ceiling cassette - daikin malaysia · 1 mff0515 1. model name fc type of air-conditioner ff :...

69
Ceiling Cassette TM-FFC-0515-C TECHNICAL MANUAL

Upload: phungkien

Post on 08-Aug-2018

248 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

Ceiling Cassette

TM-FFC-0515-CTECHNICAL MANUAL

Page 2: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

1. Model Name .......................................................................................................... 1 2. Features ................................................................................................................ 2

3. Specifications ........................................................................................................ 3 GeneralData .............................................................................................. 3 SafetyDevices .......................................................................................... 19

4. ApplicationInformation ........................................................................................ 20 OperatingRange ...................................................................................... 20 Controllers ................................................................................................ 24

5. Installations .......................................................................................................... 31

6.WiringDiagrams .................................................................................................. 44

7. Servicing&Maintenance .................................................................................... 48

8. Troubleshooting .................................................................................................. 50

9. DimensionalData ................................................................................................ 54

10.ExplodedView&PartList ................................................................................... 57

Note:Installationandmaintenancearetobeperformedonlybyqualifiedpersonnelwhoare familiarwithlocalcodesandregulations,andexperiencedwiththistypeofequipment.

Caution:Sharpedgesandcoilsurfacesareapotentialinjuryhazard.Avoidcontactwiththem.

Warning:Movingmachineryandelectricalpowerhazard.Maycauseseverepersonnel injuryordeath.Disconnectandlockoffpowerbeforeservicingequipment.

TableofContents

Page 3: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

1

TM-F

FC-0

515-

C

1. Model Name

FC

Type Of Air-Conditioner

FF : Ceiling Cassette (Capacity Index 10/15)FC : Ceiling Cassette (Capacity Index 20-50)

Series

C : C SeriesA2 : A2 Series

Power Supply

V1 : Single Phase, 220-240V, 50Hz

RefrigerantBlank : R22N : R410A

Capacity Index

20 : Based On Btu/hr

20 A2 V1

Indoor

R 20 C V1

Outdoor

Type Of Air-Conditioner

R : Single Split Condensing Unit

Series

F : F SeriesC : C Series

Power Supply

V1 : Single Phase, 220-240V, 50HzY1 : Three Phase, 380-415V, 50Hz

Refrigerant

Blank : R22N : R410A

Capacity Index

20 : Based On the Btu/hr

Page 4: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

2

TM-F

FC-0

515-

C

2. Features

Ultra Slim New Stylish Design ProfileThisunitiscontemporaryindesignandmatcheventhemostuptodateinteriordecor.Theslim,(only20mmforC-series,andonly28mmforA2-series)androundprofilefrontpanelofthisunitaddsatouchofelegancetoeverydecor.

Turbo Mixed Flow FanInnovativedesignofhighlyefficientturbofanproducesanevenaircirculationinalldirection.

Built-in High Head Drain PumpTheunithasabuilt-inhighheaddrainpumpupto700mmtoprovideandensuresmoothnessdrainageofcondensatewater.

Strong and RobustTheunitisbuiltfromstrongcasingmaterialandrobustpartstoensurelonglastingreliableservice.ThedrainpanismadefromthePOLYSTYRENEwithaplasticcoatingonthesurfacetoensurenoleakingandcondensationoccur.

Friendly ServiceabilityTheairfilter,electricalparts,fan,fanmotoranddrainpumpcanallbeinspectedandreplacedfromthebottomoftheunitbysimplyremovingtheairintakegrille.ThePOLYSTYRENEdrainpanandtheheatexchangercoilscanberemovedfromtheuniteasilybyremovingthefrontpanel.

Microcomputer Remote ControllerTheincorporatedmicroprocessoroffersmoreaccuratecontrolandwiththefollowingextrafeatures:•Fanmotorspeedcanbesetathigh/medium/loworautomatic.•Timeron/off-theunitcanbepre-settoswitchonandoffautomatically.•Electronicthermostat-roomtemperatureispreciselycontrolled,resultinginenergysavingandincreasecomfort.

Wireless Remote ControllerThecompactwirelessremotecontrollermakesitpossibletooperatetheairconditioneranywherewithinthe room.

Negative Ion GeneratorBalancingtheionizationinyourhometocombattheillfeelingsassociatedwithourstressfullifestylesandcreatetherefreshingenvironmentresemblingthenature.

Page 5: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

3

TM-F

FC-0

515-

C

3.Specifications

Specification (R22)Ceiling Cassette Type - FF-C Series

FF10CV1

R10CV1

FF15CV1

R15CV1

Btu/h 10000 13000

W 2930 3810

0.77 0.77

W 905 1190

A 3.80 5.30

Btu/hr/ W 11.05 10.92

V/Ph/Hz

kg/Ib 0.63 / 1.39 0.60 / 1.32

l/s / CFM 194 / 410 194 / 410

l/s / CFM 170 / 360 170 / 360

l/s / CFM 156 / 330 156 / 310

dBA 41 / 38 / 35 41 / 38 / 34

mm/in

mm/in

kg/Ib

mm/in

mm/in

mm/in

V/Ph/Hz

W 55 65

A 0.24 0.29

W 19 23

790 805

690 720

620 625

mm/in

mm/in

mm/in

m²/ft²

1 2

16 20

pc

LENGTH mm/in

WIDTH mm/in

THICKNESS mm/in

PANEL MATERIAL

UNIT

AIR FLOW

HIGH

EER

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

POWER SOURCE 220 - 240 / 1/ 50

INDUCTION

IP20

316X630X630 (126X690X716) / 12.4X24.8X24.8 (5X27.2X28.2)

19.1 / 3/4

15.5 + 2 / 34 + 4

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITY

NOMINAL TOTAL INPUT POWER

NOMINAL RUNNING CURRENT - 1Ø [3Ø]

SENSIBLE HEAT FACTOR

TYPE

INDEX OF PROTECTION (IP)

PACKING DIMENSION (PANEL)

UNIT WEIGHT (UNIT + PANEL)

CONDENSATE DRAIN SIZE

DRIVE DIRECT

MATERIAL ABSG20

REFRIGERANT TYPE R22

REFRIGERANT CHARGE

QUANTITY

FAN

IND

OO

R U

NIT

CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)

OPERATION WIRELESS OR WIRED REMOTE CONTROL

QUANTITY 1

THICKNESS 0.23 / 0.009

TUBE

THICKNESS 0.10 / 0.004

DIAMETER 315 / 12.4

LENGTH

TYPE WASHABLE SARANET FILTER

QUANTITY 1

TYPE

FIN

TURBO FAN

MEDIUM

LOW

SOUND PRESSURE LEVEL (H/M/L)

UNIT DIMENSION (WITH PANEL) H X W X D

H X W X D

250X570X570(295X640X640) / 9.8X22.4X22.4(11.6X25.2X25.2)

1

ROW

FIN PER INCH

FACE AREA

163 / 6.4

MATERIAL SEAMLESS INNER GROOVE COPPER

DIAMETER 7.0/0.276

MATERIAL ALUMINIUM (SLIT FIN)

INSULATION GRADE

POWER SOURCE 220 - 240 / 1/ 50

CLASS B

RATED INPUT POWER

RATED RUNNING CURRENT

MOTOR OUTPUT

POLES 6

AIR QUALITY FILTER

SPEED

COIL

SIZE

367.5 / 14.5

381.0 / 15.0

20.8 / 0.8

0.25

FAN MOTOR

CASINGABS

MATERIAL GALVANIZED STEEL

HIGH

RPMMEDIUM

LOW

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 6: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

4

TM-F

FC-0

515-

C

Specification (R22)Ceiling Cassette Type - FF-C Series (Continued)

FF10CV1

R10CV1

FF15CV1

R15CV1

l/s / CFM

dBA 46 49

mm/in

mm/in

kg/Ib

mm/in

mm/in 9.52 / 3/8 12.7 / 1/2

mm/in

V/Ph/Hz

W 52 74

A 0.23 0.33

W 19 30

RPM 730 860

cm³ / fl.oz. 320 / 10.82 350 / 11.83

V/Ph/Hz

µF

W 798 1051

A 3.33 4.68

A 19 25

mm/in

mm/in

mm/in

CASING UNIT

FLARE VALVE

SIZELIQUID 6.35 / 1/4

OU

TDO

OR

UN

IT

AIR FLOW 453 / 960

SOUND PRESSURE LEVEL

UNIT DIMENSION

DIAMETER

30

401 / 15.8

MODELINDOOR UNIT

OUTDOOR UNIT

INDEX OF PROTECTION (IP) IP23

INSULATION GRADE CLASS B

RATED INPUT POWER

RATED RUNNING CURRENT

MOTOR OUTPUT

MOTOR SPEED

INSULATION GRADE E

GALVANIZED STEELMATERIAL

MATERIAL SEAMLESS INNER GROOVE COPPER

DIAMETER 7.0 / 0.276

MATERIAL ALUMINIUMCOIL

THICKNESS 0.23 / 0.009

TUBE

THICKNESS 0.11 / 0.004

FIN PER INCH 20

FIN FACE AREA 0.35/3.82

ROW 1

FAN

QUANTITY 1

GAS

TYPE PROPELLER

DRIVE DIRECT

QUANTITY 1

MATERIAL ASG20

H X W X D 596X803X323 / 23.5X31.6X12.7

UNIT WEIGHT 28 / 61.7

PIPECONNECTION

TYPE

543X700X250 / 21.4X27.6X9.8

POWER SOURCE 220 - 240 / 1/ 50

POWER SOURCE 220 - 240 / 1/ 50

CAPACITOR

PACKING DIMENSION

H X W X D

POLES 6

COMPRESSOR

TYPE ROTARY

OIL TYPE SUNISO 4GSI/FREOL-K56

OIL AMOUNT

RATED INPUT POWER

FAN MOTOR

TYPE INDUCTION

m²/ft²

LOCKED ROTOR AMP - 1Ø [3Ø]RATED RUNNING CURRENT- 1Ø [3Ø]

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 7: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

5

TM-F

FC-0

515-

C

Specification (R22)Ceiling Cassette Type - FC-A2 Series

R18CV1 R20CV1 R20CV1 R25CV1

Btu/h 18000 20000 22000 25000

W 5275 5862 6448 7327

0.81 0.79 0.70 0.71

W 1773 2023 2146 2809

A 7.75 8.92 9.21 12.57

Btu/hr/ W 10.15 9.89 10.25 8.90

V/Ph/Hz

kg/Ib 0.90 / 1.98 0.83 / 1.83 1.13 / 2.49 1.1 / 2.43

l/s / CFM

l/s / CFM

l/s / CFM

l/s / CFM

dBA

mm/in

mm/in

kg/Ib

mm/in

mm/in

mm/in

V/Ph/Hz

W

A

W

mm/in

mm/in

mm/in

m²/ft²

pc

LENGTH mm/in

WIDTH mm/in

THICKNESS mm/in

PANEL MATERIAL

UNIT

330

300

INNER GROOVE COPPER

7.0 / 0.28

0.23 / 0.009

ALUMINIUM (SLIT FIN)

0.1 / 0.004

0.39 / 4.20

2

330

380

R22

4 WAY AUTOMATIC LOUVER (UP & DOWN)

WIRELESS OR WIRED REMOTE CONTROL

FC25A2V1

390 / 830

42 / 39 / 35 / 32

26+4 / 57+9

290 / 615

250 / 525

200 / 430

300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)

GALVANIZED STEEL

TURBO

19.1 / 3/4

1

QUANTITYAIRQUALITY

AIRFILTER

SIZE

MATERIAL

WASHABLE SARANET FILTER

NEGATIVE IONS

1

POWER SOURCE

IND

OO

R U

NIT

TYPE

FIN PER INCH

REFRIGERANT CHARGE

FANMOTOR

RPM

REFRIGERANT TYPE

AIR DISCHARGE

RATED INPUT POWER

CONTROL

INDEX OF PROTECTION (IP)

INSULATION GRADE

AIR FLOW

PACKING DIMENSION ( PANEL)

OPERATION

SOUND PRESSURE LEVEL (H/M/L/SL)

FAN

TYPE

CONDENSATE DRAIN SIZE

UNIT DIMENSION (WITH PANEL)

H X W X D

220 - 240 / 1/ 50

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITY

NOMINAL TOTAL INPUT POWER

NOMINAL RUNNING CURRENT - 1Ø [3Ø]

SENSIBLE HEAT FACTOR

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE

FC20A2V1

EER

POWER SOURCE

DIAMETER

THICKNESS

ROW

MATERIAL

THICKNESS

FACE AREA

COIL

SUPER LOW

CASING

TREATMENT

FIN

TYPE

MATERIAL

SUPER LOW

HIGH

LOW

UNIT WEIGHT (UNIT + PANEL)

H X W X D

MEDIUM

QUANTITY

MATERIAL

DRIVE

DIAMETER

LENGTH

RATED RUNNING CURRENT

POLES

MOTOR OUTPUT

TUBE

QUANTITY

SPEED

HIGH

MEDIUM

LOW

486 / 19.1

172 / 6.8

INDUCTION

1

IP20

B

220 - 240 / 1 / 50

161

340 / 730

39 / 36 / 33 / 28

265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.6X36.6X36.6)

26+4 / 57+9

18

576 / 22.7

556 / 21.9

22 / 0.87

HIPS (PLASTIC)

ASG10

DIRECT

0.71

20

6

420

370

350 / 740

280 / 595

230 / 495

200

0.94

30

470

420

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 8: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

6

TM-F

FC-0

515-

C

Specification (R22)Ceiling Cassette Type - FC-A2 Series (Continued)

l/s / CFM 755 / 1600

dBA 52

mm/inmm/inkg/Ib 50/110

mm/inmm/in

DIAMETER mm/in

V/Ph/HzW 121

A 0.53

W 60

RPM 840

cm³ / fl.oz.

V/Ph/HzµF 40

8

35 45

W 1535 1785 1869

7.93

2488

A 6.7 7.87 11.1

A 36 41 56

mm/inmm/in

mm/inm²/ft²

CASING UNIT

15.88 / 5/8

654X855X328 / 25.7X33.7X12.9

43 / 94.8

TYPE

INDEX OF PROTECTION (IP)

SIZE

MATERIAL

FACE AREA

MATERIAL

COMPRESSOR

MOTOR OUTPUT

POLES

LOCKED ROTOR AMP - 1Ø [3Ø]

COIL

PACKING DIMENSION

MODELINDOOR UNIT

OUTDOOR UNIT

OU

TDO

OR

UN

IT

FAN MOTOR

PIPECONNECTION

TYPE

H X W X D

AIR FLOW

UNIT DIMENSION

FAN

SOUND PRESSURE LEVEL

MATERIAL

MATERIAL

ROW

OIL AMOUNT

TYPE

DIAMETER

UNIT WEIGHT

INSULATION GRADE

H X W X D

RATED RUNNING CURRENT

OIL TYPE

POWER SOURCERATED INPUT POWER

QUANTITY

DRIVE

QUANTITY

GASLIQUID

TYPE

THICKNESS

FIN PER INCH

FIN

POWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENT- 1Ø [3Ø]

TUBETHICKNESS

INSULATION GRADE

MOTOR SPEED

614 / 1300

5152

693X990X415 / 27.3X39.0X16.3

9.52 / 3/86.35 / 1/4

INDUCTION

220 - 240 / 1 / 50

FLARE VALVE

PROPELLER

1

ASG20

DIRECT

793X990X415 / 31.2X39.0X16.3

756X855X328 / 29.8X33.7X12.9

1

20

455 / 17.9

SUNISO 4GSI / FREOL K56J ATMOS NM56M / SUNISO 4GDID

ALUMINIUM

0.11 / 0.004

0.51 / 5.47

GALVANIZED STEEL

1

77

0.34

32

0.61 / 6.58

IP23

CLASS F

6

SEAMLESS INNER GROOVE COPPER

7.00 / 0.276

0.23 / 0.009

680

600 / 20.3 700 / 24

E

220 - 240 / 1/ 50

ROTARY

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

R18CV1 R20CV1 R20CV1 R25CV1FC25A2V1FC20A2V1

Page 9: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

7

TM-F

FC-0

515-

C

Specification (R22)Ceiling Cassette Type - FC-A2 Series

FC40A2V1R28CV1 R30CV1 R35DV1

Btu/h 28000 30000 35000W 8206 8792 10258

0.75 0.75 0.70W 2760 3200 3360A 12.42 14.32 15.79

Btu/hr/ W 10.14 9.38 10.42

V/Ph/Hz

kg/Ib 1.95 / 4.29 2.23 / 4.91 2.00 / 4.41

l/s / CFM 490 / 1030l/s / CFM 410 / 860l/s / CFM 350 / 740l/s / CFM 295 / 620

dBA 47 / 44 / 40 / 36mm/in 300X820X820(385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)mm/in 335X916X916(124X1016X1016) / 13.2X36.1X36.1(4.9X40.0X40.0)kg/Ib 32+4 / 71+9

mm/in

mm/inmm/in

V/Ph/HzW 176A 0.79W 60

680580510435

mm/inmm/in 0.23 / 0.009

mm/inm²/ft² 0.46 / 4.97

20

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

PANEL MATERIALUNIT

INNER GROOVE COPPER7.0 / 0.28

ALUMINIUM (SLIT FIN)0.1 / 0.004

0.39 / 4.10

R22

4 WAY AUTOMATIC LOUVER (UP & DOWN)WIRELESS OR WIRED REMOTE CONTROL

FC30A2V1

420 / 890

43 / 39 / 36 / 34

26+4 / 57+9300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)

INDOOR CAP. TUBE

GALVANIZED STEEL

TURBO19.1 / 3/4

1

QUANTITYAIRQUALITY

AIRFILTER

SIZE

MATERIAL

WASHABLE SARANET FILTERNEGATIVE IONS

1

POWER SOURCE

IND

OO

R U

NIT

TYPE

FIN PER INCH

REFRIGERANT CHARGE

FANMOTOR

RPM

REFRIGERANT TYPE

AIR DISCHARGE

RATED INPUT POWER

CONTROL

INDEX OF PROTECTION (IP)INSULATION GRADE

AIR FLOW

PACKING DIMENSION ( PANEL)

OPERATION

SOUND PRESSURE LEVEL (H/M/L/SL)

FAN

TYPECONDENSATE DRAIN SIZE

UNIT DIMENSION (WITH PANEL)H X W X D

220 - 240 / 1 / 50

MODEL INDOOR UNITOUTDOOR UNIT

NOMINAL COOLING CAPACITY

NOMINAL TOTAL INPUT POWERNOMINAL RUNNING CURRENT - 1Ø [3Ø]

SENSIBLE HEAT FACTOR

REFRIGERANT CONTROL (EXPANSION DEVICE)EER

POWER SOURCE

DIAMETER

THICKNESS

ROW

MATERIAL

THICKNESS

FACE AREA

COIL

SUPER LOW

CASING

TREATMENT

FIN

TYPE

MATERIAL

SUPER LOW

HIGH

LOW

UNIT WEIGHT (UNIT + PANEL)

H X W X D

MEDIUM

QUANTITYMATERIALDRIVEDIAMETERLENGTH

RATED RUNNING CURRENT

POLESMOTOR OUTPUT

TUBE

QUANTITY

SPEED

HIGH MEDIUMLOW

486 / 19.1172 / 6.8

INDUCTION1

IP20 B

220 - 240 / 1 / 50

265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.8X36.6X36.6)

243 / 515

3220

576 / 22.7556 / 21.922 / 0.87

HIPS (PLASTIC)

630530470415

1550.6850

368 / 780290 / 615

ASG10DIRECT

6

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 10: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

8

TM-F

FC-0

515-

C

Specification (R22)Ceiling Cassette Type - FC-A2 Series (Continued)

l/s / CFM 808 / 1712 1605 / 3400

dBA 54 56 58

mm/in 852x1030x400 / 33.5x40.6x15.7

mm/in 1010x1180x514 / 39.8x46.5x20.2

kg/Ib 78 / 172

mm/inmm/in 19.05 / 3/4

DIAMETER mm/in 610 / 24

IP54

CLASS F

V/Ph/Hz

W 124 257

A 0.54 1.10

W 66 66 145

RPM 874 874 625

8

SCROLL

SUNISO 3GS

cm³ / fl.oz. 900 / 30 1242 / 42

B

V/Ph/HzµF 60 60 60

W 2481 2921 2927

A 11.2 13.1 13.9

A 62 66 97

mm/in 9.52 / 0.375

0.28/ 0.011mm/inALUMINIUM (CORRUGATED)

mm/inm²/ft² 0.87 / 9.36

16

CASING UNIT

15.88 / 5/8

57 / 126

TYPE

INDEX OF PROTECTION (IP)

SIZE

MATERIAL

FACE AREA

MATERIAL

COMPRESSOR

MOTOR OUTPUT

POLES

LOCKED ROTOR AMP - 1Ø [3Ø]

COIL

PACKING DIMENSION

MODELINDOOR UNIT

OUTDOOR UNIT

OU

TDO

OR

UN

IT

FANMOTOR

PIPECONNECTION

TYPE

H X W X D

AIR FLOW

UNIT DIMENSION

FAN

SOUND PRESSURE LEVEL

MATERIAL

MATERIAL

ROW

OIL AMOUNT

TYPE

DIAMETER

UNIT WEIGHT

INSULATION GRADE

H X W X D

RATED RUNNING CURRENT

OIL TYPE

POWER SOURCERATED INPUT POWER

QUANTITY

DRIVE

QUANTITY

GASLIQUID

TYPE

THICKNESS

FIN PER INCH

FIN

POWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENT- 1Ø [3Ø]

TUBETHICKNESS

INSULATION GRADE

MOTOR SPEED

9.52 / 3/8

INDUCTION

220 - 240 / 1 / 50

FLARE

PROPELLER

1

ASG20

DIRECT

793x990x416 / 31.2x39.0x16.4

756x855x328 / 29.8x33.7x12.9

455 / 18

ATMOS NM32A1

ALUMINIUM (RAISE LANCE)

18

0.10 / 0.004

0.61 / 6.58

GALVANIZED STEEL

1

2 1

IP23

6

INNER GROOVE COPPER

7.00 / 0.276

0.23 / 0.009

E

220 - 240 / 1 / 50

ROTARY TWIN ROTARY

SUNISO 4GSI

1050 / 36

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

FC40A2V1

R28CV1 R30CV1 R35DV1FC30A2V1

Page 11: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

9

TM-F

FC-0

515-

C

Specification (R22)Ceiling Cassette Type - FC-A2 Series

Btu/h

W

W

A

Btu/hr/ W

V/Ph/Hz

kg/Ib

l/s / CFM

l/s / CFM

l/s / CFM

l/s / CFM

dBA

mm/in

mm/in

kg/Ib

mm/in

mm/inmm/in

V/Ph/HzW

A

W

mm/in

mm/in

mm/in

m²/ft²

pc

LENGTH mm/in

WIDTH mm/in

THICKNESS mm/in

PANEL MATERIALUNIT

AIR FLOW

HIGH

EER

REFRIGERANT CONTROL (EXPANSION DEVICE)

POWER SOURCE

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITY

NOMINAL TOTAL INPUT POWER

NOMINAL RUNNING CURRENT - 1Ø [3Ø]

SENSIBLE HEAT FACTOR

TYPE

INDEX OF PROTECTION (IP)

PACKING DIMENSION (PANEL)

UNIT WEIGHT (UNIT + PANEL)

CONDENSATE DRAIN SIZE

DRIVEMATERIAL

REFRIGERANT TYPE

REFRIGERANT CHARGE

QUANTITY

FAN

IND

OO

R U

NIT

CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)

OPERATION WIRELESS OR WIRED REMOTE CONTROL

QUANTITY

THICKNESS 0.23 / 0.009

TUBE

THICKNESS

DIAMETERLENGTH

TYPE WASHABLE SARANET FILTER

QUANTITY

TYPE

FIN

MEDIUM

LOW

SUPER LOW

SOUND PRESSURE LEVEL (H/M/L/SL)

UNIT DIMENSION (WITH PANEL) H X W X D

H X W X D

ROW

FIN PER INCH

FACE AREA

MATERIAL INNER GROOVE COPPER

DIAMETER 7.0 / 0.276

MATERIAL ALUMINIUM (SLIT FIN)

INSULATION GRADE

POWER SOURCERATED INPUT POWER

RATED RUNNING CURRENT

MOTOR OUTPUT

POLES 6

AIR QUALITY FILTER

SPEED

COIL

SIZE

FAN MOTOR

CASINGMATERIAL

HIGH

RPMMEDIUMLOW

SUPER LOW

2.48 / 5.47 2.55 / 5.62

176 221

0.79 0.97

60 100

680 780

580 680

510 620

435 530

335X916X916(124X1016X1016) / 13.2X36.1X36.1(4.9X40.0X40.0)

300X820X820 (385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)

FC40A2V1

R40DY1

FC50A2V1

R50DY1

40000 50000

11723 14654

0.72 0.72

3600 4550

[6.10] [7.90]

11.11 10.99

R22

INDOOR CAP. TUBE

380 - 415 / 3 / 50

490 / 1030 570 / 1200

410 / 860 490 / 1030

350 / 740 440 / 930295 / 620 370 / 780

47 / 44 / 40 / 36 49 / 45 / 43 / 39

ASG 101

486 / 19.1

172 / 6.8

1

CLASS B

19.1 / 3/4

IP20

INDUCTION

TURBO

DIRECT

220 - 240 / 1/ 50

32+4 / 71+9

0.10 / 0.004 0.11 / 0.004

0.46 / 4.97 0.46 / 4.97

3

20

576 / 22.7

556 / 21.9

22 / 0.87

1

HIPS (PLASTIC)

GALVANIZED STEEL

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 12: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

10

TM-F

FC-0

515-

C

Specification (R22)Ceiling Cassette Type - FC-A2 Series (Continued)

l/s / CFM

dBA

mm/in

mm/in

kg/Ib 85 / 187 88 / 194

mm/in

mm/in

V/Ph/Hz

W

A

W

RPM

cm³ /fl.oz. 1400 / 47

V/Ph/Hz

µF

W 3167 4072

A [5.47] [7.21]

A [48] [59]

mm/in

mm/in

mm/in

18

CASING UNIT

SCROLL

MINERAL OIL

0.85 / 9.15

2

7.0 / 0.276

INNER GROOVE COPPER

GAS

257

IP54

CLASS F

8

INDUCTION

PROPELLER

610 / 24

FIN PER INCH

FIN

MATERIAL

ROW

POLES

QUANTITY

MOTOR SPEED

1.10

SIZE

COIL

THICKNESS

MATERIAL

OIL AMOUNT

RATED INPUT POWER

RATED RUNNING CURRENT

MOTOR OUTPUT

1

625

0.23 / 0.009

0.10 / 0.004

ALUMINIUM (CORRUGATED)

GALVANIZED STEEL

145

INSULATION GRADE

DIAMETER

POWER SOURCE

CAPACITOR

RATED INPUT POWER

RATED RUNNING CURRENT- 1Ø [3Ø]

DRIVE

COMPRESSOR

TUBE

1

ASG 20

DIRECT

19.05 / 3/4

FLARE

PACKING DIMENSION

852X1030X400 / 33.5x40.6x15.8

1010X1180X514 / 39.8x46.5x20.24

58

9.52 / 3/8

1605 / 3400

SOUND PRESSURE LEVEL

UNIT DIMENSION H X W X D

MODELINDOOR UNIT

OUTDOOR UNIT

OU

TD

OO

R U

NIT

FAN MOTOR

FAN

FACE AREA

INDEX OF PROTECTION (IP)

LOCKED ROTOR AMP- 1Ø [3Ø]

MATERIAL

INSULATION GRADE

TYPE

OIL TYPE

THICKNESS

TYPE

DIAMETER

MATERIAL

POWER SOURCE 220 - 240 / 1/ 50

LIQUID

QUANTITY

TYPE

UNIT WEIGHT

PIPECONNECTION

TYPE

H X W X D

AIR FLOW

m²/ft²

F

380-415 / 3 / 50

N/A

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

FC40A2V1

R40DY1

FC50A2V1

R50DY1

Page 13: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

11

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FFN-C Series

FFN10CV1RN10FV1

FFN15CV1RN15FV1

Btu/h 9500 12500W 2784 3664

0.84 0.84W 950 1250A 4.26 5.6

Btu/hr/ W 10.56 10

V/Ph/Hz

kg/Ib 0.725 / 1.60 0.825 / 1.82

l/s / CFM 194 / 410 194 / 410l/s / CFM 170 / 360 170 / 360l/s / CFM 156 / 330 156 / 310

dBA 41 / 38 / 35 41 / 38 / 34mm/inmm/inkg/lb

mm/in

mm/inmm/in

V/Ph/HzW 55 65A 0.24 0.29W 19 23

790 805690 720620 625

mm/inmm/in

mm/in

1 216 20

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

PANEL MATERIALUNIT

MODELINDOOR UNIT

OUTDOOR UNIT

NOMINAL COOLING CAPACITY

NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT - 1Ø [3Ø]

REFRIGERANT TYPE R410A

IND

OO

R U

NIT

CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)OPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL

AIR FLOWHIGH

15.5 + 2 / 34 + 4

MEDIUMLOW

SOUND PRESSURE LEVEL (H/M/L)UNIT DIMENSION (WITH PANEL) H X W X D

SENSIBLE HEAT FACTOR

QUANTITY

EERREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBEPOWER SOURCE 220 - 240 / 1 / 50

FAN

QUANTITY 1

FAN MOTOR

PACKING DIMENSION (PANEL) H X W X D 316X630X630 (126X690X716) / 12.4X24.8X24.8 (5X27.2X28.2)UNIT WEIGHT (UNIT + PANEL)CONDENSATE DRAIN SIZE 19.1 / 3/4

TYPE TURBO FAN

DRIVE DIRECT

INDUCTION

INDEX OF PROTECTION (IP)

POLES 6

INNER GROOVE COPPER

SPEEDHIGH

RPMLOW

FILTER

GALVANIZED STEEL

1MATERIAL ABSG20

DIAMETER

WASHABLE SARANET FILTERQUANTITY 1

MATERIALDIAMETER

POWER SOURCE 220 - 240 / 1 / 50

IP20

315 / 12.4LENGTH 163 / 6.4

7.0 / 0.276

MATERIAL ALUMINIUM (SLIT FIN)

FACE AREA

INSULATION GRADE CLASS B

RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUT

REFRIGERANT CHARGE

MEDIUM

TYPE

250X570X570(295X640X640) / 9.8X22.4X22.4(11.6X25.2X25.2)

COIL

FIN

SIZE367.5 / 14.5381.0 /15.020.8 / 0.8

THICKNESS 0.23 / 0.009TUBE

THICKNESS 0.10 / 0.004

FIN PER INCH

0.25ROW

AIR QUALITY

TYPE

CASING ABSMATERIAL

m²/ft²

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 14: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

12

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FFN-C Series (Continued)

m²/ft²

l/s / CFM 438 / 927 390 / 827

dBA 46 48

mm/inmm/in

kg/lb 28 / 61.7 29 / 63.9

mm/in

mm/in 9.52 / 3/8 12.7 / 1/2

mm/in

V/Ph/Hz

W 50 51

A 0.22 0.23

W 20

RPM 930 920

cm³ 330 320

V/Ph/HzµF 35

W 845 1134

A 3.78 5.08

A 18.00 24.50

mm/in 7 / 0.28

mm/in

mm/in0.33 / 3.55 0.32 / 3.44

2

CASING UNIT

MODELINDOOR UNIT

OUTDOOR UNIT

MOTOR SPEED

LOCKED ROTOR AMPERE - 1Ø [3Ø]

TYPE FLARE VALVE

1

GALVANIZED STEEL

MATERIAL ALUMINIUM

FACE AREA

POLES 6

MATERIAL COPPER

DIAMETER

TYPE ROTARY

OIL TYPE HAF68D1 NMOCZe -GlesRB68EP

OIL AMOUNT

RATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]

POWER SOURCE 220 - 240 / 1 / 50

CAPACITOR

MATERIAL

INSULATION GRADE E

FAN MOTOR

TYPE INDUCTION

INDEX OF PROTECTION (IP) IP23

RATED RUNNING CURRENT

MOTOR OUTPUT

POWER SOURCE 220 - 240 / 1 / 50

COMPRESSOR

INSULATION GRADE CLASS B

RATED INPUT POWER

580X775X355 / 22.8X30.5X14.0

1

MATERIAL ASG 20

DIAMETER

DRIVE DIRECT

370 / 14.6

SIZELIQUID 6.35 / 1/4

GAS

TYPE PROPELLER

OU

TDO

OR

UN

IT

AIR FLOW

SOUND PRESSURE LEVEL

UNIT DIMENSION H X W X D 550X658X273 / 21.7X25.9X10.7

PACKING DIMENSION H X W X D

ROW

UNIT WEIGHT

PIPECONNECTION

THICKNESS 0.10 / 0.039

FIN PER INCH 18

FIN

COIL

FAN

QUANTITY 1

THICKNESS 0.2 / 0.0079

TUBE

QUANTITY

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

FFN10CV1

RN10FV1

FFN15CV1

RN15FV1

Page 15: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

13

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FCN-A2 Series

FCN20A2V1RN20CV1

FCN25A2V1RN25CV1

Btu/h 18000 22000W 5275 6448

0.80 0.75W 1840 2100A 8.25 9.41

Btu/hr/ W 9.78 10.48

V/Ph/Hz

kg/Ib 1.38 / 3.04 1.55 / 3.41

l/s / CFM 340 / 730 390 / 830l/s / CFM 290 / 615 350 / 740l/s / CFM 250 / 525 280 / 595l/s / CFM 200 / 430 230 / 490

dBA 39 / 36 / 33 / 28 42 / 39 / 35 / 32mm/inmm/inkg/Ib 26+4 / 57+9

mm/in

mm/inmm/in

V/Ph/HzW 161 200A 0.71 0.94W 20 30

420 470370 420330 380300 330

mm/inmm/in

mm/inm²/ft²

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

PANEL MATERIALUNIT

FAN

TYPE

INDEX OF PROTECTION (IP)

MATERIALCOIL

SIZEAIR QUALITY FILTER

18

CASINGMATERIAL

HIPS (PLASTIC)GALVANIZED STEEL

220 - 240 / 1 / 50

300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)

CLASS B

INNER GROOVE COPPER

1

0.23 / 0.009

0.10 / 0.004

ASG 10

172 / 6.8486 / 19.1

NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT- 1Ø [3Ø]EERREFRIGERANT CONTROL (EXPANSION DEVICE)

TYPE

QUANTITYTYPE

ROW

QUANTITY

OUTDOOR CAP. TUBE

R410A

INDUCTION

MODELINDOOR UNIT

OUTDOOR UNIT

RATED RUNNING CURRENT

POLES

INSULATION GRADE

RATED INPUT POWER

DIAMETER

NOMINAL COOLING CAPACITY

LOW

IND

OO

R U

NIT

MATERIAL

AIR FLOW

SUPER LOW

H X W X D

4 WAY AUTOMATIC LOUVER (UP & DOWN)

CONDENSATE DRAIN SIZE

REFRIGERANT TYPE

UNIT DIMENSION (WITH PANEL)

UNIT WEIGHT (UNIT + PANEL)PACKING DIMENSION (PANEL) H X W X D

19.1 / 3/4

HIGH MEDIUM

SOUND PRESSURE LEVEL (H/M/L/SL)

AIR DISCHARGEOPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL

265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.8X36.6X36.6)

DRIVE DIRECT

MATERIAL

MOTOR OUTPUT

THICKNESSTUBE

THICKNESS

FIN PER INCH

FIN

DIAMETERLENGTH

POWER SOURCE 220 - 240 / 1 / 50

SENSIBLE HEAT FACTOR

REFRIGERANT CHARGE

QUANTITY 1

6

0.39 / 4.10

ALUMINIUM (SLIT FIN)

7.0 / 0.276

SPEED

HIGH

RPMMEDIUMLOWSUPER LOW

FAN MOTOR

POWER SOURCE

CONTROL

IP20

576 / 22.7556 / 21.922 / 0.87

FACE AREA

1

TURBO

WASHABLE SARANET FILTER

2

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 16: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

14

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FCN-A2 Series (Continued)

l/s / CFM 675 / 1430 755 / 1600dBA 49 52

mm/in 654X855X328 / 25.7X33.7X12.9mm/in 693X990X415 / 27.3X39.0X16.3kg/Ib 43 / 94.8 47 / 103.6

mm/in

mm/in 12.7 / 1/2 15.88 / 5/8

mm/in

IP23

V/Ph/HzW 78 121A 0.34 0.53W 32 61

RPM 710 840

cm³ / fl.oz. 670 / 23

V/Ph/HzµFW 1601 1779A 7.2 7.94A 32

mm/inmm/in

mm/inm²/ft² 0.51 / 5.49

1

20

0.50 / 5.38

CASING UNIT

0.10 / 0.0039

ALUMINIUM

455 / 17.9

0.2 / 0.0079

TYPE

INSULATION GRADE E

POWER SOURCE 220 - 240 / 1 / 50

CAPACITORRATED INPUT POWER

ROTARY

6.35 / 1/4

CLASS F

2

GALVANIZED STEEL

INDUCTION

DIAMETER

INSULATION GRADE

6

RATED RUNNING CURRENT - 1Ø [3Ø]

SIZE

FLARE

POWER SOURCE

MODELINDOOR UNIT

OUTDOOR UNIT

TYPE

OIL TYPE

PACKING DIMENSION H X W X D

TYPE

UNIT WEIGHT

LIQUID

GAS

PIPECONNECTION

H X W X D

OU

TDO

OR

UN

IT

TYPE

SOUND PRESSURE LEVELAIR FLOW

UNIT DIMENSION

OIL AMOUNT

FAN

INDEX OF PROTECTION (IP)

LOCKED ROTOR AMP- 1Ø [3Ø]

POLES

COMPRESSOR

FAN MOTOR

MATERIAL

COPPER

7.0 / 0.276

FV50S

PROPELLER

220 - 240 / 1/ 50

FIN PER INCH

QUANTITY 1

MATERIAL ASG20

DRIVE

18

DIAMETER

FIN

QUANTITY 1

MOTOR SPEED

THICKNESSTUBE

DIRECT

RATED INPUT POWERRATED RUNNING CURRENT

ROWFACE AREA

MATERIAL

MOTOR OUTPUT

MATERIAL

50

THICKNESSCOIL

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

FCN20A2V1RN20CV1

FCN25A2V1RN25CV1

Page 17: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

15

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FCN-A2 Series

Btu/hW

WA

Btu/hr/ W

V/Ph/Hz

kg/Ib 1.80 / 3.97 2.60 / 5.73

l/s / CFMl/s / CFMl/s / CFMl/s / CFM

dBAmm/inmm/inkg/Ib

mm/in

mm/inmm/in

V/Ph/HzWAW

mm/inmm/in

mm/inm²/ft²

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

PANEL MATERIALUNIT

FAN

TYPE

INDEX OF PROTECTION (IP)

MATERIALCOIL

SIZEAIR QUALITY FILTER

20

CASINGMATERIAL

HIPS (PLASTIC)GALVANIZED STEEL

220 - 240 / 1 / 50

CLASS B

INNER GROOVE COPPER

1

0.23 / 0.009

0.10 / 0.004

ASG 10

172 / 6.8486 / 19.1

NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT- 1Ø [3Ø]EERREFRIGERANT CONTROL (EXPANSION DEVICE)

TYPE

QUANTITYTYPE

ROW

QUANTITY

OUTDOOR CAP. TUBE

R410A

INDUCTION

MODELINDOOR UNIT

OUTDOOR UNIT

RATED RUNNING CURRENT

POLES

INSULATION GRADE

RATED INPUT POWER

DIAMETER

NOMINAL COOLING CAPACITY

LOW

IND

OO

R U

NIT

MATERIAL

AIR FLOW

SUPER LOW

H X W X D

4 WAY AUTOMATIC LOUVER (UP & DOWN)

CONDENSATE DRAIN SIZE

REFRIGERANT TYPE

UNIT DIMENSION (WITH PANEL)

UNIT WEIGHT (UNIT + PANEL)PACKING DIMENSION (PANEL) H X W X D

19.1 / 3/4

HIGH MEDIUM

SOUND PRESSURE LEVEL (H/M/L/SL)

AIR DISCHARGEOPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL

DRIVE DIRECT

MATERIAL

MOTOR OUTPUT

THICKNESSTUBE

THICKNESS

FIN PER INCH

FIN

DIAMETERLENGTH

POWER SOURCE 220 - 240 / 1 / 50

SENSIBLE HEAT FACTOR

REFRIGERANT CHARGE

QUANTITY 1

6

ALUMINIUM (SLIT FIN)

7.0 / 0.276

SPEED

HIGH

RPMMEDIUMLOWSUPER LOW

FAN MOTOR

POWER SOURCE

CONTROL

IP20

576 / 22.7556 / 21.922 / 0.87

FACE AREA

1

TURBO

WASHABLE SARANET FILTER

3050089390.76282013.7010.82

0.37 / 4.00 0.46 / 4.97318

3

FCN30A2V1RN28CV1

FCN40A2V1RN35DV1

2800082060.78283613.309.87

490 / 1030410 / 860350 / 740295 / 620

44 / 41 / 38 / 35300X820X820 (385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)335X916X916(124X1016X1016) / 13.2X36.1X36.1(4.9X40.0X40.0)

32+4 / 71+9

430 / 920380 / 810330 / 710290 / 610

47 / 44 / 41 / 37

26+4 / 57+9300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.8X36.6X36.6)

1760.7960

680580510435

2411.0750

630530470415

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 18: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

16

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FCN-A2 Series (Continued)

808 / 1712 1605 / 3400

54 58

852X1030X400 / 33.5X40.6X15.8

1010X1180X514 / 39.8X46.5X20.24

57 / 126 86 / 190

124 257

0.54 1.10

66 145

874 625

86

2471 2387

11.69 11.81

63 97

FLARE

756X855X328 / 29.8X33.7X12.9

793X990X415 / 31.2X39.0X16.3

SCROLL

POE OIL

15.88 / 5/8

9.52 / 3/8

1242 / 42

FV50S

1130 / 38

l/s / CFMdBA

mm/inmm/inkg/Ib

mm/in

mm/in

mm/in

IP23

CLASS FIP54

V/Ph/HzWAW

RPM

cm³ / fl.oz.

V/Ph/HzµFW

60

AA

mm/inmm/in

mm/inm²/ft²

CASING UNIT

0.11 / 0.0043

0.85 / 9.150.61 / 6.58

ALUMINIUM ALUMINIUM (CORR. FIN)

610 / 24455 / 18

0.23 / 0.009

TYPE

INSULATION GRADE E

POWER SOURCE 220 - 240 / 1 / 50

CAPACITORRATED INPUT POWER

CLASS B

2

GALVANIZED STEEL

INDUCTION

DIAMETER

INSULATION GRADE

RATED RUNNING CURRENT - 1Ø [3Ø]

SIZE

POWER SOURCE

MODELINDOOR UNIT

OUTDOOR UNIT

TYPE

OIL TYPE

PACKING DIMENSION H X W X D

TYPE

UNIT WEIGHT

LIQUID

GAS

PIPECONNECTION

H X W X D

OU

TDO

OR

UN

IT

TYPE

SOUND PRESSURE LEVELAIR FLOW

UNIT DIMENSION

OIL AMOUNT

FAN

INDEX OF PROTECTION (IP)

LOCKED ROTOR AMP- 1Ø [3Ø]

POLES

COMPRESSOR

FAN MOTOR

MATERIAL

COPPER

7.0 / 0.276

PROPELLER

220 - 240 / 1/ 50

FIN PER INCH

QUANTITY 1

MATERIAL ASG 20

DRIVE

18

DIAMETER

FIN

QUANTITY 1

MOTOR SPEED

THICKNESSTUBE

DIRECT

RATED INPUT POWERRATED RUNNING CURRENT

ROWFACE AREA

MATERIAL

MOTOR OUTPUT

MATERIAL

45

THICKNESSCOIL

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

FCN30A2V1RN28CV1

FCN40A2V1RN35DV1

Page 19: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

17

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FCN-A2 Series

FCN40A2V1RN40DY1

FCN50A2V1RN50DY1

Btu/h 40000 45000W 11723 13189

0.70 0.73W 3850 4390A [6.86] [7.8]

Btu/hr/ W 10.39 10.25

V/Ph/Hz

kg/Ib 2.10 / 4.63 2.25 / 4.96

l/s / CFM 490 / 1030 570 / 1200l/s / CFM 410 / 860 490 / 1030l/s / CFM 350 / 740 440 / 930l/s / CFM 295 / 620 370 / 780

dBA 44 / 41 / 38 / 35 47 / 44 / 43 / 39mm/inmm/inkg/lb 32 + 4 / 71 + 9

mm/in

mm/inmm/in

V/Ph/HzW 176 221A 0.79 0.97W 60 100

680 780580 680510 620435 530

mm/inmm/in

mm/inm²/ft² 0.46 / 4.97

3

pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in

PANEL MATERIALUNIT

380 - 415 / 3 / 50

POWER SOURCE 220 - 240 / 1 / 50

FAN

CLASS B

INNER GROOVE COPPER

ALUMINIUM (SLIT FIN)

7.0 / 0.276

1

6

IP20

TYPE

MATERIALCOIL

576 / 22.7

0.23 / 0.009

0.10 / 0.004

DIAMETERLENGTH

ASG 10DIRECT

486 / 19.1172 / 6.8

1

1

TURBO

INDUCTION

SENSIBLE HEAT FACTOR

REFRIGERANT CHARGE

QUANTITYMATERIALDRIVE

QUANTITY

LOW

PACKING DIMENSION (PANEL)

OUTDOOR CAP. TUBE

R410A

CONTROL

FACE AREAROW

H X W X D 335X916X916(124X1016X1016) / 13.2X36.1X36.1(5.1X40.2X39.4)

TYPE

WIRELESS MICROCOMPUTER REMOTE CONTROL

RATED INPUT POWER

UNIT WEIGHT (UNIT + PANEL)

POWER SOURCE

4 WAY AUTOMATIC LOUVER (UP & DOWN)

300X820X820 (385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)SOUND PRESSURE LEVEL (H/M/L/SL)

INDEX OF PROTECTION (IP)

19.1 / 3/4

MODEL INDOOR UNITOUTDOOR UNIT

UNIT DIMENSION (WITH PANEL)

NOMINAL COOLING CAPACITY

HIGH MEDIUM

AIR FLOW

NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT - 1Ø [3Ø]EERREFRIGERANT CONTROL (EXPANSION DEVICE)

H X W X D

REFRIGERANT TYPE

SUPER LOW

IND

OO

R U

NIT

TYPE

POLES

CONDENSATE DRAIN SIZE

INSULATION GRADE

QUANTITY

MATERIALDIAMETER

WASHABLE SARANET FILTER

OPERATION

RATED RUNNING CURRENTMOTOR OUTPUT

AIR DISCHARGE

SPEED

HIGH

RPMMEDIUMLOWSUPER LOW

FAN MOTOR

TUBE

FIN

SIZEAIR QUALITY FILTER

CASINGMATERIAL

THICKNESS

THICKNESS

FIN PER INCH 20

556 / 21.922 / 0.87

HIPS (PLASTIC)GALVANIZED STEEL

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

Page 20: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

18

TM-F

FC-0

515-

C

Specification (R410A)Ceiling Cassette Type - FCN-A2 Series (Continued)

l/s / CFM 1605 / 3400 1442 / 3056

dBA 58 60

mm/in

mm/in

kg/Ib 95 / 209 98 / 216

mm/in

mm/in

mm/in

V/Ph/Hz

W 257 276

A 1.10 1.34

W 145 145

RPM 625 625

COPELAND ULTRA 32-3 MAF

cm³ / fl.oz. 1951 / 66.0

POE OIL

1656 / 56.0

V/Ph/Hz

W

µF

3417 3893

A [6.23] [7.03]

A [64] [74]

mm/in

mm/in

mm/in

m²/ft²

CASING UNIT

POWER SOURCE 220 - 240 / 1 / 50

E

POWER SOURCE 380-415 / 3 / 50

CAPACITOR N/A

852X1030X400 / 33.5X40.6X15.7

COIL

2

THICKNESS

FIN PER INCH 18

INNER GROOVE COPPER

ALUMINIUM (CORR. FIN)

7.0 / 0.276

0.85 / 9.15

TUBE

FIN

MATERIAL

GALVANIZED STEEL

0.23 / 0.009

0.10 / 0.004

RATED INPUT POWER

LOCKED ROTOR AMP - 1Ø [3Ø]

INSULATION GRADE

MODELINDOOR UNIT

OUTDOOR UNIT

TYPE

GAS

UNIT WEIGHT

AIR FLOW

INSULATION GRADE

SOUND PRESSURE LEVEL

PROPELLER

8

SCROLL

H X W X D

OU

TD

OO

R U

NIT

QUANTITY

INDEX OF PROTECTION (IP)

UNIT DIMENSION H X W X D

TYPE

POLES

RATED RUNNING CURRENT

MOTOR OUTPUT

DIAMETER

FAN

ROW

TYPE

FACE AREA

MATERIAL

TYPEPIPECONNECTION

MATERIAL

THICKNESS

RATED INPUT POWER

PACKING DIMENSION

SIZE

COMPRESSOR

OIL TYPE

RATED RUNNING CURRENT - 1Ø [3Ø]

MOTOR SPEED

LIQUID

QUANTITY

FAN MOTOR

OIL AMOUNT

MATERIAL

DRIVE

DIAMETER

INDUCTION

DIRECT

610 / 24

ASG 20

1

CLASS F

IP54

FLARE

1010X1180X514 / 39.8X46.5X20.24

9.52 / 3/8

15.88 / 5/8

1

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.

FCN40A2V1

RN40DY1

FCN50A2V1

RN50DY1

Page 21: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

19

TM-F

FC-0

515-

C

Safety Devices Data - (R-22) Series

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

R35DV1 R40DV1

NC

OPEN kPa / psi 2937 / 426

CLOSE kPa / psi 2413 / 350

NC

OPEN kPa / psi 124 / 18

CLOSE kPa / psi 193 / 28

NA <YES>

°C / °F NA <130 / 266>

OPEN kPa / psi

CLOSE kPa / psi

OPEN kPa / psi

CLOSE kPa / psi

°C / °F

NC

124 / 18

193 / 28

<YES>

<130 / 266>

FC50A2V1

R50DY1

NC

2937 / 426

2413 / 350

MODELINDOOR UNIT

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

LOW PRESSURE SWITCH

TYPE

PHASE SEQUENCER, 1Ø <3Ø>

DISCHARGE THERMOSTAT SETTING

FC40A2V1

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

LOW PRESSURE SWITCH

DISCHARGE THERMOSTAT SETTING

TYPE

PHASE SEQUENCER, 1Ø <3Ø>

MODELINDOOR UNIT

Safety Devices Data - (R-410A) Series

1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

R35DV1 RN40DY1

NC

OPEN kPa / psi 4137 / 600

CLOSE kPa / psi 3310 / 480

NC

OPEN kPa / psi 48 / 7

CLOSE kPa / psi 152 / 22

NA <YES>

°C / °F NA <130 / 266>

OPEN kPa / psi

CLOSE kPa / psi

OPEN kPa / psi

CLOSE kPa / psi

°C / °F

NC

48 / 7

152 / 22

<YES>

<130 / 266>

FCN50A2V1

RN50DY1

NC

4137 / 600

3310 / 480

PHASE SEQUENCER, 1Ø <3Ø>

DISCHARGE THERMOSTAT SETTING

PHASE SEQUENCER, 1Ø <3Ø>

DISCHARGE THERMOSTAT SETTING

MODELINDOOR UNIT

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

LOW PRESSURE SWITCH

TYPE

MODELINDOOR UNIT

LOW PRESSURE SWITCH

TYPE

FCN40A2V1

OUTDOOR UNIT

SAFETY DEVICE

HIGH PRESSURE SWITCH

TYPE

Page 22: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

20

TM-F

FC-0

515-

C

4.ApplicationInformation

Ensure the operating temperature is in allowable range.

Cooling Only

! Caution :

The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.

OutdoorDB (°C)

46

43

19

14 19 23 Indoor WB (°C)

Cooling Operation Range

Operating Range for Air Cool Direct Expansion Unit

DB = Dry Bulb WB = Wet Bulb

Operating Range

Page 23: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

21

TM-F

FC-0

515-

C

Refrigerant Circuit Diagram

Model : (Indoor) FF10CV1, FF15CV1, FC20A2V1, FFN10CV1, FFN15CV1, FCN20A2V1, FCN25A2V1 (Outdoor) R10CV1, R15CV1, R18CV1, R20CV1, RN10FV1, RN15FV1, RN20CV1, RN25CV1

Model : (Indoor) FC25A2V1, FCN30A2V1 (Outdoor) R20CV1, R25CV1, RN28CV1

Page 24: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

22

TM-F

FC-0

515-

C

Model : (Indoor) FC30A2V1 (Outdoor) R28CV1, R30CV1

Model : (Indoor) FC40A2V1, FC50A2V1 (Outdoor) R35DV1, R40DY1, R50DY1

Page 25: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

23

TM-F

FC-0

515-

C

Model : (Indoor) FCN40A2V1, FCN50A2V1 (Outdoor) RN35DV1, RN40DY1, RN50DY1

Page 26: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

24

TM-F

FC-0

515-

C

Controller

DGS01

Operating Guide

1 Transmission Source • The source where the signal will be transmitted.

2 Signal Transmission Indication • Blink to confirm that the last setting has been transmitted to the unit.

3 “ON/OFF” Button • Press once to start the air conditioner unit. • Press again to stop the unit.

4 Fan speed selection • Press the button continuously will toggle the fan speed in the following order: Low Med High Auto • Stop pressing when the desired fan speed appears on the display screen.

5 Operation mode • Press the MODE button to select the type of operating mode. • For cooling only unit, the available modes are: COOL ( ), DRY ( ) and FAN ( ).

6 Automatic air swing • Press the SWING ( ) button to activate the automatic air swing function. • To distribute the air to a specific direction, press the SWING ( ) button and wait until the louver move to the desired direction and press the button once again.

7 Turbo function • Press for fast cooling operation. • Fan speed turn to maximum speed. • Press again to deactivate the function. • Available under COOL and DRY modes only. • Any change of fan speed will deactivate this function.

TURBO QUIET

SLEEP

ON OFF

MODE

TIMER

CANCEL CANCELCLOCK

3

13

4

9

12

7

1

2

5

6

8

10

11

Page 27: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

25

TM-F

FC-0

515-

C

7 Turbo function • Press for fast cooling operation. • Fan speed turn to maximum speed. • Press again to deactivate the function. • Available under COOL and DRY modes only. • Any change of fan speed will deactivate this function.

8 Quiet function • Press for quiet operation. • Fan speed turn to minimum speed. • Press again to deactivate the function. • Any change of fan speed will deactivate this function.

9 ON timer setting • Press the ON TIMER button will activate the on timer function. • Set the desired on time by pressing the ON TIMER button continuously. If the timer is set to 7.30am, the air conditioner will turn on at 7.30am sharp. • Press the CANCEL button to cancel the on timer setting.

10 OFF timer setting • Press the OFF TIMER button will activate the off timer function. • Set the desired off time by pressing the OFF TIMER button continuously. • Press the CANCEL button to cancel the off timer setting.

11 Clock time setting • Press and hold button to set the clock time.

12 Sleep mode setting • Press the button will activate the sleep mode function. • This is an energy saving option. When the unit is operating under cooling mode, the set temperature is increased by 0.5°C after 30 minutes, 1˚C after an hour, and 2˚C after 2 hours. • This function is available under COOL mode.

13 Temperature setting • To set the desired room temperature, press the or button to increase or decrease the set temperature. • The temperature setting range is from 16°C to 30°C. • Press both buttons and simultaneously to toggle from °C to °F setting.

Page 28: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

26

TM-F

FC-0

515-

C

DSLM8

Operating Guide

MODETURBO

TIMEROVERRIDE

TIMER

ON OFFTIMER

SWING QUIET

SLEEP

14

5

6

23

1011

8

97

1 MODE Button Press the MODE button to switch operation from COOL, AUTO*, DRY*, FAN. Check the display to

see in which mode the control is set. *AUTO and DRY are available for selected models only.

2 TURBO Fan Speed Press the Turbo key once to activate Turbo fan speed. Turbo symbol will be shown. To disable Turbo

fan speed and back to previous fan speed, press the Turbo key once again. For the unit that does not have TURBO fan speed it will show high fan speed.

3 SWING Function Press SWING button to activate the swing function. Press it again to deactivate it.

4 QUIET Fan Speed Press the Quiet key once to activate Quiet fan speed. Quiet symbol will be shown. To disable Quiet

fan speed and back to previous fan speed, press the Quiet key once again. For the unit that does not have QUIET fan speed it will show low fan speed.

5 “▲” or “▼” Set Temperature Button Press the temperature button and set the temperature of your choice by pressing “▲” or “▼” button

once, temperature changes by 1°C or 1°F. The default temperature setting range is from 16°C to 30°C (60°F to 86°F). When the Option 20 - 30ºC is set, the temperature range limit is set to 20ºC to 30ºC (68°F to 86°F). Pressing both keys simultaneously will toggle the temperature setting between ºC and ºF.

6 SLEEP Function Press the SLEEP button to activate the sleep mode. DRY MODE and FAN MODE are not valid

during sleep function.

Page 29: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

27

TM-F

FC-0

515-

C

7 “ON TIMER” and “OFF TIMER” The unit has 2-event timer, namely Timer 1 and Timer 2, each event has an ON TIMER and an OFF

TIMER. The key press activity for Timer ON and Timer OFF is shown on Table 1.1 Table 1.1: Timer ON and Timer OFF key press and event sequence.

All timers are event-triggered timers and can be overridden by the ON/OFF button and Override function.

Set Event 1 and Event 2 Timers

Process for Timer ON and Timer OFF is the same.1. Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode. (Icon ON 1 or OFF 1 will blink)2. Press UP or DOWN to select Timer 1 or Timer 2 to set. (‘1’ blinking indicate that Timer 1 is currently selected, ‘2’ blinking indicate that Timer 2 is currently selected)3. Press Timer ON/OFF key again to confirm. (Day will blink next)4. Press UP or DOWN to select the day.5. Press Timer ON/OFF key again to confirm the day. (Hour will blink next)4. Press UP or DOWN to change the hour.5. Press Timer ON/OFF key again to confirm the hour. (Minute will blink next)6. Press UP or DOWN to change the minute.7. Press Timer ON/OFF key again to confirm the minute.

Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set separately after all 7 steps, if there is no key operation for 5 seconds during setting the timer, it will automatically exits from setting mode and no changes will be made.

ON/OFF timer will be checked every 1 minute.It is not advisable to set ON TIMER and OFF TIMER to have same values. Shall these occur, the effective timer will be treated with priority as stated in Table 1.2.Example:ON TMR 2 settings: DAY – TUE, TIMER – 5.00pmOFF TMR 1 settings: DAY – TUE, TIMER – 5.00pmOutcome when RTC reaches 5.00pm on TUE: - when unit is on, no respond. - when unit is off, unit will trigger to on.

Table 1.2: Timer Priority

ON Timer 1 ON Timer 2 OFF Timer 1 OFF Timer 2 Deactivated Deactivated Deactivated Deactivated Activated Deactivated Activated Deactivated Deactivated Activated Deactivated Activated Activated Activated Activated Activated

TIMER ON KEY TIMER OFF KEY

Priority Timer

1 (Highest)

2

3

4 (Lowest)

ONTMR2

OFFTMR2

ONTMR1

OFFTMR1

Upon IR reception, IR wireless remote controller will override ON TIMER 2 and OFF TIMER 2 settings.

Page 30: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

28

TM-F

FC-0

515-

C

8 OVERRIDE Function Press the OVERRIDE key once will activate the override function for 1 hour. An indicator

“OVERRIDE 1” will show on the LCD. Press the same key again will increase the setting to 2 hours. An indicator “OVERRIDE 2” will be shown. Subsequent press will deactivate the override function. After the override timer is completed, the override function is deactivated and the logo is OFF. All other timers will be resumed.

9 FAN Speed Function Fan speed can be changed via pressing the FAN key: Low > Med > High > Auto > Low >

10 ON/OFF Button Starting Operation: - Press the ON/OFF button, the LCD will show full display and the unit is turned on. Stopping Operation: - Press the ON/OFF button, the LCD will show real time clock only and the unit is turn off.

11 Real-time Clock (RTC) Display RTC is shown on screen during the unit ON or OFF except for power failure or error code.

Set RTC Setting 1. Press RTC key one time will activate RTC setting mode. (Day will blink) 2. Press UP or DOWN to select the day. 3. Press RTC again to confi rm the day. (Hour will blink next) 4. Press UP or DOWN to change the hour. 5. Press RTC again to confi rm the hour. (Minute will blink next) 6. Press UP or DOWN to change the minute. 7. Press RTC again to confi rm the minute. RTC will only be set after all 7 steps, if there is no key operation for 5 seconds during setting the

RTC, it will automatically exits from setting mode and no changes will be made on the setting.

12 Hardware Setting The unit has 4 jumpers option to control the board function. Table 2.0: Summary of Hardware Settings

OPTION

Set Temp. Range

TURBO_QUIET

Reserved

Reserved

With Jumper

Set Temp. Range from 20˚C-30˚C

Reserved

Reserved

Without Jumper

Set Temp. Range from 16˚C-30˚C(Default)

Enable turbo and quiet fan speed

Reserved

Reserved

Disable turbo and quiet fan speed(Default)

Page 31: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

29

TM-F

FC-0

515-

C

OPERATING STATE AND FAULT TABLE

Wireless Remote Control (Universal Board)Cooling : LED Indicator Light Display

ON / ON or OFF BLINKING

Wired Remote Control (Universal Board)Cooling

POWER TIMER SLEEP

Error Code at 7 Segment Display Operation / Faulty Indication Blink E1 Room sensor contact open / short Blink E2 Indoor coil sensor contact open Blink E3 Outdoor coil sensor contact open

Blink E4 Compressor overload/ Indoor coil sensor short/Outdoor coil sensor short

Blink E5 Gas leak Blink E6 Pump faulty

POWER TIMER

1 Time

1 Time

2 Times

3 Times

2 Times

3 Times

SLEEPOperation / Faulty Indication

Cool ModeTimer OnSleep Mode On

Compressor Overload

Pump Fault

Gas Leak

Room Sensor Open or Short

Indoor Coil Sensor Open or Short

Outdoor Coil Sensor Open or Short

Page 32: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

30

TM-F

FC-0

515-

C

Water PumpThewaterpumpwillonifcompressorisonduringcoolingcycle.Thepumpwillremainonforatleast5minutesafterthecompressorisoff.Duringmodechangefromcoolingtonon-coolingmode,thepumpwillonforminimum5minutes.Duringdefrostcycle,thepumpwillonandwillonforanother5minutesoncethedefrostcycleisterminated.

Water Level SwitchThisnormallycloseswitchistodetectfaultsinwaterpumpsystem.Itwillconfirmfor30secondsforswitchopenand60secondsforswitchclose.Onceswitchisconfirmedopen,itwillforcecompressortocutoff.Iftheswitchisclosedwithin5minutes,thecompressorisallowedtocutin.Iftheswitchdoesnotcloseformorethan5minutes,thesystemwillwarnuserregardingthefault,thecompressorisnotallowedtocutin.Iftheswitchisconfirmedopenedtwicewithin30minutes,thesystemassumestherearefaults.

Phase SequencerTheunitwithScrollCompressorcanonlyrotateinonedirection.Forthisreason,aprotectivedevice(phasesequencer)isfittedtopreventincorrectwiringoftheelectricalphases.Whenthethreephasesarenotconnectedcorrectly,thephasesequenceroperates,andtheunitwillnotstart.Thisdeviceislocatedinthecontrolboxoftheoutdoorunit.

ThefollowingtableshowstheLEDindicatorlightforphasesequencerundernormaloperationandfaultconditions.

LED_PWR(Red)

LED_S (Yellow)

LED_T (Yellow)

Normal Operation

LEDs Error Indication

On

On On

On On

-On On

-

-

-

-

- -

-

On

-

Reverse Phase Blink Blink BlinkBlink

Blink

Blink

Blink

System OffBlink

Blink

Blink

T Phase Missing S Phase Missing R Phase Missing R Phase Missing (Main Power) Overload

Sensor Missing

High Pressure

Low Pressure

Notes: 1. “-” means LED off.2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common) and 81(NO) will cut off.3. The unit will check the discharge sensor availability only during power up.4. All errors can only recover through manually reset.

Page 33: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

31

TM-F

FC-0

515-

C

5.Installations

Installation GuidelineSafety Precautions

WARNING

CAUTIONPlease take note of the following important points when installing.

If gas leaks and accumulates around the unit, it may cause fire ignition.

Ensure that drainage piping is connected properly.If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.

Do not overcharge the unit.

This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.

Ensure that the unit’s panel is closed after service or installation.

Unsecured panels will cause the unit to operate noisily.

Sharp edges and coil surfaces are potential locations which may cause injury hazards.Avoid from being in contact with these places. Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” positionto prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user. Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat. Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.

IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.Do not use joined and twisted wires for incoming power supply.

Do not install the unit where leakage of flammable gas may occur. •

••

NOTICE

• Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance.• All field wiring must be installed in accordance with the national wiring regulation.• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.• The unit must be GROUNDED to prevent possible hazard due to insulation failure.• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.• Confirm that the unit has been switched OFF before installing or servicing the unit.• Disconnect from the main power supply before servicing the air conditioner unit.• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fire hazards.• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}.

Disposal requirementsYour air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste.Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.

Page 34: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

32

TM-F

FC-0

515-

C

Installation Diagram

Indoor Unit

Drain Hose

Front Panel

Air Filter(behind the grille)

Air Intake Grille

Thermal Insulation

Air Discharge

Air Discharge Louver

Air Intake

Air Intake

Outdoor Unit

Wrap the insulated pipe with the finishing tape from bottom to top

Page 35: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

33

TM-F

FC-0

515-

C

0.5m or more 0.5m or more

3m o

r le

ss

1m o

r m

ore

FloorObstacle

0.5m or more 0.3m

or

less

Bea

m

Preliminary Site SurveyBe sure to read this manual before installing the air-conditioner indoor unit.• Voltage supply fluctuation must not exceed +10% of rated voltage. Electricity supply lines must be

independent of welding transformers which can cause high supply fluctuation.• Ensure that the location is convenient for wiring, piping and drainage.• Do not exert pressure on the resin parts when opening the unit or when moving it after opening.• Do not move the unit from packaging while moving, until it reaches the installation site. Use safe

material or protection plates when unpacking it or lifting it to avoid damage or scratches to the unit.

• Ensure a location where:a) Drainage can be done easily.b) Convenient for wiring and piping.c) Which have enough space for installation and service work.d) Where no risk of fl ammable gas leakage.e) When free from any obstacles in path of cool air discharge and warm air return and must allow

spreading of air throughout the room (near the center of the room).f) Must be provided clearance for indoor unit from the wall and obstacles as shown in figure below.g) The installation place must be strong enough to support a load 4 times the indoor unit weight to

avoid amplifying noise and vibration.h) The installation place (hanging ceiling surface) must be assuring levelness and the height in the

ceiling is 350mm or more.i) The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

Unit Installation

Ceiling Opening Size = 875mm

Hanging rod size = 790mm

Cei

ling

Ope

ning

Siz

e =

875

mm

Han

ging

rod

siz

e =

621

mm

Unit

Piping Direction

• Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the hanging rod.

• The installation template is extended according to temperature and humidity. Check on dimensions in use.• The dimensions of the installation template are the same as those of the ceiling opening dimensions.• Before ceiling laminating work is completed, be sure to fi t the installation template to the indoor unit.

Installation Of The Indoor Unit

NOTE: Be sure to discuss the ceiling drilling work with the installers concerned.

FF-C FC-A2

Page 36: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

34

TM-F

FC-0

515-

C

FF-CFC-A2

Unit Hanging

Drain Piping Work

CeilingBoard

30.0mm (FF-C, FC-A2)

• Hold the unit and hang it on the hanging rod with the washer, spring washer and nut.• Adjust the unit height to 30.0mm between the indoor unit bottom surface and the ceiling surface.• Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bolt to prevent

unit falling and vibration.• Open the ceiling board along the outer edge of the paper installation template.

• Avoid installing the drain pipe in upward gradient after the drain connection.

• Ensure the height of drain pipe from ceiling is 700mm or less if it is necessary to increase the height of drain pipe to prevent water leak.

• Avoid installing the drain pipe in up and down slope to prevent reversed water flow.

• During the drain pipe connection, be careful not to exert extra force on the drain connector at indoor unit.

• The outside diameter of the drain connection at the flexible drain hose is 20mm.

• Be sure to execute heat insulation (polyethylene foam with thickness more than 8.0mm) on the drain piping to avoid the condensed water dripping inside the room.

• Connect the main drain pipe to the flexible drain hose.

• Feed water from flexible drain hose to check the piping for leakage.

• When the test is completed, connect the flexible drain hose to the drain connector on the indoor unit.

Ceiling

700.

00m

m

or le

ss

Panel

Flexible Hose

Pipe Clamp

See View A

IndoorUnit

����������

Feed water

Flexible Drain Hose

Main Drain Pipe

View A

Note: This Indoor Unit uses a drain pump for condensed water drainage. Install the unit horizontally to prevent water leakage or condensation around the air outlet.

Page 37: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

35

TM-F

FC-0

515-

C

Open

Screw

Panel Installation

• The front panel can only be fitted in one direction, follow the piping direction. (Follow piping arrow sticker on front panel)

• Be sure to remove the installation template before installing the front panel.

• Open the air intake grille by pulling back the catchers and removing it together with filter from panel.• Install the front frame panel onto the indoor unit by 4 screws and tighten it completely to prevent cool

air leakage.• Connect the LED wire and air swing wire to the indoor unit.• The air swing connector must put inside the control box after connected.

From Unit Control Box

From Front Panel

LED Wire

Air Swing Wire

Indoor UnitCool Air

Ceiling Board

Panel

Air Leak

Good Installation Bad Installation

Cool AirAir Leak

Ceiling Board

Panel

NOTE: Install the front frame panel firmly to prevent cool air leakage which will cause condensation and water dripping.

Page 38: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

36

TM-F

FC-0

515-

C

Installation Of The Outdoor Unit

As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements:

• Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.

• Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or discharge.

• The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the condensing temperature.

• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.• A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.

• The location must not be susceptible to dust or oil mist.

Installation Clearances

Dimension

MinimumDistance,mm (in)

300

A B C D

(11.8)1000(39.4)

300(11.8)

500(19.7)

Ret

urn

air

Dis

char

ge a

ir

A

Obs

tacl

e

Obs

tacl

e

B

Obs

tacl

e

Ret

urn

air

Ser

vice

acc

ess

DC

Obs

tacl

e

• Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air flow. Select the coolest possible place where intake air should not be hotter than the outside temperature (Refer to operating range).

Page 39: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

37

TM-F

FC-0

515-

C

Refrigerant Piping

Allowable Pipe Length And ElevationWhen the pipe length becomes too long, both the capacity and reliability drop. As the number of bendsincreases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result the compressor may become defective. Always choose the shortest path and follow the recommendation as tabulated below:

Piping Sizes (Flare Connection Type)Piping sizes are as follows:

R22

For R22

Indoor FF10CV1

R10CV1

12

5

10

FF15CV1

R15CV1

12

5

10

R18CV1

15

8

10

R20CV1

15

8

10

R20CV1

15

8

10

R25CV1

15

8

10

R28CV1

15

8

10

R30CV1

25

8

10

R35DV1

45

25

10

R40DY1

45

25

10

R50DY1

45

25

10

OutdoorModel

Maximum Length, m

Maximum Elevation, m

Maximum No. of Bends

Model R10CV1 R15CV1 R18/20CV1 R25CV1

R50DY1

Liquid (mm/in) 6.35 / 1/4 6.35 / 1/4 9.52 / 3/8 Suction (mm/in) 12.70 / 1/2 15.88 / 5/8 15.88 / 5/8

Model R28CV1 R30CV1R35DV1R40DY1

Liquid (mm/in) 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 Suction (mm/in) 15.88 / 5/8 19.05 / 3/4 19.05 / 3/4

Model RN10FV1

RN28CV1 RN35DV1 RN40DY1 RN50DY1

RN15FV1 RN20CV1 RN25CV1Liquid (mm/in) 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4 Suction (mm/in) 12.70 / 1/2 12.70 / 1/2 15.88 / 5/8

Model Liquid (mm/in) 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 Suction (mm/in) 15.88 / 5/8 15.88 / 5/8 15.88 / 5/8 15.88 / 5/8

R410A

6.35 / 1/4 9.52 / 3/8

9.52 / 3/8 15.88 / 5/8

6.35 / 1/49.52 / 3/8

FC20A2V1 FC25A2V1 FC30A2V1 FC40A2V1 FC50A2V1

For R410A

Indoor FFN10CV1

RN10FV1

20

10

10

FFN15CV1

RN15FV1

20

10

10

RN20CV1

20

10

10

RN25CV1

20

10

10

RN28CV1

25

8

10

RN35DV1

45

25

10

RN40DY1

45

25

10

RN50DY1

45

25

10

OutdoorModel

Maximum Length, m

Maximum Elevation, m

Maximum No. of Bends

FCN20A2V1 FCN25A2V1 FCN30A2V1 FCN40A2V1 FCN50A2V1

Page 40: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

38

TM-F

FC-0

515-

C

Piping Connection To The Units• Align the centre of the piping and tighten the flare nut sufficiently with fingers.• Finally tighten the flare nut with torque wrench unit the wrench clicks.• When tightening the flare nut with torque wrench, ensure the direction for tightening

the arrow on the wrench.

Pipe Size (mm/in) Torque (Nm) 6.35 (1/4) 18 9.52 (3/8) 42 12.70 (1/2) 55 15.88 (5/8) 65 19.05 (3/4) 78

Wiring

General Precautions• Ensure that the rated voltage of the unit corresponds to the nameplate before carrying out

proper wiring according to the wiring diagram.• Provide a power outlet to be used exclusively for each unit. A power supply disconnects and a

circuit breaker for over current protection should be provided in the exclusive line.• All wiring must be GROUNDED to prevent possible hazards due to insulation failures.• All wiring must be firmly connected.• All wiring must not come in contact with the hot refrigerant piping, compressor or any moving parts

of fan motors.

Electrical ConnectionsWiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL CODES for field wiring rules. Be sure that installation is complied with such rules and regulations.

Page 41: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

39

TM-F

FC-0

515-

C

CAUTION FOR R410ADo not top-up when servicing leak, as this will reduce the unit performance. VacuumtheunitthoroughlyandthenchargetheunitwithfreshR410Aaccordingtotheamountrecommendedinthespecification.

• The precharged outdoor unit does not need any vacuuming or charging. However once it is connected,the connecting pipe line and the indoor need to be vacuumed before releasing the R22/R410A from the outdoor unit.1) Open the service port core cap.2) Connect pressure gauge to the service port.3) Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum

to –0.1 MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).

4) After evacuation, unscrew the spindle (diagram 2) for the gas to run to indoor unit.

Note : R22: Nil R410A: Nil

Vacuuming And Charging

Page 42: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

40

TM-F

FC-0

515-

C

Additional Charge

• The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.5m, additional refrigerant charge after vacuuming is not necessary.

• When the piping length is more than 7.5m, please use the table below (unit in gram).

Example:FC25A2V1 & R25CV1 with 13m piping length, additional piping length is 5.5m. Thus,Additional Charge = 5.5 x [38g/m] = 209 [g]

* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.

For R22

Indoor FF10CV1

R10CV1

15

FF15CV1

R15CV1

15

R18CV1

22

R20CV1

22

R20CV1

38

R25CV1

38

R28CV1

55

R30CV1

55

R35DV1

56

R40DY1

56

R50DY1

54

OutdoorModel

Additional Charge OfRefrigerant (g/m)

FC20A2V1 FC25A2V1 FC30A2V1 FC40A2V1 FC50A2V1

For R410A

Indoor FFN10CV1

RN10FV1

18

FFN15CV1

RN15FV1

18

RN20CV1

20

RN25CV1

20

RN28CV1

24

RN35DV1

27

RN40DY1

24

RN50DY1

24

OutdoorModel

Additional Charge OfRefrigerant (g/m)

FCN20A2V1 FCN25A2V1 FCN30A2V1 FCN40A2V1 FCN50A2V1

Page 43: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

41

TM-F

FC-0

515-

C

The additional refrigerant charge amount recommended is a guideline for longer piping application. The actual charge required may be different from the guideline due to different application and variation in site conditions.

Diagram shows typical charging method:

Note : R22 - NilR410A - Nil

CAUTION FOR R410A Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air. The POE oil in the compressor and piping can absorb moisture from air.

Page 44: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

42

TM-F

FC-0

515-

C

Special Precautions When Dealing With Refrigerant R410A Unit

(1) What is New Refrigerant R410A?R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential.

(2) ComponentsMixture weight composition R32(50%) and R125(50%)

(3) Characteristic• R410A liquid and vapour components have different compositions when the fluid

evaporates of condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerang mixture left in the system will change and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly before recharging with R410A.

• When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to make certain that only original composition of R410A is being charged into the system.

• PVE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor. Extra precaution must be taken not to expose the R410A system too long to moist air.

(4) Check List Before Installation / Servicing• Tubing

Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the ends of the tubing prior to installation.

• Compressor oilNo additional charge of compressor oil is permitted.

• RefrigerantNo other refrigerant other that R410A

• Tools (size of service port is different from R22 system)Tools specifically for R410A only (must not be used for R22 or other refrigerant)i) Gauge manifold and charging hoseii) Gas leak detectoriii) Refrigerant cylinder/charging cylinderiv) Vacuum pump c/w adapterv) Flare toolsvi) Refrigerant recovery machine

(5) Handling and Installation GuildelinesLike R22 system, the handling and installation of R410A system are closely similar. All precautionary measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and vacuuming are equally important requirements.However, due to it hydroscopic PVE oil, additional precautions must be taken to ensure optimum and trouble free system operation.

(a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air. Residual PVE oil in the piping and components can absorb moisture from the air.

(b) Ensure that the compressor is not exposed to open air for more than the recommended time specified by its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is about to be brazed.

(c) The system should be thoroughly vacuumed to 1.0 Pa (700mmHg) or lower. This vacuuming level is more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.

Page 45: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

43

TM-F

FC-0

515-

C

(d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This isto ensure that only the original composition of R410A is being delivered into the system. The liquid composition can be different from the vapour composition.

(e) Normally, the R410A cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, if the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the bottom.

Overall Checking

• Ensure the following, in particular:1. The unit is mounted solidly and rigid in position.2. Piping and connections are leak proof after charging.3. Proper wiring has been done.

• Drainage check – pour some water into drain pan.• Test run

1. Conduct a test run after water drainage test and gas leakage test.2. Watch out for the following:

(a) Is the electric plug firmly inserted into the socket?(b) Is there any abnormal sound from the unit?(c) Is there any abnormal vibration with regard to the unit itself or piping?(d) Is there smooth drainage of water?

• Check that:1. Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).2. Indoor blower is running and discharge cool air (cooling cycle).3. Suction (low side) pressure is as per recommendations.4. The remote controller has incorporated a 3 minutes delay in the circuit. Thus, it requires

about 3 minutes before the outdoor unit can start up.

Standard Operating Condition

Ts: Dry Bulb TemperatureTh: Wet Bulb Temperature

T erutarepmeT s ºC / º T F h ºC / ºF Minimum Indoor Temperature 19.4 / 66.9 13.9 / 57.0 Maximum Indoor Temperature 26.7 / 80.1 19.4 / 66.9 Minimum Outdoor Temperature 19.4 / 66.9 13.9 / 57.0 Maximum Outdoor Temperature 46 / 114.8 24 / 75.2

Page 46: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

44

TM-F

FC-0

515-

C

6.WiringDiagrams

Indoor UnitModel : FF10CV1, FFN10CV1, FF15CV1, FFN15CV1

Outdoor UnitModel : R10CV1, RN10FV1, R15CV1, RN15FV1

Page 47: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

45

TM-F

FC-0

515-

C

Indoor UnitModel : FC20/25/30A2V1, FCN20/25/30A2V1

Outdoor UnitModel : R18/20/25/28/30CV1, RN20/25/28CV1

Page 48: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

46

TM-F

FC-0

515-

C

Indoor UnitModel: FC40A2V1, FCN40A2V1

Outdoor UnitModel: R35DV1, RN35DV1

Page 49: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

47

TM-F

FC-0

515-

C

Ind

oo

r U

nit

Mo

del

: F

C40

/50A

2V1,

FC

N40

/50A

2V1

Ou

tdo

or

Un

itM

od

el :

R40

/50D

Y1,

RN

40/5

0DY

1

Page 50: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

48

TM-F

FC-0

515-

C

7.ServicingandMaintenance

Warning: Disconnect from main supply before servicing the air conditioner

The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.

Components Recommended Schedule Air Filter

(Indoor Unit) 1. Remove any dust adhering to the filter by using a

vacuum cleaner or wash in lukewarm water (below 40˚C) with a neutral cleaning detergent.

2. Rinse the filter well and dry before placing it back onto the unit.

3. Note: Never use gasoline, volatile substances or chemicals to clean the filter.

At least once every 2 weeks. More frequently if necessary.

Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40˚C) and a neutral detergent solution.

2. Note: Never use gasoline, volatile substances or chemicals to clean the indoor unit.

At least once every 2 weeks. More frequently if necessary.

Condense Drain Pan & Pipe

1. Check the cleanliness and clean it if necessary. 2. Check the condensate water flow.

Every 3 months.

Indoor Fan Check if there is any abnormal noise. If necessary. Indoor / Outdoor

Coil 1. Check and remove the dirt between the fins. 2. Check and remove any obstacles which hinder air flow

through the indoor or outdoor.

Every month.

Power Supply 1. Check the running current and voltage for indoor and outdoor unit.

2. Check the electrical wiring and tighten the wire onto the terminal block if necessary.

Every 2 months. Every year.

Compressor No maintenance needed if refrigerant circuit remains sealed. However, check for refrigerant leak at joint and fitting.

Every 6 months.

Compressor Oil Oil is factory charged. Not necessary to add oil if circuit remains sealed.

No maintenance required.

Fan Motor Oil All motors are pre-lubricated and sealed at factory. No maintenance required.

Pre Start Up Maintenance(After Extended Shut Down)

- Inspect thoroughly and clean indoor and outdoor units.- Clean or replace air filters.- Clean condensates drain line.- Clean clogged indoor and outdoor coils.- Check fan imbalance before operation.- Tighten all wiring connections and panels.- Check for refrigerant leakage.

Maintenance Procedures

!

Page 51: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

49

TM-F

FC-0

515-

C

Caution

!

Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when performing a leakage test or an airtight test. These gases could cause severe explosion and damage if exposed to high temperature and pressure. It is recommended that only nitrogen or refrigerant be charged when performing the leakage or airtight test

Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface once every 3 months. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the systems life span may be shortened.

The design of the R/RN outdoor series allows servicing to be carried out easily. The removal of the top, front and side panels makes almost every part accessible.

For R/RN Outdoor Models

Page 52: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

50

TM-F

FC-0

515-

C

8.Troubleshooting

When a malfunction of the air conditioner unit is detected, immediately switch off the main power supplybefore proceeding with the following troubleshooting procedures.The following are common fault conditions and simple troubleshooting tips. If any other fault conditions whichare not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.

snoitca evitcerroc / sesuac elbissoP snoitidnoc tluaF oN

1 The air conditioner unit will not resume after power failure.

• The auto restart function is not functioning. Please turn on the unit with the wireless / wired controller.

2 The compressor does not operate 3 minutes after the air conditioner unit is started.

• Protection against frequent starting. • Wait for 3 or 4 minutes for the compressor to start

operating by it self.

3 The airflow is too slow or room cannot be cooled sufficiently.

• The air filter is dirty. • The doors and windows are opened. • The air suction and discharge of both indoor and

outdoor units are clogged or blocked. • The regulated temperature or temperature setting

is not low enough.

4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others, which might have adhered onto the coil, may cause odor.

• Contact your nearest dealer.

5 Condensation on the front air grille of the indoor unit.

• This is caused by air humidity after an extended period of operation.

• The set temperature is too low. Increase the temperature setting and operate the unit at high fan speed.

6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest dealer. This might be due to tilted installation.

7 Hissing airflow sound from the air conditioner unit during operation.

• Liquid refrigerant flowing into the evaporator coil.

8 The wireless controller display is dim. • The batteries are discharged. • The batteries are not correctly inserted. • The assembly is not good.

9 Compressor operates continuously. • Dirty air filter. Clean the air filter. • Temperature setting too low (cooling). Use higher

temperature setting.

10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower temperature setting.

Page 53: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

51

TM-F

FC-0

515-

C

Pressure

Data

Circuit

Too

low

A li

ttle

low

Nor

mal

A li

ttle

high

Too

high

Probable cause

High side Low side

●●

1. Overcharged with refrigerant. 2. Non-condensable gases in refrigerant circuit (e.g. air) 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit.

High side Low side

●●

1. Poor compression / no compression (compressor defective)

2. Reversing valve leaking.

High side Low side ●

● 1. Undercharged with refrigerant. 2. Refrigerant leakage. 3. Air filter clogged / dirty (indoor unit). 4. Indoor fan locked / seized.

High side Low side ●

● 1. Outdoor fan blocked (cooling). 2. Outdoor coil dirty (cooling). 3. Non-condensable gases in refrigerant circuit (e.g. air)

High side Low side

●●

1. Air intake temperature of indoor unit too high.

Diagnostic Guidelines

By means of pressure reading :

Page 54: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

52

TM-F

FC-0

515-

C

By Means Of Diagnostic Flow Chart:Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. “Starting failure” is caused by electrical defect while improper application or defects in refrigerant circuitcauses“Insufficientcooling”.

i) Diagnosis of Electric Circuit

Page 55: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

53

TM-F

FC-0

515-

C

ii ) Diagnosis Of Refrigerant Circuit / Application

Theremight be some causeswhere the unit starts running but does not perform satisfactorily, i.e. insufficientcooling.Judgementcouldbemadebymeasuring temperaturedifferenceof indoorunit’sintakeanddischargeairaswellasrunningcurrent.

Satisfactoryoperationwithtemperaturedifferenceofairintake&dischargeofindoorunit8°Cto13°C.*(*valueisforreferenceonly)

Page 56: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

54

TM-F

FC-0

515-

C

9.DimensionalData

Indoor UnitModel: FF10/15CV1, FFN10/15CV1, FC20/25/30/40/50A2V1, FCN20/25/30/40/50A2V1

Outdoor UnitModel: R10/15CV1

Note : All Dimension in mm

MODEL A B C D E F G H I J

930

820 820 385 357 28

820 820 345 28 930 626 626 555

930 930 626 626 555

FF/10/15CV1FFN10/15CV1FC20/25/30A2V1FCN20/25/30A2V1FC40/50A2V1FCN40/50A2V1

640 640 408 408 364570 570 295 275

317

20

B

A

P

RS

DO

L

QN

M

NF

E

CG H

I J

LK

Dimension

Dimension

Model A B C D E F G H I J K

700 521 250 478 175 36 95 94 86 68 440

L M N O P Q R S

130 110 15 21 19 278 80 65

R10/15CV1

ModelR10/15CV1

Note : All Dimension in mm

Page 57: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

55

TM-F

FC-0

515-

C

All dimensions are in mm

Outdoor UnitModel: RN10/15FV1

DimensionModel A B C D E F G H I J K L M N O P

RN10/15FV1 550 658 51 11 273 16 14 470 96 299 94 60 14 133 8 8

H

NJ

G

B CDE F

A

MK

L

P

O

I

Page 58: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

56

TM-F

FC-0

515-

C

Model: R35DV1, R40/50DY1RN35DV1, RN40/50DY1

Note : All Dimension in mm

A B C D E F G H I J K L M N O P Q R S T

R18/20CV1RN20/25CV1

R25/28/30CV1RN28CV1

855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75

855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75

Note : All Dimension in mm

Model: R18/20/25/28/30CV1 RN20/25/28CV1

142 746 142

2222

448

60

40.090.0

MODEL

Page 59: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

57

TM-F

FC-0

515-

C

10.ExplodedView&PartList

1

2

3

4

5

6

7

8

9

14

13

12

11

1015

16

17

18

19

20

21

22

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION

1 BASE PAN

2 FAN MOTOR

3 SIDE PANEL BACK

4 FRESH AIR ADAPTOR

5 HANGER BRACKET

6 PARTITION

7 ASSY. AIR GUIDE

8 ASSY. COVER CONTROL BOX

9 ASSY. CONTROL BOX

10 LEVEL SWITCH

11 HEXAGON BOLT

12 HEXAGON BOLT

13 EVAPORATOR COIL

14 ASSY. FAN COVER

15 VALVE PLATE

16 DRAIN PUMP BUSH

17 WATER PUMP

18 ASSY. COIL BRACKET

19 BLOWER, TURBO FAN

20 ASSY. DRAIN PAN

21 COVER, WIRE A

22 COVER, WIRE B

Model: FF10/15CV1, FFN10/15CV1

Page 60: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

58

TM-F

FC-0

515-

C

NO DESCRIPTION NO DESCRIPTION1 FRAME 11 LINKAGE COVER, MOTOR2 INTAKE GRILLE 12 ASSY., BRACKET RECEIVER3 AIR FILTER 13 AIR SWING MOTOR4 GRILLE LOCK 14 CRANK CONNECTOR5 DISCHARGE FOAM 15 LOUVER HOLDER6 DISCHARGE FOAM, LED 16 CRANK CROSS7 DISCHARGE FOAM, SHORT 17 INSULATION, LONG8 LOUVER 18 INSULATION, SHORT9 LOUVER, LED 19 INSULATION, CORNER

10 LINKAGE COVER

Panel for FF-C: BF-C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Page 61: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

59

TM-F

FC-0

515-

C

NO. PARTS DESCRIPTION NO1 ASSY. BASE PAN

13 ASSY. COVER TERMINAL

2 ASSY. COIL MAIN

14 SUPPORT, COIL B

3 ASSY. COIL BRACKET

15

4 ASSY. DRAIN PUMP MOUNTING

16 COVER, WIRE B

5 ASSY. PANEL SIDE BACK

17 BRACKET, HANGER A

6 ASSY. SIDE PANEL FRONT

18 BRACKET, HANGER B

7 MOTOR

19 BRACKET, HANGER C

8 BLOWER, TURBO FAN

20 FRESH AIR ADAPTOR

9 ASSY. DRAIN PAN

21 ASSEMBLY, VALVE PLATE

10 ASSY. FAN COVER

22 ASSY. AIR GUIDE

11 ASSY. COVER CONTROL BOX

23 ASSY. PARTITION HOLDER

12 ASSY. CONTROL BOX

24 COVER, WIRE

PARTS NOT IN THE DIAGRAML2 CONTROL MODULE

Model: FC20/25/30A2V1, FCN20/25/30A2V1

COVER, WIRE A

26 PUMP, WATER25 SWITCH WATER LEVEL DRAIN PUMP

27 HOSE, DRAIN PE

COOLING ONLY MODELSCAPACITOR

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

PARTS DESCRIPTION

Page 62: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

60

TM-F

FC-0

515-

C

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY. BASE PAN

13 ASSY. COVER TERMINAL

2 ASSY. COIL

14 SUPPORT, COIL B

3 ASSY. COIL BRACKET

15

4 ASSY. DRAIN PUMP MOUNTING

16 COVER, WIRE B

5 ASSY. PANEL SIDE BACK

17 BRACKET, HANGER A

6 ASSY. SIDE PANEL FRONT

18 BRACKET, HANGER B

7 MOTOR

19 BRACKET, HANGER C

8 BLOWER, TURBO FAN

20 ASSY. FRESH AIR KIT

9 ASSY. DRAIN PAN

21 VALVE PLATE

10 ASSY. FAN COVER

22 FOAM. EPS AIR GUIDE 238*190*70mm

11 ASSY. COVER CONTROL BOX

23 ASSY. PARTITION HOLDER

12 ASSY. CONTROL BOX

24 COVER, WIRE

PARTS NOT IN THE DIAGRAML2 CONTROL MODULE

Model: FC40/50A2V1, FCN40/50A2V1

COVER, WIRE A

26 PUMP, WATER PC -04226 - OYOB25 SWITCH WATER LEVEL DRAIN PUMP

27 HOSE, DRAIN PE 18.3 x 0.5 x 315.0

COOLING ONLY MODELSCAPACITOR

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Page 63: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

61

TM-F

FC-0

515-

C 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 FRONT PANEL 7 FIX PLATE2 RECEIVER BRACKET 8 AIR INTAKE GRILLE3 SHORT LOUVER 9 GRILLE LOCK4 LOUVER 10 AIR FILTER5 LOUVER HOLDER 11 RECEIVER COVER6 LOUVER CLIP

Panel for FC-A2: BC-A2

Page 64: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

62

TM-F

FC-0

515-

C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 VALVE BRACKET

13 RIGHT PANEL

4 COMPRESSOR

14 ASSY., FRONT PANEL

5 ASSY., PARTITION15 ASSY., CONTROL PANEL

6 SUCTION PIPE 7 DISCHARGE PIPE 8 ASSY., CAP TUBE 9 BRACKET, FAN MOTOR10

1 6 ASSY., VALVE COVER

Model : R10/15CV1

FAN MOTOR

17 ASSY., FRONT GRILLE 18 PLASTIC HANDLE 19 INSULATION PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR11 FAN BLADE

12 LEFT PANEL

Page 65: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

63

TM-F

FC-0

515-

C

Model : RN10/15FV1

NO. DESCRIPTION NO. DESCRIPTION1 ASSY. OUTDOOR COIL

12 SUCTION PIPE2 TOP PANEL

13 ASSY. CAP TUBE3 FAN MOTOR BRACKET

14 VALVE BRACKET4 ASSY PARTITION

15 ASSY. VALVE COVER16 ASSY. CONTROL PANEL17 RIGHT PANEL

5 FAN MOTOR6 FAN BLADE7 ASSY. FRONT GRILLE8 ASSY FRONT PANEL9 ASSY BASE PAN

10 COMPRESSOR11 DISCHARGE PIPE

* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.

17

16

15

1413121110987

6

5

4

3

2 1

Page 66: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

64

TM-F

FC-0

515-

C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET

13 TERMINAL COVER PANEL

4 FAN MOTOR

14 DISCHARGE PIPE

5 FAN BLADE

15 SUCTION PIPE

6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10

16 ASSY., CAP TUBE

Model : R18/20CV1, RN20/25CV1

17 ASSY., VALVE COVER 18 ASSY., FRONT GRILLE 19 PLASTIC HANDLE 20 SERVICE PANELPARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR

FRONT PANEL, LEFT11 TOP PANEL12 ASSY., CONTROL PANEL

Page 67: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

65

TM-F

FC-0

515-

C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET

13 ASSY., CONTROL PANEL

4 FAN MOTOR

14 TERMINAL COVER PANEL

5 FAN BLADE15 ASSY., VALVE COVER

6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10

16 ASSY., FRONT GRILLE

Model : R25/28/30CV1, RN28CV1

17 PLASTIC HANDLE, SIDE 18 DISCHARGE PIPE 19 SUCTION PIPE 20 ASSY., CAP TUBE PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR

SERVICE PANEL11 FRONT PANEL LEFT

12 TOP PANEL

Page 68: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

66

TM-F

FC-0

515-

C

1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., COIL3 PALTE, FLARE VALVE4 FLARE VALVE 3/8”5 FLARE VALVE 5/8”

16 MOTOR BRACKET17 FAN MOTOR18 ASSY., FRONT PANEL19 ASSY., CONTROL PANEL20 SERVICE PANEL21 FAN BLADE22 TOP PANEL23 PLASTIC HANDLE

6 PARTITION 7 COMPRESSOR 8 ACCUMULATOR 9 ASSY., CAPILLARY TUBE10 SUCTION PIPE11 TUBE ACCUMULATOR TO SUCTION12 DISCHARGE PIPE13 INSULATION14 BACK PANEL, RIGHT

15 SIDE PANEL, LEFT

PARTS NOT IN THE DIAGRAMS

Model : R35DV1, R40/50DY1, RN35DV1, RN40/50DY1

PHASE SEQUENCER HIGH PRESSURE SWITCH LOW PRESSURE SWITCH CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR TXV

Page 69: Ceiling Cassette - Daikin Malaysia · 1 MFF0515 1. Model Name FC Type Of Air-Conditioner FF : Ceiling Cassette (Capacity Index 10/15) FC : Ceiling Cassette (Capacity Index 20-50)

Branches: • Penang Tel: 04-331 1670 • Johor Tel: 07-557 7788 • Pahang Tel: 09-567 6778 • Perak Tel: 05-548 2307 • Melaka Tel: 06-288 1133 • Sabah Tel: 088-722 194 • Sarawak Tel: 082-333 299 • Negeri Sembilan Tel: 06-768 8969 • Kedah Tel: 04-733 0235 • Kelantan Tel: 09-747 4678

GROUP ASSOCIATED (C&L) SDN BHD (109719-M)

Head Office: Tel: 03-7953 8388 Fax: 03-7956 4371Email: [email protected], [email protected]

www.da i k i n . com.my