cathodic protection
DESCRIPTION
CPTRANSCRIPT
Cathodic Protection
ME 472-061 Corrosion Engineering IME, KFUPM
Dr. Zuhair M. Gasem
Dr. Z. Gasem ME 472-061
KFUPM2
References:ASM Handbook, vol 13, pp. 466-477Corrosion for Science and Engineering, K.R. Trethewey and J. Chamberlain, chapter 16Handbook of Corrosion Engineering, P.R. RobergeCathodic Protection in ARAMCO’s Engineering Encyclopedia
Dr. Z. Gasem ME 472-061
KFUPM3
Fe2+
Fe2+
HH22HH++
HH++ HH++ HH++ HH++
HH++
HH HH
e eMetal
Cathode
Anode
AcidSolution
Electron Flow
Anodic and Cathodic Reactions of Iron in Acids
Corrosion Cell on a Metal Surface
Dr. Z. Gasem ME 472-061
KFUPM4Basic Physics of CP of Iron in Acids
Electrons from an external source are forced to flow into the structure to be protected resulting in:
Increased cathodic reaction (2H+ + 2e- → H2) Decreased anodic reaction and hence reduced corrosion rate
Electrons from external source
eeee
eeeeeee
eeee
Electrolyte
H+H+ H+ H+ H+ H+ H+
eeH+Fe2+
HHHHH H H H
H2 H2 H2 H2
H+ H+
H+
H+
H+H+
Dr. Z. Gasem ME 472-061
KFUPM5Polarization Principle of CP of Iron in Acids
Before CP:ianode = icathode= icorr
E = Ecorr
After CP:icorr = iaicathode = iciapp = ic – iaE = ECP
ECP
Dr. Z. Gasem ME 472-061
KFUPM6Polarization Principle of CP of Iron in Water
The cathodic reaction for corrosion of steel and iron in aerated-water is usually (O2+2H2O+2e→4OH-) under concentration polarization. Before CP:
ianode = icathode = iLE = Ecorr
After CP:icorr = iaicathode = ic = iLiapp = ic – iaE = ECP
ECP
Dr. Z. Gasem ME 472-061
KFUPM7Cathodic Protection
Summary of cathodic protection:CP makes the structure’s potential more negative which promotes cathodic reactions and slows anodic reaction Increases icathode
Decreases ianode
Need to supply iapp = icathode - ianode
Where CP is used?CP is often applied to coated structures, with the coat providing the primary form of corrosion protection and the CP system acts as asupporting protection.
The main applications of CP include: Buried pipelineAcids storage tanksOffshore steel structures such as platforms and oil rigs ShipsConcrete structures exposed to seawater such as bridges
Dr. Z. Gasem ME 472-061
KFUPM8CP of Buried Pipelines
Before CP is applied:Anodes and cathodes are on the same surface of the pipe The soil is the electrolyteIonic current flow b/w the anode and the cathode in the external surfacesElectrons flow in the metal from anode to cathode
Dr. Z. Gasem ME 472-061
KFUPM9CP of Buried Pipelines
After CP is applied:The structure to be protected becomes the cathode The anode is an external electrode:
Amore active metal (sacrificial anode)An inert anode with impressed DC current (Impressed current)
The soil is the electrolyteIonic current flow b/w the anode and the cathode in the external surfacesElectrons flow between the anode and cathode through an insulated copper wire.
cathodeSacrificial anode
e-
+ve ions current in electrolyte
Dr. Z. Gasem ME 472-061
KFUPM10CP of Buried Pipelines
Sources of currentSacrificial anode systemImpressed current system (note the - polarity from the rectifier)
Dr. Z. Gasem ME 472-061
KFUPM11Electrochemical reaction in sacrificial Anode CP System
Cathodic reactions on the steel structure:
In aerated wet soilO2+2H2O+4e- ⇒ 4OH-
In aerated wet acidic soil O2+4H+ + 4e- ⇒ 2H2O
In neutral seawater O2+2H2O+4e- ⇒ 4OH-
In de-aerated soil or water2H2O+2e- ⇒ 2OH- +H2
Anode reactions At active anode in sacrificial anode CP system (Mg, Al, Zn)
M → M+n + ne-
Dr. Z. Gasem ME 472-061
KFUPM12CP of pipelines
Note that cathodic protection current will only protect external surfaces on buried structures, because the anode-electrolyte-cathode is at external surfaces. Above ground, structures cannot be protected by cathodic protection because the current discharged from the current source can not travel through the atmosphere (no electrolyte).CP is not usually used to protect internal surfaces of pipelines because of difficulty in placing anodes.internal surfaces of pipelines can be protected by: inhibitors, coatings, or by using a corrosion resistant alloy.
Dr. Z. Gasem ME 472-061
KFUPM13Protection Criteria
How much current is needed to protect the pipeline?
Little current will lead to ineffective protection High current will lead to disbonding of coatings and hydrogen embrittlement (more power consumption and higher cost)Experience show that we should keep the pipeline potential less than a protection potential.
Dr. Z. Gasem ME 472-061
KFUPM14Protection Criteria
In less corrosive soil, E< -0.850 mV wrtCu/CuSO4 reference electrode this reference electrode is used because it is less sensitive to temperature variation (0.318 s. SHE)In Saudi’s Aramco, the protection potential for cross-country pipeline is -1.1 V vsCu/CuSO4 (due to highly corrosive soil)More –ve potential means more current required and more operation cost.
Dr. Z. Gasem ME 472-061
KFUPM15Reference Electrodes
Common reference electrodes used in CPCu/CuSO4 in soil
CuSO4 + 2e- ↔ Cu+SO42-
E vs. SHE 0.318 V
AgCl in seawater AgCl + e- ↔ Ag + Cl-
E vs. SHE 0.222 V
Dr. Z. Gasem ME 472-061
KFUPM16Potential Protection
Why <-0.850 mV vs. Cu/CuSO4?From Pourbaix diagram, Fe is stable below -0.6 V vs SHECu/CuSO4 is more +vethan SHE by 0.318 VHence, Fe is stable and corrosion is minimum if potential is (-0.6-0.318= -0.918 V vs Cu/CuSO4)
Dr. Z. Gasem ME 472-061
KFUPM17Potential and Corrosion of Buried Steel
Severe overprotection (disbonding of coatings, hydrogen blistering, HE)
-1.1 to -1.4
Overprotection-0.9 to -1.1
Cathodic protection-0.8 to -0.9
Slow corrosion -0.7 to -0.8
Corrosion-0.6 to -0.7
Intense corrosion-0.5 to -0.6
Corrosion condition Potential (V vs. Cu/CuSO4)
Dr. Z. Gasem ME 472-061
KFUPM18NACE Standards for CP
Dr. Z. Gasem ME 472-061
KFUPM19
Saudi Aramco’s Potential Requirements
Structure Minimum Required Potentials
Buried Cross-Country Pipelines -1.10 volts versus CuSO4 electrode.
Buried Plant Piping, Tank -1.00 volt versus CuSO4 electrode.
Bottom Externals, -850 mV versus CuSO4 electrode.Isolated Buried Casings
Water Tank Interiors -0.90 volts vs. AgCl electrode
Marine structures -0.90 volt or more negative versus AgCl electrode
Dr. Z. Gasem ME 472-061
KFUPM20Soil Corrosivity
Soil is composed mainly of mineral particles (mainly SiO2).Soil is composed of a mixture of:
Fine sand (0.02-0.2 mm)Coarse sand (0.2-2 mm)Slit (0.002-0.02 mm)Clay (< 0.002 mm)
The soil particles are covered with thin surface film of moisture with dissolved salts and gases.The total volume of soil consists of solid particles and pores filled with moisture and air. Soils with a high proportion of sand have very limited storage capacity for water whereas clays are excellent in retaining water Air in the pores contains 10-20 times as much CO2 as atmospheric air. Soils with high moisture content, high electrical conductivity, high acidity, and high dissolved salts will be most corrosive.
Dr. Z. Gasem ME 472-061
KFUPM21Soil Corrosivity
Variables affecting soil corrosivity:Water is the electrolyte for electrochemical corrosion reactions Oxygen: the oxygen concentration decreases with increasing depth of soil pH: soils usually have a pH range of 5-8
Soil acidity is produced by decomposition of acidic plants, industrial wastes, and acid rain Alkaline soils tend to have high sodium, potassium, magnesium and calcium contents which form calcareous deposits on buried structures with protective properties against corrosion.
Chloride level: harmful for metals sulfate level: harmful for concreter
Dr. Z. Gasem ME 472-061
KFUPM22Soil Corrosivity
For CP design against corrosion, the most important property of a soil in determining its corrosivity is its electrical conductivity. The table shows soil corrosion severity ratings. Soil corrosion causes corrosion in underground petroleum storage tanks, pipelines, and water distribution systems.Soil resistivity is measured by Wenner 4-pin method
Very corrosive
Corrosive
Moderately corrosive
Mildly corrosive
Essentially non-corrosive
Corrosivity Rating
<1,000
1,000 to 5,000
5,000 to 10,000
10,000 to 20,000
Dry sand
Clay with saline water (sabkha)
>20,000
Soil resistivity (ohm cm)
Dr. Z. Gasem ME 472-061
KFUPM23Soil Corrosivity
Electrolyte Resistivity (ohm-cm)
Seawater (Gulf) 16Raw water 200-2000Drinking water 2000-5000
10,000
2,000
1,000500
Progressively LessCorrosive
Mildly Corrosive
Moderately CorrosiveCorrosiveVery Corrosive
Ohm-cm
Seawater Resistivity
Dr. Z. Gasem ME 472-061
KFUPM24
Current density required to reach Ecp for steel in moving and standing seawater and in soil
5-1111-3245-75160-270
Stagnant seawater
1.1-0.545.4-1111-1643-54soil
11-1632-5475-105325-375
Moving seawater
Applied CP current
Initial CP current
Applied CP current
Initial CP current
Coated steel (mA/m2)Bare Steel (mA/m2)Environment
ASM Handbook Vol#13 p.476
Dr. Z. Gasem ME 472-061
KFUPM25
Given a coated offshore structure with a surface area of 5,000 m2, 2/3 is immersed in seawater, calculate the amount of initial current and applied current necessary to cathodically protect the structure.The initial and applied current density requirement for coated seawater structures is 35 and 10 mA/m2.iinitial = 5,000*2/3*35= 116,666 mA = 117 A iapplied = 5,000*2/3*10 = 33,333 mA = 34 A
Current Calculation for Design
Dr. Z. Gasem ME 472-061
KFUPM26
Given a 150 m section of 0.75 m diameter steel pipe coated with fusion bonded epoxy (FBE), calculate the total amount of current required. Assume that 10% of the coating was damaged during installation. Assume that the required current density for FBE coated buried pipeline is 0.1 mA/m2 while for uncoated steel is 1 mA/m2 .
surface area = πDL=354 m2
iinitial = bare area*1 mA/m2 + coated area*0.1 mA/m2
= 354*0.1*1 + 354*0.9*0.1 = 67.3 mANote that if the whole pipe is not coated, then the
current requirement would be= 354*1=354 mA (5 times more than above)
Example
Dr. Z. Gasem ME 472-061
KFUPM27Coatings in CP Systems
Bare structures require more current than Bare structures require more current than coated structures coated structures Economical applications of CP for buried pipelines applied only for coated pipelines. Always assume 5-10% of coated area as bare due to damage during pipe installation.
Dr. Z. Gasem ME 472-061
KFUPM28Sacrificial Anode CP Systems
a more active metal than steels can act as a sacrificial anode.The galvanic series indicate that Mg, Zn, and Al are more active than steels.A number of anodes are electrically connected to the steel structure to be protected to provide the needed current.The amount of current output is increased by increasing the number of anodes.Usually applied in:
Low current requirement application Soil resistivity < 10,000 (Ω.cm)
Dr. Z. Gasem ME 472-061
KFUPM29Sacrificial Anode CP Systems
Advantages of sacrificial CP:No external power source neededEase of installation, low maintenance, low costProvides uniform distribution of current
DisadvantagesLimited current and power outputHigh resistivity environments or large structures require a large number of anodesPeriodic replacement of anodes
Dr. Z. Gasem ME 472-061
KFUPM30
VoltsMetal (referenced to Cu/CuSo4)
Commercially pure magnesium -1.75Magnesium alloy (6% Al, 3%, Zn, 0.15% Mn) -1.6Zinc -1.1Aluminum alloy (5% Zn) -1.1Commercially pure aluminum -0.8Mild steel (clean and shiny) -0.5 to -0.8Mild steel (rusted) -0.2 to -0.5Cast Iron -0.5Lead -0.5Mild steel in concrete -0.2Copper, brass, bronze -0.2High silicon cast iron -0.2Mill scale on steel -0.2Carbon, graphite, coke +0.3
Galvanic Series in soil and seawater
Dr. Z. Gasem ME 472-061
KFUPM31Sacrificial anodes
In soil, special backfills are used with sacrificial anodes to improve anode efficiency.Anodes are packaged in porous bags prefilled with backfill materials such as clay. Clay:
absorbs moisture from the soil and reduce anode resistance of anode/electrolyte distribute the anodic reaction all over the anodeIncrease the life of the anode
Dr. Z. Gasem ME 472-061
KFUPM32Sacrificial anodes
Anodes are packaged in bags filled with backfill material Commercial anodes (
60 inch in length4 Kg
Anodes for buried structures (pipes, tanks):
Pure Mg Mg alloy (Mg+6Al+3Zn+0.2Mn)Pure Zn
For marine applications Al alloy containing 5% Zn is used Zn alloy
Dr. Z. Gasem ME 472-061
KFUPM33Design of Sacrificial Anode CP
Select Protection Criterion (depends on the environment)For buried steel (NACE standard gives protection potential = -850 mV vs. Cu/CuSO4 )
Measure resistivity of environment (slide#34):Soil resistivity ranges from (500-20,000 Ω*cm) Seawater ranges from ( 10-50 Ω*cm)
Estimate cathodic current requirement which depends on the environment and the surface area to be protected using either:
Current requirement table (see slide#24)Current requirement test (see slide#35)
Select a suitable sacrificial anode and calculate the theoretical capacity and the driving voltage (slide#37 and 38)Estimate the number of anodes needed based on groundbed resistance (slide#41 and 42)Estimate anode life and replacement period
Dr. Z. Gasem ME 472-061
KFUPM34Wenner 4-pin Method to Measure Soil Resistivity
This method is done by placing four pins at equal distances from each other. A current is passed through the two outer pins using a power supply. the voltage across the two inner pins is measured using a voltmeter. the resistance can be calculated using Ohm's law (Resist = ∆V/I). Soil resistivity = 191.2*∆V/I*d (d in feet) ohm-cm, where R is the soil resistance and d is the pin spacing in feet.
Power supply
voltmeter
Dr. Z. Gasem ME 472-061
KFUPM35Current Requirement Test
The current may be increased gradually until the voltmeters at positions A and B reaches -0.85 V with respect to a copper sulfate reference electrode placed directly above the pipe. Current requirement test:
A small DC power system is used (10 A)A temporary anode ground bed is installedPotential loggers are installed at selected test locations to monitor potentialsA current is applied and the potential is measuredThe current that brings the potential of the whole pipe below the protective potential is used the required current for protection
Dr. Z. Gasem ME 472-061
KFUPM36Sacrificial Anode
Anodes must have:High driving potential to generate sufficient current Stable operating potentials over a range of current outputs (Eanode does not vary a lot with i) High capacity to deliver current per unit massDoes not passivate Theoretical capacity: the total charge in coulombs produced by the corrosion (dissolution) of a unit mass of the anode material [units in (A* hr)/Kg]. High Efficiency (efficiency = actual capacity/theoretical capacity*100)
Dr. Z. Gasem ME 472-061
KFUPM37Calculating the theoretical capacity
MW of Mg is 24.3 g/mol, density=1.74 g/cm3Mg→Mg+2 + 2e- (one mole of Mg produces 2 moles of electrons)Take 1 Kg of Mg as a basis:
1000g * mole/24.3g=41.2 mole of Mg# of e- mole= 2*41.2=82.4 moles of e-
82.4 moles of e- *96500 Coulomb/(mole e)= 795,1600 Coulomb/(Kg of Mg) 795,1600 Coulomb/Kg *1 hr/3600s=2,200 (A.hr)/Kg
Dr. Z. Gasem ME 472-061
KFUPM38Calculating driving potential
ED = Eanode – Ep + Epolar
ED = driving potentialEanode = anode potentialEp = protection potentialEpolar = change in potential of anode due to current flow (polarization); usually taken as 0.1 V
ED
Dr. Z. Gasem ME 472-061
KFUPM39Driving Potential
Example: calculate the driving potential for Mg in soil assuming:
Eanode = -1.75 vs Cu/CuSO4Ep (buried pipeline cross country) = -1.0 VEpolar = 0.1 VED = -1.75 – (-1.0) +0.1 = -0.65 V
Example: calculate the driving potential for Al alloy (5%Zn) in soil assume Ep = -0.85 V and Epola=0 and Eanode=-1.1V
ED = -1.1- (-0.85) = -0.25 V
Dr. Z. Gasem ME 472-061
KFUPM40Sacrificial Anodes
-1.1 -1.1-1.75 V (vsCu/CuSO4)
potential
>90%>90%50-60%Efficiency
26407801232Actual capacity
29808102200 (A*hr)/Kg
Theoretical capacity
AlZnMg
Dr. Z. Gasem ME 472-061
KFUPM41Anode bed (groundbed) resistance
In both systems, the flow of current is analogous to a simple resistive circuit.The highest resistance to current flow is due to the anode/electrolyte resistance (Rab)RS (structure/electrolyte) resistance. RLW (lead wire) resistance. Rab = Resistance of anode/electrolyte; depends on the anode shape and the resistivity of the environment. Rtotal = Ra+RLW+RS
(RS and RLW) can be neglectedRtotal ≈ Rab
R
Battery
Resistor
E
Electric CircuitI
Rtotal
Dr. Z. Gasem ME 472-061
KFUPM42Anode bed (ground bed) resistance
Dwight’s equation for single vertical anodes:Ra = ρ/(2πLa)*(ln(8La/Da) -1)(for slender anodes mounted at least 0.3 m away from the steel structure)
La= length of anode (cm)ρ = soil resistivity (Ω.cm)Da = anode diameter (cm)
Anode current output i = ED/Ra
C
A
Rab
Dr. Z. Gasem ME 472-061
KFUPM43Anode bed (ground bed) resistance
Example: Calculate the maximum current output for zinc anodes (L = 150 cm and D = 15 cm) in sacrificial anode CP system. Assume very corrosive soil (ρ=1000 Ω*cm)
1. Calculate the driving potential assuming Epola = 0.1V, EZn = -1.1 vs Cu/CuSO4, Ep (buried pipeline) = -0.85 V
ED = -1.1 – (-0.85)-0.1 = -0.15 V
2. Calculate the ground bed resistanceRa = ρ/(2πLa)*(ln(8La/Da) -1)Ra = 1000/(2π*150)*(ln(8*150/15)-1) = 3.6 Ω
3. Calculate the maximum current output from each anodei = ED/Ra = 0.15/3.6 = 0.042 A = 42 mA
Dr. Z. Gasem ME 472-061
KFUPM44Anodes distribution
Example: suppose you need 1 A to protect a steel structure by using Zn anodes as in the previous example. Each anode provides 0.042 A.Then, you need to have 1/(0.042) ≈ 24 anodes to give sufficient protection. Distance of anode to cathode:
Too far: high resistance in the soil leads to voltage dropToo short: current distribution is not uniform Needs experience (usually less than a meter)
Dr. Z. Gasem ME 472-061
KFUPM45Design Example
Example: design a CP system for a section of coated steel buried pipe assuming that the current required to shift the pipeline potential to the EP was approximated by a current requirement test to be 500 mA. Zn anodes (L=150 cm, D=15 cm) are available. (Density of Zn = 7.14 g/cm3). Assume Zn efficiency is 90% and ρ=1000 Ω*cm.
From the previous example, each Zn anode produces 42 mA. Then, #anodes = 500/42 = 12 anodes.Total mass of anodes = 12*vol*density =12*3.14*D2*L/4*7.14 g/cm3= 2270 KgTotal charge available = efficiency*theoretical capacity*mass= 0.9*810*(A.hr/Kg)*2270 Kg= 1,593,540 (A*hr)Replacement period = 1,593,540 (A*hr)/0.5A= 189540 hr = 364 years
Dr. Z. Gasem ME 472-061
KFUPM46Sacrificial Anode CP System
Install 12 anodes evenly distributed along the pipeline. Keep each anode 30-100 cm away from the pipe. The system design life is indefinite. Monitoring Sacrificial CP
Measure the potential of the pipe and make sure it is -850mV Monitor the current flow from each anode at the junction box
Dr. Z. Gasem ME 472-061
KFUPM47Applications: buried tanks, pipelines, internal protection of heat
exchangers and vessels, ship hulls, marine structures
Aluminumalloy anode
AA-036348
Anodes
Dr. Z. Gasem ME 472-061
KFUPM48Impressed Current CP (ICCP) System
ICCP is used if: high current is required high resistance electrolyte
Dr. Z. Gasem ME 472-061
KFUPM49ICCP
Components of ICCP system
A transformer: to reduce the voltage from high to low voltageA rectifier to convert AC to DC A current distributor (junction box)Anodes with backfills
Dr. Z. Gasem ME 472-061
KFUPM50Reactions
The anode potential is set at high +ve potential and the following oxidations reactions become possible:
2H2O→ O2 + 4H++4e- (in water or in wet soil)2Cl-→Cl2 + 2e- (in salt or brackish water)C+2H2O→ CO2 + 4H++4e-
(in graphite anodes)Reactions at the cathode:
In aerated wet soilO2+2H2O+4e- ⇒ 4OH-
In aerated acidic solutionO2+4H+ + 4e- ⇒ 2H2O
In neutral seawater O2+2H2O+4e- ⇒ 4OH-
In de-aerated soil or water2H2O+2e- ⇒ 2OH- +H2
anodeCathode
Dr. Z. Gasem ME 472-061
KFUPM51Advantages and Disadvantages of
Impressed Current SystemsAdvantages
Higher Current and power outputsAdjustable protection levels (controlled current)Large areas of protectionLow number of anodesCan be used to protect poorly coated structure
DisadvantagesComplex equipment and installation costsHigher maintenance costsPossible interference problems with foreign structuresRisk of incorrect polarity connections
Dr. Z. Gasem ME 472-061
KFUPM52Components of ICCP
An external power sourceAC transmission linesA solar power system
Anodes are not necessarily more active than the structure to be protected
Two types of anodes inert or non-consumable anodes: platinized anodes (a few micrometers thick coating of platinum on Ti or Niobium), graphite, consumable anodes (scrap steel, high-Si Cr cast iron)
Dr. Z. Gasem ME 472-061
KFUPM53
Anode to coke resistance
Coke-to-earthResistance
SoilCokebreeze
Anodes for ICCP
Anodes are used with carbonaceous backfill called coke-breeze to:
increases the effective size of the anode lowers the anode-to-ground resistance.extends the life of the anode.
Anode
Dr. Z. Gasem ME 472-061
KFUPM54Anodes in ICCP
applicationsConsumption rate (Kg/(A*yr)
Material
Seawater, concrete,
8x10-6Platinized niobium (inert)
Marine, soil 1-0.25High Si-cast iron
Marine, soil 7-9Scrap steel
Soil,Potable water
0.1-1Graphite (inert)
= =8x10-6Platinized Ti (inert)
Dr. Z. Gasem ME 472-061
KFUPM55Applications
Ships (with coatings)Offshore platformsBuried pipelines (prefmethod)Oil well casingConcrete Structures (offshore bridges)
Dr. Z. Gasem ME 472-061
KFUPM56Buried pipelines
Dr. Z. Gasem ME 472-061
KFUPM57
Producing Zone
Remote Surface Anode Bed
Junction Box Rectifier
Perforations
Well Casing
Dr. Z. Gasem ME 472-061
KFUPM58ICCP Design
1. Evaluation of electrolyte resistivity2. Estimating the current requirement
Current requirement testCurrent requirements theoretical estimation
3. Selecting anode material and current distribution
Uniform current distribution Avoid interference (stray current)
4. Determine the anode bed ground resistance 5. Determine number of required anodes6. Select the power source capacity
Dr. Z. Gasem ME 472-061
KFUPM591. Electrolyte Resistivity Survey
Measure soil resistivity along the pipeline The data from a soil resistivity survey along a 6 km section of pipeline is shown below. The lowest effective soil resistivity points are the most favorable anode bed locations.
Dr. Z. Gasem ME 472-061
KFUPM602. Interruption Test for Bare Pipeline in Impressed
Current System
In impressed current system for bare structure, the applied current is high and IR drop can not be neglected. Thus, protection Criteria for bare pipeline must check I*RΩ effect.The protection criterion for bare steel pipeline uses interruption test where a negative (cathodic) change in potential of >300 mV must take place immediately after CP current is applied. potential
time
CP Power off
CP power on
300 mV
Dr. Z. Gasem ME 472-061
KFUPM613. Current distribution
Variation of electrolyte resistivity b/w anode and cathode (largest current flows along least resistant path)Defects in coatings: current concentrates at defects
Dr. Z. Gasem ME 472-061
KFUPM62Stray Currents
Stray Currents: currents flowing in the electrolyte from external sources other than the applied CP. Sources of stray currents:
Subway systemInterference with another CP systemWelding equipmentElectrical power transmission lines
Dr. Z. Gasem ME 472-061
KFUPM634. Number of Required
Anodes
N = number of impressed current anodesY = design life in yearsI = total current required in amperesC = anode consumption rate in kg/A-yrW = weight of a single anode in kg
N = Y*C*I/W
Dr. Z. Gasem ME 472-061
KFUPM645. Resistance calculation
Dwight’s equation for single vertical anode:
Ra = ρ/(2πLa)*(ln(8La/Da) -1)A group of vertical or horizontal anodes (buried 6 ft below ground):
Vertical anodes ( Rv = ρ*F/537)Each anode is 8-12 in in diameter and 10 ft in length
Horizontal anodes (RH = ρ*F/483)Each anode is 10 ft in length and 6 ft below surface
F is called adjusting factor (F=1 for single anode)
Dr. Z. Gasem ME 472-061
KFUPM65F : Adjusting Factor
Dr. Z. Gasem ME 472-061
KFUPM664. Power Source Selection
The size of the power source is determined by:
the amount of current required to protect the structure (I)the voltage required to force the current through the anode ground bed resistance (R)E=I*R
Dr. Z. Gasem ME 472-061
KFUPM67Example: Design for ICCP
Design an impressed current system to protect a buried pipeline coated with fusion bonded epoxy (FBE) using the following information:
Horizontal anodes 6 ft below ground with 20 ft spacing
Anode material: High silicon-cast iron ( C=0.5 Kg/(A*yr))
Anode dimensions with backfill: 25 cm dia. x 300cm, weight=50 Kg
Pipeline length: 500 m and 115 mm in diameter
the anode to soil resistance is 0.24 ohm
Neglect cable resisitivity.
Soil resistivity: 2,000 ohm-cm
Required current density is 0.2 mA/m2 for FBE.
Design life of 20 years
Dr. Z. Gasem ME 472-061
KFUPM68Example: Design for ICCP
Current required = surface area * current density= π d L *i= 3.14*0.115*500 *0.2 = 36.1 A
# anodes= Y*I*C/W = 20*36.1*0.5/50 = 7.2 anodes . Then use 8 anodes.To calculate the resistance:
RH = ρ*F/483 (for 8 horizontal anodes F=0.184)= 2000*0.184/483 = 0.76Ω
Total R= 0.76+0.24=1 ΩE = I*R=1*36.1 = 36.1 V Hence, use a DC power with a minimum current supply of 40 A and a minimum voltage of 40 V (1600 Watt rating).