cfd analysis of rrs-mc500 air flow analysis

24
CFD Analysis of RRS - MC500 Air F low A nalysis

Upload: others

Post on 14-Nov-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CFD Analysis of RRS-MC500 Air Flow Analysis

CFD Analysis of RRS-MC500Air Flow Analysis

Page 2: CFD Analysis of RRS-MC500 Air Flow Analysis

2

Objective and Scope - CFD

Objective:

Run the CFD analysis to check the Airflow performance and identify turbulence region if

any inside MC500 unit.

Scope:

To predict the Air Flow pattern inside the MC500 unit

Page 3: CFD Analysis of RRS-MC500 Air Flow Analysis

3

Model Provided – MC500

CAD Model – MC500

Return Air

Exhaust Air

Outdoor Air

Supply Air

Static Core

(Heat Exchanger)

Page 4: CFD Analysis of RRS-MC500 Air Flow Analysis

4

CFD Model – MC500 – Supply side

CFD Model – MC500 – Supply side

Extended Inlet

Extended Outlet

Filter

Blower

Static Core

We have given extended outlet with 0 PSI at outlet surface

The purpose is to just avoid the back flow

Page 5: CFD Analysis of RRS-MC500 Air Flow Analysis

5

CFD Model – MC500 –Exhaust side

CFD Model – MC500 – Return side

Extended Inlet

Extended Outlet

FilterBlower

Static Core

Control Panel

Page 6: CFD Analysis of RRS-MC500 Air Flow Analysis

6

Modeling Details – Static Core

Static Pressure Drop Static core – MC500

Volume Flowrate (CFM)

Pressure Drop(In Wg)

350 0.22

500 0.33

750 0.52

Airflow Direction

Y – Pressure Drop (pa) X – Velocity (m/s)

Static core modelled as block

(porous media) in CFD

CFD Model – MC500 – Supply side

Static Core

(21.65” X 10.86” X 21.65”)

Page 7: CFD Analysis of RRS-MC500 Air Flow Analysis

7

Modeling Details – Static Core

Static Core

(21.65” X 10.86” X 21.65”)

Static Pressure Drop Static core – MC500

Volume Flowrate (CFM)

Pressure Drop (In Wg)

350 0.56

500 0.87

750 1.48

Airflow Direction

Y – Pressure Drop (pa) X – Velocity (m/s)

Static core modelled as block

(porous media) in CFD

CFD Model – MC500 – Exhaust side

Page 8: CFD Analysis of RRS-MC500 Air Flow Analysis

8

Modeling Details – Filter

Filter

(19.5” X 13.5” X 1.75”)

Static Pressure Drop Filter – MC500

Volume Flowrate (CFM)

Pressure Drop(In Wg)

590 0.14

980 0.25

1215 0.34

Airflow Direction

Filter modelled as block

(porous media) in CFD

Y – Pressure Drop (pa) X – Velocity (m/s)

CFD Model – MC500 – Filter

Page 9: CFD Analysis of RRS-MC500 Air Flow Analysis

9

Boundary Conditions (Supply & Exhaust)

Extended Inlets Pressure Inlet (0 PSI)

Extended Outlets Pressure Outlet (0 PSI)

Fan Blades Moving Reference Frame (1500 RPM)

Filters Porous Medium

Static Core Porous Medium

Boundary Conditions

Fan blades rotation are modelled by the Moving Reference Frame (MRF) method.

Boundary Conditions – MC500

Page 10: CFD Analysis of RRS-MC500 Air Flow Analysis

10

Results

Pressure drop for MC 500 Filter and Static Core has been recorded in

the table below

CFD Results

Supply Air Unit Δ

Ps (in.w.g.)

Exhaust Air Unit Δ

Ps (in.w.g.)

Filter 0.151 0.107

Static Core 0.428 0.687

Supply Air Unit Exhaust Air Unit

Flowrate (CFM) 808 592.2

Page 11: CFD Analysis of RRS-MC500 Air Flow Analysis

11

CFD Results – MC500 Supply Side

Page 12: CFD Analysis of RRS-MC500 Air Flow Analysis

12

Results : Velocity Contour

View Direction

Recirculation of the air has been

observed in marked regions

Plane at Mid Blower

Page 13: CFD Analysis of RRS-MC500 Air Flow Analysis

13

Results : Velocity Contour

View Direction

Recirculation of the air has been

observed in marked regions

Page 14: CFD Analysis of RRS-MC500 Air Flow Analysis

14

Results : Velocity Contour at Filter Outlet

Uniformity index close to 1 which indicates uniform air-flow

Uniformity index on Filter

Outlet =0.913

Page 15: CFD Analysis of RRS-MC500 Air Flow Analysis

15

Results : Velocity Contour at Static Core

Uniformity index at Static core Inlet =0.896

Uniformity index at Static core Outlet =0.957

Uniformity index close to 1 which indicates uniform air-flow

Page 16: CFD Analysis of RRS-MC500 Air Flow Analysis

16

Results :Streamlines

Page 17: CFD Analysis of RRS-MC500 Air Flow Analysis

17

Results :Streamlines

Page 18: CFD Analysis of RRS-MC500 Air Flow Analysis

18

CFD Results –MC500 Exhaust Side

Page 19: CFD Analysis of RRS-MC500 Air Flow Analysis

19

Results : Velocity Contour

Recirculation of the air has been

observed in marked regions

View Direction

Plane at Mid Blower

Page 20: CFD Analysis of RRS-MC500 Air Flow Analysis

20

Results : Velocity Contour

View Direction

Recirculation of the air has been

observed in marked regions

Page 21: CFD Analysis of RRS-MC500 Air Flow Analysis

21

Results : Velocity Contour at Filter Outlet

Uniformity index close to 1 which indicates uniform air-flow

Uniformity index on Filter

Outlet =0.936

Filter outlet

Page 22: CFD Analysis of RRS-MC500 Air Flow Analysis

22

Results : Velocity Contour at Static Core

Uniformity index close to 1 which indicates uniform air-flow

Uniformity index at Static core Inlet =0.936

Uniformity index at Static core Outlet =0.945

Static Core Inlet

Static Core Outlet

Page 23: CFD Analysis of RRS-MC500 Air Flow Analysis

23

Results :Streamlines

Page 24: CFD Analysis of RRS-MC500 Air Flow Analysis

24

Results :Streamlines