catalogue jiangsu sieyuan hertz[1]

Upload: daminhvien

Post on 02-Jun-2018

251 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    1/24

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    Address: No. 5, West Huimin Road, Economic Development Zone, Rugao, Jia ngsu Province, P.R.China.

    Zip code: 226572

    Tel: 0086-513-87303629

    Fax: 0086-513-87530056

    Email: [email protected]

    Http://www.sieyuan.net !"#$%&'()*JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO.,LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    !

    SieyuanSieyuanSieyuanSieyuanSieyuan

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    2/24

    Jiangsu Sieyuan Hertz Instrument Transformer Co., Ltd. conducts research and development on

    technically advanced and safe quality products on its own, including:

    35-500 kV Oil Impregnated Inverted Current Transformers,

    35-500 kV Sulfur Hexafluoride Gas Insulated Inverted Current Transformers,35-500 kV Capacitor Voltage Transformers,

    35-500 kV Sulfur Hexafluoride Gas Insulated Voltage Transformers for mounting in GIS,

    35-220 kV Inductive Voltage Transformers,

    10-220 kV Oil Impregnated Tank type Current Transformers,

    35-110 kV Dry type Current Transformers and Dry Graded Wall Bushing, etc.

    The products have obtained KEMA test certification in Holland, as well as inspection and examination

    by national authorities.

    Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained speed, with ardent

    enthusiasm, prudent attitude

    and customer orientation.

    Jiangsu Sieyuan Hertz Instrument Transformer Co., Ltd. ( www.sieyuan.net ) covers the land

    area of more than 100,000 square meters and the construction area of over 60,000 squaremeters, which is within the factory area of more than 50,000 square meters. With a sealing &

    purifying workshop up to 100,000 grade, it is regarded as a world-class instrument transformer

    production base in China.

    Sieyuan Hertz has a R&D and management team with the most competitive power, it now has

    more than 400 employees, among the employees, the percent of engineering and technology

    talents who got Ph. D or master degree or graduated from universities is 45%, and the

    Company also invites foreign professionals to take charge of the technology and quality

    management.

    Sieyuan Hertz leads the instrument transformer trade to a

    higher level at a sustained speed, with ardent enthusiasm,

    prudent attitude and customer orientation.

    Company Brief

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    Comp any Brief

    1 2

    SieyuanSieyuanSieyuanSieyuanSieyuan

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    3/24

    Advanced Facilities

    In order to realize the product design con-

    cept and reduce the uncertainty brought bymanual operation, during the production

    process, Siyuan Hertz adopts automatic pro-

    duction equipments.

    World Class Testing Condition

    Secondary Coil Winding Machine Capacitance Graded Bushings Wind-

    ing Machines

    German Welding Robots

    Sieyuan Hertz has the world-classy testing conditions and perfect testing equipments, including three

    six-facet shielding high voltage testing laboratory with the rated voltage 1000 kilovolt, 600 kilovolt, 300kilovolt and also an impulse voltage generator up to 3000 kilovolt with automatic measuring system.

    In the profession field, the company introduces firstly the partial discharge test in power frequency

    withstand voltage, which is more stringent than national and IEC standards, and ensures much more

    reliance and safety for product running.

    Transient Characteristics Tester for

    Current Transformer

    600kV Power Frequency Testing Trans-

    former

    300kV Power Frequency Testing Trans-

    former

    1000kV Power Frequency Testing

    Transformer

    3000kV Lightning Impulse Generator

    High Frequency Capacitance and Stray

    Capacitance Meter

    Ferro-resonance Testing Analysis Sys-

    tem for Capacitor Voltage Transformer

    (CVT)

    3 4

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    G e r ma n L e y b o l d

    Vacuum Treatment

    System

    Capacitance Graded Bushings Winding

    Machine for SF6Gas Insulated Products

    Assembly Shop for SF6Gas Insulated

    Current Transformer

    German B&R Aptitude Coil Machine

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    4/24

    Sieyuan Hertz promotes total quality management and strictly abiding by

    ISO9000 quality management system, the regulation of technical re-

    quirement is quite clear and uniform from parts inspection to routine test,

    so as to ensure the whole production under control and the products can

    be traced back. To ensure the product quality meeting international

    standards, all major raw materials are imported from foreign countries,

    such as: cable paper, semiconducting paper, aluminum foil, transformer

    oil, insulating material for sulfur hexafluoride gas insulated products,enameled wire and compacting material for product etc.

    Sieyuan Hertz consistently follows the mission of "service creates value" by professional, speedy,

    sincere and quality service. We endeavor to help lower our customer' operation costs while improvingtheir business efficiency and competitiveness.

    Sieyuan Hertz is committed to offer our customers with products featuring "high-safety", "high-

    reliance", "high-accuracy" and "high-standardization". Since our foundation, the company has gained

    earnest support from users in all lines. At present, our sales network covers all the cities in China and

    overseas markets. In north, east, south, and mid China, northwest and northeast China, sales offices

    and after-sale service stations have been established. In addition, the company has established

    perfect partnership with State Grid Corporation of China, and China Southern Power Grid Co., Ltd.,

    Sieyuan Hertz has continuously won bids in major power station projects in Vietnam, Burma and

    Nigeria, which marks that our products have known worldwide.

    Reliable Products & Quality

    ISO9000 Quality System Certificate (SGS)

    General Customer Service

    Hebei Electric Power

    Corporation, China

    Jiangsu Electric Power Corporation, China

    500kV SF6Gas Insulated Inverted Cur-

    rent Transformers

    Zhejiang Electric Power Corporation,

    China 500kV Oil Impregnated Inverted

    Current Transformers

    Shanxi Electric Powr

    Corporation, China

    Jiangsu Electric Power

    Corporation, China

    Jilin Electric Power

    Corporation, China

    Ningxia Electric Power

    Corporation, China

    Nanjing Electric

    Power

    Corporation,

    China

    Shanxi Electric Power

    Corporation, China

    Guangdong ElectricPower Corporation,

    China

    5 6

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    5/24

    Symbol Explanation

    LVB Series Oil Immersed Inverted Current Transformers

    L V B (T)

    Antipollution Class (W2, W3)

    Voltage Grade (kV)

    With Transient Protection

    With Protection

    Inverted

    Current Transformer

    LVB (T) series current transformer has an inverted structure with oil-immersed paper insulation (Please see the left figure).

    It is connected in series with electric energy measurement, measuring, relay protection and transient protection functions.

    Primary coil has a through-type conducting rod structure with good dynamic and thermal stability; its maximum thermal

    current can be up to 63kA/3s (when primary coil is connected in series).

    Primary coil passes through the center of secondary coil without flux leakage. Measurement precision can be up to 0.1and

    0.2S grades.

    Secondary coil is fixed in an aluminum shielded-case by casting organic materials; secondary measurement and

    protection circuits cannot be damaged by insulation breakdown.

    Optimal capacitor screen bushing is made of a complete piece of imported broadsheet cable paper; it is coiled by an

    automatic wrapping machine which is controlled by a computer with high performance. It has a technological de-centrality

    and an excellent insulation property. Partial discharge test is carried out under power frequency test voltage.

    Use the automatic vacuum drying treatment system produced by LEYBOLD in Germany, carry out pressure-changing

    vacuum drying treatment and oiling after a product is assembled completely, and all insulation materials are imported from

    foreign countries. All these ensure that the dielectric dissipation factor of complete product tan_ is less than 0.3%.

    External insulation uses a porcelain cover with high strength, optimal surface field intensity together with lower field

    intensity of internal bushing make the porcelain cover avoid explosion.Secondary outlet box is a complete structure by casting the aluminum alloy; its sealing structure meets the requirement

    of IP55, which is dust proof, water proof and air permeable; secondary terminal for wiring uses Phoenix special terminal; it

    is more convenient for operations such as plug-in, pull-out and wiring etc.

    Connection between components uses argon-arc welding, fill in high pressure nitrogen to detect leakage after assembly

    is complete, so oil penetration and oil leakage caused by oil-immersed products are resolved at root.

    Use an aluminum alloy cast case, all components including the base, connection box, stainless steel expander, and

    nameplate etc do not rust forever.

    It is light and handy with a small volume and light weight.

    This product is free-maintenance.

    Introduction to Structure

    Stainless Steel Expander

    Primary Terminal Plate on P1 Side

    Bushing

    Core and winding assembly

    Porcelain Cover

    Oil Drain ValueNameplate

    Secondary Terminal Box

    Oil Level Observation Window

    Primary Terminal Plate on P2 Side

    7 8

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    6/24

    Technical Parameters of LVB (T) - 35

    LVB-35W2/1X LVB-35W3/1X LVB(T)-35W2/2X LVB(T)-35W3/2X

    Technical Parameters of LVB 66

    LVB-66W2/1X LVB-66W3/1X LVB-66W2/2X LVB-66W3/2X

    TypeLVB-66W2/1X LVB-66W3/2X

    LVB-66W3/1X LVB-66W3/2X

    Highest voltage for equipment kV 72.5

    Rated frequency Hz 50/60

    Rated power-frquency withstand voltage (rms) kV 160

    Rated lightning impulse withstand voltage (full wave)(peak) kV 350

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 403

    Flashover distance mm 700

    Creepage distance mm 1812/2250

    Rated primary current (Maximum) A 4000

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S;0.5S;5P;10P;TPU;TPS

    Rated output VA 10-50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (Maximum) kA 63kA/3s (In series)

    Dynamic current (Maximum) kA 160

    Allowable mechanical load of transformer: Static N 3000

    Allowable mechanical load of transformer: Dynamic N 5000

    Net weight kg 200 450

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    TypeLVB-35W2/1X LVB(T)-35W2/2X

    LVB-35W3/1X LVB(T)-35W3/2X

    Highest voltage for equipment kV 40.5

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 95

    Rated lightning impulse withstand voltage(full wave)(peak)kV 200

    Rated lightning impulse withstand voltage (Chopped wave) (Peak) kV 230

    Flashover distance mm 500

    Creepage distance mm 1015/1260

    Rated primary current (Maximum) A 4000(8000)

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.1;0.2;0.5;0.2S;0.5S;5P;10P;TPY;TPS

    Rated output VA 10-50

    Safety factor FS 5;10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (Maximum) kA 63kA/3s (In series)

    Dynamic current (Maximum) kA 160

    Allowable mechanical load of transformer (Static) N 3000

    Allowable mechanical load of transformer (Dynamic) N 5000

    Net weight kg 170 420

    Outline and Dimensional Drawing Outline and Dimensional Drawing

    9 10

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    7/24

    LVB-110(132)W2/1X

    LVB-110(132)W3/1X

    LVB-110(132)W2/2X

    LVB-110(132)W3/2X

    LVB-110(132)W2/3X

    LVB-110(132)W3/3X

    11 12

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Outline and Dimensional Drawing

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Technical Parameters of LVB-110

    TypeL VB- 110W2 /1X L VB- 11 0W2/ 2X LVB- 11 0W2/ 3X

    L VB- 110W3 /1X L VB- 11 0W3/ 2X LVB- 11 0W3/ 3X

    Highest voltage for equipment kV 126

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 230Rated lightning impulse withstand voltage (full wave)(peak) kV 550

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

    Flashover distance mm 1200

    Creepage distance mm 3150/3910

    Rated primary current (Maximum) A 4000

    Rated secondary current A 1;5

    Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (Maximum) kA 50kA/3s (In series)

    Dynamic current (Maximum) kA 125

    Allowable mechanical load of transformer (Static) N 3000

    Allowable mechanical load of transformer (Dynamic) N 5000

    Net weight kg 230 475 525

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Technical Parameters of LVB-132

    TypeL VB- 132W2 /1X L VB- 13 2W2/ 2X LVB- 13 2W2/ 3X

    L VB- 132W3 /1X L VB- 13 2W3/ 2X LVB- 13 2W3/ 3X

    Highest voltage for equipment kV 145

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 275

    Rated lightning impulse withstand voltage (full wave)(peak) kV 650

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 748

    Flashover distance mm 1200

    Creepage distance mm 3625/4495

    Rated primary current (Maximum) A 4000

    Rated secondary current A 1;5

    Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (Maximum) kA 50kA/3s (In series)

    Dynamic current (Maximum) kA 125

    Allowable mechanical load of transformer (Static) N 3000

    Allowable mechanical load of transformer (Dynamic) N 5000

    Net weight kg 230 475 525

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    8/24

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Technical Parameters of LVB (T)-330500

    Outline and dimensional drawings for

    LVB(T)-330W2 Current Transformer

    Outline and dimensional drawings for

    LVB(T)-500W2 Current Transformer

    Outline and Dimensional Drawing

    Type LVB (T) -330W2 LVB (T) -500W2

    Highest voltage for equipment kV 363 550

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 510 740

    Rated lightning impulse withstand voltage (full wave)(peak) kV 1175 1675

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1352 1930

    Impulse withstand voltage (Wet Test) kV 950 1175

    Flashover distance mm 2650 4000

    Creepage distance mm 9100 13750

    Rated primary current (Maximum) A 5000 5000

    Rated secondary current A 5; 1 5; 1

    Accuracy classes (they can be combined if necessary) 0.2S; 0.5S; 0.1; 0.2S; 0.5S; 0.1;

    0. 2; 0. 5; 5P ; 10P ; T PY 0 .2; 0. 5; 5P ; 10P ; T PY

    Rated output VA 10~50 10~50

    Safety factor FS 5; 10 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30; 40 10; 15; 20; 30; 40

    Times of symmetry short-circuit current Kssc 10, 15, 20, 25, 30

    TPY Parameter Operating cycle C-O-C-O

    Output capacity VA 10, 15

    Thermal current (Maximum) kA 63 kA / 3s ( in series )

    Dynamic current (Maximum) kA 160 ( in series )

    Weight of oil 280 432

    Net weight 1000 2250

    Gross weight 1300 3000

    13 14

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    LVB-220W2/1X LVB-220W3/1X LVB-220W2/2X LVB-220W3/2X

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Technical Parameters of LVB (T)-220

    TypeLVB-220W2/2X LVB (T)-220W2/3X

    LVB-220W3/2X LVB (T)-220W3/3X

    Highest voltage for equipment kV 252

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 460

    Rated lightning impulse withstand voltage (full wave)(peak) kV 1050

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208

    Flashover distance mm 2200

    Creepage distance mm 6300/7900

    Rated primary current (Maximum) A 4000

    Rated secondary current A 15

    Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (Maximum) kA 63kA/3s (In series)

    Dynamic current (Maximum) kA 160

    Allowable mechanical load of transformer: Static N 4000

    Allowable mechanical load of transformer: Dynamic N 6000

    Net weight kg 550 800

    Outline and Dimensional Drawing

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    9/24

    LVQB series current transformer has an inverted structure with SF6 gas insulation (Please see the figure). It is connectedin series with electric energy measurement, measuring, and relay protection functions.

    Primary coil has a through-type conducting rod structure with good dynamic and thermal stability; its maximum thermal

    current can be up to 63kA/3s (when primary coil is connected in series).

    Primary coil passes through the center of secondary coil without flux leakage. Measurement precision can be up to 0.1

    and 0.2S grades.

    Secondary coil is fixed in an aluminum shielded-case by casting organic materials; measurement and protection circuits

    cannot be damaged by insulation breakdown.

    Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an excellent

    insulation property. Partial discharge test is carried out under power frequency test voltage.

    There are two types of external insulation bushing for customers: they have excellent explosion-resistant and shock-

    resistant behaviors.

    External bushing uses silicon rubber umbrella type apron reinforced by glass fiber. Optimal external surface field makes

    silicon rubber avoid electrical erosion.

    Porcelain bushing shell with high-strength.

    Secondary outlet box is a complete structure by casting the aluminum alloy; its sealing structure meets the requirement

    of IP55, which is dust proof, water proof and air permeable; secondary terminal for wiring uses Phoenix special terminal; itis more convenient for operations such as plug-in, pull-out and wiring etc.

    Seal ring is made of imported fluorocarbon silicone rubber, it is suitable for using in the area where there is great

    temperature change or the environmental temperature is extreme. The leakage rate per year is less than 0.5%.

    Product performance keeps changeless after severe transporting test.

    Use an aluminum alloy cast case, all components including the base, connection box, stainless steel expander, and

    nameplate etc do not rust forever.

    A density meter is installed on the base, this meter can show the gas pressure and density in the transformer (The show

    value is turned to be the internal gas pressure at 20automatically). A signal for refilling gas is sent out when the pressure

    in the transformer drops down to the alarm pressure.

    Introduction to Structure

    Shell

    Silicon Rubber Bushing

    Secondary Lead Pipe

    Outlet BoxBase

    Nameplate

    Electrode

    Conducting Block

    Main Body

    Rupture Disc

    15 16

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    LVQB Series SF6Gas-insulated Inverted Current Transformer

    Antipollution Class (W2, W3)

    Voltage Grade (kV)

    With Transient protection

    With Protection

    SF6Gas-insulation

    Inverted

    Current Transformer

    L V Q B (T)

    Symbol Explanation

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    10/24

    17 18

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Fig. 2

    Technical Parameters of LVQB-110

    LVQB-110W2/1X LVQB-110W3/1X LVQB-110W2/2X LVQB-110W3/2X

    Outline and Dimensional Drawing

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    TypeLVQB-110W2/1X LVQB-110W2/2X

    LVQB-110W3/1X LVQB-110W3/2X

    Highest Voltage for Equipment kV 126

    Rated Frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 230

    Rated lightning impulse withstand voltage (full wave)(peak) kV 550

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

    Flashover Distance mm 1100

    Creepage Distance mm 3150, 3950

    Rated Primary Current In (Maximum) A 2400 (1:2; 1:2:4 available)

    Rated Secondary Current A 1; 5

    Accuracy Classes (They can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated Output VA 10~50

    Safety Factor FS 5; 10

    Accuracy limit Factor ALF 10; 15; 20; 30

    Thermal Current (Maximum) kA 50kA/3s

    Dynamic Current (Maximum) kA 125

    Air Pressure (Absolute value) MPa 0.5

    Outline and Installation Dimensions Fig.2

    Net Weight kg 490 565

    Gross Weight kg 590 670

    Technical Parameters of LVQB-66

    Fig.1 LVQB-66W2

    Type LVQB-66W2 LVQB-66W3

    Highest voltage for Equipment kV 72.5

    Rated Frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 160

    Rated lightning impulse withstand voltage (full wave)(peak) kV 350

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 403

    Flashover Distance mm 650

    Creepage Distance mm 1812, 2250

    Rated Primary Current In (Maximum) A 4000

    Rated Secondary Current A 1; 5

    Accuracy Classes (They can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated Output VA 10~50

    Safety Factor FS 5; 10

    Accuracy Limit Factor ALF 10; 15; 20; 30

    Thermal Current (Maximum) kA 50kA/3s (In series)

    Dynamic Current (Maximum) kA 125

    Air Pressure (Absolute Value) MPa 0.5

    Outline and Installation Dimensions Fig.1

    Net Weight kg 400

    Gross Weight kg 490

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Outline and Dimensional Drawing

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    11/24

    19 20

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Outline and dimensional drawings for

    LVQB(T)-330W3 Current Transformer

    Outline and dimensional drawings for

    LVQB(T)-500W3 Current Transformer

    Technical Parameters of LVB (T)-330500

    Outline and Dimensional Drawing

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Type LVQB(T)-330W3 LVQB(T) -500W3

    Highest voltage for equipment kV 363 550

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 510/567 740

    Rated lightning impulse withstand voltage (full wave)(peak) kV 1175/1305 1675

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1352/1501 1930

    Impulse withstand voltage (Wet Test) kV 950/1156 1175

    Flashover distance mm 2850 4220

    Creepage distance mm 9080 17050

    Rated primary current (Maximum) A 5000(2 2500) 5000(2 2500)

    Rated secondary current A 5; 1 5; 1

    Accuracy classes (they can be combined if necessary)0.2S;0.5S;0.1;0.2; 0.2S;0.5S;0.1;0.2;

    0.5;5P;10P;TPY 0.5;5P;10P;TPY

    Rated output VA 10~50 10~50

    Safety factor FS 5; 10 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30; 40 10; 15; 20; 30; 40

    Times of symmetry short-circuit current Kssc 10, 15, 20, 25, 30

    TPY Parameter Operating cycle C - O - C - O

    Output capacity VA 10, 15

    Thermal current (Maximum) kA 63 kA / 3s ( in series )

    Dynamic current (Maximum) kA 160 ( in series )

    Weight of oil 280 432

    Net weight 1800 3000

    Gross weight 2600 4000

    Fig. 3LVQB-220W2/1X LVQB-220W3/1X

    Technical Parameters of LVQB-220

    Outline and Dimensional Drawing

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    LVQB(T)-220W2/2X LVQB(T)-220W3/2X

    TypeLVQB-220W2/1X LVQB(T)-220W2/2X

    LVQB-220W3/1X LVQB(T)-220W3/2X

    Highest voltage for equipment kV 252

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 460

    Rated lightning impulse withstand voltage (full wave)(peak) kV 1050

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208

    Flashover distance mm 2250

    Creepage distance mm 6300, 7900

    Rated primary current In (Maximum) A 4000

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.1;0.2;0.5;0.2S;0.5S;5P;10P 0.1;0.2;0.5;0.2S;0.5S5P;10PTPY;TPS

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Thermal current (Maximum) kA 63kA/3s

    Dynamic current (Maximum) kA 160

    Rated gas pressure (Absolute value) MPa 0.5

    Outline and installation dimensions Fig.3

    Net weight kg 1050 1200

    Gross weight kg 1350 1500

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    12/24

    21 22

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    JDQXF Series SF6Gas-insulated Voltage Transformer

    Transformer cabinet is at the bottom of product, main body is in

    it, there is a silicon rubber composite insulation bushing or high

    strength porcelain bushing at the middle and primary terminals are

    at top both sides of product.A SF6 gas density controller is equipped on the transformer

    cabinet; it can monitor the SF6 gas pressure in-line. There is a

    pressure-relief device on the top; the rupture (relief) pressure is 0.

    7 MPa without oil or explosion risk, and it is free-maintenance.

    Main body is inside the cabinet, use the composite insulation of

    polyester film and SF6 as interlayer insulation, so it has high

    strength insulation. Coil uses single-staged tower structure, so it

    has a good shock resistant performance.

    Product shell is carried out hot galvanizing or uses cast aluminum

    alloy, all components including stainless steel fasteners and name-

    plate etc work in outdoor for long time without rust.

    Primary terminal block uses cast aluminum part, the static test

    load it can bear is no less than 3000N.

    Secondary outlet box is a complete structure by casting the

    aluminum alloy; its sealing structure meets the requirement of IP55,

    which is dust proof, water proof and air permeable; secondaryterminal for wiring uses Phoenix special terminal; it is more conve-

    Introduction to Structure

    Symbol Explanation

    Antipollution Class W2 or W3

    Rated Voltage Grade

    Measurement Coil and Pro-

    tection Coil Being Separate

    With Residual Voltage Coil

    Gas-insulation

    Single Phase

    Voltage Transformer

    nient for operations such as plug-in, pull-out and wiring etc.

    Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an excellent

    insulation property. Partial discharge test is carried out under power frequency test voltage.

    Seal ring is made of imported fluorocarbon silicone rubber, it is suitable for using in the area where there is great

    temperature change or the environmental temperature is extreme. The leakage rate per year is less than 0.5%.

    High voltage coil is made of imported polyester film and conducting wires with high insulation strength and stable

    performance; use imported automatic winding equipment to complete the wire winding and the wrapping of interlayer

    insulation automatically according to entered instructions.

    J D Q X F

    Secondary Outlet Box

    Cabinet

    Main Body

    Primary Conducting Pipe

    Bushing Electrode

    Silicon Rubber Insulated Bushing

    Primary Terminal Block

    Explosion Resistant Device

    Technical Parameters

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 We also can provide with products which meet the requirement of IEC and ANSI.

    Type JDQXF-110W2 / JDQXF-110W3

    Highest voltage for equipment kV 126

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 230

    Rated lightning impulse withstand voltage (full wave)(peak) kV 550

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

    Flashover distance mm 1160

    Creepage distance mm 3150 / 3950

    Rated gas pressure (Absolute value) MPa 0.5

    Rated voltage factor/time1.2/continual 1.5/30s

    Accuracy class and rated output

    Secondary coil 1 Secondary coil 2 Residual voltage coil

    Accuracy class 0.2 0.5or3P 3P

    Rated output VA150 300

    100 150 300

    Thermal limit output VA 2000

    Outline and installation dimensions See the figure

    Net weight kg 450

    Gross weight kg 550

    JDQXF-110W2

    It can be designed and made with three coils (one primary coil, one secondary coil and one residual voltage coil) or four

    coils (one primary coil, two secondary coils and one residual voltage coil) according to the requirement of customer.

    Integrated design is reasonable; it shows capacitive character under certain voltage.

    Outline and Dimensional Drawing

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    13/24

    Technical Parameters

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 We also can provide with products which meet the requirement of IEC and ANSI.

    Leading wire of secondary coil and leading wire of ground terminal of primary coil are connected with Phoenix special

    terminal in the secondary terminal box via the terminal block cast as a whole with epoxy on the shell. It is more convenient

    for operations such as plug-in, pull-out and wiring etc. The sealing performance meets the requirement of IP55.

    The transformer can be installed horizontally or vertically.

    Type JDQXF-110ZH

    Highest voltage for equipment kV 126/145

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 230/275

    Rated lightning impulse withst and voltage (full wave)(peak) kV 550/650

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633/748

    Rated gas pressure (Absol ute value) MPa 0.5/0.6

    Rated voltage factor/time 1.2/continual 1.5/30s

    Accuracy class and rated output

    Secondary co il 1 Secondary co il 2 Residua l vol tage co il

    Accuracy class 0.2 0.5or3P 3P

    Rated output VA150 300

    75 120 300

    Thermal limit output VA 2000

    Outline and installation dimensions See the figure

    Net weight kg 400

    Gross weight kg 500

    Outline and Dimensional Drawing

    23 24

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    GIS Gas-insulated Voltage Transformer

    Voltage transformer matched with GIS is used for SF6

    close combined apparatus; it is connected between the

    phase and ground. It uses SF6gas as main insulation, anduses polyester film, which is used for interlayer insulation,

    as additional insulation.

    Main components of transformer

    There are lifting blocks, a ground terminal, a nameplate,

    an instruction plate and a secondary terminal box on the

    metal shell. The shell body is formed by welding steel

    plates and hot galvanizing, all connecting bolts uses stain-

    less standard parts, they can work in outdoor place for long

    time, and do not rust forever. A metal rupture disc is

    installed on the base. If a high energy discharge occurs in

    it, the rupture disc will break to relief pressure, so the safety

    of product is improved.

    Main body is installed in the shell, high voltage electrode

    Introduction to Structure

    J D Q X F

    Supporting rack

    Shell

    Charging

    Connection

    Lifting Block

    Grounding Base

    Insulator

    Conduit

    Core andWindingAssembly

    and low voltage shielded plate use aluminum plates, which are rotated and pressed to form and carried out polishing

    treatment. Optimal Electrode shielded structure improves internal and external field distribution of the product. It has anexcellent insulation property. Partial discharge test is carried out under power frequency test voltage.

    High voltage coil uses single-staged tower structure, so it has a good shock resistant performance. Use imported polyester

    films and high strength enameled wires, so it has high insulation strength. Use imported automatic winding equipment to

    complete the wire winding and the wrapping of interlayer insulation automatically according to entered instructions.

    It can be designed and made with three coils (one primary coil, one secondary coil and one residual voltage coil) or four

    coils (one primary coil, two secondary coils and one residual voltage coil) according to the requirement of customer.

    Disc insulator is used as the partition between the gas chamber of transformer and that of composite apparatus.

    Transformer and composite apparatus can have SF6 gas with different pressure. The connection between high voltage

    conductor and high voltage electrode on main body uses elastic structure.

    Rated Voltage

    Measurement Coil and Protection Coil Being Separate

    With Residual Voltage Coil

    Gas-insulation

    Dfor Single Phase;Sfor Three Phases

    Voltage Transformer

    Symbol Explanation

    Secondary

    Outlet Box

    Explosion Re-

    sistant Device

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    14/24

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Fig.1 Outline and Installation Dimensions of LB6-110 type Current Transformer (Primary Coil is in series)

    Outline and Dimensional Drawing

    Main technical Parameters

    Type LB6-110(W2) LB6-110(W3) GY

    Rated primary voltage kV 110

    Highest Voltage for Equipment kV 126

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 230

    Rated lightning impulse withstand voltage (full wave)(peak) kV 550

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

    Flashover distance mm 1000

    Creepage distance mm 3150, 3906

    Rated primary current In (Maximum) A 2 50~2 1000

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated output (Maximum) VA 50 (Pigtail 30)

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (depend on the number of31.5~45kA / 1s

    turns of primary and secondary coils) kA

    Dynamic current (Maximum) kA 80~115

    Allowable mechanical load of transformer: Static 2000N

    Outline and installation dimensions Fig.1

    Net weight kg 690 730

    Gross weight kg 750 780

    25 26

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    LB6-110 type Current Transformer

    Symbol Explanation

    L B 6

    110

    Voltage Grade, kV

    Design No.

    With Protection

    Current Transformer

    Except for the above basic symbol, suffix W2means that it is

    suitable for using in Grade area, suffixW3means that it is

    suitable for using in Grade area, and suffixGYmeans that it

    is suitable for using in plateau area.

    Introduction to Structure

    LB6-110 type current transformer has an oil-immersed fully-

    sealed structure. The primary coil is U-shape, the main body is fixed

    on the bracket, the main insulation uses capacitor type oilpaper, use

    the high voltage cable paper to wrap the core of primary coil, and set

    up several capacitor shields among it, the internal shield is con-

    nected to high potential, and the external shield is connected to

    ground reliably.

    There is a porcelain bushing at the upper part of oil tank, and an

    oil conservator is set up on top of porcelain bushing, primary outlet

    terminal is on the oil conservator, series-parallel connection uses an

    external switch device, i.e., the switching operation is carried out

    outside the oil conservator.

    Use a stainless steel expander as the oil compensation device to

    ensure oil quality. Oil level is indicated by the pointer at the upper

    window of expander.

    A nameplate is set up on the oil tank to show the technical data. There are four lifting blocks for hoisting, an oil-discharge

    valve and earthing bolts at the bottom of oil tank.

    The product can have four to six secondary coils, the secondary measurement coil is made by microcrystalline alloy with

    high magnetic conductivity, thus can ensure that the measurement precision reaches up to 0.2 grade or 0.2S grade. 2600A

    or above current transformer has a pigtail at measurement secondary coil, in order to get two current ratios.

    Use new technology and new materials such as hot galvanizing or stainless steel standard parts etc for outside of the

    product to make complete equipment rustless.

    Reasonable and originative structure as well as advanced technology ensures that the product runs reliably, safely and

    durably.

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    15/24

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.4 We also can provide with products which meet the requirement of IEC and ANSI.

    Outline and Dimensional Drawings for LB7-220 type Current Transformer

    Outline and Dimensional Drawing

    Technical Parameters of LB7-220

    Type LB7-220

    Highest Voltage for Equipment kV 252

    Rated frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 460

    Rated lightning impulse withstand voltage (full wave)(peak) kV 1050Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208

    Flashover distance mm 2200

    Creepage distance mm 6300W2)7900W3

    Rated primary current (Maximum) A 2 6002 800

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (Maximum) kA 50kA/3s (In series)

    Dynamic current (Maximum) kA 125

    Allowable mechanical load of transformer (Static) N 3000

    Net weight kg 1180

    27 28

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Introduction to Product

    This product has an oil-immersed fully-sealed structure. It con-

    sists of metal expander, oil conservator, main body and other

    accessories. The primary coil is U-shape, the main insulation uses

    capacitor type oilpaper, use the high voltage cable paper to wrap

    the core of primary coil, and set up several main shields among it.

    The secondary coil is set up at the lower part of primary coil; the

    whole main body is fixed in the oil tank. There is a bushing at upper

    part of oil tank, and an oil conservator is set up on top of bushing, the

    primary wire is lead out via the hole of oil conservator, the series-

    parallel switching operation is carried out outside the oil conservator.

    Use a stainless steel expander as the oil compensation device to

    ensure oil quality. Oil level is indicated by the pointer at the upper window of expander.

    A nameplate showing the technical data and a description plate showing the coils arrangement schematic diagram are set

    up on the oil tank. There are four holes or lifting blocks on the under-frame for hoisting the product, and an oil-discharge valve

    and earthing bolts at bottom of oil tank.

    The product can have five or six secondary coils, the secondary measurement coil is made by microcrystalline alloy with

    high magnetic conductivity, thus can ensure that the measurement precision reaches up to 0.2 grade or 0.2S grade.

    The secondary terminal has limit and double sealing functions. The outlet box is made by stretching wholly; it is elaborate

    and practical. The oil tank is carried out surface treatment; it is bright and durable.

    Complete transformer is fully sealed. New technology and new materials such as hot galvanizing or stainless steel

    standard parts etc are used for outside of the product to prevent from rustless and get long working life.

    Reasonable and originative structure as well as advanced technology ensures that the product runs reliably, safely and

    durably.

    LB7-220 type Current Transformer

    Symbol Explanation

    L B 7220

    Voltage Grade, kV

    Design No.

    With Protection

    Current Transformer

    Except for the above basic symbol, suffixW2means that it is

    suitable for using in Grade area, suffixW3means that it is

    suitable for using in Grade area, and suffixGYmeans that it

    is suitable for using in plateau area.

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    16/24

    29 30

    Rated primary voltage kV 35

    Highest voltage for the equipment kV 40.5

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 95

    Rated lightning impulse withstand voltage (full wave)(peak) 185

    Flashover distance mm 450

    Creepage distance mm 10501256

    Rated primary current A 52000

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 40. 2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated output VA 10~40

    Safety factor FS 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Thermal current (Maximum) kA 40 kA/ 1s

    Dynamic current (Maximum) kA 100

    Type LAB6-35

    Main Technical Parameters

    Outline and Dimensional Drawing

    Outline and Dimensional Drawing for LAB6-35 type Current Transformer with Expander

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    LAB6-35 type Current Transformer

    Symbol explanation

    L A B 635

    Voltage Grade, kV

    Design No.

    With Protection

    Chain type

    Current Transformer

    Except for the above basic symbol, suffixW2means that it is suitable for using in Gradepolluted area, suffixW3

    means that it is suitable for using in Gradepolluted area.

    Introduction to product

    LAB6-35 type current transformer uses oilpaper insulation for outdoor use, it is a fully sealed product. It is used as a current,

    electric energy measurement and relay protective device for AC power system with highest voltage for the equipment of the

    equipment 40.5 kV and rated frequency 50Hz.

    The product can have three or four secondary coils, the magnetic core uses microcrystalline alloy with high magnetic

    conductivity, the measurement precision of secondary coil can be up to 0.2 grade or 0.2S grade.

    The oil conservator of this product is made of aluminum alloy. The oil tank is made by high-quality steel plate stretching

    to form as a whole, in order to reduce welding seam leakage points; it has not exposed sealing structure, so it can lengthen

    the aging period of seal ring, ensure that the sealing performance is reliable, improve the run quality of insulation oil, and

    ensure that the run is safe and reliable.

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    17/24

    Outline and Dimensional Drawing for LGBJ-35 type Current Transformer

    Technical Parameters of LGBJ-35 Current Transformer

    Outline and Dimensional Drawing

    Highest voltage for the equipment kV 40.5

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 95

    Rated lightning impulse withstand voltage (full wave)(peak)kV 200Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230

    Flashover distance mm 380

    Creepage distance mm 1020/1260

    Rated primary current (Maximum) A 2000

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-time thermal current (depend on the number of turns of 50kA/ 3s (In series)

    primary and secondary coils)MaximumkA

    Dynamic Current (Maximum) kA 125

    Allowable mechanical load of transformer: Static 2000N

    Outline and installation dimensions Fig.1

    Net weight kg 100

    Gross weight kg 120

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to therequirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    Type LGBJ-35W2 LGBJ-35W3

    31 32

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    LGBJ type Current Transformer

    Introduction to Product

    This product uses the capacitor equalizing theory; it uses optimal

    structural design by special electric field analysis and calculation; it

    is light and handy, and it is convenient for installation.

    The product is made of fire resistant and corrosion resistant

    material without oil or porcelain. It not only can be used in the city

    with high sanitary requirement, but also can be used in the area with

    severe pollution.

    This series product consists of primary coil, secondary coil, shell

    and base plate etc components.

    The secondary coil is set up at the bottom; it is covered by shell

    completely to prevent from dust and outer matters entering, and

    prevent from being corroded by sand blown by wind.

    The end shield or ground shield is led out separately to be convenient for test, and it also has good humidity resistance.

    The insulation resistance is stable and reliable.

    The secondary terminal block uses cast as a whole.

    This is a patented product of our company, and the patent No. is ZL 02 2 88478.5.

    This product uses organic composite material as its main insulation, so it has a long working life, and can be up to 30 years.

    No oil: there is not explosion risk, it is safe and does not leak forever.

    No porcelain: small and light.

    No gas: there is not possibility to pollute environment.

    Non-epoxy cast: it is used in the open air, it is stable and reliable.

    Advanced technology: use the optimal design concept with uniform voltage distribution; partial discharge is small and

    dielectric loss factor is low.

    Use special technology, carry out 1% NaCl water cooking test for 42 hours, the data do not change obviously before and

    after the test.

    The primary terminal uses copper or aluminium; it is led out horizontally, so it is convenient for wiring.

    Symbol explanation

    L G B J

    110 GY W2

    Antipollution Class

    Tableland type

    Voltage Class, kV

    With High Insulation

    With Protection

    Dry type

    Current Transformer

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    18/24

    Technical Parameters of LGBJ-110 type Current Transformer

    Outline and Dimensional Drawing for LGBJ-110 type Current Transformer

    Outline and Dimensional Drawing

    Type LGBJ -110W2 LGBJ -110W3

    Highest voltage for the equipment kV 126

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 230

    Rated lightning impulse withstand voltage (full wave)(peak) kV 550Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

    Flashover distance mm 1000

    Creepage distance mm 3150/3910

    Rated primary current (Maximum) A 2000

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Short-t ime thermal current (depend on the number o f turns of pr imary and 50kA/3s (In ser ies)

    secondary coils) (Maximum) kA

    Dynamic current (Maximum) kA 125

    Allowable mechanical load of transformer: Static N 2000N

    Outline and installation dimensions Fig.3

    Net weight kg 300

    Gross weight kg 350

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to therequirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    33 34

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Outline and Dimensional Drawing for LGBJ-66 type Current Transformer

    Technical Parameters of LGBJ-66 type Current Transformer

    Outline and Dimensional Drawing

    Type LGBJ-66W2 LGBJ-66W3

    Highest voltage for the equipment kV 72.5

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 140

    Rated lightning impulse withstand voltage (full wave)(peak) kV 325Rated lightning impulse withstand voltage (chopped wave)(peak) kV 374

    Flashover distance mm 700

    Creepage distance mm 1820/2250

    Rated primary current (Maximum) A 1250

    Rated secondary current A 1; 5

    Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    Rated output VA 10~50

    Safety factor FS 5; 10

    Accuracy limit factor ALF 10; 15; 20; 30

    Sho rt -t im e the rm al cur re nt ( de pe nd o n the n um be r o f turns o f p ri ma ry 5 0kA/3s ( In ser ie s)

    and secondary coils) (Maximum) kA

    Dynamic current (Maximum) kA 125

    Allowable mechanical load of transformer: Static N 2000N

    Net weight kg 220

    Gross weight kg 230

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    19/24

    Note: 1 We can supply the plateau type product which is suitable for altitude 3000m or above according to the requirement of customer,

    its technical parameters are the same as that of the product with 31mm/kV ratio of creepage distance and the highest voltage for

    equipment of the system;

    2 We also can provide with products which meet the requirement of IEC and ANSI.

    Type JDC6-110 JDCF-110

    Highest voltage for equipment kV 126

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 200

    Rated lightning impulse withstand voltage (full wave)(peak) kV 480

    Flashover distance mm 552

    Creepage distance mm 3150/3910

    Rated voltage factor 1.2/ continual 1.5/ 30s 1.2/ continual 1.5/ 30s

    Rated voltage ratio 110/ /0.1/ /0.1 110/ /0.1/ /0.1/ /0.1

    Accuracy class 0.2(0.5, 3P)/3P 0.2/0.5/3P

    Rated output VA 150(300,500)/300 100/250/300

    Limit output VA 2000 2000

    Oil weight kg 130/165 130/165

    Total weight kg 675/695 675/695

    Main Technical Parameters

    33 333

    Outline and Dimensional Drawing

    35 36

    JDCF-110 type Inductive Voltage Transformer

    (Creepage Distance25mm/kV

    JDCF-110 type Inductive Voltage Transformer

    Creepage Distance31mm/kV

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    JDC6-110 and JDCF-110 type Inductive Voltage Transformers

    Introduction to Product

    JDC6 -110 and JDCF-110 type voltage transformers use electromagnetic oilpaper insulation for outdoor use; it is a fully

    sealed product. It is used as a current, electric energy measurement and relay protective device for the system with effectively

    earthed neutral with the highest voltage for equipment 126 kV and rated frequency 50Hz.

    This product has a reliable design and low magnetic density, it can avoid ferroresonance over-voltage, the secondary coil

    can separate measurement from protection; the measuring precision can be up to grade 0.2 to meet the different requirement

    of customers and the high precision measuring requirement required by power departments.

    This product uses a stainless steel expander; it is carried out advanced vacuum drying and vacuum oiling treatment

    technology, so it has small dielectric loss and low partial discharge, and can ensure that the operation of product is safe and

    reliable.

    Symbol explanation

    J D C 6 110W

    Anti Fouling

    Rated Voltage, kV

    Design Number

    With Residual Voltage

    Winding in Cascade Stage

    Single Phase

    Voltage Transformer

    J D

    C F

    110

    W

    Anti Fouling

    Rated Voltage, kV

    With Secondary Winding for

    Measurement and Protection

    respectively

    With Residual Voltage

    Winding in Cascade Stage

    Single Phase

    Voltage Transformer

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    20/24

    37 38

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Outline and Dimensional Drawing of

    JDX6-35W3 Inductive Voltage Transformer(Accuracy Class 0.5/3P)

    Outline and Dimensional Drawing of

    JD6-35W3 Inductive Voltage Transformer

    Main Technical Parameters

    Outline and Dimensional Drawing

    Type JD6-35 JDX6-35

    Highest voltage for equipment kV 40.5

    Rated frequency Hz 50

    Rated power-frequency withstand voltage (rms) kV 95

    Rated lightning impulse withstand voltage (full wave)(peak) kV 200Rated lightning impulse wit hstand voltage (chopped wave)(peak) kV 230

    Creepage distance 31

    Rated voltage factor 1.2 continual 1.2 continual/ 1.98h

    Rated voltage ratio 35/0.135/ /0.1/ /0.1/3

    35/ /0.1/ /0.1/ /0.1/3

    Accuracy class 0.2(0.5)0.2(0.5)/3P

    0.2/1.5/3P

    Rated output VA 80(150)80(150)/10

    30/80/1000

    Limit output VA 1000 1000

    Oil weight kg 29 24

    Total weight kg 135 127

    3 3

    3 3 3

    Outline and Dimensional Drawing of

    JDX6-35W3 Inductive Voltage Transformer(Accuracy Class 0.2/0.5/3P)

    JD6-35 and JDX6-35 type Inductive Voltage Transformers

    Symbol explanation

    J D (X) 6 35 W

    Anti Fouling

    Rated Voltage, kV

    Design Number

    With Residual Voltage Winding

    Single Phase

    Voltage Transformer

    Introduction to Product

    JD6-35 and JDX6-35 type voltage transformers use oilpaper insulation for outdoor use; it is a fully sealed product. It is used

    as a current, electric energy measurement and relay protective device for the system with the highest voltage for equipment

    40.5 kV and rated frequency 50Hz.

    JD6-35 type voltage transformer has a structure with single phase and double coils, it is suitable for connecting at the place

    between the phase and phase in a system with ineffectively earthed neutral.

    JDX6-35 type voltage transformer has a structure with single phase and triple coils; it is suitable for connecting at the place

    between the phase and ground in a system with ineffectively earthed neutral.

    The core of product uses high quality silicon steel sheets, the measuring precision can be up to grade 0.2; the oil tank has

    a form structure, it is formed by stretching high quality steel plate wholly to reduce the number of welding seam leakage points.

    The rubber ring uses double sealing to ensure that the operation of product is reliable.

    JDX6-35JD6-35

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    21/24

    39 40

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    TYD110/220 type Capacitor Voltage Transformer

    Symbol explanation

    T YD 110/220 0.01 H

    Anti Fouling

    Rated Capacitance, F

    Rated Phase Voltage

    Capacitor Voltage Transformer

    Integrated Equipment

    Introduction to Product

    Capacitor voltage transformer series products are suitable for current, electric energy measurement and relay protection

    in a system with effectively earthed neutral with rated voltage 35kV, 66kV, 110kV or 220kV and rated frequency 50Hz. It can

    also be used for carrier wave communication concurrently.

    This product consists of capacitor voltage divider and electromagnetic unit the medium voltage terminal and low voltage

    terminal of capacitor voltage divider are lead out into an oil tank equipped with electromagnetic unit. The electromagnetic unit

    consists of middle transformer, a compensation reactor and a damper

    The capacitor voltage divider consists of a bushing, a core and a metal expander. The core of capacitor is combined by

    several film-paper composite media and serial parts which are made by coiling aluminum foils, it is carried out vacuum dipping

    treatment, the porcelain bushing is filled with transformer oil, and it is equipped with the metal expander to compensate the

    change of oil volume at different temperatures.

    This series transformer has a quick saturation damping device with a quick transient response speed, and it also can damp

    ferroresonance reliably.

    There is a carrier wave communication terminal in the secondary outlet box, and it also has an over-voltage protection clearance.

    There are an oil level gauge, an outlet box, a nameplate, an oil-discharge plug and an earthing base outside the oil tank.

    The sealing structure of product is optimized, so it has a good sealing performance.

    3

    Maintechnicalparameters

    Note:1Theparametersinthetablearenotchangeless;theCompanyreservestherighttochan

    gethem.

    2Whentheparametersrequ

    iredbythecustomeraredifferentfromthatinthetable,theycanbenegotiatedaccordingtotherequirementofthecustom

    er.

    3Wecansupplytheproductwith31mm/kVratioofcreepagedistanceandhighestvoltageforequipmentofthesystem;

    4WealsocanprovidewithproductswhichmeettherequirementofIECandANSI

    3 3 3 3 3 3

    1

    TYD35/

    -0.02W3

    40.5

    35/

    0.1/

    0.1/

    0.1/3

    50

    0.2

    50

    0.5

    100

    3P

    95/200

    3

    1

    500

    2

    TYD66/

    -0.02W3

    72.5

    66/

    0.1/

    0.1/

    0.1/3

    100

    0.2

    100

    0.5

    100

    3P

    140/325

    3

    1

    500

    3

    TYD110/

    -0.0066H

    126

    110/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    200/480

    2

    5

    500

    4

    TYD110/

    -0.007H

    126

    110/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    200/480

    2

    5

    500

    5

    TYD110/

    -0.008H

    126

    110/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    200/480

    2

    5

    500

    6

    TYD110/

    -0.01H

    126

    110/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    200/480

    2

    5

    500

    7

    TYD110/

    -0.01H

    126

    110/

    0.1/

    0.1/

    0.1

    100

    /0.2

    100/0.5

    100/3P

    100/3P

    200/480

    2

    5

    570

    8

    TYD110/

    -0.015H

    126

    110/

    0.1/

    0.1/

    0.1

    100

    /0.2

    100/0.5

    100/3P

    100/3P

    200/480

    2

    5

    570

    9

    TYD110/

    -0.02H

    126

    110/

    0.1/

    0.1/

    0.1

    150

    /0.2

    150/0.5

    150/3P

    100/3P

    200/480

    2

    5

    680

    10

    TYD220/

    -0.0033H

    252

    220/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    395/950

    2

    5

    750

    11

    TYD220/

    -0.0035H

    252

    220/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    395/950

    2

    5

    750

    12

    TYD220/

    -0.004H

    252

    220/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    395/950

    2

    5

    750

    13

    TYD220/

    -0.005H

    252

    220/

    0.1/

    0.1

    100

    /0.2

    150

    /0.5

    100/3P

    395/950

    2

    5

    750

    14

    TYD220/

    -0.005H

    252

    220/

    0.1/

    0.1/

    0.1

    100

    /0.2

    100/0.5

    100/3P

    100/3P

    395/950

    2

    5

    820

    15

    TYD220/

    -0.0075H

    252

    220/

    0.1/

    0.1/

    0.1

    100

    /0.2

    100/0.5

    100/3P

    100/3P

    395/950

    2

    5

    820

    16

    TYD220/

    -0.01H

    252

    220/

    0.1/

    0.1/

    0.1

    150

    /0.2

    150/0.5

    150/3P

    100/3P

    395/950

    2

    5

    910

    H

    ighestRatedPrimary

    RatedSecondary

    RatedOutput(VA)

    Insulation

    Ratioofcree

    pagedistance

    S/N

    Type

    V

    oltage

    Voltage

    Voltage(kV)

    /AccuracyClass

    Level(kV)

    andHighes

    tvoltagefor

    Weight

    (kV)

    (kV)

    1a-1n

    2a-2n

    da-dn

    1a-1n

    2a-2n

    da-dn

    PowerFrequency/Lightnin

    equipment(mm/kV)

    (kg)

    33 3 3 3 3 3 3 3 3 3 3 3 3

    33 3 3 3 3 3 3 3 3 3 3 3 3

    33 3 3 3 3 3 3 3 3 3 3 3 3

    3 3

    3 3

    3 3

    3 3

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    22/24

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    23/24

    43 44

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Outline and Dimensional Drawings of CWG - L - 40.5 - CWG - L - 126

    CWG-72.5/630 220 22040 4-14

    60

    CWG-72.5/800 220 220 181565

    CWG-72.5/1000 2470 770 220 770 220 1040 5 50 275 300 2250

    CWG-72.5/1250 220 220 50 4-18 70

    CWG-72.5/1600 220 2206-18

    75

    CWG-126/6301040

    2201040

    2201390 40 4-14

    80

    CWG-126/800 220 220 90

    CWG-126/10003 16 0 1 04 0

    2201040

    2201390 700 350 350

    315095

    CWG-126/1250 220 220 50 4-1 8 39 06

    CWG-126/16001040

    2201040

    2201390

    110

    CWG-126/2000 220 220 120

    Table 2 unit: mm

    O ut do or si de I nd oo r S id e E ar th P ot en ti al I ns ta ll at io n F la ng e T er mi na l B lo ck C re e- W ei -

    Type Total Insulation Maximum Insulation Maximum Total Total Indoor Diameter of Instal lation Distance Between Instal l- page ght

    Length Distance External Insulation External Length Length L5 Installation Hole Hole the Center of Two Holes a ti on d is t- kg

    L1 Diameter L3 Diameter L4 L2 D1 a1 Hole ance

    CWG-L-40.5/630 180 18040 4-14

    50

    CWG-L-40.5/800 55

    CWG-L-40.5/1000 1910 220 220 101560

    CWG-L-40.5/1250 470 220 470 220 970 450 500 200 50 4-18 1 26065

    CWG-L-40.5/1600 220 220

    CWG-L-40.5/3150 2070 220 220 60 8-18 70

    CWG-L-40.5/4000 2070 220 220 60 8-18 70

    CWG-L-72.5/630 220 220 40 4-14 65

    CWG-L-72.5/800 220 220 6-18 181570

    CWG-L-72.5/1000 2820 730 220 730 220 1400 9 70 670 300 2250

    CWG-L-72.5/1250 220 220 50 4-18 75

    CWG-L-72.5/1600 220 220 80

    CWG-L-126/6301100

    2201100

    2202070 40 4-14

    80

    CWG-L-126/800 220 220 90

    CWG-L-126/1000 35601100

    2201100

    2202070 950 600 350

    315095

    CWG-L-126/1250 220 22050 4-18

    3906

    CWG-L-126/16001100

    2201100

    2202070

    110

    CWG-L-126/2000 220 220 120

    Main Technical Parameters

    Type test items

    Complete all test items according to the requirement of GB/T4109-1991.

    Rated voltage is 12~126 kV, standard current values can be chosen from the following (Unit: A)

    250, 400, 630, 800, 1000, 1250, 1600, 2000, 3150, 4000

    Precision of attached current transformer:

    1. Measurement coil: 0.1, 0.2, 0.5, 0.2S, 0.5S (Grade)

    2. Accuracy grade of protection coil: 5P, 10P; Accuracy limit factor:10, 15, 20, 30

    3. Secondary output capacity (VA): 20, 25, 30, 40 50

    Antipollution grade and cree page distance

    Outline and Dimensional Drawings of CWG-40.5-CWG-126

    Insulation Level and Discharge Level (Voltage Unit: kV)

    R ated Vol ta ge N om in al Vol ta ge Pow er -f re qu en cy Withs ta nd L ig htni ng Imp ul se Par ti al D isch arge L evel

    Ur o f th e System Vol ta ge (Dry or Wet ) Withs ta nd Vo ltag e M ea su re me nt Vol ta ge pC

    40.5 35 95 200 35 10

    72.5 66 147 325 63 10

    126 110 230 550 109 10

    Light, Medium 20 3.5

    Severe 25 4.0

    Special severe 31 4.0

    Nominal Value of Minimum Ratio of Creepage Distance and Highest Voltage

    for Equipment Relative to Ground mm/kV ( Highest Voltage for Equipment )

    Ratio of Creepage Distance and Highest

    Voltage for Equipment/ Flashover Distance

    Antipollution

    Grade

    Table 1 unit: mm

    O ut do or si de I nd oo r S id e E ar th P ot en ti al I ns ta ll at io n F la ng e T er mi na l B lo ck C re e- W ei -

    Type Total Insulation Maximum Insulation Maximum Total Total Indoor Diameter of Instal lation Distance Between Install- page ght

    Length Distance External Insulation External Length Length L5 Installation Hole Hole the Center of Two Holes a ti on d is t- kg

    L1 Diameter L3 Diameter L4 L2 D1 a1 Hole ance

    CWG-40.5/630180 180 40 4-14

    45

    CWG-40.5/800 50

    CWG-40.5/1000 1560 220 220 101555

    CWG-40.5/1250440

    220440

    220600 300 150 200 6-f18

    50 4-18 1260 60

    CWG-40.5/1600 220 220 60

    CWG-40.5/31501720

    220 22060 8-18

    65

    CWG-40.5/4000 220 220 65

  • 8/11/2019 Catalogue Jiangsu Sieyuan Hertz[1]

    24/24

    45

    !"#$%&'()*

    JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

    SieyuanSieyuanSieyuanSieyuanSieyuan

    Parameters of CWG-126 (CWG-L-126)

    Type CWG-126/250~4000 CWG-L-126/250~4000

    Highest Voltage for Equipment kV 126

    Rated Frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 230

    Rated lightning impulse withstand voltage (full wave)(peak) kV 550Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

    Flashout Distance mm 1200

    Creepage Distance mm 3150 or 3906

    Rated Primary Current (Maximum) A 2000

    Rated Secondary Current of Built-in Current Transformer A 15

    Accuracy Classes of Built-in Current Transformer0.10.20.50.2S; 0.5S; 5P; 10P

    (They can be combined if necessary)

    Rated Output of Built-in Current Transformer VA 10-50

    Safety Factor of Built-in Current Transformer FS 5; 10

    Accuracy Limit Factor of Built-in Current Transformer 10; 15; 20; 30

    Short-time Thermal Current 25 times of rated current

    Bending Load Withstand Test 2000N

    Outline and Installation Dimensions See the corresponding drawings

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 We can supply the product with 31mm/kV ratio of creepage distance and highest voltage for equipment of the system;

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    CWG-126/2504000

    CWG-L-126/2504000

    126

    50/60

    230

    550

    633

    1200

    3150 or 3906

    2000

    15

    0.10.20.50.2S; 0.5S; 5P; 10P

    10-50

    5; 1010; 15; 20; 30

    25 times of rated current

    2000N

    See the corresponding drawings

    Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the requirement of the customer.

    3 We can supply the product with 31mm/kV ratio of creepage distance and highest voltage for equipment of the system;

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    TypeCWG-72.5/2504000

    CWG-L-72.5/2504000

    Highest Voltage for Equipment kV 126

    Rated Frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 230

    Rated lightning impulse withstand voltage (full wave)(peak) kV 550

    Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633

    Flashout Distance mm 1200

    Creepage Distance mm 1815 or 2250

    Rated Primary Current (Maximum) A 2000

    R ated Secon da ry C ur re nt o f Bui lt -i n C ur re nt T ra ns fo rm er A 15

    Accuracy Classes of Built-in Current Transformer0.10.20.50.2S;0.5S;5P;10P

    (They can be combined if necessary)

    Rated Output of Built-in Current Transformer VA 10-50

    Safety Factor of Built-in Current Transformer FS 5;10Accuracy Limit factor of Built-in Current Transformer 10; 15; 20; 30

    Short-time Thermal Current 25 times of rated current

    Bending Load Withstand Test 2000N

    Outline and Installation Dimensions See the corresponding drawings

    Parameters of CWG-72.5 (CWG-L-72.5)

    Parameters of CWG-40.5 (CWG-L-40.5)

    Type CWG-40.5/250~4000 CWG-L-40.5/250~4000

    Highest Voltage for Equipment kV 40.5

    Rated Frequency Hz 50/60

    Rated power-frequency withstand voltage (rms) kV 95

    Rated lightning impulse withstand voltage (full wave)(peak) kV 200Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230

    Creepage Distance mm 1015 or 1260

    Rated Primary Current (Maximum) A 4000

    Rated Secondary Current of Built-in Current Transformer A 1, 5

    Accuracy Classes of Built-in Current Transformer0.2; 0.5; 0.2S; 0.5S; 5P; 10P

    (They can be combined if necessary)

    Rated Output VA 10-50

    Safety Factor FS 5, 10

    Accuracy limit Factor ALF 10; 15; 20; 30

    Short-time Thermal Current 25 times of rated current

    Bending Load Withstand Test 2000N

    Outline and Installation Dimensions See the corresponding drawings

    Note: 1 The Company reserves the right to change the parameters in the table.

    2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the

    requirement of the customer.

    3 There are several current ratios for one-time switch of the transformer.

    4 We also can provide with products which meet the requirement of IEC and ANSI.

    46