: 240V AC or 30V DC, 2A × output points (resistive load)
Minimum Applicable Load 5V DC, 1mA (reference value)
Contact Resistance 30mΩ maximum (initial value)
Life RatingsMechanical: 20,000,000 operations (no load) at 1,800 operations/hourElectrical: 100,000 operations (rated load) at 1,800 operations/hour
Each unit can be used as a CPU or expansion I/O using a selection switch. Sink/source inputs can be used with NPN- or PNP-output sensors. Input on and off times can be selected using the input filter function (FUN7 setting).
CPU Input/Output
Key features of the Micro3 and Micro3C input include:• AC or DC inputs (Micro3) or DC inputs (Micro3C)• Expandable from 10 to 48 I/O points• Configure inputs: Sink or source for NPN or PNP devices• Each unit selectable: CPU or expansion I/O• LED indicators• Optical isolation
Programmable Logic Controllers Micro3 Series
J-92 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
G NC NC 20 1 3
COMGND
L N
GND100 to
240V AC
100 to120V
AC
C
AC Inputs(Micro3 only)
C0 1 2 3COM
COM
0 C1
LL
L L
Relay Outputs 10 I/O
External Power240V AC/30V DC2A x Output Points
0 1 2 3 64 5 +V––COM
COM
LL
LL
LL
L
+
–
0 1 2 3 64 5 -V++COM
COM
LL
LL
LL
L+
–ExternalPower24V DC
C0 1 2 3 64 5COM
COM
0 C1 C2COM
LL
LL
LL
L
C0 1 2 3 64 5COM
COM
0 C1 C2COM
LL
LL
LL
L
7 10 11C3COM
LLL
16 I/O24 I/O
ExternalPower24V DC
Transistor Outputs
DC Input Circuit Diagrams
Transistor and Relay Output Circuit Diagrams
G 20 1 3C
COMGND4 5
GND
+ – NC NC
ExternalPower
24V DC
+
–
G 20 1 3C
COMGND4 5
GND
+ – NC NC
ExternalPower
24V DC+
–
G 24V 0V 20 1 3C
COMGND4 5L N
GND
G 24V 0V 20 1 3C
COMGND4 5L N
GND
G 24V 0V 20 1 3C
COMGND4 5L N
GND
G 24V 0V 20 1 3C
COMGND4 5L N
GND
Using Sensor P/S
Using External P/S
100 to240V AC
100 to240V AC
100 to240V AC
100 to240V AC
24V DC 24V DC+– +
–
Sen
sor
Sen
sorDC Inputs
(AC power)
DC Inputs(DC power)
(Micro3 only)
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-93
J
Tran
sist
or O
utpu
t Spe
cific
atio
ns
Configuration10 I/O 4 outputs: Common NO = 4 points
16 I/O 7 outputs: Common NO = 3 points + 4 points24 I/O 10 outputs: Common NO = 5 points + 5 points
Rated Load 0.5A, 24V DC — Maximum: 0.625A/circuit (30V DC)Inrush Current 5A, 1ms (maximum)Leakage Current 0.1mA (maximum)On Voltage Sink: 1.5V DC (maximum)
On/Off Time On: 500µs (output Q0: 5µs),Off: 500µs (output Q0: 5µs)
External Current Draw 24V DC, 100mA (maximum)
16 I/O 24 I/O10 I/O
CPU: Transistor Output (Micro3 only)
Each unit can be used as a CPU or expansion I/O using a selection switch. Sink/source inputs can be used with NPN- or PNP-output sensors. Input on and off times can be selected using the input filter function (FUN7 setting).
DC
Inpu
t Spe
cific
atio
ns
Rated Input Voltage(allowable range)
24V DC(19 to 30V DC)
Rated Input Current 7mA (input I0: 13mA)
Input Impedance 3.3kΩ (input I0: 1.8kΩ)
On/Off Current On: 2.5mA (minimum) at 11V DC Off: 1.2mA (maximum)
On/Off Voltage On: 11V DC (minimum)Off: 5V DC (maximum)
On/Off Time Depends on input filter setting (see note)
Programmable Logic Controllers Micro3 Series
J-94 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Key features of the analog input and output units include:• Micro supports one analog in and one analog out• Input/output units accept a variety of signals • Units connect to input Ø and/or output Ø
AD Converter Unit DA Converter Unit
Spec
ifica
tions
Number of Inputs 1 channel 1 channel
Resolution 250 (see chart below) 245 (see chart below)
Total Accuracy ± 1% of the maximum value ± 1% of the maximum value
Conversion Time 125ms 0 to 95%: 500ms
Maximum Applicable Input 16V DC 30V DC
Maximum Applicable Output 30V DC Voltage output: 12V DC
Current output: 12V DC or –0.6V DC
Output Short Circuit Not allowed Allowed (infinite period of time)
Recommended Output LoadImpedance
—Voltage output: 5kΩ or moreCurrent output: 250Ω or less (300Ω maxi-mum)
Input Frequency — 312.5Hz (PWM mode must be set to MODE3)
Output Ripple — 1 LSB or less
Analog Input/Output Units
Analog output is only available for the Micro3.
Increments
PWM Operand S10 249
Minimum
Maximum
245
5
InputMinimum Maximum
0
249
250Increments
A/D Converted Value
D/A Converted Value
Analog/Digital Conversion Charts
Type Input Signal Range
AD
0 to 5V DC
0 to 10V DC
±5V DC
4 to 20mA DC
±10V DC
DA
0 to 5V DC
0 to 10V DC
±5V DC
4 to 20mA DC
±10V DC
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-95
J
+ –24V DC
A/D UNIT
INPUT4-20mA
POWER
SINK
SCE
+ –ANALOG WIRE TO
IN 0
INPUT OUTPUT
DC OUT24V 0V
DC INCOM 0
24V DCPower
+–
FG
AnalogInput
Shield Wire
Set the output selector switch to SCE.
When using the Micro inthe sink input connec-tion, select the sourceoutput from the A/Dconverter unit.
3A Fuse
1
PNP
+ –24V DC
A/D UNIT
INPUT4-20mA
POWER
SINK
SCE
+ –ANALOG WIRE TO
IN 0
INPUT OUTPUT
DC OUT24V 0V
DC INCOM 0
24V DCPower
+–
FG
Set the output selector
AnalogInput
Shield Wire
switch to SINK.
When using the Microin the source inputconnection, select thesink output from theA/D converter unit.
1
NPN
3A Fuse
Analog Input and Wiring Diagrams (Micro3 and Micro3C)
The A/D converter unit is used with the Micros to perform an 8-bitA/D conversion. The A/D converter unit reads an analog input sig-nal from an analog output device such as an analog distance sen-sor. The output from the A/D converter unit is entered to the Microinput I0 and converted into a digital value (0 through 249) using theA/D (analog/digital conversion) instruction. If the input to the A/D converter unit exceeds the input range, thenan overflow occurs, and 250 is set to the destination operand of theA/D instruction. Only one A/D converter unit can be connected tothe Micro base unit.
When the A/D converter unit is connected to the Micro, the HSC (high-speed counter) function cannot be used.
Source Input
Sink Input
Programmable Logic Controllers Micro3 Series
J-96 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
The D/A converter unit is used with the transistor output typeMicro3 base unit to perform an 8-bit D/A conversion. The pulsewidth modulation instruction is used to convert the digital value toa pulse output signal. The output from the Micro3 output Q0 isentered to the D/A converter unit to generate an analog current orvoltage output to control an inverter. Only one D/A converter unitcan be connected to the Micro3 base unit.
24V DCPower
+–FG
Set the input selector
Analog
Shield Wire
+ –24V DC
D/A UNIT
OUTPUT4-20mA
POWER
SCE
SINK
+ –ANALOG WIRE TO
OUT 0
OUTPUT INPUT
Ground the FG terminal.
switch to SINK.
Output
OUTCOM0(+) 0 1 2 3 OUT
COM1(+) 4 5 6 –V
When using a transistor protect source output type Micro3 base unit, select the sink input to the D/A converter unit.
1A Fuse
24V DCPower
+–FG
Set the input selector
Analog
Shield Wire
+ –24V DC
D/A UNIT
OUTPUT4-20mA
POWER
SCE
SINK
+ –ANALOG WIRE TO
OUT 0
OUTPUT INPUT
Ground the FG terminal.
switch to SCE.
Output
OUTCOM0(–) 0 1 2 3 OUT
COM1(–) 4 5 6 +V
When using a transistor sink out-put type Micro3 base unit, selectthe source input to the D/A con-verter unit.
1A Fuse
Analog Output and Wiring Diagrams (Micro3 only)
Transistor Sink Output
Transistor Protection Source Output form Micro3
Programmable Logic Controllers Micro3 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-97
J
Steps Instruction Description
Adv
ance
d In
stru
ctio
ns
1 0 NOP No operation
3 – 43 – 45 – 65 – 6
11121314
MOVMOVNIMOVIMOVN
Word moveWord move notWord indirect moveWord indirect move not
4 – 54 – 54 – 54 – 54 – 54 – 5
212223242526
CMP=CMP<>CMP<CMP>CMP<=CMP>=
Equal compareNot equal compareLess than compareGreater than compareLess than or equal compareGreater than or equal compare
4 – 54 – 54 – 54 – 5
31323334
ADDSUBMULDIV
AdditionSubtractionMultiplicationDivision
4 – 54 – 54 – 5
414243
ANDWORWXORW
And wordOr wordExclusive or word
3333
51525354
SFTLSFTRROTLROTR
Shift leftShift rightRotate leftRotate right
22221
7172737475
CALRCALWCLKRCLKWADJ
Calendar read*Calendar write*Clock read*Clock write*Adjust*
442
818283
DISPDGRDANR0
DisplayDigital switch readAnalog potentiometer 0 read
2 84 ANR1 Analog potentiometer 1 read*
332
919293
PULSPWMA/D
Pulse outputPulse width modulationConvert analog to digital
4242
A1A2A3A4
HSC0HSC1HSC2HSC3
H/S counter 0 (32 bits)H/S counter 1 (32 bits)H/S counter 2 (32 bits)H/S counter 3 (16 bits)
5 – 404 B1 TXD Transmit (Micro3C only)
5 – 404 B2 RXD Receive (Micro3C only)
4 – 5 B3 COMP2 Double word compare (Micro3C only)
Steps Instruction Description
Bas
ic In
stru
ctio
ns
111
ANDAND LODANDN
AndAnd loadAnd not
111
BPPBPSBRD
Bit popBit pushBit read
222
CNTCC=CC≥
CounterCounter compare =Counter compare ≥
1 END End11
JENDJMP
Jump endJump
11
LODLODN
LoadLoad not
11
MCSMCR
Master control setMaster control reset
— NOT Not111
OROR LODORN
OrOr loadOr not
11
OUTOUTN
OutputOutput not
11
RSTSET
ResetSet
22
SFRSFRN
Shift registerShift register not
11
SOTDSOTU
Single output fallingSingle output rising
222
TIMTMTMS
100ms timer10ms timer1ms timer
Instruction Set
Instructions designated by * are not affected by the change to the year 2000.
Programmable Logic Controllers Micro3 Series
J-98 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Dimensions
Key to Dimensions
AC Input Units W C
10 I/O 4.134" (105mm) 3.386" (86mm)
16 I/O 5.315" (135mm) 4.567" (116mm)
24 I/O* 6.496" (165mm) 5.748" (146mm)*
3.740"(95mm)
3.150"(80mm)
1.181"(30mm)
0.984"(25mm)
7.283"(185mm)
Program Loader
3.031"(77mm)
M4 tapped orØ 0.177" (Ø 4.5mm)
C
Mounting Hole Layout
1.77"(45mm)
2.76"(70mm)
2.76"(70mm)
3.15"(80mm)
1.38"(35mm)
Ø 0.17"
2 holes(4.3mm)
A/D and D/A Analog Converters
3.346"
(85mm)
W
2.362"
(60mm)
Micro3 and Micro3C Base Units
*Dimensions are the same for the 16 I/O AC input unit.
Programmable Logic Controllers Micro-1 Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-99
J
Gen
eral
Spe
cific
atio
ns
Programming Boolean or ladder logic
Available Instructions 15 basic instructions, 2 FUN instructions
Program Capacity 600 steps
Memory EEPROM memory built-in to base unit
Scan Time Average: 8µs per basic instruction
Input Base unit: 8 points, Expansion: 8, 4, or 2 points
Output Base unit: 6 points, Expansion: 6, 3, or 2 points
Total I/O Points 28 points (maximum)
Internal Relay 160 points (all points can be maintained)
Special Internal Relay 96 points
Shift Register 128 points
Catch Input 1 point, 0.5ms pulse
Single Shot Output 96 points
Timer 80 points, subtracting (0 to 999.9s)
Counter 45 points, adding (0 to 9999)(all points can be maintained)
Reversible Counter 2 points (all points can be maintained)
Computer Link Via RS232 interface unit
External Control Input Start/stop using switch on program loader
Power Failure Protection Capacitor back-up: 3 days; internal relay, shift register, counter, reversible counter
Self-Diagnostics CPU error (WDT), CRC error, check sumerror, communication error
Auto Start Function Operation starts after power-up
FA Series Compatibility Program loaders are interchangeable using special cables
Micro-1:The Original Micro-PLCEl
ectr
ical
Spe
cific
atio
ns
Rated Supply Voltage AC CPU base unit and (8 in/6 out) expansion: 100 to 240V AC, 50/60Hz (47.5–63Hz)24V DC base unit and all expansion units: 12V DC CPU base unit and (8 in/6 out) expansion
Voltage Range AC: 85 to 110% of rated voltage 24V DC: 80 to 120%; 12V DC: 70 to 120%
Dielectric Strength Between power or I/O terminal and ground: 1,500V AC, 1 minute
Insulation Resistance Between power or I/O terminal and ground: 10MΩ (500V DC megger)
Temperature Operating: 0 to +55°C; Storage: – 20 to +70°C
Operating Humidity 45 to 85% RH (avoid condensation)
Vibration Resistance 5 to 55Hz, 6G for 2 hours in each of 3 axes
Shock Resistance 30G, 3 shocks in each of 3 axes
Noise Resistance Between power or I/O terminal and ground: AC: ±1.3kV, 1µs; 24V DC: ±1.0kV, 1µs; 12V DC: ±500V, 1µs
Ground Resistance 100Ω (maximum)
Mounting Style 35mm DIN rail and panel mount
UL ListedFile No. E102542
CSA CertifiedFile No. LR66809
CE Certified
The CPU base unit suppliespower to the micro-expansionunits and program loader.Micro-expansion units are notcompatible with 12V DC CPU.
Key features of the Micro-1 PLC include:• Intelligent control economically replaces hard-wired systems • 8 inputs, 6 outputs• DC inputs, relay or transistor outputs• Expansion unit doubles I/O (16 inputs, 12 outputs)• Micro-expansion I/O for incremental I/O increases• 80 timers, 47 counters, 160 internal relays• CPU base unit supplies power for input signals• Program capacity 600 steps• Computer link, networking
EMC ApprovedFile No. E951113332321
Programmable Logic Controllers Micro-1 Series
J-100 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Part Numbers: Micro-1
CPU Base Unit
ACRelay Output
Source Input FC1A-C1A1E Power: 100–240V AC; NPN transistor inputs, relay outputsSink Input FC1A-C2A1E Power: 100–240V AC; PNP transistor inputs, relay outputs
Transistor OutputSource Input/Sink Output FC1A-C1B1E Power: 100–240V AC; NPN transistor inputs, NPN transistor outputsSink Input/Source Output FC1A-C2C1E Power: 100–240V AC; PNP transistor inputs, PNP transistor outputs
DC
Relay OutputSource Input
FC1A-C1A4E Power: 24V DC; NPN transistor inputs, relay outputsFC1A-C1A2E Power: 12V DC; NPN transistor inputs, relay outputs
Sink InputFC1A-C2A4E Power: 24V DC; PNP transistor inputs, relay outputsFC1A-C2A2E Power: 12V DC; PNP transistor inputs, relay outputs
Transistor OutputSource Input/Sink Output
FC1A-C1B4E Power: 24V DC; NPN transistor inputs, NPN transistor outputsFC1A-C1B2E Power: 12V DC; NPN transistor inputs, NPN transistor outputs
Sink Input/Source OutputFC1A-C2C4E Power: 24V DC; PNP transistor inputs, PNP transistor outputsFC1A-C2C2E Power: 12V DC; PNP transistor inputs, PNP transistor outputs
Expansion I/O
Relay OutputSource Input FC1A-E1A1E Power: 100–240V AC, NPN transistor inputs, relay outputs
Sink Input FC1A-E2A1E Power: 100–240V AC, PNP transistor inputs, relay outputs
Transistor OutputSource Input/Sink Output FC1A-E1B1E Power: 100–240V AC; NPN transistor inputs, NPN transistor outputs
Sink Input/Source Output FC1A-E2C1E Power: 100–240V AC; PNP transistor inputs, PNP transistor outputs
Relay OutputSource Input FC1A-E1A4E
FC1A-E1A2EPower: 24V DC, NPN transistor inputs, relay outputsPower: 12V DC, NPN transistor inputs, relay outputs
Sink Input FC1A-E2A4EFC1A-E2A2E
Power: 24V DC, PNP transistor inputs, relay outputsPower: 12V DC, PNP transistor inputs, relay outputs
Transistor OutputSource Input/Sink Output FC1A-E1B4E
FC1A-E1B2EPower: 24V DC, NPN transistor inputs, NPN transistor outputsPower: 12V DC, NPN transistor inputs, NPN transistor outputs
Sink Input/Source Output FC1A-E2C4EFC1A-E2C2E
Power: 24V DC, PNP transistor inputs, PNP transistor outputsPower: 12V DC, PNP transistor inputs, PNP transistor outputs
Accessories
Program Loader FC1A-HL1E 24 keys, 16-character LCD
Data Preset LoaderStandard FC1A-PL1E Change timer/counter presets, monitor I/O, internal relay, timer, counter
Multi-Function FC1A-PL2E Change preset values, monitor, direct set/reset, read program, and more
Loader Extension CableFC1A-KL1AFC1A-KL2AFC1A-KL3AFC1A-KL4A
5' (1.5m), connects program loader to base unit2.75" (70mm) curl cord (attached to loader)5' (1.5m), connects FA series program loader to Micro-1 base unit5' (1.5m), connects Micro-1 program loader to FA series CPU
I/O Expansion Cable FC1A-KE1PFA-1A*
1.57" (40mm) (attached to expansion unit)*21: 19.7" (0.5m), 22: 29.53" (0.75m), 23: 39.37" (1m)
Connect expansionunit to base unit
Micro Expansion Unit
FC1A-M1XEFC1A-M2XEFC1A-MXAEFC1A-M1BEFC1A-M2CE
4-point source input4-point sink input3-point relay output2-point source input, 2-point sink output2-point sink input, 2-point source output
Micro Expansion Cable FC1A-KM* *1: 19.7" (0.5m), 2: 39.37" (1m)
Serial I/O Module FC1A-SM1E 8 inputs and 8 outputs with serial cable (order FC1A-KS*A separately)
Serial Cable FC1A-KS*A *1: 39.37" (1m), 2: 78.74" (2m), 3: 118.11" (3m) Connect serial I/O module to CPU base unit (with shield terminal—one end)
Serial I/O Transition 20-pin interface to discrete terminal blocks (simplify installation of serial I/O)
Analog Timer UnitExternal Power SupplyDigital Display Mother Board
FC1A-TA1PSR-AD07*EFC1A-PD1
Contains 4 analog timers (8 time ranges from 1 second to 10 minutes)*12: 12V DC, 0.63A output, 24: 24V DC, 0.32A outputTo mount a serial I/O module and digital displays such as IDEC’s DD33 series
Link Adaptor CableFC Link CableComputer Link Cable
PF2-CLAFC1A-KC1APFA-1A54A
Interface PC to Micro-1 CPU base unit for 1:1 communication5.91" (150mm) curl cord: CPU base unit to PFJ-U11, PFJ-U21, or PF2-CLA78.74" (2m), connects PC to PFJ-U12, PFJ-U22, or PF2-CLA
Software WINDLDR Windows-based programming software
Micro-1 Starter Kit MM-MICRO-1 Micro-1 PLC, WindLDR™ software, computer link cable
Programmable Logic Controllers FA2J Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-101
J
Key features of the FA2J flat-pack modular include:• 6ms/K processing• Up to 128 inputs, 128 outputs• DC inputs, relay or transistor outputs• Low profile for shallow panels• 8-bit or 12-bit analog input, multiplexer• Replaceable relays• Memory: 1K, 4K• High-speed counter• Computer link, networking
Flat-Pak ModularSp
ecifi
catio
ns
Programming Boolean or ladder logic
Available Instructions 15 basic, 57 advanced instructions [FA1J: 27 advanced instructions]
Capacity 964 steps (1K memory) 3,300 steps (4K memory)
Memory 1K, 4K CMOS-RAM (with battery) 4K EEPROM
Processing 6ms per 1K (basic instructions) [FA1J: 32ms per 1K]
Input 128 points (maximum)
Output 128 points (maximum)
Total I/O 256 points (maximum)
Internal Relay 608 points (240 can be maintained) [FA1J: 240 points; all can be maintained]
Special I/R 16 points
Shift Register 128 points (all can be maintained)
Single Shot Output 96 points
10ms Timer 80 points, subtracting, 0 to 999.9s 80 points [FA1J: not available]
Counter 45 points, adding, 0 to 9,999 (all can be maintained)
Reversible Counter 2 points (all can be maintained)
Data Register 400 points (all can be maintained) [FA1J: 100 points; all can be maintained]
Computer Interface RS-232 link adaptor
External Control Start: input 0; Stop and reset: function settings
Power Failure Protection Internal relay, shift register, counter, reversible counter, data register
Diagnostics CPU error (WDT), communication error, CRC error in user programs, operation code error
Auto Start After power-up, automatic run state using function setting
Rated Voltage 100 to 240V AC 50/60Hz; Allowable: 85 to 110% of rated voltage;24V DC ±20% (ripple 10% maximum)
Dielectric Strength Between power or I/O terminal and ground: 1,500V AC, 1 minute (500V AC for analog lines)
Insulation Resistance Between power or I/O terminal and ground: 10MΩ (500V DC megger)
Temperature Operating: 0 to +55°C; Storage: – 20 to +70°C
Operating Humidity 45 to 85% RH (avoid condensation)
Vibration Resistance 2G, 1 hour in each of 3 axes
Shock Resistance 10G
Noise Resistance Between power or I/O terminal and ground: ±1.3kV p-p, 1µs (1kV DC pulse generator)
Ground Resistance 100Ω (maximum)
Mounting Style Panel mount
UL ListedFile No. E102542
CSA CertifiedFile No. LR66809
Programmable Logic Controllers FA2J Series
J-102 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Part Numbers: FA2J
Item Part Number Description
CPUAC PF2J-CPU1E
PFJ-CR1EFA2J CPU; power: 100 to 240V ACFA1J CPU; power: 100 to 240V AC
DC PF2J-CPU1DCEPFJ-CR1DCE
FA2J CPU; power: 24V DCFA1J CPU; power: 24V DC
PowerACDC
PFJ-PS1PFJ-PS1DC
Internal power supply for I/O expansion (100 to 240V AC)Internal power supply for I/O expansion (24V DC)
External PFJ-PU2 External power supply for DC inputs, sensors (24V DC/0.5A)
Expansion
Base Plate PFJ-EB1 For installing two I/O modules
Double-Stack Expan-sion
PFJ-DP1 Mount CPU or expansion power, plus “piggyback” mountingcapacity for two I/O modules (order one PFJ-EB1 separately)
PFJ-DP2 Mount two I/O modules, plus “piggyback” mounting capacityfor two more I/O modules (order two PFJ-EB1s parts separately)
Input
8-Point DCTransistor (source) PFJ-N081 24V DC NPN transistor inputsTransistor (sink) PFJ-N082 24V DC PNP transistor inputs
8-Point AC100V AC PFJ-N083
PFJ-N083A100 to 120V AC inputs, standard response100 to 120V AC inputs, fast response
200V AC PFJ-N084PFJ-N084A
200 to 240V AC inputs, standard response200 to 240V AC inputs, fast response
16-Point DCTransistor (source) PFJ-N161
PFJ-N161A24V DC NPN transistor inputs5V DC NPN transistor inputs
Transistor (sink) PFJ-N162 24V DC PNP transistor inputs
AnalogInput
8-BitVoltage PFJ-N012
PFJ-N012A0 to 10V DC inputs, 8-bit resolution, fast response0 to 10V DC inputs, 8-bit resolution, standard response
Current PFJ-N013PFJ-N013A
4 to 20mA DC inputs, 8-bit resolution, fast response4 to 20mA DC inputs, 8-bit resolution, standard response
12-BitVoltage PFJ-N112A
PFJ-N113A0 to 10V DC analog input, 1 point, 12-bit resolution1 to 5V DC analog input, 1 point, 12-bit resolution
Current PFJ-N114A 4 to 20mA DC analog input, 1 point, 12-bit resolution
Multiplexer 12-BitAnalog Input
VoltageCurrent
PFJ-4MPVPFJ-4MPI
Analog multiplexer module, 4 points, voltageAnalog multiplexer module, 4 points, current
Output
8-PointRelay PFJ-T081 1NO contact, rated load 110V AC, 5A; 220V AC, 2ATransistor (sink) PFJ-T082 Rated load 12 to 48V DC, 1A per pointSSR PFJ-T083 Rated load 100 to 240V AC 1A per point
16-PointTransistor
Transistor (sink) PFJ-T162PFJ-T162A
Rated load 12 to 28V DC, 0.5A per pointRated load 5 to 12V DC, 20mA per point
Transistor (source) PFJ-T162BPFJ-T162C
Rated load 12 to 28V DC, 50mA per pointRated load 12 to 28V DC, 0.5A per point
Analog VoltageCurrent
PFJ-T012PFJ-T013
0 to 10V DC output, 8-bit resolution4 to 20mA DC output, 8-bit resolution
Program Loader LoaderExtension Cable
PF2-2H4REPFA-1A11
Program loader with built-in PROM burner 59" (1.5m) —not included with program loader
Memory Packs(see details on page J-103)
PFA-1M14PFA-1M21PFA-1M24
4K EEPROM (compatible with FA3S)1K CMOS-RAM (compatible with FA3S)4K CMOS-RAM (compatible with FA3S)
High Performance Input High-Speed Counter PFA-N011APFA-N011B
Single-phase, for high-frequency inputsTwo-phase, for quadrature rotary encoder inputs
Blank Module PFJ-DM Occupies unused slot on base plate
Computer Interface
PF2-CLAPFJ-U21PFJ-U22PFA-1A51PFA-1A54ACLIP
Link adaptor for 1:1 communications to IBM-compatible PCLink for 1:N communication (use with twisted-pair cable)Main unit for 1:N communication (use with twisted-pair cable)Link cable, FA series CPU to link adapter 12” (300mm)Link cable, PC to link adapter, 78.74” (2m)Ladder diagram software for programming and monitoring
Programmable Logic Controllers FA3S Series
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-103
J
Standard CPUS High-Performance CPU
Gen
eral
Spe
cific
atio
ns
Available Instructions 15 basic, 57 advancedCP11T: plus 6 clock and protect instructions
15 basic122 advanced
Program CapacityCP11: 964 steps (1K memory)3,300 steps (4K memory)CP11T: 3,300 steps (built-in EEPROM)
964 steps (1K memory)4,036 steps (4K memory)CP13: 8,072 steps (8K memory)
MemoryCP11: 1K and 4K CMOS-RAM (with battery);4K EEPROM; 4K EPROMCP11T: Built-in 4K EEPROM memory
1K and 4K CMOS-RAM (with battery);4K EEPROMCP13: 8K CMOS-RAM or EEPROM
Average Scan Time 6µs per basic instruction 0.3µs per basic instruction
Input 128 points (maximum) I/O configurable
Output 128 points (maximum) I/O configurable
Total I/O Points 256 points 256 points
Internal Relay 608 points (240 points can be maintained) 1,024 points (240 points can be maintained)
Special Internal Relay CP11: 16 points; CP11T: 18 points 32 points
Shift Register 128 points 224 points
Single Shot Output 96 points 256 points
Timer 80 points, subtracting (0–999.9s) 256 points
10ms Timer 80 points 80 points
Counter 45 points, adding (0–9,999)(all points can be maintained)
100 points, adding (0–9,999) (all points can be maintained)
Reversible Counter 2 points (all points can be maintained) 2 points (all points can be maintained)
Data Register 400 points (all points can be maintained) 1,000 points (all points can be maintained)
Forced I/O Not available Available (50 points simultaneously)
Remote I/O Not available 1,024 points (plus 256 points basic capacity)
Runtime Program Modify Not available Available
Real-Time Clock/Calendar Runtime Available on CP11T only Not available
Program Protection Available on CP11T only Available
High-Performance Modules High-speed counter (PF3S-HSC2) High-speed counters (PF3S-HSC1 and -HSC2),high-speed interrupt I/O, remote I/O, RS232, RS485
External Control Start: input 0 (release possible); Stop/reset: function designated
Power Failure Protected: Internal relay, shift register, counter, reversible counter, data register
Self-Diagnostics CPU error (WDT), communication error, CRC error in user programs, operation code error
Auto Start Function After power-up, automatic run, function designated
Key features of the FA3S include:• Up to 256 local I/O points• Up to 1,024 fiber optic remote I/O points,
from up to 3,280’ (1km) away• 8-channel analog module• RS232 and RS485 modules available• Modem communications• Real-time clock and calendar available• High-speed interrupt I/O (16 or 32 points)• Average Boolean scan: 0.3ms/K• Up to 8K program steps• Built-in programming/ASCII port
UL ListedFile No. E102542
CSA CertifiedFile No. LR66809
CE CertifiedEMC Approved*File No. E9960513332*Some modules excepted
The FA2 loader (PF2-2H4RE) and FA3 loader (PF3S-HL161E) are compatible with all FA series PLCs and the Micro-1.
FA3S: The Powerhouse
Programmable Logic Controllers FA3S Series
J-104 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
JThe power requirements listed are maximums. For input modules, all inputs are on. For output modules, all outputs are on. For combination I/O modules, all inputs and outputs are on.
Pow
er R
equi
rem
ents
Standard CPU PF3S-CP11with program loader
130mA 480mA
Standard CPU withClock Protection
PF3S-CP11Twith program loader
80mA 430mA
High-Performance CPUs PF3S-CP12, -CP13with program loader
120mA 470mA
In: 16-Point Transistor PF3S-N16B 80mAIn: 32-Point Transistor PF3S-N32B, -N325B 160mAIn: 16-Point AC PF3S-N16A1, -N16A2 90mAIn: 8 Channel Analog Input PF3S-AD8B1, -AD8B2 150mAIn: Analog PF3S-AD121, -AD122 40mAMultiplexer PF3S-MP41 60mACombination I/O PF3S-M32K, -M325K 190mAOut: 8-Point Relay PF3S-R081 170mAOut: 16-Point Relay PF3S-R161 330mAOut: 16-Point SSR PF3S-S161 280mAOut: 16-Point Transistor PF3S-T16K, -T16S 130mAOut: 32-Point Transistor PF3S-T32K, -T325K, -T32S 240mAOut: Analog PF3S-DA121 40mAHigh-Speed Counter PF3S-HSC1, -HSC2 30mAHigh-Speed I/O PF3S-HSL1 200mA
Serial Interface PF3S-SIF2PF3S-SIF4
60mA110mA
Remote I/O Master PF3S-RMP1, -RMQ1 180mARemote I/O Slave PF3S-RTP1, -RTQ1 250mAAC Power Supply (standard) PF3S-PSA1 50VAAC Power Supply (large capacity) PF3S-PSA2 85VADC Power Supply PF3S-PSD1 32WExternal Power Supply PF3S-EPA1 85VABackplane 2 slot PF3S-BP12Backplane 3 slot PF3S-BP13
Part Numbers: FA3S Series
Programmable Logic Controllers Programming Software
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC J-105
J
WindLDR™ Programming Software
Where Logic and Intuition ConvergeWindLDR, IDEC’s Windows-based, Ladder programming tool successfully com-bines logic and intuition. IDEC’s WindLDR includes a graphic interface, icon-driven tool bar, on-line help, and debugging tools. In its first release, WindLDRprograms the Micro-1, Micro3, Micro3C, FA Series, ONC and MicroSmart.
WindLDR is your icon-driven, multi-window, all-inclusive tool.
Key features of the WindLDR software package include:• Use the Tag Editor to access and edit all coil data in one
convenient option• Customize toolbars, ladder file characteristics, and more• Access the most common commands with the context-sensitive
right mouse button• Open and use unlimited ladder files• Monitor and de-bug PLC functionality on-line• Edit ladders simply, with a drag and drop toolbar
Tag Name Editor
Tag Name Editor
Gen
eral
Spe
cific
atio
ns
Cut and Paste Function Select one rung or multiple rungs
Tag Editor Access and edit all coil data in one convenient option
Customization For toolbars, ladder file characteristics, and many program features
Right Mouse Button Context-sensitive for convenient access to most commonly used commands
On-Line MonitoringDe-bug and observe real-time PLC functionality,right from your PC.Write new values to counters, timers, and data registers.
Multiple Ladder Files Open unlimited ladder files to compare and reuse instantly, even if they are written for different PLCs
Drag and Drop User friendly toolbar makes ladder creation andediting simple
Find String Searches for text in various ways; large ladder filesare easy to manage
Multi-Level Undo Limited only by available memory
CLIP and CUBIQ Fully compatible for upgrade
On-Line Help Context-sensitive; extensive coverage of WindLDRand PLC functionality
ManualsThe WindLDR Tutorial provides a quick, simple way to get up and running; the comprehensive WindLDR Reference Manual answers basic through advanced questions
Support IDEC engineers maintain an excellent level of customerservice and software support
Platforms Microsoft® Windows 95, 98, 2000, Me, NT 4.0
System RequirementsCPU: Pentium 75MHz or higher; 24MB available RAM on Win95 and Win98; 32MB available RAM on Win2000, NT20MB free hard disk space
Installation Software CD-ROM
Programmable Logic Controllers Programming Software
J-106 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
J
Programming Instruction Set
Instruction Set Mic
ro-3
Mic
ro-3
C
ON
C
Mic
roSm
art
Basic Instruction ListAND And • • • •ANDLOD And load • • • •ANDN And Not • • • •BPP Bit Pop • • • •BPS Bit Push • • • •BRD Bit Read • • • •CC= Counter Comparison (=) • • • •CC≥ Counter Comparison (≥) • • • •CDP Dual Pulse Reversible Counter • • • •CNT Counter • • • •DC= Data Register Comparison (=) • •DC≥ Data Register Comparison (≥) • •END End • • • •JEND Jump End • • • •JMP Jump • • • •LOD Load • • • •LODN Load Not • • • •MCR Master Control Reset • • • •MCS Master Control Set • • • •OR Or • • • •OR LOD Or Load • • • •ORN Or Not • • • •OUT Output • • • •OUTN Output Not • • • •RST Reset • • • •SET Set • • • •SFR Shift Register • • • •SFRN Shift Register Not • • • •SOTD Single Output Down • • • •SOTU Single Output Up • • • •TIM Timer • • • •Advanced Instruction ListGroup Symbol • •NOP NOP • • • •
Move
MOV • • • •MOVN • • • •IMOV • • • •IMOVN • • • •BMOV • •IBMV • •IBMVN • •
Data Comparison
CMP= • • • •CMP<> • • • •CMP< • • • •CMP> • • • •CMP<= • • • •CMP>= • • • •ICMP>= • •
Binary Arithmetic
ADD • • • •SUB • • • •MUL • • • •DIV • • • •ROOT • •
BooleanComputation
ANDW • • • •ORW • • • •XORW • • • •
Shift and Rotate
SFTL • • • •SFTR • • • •BCDLS • •WSFT •ROTL • • • •ROTR • • • •
Instruction Set Mic
ro-3
Mic
ro-3
C
ON
C
Mic
roSm
art
Advanced Instruction List, continuedHTOB Hex to BCD • •BTOH BCD to Hex • •HTOA Hex to ASCII • •ATOH ASCII to Hex • •BTOA BCD to ASCII • •ATOB ASCII to BCD • •ENCO Encode •DECO Decode •BCNT Bit Count •ALT Alternate Output •WKTIM Week TImer •WKTBL Week Table • •DISP Display • • • •DGRD Digital Read • • • •TXD Transmit • • •RXD Receive • • •LABEL Label • •LJMP Label Jump • •LCAL Label Call • •LRET Label Return • •IOREF I/O Refresh •DI Disable Interrupt •EI Enable Interrupt •XYFS XY Format Set • •CVXTY Convert X to Y • •CVYTX Convert Y to X • •PULS Pulse Output • •PWM Pulse Width Modulation • •RAMP Ramp Pulse Output •ZRN1 Zero Return 1 •ZRN2 Zero Return 2 •PID PID Control • •DTML 1-sec Dual Timer • •DTIM 100-msec Dual Timer • •DTMH 10-msec Dual Timer • •DTMS 1-msec Dual Timer • •TTIM Timer • •