Corroded Beam Reinforcement in Gas Separation Plant

Cold Bonding Solution

Page 2: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Major Petrochemical Plant , Rayong , Thailand Severe corrosion and metal loss on Pipe rack beam

throughout the plant can lead to Pipe rack collapse and serious accident.

Page 3: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

The corrosion was caused by “crack cementitious-fireproof ”.

The corrosion hided under thick fireproof paint and was not detected by visual inspection.

Inspection in 2007 was decided to remove crack fireproof paint for inspection

Pipe rack beam arrangement

Page 4: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Corrosion on Beam after Grit blast to remove Fireproof paint

Page 5: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Typical arrangement of Cementitioius fireproof on Beam

Cause of corrosion was the result of cementitious fireproof Cracking & deterioration.

Page 6: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

SOLUTION : Severe metal loss raised concern about Beam

strength and integrity. External Engineering specialist was contacted by

client to verify the Beam strength and they recommended to reinstate the Beam.

Available solutions were

1. Replace the new Beam

2. Hot Welding to reinstate the Beam

3. Cold Bonding to reinstate the Beam

Page 7: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

SOLUTION : Available solutions

1. Replace the new Beam is not possible because ;

Pipe rack beam run throughout the plant Complexity of Pipe rack arrangement Some areas were hard to access Very Expensive and Partial Plant shutdown required

2. Hot Welding to reinstate the Beam Possible but too risky because the Beam was

supporting Hydrocarbon Pipeline Many technical limitation for welding efficiency

Page 8: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

SOLUTION : The Cold Repair by BELZONA Cold Bonding Method

was considered only the reasonable solution Client requested us to do “Load test” to prove that

BELZONA Cold Bonding can reinstate the Beam strength

Testing was agreed to carry out by Pan Mechanic and Client

Page 9: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TEST OBJECTIVE :

The test was carried out to calculate the “Deflection”

comparing between

1. Standard Beam

2. Defected Beam + Reinforced with Metal plate by BELZONA Cold Bonding

the Item 2 shall provide equal or less deflection than Item 1 when applied at the same load to prove that Reinforced by Cold Bonding can reinstate the Beam strength.

Page 10: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Load Test Table

Page 11: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

Beam and Reinforcement Plate Belzona 1121 Super-XL Metal(as Cold Bonding Material)

Page 12: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

Cut of some of Beam surface to Stimulate the corrosion/metal loss

Page 13: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

Grit Blast the Beam / Plate to SA2.5 roughness > 75 microns

Blasted Beam & Plate

Page 14: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

Mix Belzona 1121 Super-XL Metal Apply to the prepared area

Page 15: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

Put thickness shim 2mm on the plate to control the thickness of the Bonding

Bond the plate to prepared area

Page 16: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

Leave the Plate to be cured , then remove the clamp

Page 17: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

(Another Beam) Bond the plate underneath the bottom beam

Page 18: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Beam Preparation

Leave the Plate to be cured , then remove the clamp

Page 19: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Test Equipment

Page 20: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Test Equipments

Page 21: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Load & Deflection Calculation

Page 22: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Load Test

Standard Beam Test , read dial gauge and pressure gauge

Page 23: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Load Test

Reinforced Beam Test (Uniform / Point Load )

Page 24: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Load Test

Reinforced Beam Test (Uniform / Point Load ) , test until failure

Page 25: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TEST

RESULT :

Page 26: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TEST

RESULT :

Page 27: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Test Summary

1. Reinforced beam have less deflection compared to the standard beam thus providing more strength than standard beam.

2. From the calculation , the maximum deflection of Standard Beam length 0.8 m. shall not more than 1.32 mm. From the graph , at 1.32 mm deflection , all reinforced Beam will provide more load bearing capability.

3. At 1.32 mm deflection , Belzona Bonding was still adhere well to the Beam

Page 28: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

TESTING : Test Result

BELZONA Cold Bonding was selected as the repair solution for the corroded beam

Material used : Belzona 1121 Super-XL Metal approx 1,000 kg Belzona 1121 will provide long working time to apply on large metal plate.

Page 29: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Beam and Reinforcement Plate were Grit blast to SA2.5 and

Roughness more than 75 microns

REPAIR APPLICATION

Page 30: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Beam and Reinforcement Plate were Grit blast to SA2.5 and

Roughness more than 75 microns

REPAIR APPLICATION

Page 31: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Belzona 1121 Super-XL Metal as bonding materials

REPAIR APPLICATION

Page 32: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Apply Belzona 1121 on the reinforcement plate and Beam

REPAIR APPLICATION

Page 33: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

Put the 2 mm-thick washer on the plate as the shim

REPAIR APPLICATION

Page 34: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

REPAIR APPLICATION

Adhere the plate to the Beam securing with clamps

Page 35: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

REPAIR APPLICATION

Adhere the plate to the Beam securing with clamps

Page 36: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

REPAIR APPLICATION

Adhere the plate to the Beam securing with clamps

Page 37: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

REPAIR APPLICATION

Adhere the plate to the Beam securing with clamps

Leave the bonding material to cure for 2 hours before removing the clamp.

Page 38: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

BENEFIT of BELZONA Cold Bonding

1. No Hot Work (Except Grit Blasting )

2. No partial plant shutdown

3. Short repair time

4. Economic

Page 39: CDB Corroded Beam Reinforcement in Thai Gas Seperation Plant.pptx

Facilitated by

Corroded Beam ReinforcementCase Study

LESSON LEARN FROM THIS CASE

1. Although not every cases , Cold Bonding Repair can replace many conventional hot work in your plants with comparable efficiency but less risk / less production loss

2. Severe corrosion problem may hide in some places in your plants such as under insulation , under damaged fireproof system , under pipe support , under tank base , splash zone, underwater…etc.

Inspection plan shall also focus on these invisible areas apart from the general areas.