caution installation & maintenance manual digital flow

3
Installation & Maintenance Manual Digital Flow Switch PFMB7201/7501/7102/7202 PFMB7-TFQ04-A 2 Summary of Product parts A H G D E B D F IN C OUT IN Warning Do not disassemble, modify (including changing the printed circuit board) or repair. An injury or failure can result. Do not operate the product outside of the specifications. Do not use for flammable or harmful fluids. Fire, malfunction, or damage to the product can result. Verify the specifications before use. Do not operate in an atmosphere containing flammable, explosive or corrosive gas. Fire, explosion or corrosion can result. This product is not designed to be explosion proof. Do not use the product for flammable fluid. Fire or explosion can result. Only air and N2 are applicable. Do not use the product in a place where static electricity is a problem. Otherwise it can cause failure or malfunction of the system. If using the product in an interlocking circuit: •Provide a double interlocking system, for example a mechanical system. •Check the product regularly for proper operation. Otherwise malfunction can result, causing an accident. The following instructions must be followed during maintenance: •Turn off the power supply. •Stop the air supply, exhaust the residual pressure and verify that the air is released before performing maintenance work. Otherwise an injury can result. Caution Display 1 Element Description See below. Connector Lock ring 2 Piping port A B G D Through hole F Flow adjustment valve 2 H Body E Lead wire with connector C 2 Summary of Product parts (Continued) Mounting •Never mount the product in a place where it will be used as a mechanical support. •Mount the product so that the fluid flows in the direction indicated by the arrow on the side of the body. 1 Safety Instructions This manual contains essential information for the protection of users and others from possible injury and/or equipment damage. •Read this manual before using the product, to ensure correct handling, and read the manuals of related apparatus before use. •Keep this manual in a safe place for future reference. •These instructions indicate the level of potential hazard by label of "Caution", "Warning" or "Danger", followed by important safety information which must be carefully followed. •To ensure safety of personnel and equipment the safety instructions in this manual and the product catalogue must be observed, along with other relevant safety practices. CAUTION indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. Caution Warning Danger WARNING indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury. DANGER indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury. This product is class A equipment that is intended for use in an industrial environment. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbances. Do not touch the terminals and connectors while the power is on. Otherwise electric shock, malfunction or damage to the product can result. After maintenance is complete, perform appropriate functional inspections and leak tests. Stop operation if the equipment does not function properly or there is a leakage of fluid. When leakage occurs from parts other than the piping, the product might be faulty. Disconnect the power supply and stop the fluid supply. Do not apply fluid under leaking conditions. Safety cannot be assured in the case of unexpected malfunction. For piping connections. Connected to the fluid inlet at IN and to the fluid outlet at OUT. The body of the product. Lead wire for power supply and outputs. 1: A protective tape is affixed to the display. Please remove it before use. 2: The table lists the parts when a flow adjusting valve is included. Body Used to lock the flow adjustment valve. Orifice mechanism to adjust the flow rate. Connector for electrical connections. Used to mount the product on a DIN rail or directly to a panel. Panel mounting (Only PFMB7201) •Refer to the diagram and table below for mounting details. •Refer to the operation manual on the SMC website (URL http://www.smcworld.com ) for panel thickness and panel cut-out dimensions. Panel Insert 1 2 Bracket NOTE The direct current power supply used should be UL approved as follows. Circuit (class 2) of maximum 30 Vrms (42.4 V peak) or less, with UL1310 class 2 power supply unit or UL1585 class 2 transformer. The product is a UL approved product only if it has a mark on the body. Bracket mounting (PFMB7501/7102/7202 shown below) •Refer to the diagram and table below for mounting details. •Refer to the operation manual on the SMC website (URL http://www.smcworld.com ) for bracket thickness and mounting hole dimensions. 1 Mounting screws 2 Screws prepared by customer. PFMB7201 Model Mounting crew Mounting bracket PFMB7501 PFMB7102 PFMB7202 Tightening torque 0.45 to 0.55 Nm 0.5 to 0.7 Nm Screw M3 screws (4 pcs.) M4 screws (4 pcs.) Mounting to equipment Direct mounting •Refer to the diagram and table below for mounting details. •Refer to the operation manual on the SMC website (URL http://www.smcworld.com ) for mounting hole sizes. Screws prepared by customer. PFMB7201 Model Screw M3 screws (2 pcs.) Direct mounting Tightening torque 0.35 to 0.45 Nm PFMB7501 Self tapping screws (nominal size: 3.0 x 4 pcs.) 0.5 to 0.7 Nm PFMB7102 PFMB7202 PFMB7201 PFMB7501/7102/7202 OUT IN A B E C D D K M L I J LED display Element Description Displays the flow value, setting mode and error codes. Indicator LED S button (SET) button (DOWN) 3 I J L M Unit indicator N button (UP) 3 Displays the output status of OUT1 and OUT2. When the accumulated pulse output mode is selected, the LED will turn OFF. K Selects the mode and decreases the ON/OFF set value. 3: When the reversed display is used, the function of the and buttons is reversed. Selects the mode and increases the ON/OFF set value. Press this button to change the mode and to set a value. Indicates the unit currently selected. Display PFMB7201 PFMB7501/7102/7202 K L M I J N O S DIN rail mounting (Only PFMB7201) •Refer to the diagram and table below for mounting details. 1 2 DIN rail mounting screws DIN rail mounting bracket Bracket (Tapped) Joint screws Spring washers Bracket (Mounting hole) DIN rail is prepared by customer. DIN rail is not suitable for port size F02 (G1/4). PFMB7201 Model Screw Bracket Tightening torque Screw DIN rail mounting bracket 3 Mounting and Installation (Continued) Joint screws 0.35 to 0.45 Nm DIN rail mounting screws Tightening torque 0.35 to 0.45 Nm Piping •Never mount the product upside down. •The straight piping length shall be 8 cm or longer. Otherwise, if a straight section of piping is not installed, the accuracy varies by approximately ±2%F.S. •Avoid sudden changes in the piping size on the IN side of the product. •Do not release the OUT side piping port of the product directly to the atmosphere without the piping connected. If the product is used with the piping port released to atmosphere, the accuracy may vary. Flow direction OUT side IN side Restrictor 8 cm or longer Piping for the One-touch fitting •Accuracy can vary approximately ±2% when tubing other than the recommended tubing is used. •Insert the tube all the way into the fitting so that it cannot be pulled out. •Insertion with excessive force can cause damage. •Ensure there is no leakage after piping. •Use the product within the specified operating pressure and temperature range. Refer to the operation manual on the SMC website (URL http://www.smcworld.com ) for more information about safety instructions. 3 Mounting and Installation Accessory 1 Safety Instructions (Continued) Reference condition indicator O Indicates the reference condition selected. LED is ON (red) when standard condition is selected.

Upload: others

Post on 18-Dec-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Caution Installation & Maintenance Manual Digital Flow

Installation & Maintenance ManualDigital Flow Switch

PFMB7201/7501/7102/7202

PFMB7-TFQ04-A

2 Summary of Product parts

A

HG

DE

B DF

INC

OUT

IN

Warning

Do not disassemble, modify (including changing the printed

circuit board) or repair.

An injury or failure can result.

Do not operate the product outside of the specifications.

Do not use for flammable or harmful fluids.

Fire, malfunction, or damage to the product can result.

Verify the specifications before use.

Do not operate in an atmosphere containing flammable, explosive

or corrosive gas.

Fire, explosion or corrosion can result.

This product is not designed to be explosion proof.

Do not use the product for flammable fluid.

Fire or explosion can result.

Only air and N2 are applicable.

Do not use the product in a place where static electricity is a

problem.

Otherwise it can cause failure or malfunction of the system.

If using the product in an interlocking circuit:

•Provide a double interlocking system, for example a mechanical

system.

•Check the product regularly for proper operation.

Otherwise malfunction can result, causing an accident.

The following instructions must be followed during maintenance:

•Turn off the power supply.

•Stop the air supply, exhaust the residual pressure and verify that the

air is released before performing maintenance work.

Otherwise an injury can result.

Caution

Display ∗1

Element Description

See below.

Connector

Lock ring ∗2

Piping port

A

B

G

D

Through holeF

Flow adjustmentvalve ∗2

H

BodyE

Lead wire with connectorC

2 Summary of Product parts (Continued)

Mounting

•Never mount the product in a place where it will be used as a mechanical

support.

•Mount the product so that the fluid flows in the direction indicated by the

arrow on the side of the body.

1 Safety Instructions

This manual contains essential information for the protection of users

and others from possible injury and/or equipment damage.

•Read this manual before using the product, to ensure correct handling,

and read the manuals of related apparatus before use.

•Keep this manual in a safe place for future reference.

•These instructions indicate the level of potential hazard by label of

"Caution", "Warning" or "Danger", followed by important safety

information which must be carefully followed.

•To ensure safety of personnel and equipment the safety instructions in

this manual and the product catalogue must be observed, along with

other relevant safety practices.

CAUTION indicates a hazard with a low level of riskwhich, if not avoided, could result in minor ormoderate injury.

Caution

Warning

Danger

WARNING indicates a hazard with a medium levelof risk which, if not avoided, could result in death orserious injury.

DANGER indicates a hazard with a high level of riskwhich, if not avoided, will result in death or seriousinjury.

This product is class A equipment that is intended for use in an industrial

environment.

There may be potential difficulties in ensuring electromagnetic

compatibility in other environments due to conducted as well as radiated

disturbances.

Do not touch the terminals and connectors while the power is on.

Otherwise electric shock, malfunction or damage to the product can result.

After maintenance is complete, perform appropriate functional

inspections and leak tests.

Stop operation if the equipment does not function properly or there is a

leakage of fluid.

When leakage occurs from parts other than the piping, the product might

be faulty.

Disconnect the power supply and stop the fluid supply.

Do not apply fluid under leaking conditions.

Safety cannot be assured in the case of unexpected malfunction.

For piping connections. Connected to the fluid inlet at INand to the fluid outlet at OUT.

The body of the product.

Lead wire for power supply and outputs.

∗1: A protective tape is affixed to the display. Please remove it before use.∗2: The table lists the parts when a flow adjusting valve is included.

Body

Used to lock the flow adjustment valve.

Orifice mechanism to adjust the flow rate.

Connector for electrical connections.

Used to mount the product on a DIN rail or directly to apanel.

Panel mounting (Only PFMB7201)

•Refer to the diagram and table below for mounting details.

•Refer to the operation manual on the SMC website

(URL http://www.smcworld.com) for panel thickness and panel cut-out

dimensions.

Panel

Insert

1 2

Bracket

NOTE

The direct current power supply used should be UL approved as follows.

Circuit (class 2) of maximum 30 Vrms (42.4 V peak) or less, with UL1310

class 2 power supply unit or UL1585 class 2 transformer.

The product is a UL approved product only if it has a mark on the

body.

Bracket mounting (PFMB7501/7102/7202 shown below)

•Refer to the diagram and table below for mounting details.

•Refer to the operation manual on the SMC website

(URL http://www.smcworld.com) for bracket thickness and mounting hole

dimensions.

1 Mountingscrews

2 Screws preparedby customer.

PFMB7201

ModelMounting crew

Mounting bracket

PFMB7501

PFMB7102

PFMB7202

Tightening torque

0.45 to 0.55 Nm

0.5 to 0.7 Nm

Screw

M3 screws (4 pcs.)

M4 screws (4 pcs.)

Mounting to equipment

Direct mounting

•Refer to the diagram and table below for mounting details.

•Refer to the operation manual on the SMC website

(URL http://www.smcworld.com) for mounting hole sizes.

Screws prepared by customer.

PFMB7201

ModelScrew

M3 screws (2 pcs.)

Direct mounting

Tightening torque

0.35 to 0.45 Nm

PFMB7501Self tapping screws

(nominal size: 3.0 x 4 pcs.)0.5 to 0.7 NmPFMB7102

PFMB7202

PFMB7201 PFMB7501/7102/7202

OUT

IN

AB

ECD

D

KM

LI

J

LED display

Element Description

Displays the flow value, setting mode and error codes.

Indicator LED

S button (SET)

button (DOWN) ∗3

I

J

L

M

Unit indicatorN

button (UP) ∗3

Displays the output status of OUT1 and OUT2.When the accumulated pulse output mode is selected,the LED will turn OFF.

K

Selects the mode and decreases the ON/OFF setvalue.

∗3: When the reversed display is used, the function of the and buttons isreversed.

Selects the mode and increases the ON/OFF set value.

Press this button to change the mode and to set avalue.

Indicates the unit currently selected.

Display

PFMB7201 PFMB7501/7102/7202

KLM

I J

NO

SS

DIN rail mounting (Only PFMB7201)

•Refer to the diagram and table below for mounting details.

1 2

DIN rail mountingscrews

DIN rail mountingbracket

Bracket (Tapped)

Joint screwsSpring washers

Bracket(Mounting hole)

DIN rail is prepared by customer.DIN rail is not suitable for port size F02 (G1/4).

PFMB7201

ModelScrew

Bracket

Tightening torque Screw

DIN rail mounting bracket

3 Mounting and Installation (Continued)

Jointscrews

0.35 to 0.45 NmDIN rail

mountingscrews

Tightening torque

0.35 to 0.45 Nm

Piping

•Never mount the product upside down.

•The straight piping length shall be 8 cm or longer.

Otherwise, if a straight section of piping is not installed, the accuracy

varies by approximately ±2%F.S.

•Avoid sudden changes in the piping size on the IN side of the product.

•Do not release the OUT side piping port of the product directly to the

atmosphere without the piping connected. If the product is used with

the piping port released to atmosphere, the accuracy may vary.

Flow directionOUT sideIN side

Restrictor8 cm or longer

Piping for the One-touch fitting

•Accuracy can vary approximately

±2% when tubing other than the

recommended tubing is used.

•Insert the tube all the way into the

fitting so that it cannot be pulled out.

•Insertion with excessive force can

cause damage.

•Ensure there is no leakage after

piping.

•Use the product within the specified

operating pressure and temperature range.

Refer to the operation manual on the SMC website

(URL http://www.smcworld.com) for more information about safety

instructions.

3 Mounting and Installation

Accessory

1 Safety Instructions (Continued)

Reference conditionindicator

OIndicates the reference condition selected. LED is ON(red) when standard condition is selected.

Page 2: Caution Installation & Maintenance Manual Digital Flow

Piping for the metal attachment

•Tighten to the specified torque. Refer to the table below for the

required torque values.

•Use a suitable spanner for the appropriate torque. Do not use a

spanner 40 cm or longer.

•If the tightening torque is exceeded, the product can be broken.

If the tightening torque is insufficient, the fitting may become loose.

•Avoid any sealing tape getting inside the flow path.

•Ensure there is no leakage after piping.

•When mounting the fitting, a spanner should be used on the metal

part (attachment) of the fitting only.

Holding other parts of the product with a spanner may damage the

product.

Specifically, make sure that the spanner does not damage the

connector.

PFMB7-TFQ04-A

Caution

Attachment

Attachment

Caution

3 Mounting and Installation (Continued)

3 step setting mode

In this mode, only the set values can be input, in just 3 steps.

Use this mode if the product is to be used straight away, after changing only

the set values.

Default settings

When the flow exceeds the set value [P_1], the switch will be turned ON.

When the flow falls below the set value by the amount of hysteresis [H_1]

or more, the switch will turn OFF.

If the operation shown in the diagram below is acceptable, then keep

these settings.

5 Flow Setting (set value only) of OUT1 • OUT2 (Continued)

Hysteresis[H_1]

Time

Time

Switch ONSwitch OFF

Flow

[L/m

in]

[P_1]Set value

Item Model

[P_1] Set value of OUT1

[P_2] Set value of OUT2 ∗

[H_1] Hysteresis of OUT1[H_2] Hysteresis of OUT2 ∗

PFMB7201

Setting

PFMB7501

PFMB7102

PFMB7201

PFMB7501

PFMB7102

100 L/min

250 L/min

500 L/min

10 L/min

25 L/min

50 L/min

PFMB7202

PFMB7202

1000 L/min

100 L/min

∗: Only available for models with switch outputs for both OUT1 and OUT2.

Refer to the function selection mode to change the hysteresis.

For more detailed settings, set each function in function selection mode.

Operation (The example below is the explanation for PFMB7201

(1 output type) when reverse function is not used.)

Press the S button once in measurement mode.

[P_1] or [n_1] and [the current set value] are displayed in turn.

Displayedin turn

Set value

SSSS

∗: For models with switch outputs for both OUT1 and OUT2, [P_2] or [n_2] will bedisplayed too.Set as above.

∗: If a mode other than Hysteresis Mode is selected, refer to the operation manual fromSMC website (URL http://www.smcworld.com) or contact SMC.

∗: Note that the set value and hysteresis are limited by each other.∗: For more detailed settings, set each function in function selection mode.

Press the or button to change the set value.

The button is to increase and the button is to decrease the set

value.

SS

SS

SS

Press the button

continuously to keep

increasing the set value.

Press the button

continuously to keep

decreasing the set value.

Press the S button to complete the setting.

Return to measurement mode.

SS SSSS

2

3

Function selection mode

In this mode, each function setting can be changed separately.

In measurement mode, press the S button for 2 seconds or longer to

display [F 0].

Press the or button to select the function to be changed.

Function selection mode

SettingF0

SettingF1

SettingF99

SS SS SS

SSPress the button for 2 seconds or longer.

Measurement mode

PFMB7201

ModelRequired

torque

12 to 14 Nm

PFMB7501

PFMB7102

PFMB7202

PFMB7501

PFMB7102

PFMB7202

28 to 30 Nm PFMB7201

ModelNominal

thread size

Rc1/4NPT1/4

Width acrossflats of

attachment

G1/4

1/2

17 mm

21 mm

30 mm

35 mm

Wiring

Connection

•Connections should only be made with the power supply turned off.

•Use a separate route for the product wiring and any power or high

voltage wiring. Otherwise, malfunction may result due to noise.

•Ensure that the FG terminal is connected to ground when using a

commercially available switch-mode power supply. When a switch-

mode power supply is connected to the product, switching noise will

be superimposed and the product specification can no longer be met.

This can be prevented by inserting a noise filter, such as a line noise

filter and ferrite core, between the switch-mode power supply and the

product or by using a series power supply instead of a switch-mode

power supply.

Connecting/Disconnecting

•When mounting the connector, insert it

straight into the socket, holding the lever

and connector body, and push the

connector until the lever hooks into the

housing, and locks.

•When removing the connector, press

down the lever to release the hook from

the housing and pull the connector

straight out.

Connector

Lever

Cable body

1 Brown

+ 2 1 -

4321

2

3

4

White

Black

Blue

DC(+)

OUT2/Analogue output/External input

OUT1

DC(-)

4 Outline of Settings

The output will not operate for 3 seconds after supplying power.

The identification code of the product is displayed.

Power is supplied

Press the S button

once.

Press the S button for

2 seconds or longer.

∗: The outputs will continue to operate during setting.∗: If a button operation is not performed for 30 seconds during the setting, the display

will flash.(This is to prevent the setting from remaining incomplete if, for instance, an operatorwere to leave during setting)

∗: 3 step setting mode and Function selection mode are reflected on each other.

[Measurement mode]

Measurement mode is the condition where the flow is detected and

displayed, and the switch function is operating.

This is the basic mode; other modes should be selected for set-point

changes and other function settings.

Flow Setting[3 step setting mode]

Function Setting[Function selection mode] Other functions

Reversed output

∗: The operation may become unstable if hysteresis mode or window comparatormode are used during fluctuating flow conditions. In this case, maintain an intervalbetween the set values and start using after confirming stable operation.

Set valueP1.1+P1.2+P1.3

Set valueP1.1+P1.2+P1.3

OFF

ONOutput

0

Display: Count down (AC1 = dEC)

Accumulated flow

Time

TimeCount down form set value.Turn ON when the “0” is reached.Return to set value by set.

OFF

ONOutput

0

Display: Count up (AC1 = Add)

Time

TimeCount up form “0”.Turn ON when the set value is reached.Return to “0” by set.

Accumulated flow

Count down form set value.Turn OFF when the “0” is reached.Return to set value by set.

Count up form “0”.Turn OFF when the set value is reached.Return to “0” by set.

OFF

ONOutput

0 Time

Time

Set valuen1.1+n1.2+n1.3

Accumulated flow

Display: Count up (AC1 = Add)

TimeOFF

ONOutput

0 Time

Set valuen1.1+n1.2+n1.3

Accumulated flow

Display: Count down (AC1 = dEC)

Normal output

OFF

ONOutput

Time

Time0

Instantaneous flow

HysteresisH_1

Set valueP_1

Flowincreased

Flowdecreased

OFF

ONOutput

Time

0Time

HysteresisH_1Set value

n_1

Flowdecreased

Instantaneous flow

Flowincreased

P1LLower limit value

P1HUpper limit value

OFF

ONOutput

0

Time

Time

Instantaneous flow

HysteresisH 1

Flowincreased

Flowdecreased

TimeOFF

ONOutput

n1LLower limit value

n1HUpper limit value

Time0

HysteresisH 1

HysteresisH 1

Instantaneous flow

Win

do

w c

om

pa

rato

r m

od

eA

ccu

mu

late

d o

utp

ut m

od

e

Output

7 Setting of OUT1 • • • [F 1]

Select the operation required from the table below. For example . . .

•Turn the switch output ON when the flow exceeds the set value.

•Turn the switch output ON when the flow falls below the set value.

•Turn the switch output ON when the flow is more, or less, than a

specific flow range.

Switch output operation list

5 Flow Setting (set value only) of OUT1 • OUT2

1

Hyste

resis

mo

de

Time

50 ms

Time

OFF

ONOutput

0

Accumulated flow

OFF 50 msON

Output

0

Accumulated flow

Time

Time

Accu

mu

late

d p

uls

e o

utp

ut m

od

e

6 Function Setting

mode

Switchoperation

Press the S button for 2 seconds or longer in function selection

mode to return to measurement mode.

3/4

Refer to the specific product precautions in the operation manual on the

SMC website (URL http://www.smcworld.com) for more information

about installation.

1

A

C

C

B

BA

Page 3: Caution Installation & Maintenance Manual Digital Flow

In measurement mode, press the S button for 2 seconds or longer to

display [F 0].

Press the or button to display [F99]. Press the S button.

Press the or button to display [ on]. Press the S and buttons

simultaneously for 5 seconds or longer.

Reset to the default settings is complete. Press the S button for 2

seconds or longer to return to measurement mode.

PFMB7-TFQ04-A

Operation

Follow the setting flowchart.

In measurement mode, press the S button

for 2 seconds or longer to enter function

selection mode.

Press the or button in function

selection mode to display [F 1].

[F 1] and [oU1] are displayed in turn.

Press the S button.

Output mode

[oU1] and [the current set value] are

displayed in turn.

Press the or button to select.

Press the S button to set.

Switch operation

[1ot] and [the current set value] are

displayed in turn.

Press the or button to select.∗: By switching to reversed output, the display

colour will change in relation to the setting.

Hysteresis (When hysteresis mode, window comparator mode is

selected)

Press the or button to change the value.∗: The set value and hysteresis settings limit each other.

Press the S button to set.

Display colour

[CoL] and [the current set value] are

displayed in turn.

Press the or button to select.

Press the S button to complete

the setting.

Return to function selection mode.

Press the S button for 2 seconds or longer to return to measurement mode.

Press the button for2 seconds or longer.

SS

Measurementmode

Functionselection

mode

Output mode Set value

Displayed in turn

Set value

Displayed in turn

Selectreversedoutput

Set value

Displayed in turn

Displaycolour

Refer to the operation manual on the SMC website

(URL http://www.smcworld.com) for settings other than those shown above.

13 Troubleshooting

∗: If the error cannot be reset after the above measures are taken, then please contact SMC.

Error indication

Instantaneousflow error

The flow has exceededthe upper limit of the flowdisplay range.

Reduce the flow.

Error name Error code Description Measures

OUT1 overcurrent error

The switch output (OUT1)load current hasexceeded 80 mA.

The switch output (OUT2)load current hasexceeded 80 mA.

Turn the powerOFF and removethe cause of theover current. Thenturn the power ONagain.

System errorAn internal data error hasoccurred.

Turn the powerOFF and turn it ONagain.

The accumulated flowhas reached the setaccumulated flow value.(For count down display)

The accumulated flowhas exceeded theaccumulated flow range.(For count up display)

Fluid is flowing in thereverse direction by atleast -5% of the maximumrated flow value.

Connect the fluidflow in the correctdirection.

Reset theaccumulated flow.(Press the and

buttonssimultaneously for1 second or longer)

10 Specifications

Refer to the product catalogue or operation manual on the SMC website

(URL http://www.smcworld.com) for more information about product

specifications.

OUT2 overcurrent error

Accumulatedflow displayed

(flashing)

Accumulatedflow displayed

(flashing)

Accumulatedflow error

11 Dimensions

Refer to the product catalogue or operation manual on the SMC website

(URL http://www.smcworld.com) for more information about product

dimensions.

9 Maintenance

Refer to the operation manual on the SMC website

(URL http://www.smcworld.com) for more information about product

maintenance.

URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)

Specifications are subject to change without prior notice from the manufacturer.

© 2012-2015 SMC Corporation All Rights Reserved

14 Contacts

AUSTRIA (43) 2262 62280-0

NETHERLANDS (31) 20 531 8888

BELGIUM (32) 3 355 1464

NORWAY (47) 67 12 90 20 CZECH REP. (420) 541 424 611

POLAND (48) 22 211 9600 DENMARK (45) 7025 2900

PORTUGAL (351) 21 471 1880

FINLAND (358) 207 513513

SLOVAKIA (421) 2 444 56725 FRANCE (33) 1 6476 1000

SLOVENIA (386) 73 885 412GERMANY (49) 6103 4020

SPAIN (34) 945 184 100 GREECE (30) 210 271 7265

SWEDEN (46) 8 603 1200 HUNGARY (36) 23 511 390

SWITZERLAND (41) 52 396 3131 IRELAND (353) 1 403 9000

UNITED KINGDOM (44) 1908 563888 ITALY (39) 02 92711

BULGARIA (359) 2 974 4492

ESTONIA (372) 651 0370

ROMANIA (40) 21 320 5111

LATVIA (371) 781 77 00

LITHUANIA (370) 5 264 8126

Default settings

Item

[ ] [ ]

Unit selection function ∗1[ ]

Output mode of OUT1[ ]

Switch operation of OUT1[ ]

Hysteresis of OUT1[ ]

Default settings

L/min[ ]

Hysteresis mode[ ]

Normal output[ ]

100 L/min (PFM7201)[ ]

10 L/min (PFM7201)[ ]

Display colour[ ] ON: GreenOFF: Red

[ ]

[ ] [ ]

Output mode of OUT2 ∗2[ ]

Switch operation ofOUT2 ∗2

[ ]

Set value of OUT2 ∗2[ ]

Hysteresis mode[ ]

Normal output[ ]

[ ] [ ] Response time[ ] 1 second[ ]

[ ] [ ] Display mode[ ] Instantaneous flow[ ]

[ ] [ ] Accumulated flowexternal reset

[ ]

[ ] [ ] Setting of analogueoutput ∗4

[ ] Variable OFF[ ]

Set value of OUT1[ ]250 L/min (PFM7501)[ ]

Hysteresis of OUT2 ∗2[ ]

∗1: This setting is only available for models with the unit selection function.∗2: This setting is only available for models with switch outputs for both OUT1 and

OUT2.∗3: This setting is only available for models with the external input.∗4: This setting is only available for models with the analogue output.

[ ] [ ] Reversed display[ ] Unused[ ]

Standard condition[ ]

8 Other Functions

Peak value display

(Press the button for 1 second).

Bottom value display

(Press the button for 1 second).

Reset operation

(Press the and buttons simultaneously for 1 second or longer.)

Key lock function

(Press the S button for 5 seconds or longer.)

Setting flowchart

Refer to the list of Switch output operation list for the setting

procedure. Characters in ( ) are for OUT2.

Mark the procedure path with a pen or marker.

Hysteresis

The display colourcan be set to changedepending upon thestatus of OUT1.

[ ] [ ] [ ] [ ]

[ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ]

[ ] [ ] [ ] [ ]

[ ]

[ ] [ ]

[ ][ ]

[ ] [ ]

[ ]

[ ]

[ ] [ ]

[ ]

[ ]

[ ] [ ][ ][ ]

Outp

ut m

ode

Hyste

resis

Set v

alue

Switc

hop

erat

ionDi

splay

colou

r

Hysteresismode

Window comparatormode

Accumulated outputmode

Accumulated pulsemode

Normal Normal Normal Normal ReversedReversedReversedReversed

Upper3 digits

Upper3 digits

Middle3 digits

Middle3 digits

Lower3 digits

Lower3 digits

[ ]

Lowerlimit

Upperlimit

Upperlimit

Lowerlimit

Setvalue

Setvalue

Hysteresis

Always: GreenAlways: RedON: RedOFF: Green

ON: Green OFF: Red

∗∗

Coun

t up

/Co

unt d

own

Coun

t up

displa

y

Coun

t dow

ndis

play

Coun

t up

displa

y

Coun

t dow

ndis

play

∗: The accumulated output can be set between 0 to 999, 999, 999 L.The set value is input starting from the upper 3 digits.

Enter the items in [ ] that you selected, following the procedure below.

12 Reset to the default settings

7 Setting of OUT1 • • • [F 1] (Continued) 7 Setting of OUT1 • • • [F 1] (Continued)

Press the S button to set.

[ ] [ ] Accumulated value hold[ ] Unused[ ]

[ ] [ ]

Orientation correction[ ] Horizontal mounting[ ]

Supply pressure[ ]

[ ] [ ] Display OFF mode[ ]

[ ] [ ] Security code[ ] Unused[ ]

[ ] [ ] Setting of all items[ ]

[ ] [ ] Output check[ ]

[ ] [ ] Reset to the defaultsettings

[ ]

Unused[ ]

0.4 MPa minimum,0.6 MPa maximum

[ ]

Display ON[ ]

Normal output[ ]

Unused[ ]

Press the S button to set.

Set value (When hysteresis mode, window comparator mode,

accumulated output mode is selected)

Press the or button to change the value.∗: The set value and hysteresis settings limit each other.

Reference condition[ ][ ] [ ]

External input ∗3[ ]

Refer to the operation manual on theSMC website

(URL http://www.smcworld.com) for more information about

troubleshooting.

500 L/min (PFM7102)[ ]

1000 L/min (PFM7202)[ ]

100 L/min (PFM7202)[ ]

25 L/min (PFM7501)[ ]

50 L/min (PFM7102)[ ]

100 L/min (PFM7201)[ ]

10 L/min (PFM7201)[ ]

250 L/min (PFM7501)[ ]

500 L/min (PFM7102)[ ]

1000 L/min (PFM7202)[ ]

100 L/min (PFM7202)[ ]

25 L/min (PFM7501)[ ]

50 L/min (PFM7102)[ ]

12 Reset to the default settings (Continued)

2

3

1

2

3

4