Service Facts IMPORTANT — This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work. © 2013 Trane NOTICE: The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice. WARNING ! THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE. CAUTION ! RECONNECT ALL GROUNDING DEVICES. ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED TO COMPLETE A PATH TO GROUND ARE REMOVED FOR SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL POSITION AND PROPERLY FASTENED. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE CAPACITORS BEFORE SERVICING CAUTION ! UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE TO USE PROPER SERVICE TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR PERSONAL INJURY. SERVICE USE ONLY R-410A REFRIGERANT AND APPROVED POE COMPRESSOR OIL. PRODUCT SPECIFICATIONS OUTDOOR UNIT POWER CONNS. — V/PH/HZ 1 MIN. BRCH. CIR. AMPACITY BR CIR PROT RTG – MAX. (AMPS) COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS 5 - L.R. AMPS FACTORY INSTALLED START COMPONENTS 6 INSUL/SOUND BLANKET COMPRESSOR HEAT OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. 2 NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT REFRIGERANT CONTROL LBS — R-410A (O.D. UNIT) 3 FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS 4 LINE SIZE - IN. O.D. LIQ. 4 CHARGING SPECIFICATION TXV SYS CHGD TO SUBCOOL CAPILLARY SYS CHGD TO SUPERHEAT DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.) Tubing lengths in excess of sixty (60) feet see application software. 4TTA3AD-SF-1A Split System Cooling 4TTA3030AD000A, 4TTA3036AD000A, 4TTA3042AD000A, 4TTA3048AD000A, 4TTA3060AD000A 10/13 4TTA3042AD000A 380-415/3/50 12 21 SCROLL 1 - 1 380-415/3/50 6.9 - 52.0 NO NO YES PROPELLER 27.6 - 1 DIRECT - 1 3525 1 - 1/6 700 380-415/3/50 0.7 SPINE FIN™ 1 - 24 27.86 3/8 R-410A TXV/Capillary 8 LBS., 6 OZ. YES 7/8 3/8 10°F 10°F H X W X D 46.4 x 35.1 x 38.7 277 240 4TTA3048AD000A 380-415/3/50 12 21 SCROLL 1 - 1 380-415/3/50 7.6 - 51.5 NO NO YES PROPELLER 27.6 - 1 DIRECT - 1 3980 1 - 1/6 700 380-415/3/50 0.7 SPINE FIN™ 1 - 24 30.79 3/8 R-410A TXV/Capillary 9 LBS., 13 OZ. YES 7/8 3/8 10°F 10°F H X W X D 51 x 35.1 x 38.7 292 255 4TTA3060AD000A 380-415/3/50 14 25 SCROLL 1 - 1 380-415/3/50 8.9 - 67.1 NO NO YES PROPELLER 27.6 - 1 DIRECT - 1 3980 1 - 1/6 700 380-415/3/50 0.7 SPINE FIN™ 1 - 24 30.79 3/8 R-410A TXV/Capillary 9 LBS., 14 OZ. YES 7/8 3/8 10°F 10°F H X W X D 51 x 35.1 x 38.7 297 260 4TTA3030AD000A 380-415/3/50 9 15 SCROLL 1 - 1 380-415/3/50 6.1 - 38.0 NO NO YES PROPELLER 27.6 - 1 DIRECT - 1 3525 1 - 1/6 700 380-415/3/50 0.7 SPINE FIN™ 1 - 24 24.93 3/8 R-410A TXV/Capillary 7 LBS., 11 OZ. YES 3/4 3/8 10°F 10°F H X W X D 42.4 x 35.1 x 38.7 217 182 4TTA3036AD000A 380-415/3/50 11 19 SCROLL 1 - 1 380-415/3/50 6.7 - 43.0 NO NO YES PROPELLER 27.6 - 1 DIRECT - 1 3525 1 - 1/6 700 380-415/3/50 0.7 SPINE FIN™ 1 - 24 24.93 3/8 R-410A TXV/Capillary 8 LBS., 8 OZ. YES 7/8 3/8 10°F 10°F H X W X D 42.4 x 35.1 x 38.7 254 219 TUBING INFORMATION LINE TYPE REFRIGERANT TO ADD AT SPECIFIED ADDITIONAL LENGTH Suction Liquid 20 ft 30 ft 40 ft 50 ft 60 ft 3/4" 3/8" 3 oz 9 oz 15 oz 21 oz 27 oz 7/8" 3/8" 3 oz 9 oz 16 oz 22 oz 28 oz CONTAINS REFRIGERANT! SYSTEM CONTAINS OIL AND REFRIGERANT UNDER HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE PRESSURE BEFORE OPENING SYSTEM. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. CAUTION ! HOT SURFACE! DO NOT TOUCH TOP OF COMPRESSOR. May cause minor to severe burning. CAUTION ! 1 Calculated in accordance with Natl. Elec. Codes. Only use HACR circuit breakers or fuses. 2 Standard Air — Dry Coil — Outdoor 3 This value approximate. For more precise value see unit nameplate. 4 Max. linear length 80 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft. For greater length consult refrigerant piping software Pub. No. 32-3312-0* (* denotes latest revision). 5 This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current. 6 No means no start components. Yes means quick start kit com- ponents. PTC means positive temperature coefficient starter.

Upload: others

Post on 09-Apr-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CAUTION Service Facts - juma-ac.ae

Service Facts

IMPORTANT — This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.

© 2013 Trane

NOTICE: The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

WARNING!THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.

CAUTION!RECONNECT ALL GROUNDING DEVICES.ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED TO COMPLETE A PATH TO GROUND ARE REMOVED FOR SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL POSITION AND PROPERLY FASTENED.

WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE CAPACITORS BEFORE SERVICING

CAUTION!

UNIT CONTAINS R-410A REFRIGERANT!R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE TO USE PROPER SERVICE TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR PERSONAL INJURY.

SERVICEUSE ONLY R-410A REFRIGERANT ANDAPPROVED POE COMPRESSOR OIL.

PRODUCT SPECIFICATIONS OUTDOOR UNIT POWER CONNS. — V/PH/HZ 1 MIN. BRCH. CIR. AMPACITY BR CIR PROT RTG – MAX. (AMPS) COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS 5 - L.R. AMPS FACTORY INSTALLED START COMPONENTS 6 INSUL/SOUND BLANKET COMPRESSOR HEAT OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. 2 NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT REFRIGERANT CONTROL LBS — R-410A (O.D. UNIT) 3 FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS 4 LINE SIZE - IN. O.D. LIQ. 4 CHARGING SPECIFICATION TXV SYS CHGD TO SUBCOOL CAPILLARY SYS CHGD TO SUPERHEAT DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)

Tubing lengths in excess of sixty (60) feet see application software.

4TTA3AD-SF-1A

Split System Cooling4TTA3030AD000A, 4TTA3036AD000A, 4TTA3042AD000A, 4TTA3048AD000A, 4TTA3060AD000A

10/13

4TTA3042AD000A380-415/3/50

1221

SCROLL 1 - 1

380-415/3/506.9 - 52.0

NONOYES

PROPELLER27.6 - 1

DIRECT - 13525

1 - 1/6700

380-415/3/500.7

SPINE FIN™1 - 2427.863/8

R-410ATXV/Capillary8 LBS., 6 OZ.

YES7/83/8

10°F10°F

H X W X D46.4 x 35.1 x 38.7

277240

4TTA3048AD000A380-415/3/50

1221

SCROLL1 - 1

380-415/3/507.6 - 51.5

NONOYES

PROPELLER27.6 - 1

DIRECT - 13980

1 - 1/6700

380-415/3/500.7

SPINE FIN™1 - 2430.793/8

R-410ATXV/Capillary9 LBS., 13 OZ.

YES7/83/8

10°F10°F

H X W X D51 x 35.1 x 38.7

292255

4TTA3060AD000A380-415/3/50

1425

SCROLL1 - 1

380-415/3/508.9 - 67.1

NONOYES

PROPELLER27.6 - 1

DIRECT - 13980

1 - 1/6700

380-415/3/500.7

SPINE FIN™1 - 2430.793/8

R-410ATXV/Capillary9 LBS., 14 OZ.

YES7/83/8

10°F10°F

H X W X D51 x 35.1 x 38.7

297260

4TTA3030AD000A380-415/3/50

915

SCROLL1 - 1

380-415/3/506.1 - 38.0

NONOYES

PROPELLER27.6 - 1

DIRECT - 13525

1 - 1/6700

380-415/3/500.7

SPINE FIN™1 - 2424.933/8

R-410ATXV/Capillary7 LBS., 11 OZ.

YES3/43/8

10°F10°F

H X W X D42.4 x 35.1 x 38.7

217182

4TTA3036AD000A380-415/3/50

1119

SCROLL 1 - 1

380-415/3/506.7 - 43.0

NONOYES

PROPELLER27.6 - 1

DIRECT - 13525

1 - 1/6700

380-415/3/500.7

SPINE FIN™1 - 2424.933/8

R-410ATXV/Capillary8 LBS., 8 OZ.

YES7/83/8

10°F10°F

H X W X D42.4 x 35.1 x 38.7

254219

TUBING INFORMATION

LINE TYPEREFRIGERANT TO ADD AT SPECIFIED

ADDITIONAL LENGTH

Suction Liquid 20 ft 30 ft 40 ft 50 ft 60 ft

3/4" 3/8" 3 oz 9 oz 15 oz 21 oz 27 oz

7/8" 3/8" 3 oz 9 oz 16 oz 22 oz 28 oz

CONTAINS REFRIGERANT!SYSTEM CONTAINS OIL AND REFRIGERANT UNDER HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE PRESSURE BEFORE OPENING SYSTEM.Failure to follow proper procedures can result in personalillness or injury or severe equipment damage.

CAUTION!

HOT SURFACE!DO NOT TOUCH TOP OF COMPRESSOR.May cause minor to severe burning.

CAUTION!

1 Calculated in accordance with Natl. Elec. Codes. Only use HACR circuit breakers or fuses.

2 Standard Air — Dry Coil — Outdoor3 This value approximate. For more precise value see unit nameplate.4 Max. linear length 80 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid

60 ft. For greater length consult refrigerant piping software Pub. No. 32-3312-0* (* denotes latest revision).

5 This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current.

6 No means no start components. Yes means quick start kit com-ponents. PTC means positive temperature coefficient starter.

Page 2: CAUTION Service Facts - juma-ac.ae

SCHEMATIC DIAGRAM

SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENTThe manufacturer has always recommended installing approved matched indoor and outdoor systems.

All split systems are AHRI rated with only TXV indoor systems.

The benefits of installing approved indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.

The following charging methods are therefore prescribed for systems with indoor TXVs.

1. Subcooling (in the cooling mode) is the only recommended method of charging above 55°F ambient temperatures.

2. For best results – the indoor temperature should be kept between 70°F to 80°F. Add system heat if needed.

3. At startup, or whenever charge is removed or added, the system must be operated for a minimum 20 minutes to stabilize before accurate measurements can be made.

4. Measure Liquid Line Temperature and Refrigerant Pressure at service valves.

5. Determine total refrigerant line length, and height (lift) if indoor section is above the condenser.

6. Determine the Design Subcool Charging Temperature from the unit nameplate.

7. Locate this value in the appropriate column of the Sub cooling Charging Table. Locate your liquid line temperature in the left column of the table, and the intersecting liquid line pressure under your nameplate subcool value column. Add refrigerant to raise the pressure to match the table, or remove refrigerant

to lower the pressure. Again, wait 20 minutes for the system conditions to stabilize before adjusting charge again.

8. When system is correctly charged, you can refer to System Pressure Curves to verify typical performance.

8 9 10 11 12 13 14

55 179 182 185 188 191 195 19860 195 198 201 204 208 211 21565 211 215 218 222 225 229 23270 229 232 236 240 243 247 25175 247 251 255 259 263 267 27180 267 271 275 279 283 287 29185 287 291 296 300 304 309 31390 309 313 318 322 327 331 33695 331 336 341 346 351 355 360100 355 360 365 370 376 381 386105 381 386 391 396 402 407 413110 407 413 418 424 429 435 441115 435 441 446 452 458 464 470120 464 470 476 482 488 495 501125 495 501 507 514 520 527 533

R-410A REFRIGERANT CHARGING CHART

Refer to Service Facts or Installer's Guide for charging method.

LIQUIDTEMP(°F)

DESIGN SUBCOOLING (°F)

LIQUID GAGE PRESSURE (PSI)

From Dwg. D154557P01 Rev. 2

2 4TTA3AD-SF-1A

Page 3: CAUTION Service Facts - juma-ac.ae

WIRING DIAGRAM3

1/2

Ton

Add 6°

Add 5°

TOTAL REFRIGERANT LINE LENGTH (FEET)

REFR

IGERA

NT LIN

E LIFT

(FEE

T)

10 20 25 30 40 60

Add 3° of Subcooling

Add 2° of Subcooling

Add 1° of Subcooling

Use Design Subcool Value

60

50

40

30

25

20

15

10

0

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

4 To

n

Add 6°

TOTAL REFRIGERANT LINE LENGTH (FEET)

REFR

IGERA

NT LIN

E LIFT

(FEE

T)

10 20 25 30 40 60

Add 4° of Subcooling

Add 3° of Subcooling

Add 2° of SubcoolingAdd 1° of Subcooling

Use Design Subcool Value

60

50

40

30

25

20

15

10

0

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

3 To

n

2 1/

2 To

n

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

TOTAL REFRIGERANT LINE LENGTH (FEET)

REFR

IGERA

NT LIN

E LIFT

(FEE

T)

10 20 25 30 40 60

Use Design Subcool Value

60

50

40

30

25

20

15

10

0

Add 5°

Add 4°

Add 2°

Add 3° of Subcooling

Add 1° of Subcooling

Add 4°

Add 3°

TOTAL REFRIGERANT LINE LENGTH (FEET)

REFR

IGERA

NT LIN

E LIFT

(FEE

T)

10 20 25 30 40 60

Add 2° of Subcooling

Add 1° of Subcooling

Use Design Subcool Value

60

50

40

30

25

20

15

10

0

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

5 To

n

Add 6°

TOTAL REFRIGERANT LINE LENGTH (FEET)

REFR

IGERA

NT LIN

E LIFT

(FEE

T)

10 20 25 30 40 60

Add 5° of Subcooling

Add 4° of Subcooling

Add 3° of SubcoolingAdd 2° of Subcooling

Add 1° of SubcoolingDesign

60

50

40

30

25

20

15

10

0

SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)

4TTA3AD-SF-1A 3

Page 4: CAUTION Service Facts - juma-ac.ae

4 4TTA3AD-SF-1A

TROUBLESHOOTING

L2L1

T2

T1

INOU

T

L2L1

T2

T1

Sin

gle

Po

le C

on

tact

or

(MS

)*D

ou

ble

Po

le C

on

tact

or

(MS

)*

Co

nta

cto

r C

oil

24 V

AC

HIGH

VOLT

AGE

INOU

T

HIGH

VOLT

AGE

*Ref

er to

Wiri

ng D

iagr

am to

det

erm

ine

if a

sing

le p

ole

or d

oubl

e po

le c

onta

ctor

is u

sed.

Che

ck fo

r ope

n IO

L (In

tern

al O

verlo

ad)

Che

ck re

sist

ance

of

C to

S a

nd C

to R

Doe

s th

e re

sist

ance

che

ck

show

an

open

ci

rcui

t fro

m C

to S

or

C to

R?

YES

Allo

w c

ompr

esso

r tim

e to

coo

l and

re

-test

NO

Che

ck fo

r ope

n w

indi

ngs.

YE

SD

oes

a re

sist

ance

che

ck

show

an

open

circ

uit

betw

een

R a

nd S

?

Rep

lace

the

com

pres

sor

NO

Che

ck fo

r loc

ked

roto

r

Is v

olta

ge p

rese

nt

at C

to S

and

C

to R

with

lock

ed

roto

r am

ps o

n C

?

YE

SC

heck

Sta

rt-C

apac

itor a

nd

Rel

ay (i

f pre

sent

) an

d R

un C

apac

itor

Do

the

star

t co

mpo

nent

s an

d ru

n ca

paci

tor

chec

k go

od?

YE

SR

epla

ce th

e co

mpr

esso

r

NO

Rep

lace

sta

rt co

mpo

nent

s an

d/or

run

capa

cito

r

NO

Che

ck w

iring

to

com

pres

sor

C, S

and

R

Che

ck fo

r hig

h vo

ltage

to c

onta

ctor

Is h

igh

volta

ge p

rese

nt

at T

1 an

d T2

?Y

ES

NO

Che

ck p

ower

su

pply

from

di

scon

nect

and

/or

brea

ker p

anel

.

Com

pres

sor w

on’t

run

Con

tact

or is

clo

sed

Is c

onta

ctor

en

ergi

zed?

(c

onta

cts

clos

ed)

Is v

olta

ge

pres

ent a

t co

ntac

tor c

oil?

R

epla

ce c

onta

ctor

YE

S

NO

NO

Che

ck fo

r 24

volts

AC

ac

ross

con

tact

or c

oil

Che

ck c

ontro

l tra

nsfo

rmer

and

co

ntro

l fus

e

Is th

e co

ntro

l tra

nsfo

rmer

an

d fu

se g

ood?

NO

YE

S

Rep

air o

r rep

lace

tra

nsfo

rmer

or f

use.

In

vest

igat

e ca

use

for

failu

re (p

ossi

ble

shor

t in

field

wiri

ng)

Jum

per R

to Y

low

vo

ltage

term

inal

s at

ther

mos

tat s

ub

base

.

Doe

s th

e co

ntac

tor

ener

gize

?

NO

Rep

air o

r rep

lace

co

nnec

ting

wiri

ng

YE

SG

o To

:Com

pres

sor w

on’t

run

Rep

lace

the

room

th

erm

osta

tY

ES

Com

pres

sor f

ails

to s

tart

Con

tact

or c

heck

Page 5: CAUTION Service Facts - juma-ac.ae

REFRIGERANT CIRCUIT 4TTA3030AD, 036AD, 42AD

REFRIGERANT CIRCUIT 4TTA3048AD/060AD

Printed from D157826

Printed from D157878

4TTA3AD-SF-1A 5

Page 6: CAUTION Service Facts - juma-ac.ae

PRESSURE CURVES FOR 4TTA3030AD

MCDA30Cooling with FCCV or Capillary Tubes

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

)

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .

EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 980 CFM IS 369 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 980 CFM IS 134 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 3/4"Liquid - 3/8"

DWG.NO. 4TTA3030AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

PRESSURE CURVES FOR 4TTA3042AD

MCDB42Cooling with FCCV or Capillary Tubes

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 1259 CFM IS 390 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 1259 CFM IS 132 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 7/8"Liquid - 3/8"

DWG.NO. 4TTA3042AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

PRESSURE CURVES FOR 4TTA3030AD

GAF2A0A36Cooling with Thermal Expansion Valve

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

)

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 975 CFM IS 376 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 975 CFM IS 133 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 3/4"Liquid - 3/8"

DWG.NO. 4TTA3030AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

PRESSURE CURVES FOR 4TTA3042AD

GAT2A0A48Cooling with Thermal Expansion Valve

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

)

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 1581 CFM IS 399 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 1581 CFM IS 141 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 7/8"Liquid - 3/8"

DWG.NO. 4TTA3042AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

6 4TTA3AD-SF-1A

Page 7: CAUTION Service Facts - juma-ac.ae

PRESSURE CURVES FOR 4TTA3036AD

MCDA36Cooling with FCCV or Capillary Tubes

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

)

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .

EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 1082 CFM IS 365 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 1082 CFM IS 129 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 7/8"Liquid - 3/8"

DWG.NO. 4TTA3036AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

PRESSURE CURVES FOR 4TTA3048AD

MCDB48Cooling with FCCV or Capillary Tubes

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 1369 CFM IS 390 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 1369 CFM IS 134 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 7/8"Liquid - 3/8"

DWG.NO. 4TTA3048AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

PRESSURE CURVES FOR 4TTA3036AD

GAF2A0A36Cooling with Thermal Expansion Valve

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 975 CFM IS 372 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 975 CFM IS 126 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 7/8"Liquid - 3/8"

DWG.NO. 4TTA3036AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

PRESSURE CURVES FOR 4TTA3048AD

GAT2A0A48Cooling with Thermal Expansion Valve

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

)

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 85 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 1581 CFM IS 389 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 1581 CFM IS 138 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESSuction - 7/8"Liquid - 3/8"

DWG.NO. 4TTA3048AD

110

115

120

125

130

135

140

145

150

155

160

165

170

70 80 90 100 110 120 130

250

300

350

400

450

500

550

600

70 80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

4TTA3AD-SF-1A 7

Page 8: CAUTION Service Facts - juma-ac.ae

PRESSURE CURVES FOR 4TTA3060AD

GAF2A0A60Cooling with Thermal Expansion Valve

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

)

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .

EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 1750 CFM IS 134 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 1750 CFM IS 404 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESGAS - 7/8" O.D.LIQUID - 3/8" O.D.

DWG.NO. 4TTA3060AD

115

120

125

130

135

140

145

150

155

160

165

170

80 90 100 110 120 130

330

380

430

480

530

580

80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG

PRESSURE CURVES FOR 4TTA3060AD

MCDB60Cooling with FCCV or Capillary Tubes

LIQ

UID

PR

ESSU

RE

(PSI

G)

OUTDOOR TEMPERATURE (Degree F)

SUC

TIO

N P

RES

SUR

E (P

SIG

)

OUTDOOR TEMPERATURE (Degree F)COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .

EXAMPLE: (1) OUTDOOR TEMP. 95 F. (2) INDOOR WET BULB 63 F. (3) AT INTERSECTION ACTUAL: (4) LIQUID PRESSURE @ 1525 CFM IS 399 PSIG LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART (5) SUCTION PRESSURE @ 1525 CFM IS 126 PSIG SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINESGAS - 7/8" O.D.LIQUID - 3/8" O.D.

DWG.NO. 4TTA3060AD

105110115120125130135140145150155160165170

80 90 100 110 120 130

320

370

420

470

520

570

80 90 100 110 120 130

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVESTOP TO BOTTOM 71, 67, 63 AND 59 DEG

8 4TTA3AD-SF-1A