![Page 1: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/1.jpg)
Levante Sistemas de Automatización y Control S.L.
Catálogos
www.lsa-control.com
Distribuidor oficial Bosch Rexroth, Indramat, Bosch y Aventics.
LSA Control S.L. - Bosch Rexroth Sales PartnerRonda Narciso Monturiol y Estarriol, 7-9Edificio TecnoParQ Planta 1ª Derecha, Oficina 14(Parque Tecnológico de Paterna)46980 Paterna (Valencia)Telf. (+34) 960 62 43 01 [email protected] www.lsa-control.com www.boschrexroth.es
![Page 2: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/2.jpg)
SYNAXDecentralized System for the
Synchronization of Machine Axes
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Firmware Version FWA-CLC*DP-SY*-05VRS
mannesmannRexroth
engineering
Indramat278042
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 3: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/3.jpg)
About this documentation SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
SYNAX Decentralized System for the Synchronization of Machine Axes
Firmware Versions Description
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
• Mappe 40-05V-EN / Register 9
• SY105E_V.doc
• Drawing number 209-0061-4340-01
This document is a supplement to the Applications Description: SYNAXDecentralized System for the Synchronization of Machine Axes (Version05VRS), doc. no.: DOK-SYNAX*-SY*-05VRS**-FKB1-EN-P.
The documentation describes the difference between SYNAX version05VRS and the previous SYNAX version 04VRS.
Document designation ofprevious editions
Status Comments
209-0061-4306-00 10.95 Version 02VRS
DOK-SYNAX*-SY*-03V10**-FRN1-EN-P 08.96 Version 03VRS
DOK-SYNAX*-SY*-04VRS**-FVN1-EN-P 02.97 Version 04VRS
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P 02.98 Version 05VRS
INDRAMAT GmbH, 1998
Copying this document, and giving it to others and the use orcommunication of the contents thereof without express authority areforbidden. Offenders are liable for the payment of damages. All rights arereserved in the event of the grant of a patent or the registration of a utilitymodel or design (DIN 34-1).
All rights are reserved with respect to the content of this documentationand the available of the product.
INDRAMAT GmbH • Bgm.-Dr.-Nebel-Str. 2 • D-97816 Lohr a. Main
Telefon 09352/40-0 • Tx 689421 • Fax 09352/40-4885
Dept. EAP, ESP (KST, TI)
This document is printed on paper bleached without the use of chlorine.
Title
Type of documentation
Document code
Internal file reference
The purpose of thedocumentation
Editing sequence
Copyright
Validity
Published by
Note
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 4: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/4.jpg)
SYNAX Contents I
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Contents
1 References 1-11.1 Product Family ..................................................................................................................................... 1-1
1.2 Referenced hardware .......................................................................................................................... 1-1
1.3 Referenced firmware............................................................................................................................ 1-2
1.4 Supplementary documentation ............................................................................................................ 1-3
1.5 EPROM types ...................................................................................................................................... 1-3
2 Firmware Version CLC*DP-SY*-05VRS 2-12.1 Release notes on CLC*DP-SY*-05V08................................................................................................ 2-1
2.2 EPROM Labelling CLC*DP-SY*-05V08............................................................................................... 2-1
2.3 Notes on replacing firmware ................................................................................................................ 2-1
2.4 New function ........................................................................................................................................ 2-3
Special Operating Mode "Relative Set-Up"................................................................................... 2-3
Additive Group Command Value................................................................................................... 2-3
CLC Emergency Reaction............................................................................................................. 2-3
Output of High Speed Cams ......................................................................................................... 2-3
Parameter Channel in Profibus-DP............................................................................................... 2-3
New C parameters ........................................................................................................................ 2-4
New A Parameters ........................................................................................................................ 2-4
New Inputs and Outputs................................................................................................................ 2-5
New Diagnostic Messages............................................................................................................ 2-5
2.5 Changed and Expanded Functions...................................................................................................... 2-6
Configuring the Operating Modes ................................................................................................. 2-6
Master Axis ................................................................................................................................... 2-6
Register Controller ........................................................................................................................ 2-7
Tension Control ............................................................................................................................. 2-9
Jog Function.................................................................................................................................. 2-9
I/O Logic........................................................................................................................................ 2-9
Analog Inputs ................................................................................................................................ 2-9
Serial Communications ................................................................................................................. 2-9
ARCNET Interface ........................................................................................................................ 2-9
Fieldbus Interface (Interbus, Profibus) ........................................................................................ 2-10
Terminal Function ....................................................................................................................... 2-11
2.6 Changed and Expanded Parameters, Outputs and Diagnoses......................................................... 2-12
Changed C Parameters .............................................................................................................. 2-12
Changed A Parameters............................................................................................................... 2-13
Changed diagnostics messages ................................................................................................. 2-14
2.7 Phaseout of Functions / Hardware..................................................................................................... 2-15
2.8 Faults Cleared.................................................................................................................................... 2-15
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 5: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/5.jpg)
II Contents SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Interfaces - General .................................................................................................................... 2-15
ARCNET Interface ...................................................................................................................... 2-15
Fieldbus Interface........................................................................................................................ 2-15
3964R Interface........................................................................................................................... 2-15
Dual Port RAM (CLC-P) .............................................................................................................. 2-15
3 SynTop Version SYNTOP-INB-03VRS 3-13.1 Release Notes of SYNTOP-INB-03V03............................................................................................... 3-1
3.2 CD Labelling SYNTOP-INB-03V03...................................................................................................... 3-1
3.3 Notes on Software Installation ............................................................................................................. 3-1
System Pre-Requisities................................................................................................................. 3-1
Guidelines on Software Installation............................................................................................... 3-1
3.4 New Functions ..................................................................................................................................... 3-2
Editing and Loading I/O Logic ....................................................................................................... 3-2
Load Base Parameters ................................................................................................................. 3-2
New Commissioning Dialogs ........................................................................................................ 3-2
New Diagnoses Dialogs ................................................................................................................ 3-3
3.5 Changed and Expanded Functions...................................................................................................... 3-3
Downwards Compatibility to SY*-03VRS...................................................................................... 3-3
Known Firmware ........................................................................................................................... 3-3
Online Help.................................................................................................................................... 3-4
Commissioning Dialogs................................................................................................................. 3-4
Parameter Expansion.................................................................................................................... 3-4
Setting Base Parameters .............................................................................................................. 3-4
Internal I/O Diagnoses .................................................................................................................. 3-4
3.6 Faults Cleared...................................................................................................................................... 3-4
Refreshing the Firmware Cache ................................................................................................... 3-4
Menu Item „Setting/Loading Base Parameters“ ............................................................................ 3-5
Dialog „Tension Controller Measurement Set-Up“ ........................................................................ 3-5
4 Glossary 4-1
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 6: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/6.jpg)
SYNAX References 1-1
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
1 References
1.1 Product Family
The firmware version description references the product family:
SYNAX Decentralized System for the Synchronization of Machine Axes
Current firmware version: FWA-CLC*DP-SY*-05VRS.
1.2 Referenced hardware
Permissible CLC hardware
• CLC-D
• CLC-P
Permissible CLC daughter boards
• DAK01.1M (ARCNet)
• DAQ02.1M (CLC link or/and ARCNet)
• DEA28.1M (Digital I/O)
• DEA29.1M (Digital I/O)
• DEA30.1M (Digital I/O)
• DPF05.1M (Profibus combi slave)
• DBS03.1M (Interbus slave)
• DBS04.1M (Interbus slave)
Permissible drives
Drives belonging to the families DIAX03, DIAX04 and ECODRIVE may beused. Drives of the DIAX01 and DIAX02 families are not supported.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 7: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/7.jpg)
1-2 References SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
1.3 Referenced firmware
Product: Product firmware(order designation):
Printed board firmware(EPROM labelling):
CLC P / CLC D & CCD FWA-CLC*DP-SY*-05VRS-MS FWC-CLC*DP-SY*-05VRS-MS
CLC D & CCD+ Interbus
FWA-CLC*DP-SS1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DBS3.1-CI1-02VRS-NN
CLC D & CCD+ Profibus
FWA-CLC*DP-SP1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DPF5.1-CP1-02VRS-NN
CLC D &drive family DIAX03
FWA-DIAX03-SY2-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DSM2.3-ELS-04VRS-MS
CLC D &drive family DIAX03
FWA-DIAX03-SY1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DSM2.3-ELS-05VRS-MS
drive family DIAX03 FWA-DIAX03-ELS-04VRS-MS FWC-DSM2.3-ELS-04VRS-MS
drive family DIAX03 FWA-DIAX03-ELS-05VRS-MS FWC-DSM2.3-ELS-05VRS-MS
CLC D & Profibusdrive family DIAX03
FWA-DIAX03-SP1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DPF5.1-CP1-02VRS-NNFWC-DSM2.3-ELS-05VRS-MS
CLC D & Interbusdrive family DIAX03
FWA-DIAX03-SS1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DPS3.1-CI1-02VRS-NNFWC-DSM2.3-ELS-05VRS-MS
CLC D &drive family DIAX04
FWA-DIAX04-SY1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-HSM1.1-ELS-05VRS-MS
drive family DIAX04 FWA-DIAX04-ELS-05VRS-MS FWC-HSM1.1-ELS-05VRS-MS
CLC D & Profibusdrive family DIAX04
FWA-DIAX04-SP1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DPF5.1-CP1-02VRS-NNFWC-HSM1.1-ELS-05VRS-MS
CLC D & Interbusdrive family DIAX04
FWA-DIAX04-SS1-05VRS-MS FWC-CLC*DP-SY*-05VRS-MSFWC-DPS3.1-CI1-02VRS-NNFWC-HSM1.1-ELS-05VRS-MS
Ecodrive FWA-ECODRV-SSE-02VRS-MSFWA-ECODRV-SSE-03VRS-MS
FWC-DKC2.1-SSE-02VRS-MSFWC-DKC2.1-SSE-03VRS-MS
User interfaceSYNTOP
SWA-SYNTOP-INB-03VRS-MS-CD600-COPY SWD-SYNTOP-INB-03VRS-MS-CD600
Fig. 1-1: Referenced firmware
Note: The software with suffix -COPY may be copied
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 8: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/8.jpg)
SYNAX References 1-3
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
1.4 Supplementary documentation
Order text: Title:
DOK-SYNAX*-SY*-05VRS**-FKB1-DE-P SYNAX - Functional Description
DOK-SYNAX*-SY*-05VRS**-PRJ1-DE-P SYNAX - Project Planning
DOK-SYNAX*-SY*-05VRS**-WAR1-DE-P SYNAX - Trouble Shooting Guide
DOK-SYNAX*-SY*-05VRS**-FVN1-DE-P SYNAX - Version notes
DOK-SYNAX*-SY*-05VRS**-40M1-DE-P SYNAX - Mappe 40-05V
DOK-SYNAX*-SY*-05VRS**-40M1-DE-D0600 General support for SYNAX - Version 05VRS
DOK-DIAX03-ELS-05VRS**-50M1-DE-P DIAX03 - Mappe 50-05V
DOK-DIAX03-ELS-05VRS**-50M1-DE-H1,44 General support for DIAX03 - Version 05VRS
DOK-ECODRV-SSE-03VRS**-57M1-DE-P ECODRIVE - Mappe 57-03V
DOK-ECODRV-SSE-03VRS**-57M1-DE-H1,44 General support for ECODRIVE - Version 03VRS
Fig. 1-2: Supplementary documentation
1.5 EPROM types
The following EPROM types may be used in conjunction with the CLCcontrol card:
Manufactured by Article code
AMD AM27C4096 -100DC
SGS-Thomson M27C4002-10F1
Fig. 1-3: EPROM types for use with the CLC
EPROM IC14 (Low)and IC15 (High)
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 9: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/9.jpg)
1-4 References SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 10: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/10.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-1
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
2 Firmware Version CLC*DP-SY*-05VRS
2.1 Release notes on CLC*DP-SY*-05V08
The SYNAX firmware version CLC*DP-SY*-05V08 was released
February 27, 1998
2.2 EPROM Labelling CLC*DP-SY*-05V08
2 7 2 6 8 4
LOW
FWC-CLC*DP-SY*-05V08-MS
9C92
2 7 2 6 8 4
HIGH
FWC-CLC*DP-SY*-05V08-MS
42CB
2.3 Notes on replacing firmware
The following points must be noted when replacing the firmware andperformed in the order as indicated:
• Check the CLC hardware version in parameter "CLC -Hardware Version" (C-0-0024)The CLC firmware must support this CLC hardware (see section"Referenced hardware").
• Secure the current parameter set of the machine inSAVE.ASCPrior to replacing the CLC firmware, all A and C parameters must bestored with the CLC terminal function "store parameters" or with "File","Store" in SynTop. This file must be named SAVE.ASC.
• Switch machine off, set jumper S2 and replace thefirmware of the CLCBy setting jumper S2, SynTop is forced to terminal X27 when poweringup.
Note the older position of the jumper.
EPROM IC14:
EPROM IC15:
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 11: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/11.jpg)
2-2 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
• Switch machine onCLC-D: After powering up, the CLC-D will boot up into parametrizationmode and then will display, due to invalid parameter, diagnosis 14"CLC parameter checksum error (see C-0-0068)". The drive withaddress 1 now displays P2. All others display the warning E4/10 "Drivenot scanned or address 0".
CLC-P: The CLC-P boots up to initialization mode only after powering.
• Connect PC to interface X27 and start SynTopSkip the possible error message from SynTop with ’ignore’.
• Switch machine into initialization modeVia SynTop, the CLC is switched into initialization mode (menu’extras’, ’phase changeover’, ’phase 0’, ’close’)
• Preset the parameters of the CLC with default valuesThe A and C parameters of the CLC are preset for all possible driveswith their default values:
Call up menu item ’File’, ’Load base parameters → CLC’ in SynTop.Load base parameters and then leave the menu with ’Close’
• Load SAVE.ASC back into CLCThe A and parameters are loaded back into the CLC via menu ’file’,’load’. Note here that ’all drives’ and ’A parameters’ or ’C parameters’are selected here.
• Re-translate I/O logic and loadThe I/O logic is re-translated via menu ’File’, ’I/O logic ...’ and thenloaded back into the CLC.
• Swith machine off, set jumperThe jumpers S1 and S2 are set as before.
Exception: If terminal function was on terminal X27 before, without aset jumper, then jumper S1 must now be set.
• Switching machine onThe CLC parameters are now valid for all drives. SYNAX boots up into"SYNAX - power up target mode" (C-0-0101).
The machine is now operable with the new firmware.
• Final activitiesSecure the new A and C parameters on the CLC.
• Checking the functionsAfter replacing the firmware, carefully check the functions of the newlyequipped machine.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 12: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/12.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-3
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
2.4 New function
Special Operating Mode "Relative Set-Up"In operating mode ’relative set-up’ an axis can be moved over a specifieddistance. The new operating mode is configured and activated as a"Special operation mode" (parameter A-0-0070, binary input _E:F#.23).The travel path is written into parameter "Setup mode relative - traveldistance" (A-0-0135) and made valid via the binary input "Relative positioncommand lock" (_E:F#.27).
Additive Group Command ValueIn modes ’Phase synchronization’ and ’Electronic cam’ the phase offsetbetween slave and master axis can be adjusted. The effective phaseoffset is calculated using "Position command offset" (A-0-0004) and thenewly introduced "Group parameter additive - command value" (A-0-0132) and is then transmitted to the drive as "Additive position commandvalue" (S-0-0048).
"Additive group parameter command value" can be distributed to up to 8drives via list "Group parameter additive - drive addresses" (A-0-0133).The individual "Group parameter additive - weighting" (A-0-0134) can beset, however.
CLC Emergency ReactionIn the event of a fatal error (fiber optic cable break, critical operatingsystem error from no. 4000), the CLC switches into initialization mode(P0).
It is possible to access both A and C parameters in this state. The PLCcan, for example, read diagnostics parameter C-0-0046.
Note: A renewed run up executes an internal reset on the CLC. As aresult, communications to the PLC could breakdown for ashort period.
Output of High Speed CamsHigh speed cams can now be output on the I/O cards DEA08 and DEA28as well as the DPRAM of a CLC P.
Parameter Channel in Profibus-DPIn Profibus applications exclusively using the Profibus DP protocol thefieldbus cannot execute bus parametrization (this applies to numerousPLC systems).
The Indramat-specific protocol expansion for the parameter channel inProfibus-DP generates the basic FMS services for the data exchangewithin the Profibus-DP protocol thus making bus parametrization possiblefor the fieldbus master.
Note: Special protocol expansions executed by the PNO for theProfibus DP protocol, necessitate special masters that are,however, presently only available for the Siemens’ PLCs. (DP-expansion E1 /V1).New Parameters, Outputs and Diagnostics
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 13: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/13.jpg)
2-4 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
New C parameters
ID no. Name of the parameter
C-0-0123 EAENET2 - group identification number
C-0-0124 Serial Communication - time out
C-0-0125 Fieldbus address
C-0-0126 Fieldbus: length of process data channel
C-0-0127 Fieldbus: object list of process data input
C-0-0128 Fieldbus: object list of process data output
C-0-0129 Fieldbus: control word
C-0-0130 Internal I/O: high speed cam switches outputs
C-0-0131 Fieldbus - multiplex size
C-0-0132 Fieldbus: start address of multiplex channel
C-0-0133 CLC - hardware status
C-0-0134 CLC - expansion bus status
C-0-0135 Command shutdown in flash-programming-mode
Fig. 2-1: New C parameters
New A Parameters
ID no. Name of the parameter
A-0-0009 Configuration idle mode / set up mode
A-0-0120 Register control - register deviation
A-0-0121 Register control - probe distance
A-0-0122 Indirect register control - positive control output limit
A-0-0123 Indirect register control - negative control output limit
A-0-0124 Cam shaft distance
A-0-0125 Register control - position command increments
A-0-0126 Master drive gear output revolutions
A-0-0127 Register control - max. register mark losses
A-0-0128 Register control- probe dead time compensation
A-0-0129 Register control - mark gating
A-0-0130 Process controller 1 - P-gain adaption operation point 1
A-0-0131 Process controller 1 - P-gain adaption operation point 2
A-0-0132 Group parameter additive - value
A-0-0133 Group parameter additive - drive addresses
A-0-0134 Group parameter additive - weighting
A-0-0135 Setup mode relative - travel distance
Fig. 2-2: New A parameters
List of new C parameters
List of new A parameters
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 14: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/14.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-5
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
New Inputs and Outputs
Designation Function
_E:F#.21 Best possible standstill with drive enable removed
_E:F#.27 Relative position command lock
_E:F#.35 Process controller command lock
_E:F#.36 Process controller preset 2
_E:T#.01
... _E:T#.32
External inputs of the "input/output interface" DEA08
Fig. 2-3: New inputs
Designation Function
_A:F#.35 Acknowledge process controller - command lock
_A:F#.36 Acknowledge process controller preset 2
_A:F#.37 Register controller - mark failure
_A:C01.08 Fieldbus real time channel active
_A:W#.01
... _A:W#.8
Drive cam 1
... drive cam 8
_A:K01.01
... _A:K01.32
High speed cam of the master axis
_A:T#.01
... _A:T#.24
External outputs of the "Input/output interface" DEA08
Fig. 2-4: New outputs
New Diagnostic Messages
C-0-0048Fault-number
C-0-0047 diagnostics text in the CLCsystem
C-0-0046diagn.info
Dis-play
Binaryoutput
Cancelvia
17 CLC SRAM defective 10000h = -- --
19 CLC hardware defective 10000h ≡ -- --
96 Fieldbus card - hardware failure 10000h 96 -- --
152 Process data are invalid(C-0-0129 / C-0-0128 / C-0-0127 / C-0-0126 /C-0-0131 / C-0-0132 and DBs)
10000h 15 _A:C01.01 --
153 Parameter channel is not possible(s. C-0-0126 and C-0-0129)
10000h 15 _A:C01.01 --
154 Multiplex channel is not possible(s. C-0-0126/C-0-0129/C-0-0132)
10000h 15 _A:C01.01 --
160 More than one register controller per axis notpossible
n = address 15 -- --
161 Winding axis must be in speed synchronization(A-0-0003, A-0-0025)
n = address 15 -- --
178 Tension controlled axis must be speed synch.(A-0-0003, A-0-0025, A-0-0087)
n = address 15 -- --
179 More than one tension controller per axis notpossible
n = address 15 -- --
New Inputs
New Outputs
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 15: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/15.jpg)
2-6 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
192 C-0-0013: PLC-interface not allowed on CLC Dand CLC P01
10000h 15 _A:C01.01 --
193 No different feedbacks selectable(s. A-0-0003/A-0-0009/A-0-0070)
n = address 15 -- --
232 A-0-0009: Drive does not support selected setup mode
n = address 15 _A:C01.01 --
233 Drive locked with password (see S-0-0267) n = address 15 -- --
234 Electr. Gear ratio not possible(s. S-0-0236/S-0-0237)
n = address 15 -- --
235 A-0-0107: Master drive gear not available(P-0-0156/P-0-0157)
n = address 15 -- --
236 Register control only possible with modulo axis(s. A-0-0001, A-0-0025)
n = address 15 -- --
237 Register controlled axis without synchronization(s. A-0-0003)
n = address 15 -- --
240 HS waypoints and I/O to DEA4.1 not possible(C-0-0013, C-0-0049, C-0-0036)
n = address 15
241 HS waypoints and I/O to DEA28.1 not possible(C-0-0013, C-0-0049)
10000h 15 -- --
242 C-0-0013: DEA4.1 and DEA8.1 simultaneouslynot possible
n = address 15 -- --
243 Drive does not support DEA8.1 card n = address 15 -- --
244 Combination of used functions not possible(realtime bits)
n = address 15 -- --
250 Target axis must be phase sync or cam axis(A-0-0133)
n = address 15 -- --
251 More than one group parameter per axis notpossible
n = address 15 -- --
Fig. 2-5: New diagnostics messages
2.5 Changed and Expanded Functions
Configuring the Operating ModesAuxiliary operating modes will no longer be configured in parameter"Synchronization mode" (A-0-0003). If a synchronization mode is nolonger needed (e.g., positioning axes) then entry 0x0000 0000 ("nosynchronization mode") is permissible.
For auxiliary modes set-up and idle, parameter "Configuration idle mode /setup mode" (A-0-0009) has been introduced.
Special modes such as "Relative set-up" are set in parameter A-0-0070.
Master Axis
Jerk limitJerk limit is now optionally active even with an emergency stop of thevirtual master axis. The limit is activated in "ELS master - control word"(C-0-0004, bit 8).
If C-0-0077 = 0 then the jerk limit is generally switched off (until now themaster axis did not runup with this setting.)
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 16: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/16.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-7
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Register Controller
Sensor DistanceThe distance between the sensor for detecting printing marks and themeasuring axis can now be larger than one format length. The distance isset in parameter "Register control - probe distance" (A-0-0121). Thecorrection is delayed by as many product cycles as there are formatsbetween the regulated axis and the sensor.
Sensor Deadtime CompensationThe delay times between the detection of the printing mark and the edgeof the measuring signal at sensor output result in a measuring error withposition detection at the measuring axis. The measring error results in aspeed-dependent register error. If the deadtime of the mark reader isentered into parameter "Register control - probe deadtime compensation"(A-0-0128), then the measuring error will be taken into account whengenerating the correction angle.
Masking Register MarksIf control is to take place only every nth mark on a web, then invalid markscan be masked off. It is set in parameter "Register control - mark gating"(A-0-0129) which marks are to be evaluated for the control.
Actual Value DisplayThe difference between position command and actual values can be readout of "Register control - register deviation" in degrees from parameterA-0-0120.
Indirect ControlThe output of an indirect register controller can be limited via parametersA-0-0121 and A-0-0122.
The output of an indirect controller can be frozen via binary input "Processcontroller pause".
Jogging the Position Command ValueThe position command value for the register controller can now bechanged with the CLC jog function.
By setting bit 21 in "Process control - control word" (A-0-0025) the joginputs are directed to the position command value (A-0-0084).
The position command value can be jogged if the drive enable is insynchronization mode and the register controller enabled. In all otheroperating modes, the affects of the jog inputs on the process variablesallocated to the activated modes remain as given.
Parameter "Register control - position command increments" (A-0-0125)has been newly introduced for the jog function.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 17: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/17.jpg)
2-8 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Setting the Position Command Value via Binary InputsThe position command values for the register control can be set with thehelp of the binary inputs "Process controller - command lock" (_E:F#.27).If the printing mark is under the mark reader, however, then by settingthis input, the current actual position value at the measuring axis is writteninto the position command value.
New Control VariablesThe choice of manipulated variables (A-0-0107) was expanded with thefollowing:
Control variables Effective in mode Controller
"Additive speed commandvalue" (S-0-0037)
speed synchronization indirect
"Fine adjustment - gearratio" (P-0-0083)
speed synchronization direct
"Cam shaft distance"(P-0-0093)
electronic cam direct, indirect
"Master axis gear outputrevolution" (P-0-0156)
speed synchronization,phase synchronization,electronic cam
direct, indirect
Fig. 2-6: New manipulated variables for register control
• Cam stroke:
The cam stroke is set via the new parameter "Cam shaft distance"(A-0-0124). Given an activated register controller, this preset value isaccounted for with the controller output.
• Master axis gear:
With drive firmware 05VRS a new master axis gear was introduced.The new gear function supports speed matching of synchronous axesand works in the three operating modes speed synchronization, phasesynchronization and electronic cam.
Parameter "Master axis gear output revolutions" (P-0-0156) can beselected as a manipulated variable for the register controller.Parameter "Master axis gear output revolutions" (A-0-0126) wasintroduced on the CLC for presetting.
Setting the Correction WindowIt is no longer necessary to note the rotational direction when setting thecorrection window for direct control. The angles for start and endcorrection (A-0-0085, A-0-0086) are always entered in a mathematicallypositive direction.
Connecting the Sensor
Note: As of drive firmware 05VRS the mark reader must beconnected to probe 1. Probe 2 is no longer available to theregister controller.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 18: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/18.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-9
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Tension Control
Controlling Several Tension AxesOne tension controller can control up to four axes. The addresses of thetension controlled axes are entered in parameter "Process control - driveaddresses" (A-0-0087).
Adaptive ControlTwo parameters have been introduced for the speed-dependent adaptionof the P-gain.
"Process controller 1 - Adapt P-gain operating point 1" (A-0-0130),
"Process controller 1 - Adapt P-gain operating point 2" (A-0-0131).
Setting the Command ValueThe command value for the tension controller can be set with binary input"Process controller - command lock" (_E:F#.27). The current actualtension control value (analog signal) is assumed as a tension commandvalue.
Jog Function"Jogging time constant" (C-0-0029) can be set to ’0’. A signal to a joginput thus effects, without delay, the selected process variable.
I/O LogicThe high speed cam of the master axis and the drive cam (dynamic camswitch group) can be processed in the I/O logic.
As of drive firmware version 05VRS plug-in module "input/outputinterface" DEA08 is supported.
Analog InputsAs of drive firmware 05VRS, the DRF plug-in module will be replaced by"Analog interface with incremantal encoder emulation" DAE02.1. The newconfiguration will automatically be detected by the CLC. Parameterrecords of running analogs with DRF modules can be assumed withoutchange.
Serial CommunicationsParameter "Communications interface - time out" (C-0-0124) wasintroduced to monitor communications via the serial interface. If the CLCinternal processing of a request takes longer than timeout permits, then aBUSY signal is generated.
ARCNET Interface
New Data BlocksThe concept of the data blocks for the ARCNET interface has beenexpanded:
• For the transmission of parameters, the configurable data blocks 109through 116 are now also available.
• Using the pre-defined data block 98, data transmission (with followingtelegram) can be terminated.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 19: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/19.jpg)
2-10 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Long Data PackageThe ARCNET interface of the CLC now also supports long data packagesof up to 508 data bytes to accomodate a command telegram.
Note: The CLC will continue to send all reaction telegrams in shortdata packages.
Data Request Processing TimeBy optimizing the output of a reaction telegram it is possible to shorten theprocessing time of a data request by up to 50 ms.
Fieldbus Interface (Interbus, Profibus)
Parameter Access via the Process Data ChannelThe cyclical parameter transmission in (real-time channel of the) processdata channel has been expanded to all SYNAX parameters. Supportedare:
• write-access to all SYNAX parameters (A, C, S and P parameters) inthe process data channel
• read-access to all drive parameters (S, P parameters) not configuredin the drive telegram (AT)
Note: The parameters cyclically transmitted via the fieldbus are nothandled internally by SYNAX over real-time channels. Thetransmission scenario is explained in the SYNAX FunctionalDescription.
Communications ChannelAcyclical communications via data exchange objects 5F70 - 5F73 wereadapted to the changed SIS protocol specification:
• The introduction of the new SYNAX specific SIS service 0x91 and0x9F means it is possible to transmit a single element of a listparameter.
• The bytes of the old SIS protocol have been adapted to the new SISprotocol head and some bits in some of these bytes have beenchanged.
Note: This change is not compatible with version SY*-04VRS!
Bus Parametrization via the CLCThe parametrization of a fieldbus can (e.g., in the case of a fieldbusmaster that does not support the communications channel) now use theCLC. The configuration method is hereby set in parameter C-0-0129. Forbus parametrization, parameters C-0-0125 through C-0-0128 and C-0-0131 and C-0-0132 are available.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 20: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/20.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-11
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Note: Bus parametrization via the bus master means that thefieldbus parameters (except for C-0-0129) are generally write-protected and only support diagnoses.
Automatic Reconfiguration of the FieldbusAfter changing parameters that effect the fieldbus interface, there is anautomatic triggering of a reconfiguration interrupt on the fieldbus card.This applies to:
• subsequential applications of a fieldbus interface in parameterC-0-0033
• reconfiguration of a fieldbus via fieldbus parameters of the CLC
The fieldbus slave then starts the initialization of the fieldbus interface onthe CLC and can, if necessary, assume the (new) bus parametrization ofthe CLC.
After such events where a phase jump in the SERCOS cycle can occur,there is also a reconfiguration interrupt on the fieldbus card. This stepsolely supports the re-establishment of a possibly violated synchronizationbetween the fieldbus card and the CLC. Such events can be:
• a reboot of the CLC (due to progression) after a SERCOS emergencyreaction
• a reboot of the CLC (due to progression) after an operating systemserror
• the switching of a DAQ in the CLC link to a link slave
Note: During the reconfiguration of the fieldbus interface,communications between master and slave is interrupted forabout six (6) seconds. Add another two (2) for a reboot!
Terminal FunctionThe new submenu ‘High speed cams’ in menu ‘Diagnosis’ displays theoutputs of the high-speed cam.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 21: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/21.jpg)
2-12 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
2.6 Changed and Expanded Parameters, Outputs andDiagnoses
Changed C Parameters
ID no. Name of the parameter
C-0-0004 ELS master - control word
C-0-0012 I/O - assignment - file info
C-0-0013 I/O - assignment of internal/external I/Os
C-0-0015 CLC identification number
C-0-0029 Jogging time constant
C-0-0033 Host communication - control word
C-0-0049 High speed cam switches - control word
C-0-0050 High speed cam switches - ON/OFF angle
C-0-0079 Configuration list data block 110
Fig. 2-7: Changed C parameters
C-0-0004 ELS master - control wordBit 8 has a new definition:
Bit 8 = 0: jerk limit of the virtual master axis with emergency stop notactive
Bit 8 = 1: jerk limit of the virtual master axis with emergency stop active
C-0-0012 I/O - assignment - file infoChange in parameter name from ‘ - reserved - ‘ in ‘I/O allocation -file information’.
This parameter contains a variable textstring with information about theVKL file:
• file name (with extension)
• date and time of the last change in the file
• selected hardware platform (CLC or PPC)
C-0-0013 I/O - assignment of internal/external I/OsThe header of the default allocations list between the words ‘Releasestatus’ and ‘Re-jump instruction’ has been expanded by
• the offset of OPCODE (starting with the actual length of the list)
• the default textstring for parameter C-0-0012 (‘I/O allocation . fileinformation’) :‘Empty I/O logic!’
C-0-0015 CLC identification numberParameter C-0-0015 is no longer write protected.
C-0-0029 Jogging time constantThe minimum input value has been changed from 100 ms to 0 ms.
List of changedC parameters
Specific changes in the Cparameters
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 22: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/22.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-13
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
C-0-0033 Host communication - control word
• The name of the parameter has been changed from ‘Serialcommunication - control word’ to ‘Host communication - control word’.
• Format bit (bit 7: Intel/Motorola) can be used to control the parallelinterface (CLC P).
C-0-0049 High speed cam switches - control wordConfiguration of the I/O unit has been expanded with bit 9:
Bit 9 Bit 8 E/A unit
0 1 DEA4
0 1 Dual Port RAM
1 0 DEA28 (new)
1 1 DEA8 (new)Fig. 2-8: E/A-Units for the high-speed cam
C-0-0050 High speed cam switches - ON/OFF angleThe number of programmed cams is reduced from 50 to 32.
C-0-0079 Configuration list data block 110The default configuration list of data block 110 was changed from the‘empty list’ to a list with a single element ‘CLC:C-0-0066’.
Changed A Parameters
ID no. Name of parameter
A-0-0003 Synchronization mode
A-0-0025 Process control - control word
A-0-0107 Register control - target parameter selection
Fig. 2-9: Changed A parameters
A-0-0003 Synchronization modeA new parameter (A-0-0009) has been introduced for the configuration ofauxiliary modes 'Idle' and 'Absolute set-up'. Bits 24 and 26 no longer havea function and must be set to '0'.
Bit 17 is no longer evaluated; set it to '0'.
A-0-0025 Process control - control wordThe setting possibilities for the tension and register controllers have beenexpanded.
Tension controller:
Bit 3 = 0: P-gain as per parameter A-0-0030
Bit 3 = 1: speed-dependent adaption of P-gain
Bit 4 = 0: tension controller affects own drive address
Bit 4 = 1: tension controller affects several tension axes
List of changedA parameters
Specific changes in the Aparameters
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 23: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/23.jpg)
2-14 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Register controller:
Bit 21 = 0: position command value A-0-0084 not jogged
Bit 21 = 1: jog inputs effect A-0-0084
A-0-0107 Register control - target parameter selectionNew variables with direct correction:
Bit 1 Bit 0 Variables
0 1 fine adjustment of gear ratio (P-0-0083)
1 1 master axis gear output revolutions (P-0-0157)Fig. 2-10: New variables with direct correction
New variables with indirect correction:
Bit 9 Bit 8 Variables
0 1 additive speed command value (S-0-0037)
1 1 master axis gear output revolutions (P-0-0157)Fig. 2-11: New variables with indirect correction
Changed diagnostics messages
C-0-0048faultnumber
C-0-0047 diagnotics text in the CLCsystem
C-0-0046diagn.Info
Dis-play
binaryoutput
cancelvia
01 "SERCOS interface - ring break" 10000h 01 _A:C01.01 --
05 "SERCOS interface - double drive telegramfailure"
n = address 05 _A:C01.01 --
40 "CLC link - ring break (primary ring)" 10000h 40 _A:C01.04
_A:C01.05
_E:C01.04
41 This diagnostic message has been dropped! -- 41 -- --
42 "CLC link - master position fault (MDT) " 10000h 42 _A:C01.04 _E:C01.04
43 "CLC link - master position fault (AT)" n = address 43 _A:C01.04 _E:C01.04
151 "Non-supported firmware version of theinterface board"
10000h 33 _A:C01.03 --
182 "C-0-0013: Synchronization mode notpermissible (A-0-0003)"
n = address 15 _A:C01.01 --
184 "C-0-0013: Idle mode not permissible(see A-0-0009)"
n = address 15 _A:C01.01 --
185 "C-0-0013: Set-up mode not permissible (seeA-0-0009)"
n = address 15 _A:C01.01 --
190 "CLC link - other link master already active" 10000h 15 _A:C01.01 --
198 "Special mode only with CLC P possible(A-0-0070/A-0-0071/A-0-0072/A-0-0073)"
n = address 15 _A:C01.01 --
221 "Port A (X27) multiple assigned(C-0-0011/C-0-0033/C-0-0104/Jumper)"
10000h 15 _A:C01.01 --
222 "Port B (X28) multiple assigned(C-0-0011/C-0-0033/C-0-0104/Jumper)"
10000h 15 _A:C01.01 --
Fig. 2-12: Changed diagnostics messages
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 24: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/24.jpg)
SYNAX Firmware Version CLC*DP-SY*-05VRS 2-15
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
2.7 Phaseout of Functions / Hardware
- none -
2.8 Faults Cleared
Interfaces - GeneralGlobally for all interfaces (serial and parallel), three errors have beencleared.
• After an internal transmission error a serial interface can no longersporadically access parameters.
• Unallowable A/C parameters and invalid axes addresses in theconfiguration list of the data blocks sporadically generated BSF 4002(address bus error).
• With R/W access, after error code "ID no. not available", an internaldata transmission is started. This generates a second reactionaffecting the same command telegram and also possiblemisinformation.
ARCNET InterfaceTwo errors were cleared that affected the ARCNET interface.
• When moving from the ARCNET interface to another, BSF 5403sporadically occurred.
• If phase progression was activated while the SERCOS ring wasinterruped, then the CLC D remained in an infinite loop specifyingphase 0 until the SERCOS ring could be closed again.During this time (there are no limits) the ARCNET interface remainedblocked. Thus, no A/C parameters could be either write or readaccessed.
Fieldbus InterfaceHigh and low bytes were transposed in the I/O data of the fieldbusinterface.
3964R InterfaceThe attempt to write a list into a long list during internal transmissionmeant that the CLC-D sporadically generated an error in the sequencefrom normal and following telegrams (synchronization error 2) eventhough the master maintains the correct order.
Dual Port RAM (CLC-P)An incorrect phase changeover due to a global error (e.g., minimum /maximum value violation) meant that the CLC generated a local transitionerror.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 25: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/25.jpg)
2-16 Firmware Version CLC*DP-SY*-05VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 26: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/26.jpg)
SYNAX SynTop Version SYNTOP-INB-03VRS 3-1
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
3 SynTop Version SYNTOP-INB-03VRS
3.1 Release Notes of SYNTOP-INB-03V03
The SynTop software version SWA-SYNTOP-INB-03V03-MS-CD600-COPY was released on
February 27, 1998.
3.2 CD Labelling SYNTOP-INB-03V03
SynTop for MS-WindowsUser interface for SYNAXInstallation with d.\Sytp3v03\Disk1\setup
Type: SWD-SYNTOP-INB-03V03-MS-CD600Serial number:
Part no.: 277979 Date: 27.02.98
Fig. 3-1: CD-ROM labelling SYNTOP-INB-03V03
3.3 Notes on Software Installation
System Pre-RequisitiesSynTop can be operated with MS-Windows 3.1, Windows 95 andWindows NT and makes the following hardware demands of the PCused:
• 80486 processor or higher
• at least 8 MB main memory
• at least 5 MB available hard drive memory
• a free serial RS232 interface (only with serial communications)
Guidelines on Software InstallationPrior to installing the software, note the following points:
• Release documentation must be completely read through
• and ensure that the above referenced hardware is at hand
Note: If SynTop is to be installed on a PC on which an older SynTopversion is already installed, then the older version will remainintact. The version number is in the directory of the installationprogram. The icon is in the program group.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 27: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/27.jpg)
3-2 SynTop Version SYNTOP-INB-03VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Any already existing parameter files (in subdirectories "PARAM") shouldbe copied into the new directory.
If an older SynTop version is to be removed from the hard drive, then itsuffices to erase the directory in which the relevant "syntop.exe" is found.This also applies to the icon in the programm group.
3.4 New Functions
Editing and Loading I/O LogicMenu item "I/O logic" is in menu „File“. Using the I/O logic dialog, it ispossible to generate, translate and load different text files. Text fileexamples for the I/O logics are supplied for DEA4, DEA8, DEA28,fieldbus and other external communications.
In menu "Options" there is also the menu item „VKL editor“. The editorwhich the user prefers can be set here.
Load Base ParametersMenu item "Load base parameters" is in menu „File“. It is possible to loadthe base parameters for the CLC and for each drive separately using thecorresponding dialogs.
New Commissioning Dialogs
FieldbussesParameters relevant to the fieldbusses „Profibus“ and „Interbus-S“ can beset in the commissioning diaglogues (only in connection with SYNAX05VRS). Menu "Parameter", menu item „CLC (Host) communication“.Dialog “Fieldbusses - Fieldbus settings“, „Fieldbusses - Fieldbus processdata channel“, „Fieldbusses - data blocks CLC -> bus“ and „Fieldbusses -data block bus -> CLC“.
Data BlocksThe parameters relevant to protocols 3964R and ARCNet can be set inthe commissioning dialogs (only in connection with SYNAX 05VRS).menu "Parameter", menu item „CLC (host) communication“. Dialogs“Data blocks“.
High-Speed Cam Switch GroupThe expanded high-speed cam switch group of the master axis of SYNAX05VRS can be parametrized using buttons in menu „Parameter“, menuitem "Select master axis".
Error ReactionThe parameters relevant to the error reactions of the drive can be set inthe commissioning dialogs. Menu "Parameter", menu item „Errorreaction“. Dialogs „Error reaction - drives“ and Dialog „Error reaction -Power supply module“.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 28: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/28.jpg)
SYNAX SynTop Version SYNTOP-INB-03VRS 3-3
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Group Command ValuesThe parameters relevant to the group command values of SYNAX 05VRScan be set in the commissioning dialog. Menu „Parameter“, menu item„Expanded SYNAX functions - group command value“. Dialog “Groupcommand values".
Register ControllerThe parameters relevant to the register controller of SYNAX 05VRS canbe set in the commissioning dialogs. Menu "Parameter", menu item„Expanded SYNAX functions register controller“. Dialogs „Basic settings“,„Read marks“, „Controlled axes“ and „Settings“.
Tension ControllerThe parameters relevant to the tension controller of SYNAX 05VRS canbe set in the commissioning dialogs. Menu "Parameter", menu item„Expanded SYNAX functions tension controller“. Dialogs „Basic settings“and „Block diagram“.
New Diagnoses Dialogs
High-Speed Cam Switch GroupThe internal inputs/outputs of the high-speed cam switch group aresupported in menu "Extras", menu item "Diagnoses internal I/O high-Speed cam switch group".
3.5 Changed and Expanded Functions
Downwards Compatibility to SY*-03VRSAs is presently the case, SynTop 03VRS can be used to parametrizeSYNAX firmware versions 03 and 04. What has been added is thesupport capabilities for SYNAX firmware version 05VRS. SynTopautomatically recognizes on its own which firmware is given and thenbranches into the relevant dialogs.
This means that for all SYNAX firmwares only one SynTop is needed.
Known Firmware
New:SynTop knows drive firmware DIAX03/04-ELS-05VRS.
If the user wants to open a dialog window of an unknown firmwareversion, then it is differentiated as to whether it is a completely unknownfirmware type or an unknown firmware version of a known firmwarefamily. In the former case, SynTop branches, after positivelyacknowledging the message, into the commissioning dialog of firmwareversion DIAX03/04-ELS-05VRS. In the latter case, it goes into thecommissioning dialog of the given firmware family.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 29: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/29.jpg)
3-4 SynTop Version SYNTOP-INB-03VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Online HelpNo online help is supplied to the drives and to SYNAX with SynTop. Thepresently available helps for the drive (DIAX03-ELS-04VRS, DIAX03-ELS-05VRS and ECODRIVE-SSE-03VRS) and SYNAX 04VRS as well asSYNAX 05VRS can be installed separately and are then detected andsupported by SynTop.
Commissioning Dialogs
Menu item „CLC (host) communication"This menu item was expanded. Not only can basic settings now beperformed, but if SYNAX 05VRS is used, then the fieldbusses („Profibus“and „Interbus-S“) and the data blocks of ARCNet and 3964R protocolscan be parametrized.
If a CLC-P is used, then dialog „CLC (host) communication - basicsettings“ can be used to set the data formats for communications via theDP-RAM.
Parameter ExpansionDialog "Error reaction - drive" was expanded with parameters "Velocityramp 1" and "Command Value smoothing time constant" for drivefirmware DIAX03/04-ELS-04VRS.
Setting Base ParametersMenu item „Set base parameters“ was replaced with menu item „Loadbase parameters“ and moved into menu „File“. It is also possible to loadbase parameters into specific dialogs.
Internal I/O DiagnosesThe diagnosis dialogs now support all diagnosis messages of SYNAX05VRS as well.
3.6 Faults Cleared
Refreshing the Firmware CacheThe firmware cache was not refreshed during an offline setting of SynTopand renewed online going. As a result, incorrect dialogs were displayedafter the drive firmware was replaced in SynTop offline mode followed byonline going.
This error has been cleared.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 30: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/30.jpg)
SYNAX SynTop Version SYNTOP-INB-03VRS 3-5
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Menu Item „Setting/Loading Base Parameters“During an offline setting of SynTop and a renewed online going, menuitem „Set or load base parameters“ was no longer displayed.
This error has been cleared.
Dialog „Tension Controller Measurement Set-Up“It was not possible to select measurement in front of or behind the pullroll.
This error has been cleared.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 31: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/31.jpg)
3-6 SynTop Version SYNTOP-INB-03VRS SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 32: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/32.jpg)
SYNAX Glossary 4-1
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
4 Glossary
1MB
AC kit motor with water cooling for integration in spindles (inductanceprinciples).
2AD
AC motors in power range of approx. 3.5 - 93 KW (inductance principle).
Absolute encoder
Encoders that supply an absolute position over several rotations (e.g.,4096).
ARCNet
Serial communication system (coaxial line).If used with printing machines, for example.
CCD
Housing for CLC D + daughter boards
CLC
Families of control cards with SERCOS interface. Available are CLC Pand CLC D. Various software packages are available (here SYNAX).
CLC link
With the help of a SERCOS interface ring, up to 32 CLC D controls canbe connected. Master axis positions are synchronously distributed to allCLC D’s for this purpose.
CLC D02
Plugin control for DIAX03 drives and CCD box.
CLC D03
Plugin control for CCD box with external battery (requires two slots).
CLC P01
PC plugin control with ISA bus.
CLC P02
PC plugin control with PC/104 bus.
DAG
SSI- EnDat encoder interface
DAQ
CLC link and/or ARCNet connection - CLC D daughter board.
DBS
INTERBUS-S slave connection - CLC D daughter board.
DEA
Digital 24V I/Os- CLC D daughter board or plugin module for digitaldrives.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 33: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/33.jpg)
4-2 Glossary SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
DFF
High resolution master axis encoder interface - plugin module for digitaldrives.
DIAX03
Controller family with an output width of 1 ... 100kW. (DDS02.2 /DDS03.2 / DKR02.1 / DKR03.1 / DKR04.1)
DIAX03 controller
Controller with uniform functions and a output band width of 1... 100kW.(DDS02.2 / DDS03.2 / DKR02.1 / DKR03.1 / DKR04.1)
DLF
High resolution sinusoidal encoder interface - plugin module for digitaldrives.
DPF
Profibus slave connetion - CLC daughter board.
DRF
Analog input interface - plugin module for digital drives.
DSA
Master axis position with SSI signals - plugin module for digital drives.
DSS
SERCOS interface - plugin module for digital drives.
DZF
High resolution gear/tooth interface - plugin module for digital drives.
GDS
Master axis encoder.
I/O logicSimply logic with e.g. AND, OR, NOT allocations with which simply I/Oallocations are executed.The I/O logic is generated as a text file and translated. The results of thistranslation procedure are loaded into the CLC D. A return to the original isnot possible.
LAF
AC linear motor - flat construction (inductance principle).
LAR
AC linear motor - roand construction (inductance principle).
LSF
AC linear motor - flat construction (synchronous principle)
LWL
Fiber optic cable, e.g., for SERCOS interface
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 34: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/34.jpg)
SYNAX Glossary 4-3
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Master axis encoder
The master axis encoder is a high resolution digital path scale systemwith 1048580 (=2^20) increments. This encoder is absolute over onerevolution.
MBW
AC mounting motor with hollow shaft for printing cylinders (inductanceprinciple).
MDD
AC motor with digital servo feedback synchronous principle)
MKD
AC motor with resolver feedback (synchronous principle)
Multi-Turn
Encoder, that supplies an absolute position over several revolutions (e.g.4096).
Select lists
Documentation used to determine, for a specific application, a specificmotor/controller combination.
SERCOS interface
Internationally standardized digital interface (IEC1491) forcommunications between control and drives in numerically controlleddrives.
Single-Turn
Encoder, that supplies an absolute position over a single revolution.
SSI
Synchronous serial interface. Interface for encoder systems with serialtransmissions of digital actual values.
SYNAX
Decentralized System for the Synchronization of Machine Axes, made upof SYNAX firmware, SynTop software, CLC control, DIAX03 andECODRIVE drives.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 35: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/35.jpg)
4-4 Glossary SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 36: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/36.jpg)
SYNAX Directory of Customer Service Locations
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Directory of Customer Service LocationsGermany
Sales Region Central
INDRAMAT GmbHD-97816 Lohr am MainBgm.-Dr.-Nebel-Str. 2
Telefon: 09352/40-4817Telefax: 09352/40-4989
Sales Region East
INDRAMAT GmbHD-09120 ChemnitzBeckerstraße 31
Telefon: 0371/3555-0Telefax: 0371/3555-230
Sales Region West
INDRAMAT GmbHD-40880 RatingenHarkortstraße 25
Telefon: 02102/4318-0Telefax: 02102/41315
Sales Region North
INDRAMAT GmbHD-22525 HamburgFährhausstraße 11
Telefon: 040/853157-0Telefax: 040/853157-15
Sales Region South
INDRAMAT GmbHD-80339 MünchenRidlerstraße 75
Telefon: 089/540138-30Telefax: 089/540138-10
Sales Region Southwest
INDRAMAT GmbHD-71229 LeonbergBöblinger Straße 25
Telefon: 07152/972-6Telefax: 07152/972-727
INDRAMAT Service-Hotline
INDRAMAT GmbHTelefon: D-0172/660 040 6
-or-
Telefon: D-0171/333 882 6
Customer service locations in Germany
EuropeAustria
G.L.Rexroth Ges.m.b.H.Geschäftsbereich INDRAMATHägelingasse 3A-1140 Wien
Telefon: +43 1/985 25 40-400Telefax:+43 1/985 25 40-93
Austria
G.L.Rexroth Ges.m.b.H.Geschäftsbereich INDRAMATRandlstraße 14A-4061 Pasching
Telefon: +43 7229/644 01-36Telefax: +43 7229/644 01-80
Belgium
Mannesmann Rexroth N.V.-S.A.Geschäftsbereich INDRAMATIndustrielaan 8B-1740 Ternat
Telefon: +32 2/582 31 80Telefax: +32 2/582 43 10
Denmark
BEC ASZinkvej 6DK-8900 Randers
Telefon: +45 87/11 90 60Telefax: +45 87/11 90 61
England
Mannesmann Rexroth Ltd.INDRAMAT DivisionBroadway Lane, South CerneyCirencester, Glos GL7 5UH
Telefon: +44 1285/86 30 00Telefax: +44 1285/86 30 03
Finnland
Rexroth Mecman OYRiihimiehentie 3SF-01720 Vantaa
Telefon: +358 9/84 91 11Telefax: +358 9/84 63 87
France
Rexroth - Sigma S.A.Division INDRAMATParc des Barbanniers 4,Place du VillageF-92632 Gennevilliers Cedex
Telefon: +33 1/41 47 54 30Telefax: +33 1/47 94 69 41
France
Rexroth - Sigma S.A.Division INDRAMAT17, Loree du GolfF-69380 Dommartin
Telefon: +33 4/78 43 56 58Telefax: +33 4/78 43 59 05
France
Rexroth - Sigma S.A.Division INDRAMAT270, Avenue de lardenneF-31100 Toulouse
Telefon: +33 5/61 49 95 19Telefax: +33 5/61 31 00 41
Italy
Rexroth S.p.A.Divisione INDRAMATVia G. Di Vittoria, 1I-20063 Cernusco S/N.MI
Telefon: +39 2/923 65-270Telex: 331695Telefax: +39 2/92 36 55 12
Italy
Rexroth S.p.A. DivisioneINDRAMATVia Borgomanero, 11I-10145 Torino
Telefon: +39 11/771 22 30Telefax: +39 11/771 01 90
Netherlands
Hydraudyne Hydrauliek B.V.Kruisbroeksestraat 1aP.O. Box 32NL-5280 AA Boxtel
Telefon: +31 41 16/519 51Telefax: +31 41 16/514 83
Spain
Rexroth S.A.Centro Industrial SantiagoObradors s/nE-08130 Santa Perpetua deMogoda (Barcelona)
Telefon: +34 3/7 47 94 00Telefax: +34 3/7 47 94 01
Spain
Goimendi S.A.División IndramatJolastokieta (Herrera)Apartado 11 37San Sebastion, 20017
Telefon: +34 43/40 01 63Telex: 361 72Telefax: +34 43/39 93 95
Sweden
AB Rexroth MecmanINDRAMAT DivisionVaruvägen 7S-125 81 Stockholm
Telefon: +46 8/727 92 00Telefax: +46 8/64 73 277
Switzerland
Rexroth SADépartement INDRAMATChemin de l`Ecole 6CH-1036 Sullens
Telefon:+41 21/731 43 77Telefax: +41 21/731 46 78
Switzerland
Rexroth AGGeschäftsbereich INDRAMATGewerbestraße 3CH-8500 Frauenfeld
Telefon: +41 52/720 21 00Telefax: +41 52/720 21 11
Russia
Tschudnenko E.B.Arsenia 22153000 IvanovoRußland
Telefon: +7 93/22 39 633
European customer service locations excluding Germany
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 37: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/37.jpg)
Directory of Customer Service Locations SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Outside of EuropeArgentina
Mannesmann Rexroth S.A.I.C.Division INDRAMATAcassusso 48 41/71605 Munro (Buenos Aires)Argentina
Telefon: +54 1/756 01 40 +54 1/756 02 40Telex: 262 66 rexro arTelefax: +54 1/756 01 36
Argentina
NakaseAsesoramiento TecnicoDiaz Velez 29291636 Olivos(Provincia de Buenos Aires)ArgentinaArgentina
Telefon +54 1/790 52 30
Australia
Australian Industrial MachineryServices Pty. Ltd.Unit ¾5 Horne STCampbellfield VIC 2061Australia
Telefon: +61 3/93 59 0228Telefax: +61 3/93 59 02886
Brazil
Mannesmann Rexroth AutomaçãoLtda.Divisão INDRAMATRua Georg Rexroth, 609Vila Padre AnchietaBR-09.951-250 Diadema-SPCaixa Postal 377BR-09.901-970 Diadema-SP
Telefon: +55 11/745 90 65 +55 11/745 90 70Telefax: +55 11/745 90 50
Canada
Basic Technologies CorporationBurlington Division3426 Mainway DriveBurlington, OntarioCanada L7M 1A8
Telefon: +1 905/335-55 11Telefax: +1 905/335-41 84
China
Rexroth (China) Ltd.Shanghai OfficeRoom 206Shanghai Intern. Trade Centre2200 Yanan Xi LuShanghai 200335P.R. China
Telefon: +86 21/627 55 333Telefax: +86 21/627 55 666
China
Rexroth (China) Ltd.Shanghai Parts & Service Centre199 Wu Cao Road, Hua CaoMinhang DistrictShanghai 201 103P.R. China
Telefon: +86 21/622 00 058Telefax: +86 21/622 00 068
China
Rexroth (China) Ltd.1430 China World Trade Centre1, Jianguomenwai AvenueBeijing 100004P.R. China
Telefon: +86 10/50 50 380Telefax: +86 10/50 50 379
China
Rexroth (China) Ltd.A-5F., 123 Lian Shan StreetSha He Kou DistrictDalian 116 023P.R. China
Telefon: +86 411/46 78 930Telefax: +86 411/46 78 932
Hongkong
Rexroth (China) Ltd.19 Cheung Shun Street1st Floor, Cheung Sha Wan,Kowloon, Honkong
Telefon: +852 2741 13 51/-54 and +852 741 14 30Telex: 3346 17 GL REX HXTelefax: +852 786 40 19 +852 786 07 33
India
Mannesmann Rexroth (India) Ltd.INDRAMAT DivisionPlot. 96, Phase IIIPeenya Industrial AreaBangalore - 560058
Telefon: +91 80/839 21 01 +91 80/839 73 74Telex: 845 5028 RexBTelefax: +91 80/839 43 45
Japan
Rexroth Co., Ltd.INDRAMAT DivisionI.R. BuildingNakamachidai 4-26-44Tsuzuki-ku, Yokohama 226Japan
Telefon: +81 45/942-72 10Telefax: +81 45/942-03 41
Korea
Rexroth-Seki Co Ltd.1500-12 Da-Dae-DongSaha-Gu, Pusan, 604-050
Telefon: +82 51/264 90 01Telefax: +82 51/264 90 10
Korea
Seo Chang Corporation Ltd.Room 903, Jeail Building44-35 Yoido-DongYoungdeungpo-KuSeoul, Korea
Telefon: +82 2/780-82 07 ~9Telefax: +82 2/784-54 08
Mexico
Motorización yDiseño de Controles, S.A. de C.V.Av. Dr. Gustavo Baz No. 288Col. Parque Industrial la IomaApartado Postal No. 31854060 TlalnepantlaEstado de Mexico
Telefon: +52 /397 86 44Telefax: +52 /398 98 88
USA
Rexroth CorporationINDRAMAT Division5150 Prairie Stone ParkwayHoffman Estates, Illinois 60192
Telefon: +1 847/645-36 00Telefax: +1 847/645-62 01
USA
Rexroth CorporationINDRAMAT Division2110 Austin AvenueRochester Hills, Michigan 48309
Telefon: +1 810/853-82 90Telefax: +1 810/853-82 90
USA
Rexroth CorporationINDRAMAT DivisionNortheastern Sales Office7 Columbia Blvd.Peabody, MA 019660
Telefon: +1 508/531-25 74Telefax: +1 508/531-2574
USA
Rexroth CorporationINDRAMAT DivisionSoutheastern Sales Office3625 Swiftwater Park DriveSuwanee, GA 30174
Telefon: +1 770/932 3200Telefax: +1 770/932-1903
Customer service locations outside of Europe
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 38: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/38.jpg)
SYNAX
DOK-SYNAX*-SY*-05VRS**-FVN1-EN-P
Notes
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
![Page 39: Catálogos Levante Sistemas de Automatización y …...By setting jumper S2, SynTop is forced to terminal X27 when powering up. Note the older position of the jumper. EPROM IC14: EPROM](https://reader033.vdocuments.net/reader033/viewer/2022060409/5f1010527e708231d4474420/html5/thumbnails/39.jpg)
IndramatLSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01