BT12E012IGB-00 TECHNICAL BULLETIN The CE-X remote air-cooled condensers can be matched to ME-X and CASR-X Clivet units for indoor installation, to UCP-DX Data Center units and they can also be connected to other motor-evaporating units. They are available in two acoustic configurations, Standard (ST) and Low Noise (LN), to fulfil also the most severe project requirements respecting the sound levels required. They use axial fans extremely silent and with high heat exchange efficiencies, housed inside aerodynamic conveyors. Thanks to optional devices for the fan speed control, phase cutting or ECOBREEZE type, is possible to increase the energy savings of the entire system, to optimize the combined unit operation and to further increase the silence. All units respect the high quality standards that Clivet guarantees with severe tests during the entire production cycle. CE-X 222-452 SERIES Condenser capacity from 83 kW to 267 kW CE-X REMOTE AIR COOLED CONDENSER FOR OUTDOOR INSTALLATION

Upload: others

Post on 20-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

BT12E012IGB-00

TECHNICAL BULLETIN

The CE-X remote air-cooled condensers can be matched to ME-X and CASR-X Clivet units for indoor installation, to UCP-DX Data Center units and they can also be connected to other motor-evaporating units. They are available in two acoustic configurations, Standard (ST) and Low Noise (LN), to fulfil also the most severe project requirements respecting the sound levels required. They use axial fans extremely silent and with high heat exchange efficiencies, housed inside aerodynamic conveyors. Thanks to optional devices for the fan speed control, phase cutting or ECOBREEZE type, is possible to increase the energy savings of the entire system, to optimize the combined unit operation and to further increase the silence. All units respect the high quality standards that Clivet guarantees with severe tests during the entire production cycle.

CE-X 222-452 SERIES Condenser capacity from 83 kW to 267 kW

CE-X REMOTE AIR COOLED CONDENSER FOR OUTDOOR INSTALLATION

Page 2: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

2

CE-X 222-452

BT12E012GB-00

ST

SOUND PRESSURE LEVEL [dB(A)]

60

40

20

0

LN

6660

80

ULTRA-SILENCE OPERATION The units are available with different functions and accessories, to perfectly integrate them into different types of projects. In particular, the low noise acoustic configuration, using a different fan speed regulation, enables to:

• reduce the external sound emission up to 14 dB; • lower the power absorbed by the fans.

GREAT VERSATILITY IN POSITIONING

The unit offers the maximum versatility for the positioning. In fact it is suitable for vertical installation (horizontal air flow) and can also be installed horizontally (vertical air flow) thanks to the mounting and support optional kit.

BUSINESS ORIENTED The remote condenser is sturdiness and resistant to atmospheric agents. Easy to be matched to the internal units based on different parameters like:

• compactness, where the initial investment cost is preferred also if the operation range is limited;

• low noise level, with special accessories and acoustic configurations

able to control the sound emissions; • efficiency, with more heat exchange surfaces and special accessories

able to modulate the fans speed to optimize the operation of the internal unit.

ADVANCED AEROFOIL FANS

4,000

AIRFLOW [m3/h]

SOUND PRESSURE LEVEL [dB(A)]80

60

40

208,000 12,000 16,000 20,000 24,000

Winglet fan

Traditional fan

The external axial fans are equipped with the innovative Winglet airfoil-vane with integrated baffle, able to increase the aerodynamic efficiency. It results in a consumption reduction of the 10% and a medium sound emission lower of 6 dB than the traditional fans.

USE ALSO IN EXTREMELY COLD CLIMATES

For some applications, like Data Center, it is requested the cooling operation of the internal unit also with low outdoor temperatures. The remote condenser also meets this request thanks to the combination of the fan speed regulator, phase cut type or the very efficient ECOBREEZE, and of the “Winter kit” that includes the heated expansion tank to bypass the direct expansion exchanger and keep the refrigerant pressure under control.

Esempio a scopo illustrativo non in scala

Example referred to 120 kW discharged capacity. sound pressure levels distance 1 meter of the models ST 262, LN 302.

Page 3: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

3

CE-X 222-452

BT12E012GB-00

100 75 50 25 % LOAD

SOUNDPRESSURE LEVEL

OPERATION TIME(EUROVENT)

-8dB(A)

23 %

41 %33 %

3 %

HIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls the flammability. It is a chlorine free refrigerant (HFC) with numerous advantages:

• ODP (Ozone Depletion Potential) = 0

• High volumetric effect thanks to the high coefficient global thermal exchange and to the pressure variation (glide) which is almost nil during the evaporation phase;

• Elevated density and efficiency, with greater compactness of the refrigerant circuit and therefore the responsible use of materials and small refrigerant quantity, for a reduced environmental impact.

HFC-32CH2F2

HFC-125CHF2CF3

EC TECHNOLOGY

THE VALUE OF CONDENSATION CONTROL The refrigerant condensation control:

• this function is mandatory when the internal unit is equipped with more compressors for each circuit. The condensation pressure is therefore kept under control also during operation at partial load;

• It extends the operating field of the internal unit also with low external temperatures;

• it can produce further advantages like the reduction of fan electrical consumptions and improve silence in partial load conditions.

VARIABLE SPEED FANS TO OPTIMIZE THE CONDENSATION

The standard unit is equipped with a free contact for the on/off management of the fans. When the internal unit is Clivet the free contact can be taken directly from it. It is also possible to choose two different fan speed controls:

• Phase cut with automatic management of fan speed by measuring the condensation pressure. Fans are started at the max speed for 5 seconds to grant the correct speed also in presence of predominant winds, or leaves or snow on the blades;

• ECOBREEZE that must be controlled through an external 0-10V signal that in the Clivet standard unit it directly supply by internal unit.

ECOBREEZE ELECTRONICALLY CONTROLLED FAN TECHNOLOGY With electronically controlled ECOBREEZE fans, which do not require inverter, you have: • reduction over 50% of the nominal absorbed power by the unit during

full load operation;

• reduction of the sound pressure up to 8 dB (A) when compared to the full load operation with clear benefit mainly during the night when the load is reduced but noise sensitivity is higher;

• annual reduction of total electric consumption thanks to the part load operation representing 90% of the operation time of a comfort unit.

SUITABLE ALSO FOR AGGRESSIVE ENVIRONMENTS

In the marine environments or with air contaminated by aggressive chemical agents (except sulphurous environments) are available heat exchangers with epoxy coating or copper/copper, keeping unchanged in time the life and the heat transfer capacity.

Page 4: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

4

CE-X 222-452

BT12E012GB-00

STANDARD UNIT SPECIFICATIONS

STRUCTURE Structure made of galvanized and pre-painted steel, with RAL 9001 painted nozzle to better resist to corrosion. The fan nozzle is shaped to avoid the air recirculation and to reduce noise EXTERNAL EXCHANGER finned exchanger, made from copper pipes arranged in staggered rows and mechanically expanded for better adherence to the collar of the fins. The fins are made from aluminium with a special corrugated surface, set a suitable distance apart to ensure maximum heat exchange efficiency. FAN Axial fans diam. 800mm with aluminium die-cast blades, directly coupled to a IP54 three-phase electric motor with external rotor, with thermal protection. Placed into aerodynamic shaped nozzles, to increase efficiency and minimize the noise level, are equipped of protection grilles to avoid accidents. ELECTRICAL PANEL The electrical panel is located inside the unit and is easily accessible thanks to removable panels. The capacity section includes: - terminal block for the fan connection - main line isolator switch - contactor for the fan power The control section includes: - Terminal block to connect the internal unit, with free contacts for

unit ON/OFF (from internal to external unit) and for cumulative alarm (from external to internal unit). The accessory CREFB includes an analogical input 0-10 V for the fan speed management.

CONNECTIONS Gas line connections to be brazed CONFIGURATIONS - ST Standard acoustic configuration (Standard) - LN Low noise configuration ACCESSORI - Copper /copper condenser coil - Copper /Copper / acrylic aluminium condenser coil - Installation coil with up flow configuration - Device for fan consumption reduction of the external section with

variable speed (phase-cutting) - Device for reduction of fan consumption ECOBREEZE - Liquid receiver kit (separately supplied accessories) - Vertical airflow (separately supplied accessories) - Packing with wooden crate - Winter kit (separately supplied accessories) TEST The finned coil is tested at adequate pressure, properly degreased and dried with dry air. The condenser is delivered with a nitrogen holding charge (Max 2 bar).

ACOUSTIC CONFIGURATION: STANDARD (ST) / LOW NOISE (LN)

OPERATING RANGE

STORAGE OPERATION (1)

Min Max Min Max

Standard Unit -40 °C +70°C -25 °C +55°C

Unit with ‘CREFP accessory – Variable speed device to reduce fan consumptions of external section (phase cutting)’

-40 °C +70°C -20 °C (2) +55°C

Unit with accessory ‘CREFB – ECOBREEZE type device to reduce fans consumptions of external section

-40 °C +70°C -25 °C (2) +60°C

The standard unit is equipped with a free contact for on-off fan management. The on-off signal must be supplied externally. The data are referred to the air temperature through the fan. The max temperature can be easily checked by the simplified formula: T [°C] = Text + Pt * 1000 / (Q * 1.2) Text = external air temperature in °C Pt= Heating capacity in kW rejected by the condenser Q = Condenser nominal air flow in l/s

(2) Operating min temperatures are achieved using the Winter Kit accessory.

(1) The min and max operating working temperatures must be controlled after having decided the combination between condenserless unit and remote condenser. In order to operate with air temperatures lower than 10/15 °C it is necessary to take into account the use of accessories to modulate the condensation air flow.

STORAGE: unit not feeded OPERATION (1): feeded and operating unit

Page 5: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

5

CE-X 222-452

BT12E012GB-00

ACOUSTIC CONFIGURATION: STANDARD (ST)

(1) Data referred to 30°C outdoor air temperature and 45°C condensation temperature. Data referred to 25°C de-superheating temperature of and 5°C sub-cooling temperature.

(2) Standard fans at nominal operating conditions.

(3) ‘CREFB fans – Device to reduce external fans consumption ECOBREEZE’ type at nominal operating conditions.

(4) Dimensions referred to the external diameter.

Voltage unbalance: max 2 % Power supply 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

F.L.A. FULL LOAD CURRENT F.L.A. Total A 7.8 7.8 11.7 11.7 15.6 15.6

F.L.I. POWER INPUT

ELECTRICAL DATA ACCESSORY ‘CREFB’ (Device to reduce external fans consumption ECOBREEZE’ type )

Voltage unbalance: max 2 % Power supply 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

ELECTRICAL DATA

Size 222 262 302 362 402 452

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS

F.L.A. - Single External Fan A 4.1 4.1 4.1 4.1 4.1 4.1

F.L.A. - Total A 8.2 8.2 12.3 12.3 16.4 16.4 L.R.A. LOCKED ROTOR AMPERES

L.R.A. - Single External Fan A 14 14 14 14 14 14 F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

F.L.I. - Single External Fan kW 1.9 1.9 1.9 1.9 1.9 1.9 F.L.I. - Total kW 3.9 3.9 5.8 5.8 7.8 7.8

M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value A 28 28 42 42 56 56

GENERAL TECHNICAL SPECIFICATIONS

Size 222 262 302 362 402 452

Cooling capacity 1 kW 82.8 119.5 132.1 175.9 247.3 266.8

EXTERNAL SECTION FANS Number of fans Nr 2 2 3 3 4 4

Fan diameter mm 800 800 800 800 800 800

Fan RPM rpm 880 880 880 880 880 880

Standard air flow l/s 11667 11389 17917 17083 22778 22222 Installed unit power 2 kW 3.2 3.2 4.6 4.8 6.4 6.5 Installed unit power 3 kW 2.6 2.9 4.1 4.2 5.5 5.7

CONNECTIONS Gas connection 4 mm 28 28 35 35 42 42 Liquid connection 4 mm 28 28 35 35 42 42

POWER SUPPLY Standard power supply V 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50

NOISE LEVELS Sound pressure level (1 m) dB(A) 69 68 72 71 73 73

Size 222 262 302 362 402 452

F.L.I. Total A 5.1 5.1 7.7 7.7 10.3 10.3

Page 6: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

6

CE-X 222-452

BT12E012GB-00

35 40 45 50 55 58.5

kW kW kW kW kW kW

20 80.3 114.0 147.2 180.9 214.6 240.6

25 49.1 81.7 115.2 148.4 181.9 208.1

30 - 49.8 82.8 116.0 150.1 174.8

35 - - 50.8 83.3 116.9 142.2

40 - - - 51.7 84.5 109.7

46 - - - - 46.3 70.6

20 116.3 163.5 212.1 259.9 309.4 347.1

25 71.8 119.2 166.0 213.1 262.6 300.3

30 - 73.0 119.5 166.7 215.8 253.0

35 - - 73.5 120.2 169.4 206.1

40 - - - 74.7 122.8 159.0

46 - - - - 67.5 102.2

20 128.6 182.5 236.3 288.9 342.4 384.7

25 78.1 130.8 184.2 237.3 291.0 332.4

30 - 80.1 132.1 185.2 238.1 278.3

35 - - 80.9 133.4 187.1 227.6

40 - - - 82.8 135.1 175.5

46 - - - - 73.8 111.9

20 170.2 239.9 311.5 382.7 454.8 512.6

25 105.4 174.1 243.3 313.8 385.1 441.8

30 - 109.6 175.9 243.7 317.3 371.1

35 - - 110.7 179.2 249.4 301.5

40 - - - 111.5 180.5 234.6

46 - - - - 100.0 151.0

20 239.7 332.3 426.0 516.8 609.2 678.0

25 150.5 245.1 335.2 437.8 521.5 602.3

30 - 152.5 247.3 328.9 431.1 513.4

35 - - 153.0 250.0 342.6 412.3

40 - - - 159.0 251.5 321.1

46 - - - - 144.0 213.1

20 261.2 358.0 452.7 544.1 637.3 717.9

25 165.2 264.8 358.4 454.2 547.4 619.1

30 - 169.3 266.8 352.9 460.7 539.3

35 - - 168.1 267.3 365.7 436.6

40 - - - 175.0 272.8 354.2

46 - - - - 160.1 231.8

362

402

452

Ta(°C) DB

222

262

302

Ta = Outside air temperature (°C) Data refer to the de-superheating temperature of 25 °C and subcooling temperature of 5 °C.

ACOUSTIC CONFIGURATION: STANDARD (ST)

CONDENSER PERFORMANCE

Grandezze

CONDENSING TEMPERATURE (°C)

Page 7: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

7

CE-X 222-452

BT12E012GB-00

ACOUSTIC CONFIGURATION: LOW NOISE (LN)

Voltage unbalance: max 2 % Power supply 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

(1) Data referred to 30°C outdoor air temperature and 45°C condensation temperature. Data referred to 25°C de-superheating temperature of and 5°C sub-cooling temperature.

(2) Standard fans at nominal operating conditions.

(3) ‘CREFB fans – Device to reduce external fans consumption ECOBREEZE’ type at nominal operating conditions.

(4) Dimensions referred to the external diameter.

GENERAL TECHNICAL SPECIFICATIONS

SIZE 222 262 302 362 402 452

Cooling capacity 1 kW 74.3 106.3 117.7 151.6 211.3 226.2

EXTERNAL SECTION FANS Number of fans Nr 2 2 3 3 4 4

Fan diameter mm 800 800 800 800 800 800

Fan RPM rpm 670 670 670 670 670 670

Standard air flow l/s 9722 9444 14583 13750 18333 17778

Installed unit power 2 kW 2.1 2.2 3.1 3.3 4.4 4.5

Installed unit power 3 kW 1.6 1.8 2.3 2.3 3 3

CONNECTIONS Gas connection 4 mm 28 28 35 35 42 42 Liquid connection 4 mm 28 28 35 35 42 42

POWER SUPPLY Standard power supply V 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50

NOISE LEVELS Sound pressure level (1m) dB(A) 64 63 67 66 69 69

ELECTRICAL DATA

SIZE 222 262 302 362 402 452

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS

F.L.A. - Single External Fan A 2.3 2.3 2.3 2.3 2.3 2.3 F.L.A. - Total A 4.6 4.6 6.9 6.9 9.2 9.2

L.R.A. LOCKED ROTOR AMPERES

L.R.A. - Single External Fan A 4.1 4.1 4.1 4.1 4.1 4.1

F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

F.L.I. - Single External Fan kW 1.2 1.2 1.2 1.2 1.2 1.2

F.L.I. - Total kW 2.4 2.4 3.6 3.6 4.8 4.8 M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value A 8.2 8.2 12.3 12.3 16.4 16.4

F.L.A. FULL LOAD CURRENT F.L.A. Total A 7.8 7.8 11.7 11.7 15.6 15.6

F.L.I. POWER INPUT

ELECTRICAL DATA ACCESSORY ‘CREFB’ (Device to reduce external fans consumption ECOBREEZE’ type )

Voltage unbalance: max 2 % Power supply 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

Size 222 262 302 362 402 452

F.L.I. Total A 5.1 5.1 7.7 7.7 10.3 10.3

Page 8: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

8

CE-X 222-452

BT12E012GB-00

35 40 45 50 55 58.5

kW kW kW kW kW kW

20 72.2 102.3 132.8 162.8 192.8 216.7

25 44.4 73.6 103.3 133.2 163.4 186.9

30 - 45.3 74.3 104.3 134.1 157.4

35 - - 45.6 75.1 104.6 127.4

40 - - - 46.1 76.0 98.3

46 - - - - 41.4 63.4

20 103.9 144.0 188.0 230.6 273.7 307.5

25 64.0 104.9 146.6 188.6 231.9 264.9

30 - 65.5 106.3 147.4 190.4 223.0

35 - - 65.6 107.4 149.4 181.5

40 - - - 66.7 108.8 140.8

46 - - - - 59.9 89.7

20 113.9 160.3 209.4 256.1 303.7 341.5

25 69.0 116.3 163.2 210.0 257.4 295.1

30 - 71.0 117.7 164.0 211.1 247.6

35 - - 72.5 118.9 164.2 201.4

40 - - - 72.8 119.4 155.0

46 - - - - 65.3 99.1

20 148.2 207.2 267.4 329.5 391.7 441.3

25 92.3 149.3 210.5 269.5 330.7 379.9

30 - 92.1 151.6 210.2 272.2 320.1

35 - - 93.3 153.1 213.6 259.2

40 - - - 96.8 156.4 199.5

46 - - - - 86.4 130.5

20 207.8 289.5 368.7 449.2 538.1 592.4

25 132.2 209.9 290.2 362.3 459.1 513.7

30 - 132.9 211.3 288.7 374.3 435.5

35 - - 134.7 213.1 295.4 356.2

40 - - - 135.4 215.1 276.0

46 - - - - 122.9 181.7

20 224.7 305.9 387.7 471.2 556.9 613.3

25 142.1 224.0 308.5 396.0 472.7 533.5

30 - 142.7 226.2 308.9 398.9 461.2

35 - - 144.8 229.1 312.3 374.7

40 - - - 146.4 231.8 292.6

46 - - - - 132.6 194.6

362

402

452

Ta(°C) DB

222

262

302

ACOUSTIC CONFIGURATION: LOW NOISE (LN)

CONDENSER PERFORMANCE

Ta = Outside air temperature (°C) Data refer to the de-superheating temperature of 25 °C and subcooling temperature of 5 °C.

Size

CONDENSING TEMPERATURE (°C)

Page 9: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

9

CE-X 222-452

BT12E012GB-00

SOUND LEVELS

ACOUSTIC CONFIGURATION: STANDARD (ST)

ACOUSTIC CONFIGURATION: LOW NOISE (LN)

Size

Sound Power Level (dB) Sound pressure

level Octave band (Hz)

63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)

222 48 46 56 60 63 66 62 58 69 76

262 50 47 57 60 63 66 63 58 68 75

302 51 50 60 63 66 69 66 61 72 78

362 51 49 59 62 65 68 65 60 71 77

402 52 50 60 63 64 69 66 61 73 79

452 52 50 60 63 64 69 66 61 73 79

Sound power level

Size

Sound Power Level (dB) Sound pressure

level Octave band (Hz)

63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)

222 40 38 48 52 55 58 54 50 64 70

262 42 39 50 52 55 58 55 50 63 69

302 43 42 52 56 58 61 58 53 67 72

362 43 41 51 55 57 60 59 53 66 71

402 44 42 52 55 56 65 58 53 69 73

452 44 42 52 55 56 62 28 53 69 73

Sound power level

The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. Please note that when the unit is installed in conditions different from nominal test conditions (e.g. near walls or obstacles in general), the sound levels may undergo substantial variations.

The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. Please note that when the unit is installed in conditions different from nominal test conditions (e.g. near walls or obstacles in general), the sound levels may undergo substantial variations.

Page 10: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

10

CE-X 222-452

BT12E012GB-00

ACCESSORIES

CCCA - COPPER / ALUMINIUM CONDENSING COIL WITH ACRYLIC COVERING

The package heat exchanger finned coils in copper /aluminium with acrylic covering can be used in places with concentrations in the air of saline and moderately aggressive agents.

Attention! - Cooling capacity variation -2.7%

CCCC - COPPER / COPPER CONDENSING COIL

A treatment which offers an optimal thermal exchange and guarantees and protects the finned coil exchangers from corrosion over time. Can be used in settings with very aggressive saline concentrations and other chemical agents in the air thus maintaining the performance of the coils over time.

FAVX - VERTICAL AIR FLOW

Feets for vertical air flow installation, painted steel RAL 9001.

Accessorio fornito separatamente.

CREFP - FAN CONSUMPTION REDUCTION DEVICE OF EXTERNAL SECTION AT VARIABLE SPEED (PHASE CUTTING)

Option used with low outdoor air temperature, enabling the condensation pressure control through the automatic reduction of the fan speed. When the external air temperature is low, a minimum airflow is sufficient to keep the condensation pressure low. Therefore with low outdoor air temperature the fan speed is reduced with consequent reduction of energy consumption. It includes the phase cut type fan speed regulation device, a pressure probe and a pressure transducer on the cooling circuit.

Per le dimensioni dell’unità con opzione ‘FAVX - Flusso aria verticale’ fare riferimento alla sezione ‘Dimensionali’.

The operating temperatures refer to the ‘Operating range’ schedule.

CREFB - ECOBREEZE EXTERNAL SECTION FANS CONSUMPTION REDUCTION DEVICE

This option is used with low outdoor air temperatures, suggested to clearly reduce the electric power consumption of the fans and to limit the sound emissions in the external section of the unit, using high efficiency fans. The ECOBREEZE logic enables to automatically operate the external axial fans with a variable rotation speed according to the condensation pressure. With low outdoor air temperature a minimum air flow is sufficient to keep the condensation pressure low. Therefore with low outdoor air temperature the fan speed is reduced with consequent reduction of electric consumption and of sound emissions. ECOBREEZE option includes axial external fan with electronic control motor (IP54) driven by continuous magnetic commuting of the stator. Being brushless and having a particular power supply increase both efficiency and life time. ECOBREEZE is especially suggested on units working 365 days per year, like on Close Control units.

The operating temperatures refer to the ‘Operating range’ schedule.

This option is not suitable for application in sulphuric environments.

H

SIZE 222 - 262 - 302 - 362 - 402 - 452

H mm 1103

HEIGHT DIMENSIONS OF THE FEET

Page 11: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

11

CE-X 222-452

BT12E012GB-00

LRX - LIQUID RECEIVER KIT

The liquid receiver has the function to constantly grant an adequate quantity of refrigerant to the evaporator, and it enables to compensate possible volume variations due the outdoor temperature. Ideal for applications where the difference in height between the internal unit and remote condenser is above 15m. The kit includes corrosion proof painted steel tank, installation supports, safety valve, Rotalock connections. The device is arranged for the installation beside the unit or, in case of vertical airflow installation, under the unit. (installation made by the Customer).

Accessory separately supplied.

WKX - WINTER KIT

This accessory must be matched to ‘CREFP option – device to reduce the fan consumptions of the external section at variable speed (phase cut)’ or as alternative ‘CREFB . Device to reduce fan consumptions of the external section ECOBREEZE type’.

Accessory separately supplied.

1. Compressor 2. Bypass valve 3. Condenser 4. Liquid receiver

The winter kit is the device that is used to keep an adequate refrigerant pressure (2.030 kPa), when the outdoor air temperature is very low. The option includes the liquid receiver to be positioned indoor and the automatic by pass valve on board of the unit, able to bypass the finned coil towards the liquid receiver.

Device Installtion are encharged to the Client.

Page 12: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

12

CE-X 222-452

BT12E012GB-00

DIMENSIONAL DRAWING : CE-X 222 - 262

(1) ELECTRIC FAN (2) FINNED EXCHANGER (3) FINNED COIL INLET (4) FINNED COIL OUTLET (5) ELECTRICAL PANEL (6) POWER INPUT (7) FAN SPEED CONTROLLER (OPTIONAL) (8) MAIN ISOLATOR SWITCH (9) SUPPORT AND FIXING POINTS (10) FUNCTIONAL CLEARANCES (R) AIR INTAKE (M) AIR SUPPLY

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

SIZE 222 262

W1 Supporting Point Kg 72.3 79.5

W2 Supporting Point Kg 72.3 79.5

W3 Supporting Point Kg 48.2 53

W4 Supporting Point Kg 48.2 53

Shipping weight Kg 241 265

ACOUSTIC CONFIGURATION: STANDARD (ST) / LOW NOISE (LN)

DAA52222_262_0

Data: 18/05/2012

752

648

8048380

800

(10)

Y

(

10)

300 (10)

700 (10)

136

0

Y > 1360

136

0

Y>

580

Y > 680

206 2058 206

1430

13

57

2470

8

6

9

12

4

3

5

7

W1

W4W3

M

R

W2

DRAWING TO CALCULATE ' Y ' (SPACE OF CLEARANCE)

Page 13: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

13

CE-X 222-452

BT12E012GB-00

DIMENSIONAL DRAWING: CE-X 222 - 262 WITH ‘VERTICAL AIR FLOW’ OPTION

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

SIZE 222 262

W1 Supporting Point Kg 63.3 69

W2 Supporting Point Kg 63.3 69

W3 Supporting Point Kg 63.3 69

W4 Supporting Point Kg 63.3 69

Shipping weight Kg 253 276

ACOUSTIC CONFIGURATION: STANDARD (ST) / LOW NOISE (LN)

(1) ELECTRIC FAN (2) FINNED EXCHANGER (3) FINNED COIL INLET (4) FINNED COIL OUTLET (5) ELECTRICAL PANEL (6) POWER INPUT (7) FAN SPEED CONTROLLER (OPTIONAL) (8) MAIN ISOLATOR SWITCH (9) SUPPORT AND FIXING POINTS (10) FUNCTIONAL CLEARANCES (R) AIR INTAKE (M) AIR SUPPLY

DAA52222_262_FAVX_0

Data: 18/05/2012

110

3

132

3

206 2058 206

2470

300 (10)

810

(1

0)

700 (10)

81

0

(1

0)30 1355 30

1357

1415

108

5Y

>

13

57

M

R9

6

87

5

3 4

2

1

W4W3

W2W1

DRAWING TO CALCULATE ' Y ' (SPACE OF CLEARANCE)

Page 14: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

14

CE-X 222-452

BT12E012GB-00

(1) ELECTRIC FAN (2) FINNED EXCHANGER (3) FINNED COIL INLET (4) FINNED COIL OUTLET (5) ELECTRICAL PANEL (6) POWER INPUT (7) FAN SPEED CONTROLLER (OPTIONAL) (8) MAIN ISOLATOR SWITCH (9) SUPPORT AND FIXING POINTS (10) FUNCTIONAL CLEARANCES (R) AIR INTAKE (M) AIR SUPPLY

DIMENSIONAL DRAWING : CE-X 302 - 362

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

ACOUSTIC CONFIGURATION: STANDARD (ST) / LOW NOISE (LN)

SIZE 302 362

W1 Supporting Point Kg 70.8 78.6

W2 Supporting Point Kg 70.8 78.6

W3 Supporting Point Kg 70.8 78.6

W4 Supporting Point Kg 47.2 52.4

Shipping weight Kg 354 393

W5 Supporting Point Kg 47.2 52.4

W6 Supporting Point Kg 47.2 52.4

DAA52302_362_0

752

648

8048380

800

(

10

Y

(10)

300 (10)

700 (10

136

0

Y > 1360

136

0

Y>

580

Y > 680

206 206

143

0

135

7

7

5

3

4

2 1

16221785

3820

8

6

9

W2W1

M

)

)R

W3

W6W5W4

Data: 18/05/2012

DRAWING TO CALCULATE ' Y ' (SPACE OF CLEARANCE)

Page 15: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

15

CE-X 222-452

BT12E012GB-00

DIMENSIONAL DRAWING : CE-X 302 - 362 WITH ‘VERTICAL AIR FLOW’ OPTION

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

ACOUSTIC CONFIGURATION: STANDARD (ST) / LOW NOISE (LN)

(1) ELECTRIC FAN (2) FINNED EXCHANGER (3) FINNED COIL INLET (4) FINNED COIL OUTLET (5) ELECTRICAL PANEL (6) POWER INPUT (7) FAN SPEED CONTROLLER (OPTIONAL) (8) MAIN ISOLATOR SWITCH (9) SUPPORT AND FIXING POINTS (10) FUNCTIONAL CLEARANCES (R) AIR INTAKE (M) AIR SUPPLY

DAA52302_362_FAVX_0

Data: 18/05/2012

SIZE 302 362

W1 Supporting Point Kg 62 68.3

W2 Supporting Point Kg 62 68.3

W3 Supporting Point Kg 62 68.3

W4 Supporting Point Kg 62 68.3

Shipping weight Kg 372 410

W5 Supporting Point Kg 62 68.3

W6 Supporting Point Kg 62 68.3

13

23

206

3820

300 (10)

810

(10)

700 (10)

81

0

(1

0)

30 1355 30

1357

1415

135

7

10

85

Y>

110

3

1785 1622 206

M

R9

6

87

5

3 4

2

1

W1

W4 W5 W6

W3W2

DRAWING TO CALCULATE ' Y ' (SPACE OF CLEARANCE)

Page 16: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

16

CE-X 222-452

BT12E012GB-00

DIMENSIONAL DRAWING : CE-X 402 - 452

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

ACOUSTIC CONFIGURATION: STANDARD (ST) / LOW NOISE (LN)

(1) ELECTRIC FAN (2) FINNED EXCHANGER (3) FINNED COIL INLET (4) FINNED COIL OUTLET (5) ELECTRICAL PANEL (6) POWER INPUT (7) FAN SPEED CONTROLLER (OPTIONAL) (8) MAIN ISOLATOR SWITCH (9) SUPPORT AND FIXING POINTS (10) FUNCTIONAL CLEARANCES (R) AIR INTAKE (M) AIR SUPPLY

DAA52402_452_0

Data: 18/05/2012

SIZE 402 454

W1 Supporting Point Kg 78.2 83.4

W2 Supporting Point Kg 78.2 83.4

W3 Supporting Point Kg 78.2 83.4

W4 Supporting Point Kg 78.2 83.4

Shipping weight Kg 521 556

W5 Supporting Point Kg 52.1 55.6

W6 Supporting Point Kg 52.1 55.6

W7 Supporting Point Kg 52.1 55.6

W8 Supporting Point Kg 52.1 55.6

752

648

8048380

800

(1

0)

Y

(1

0)

300 (10)

700

1360

Y > 1360

1360

Y>

580

Y > 680

206

143

0

1357

162013501788206

5170

M

W8

9

8

6

12

4

3

5

7

(10)R

W1

W5

W2

W6

W3 W4

W7

DRAWING TO CALCULATE ' Y ' (SPACE OF CLEARANCE)

Page 17: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

17

CE-X 222-452

BT12E012GB-00

DIMENSIONAL DRAWING : CE-X 402 - 452 WITH ‘VERTICAL AIR FLOW’ OPTION

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

ACOUSTIC CONFIGURATION: STANDARD (ST) / LOW NOISE (LN)

(1) ELECTRIC FAN (2) FINNED EXCHANGER (3) FINNED COIL INLET (4) FINNED COIL OUTLET (5) ELECTRICAL PANEL (6) POWER INPUT (7) FAN SPEED CONTROLLER (OPTIONAL) (8) MAIN ISOLATOR SWITCH (9) SUPPORT AND FIXING POINTS (10) FUNCTIONAL CLEARANCES (R) AIR INTAKE (M) AIR SUPPLY

DAA52402_452_FAVX_0

Data: 18/05/2012

SIZE 402 454

W1 Supporting Point Kg 68.1 72.4

W2 Supporting Point Kg 68.1 72.4

W3 Supporting Point Kg 68.1 72.4

W4 Supporting Point Kg 68.1 72.4

Shipping weight Kg 545 579

W5 Supporting Point Kg 68.1 72.4

W6 Supporting Point Kg 68.1 72.4

W7 Supporting Point Kg 68.1 72.4

W8 Supporting Point Kg 68.1 72.4

132

3

5170

300 (10)

810

(

10)

700 (10)

810

(

10)

30 1355 30

1357

1415

110

3

206

10

85Y

>

13

57

162013501788206

M

R9

6

87

5

3 4

2

1

W1

W5

W2 W3

W6 W7 W8

W4

DRAWING TO CALCULATE ' Y ' (SPACE OF CLEARANCE)

Page 18: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

18

CE-X 222-452

BT12E012GB-00

PAGE INTENTIONALLY LEFT BLANK

Page 19: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

19

CE-X 222-452

BT12E012GB-00

INDEX

► FEATURES AND BENEFITS Pag. 2-3

► STANDARD UNIT SPECIFICATIONS - OPERATING RANGE Pag. 4

► GENERAL TECHNICAL SPECIFICATIONS- STANDARD ACOUSTIC CONFIGURATION (ST) Pag. 5

► CONDENSER PERFORMANCE - STANDARD ACOUSTIC CONFIGURATION (ST) Pag. 6

► GENERAL TECHNICAL SPECIFICATIONS - LOW NOISE ACOUSTIC CONFIGURATION (LN) Pag. 7

► CONDENSER PERFORMANCE - LOW NOISE ACOUSTIC CONFIGURATION (LN) Pag. 8

► SOUND LEVELS Pag. 9

► ACCESSORIES Pag. 10-11

► DIMENSIONAL DRAWING Pag. 12-17

Page 20: CE-Xatrina.org/images/kondansing/3.pdfHIGH EFFICIENT REFRIGERANT R410A is the mix of two refrigerants used in equal parts: R32 that supplies the thermal capacity and R125 that controls

I d

ati

con

tenu

ti ne

l pre

sen

te b

olle

ttin

o n

on s

ono

imp

egn

ativ

i e p

oss

ono

ve

nire

cam

bia

ti da

l co

stru

ttore

sen

za o

bb

ligo

di p

rea

vvis

o.

R

ipro

du

zio

ne

an

che

pa

rzia

le V

IET

AT

A ©

Cop

yrig

ht

- C

LIV

ET

S.p

.A.

- F

eltr

e (

BL

) -

Italia

CLIVET SPA Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - [email protected] CLIVET UK LTD 4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - [email protected] CLIVET ESPAÑA S.A. Parque Empresarial Villapark, Avda. Quitapesares 50 - 28670, Villaviciosa de Odón, Madrid - España Tel. + 34 91 6658280 - Fax + 34 91 6657806 - [email protected] CLIVET GmbH Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - [email protected] CLIVET NEDERLAND B.V. Siliciumweg 20a, 3812 SX Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - [email protected] CLIVET RUSSIA Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - [email protected] CLIVET MIDEAST FZC Rep Office: PO Box 28178 - Light industrial unit #10 -Dubai Silicon Oasis - Dubai,UAE Tel. + 97 14 3208499 - Fax + 97 14 3208216 - [email protected] CLIVET AIRCONDITIONING SYSTEMS (P) LTD 3C3, Gundecha Onclave, Kherani Road, Saki Naka, Andheri (East), Mumbai 400 072 (INDIA) Tel. + 91 - 22 - 6193 7000 - Fax + 91 - 22 - 6193 7001 - [email protected]

www.clivet.com