DIMENZIONISANJE LE@I[NE PLO^E I ANKERA Merodavni uticaji: Nmin= 16.27 kN M= 50.91 kNm T= 14.37 kN Dimenzije stuba: L= 28 cm B= 19 cm Usvojene mere le`i{ne plo~e: L= 52 cm B= 25 cm 1 = 0.44 kN/cm2 2 = -0.46 kN/cm2 h = 0.45 m b = 0.25 m k = 0.12 m Pretpostavljaju se ankeri: M27; As(cm2) = 4.59 Z= 105.19 kN Zdop= 62.80 kN z = 7.63 kN/cm2 <11kN/cm2 USVAJAJU SE ANKERI: 2M27+2M27-klase ~vrsto}e ...5.6 Du`ina ankera: 100 cm POTREBNA DEBLJINA LE@I[NE PLO^E: ly/lx= 1.26 k= 0.112 m= 18.78 kNcm/cm' M1= 2.09 kNcm/cm' tpot= 2.50 cm USVAJA SE DEBLJINA LE@I[NE PLO^E: t pl= 25 mm KONTROLA ZAVARENOG SPOJA 2 Dimenzije stuba: L = 28 B = 19 1 M= 50.91 kNm 26 28 T = 14.37 kN a1(mm) = 7 a2(mm) = 8 17 L1 =L01-2a= 24.60 cm 19 L2 =L02-2a= 15.40 cm Yc= 14.4 cm Ix{= 6846.16 cm4 Wx{= 462.58 cm4 NAPON U TA^KI 2: nmax= 110.057 MPa nmax<120MPa T M N L

Upload: calest

Post on 25-Oct-2015

21 views

Category:

Documents


11 download

DESCRIPTION

c

TRANSCRIPT

Page 1: CELIK ANKERIUJA

DIMENZIONISANJE LE@I[NE PLO^E I ANKERAMerodavni uticaji: Nmin= 16.27

M= 50.91T= 14.37

Dimenzije stuba: L= 28B= 19

Usvojene mere le`i{ne plo~e:L= 52B= 25

1 = 0.44 2 = -0.46

h = 0.45b = 0.25k = 0.12

Pretpostavljaju se ankeri: M27; As(cm2) = 4.59Z= 105.19 kN

Zdop= 62.80 kN z = 7.63 kN/cm2 <11kN/cm2

USVAJAJU SE ANKERI: 2M27+2M27-klase ~vrsto}e ...5.6

Du`ina ankera: 100 cm

POTREBNA DEBLJINA LE@I[NE PLO^E:

ly/lx= 1.26k= 0.112

m= 18.78 kNcm/cm'M1= 2.09 kNcm/cm'

tpot= 2.50 cmUSVAJA SE DEBLJINA LE@I[NE PLO^E: t pl= 25 mm

KONTROLA ZAVARENOG SPOJA

2 Dimenzije stuba: L =B =

1M= 50.91

26 28 T = 14.37a1(mm) = 7a2(mm) = 8

17 L1 =L01-2a= 24.6019 L2 =L02-2a= 15.40

Yc= 14.4 cmIx{= 6846.16 cm4

Wx{= 462.58 cm4

NAPON U TA^KI 2:nmax= 110.057 MPa

nmax<120MPa

T

M

N

L

Page 2: CELIK ANKERIUJA

NAPON U TA^KI 1: n= 92.09 MPa3.65 MPa

92.16 MPa (<120MPa)VII=su=

Page 3: CELIK ANKERIUJA

kNkNmkNcmcm

cmcm

kN/cm2kN/cm2 treba da bude manje od 0,8kN/cm2 za MB 30,odnosno manje od 0,5kN/cm2 za MB 20

mmm

(As)str 98 djacka knjiga ILI 835

TABLICA STRANA 854<11kN/cm2 VIDI STR.351 (napon zatezanja u jednom ankeru)zato x0.5

7.065

VIDI STR.358

KONZOLNI LIMOVI: Usvajaju se limovi d=15mm Podlivanje le`i{ne spojnice cem.malterom MB 30.

28 cm19 cm

kNmkN

cmcm

Page 4: CELIK ANKERIUJA

(<120MPa)

Page 5: CELIK ANKERIUJA

treba da bude manje od 0,8kN/cm2 za MB 30,odnosno manje od 0,5kN/cm2 za MB 20

(napon zatezanja u jednom ankeru)zato x0.5

Usvajaju se limovi d=15mm Podlivanje le`i{ne spojnice cem.malterom MB 30.