Central Emergency Lighting Inverter Systems
1
Series highlights
PerformanceThe Emerg-Power Systems works with any type of lightingload to provide full light output for minimum 90 min. It isdesigned to support incandescent, fluorescent, HID*, quartzre-strike or halogen lamps. It will work into these loads at coldstarts for all normally off circuits or normally on circuits.
*except IPS systems
True Sine WaveformUsing a solid-state, pulse width modulation (PWM) inverterthe systems produce pure sinusoidal output waveform withless than 3% maximum Total Harmonic Distortion (THD) forlinear loads. Microprocessor and crystal controlled.
ReliabilityThe product is third generation inverter technology. Provensolid design with double ratings of all critical components.LVD (Low Voltage Disconnect) for long power outageseliminates battery drain.
BatteriesFront access connections for easy installation significantlyreduce the footprint, installation and maintenance time whileincreasing safety. Automatic restart and recharge uponrestoration of utility.
ApprovalsUL listed to UL924. Meets UL924, NFPA101, NFPA70, NFPA110, OSHA, UBC, SBCCI.N.Y. City approved.
ApplicationsEmerg-Power Systems can be used in almost every type ofbuilding, especially in architecturally sensitive applications orwhen maintenance costs and individual testing of unitequipment becomes very significant. Our systems aredesigned to work with power factor corrected as well as themost recent T5 and T5-HO electronic ballasts.
OptionsA full range of options such as integrated output circuitbreakers, bypass relays, dry contacts, etc., makesEmerg-Power Power Systems an industry leader in emergencylighting central systems (see page 12)
Features
Self-Diagnostic/Self-TestingProgrammable monthly and annual self-testing.Proven self-diagnostic with over 120 parametersstored in separate memory logs for Test, Eventand Alarm. Microprocessor monitoring andcontrol.
Low heat dissipationVery low heat loss technology in normaloperating mode (see specifications forexact values). Convection cooling in normalmode with forced air during emergency mode.Battery cabinets: convection cooling only.
Maximum EfficiencyHighest efficiency in the industry, 98% at 100%load with no requirement for cooling in normaloperating mode.Low input harmonic distortion <10%.
Versatile InstallationModular design, easy front access freestandingcabinets, fasten together when more than onecabinet is required. Optional seismic kitavailable. All wiring provided is pre-cut andterminated, along with the necessary hardwareand electrical fittings, for proper installation.
Complete ProtectionInput circuit breaker and fused battery circuit isstandard. Systems offer overload capacity,short-circuit protection, current- limiting,low-battery disconnect, reverse polarity andbrownout protection as standard.
Thermal PerformanceBonded fin heat sink technology for maximumthermal performance. Cooling fans are energizedonly in inverter mode.
Monitoring and ControlUser friendly programmable interface with LEDindicators and LCD display provides full meteringvalues, easy program and control functions anda wide range of visual and audible alarms.
Compact Series
1PH IPS
1PH FTC
3PH FTC
Outdoor 1 PH FTC
Outdoor 3 PH FTC
500VA 1500 VA 2000VA 3KVA 4KVA 4.8KVA 8KVA 16.7KVA 50KVACapacity (KVA=KW)
System type
2
SUMMARY
GENERAL PRESENTATION PAGE 1,2
SINGLE PHASE COMPACT SYSTEMS PAGE 3,4
SINGLE PHASE INTERRUPTIBLE SYSTEMS PAGE 5,6
SINGLE PHASE FAST TRANSFER SYSTEMS PAGE 7,8
THREE PHASE FAST TRANSFER SYSTEMS PAGE 9,10
OUTDOOR SYSTEMS PAGE 11
OPTIONAL FEATURES - DETAILS PAGE 12
USER INTERFACE AND DISPLAY PAGE 13
WHAT TO CONSIDER WHEN PAGE14REQUESTING A CENTRAL SYSTEM
Benefits
Compliance with NFPA101The self-testing meets the requirements of NFPA
and UL. User programmable time of testing.Test results, events or alarms can be downloaded
from history logs. Load monitoring. Reducedtesting/service time.
Less air-conditioningReduced costs for air-conditioning required to
ensure the optimum operating temperature whencompared with equivalent systems that dissipatemuch more heat. Higher reliability of fans and the
electronic components.
Lower energy billsLow consumption of the system itself will
result in lower energy bills paid over the system lifetime. Comparative analysis available on request.
Easy to installQuick installation and connection through flexible
cable entries and fast access terminal blocks.Reduced footprint for systems with stackable
cabinets. Low MTTR (<15 min.) due to modulardesign, quick disconnect means and
frontal access.
Reduced damage risksThe full protection of the system will eliminate
damage created by external events and willincrease lifetime of the electronics and the
batteries. Also will provide safety duringmaintenance.
Increased MTBFIncreased reliability and reduced
preventative maintenance.No air filters needed.
Easy maintenanceEasier diagnostic, troubleshooting, preventative
maintenance and service through the indicators anddisplay or by using the history logs. Remote
versions available.
3
ELECTRICAL/MECHANICAL CHARACTERISTICS
1- system capacity can be upgraded in the field up to 2000VA by adding more battery cabinets. Re-programming required by factory service technician.2- batteries are installed in separate modular cabinets3- battery cabinets are stackable. Must be installed under the electronics cabinet4- special voltages can change the size, weight or number of cabinets
For all fluorescent/incandescent or HID light loads
UL listed to UL924. Meets NFPA101, NFPA70, NFPA 110,OSHA, UBC, SBCCI. N.Y City approved.
Emerg-Power Systems COMPACT SERIES
Uninterruptible emergency lighting, 1PH,inverter system 500VA – 2000VA
Features:98% efficient @ full load
PWM/MOSFET technology
Self-testing/Self-diagnostic
User programmable with password protection
Standard input circuit breaker
Standard output circuit breaker
Micro-processor controlled
Floor or wall mountable
Field upgradeable (500VA steps)
90 min. standard run time
Electronic and magnetic ballast compatible
Automatic event, test and alarm log
LCD display
Very small footprint (stackable cabinets)
Maintenance free standard batteries
Forced air cooling during emergency mode only
(4)
120277
SG- lead calcium 500100015002000
ICB OCBxxxx*OCAxxxx*
Inputvoltage
Batterytype
VA/Wrating
Outputvoltage
Runtime
ORDERING INFORMATION Example: 120SG1500-FTCM-120-90-ICB-OCB0420-WB
Systemtype
Inputbreaker
Outputbreakers Options
FTCM 120277
90
1- see page 12 for options description2- other run times available3- special voltages may change the size, weight or number of cabinets4- max. 2 more additional output breakers for a total of 3. See page 12 for output breakers details.
NOFF- normally OFF outputWB- wall mount bracketDCS- dry summary alarm contactsINVON- inverter on dry contactVTD- variable time delayBPR- bypass relayRMP- remote metering panelRSAP- remote summary alarm panelRS232- communication interfaceMOD- modem
(4)(3) (2) (1)(3)
PowerRating(1)
VA=W
Effic.at fullload%
Max. inputcurrent (A)
Heatloss innormalmode(BTU/hr)
Batt.
VDC
Batt.
A
No. ofbatt.
UPS cabinetdimensions
Battery cabinetdimensions(2)(3)
No. ofbattcab.
Batt. cab.weightlbs
(empty)
UPS cab.weightlbs
Batt.weightlbs
Totalsystemweight(lbs)
120V
277V
W” H” D” W” H” D”
500 98 5.2 2.3 34 48 13.5 4 26 10 10 26 10 10 1 22 77 107 206
1000 98 10.5 4.5 68 48 26.5 8 26 10 10 26 10 10 2 22 77 214 335
1500 98 15.6 6.8 102 48 40 12 26 10 10 26 10 10 3 22 77 321 464
2000 98 20.8 9 136 48 52 16 26 10 10 26 10 10 4 22 77 428 592
4
Design
Control
Metering
Communications
Stand-by no break. PWM inverter type utilizingMOSFET technology with 2ms transfer time.Microprocessor controlled , 2 x 20-character displaywith touch pad controls & functions5 LED indicators & alarm with ring-back featureInput & Output Voltage, Battery Voltage, Battery &Output Current, Output VA, Temperature, InverterWattage
Optional RS-232 port (DB9)
120 or 277VAC 1-phase 2-wire +10% - 15%.Contact factory for all other voltages.Limiting inrush current to less than 125%, 10times for 1 line cycle60Hz, +/-3Hz
Standard Input Circuit Breaker
<10%
0.5 lag/lead
Voltage
Input Power Walk-In
Input Frequency
Protection
Harmonic Distortion
Power Factor
Voltage
Static Voltage
Dynamic Voltage
Harmonic DistortionOutput FrequencyLoad Power FactorInverter OverloadProtection
Crest Factor
120 or 277VAC 1-phase 2-wire.Contact factory for all other voltages.Load current change +/-2%, batterydischarge +/-12.5%+/-2% for +/-25% load step change,+/-3% for a 50% load step change,recovery within 3 cycles<3% THD for linear load60Hz +/- 0.05Hz during emergency mode0.5 lag to 0.5 lead115% for 5 minutesStandard Output Circuit Breaker (normally on)2.8
Storage/Transport
Operating temperature
Altitude
Relative Humidity
Audible noise
-4ºF to 158ºF (-20ºC to 70ºC) without batteries-0ºF to 104ºF (-18ºC to 40ºC) with batteriesSystem operates safely from 32°F to 104°F(0°C to 40°C) but optimum operation isbetween 68° F and 86°F (20°C to 30°C).Battery performance can be affected bytemperature.<10,000 feet (above sea level) withoutde-rating0 to 95% non-condensing
45 dBA @ 1m from surface in emergency
mode
CABINETS
Modular design, freestanding or wall mount NEMA type 1steel cabinets powder coated for corrosion and scratchresistance. Front access design. Cabinets are stackable.Top and left side conduit entry with knockouts.
INVERTERUsing MOSFET/PWM technology the inverter converts theDC voltage supplied by the batteries to AC voltage of aprecise stabilized amplitude and frequency, suitable for mostsophisticated electrical equipment. True sinusoidal outputwaveform with very low distortion (less than 3% for linearloads). Overload capability of up to 150% for 12 line cycles.
CHARGERFully automatic, temperature compensated, microprocessorcontrolled charger recharges fully discharged batteries inmaximum 24 hours at nominal AC input voltage. AC inputcurrent limiting and over-voltage protection included.
BATTERYSystem is provided with 10 year, maintenance free, sealedvalve regulated lead calcium batteries. 90 min. standarddischarge time at full load under normal operatingtemperature. Low Voltage Disconnect protection included.No special ventilation required.
SUPERVISIONAutomatic self-test consists of a 5-minute monthly and 90-minute annual function.The front-mounted control panel includes 5 LED indicators,a 2-line 20-character LCD display, a keypad to control andmonitor the internal operation of the system. This allows theoperator to easily “watch” system functions as they occurand check on virtually any aspect of the system's operation.Self-diagnostic function monitors, controls, generates alarmsand memorizes events.
ALARMSHigh/Low Battery Charger Voltage, High/Low AC InputVoltage, Near Low Battery, Low Battery, Load ReductionFault, Output Overload, High Ambient Temperature, InverterFault, Output Fault, Optional Output Circuit Breaker Trip
OPTIONAL FEATURESNormally OFF output, Output Circuit Breakers, Output TripAlarm, RS232 communication port, 12 Hours Fast Recharge,Remote Meter Panel, Remote Summary Alarm Panel,Summary Alarm Dry Form C Contact, Inverter on DryContacts, Variable Time Delay, Modem, Bypass Relays, Wallmount bracket
FACTORY START-UPIncludes one additional year of warranty.See warranty conditions.
WARRANTY(full limited warranty conditions available upon request)Limited manufacturer warranty is one-year, parts and labor,for system electronics or two-year with factory start-upprogram. Battery warranty is one year full plus 9 years pro-ratafor a total of 10 years, under normal operating conditions.System must be put in service within 180 days from shipdate in order to validate warranty.
NORMALEMERGENCYSINGLE LINE DIAGRAM
(1)
1- max. 3 months at 104° F (40° C)
Characteristics, specifications or dimensions subject to change without notice.
SYSTEM SPECIFICATIONSGENERAL
ELECTRICAL INPUT
ELECTRICAL OUTPUT
EVIRONMENTAL CONDITIONS
5
Features:98% efficient @ full load
PWM/IGBT technology
Self-testing/Self-diagnostic
User programmable with password protection
Standard input circuit breaker
Standard Normally Off output
RS232 communication port
Micro-processor controlled
Automatic event and alarm log
90 min. standard run time
Generator compatibility
Electronic and magnetic ballast compatible
Custom voltages available
Automatic event, test and alarm log
LCD display
Reduced footprint (stackable cabinets)
Maintenance free standard batteries
Forced air cooling during emergency mode only
Emerg-Power Systems IPS SINGLE PHASE SERIES
Interruptible emergency lightinginverter system 1.5KVA –16.7KVA
For all fluorescent/incandescent loads
ELECTRICAL/MECHANICAL CHARACTERISTICS (data provided for standard lead calcium batteries)
1-consult factory for 20 year type batteries or for wet nickel cadmium batteries2- batteries are installed in the electronics cabinet for 1.5 to 5kVA systems3- battery cabinets are stackable. To be installed on the right side of the electronics cabinet4- special voltages or batteries may change the size, weight or number of cabinets
UL listed to UL924. Meets NFPA101, NFPA70,NFPA 110, OSHA, UBC, SBCCI. N.Y City approved.
(4) (1)(4)
120208240277
SG - sealedlead calciumNC - wetnickel
cadmium
1500225030003750500060008000100001250016700
ICB OCBxxxx -no trip alarm
OCAxxxx -with trip alarm
Batterytype
VA/Wrating
Outputvoltage
Runtime
ORDERING INFORMATION Example: 277SG6000-IPS-277-90-ICB-RS232-OCB0420-DCS-20Y
Systemtype
Inputbreaker
Outputbreakers Options
IPS 120277208
120/240120/277
90 20Y - 20 yr sealed batteries12HR - 12 hr fast rechargeMBYP - internal bypass switchEMBP - external bypass switchRMP - remote metering panelRSAP - remote summary alarm panelDCS - dry summary alarm contactsINVON - inverter on dry contactsVTD - variable time delayMOD - external modemFAX - fax modemBPR - bypass relaysDIAL - autodialerSEIS - seismic mountingZONEM - zone monitoringBATM - battery cycle warranty monitor
1- see page 12 for options description2- other run times available3- special voltages may change the size, weight or number of cabinets4- max. 12 unsupervised single pole positions or 8 with trip alarm. For more output breakers please consult factory. See page 12 for output breakers option details.5- external bypass switch is not compatible with integrated output circuit breakers. Input/output voltage has to be the same.
RS232portRS232
(1)(3) (2)
(4)
(5)
Inputvoltage (3)
1.52.253
3.755681012.516.7
98989898989898989898
1624
3239506384105131174
7111417222736455776
30303030303030303030
NANANANANA11222
NANANANANA210232420420464
250265295305315350375435465530
29644459274088811101480177622202960
5467098871045120316702087263131053954
47474747474747474747
25252525252525252525
NANANANANA3030303030
NANANANANA4747474747
NANANANANA2525252525
(2) (3)
1021532042553404085446808501136
487296120144180240144180240
46810121520243040
39383837404039828280
Powerrating
kVA/kW
Effic.at fullload%
Max. inputcurrent (A)
120V
277V
UPS cabinetdimensions
W” H” D” W” H” D”
Battery cabinetdimensions
No. ofbattcab.
Batt. cab.weightlbs
(empty)
UPS cab.weightlbs
Batt.weightlbs
Totalsystemweightlbs
Heat lossin normalmode(BTU/hr)
Batt.
A
No. ofbatt.
Batt.
VDC
6
Design
Control
Metering
Communications
Stand-by no break. PWM inverter type utilizingIGBT technology with 50ms transfer time.Microprocessor controlled , 2 x 20-characterdisplay with touch pad controls & functions5 LED indicators & alarm with ring-back featureInput & Output Voltage, Battery Voltage, Battery &Output Current, Output VA, Temperature, InverterWattage
RS-232 port (DB9)
120 or 277VAC 1-phase 2-wire +10% - 15%.Contact factory for all other voltages.Limiting inrush current to less than 125%, 10times for 1 line cycle
60Hz, +/-3%, 50Hz available upon request
Input Circuit Breaker<10%
0.5 lag/lead
Voltage
Input Power Walk-In
Input Frequency
Protection
Harmonic Distortion
Power Factor
Voltage
Static Voltage
Dynamic Voltage
Harmonic DistortionOutput FrequencyLoad Power FactorInverter OverloadProtectionCrest Factor
120 or 277VAC 1-phase 2-wire.Contact factory for all other voltages.Load current change +/-2%, batterydischarge +/-12.5%+/-2% for +/-25% load step change,+/-3% for a 50% load step change,recovery within 3 cycles<3% THD for linear load60Hz +/- 0.05Hz during emergency mode0.5 lag to 0.5 lead125% for 5 minutesOptional Distribution Circuit Breaker2.8
Storage/Transport
Operating temperature
Altitude
Relative Humidity
Audible noise
-4ºF to 158ºF (-20ºC to 70ºC) without batteries-0ºF to 104ºF (-18ºC to 40ºC) with batteriesSystem operates safely from 32°F to 104°F(0°C to 40°C) but optimum operation isbetween 68° F and 86°F (20°C to 30°C).Battery performance can be affected bytemperature.<10,000 feet (above sea level) withoutde-rating0 to 95% non-condensing
45 dBA @ 1m from surface in emergency mode
NORMALEMERGENCYSINGLE LINE DIAGRAM
*output breakers are optional
(1)
(2)
Characteristics, specifications or dimensions subject to change without notice.
1- max. 3 months at 104° F (40° C)
CABINETS
Modular design, freestanding NEMA type 1 steel cabinetspowder coated for corrosion and scratch resistance. Frontaccess design through hinged lockable doors requires only39” front clearance and 12” top clearance. Cabinets arestackable if required to further reduce the footprint. Top andleft side conduit entry with knockouts.
INVERTERUsing IGBT/PWM technology the inverter converts DCvoltage supplied by the batteries to AC voltage of a precisestabilized amplitude and frequency, suitable for mostsophisticated electrical equipment. True sinusoidal outputwaveform with very low distortion (less than 3% for linearloads). Overload capability of up to 150% for 12 line cycles.
CHARGERFully automatic, temperature compensated, microprocessorcontrolled charger recharges fully discharged batteries inmaximum 24 hours at nominal AC input voltage. AC inputcurrent limiting and over-voltage protection included.
BATTERYSystem is provided standard with 10 year, maintenance free,sealed valve regulated, front terminals lead calcium batteries.20 years life sealed lead calcium or wet nickel cadmiumbatteries also available. 90 min. standard discharge time atfull load under normal operating temperature. Low VoltageDisconnect protection included. No special ventilationrequired.
SUPERVISIONAutomatic self tests consist of a 5-minute monthly and90-minute annual function.The front-mounted control panel includes 5 LED indicators,a 2-line 20-character LCD display, a keypad to control andmonitor the internal operation of the system. This allows theoperator to easily “watch” system functions as they occurand check on virtually any aspect of the system's operation.Standard RS232 diagnostic interface.
ALARMSHigh/Low Battery Charger Voltage, High/Low AC InputVoltage, Near Low Battery, Low Battery, Load ReductionFault, Output Overload, High Ambient Temperature, InverterFault, Output Fault, Optional Output Circuit Breaker Trip
OPTIONAL FEATURESOutput Circuit Breakers, Output Trip Alarms, 20 Years SealedBatteries, 12 Hours Fast Recharge, Internal/ExternalMaintenance Bypass Switch, Remote Meter Panel, RemoteSummary Alarm Panel, Summary Alarm Dry Form C Contact,Inverter on Dry Contacts, Fax/Modem, Bypass Relays, AutoDialer, Seismic Mounting.
FACTORY START-UPIncludes one additional year of warranty. See warranty conditions.
WARRANTY(full limited warranty conditions available upon request)Limited manufacturer warranty is one-year, parts and labor,for system electronics or two-year with factory start-upprogram. Battery warranty is one year full plus 9 years pro-ratafor a total of 10 years, under normal operating conditions.System must be put in service within 6 months from shipdate in order to validate warranty.2- Consult factory for other type batteries than the standard one.
SYSTEM SPECIFICATIONSGENERAL
ELECTRICAL INPUT
ELECTRICAL OUTPUT
EVIRONMENTAL CONDITIONS
7
Features:98% efficient @ full loadPWM/IGBT technologySelf-testing/Self-diagnosticUser programmable with password protectionStandard input circuit breakerRS232 communication portMicro-processor controlledAutomatic event and alarm log90 min. standard run timeGenerator compatibilityElectronic and magnetic ballast compatibleCustom voltages availableAutomatic event, test and alarm logLCD displayReduced footprint (stackable cabinets)Maintenance free standard batteriesForced air cooling during emergency mode only
Emerg-Power Systems FTC SINGLE PHASE SERIES
Uninterruptible emergency lightinginverter system 1.5KVA –16.7KVA
For all fluorescent/incandescent or HID light loads
ELECTRICAL/MECHANICAL CHARACTERISTICS (data provided for standard lead calcium batteries)
1-consult factory for 20 year type batteries or for wet nickel cadmium batteries2- batteries are installed in the electronics cabinet for 1.5 to 5kVA systems3- battery cabinets are stackable. To be installed on the right side of the electronics cabinet4- special voltages or batteries may change the size, weight or number of cabinets
UL listed to UL924. Meets NFPA101, NFPA70, NFPA 110,OSHA, UBC, SBCCI. N.Y City approved.
(4) (1) (4)
120208240277
SG - sealedlead calciumNC - wetnickel
cadmium
1500225030003750500060008000100001250016700
ICB OCBxxxx -no trip alarm
OCAxxxx -with trip alarm
Batterytype
Outputvoltage
Runtime
ORDERING INFORMATION Example: 277SG6000-FTC-277-90-ICB-RS232-OCB0420-DCS-20Y
VA/Wrating
Inputbreaker
Outputbreakers Options
FTC 120277208
120/240120/277
90 20Y - 20 yr sealed batteries12HR - 12 hr fast rechargeMBYP - internal bypass switchEMBP - external bypass switchRMP - remote metering panelRSAP - remote summary alarm panelDCS - dry summary alarm contactsINVON - inverter on dry contactsNOFF - normally OFF outputMOD - external modemFAX - fax modemBPR - bypass relaysDIAL - autodialerSEIS - seismic mountingZONEM - zone monitoringBATM - battery cycle warranty monitor
1- see page 12 for options description2- other run times available3- special voltages may change the size, weight or number of cabinets4- max. 12 unsupervised single pole positions or 8 with trip alarm. For more output breakers please consult factory. See page 12 for output breakers option details.5- external bypass switch is not compatible with integrated output circuit breakers. Input/output voltage has to be the same6- normally off loads cannot exceed 20% of total KVA rating with any combination of H.I.D. loads.
RS232portRS232
(4) (1)(3) (2)
(5)
(6)
Inputvoltage (3)
Systemtype
1.52.253
3.755681012.516.7
98989898989898989898
16243239506384105131174
7111417222736455776
30303030303030303030
NANANANANA11222
NANANANANA210232420420464
250265295305315350375435465530
29644459274088811101480177622202960
5467098871045120316702087263131053954
47474747474747474747
25252525252525252525
NANANANANA3030303030
NANANANANA4747474747
NANANANANA2525252525
(2) (3)
1021532042553404085446808501136
487296120144180240144180240
46810121520243040
39383837404039828280
Powerrating
kVA/kW
Effic.at fullload%
Max. inputcurrent (A)
120V
277V
UPS cabinetdimensions
W” H” D” W” H” D”
Battery cabinetdimensions
No. ofbattcab.
Batt. cab.weightlbs
(empty)
UPS cab.weightlbs
Batt.weightlbs
Totalsystemweightlbs
Heat lossin normalmode(BTU/hr)
Batt.
A
No. ofbatt.
Batt.
VDC
8
Design
Control
Metering
Communications
Stand-by no break. PWM inverter type utilizing IGBTtechnology with 2ms transfer time.Microprocessor controlled , 2 x 20-character displaywith touch pad controls & functions5 LED indicators & alarm with ring-back featureInput & Output Voltage, Battery Voltage, Battery &Output Current, Output VA, Temperature, InverterWattage
RS-232 port (DB9)
120 or 277VAC 1-phase 2-wire +10% - 15%.Contact factory for all other voltages.Limiting inrush current to less than 125%, 10times for 1 line cycle
60Hz, +/-3%, 50Hz available upon request
Input Circuit Breaker<10%
0.5 lag/lead
Voltage
Input Power Walk-In
Input Frequency
ProtectionHarmonic Distortion
Power Factor
Voltage
Static Voltage
Dynamic Voltage
Harmonic DistortionOutput FrequencyLoad Power FactorInverter OverloadProtectionCrest Factor
120 or 277VAC 1-phase 2-wire.Contact factory for all other voltages.Load current change +/-2%, batterydischarge +/-12.5%+/-2% for +/-25% load step change,+/-3% for a 50% load step change,recovery within 3 cycles<3% THD for linear load60Hz +/- 0.05Hz during emergency mode0.5 lag to 0.5 lead125% for 5 minutesOptional Distribution Circuit Breaker2.8
Storage/Transport
Operating temperature
Altitude
Relative Humidity
Audible noise
-4ºF to 158ºF (-20ºC to 70ºC) without batteries-0ºF to 104ºF (-18ºC to 40ºC) with batteriesSystem operates safely from 32°F to 104°F(0°C to 40°C) but optimum operation isbetween 68° F and 86°F (20°C to 30°C).Battery performance can be affected bytemperature.<10,000 feet (above sea level) withoutde-rating0 to 95% non-condensing
45 dBA @ 1m from surface in emergency
mode
CABINETS
Modular design, freestanding NEMA type 1 steel cabinetspowder coated for corrosion and scratch resistance. Frontaccess design through hinged lockable doors requires only39” front clearance and 12” top clearance. Cabinets arestackable if required to further reduce the footprint. Top andleft side conduit entry with knockouts.
INVERTERUsing IGBT/PWM technology the inverter converts the DCvoltage supplied by the batteries to AC voltage of a precisestabilized amplitude and frequency, suitable for mostsophisticated electrical equipment. True sinusoidal outputwaveform with very low distortion (less than 3% for linearloads). Overload capability of up to 150% for 12 line cycles.
CHARGERFully automatic, temperature compensated, microprocessorcontrolled charger recharges fully discharged batteries inmaximum 24 hours at nominal AC input voltage. AC inputcurrent limiting and over-voltage protection included.
BATTERYSystem is provided standard with 10 year, maintenance free,sealed valve regulated, front terminals lead calcium batteries.20 years life sealed lead calcium or wet nickel cadmiumbatteries also available. 90 min. standard discharge time atfull load under normal operating temperature. Low VoltageDisconnect protection included. No special ventilationrequired.
SUPERVISIONAutomatic self tests consist of a 5-minute monthly and90-minute annual function.The front-mounted control panel includes 5 LED indicators,a 2-line 20-character LCD display, a keypad to control andmonitor the internal operation of the system. This allows theoperator to easily “watch” system functions as they occurand check on virtually any aspect of the system's operation.Standard RS232 diagnostic interface.
ALARMSHigh/Low Battery Charger Voltage, High/Low AC InputVoltage, Near Low Battery, Low Battery, Load ReductionFault, Output Overload, High Ambient Temperature, InverterFault, Output Fault, Optional Output Circuit Breaker Trip
OPTIONAL FEATURESOutput Circuit Breakers, Output Trip Alarms, 20 Years SealedBatteries, 12 Hours Fast Recharge, Internal/ExternalMaintenance Bypass Switch, Remote Meter Panel, RemoteSummary Alarm Panel, Summary Alarm Dry Form C Contact,Inverter on Dry Contacts, Normally OFF output, Fax/Modem,Bypass Relays, Auto Dialer, Seismic Mounting.
FACTORY START-UPIncludes one additional year of warranty. See warrantyconditions.
WARRANTY(full limited warranty conditions available upon request)Limited manufacturer warranty is one-year, parts and labor,for system electronics or two-year with factory start-upprogram. Battery warranty is one year full plus 9 years pro-ratafor a total of 10 years, under normal operating conditions.System must be put in service within 6 months from shipdate in order to validate warranty.2- Consult factory for other type batteries than the standard one.
INPUTBREAKER
MICROPROCESSORCONTROLLED PWM
BI-DIRECTIONALINVERTER/BATT. CHARGER
AC TO DC
DC TO AC
BATTERY
OUTPUTTRANSFORMER
AUTOMATICTRANSFERMODULE
OUTPUTBREAKER
NORMALEMERGENCYSINGLE LINE DIAGRAM
*output breakers are optional
1- max. 3 months at 104° F (40° C)
(2)
Characteristics, specifications or dimensions subject to change without notice.
NORMALLY ONOUTPUT CIRCUIT
(1)
SYSTEM SPECIFICATIONSGENERAL
ELECTRICAL INPUT
ELECTRICAL OUTPUT
EVIRONMENTAL CONDITIONS
9
Emerg-Power Systems 3FTC THREE PHASE SERIES
Uninterruptible emergency lighting inverter system 4.8KVA –50KVA
Features:98% efficient @ full loadPWM/IGBT technologySelf-testing/Self-diagnosticUser programmable with password protectionStandard input circuit breakerStandard internal bypass switchRS232 communication portMicro-processor controlledAutomatic event and alarm log90 min. standard run timeGenerator compatibilityAvailable in Y or ∆ input configurationCustom voltages availableAutomatic event, test and alarm logLCD displayReduced footprintMaintenance free standard batteriesForced air cooling during emergency only
ELECTRICAL/MECHANICAL CHARACTERISTICS (data provided for standard lead calcium batteries)
PowerRating
kVA/kW
Effic.at fullload%
Heatloss innormalmode(BTU/hr)
Batt.
A
Max. inputcurrent (A)
120/208V
277/480V
No. ofbatt.
UPS cabinetdimensions
W” H” D” W” H” D”
Battery cabinetdimensions
No. ofbattcab.
Batt. cab.weightlbs
(empty)
UPS cab.weightlbs
Batt.weightlbs
Totalsystemweightlbs
4.8681012.516.724334050
98989898989898989898
1721
2835435884115139174
7912
15192536506075
326408
54468085011361632224427203400
144180240144180240240240240240
1215
20243040604010060
3030
3030303048484848
11
12221222
210210
232420420464700130013001300
535535
5356396396391250125014501450
8881110
14801776222029604440608074009120
16331855
2247283532794063639086301015011980
1- consult factory for 20 year type batteries or for wet nickel cadmium batteries2- KVA=KW3- battery cabinets up to 16.7KVA are stackable. To be installed on the right side of the electronics cabinet4- special voltages or batteries may change the size, weight or number of cabinets
Batt.
VDC
3939
39818181117160194243
47474747474772727272
25252525252531313131
3030
3030303048484848
4747
4747474772727272
2525
2525252531313131
UL listed to UL924. Meets NFPA101, NFPA70, NFPA 110, OSHA,UBC, SBCCI. N.Y City approved.
For all fluorescent/incandescent or HID light loads
(4)
(3)(2)
(1)(4)
120/208277/480
SG - sealedlead calciumNC - wetnickel
cadmium
48006000800010000125001670024000330004000050000
ICB OCBxxxx -no trip alarmOCAxxxx -
with trip alarm
System
type
Battery
type
Input
voltage
Output
voltage
Run
time
ORDERING INFORMATION Example: 277/480SG24000-3FTC-277/480-90-ICB-RS232-MBYP-OCB1220-DCS-20Y
VA/W
rating
Input
breaker
Output
breakers Options
3FTC 120/208277/480
90 20Y - 20 yr sealed batteries12HR - 12 hr fast rechargeNOFF - normally off output 1PHEMBP - external bypass switchRMP - remote metering panelRSAP - remote summary alarm panelDCS - dry summary alarm contactsINVON - inverter on dry contactsNOFF3 - normally OFF output 3PHMOD - external modemFAX - fax modemBPR - bypass relaysDIAL - autodialerSEIS - seismic mountingZONEM - zone monitoringBATM - battery cycle warranty monitor
1- see page 12 for options description2- other run times available3- special voltages may change the size, weight or number of cabinets. 3 wire, ∆ input configuration available.4- max. 12 unsupervised single pole positions or 8 with trip alarm, up to 16.7kVA systems. 24 unsupervised or 16 with trip alarm for systems 24kVA to50kVA. For more output breakers please consult factory. See page 12 for output breakers option details.5- external bypass switch is not compatible with integrated output circuit breakers. Input/output voltage has to be the same6- normally off loads cannot exceed 20% of total KVA rating with any combination of H.I.D. loads.
RS232
port
RS232 MBYP
Internal BypassSwitch (4)(3)(3) (2)
(5)
(6)
(6)
(1)
NORMALEMERGENCYMAINTENANCE
10
Design
Control
Metering
Communications
Stand-by no break. PWM inverter type utilizingIGBT technology with 2ms transfer time.Microprocessor controlled , 2 x 20-characterdisplay with touch pad controls & functions5 LED indicators & alarm with ring-back featureInput & Output Voltage, Battery Voltage, Battery &Output Current, Output VA, Temperature, InverterWattage
RS-232 port (DB9)
120/208 or 277/480 3 phase 4-wire +10% -15%. Contact factory for all other voltages.Limiting inrush current to less than 125%, 10times for 1 line cycle
60Hz, +/-3%, 50Hz available upon request
Input Circuit Breaker
<10%
0.5 lag/lead
Voltage
Input Power Walk-In
Input Frequency
ProtectionHarmonic Distortion
Power Factor
Voltage
Static Voltage
Dynamic Voltage
Harmonic DistortionOutput FrequencyLoad Power FactorInverter OverloadProtectionCrest Factor
120/208 or 277/480VAC 3-phase 4-wire
Load current change +/-4%, batterydischarge +/-4%+/-3% for +/-25% load step change,+/-6% load step change,recovery within 3 cycles<3% THD for linear load60Hz +/- 0.05Hz during emergency mode0.5 lag to 0.5 lead115% for 5 minutesOptional Distribution Circuit Breaker2.8
Storage/Transport (C)
Operating temperature
Altitude
Relative Humidity
Audible noise
-4ºF to 158ºF (-20ºC to 70ºC) without batteries-0ºF to 104ºF (-18ºC to 40ºC) with batteriesSystem operates safely from 32°F to 104°F(0°C to 40°C) but optimum operation isbetween 68° F and 86°F (20°C to 30°C).Battery performance can be affected bytemperature.<10,000 feet (above sea level) withoutde-rating0 to 95% non-condensing
45 dBA @ 1m from surface in emergency
mode
SINGLE LINE DIAGRAM
*output breakers are optional
1- max. 3 months at 104° F (40° C)
(1)
Characteristics, specifications or dimensions subject to change without notice.
SYSTEM SPECIFICATIONSGENERAL
ELECTRICAL INPUT
ELECTRICAL OUTPUT
EVIRONMENTAL CONDITIONS
CABINETS
Modular design, freestanding NEMA type 1 steel cabinetspowder coated for corrosion and scratch resistance. Frontaccess design through hinged lockable doors requires only 39”front clearance and 12” top clearance. Cabinets are stackableup to 16.7kVA, if required to further reduce the footprint. Topand left side conduit entry with knockouts up to 16.7kVA . Leftside only for 24kVA and up.
INVERTERUsing IGBT/PWM technology the inverter converts the DCvoltage supplied by the batteries to AC voltage of a precisestabilized amplitude and frequency, suitable for mostsophisticated electrical equipment. True sinusoidal outputwaveform with very low distortion (less than 3% for linear loads).Overload capability of up to 150% for 12 line cycles.
CHARGERFully automatic, temperature compensated, microprocessorcontrolled charger recharges fully discharged batteries inmaximum 24 hours at nominal AC input voltage. AC inputcurrent limiting and over-voltage protection included.
BATTERYSystem is provided standard with 10 year, maintenance free,sealed valve regulated, front terminals lead calcium batteries.20 years life sealed lead calcium or wet nickel cadmiumbatteries also available. 90 min. standard discharge time at fullload under normal operating temperature. Low VoltageDisconnect protection included. No special ventilation or filtersrequired.
SUPERVISIONAutomatic self tests consist of a 5-minute monthly and90-minute annual function.The front-mounted control panel includes 5 LED indicators, a2-line 20-character LCD display, a keypad to control andmonitor the internal operation of the system. This allows theoperator to easily “watch” system functions as they occur andcheck on virtually any aspect of the system's operation.Standard RS232 diagnostic interface.
ALARMSHigh/Low Battery Charger Voltage, High/Low AC Input Voltage,Near Low Battery, Low Battery, Load Reduction Fault, OutputOverload, High Ambient Temperature, Inverter Fault, OutputFault, Optional Output Circuit Breaker Trip
OPTIONAL FEATURESOutput Circuit Breakers, Output Trip Alarms, 20 Years SealedBatteries, 12 Hours Fast Recharge, External MaintenanceBypass Switch, Remote Meter Panel, Remote Summary AlarmPanel, Summary Alarm Dry Form C Contact, Inverter on DryContacts, Normally OFF output, Fax/Modem, Bypass Relays,Auto Dialer, Seismic Mounting.
FACTORY START-UPIncludes one additional year of warranty.See warranty conditions
WARRANTY(full limited warranty conditions available upon request)Limited manufacturer warranty is one-year, parts and labor, forsystem electronics or two-year with factory start-up program.Battery warranty is one year full plus 9 years pro-rata for a total of10 years, under normal operating conditions.System must be put in service within 6 months from ship date inorder to validate warranty.2-Consult factory for other type batteries than the standard one.
11
Emerg-Power SystemsFTC3R&3FTC3ROUTDOOR SERIES
Outdoor uninterruptible emergency lighting inverter system 3KVA –8KVA
Features:98% efficient @ full loadPWM/IGBT technologySelf-testing/Self-diagnosticStandard input circuit breakerStandard internal bypass switchRS232 communication portStandard seismic zone 4 bracketsStandard summary dry contactsAutomatic event and alarm logNEMA 3R cabinet for outdoors90 min. standard run timeGenerator compatibilityCustom voltages availableAutomatic event, test and alarm logLCD displayOne size cabinetMaintenance free standard batteriesTemperature controlled cooling fans
ELECTRICAL/MECHANICAL CHARACTERISTICS
PowerRating
kVA/kW
Effic.at fullload%
HeatlossBTU
Batt.
A
Nomberof
batt. (2)
UPS cabinetdimensions
W” (1) H” D”
UPScab. weight
lbs
Batt.weightlbs
Totalsystem
weight lbs
3 (1PH)
4 (1PH)
5 (1PH)
6.5 (1PH)
8 (1PH)
4 ( 3PH)
5 ( 3PH)
6.5 (3PH)
8 (3PH)
98
98
98
98
98
98
98
98
98
255
340
408
544
680
326
408
544
680
120
144
180
240
144
144
180
240
144
10
12
15
20
24
12
15
20
24
48
48
48
48
48
48
48
48
48
535
535
535
639
639
639
1250
1250
1450
888
1110
1480
1776
2220
2960
4440
6080
7400
1633
1855
2247
2835
3279
4063
6390
8630
10150
1- factory installed floor mount brackets; add 2.5” to each side (total 53”)2- standard batteries are 5 year life expectancy. Batteries are installed in the same cabinet with electronics.3- UL rated for 90 min. run time for temperatures: 50ºF to 104ºF (10ºC to 40ºC) or -4ºF to 104ºF (-20ºC to 40ºC) with optional heater.4- NEMA type3R, freestanding, two-door powder coat cold rolled steel cabinet standard. Stainless steel enclosure is optional.
Batt.
VDC
37
40
40
39
82
39
39
39
81
76
76
76
76
76
76
76
76
76
30
30
30
30
30
30
30
30
30
UL listed to UL924. Meets NFPA101, NFPA70, NFPA 110, OSHA,UBC, SBCCI. N.Y City approved.
For all fluorescent/incandescent or HID light loads
(3) (4)
120, 1PH208, 1PH240, 1PH277, 1PH
120/208, 3PH277/480, 3PH
SG - sealedlead calcium
30004000500065008000
ICB OCBxxxx -no trip alarm
OCAxxxx -with trip alarm
System
type
Battery
typeInput
voltage
Output
voltage
Run
time
ORDERING INFORMATION Example: 277/480SG5000-FTC3R-277/480-90-ICB-RS232-MBYP-OCB1020-DCS-20Y
VA/W
rating
Input
breaker
Output
breakers Options
FTC3R –single phase
3FTC3R-3 phase
120208277
120/208277/480
90 10Y - 10 yr sealed batteries12HR - 12 hr fast rechargeNOFF - normally off outputEMBP - external bypass switchRMP - remote metering panelRSAP - remote summary alarm panelHTR - heaterINVON - inverter on dry contactsMOD - external modemFAX - fax modemBPR - bypass relaysSS - stainless steel enclosure
1- see page 12 for options description. Summary alarm dry contacts and seismic brackets are standard.2- other run times available3- 1PH are input voltages available for 1 phase systems. 3PH are input voltages available for 3phase systems.4- max. 14 unsupervised single pole positions or 8 with trip alarm. See page 12 for output breakers option details.5- not available in 3 phase version6- normally off loads cannot exceed 20% of total KVA rating with any combination of H.I.D. loads.
RS232
port
RS232 MBYP
Internal
Bypass Switch (1)(3)
(5)
(2)
(5)
(6)
(4)
12
SYSTEMS OPTIONS-DETAILS-
*See the ordering information pages for the applicable list of options for each system type
INTEGRATED OUTPUT CIRCUIT BREAKERS:
Trip AlarmOCB - No Breaker Trip
Alarm
OCA - With Breaker TripAlarm
Number of Circuit BreakersCombination of 1 pole, 2 pole and 3
pole breakers available.
*For max. number of circuit breakersavailable please consult factory
Breaker Rating(Amps)
*Various ratingsavailable
Number of poles
Blank - 1 pole-2P - 2 poles-3P - 3poles
Breaker VoltageBlank- matches system output
voltage-120VAC-208VAC-240VAC-277VAC-480VAC
Operation ModeBlank : Normally-On-NOFF : Normally-Off
-OCB 12 20
Distribution circuit breakers are for output load protection. Protection for the normally on and/or for the normally off loads. All circuitbreakers are rated for 10,000 AIC.If ordered, an audible and visual alarm activates when an output distribution circuit breaker is open or has tripped.
(-20YR) 20 Year Sealed Lead Calcium BatteriesMaintenance free battery requires no addition of water overthe life of the battery. The battery cells are housed inprotective, modular steel trays. Life expectancy is designedfor 20-years at 77ºF (25ºC).(-12HR) 12 Hour Fast RechargeBattery charger upgrade option which decreases the timerequired to return a fully discharged battery to the fullycharged state. The normal 24 hour recharge cycle is reducedto a 12 hour period.(-MBYP) Internal Maintenance Bypass SwitchInternally mounted device permits maintenance personnel toeasily bypass the protected equipment directly to the ACutility power. The manual make before break switch isolatesthe system to perform routine maintenance or servicingwithout interruption of utility power to the connected load.(-EMBP) External Maintenance Bypass SwitchThe external maintenance bypass switch is mounted in a 20”Hx 16”W x 9”D NEMA 1 separate enclosure, used to completelyisolate the inverter system from the connected load and ACutility input. This option allows the system to be safelypowered down for maintenance or service. The option maynot be used on systems with more than one single pole outputcircuit breaker which must be sized for the total system outputcurrent.(-RMP) Remote Meter PanelThe panel allows monitoring of parameters and control fromremote locations up to 150 feet away from the inverter system.Also, the remote panel provides a complete touch padinterface allowing the user to monitor, control and program theinverter system.(-RSAP) Remote Summary Alarm PanelWall mountable box provides visual and audible alarms withsilent switch. The panel consists of LED indicators and built inaudible alarm and may be located up to 1,000 feet away fromthe inverter system.(-DCS) Summary Alarm Dry ContactsForm C dry contacts for remote monitoring purposes. Rated at5 amps max. (250VAC/30VDC), the contacts will change statewhen any of the following alarms: High/Low Battery ChargerVoltage, High/Low AC Input Voltage, Near Low BatteryVoltage, Low Battery Voltage, Load Reduction Fault, HighAmbient Temperature, Inverter Fault, Output Fault, OutputOverload or Optional circuit breaker trip alarms, occurs.(-INVON) Inverter On Dry ContactsForm C dry contacts that will change state when the systemtransfers to battery operation(-VTD) Variable Time Delay (for normally off circuits)After a return of AC utility power, delays retransfer of theinverter for up to 15 min. and continues to supply emergencypower to the normally off circuits.
(-NOFF) Normally Off OutputThis output circuit is dedicated for the emergency onlyequipment. Emergency only equipment operates duringpower outages and when the system is on battery back up.This option leaves the normally off load circuits off duringnormal utility power conditions. A 1-pole circuit breaker isprovided. For 3 phase systems, 3 pole normally off circuitsare available as well.(-MOD) External ModemExternal modem device is designed to boost the signal levelof the RS-232 diagnostic interface to remote monitoringlocations located more than 100 feet away from the system.(-FAX) Internal Fax Modem
The internal fax modem enables the system to send a faxautomatically to several pre-programmed numbers when oneof the following conditions occurs: utility failure, output failureor any alarm. The Fax Modem option requires a user supplieddedicated phone line.(-BPR) Bypass RelaysInternal bypass relays will allow overriding circuits that can beswitched on/off, so in case of a power failure the emergencycircuits will be supplied from the inverter system whateverthe position of the switching device. Please consult factoryfor more details.(-DIAL) Auto DialerThe Auto Dialer modem option automatically dials up tofour user-programmable phone numbers in the event ofany system alarm condition. The option is designed todeliver a predetermined digital or audible message whenactivated. The Auto Dialer option requires a user supplieddedicated digital or analog phone line.(-SEIS) Seismic Mounting KitThe seismic mounting kit option is designed to preventsystem movement during seismic events. Heavy dutybrackets are provided to secure system cabinetry to floorsurfaces. Meets Zone 4 requirements.(-ZONEM) Zone MonitoringAllows voltage monitoring of different circuits than thestandard AC utility input. When the voltage of one of thesecircuits drops, the inverter system will go into batteryback-up operation mode. Number and voltage of themonitored circuits to be specified.(-RS232) Diagnostic InterfaceA microprocessor-based data acquisition system designed tomonitor all the system parameters remotely. Monitors alarmlog, event log and automatic test log. User can commandthe system to perform a battery test and review all systemparameters. Access is through a DB9 connector andtransmits at 9600 baud.(-BATM) Battery Cycle Warranty MonitorDevice providing battery monitoring at string level or celllevel. Please consult factory for more details.
13
Meter Functions• AC Voltage Input• AC Voltage Output• AC Current output• Battery Voltage• Battery Current• VA Output• Inverter Watts• Ambient Temperature• System Days (cumulative)• Inverter Minutes
(cumulative)Control Functions• Test and Event Logs
(75 logs stored) Logs record thefollowing data: Date, Time, Duration,Output Voltage, Output Current, AmbientTemperature and Alarms Present.
• Alarm Logs(50 logs stored) Logs record the followingdata: Date,Time and Alarm type
• Buzzer On/Off (toggle)• 5 LED Indicators and Alarms With
Ringback Feature
Program Functions• Set Date• Set Time• Set Monthly Test Date and Time• Set Annual Test Date and Time• Set Load Fault Reduction Setting• Set Low Battery Alarm• Set Near Low Battery Alarm• Set Low AC Voltage Alarm• Set High AC Alarm• Set Ambient Temperature Alarm
Alarms• High Battery Charger Voltage• Low Battery Charger Voltage• High AC Input Voltage• Low AC Input Voltage• Near Low Battery Voltage• Low Battery Voltage• Load Reduction Fault• High Ambient Temperature• Inverter Fault• Output Fault• Output Overload
System TestingSystems provide one manual and two automatic test functions. Manual tests of system may be performed at anytime using the control panel test key. Automatic self-diagnostic tests consist of a 5-minute monthly and 90-minuteannual function (the user can program the date and time of day the test is to take place). The microprocessor
automatically records the last 75 test events in its own separate test result log.
CONTROL PANEL & DISPLAY FUNCTIONS
1) Input voltage
Single phase (2 wire + ground) 120VAC□ 208VAC□ 240VAC□ 277VAC□Three phase (4 wire + ground, Y) 120/208VAC□ 277/480V□Three phase (3 wire + ground, ∆) 208VAC□ 480VAC□2) Output voltage
Single phase (2 wire + ground) 120VAC□ 208VAC□ 277VAC□Single phase (3 wire + ground) 120/240V□ 120/277□Three phase (4 wire + ground, Y) 120/208VAC□ 277/480V□3) System capacity
KVA rating :__________________ System series type______________
a) Please consider power consumption and maximum current of the complete lamp fixture not just the lamp
wattage (ie: ballasts consumption)
b) Please consider loads power factor
c) Even if the systems can run with 100% load, it is recommended as standard practice to use a
system with a capacity at least 10% over maximum connected load
4) Type of loads
Incandescent□ Fluorescent□ H.I.D (metal halide, high pressure sodium, etc.)□Others ____________________________________________________________________
5) Mode of operation
Normally ON (24/7)□ Normally OFF (emergency only)□ Switched loads ON/OFF□a) Please consider internal bypass relays or external override relays for switched On/Off loads.
Each switched output circuit will require a bypass relay. Maximum 20 A per circuit.
6) Integrated output circuit breakers
# of CB_____ Amps_____ Voltage_____ # of poles ___ NON□ NOFF□ Trip alarm□#of CB______ Amps_____ Voltage_____ # of poles ___ NON□ NOFF□ Trip alarm□7) Type of batteries (check availability for each type system)
10 yr sealed lead calcium□ 20 yr sealed lead calcium□ wet nickel cadmium□8) Options (refer to available options for each type system)
□12HR- 12 hr fast recharge□MBYP- internal bypass switch□EMBP- external bypass switch□RMP- remote metering panel□RSAP- remote summary alarm panel□DCS- dry summary alarm contacts□INVON- inverter on dry contacts□RS232- diagnostic interface□WB- wall mount bracket
14
CENTRAL SYSTEM REQUEST DATA
□NOFF – normally OFF output□MOD- external modem□FAX- fax modem□BPR- bypass relays How many_____□DIAL- autodialer□SEIS- seismic mounting□ZONEM- zone monitoring□VTD- variable time delay□BATM – battery cycle warranty monitor
All information and specifications contained in this catalogue are subject to change due to engineer design, errors and omissions.Illustrations and diagrams within this catalogue may vary from actual products.© 2008 Thomas & Betts Limited. All rights reserved. Printed in Canada 04/08/5000. Order No.: EL-InverterSystemsCAT-US