Training Center for Automation and Drives SIMATIC PCS 7 System Training Configuring with SFC Page 1 Date: 07.12.2006 File:ST-PCS7SYS_V70_sfc.1 SIMATIC PCS 7 Siemens AG 2005. All rights reserved. SITRAIN Training for Automation and Drives Cinfiguring Sequences with SFC Content Page Overview .......................................................................................................................................... 2 Sequence Structures ........................................................................................................................ 3 Action and Transition ........................................................................................................................ 4 Preprocessing and Postprocessing for a Sequencer ......................................................................... 5 Operating State Logic of a Sequencer .............................................................................................. 6 Exercise: Sequence Control - Temperature ..................................................................................... 7 Open SFC (in Test Mode) ................................................................................................................ 9 Sequence Control - Reactor ............................................................................................................. 10 Parameter Control via the SFC ......................................................................................................... 11 Notes ............................................................................................................................................... 12 SFC Operating Mode Logic .............................................................................................................. 13 Run Behavior of an SFC .................................................................................................................. 14 Restart Behavior of the SFC(1) ........................................................................................................ 15 Restart Behavior of the SFC(2) ........................................................................................................ 16 External View of SFC ....................................................................................................................... 17 Exercise: Adding Two Sequencers to the Sequential Control ............................................................ 18 Holding Sequencer with Data Block for Values to be Saved .............................................................. 19 Creating an SFC Type ...................................................................................................................... 20 Creating an SFC Instance ................................................................................................................ 21 Miscellaneous Reference Data ......................................................................................................... 22

Upload: romanholo

Post on 10-Jun-2015

256 views

Category:

Technology


8 download

DESCRIPTION

treinamento automação siemens, pcs7 v7

TRANSCRIPT

Page 1: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 1

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.1

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Cinfiguring Sequences with SFC

Content Page

Overview .......................................................................................................................................... 2Sequence Structures ........................................................................................................................ 3Action and Transition ........................................................................................................................ 4Preprocessing and Postprocessing for a Sequencer ......................................................................... 5Operating State Logic of a Sequencer .............................................................................................. 6Exercise: Sequence Control - Temperature ..................................................................................... 7Open SFC (in Test Mode) ................................................................................................................ 9Sequence Control - Reactor ............................................................................................................. 10Parameter Control via the SFC ......................................................................................................... 11Notes ............................................................................................................................................... 12SFC Operating Mode Logic .............................................................................................................. 13Run Behavior of an SFC .................................................................................................................. 14Restart Behavior of the SFC(1) ........................................................................................................ 15Restart Behavior of the SFC(2) ........................................................................................................ 16External View of SFC ....................................................................................................................... 17Exercise: Adding Two Sequencers to the Sequential Control ............................................................ 18Holding Sequencer with Data Block for Values to be Saved .............................................................. 19Creating an SFC Type ...................................................................................................................... 20Creating an SFC Instance ................................................................................................................ 21Miscellaneous Reference Data ......................................................................................................... 22

Page 2: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 2

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.2

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Overview

Menu bar

START

END

S1

S2 S3

S4

T1

T2

T3

T4

S1 to S4 StepsT1...T4 Transitions

Element bar

SFC Flow Chart The chart topology, the action functions of the steps, the switching conditions of the transitions and the runtime properties specify the flowchart created with SFC.

Editor Graphics are used to structure the flow chart. Connections with block parameters already present in the CFC charts are used to configure the individual components (steps and transitions). Therefore, there is no programming; instead, you just access templates.

Insert You can select the structure symbols from the step symbol bar. You click the symbols to insert them (before/after a transition). Steps are always inserted together with the necessary transitions.

Step Double click the step symbol to begin configuring the step. You must fill out the tabs for this. When configuring actions, you can use the "Browse…" button to display the blocks contained in the CFC charts ("Magnifying glass") and transfer their parameters to the action list.

Transition Double-click the transition symbol to begin configuring the transition. You must fill out the tabs for this. The same things apply to configuring actions as to configuring steps.

Runtime Properties The chart will be automatically inserted into the OB where the pointer for the runtime sequence is positioned.

Compile/Download Compilation and download are performed in the same way as for CFC. All chart information is maintained in the chart folder. The compilation result is entered in the block folder and downloaded from there to the CPU.

Test The sequencer can be run and tested when the CPU is connected and test mode is selected (Test menu). Double-click the step/transition symbol to display the current states.

Page 3: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 3

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.3

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Sequence Structures

S1

T12

S2

T23

Linear

S21S22

T23

T12

Parallel

S2 S3

T12 T13

T24 T34

Alternative

S2 T2

T23

Loop

S4S3S3

S1 S1

T12

S1

S2

T2

T23

Jump

S3

T12

S1

S3

Linear Sequence Start position: S1 and T12 are active. Step enabling: if T12 is fulfilled, then S1 becomes inactive, and S2 and T23 become active.

Parallel Branch Start position: S1 and T12 are active. Step enabling: if T12 is fulfilled, then S1 is inactive, and S21, S22 and T23 become active.

Alternative Branch Start position: S1, T12 and T13 are active. Step enabling: 1. If T12 is fulfilled, then S1 is inactive, and S2 and T24 are active (T13, S3, T34 inactive).2. If T13 is fulfilled, then S1 is inactive, and S3 and T34 are active (T12, S2, T24 inactive).3. If T12 and T13 are fulfilled, priority to the left is higher; the left branch is active.

Loop Start position: S1 and T12 are active. Step enabling: 1. If T12 is fulfilled, then S2 is active, and T23 and T2 are active.2. If T23 is fulfilled, S2 terminates and S3 is active.3. If T2 is fulfilled, S2 terminates and is initialized again.4. If T23 and T2 are fulfilled, then to S3.

Jump Start position: S1, T12 and T13 are active. Step enabling: 1. If T12 is fulfilled, then S2 and T23 are active.2. If T2 is fulfilled, then S3 and its following transition are active.3. If T12 and T2 are fulfilled, priority to the left is higher; normal sequence (no jump).

Page 4: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 4

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.4

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Action and Transition

Step active

Transition fulfilled

Cycles

Cycles

Actions Actions that determine what steps must do in the process (such as specify parameters and trigger switching operations) must be configured within the step. You can enter up to 50 actions per step section.

Step A step consists of actions that run in three sections:Initialization Initialization is carried out once (for one program run from the OB) when the step

becomes active.Processing This section is carried out for every run from the OB until the next transition is

fulfilled. If the transition is fulfilled, the terminating section (see below) is carried out during the next OB run of the sequence.

Termination This section is carried out once, after the next transition is fulfilled. After the last command, the step becomes inactive and simultaneously, the following step becomes active (with its initialization), depending on the topology.

Transitions Transitions contain the step enabling conditions for the next step in the sequence. You can evaluate the validity of up to 16 conditions using five logical gates. If you mouse-click the gate or connecting line, you can convert it to AND, NAND, OR or NOR.

Page 5: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 5

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.5

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Preprocessing and Postprocessing for a Sequencer

Possible for each individual sequencer

If Blue background=

Tab content has been changed

SFC Sequencers When created, an SFC chart has a sequencer (called RUN). It can be extended to include other sequencers (which can be inserted, moved or deleted in the chart in the lower bar using the right mouse button). After insertion. the sequencer can be displayed by clicking the associated tab.

Start Conditions A logic can be constructed in the sequencer properties same as for with the transition. In this tab, you can define the conditions for the SFC chart/type that are to start the sequencer (e.g. "SFCName.RUN = Active" starts the sequencer if the SFC chart is in "Active" mode). At any one time there is always a maximum of ONE sequencer being processed (active) in an SFC chart. If the start conditions are fulfilled for several sequencers, the "Priority" property decides which sequencer is executed (1 is the lowest and 255 the highest priority). If sequencers with start conditions that are fulfilled at the same time also have the same priority, the sequencer which is located further to the left is initiated first.

Preprocessing In this tab, you can define the actions for the SFC chart or type that must be carried out before each sequencer processing call (regardless of whether the respective current step is in initialization, processing or finishing). Each line constitutes one statement. Up to 50 statements are possible in each case. You can change the selection of displayed statements (10) using the vertical scroll bar at the right-hand side.

Postprocessing In this tab, you can define the actions for the SFC chart or type that must be carried out after each sequencer processing call. Here, too, up to 50 statements are permitted.The preprocessing and postprocessing tabs are actuated before and after each sequencer cycle, as long as the sequencer is active.

Run sequence The recommended rule here is: the SFC is called after the blocks that it queries in the transitions, but before the blocks that it writes with commands (to the extent possible).

Remark You will first create an SFC chart with one sequencer. Then, after more information is provided, you will add additional sequencers to the SFC chart.

Page 6: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 6

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.6

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Operating State Logic of a Sequencer

Step Control Modes

T with TransitionT or O with Transition or OperationT and O with Transition and OperationB with OperationT/T and O with step-specific operation

Operating mode

Operator commands

(Online Help Index: operating state logic or OSL)

States Following the download operation to the CPU, the sequential control system is in a defined state. This defined state is specified with the SFC Editor (default: Ready). Now the sequential control can begin either automatically (SFC Chart Properties -> Start Options -> Autostart) or after a start command (menu Chart -> Properties -> Start Options -> Operating Parameters).

Sequencer Operating State Logic (OSL)Processing of the sequencers is controlled by the sequencer operating state logic. The sequencer's operating state logic is defined in the diagram of the state transitions for sequencer OSL.

Operator Commands You can use commands to change the sequential control system between states (e.g. Start, Hold, Resume, Abort, Complete).

Step Control Modes The different step control modes modify the behavior of prepared or fulfilled transitions. A change in the step control modes is possible in all of the operating states. The individual step control modes mutually exclude each other. The following step control modes are available:T with TransitionT or O with Transition or OperationT and O with Transition and OperationB with OperationT/T and O with step-specific operation

Page 7: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 7

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.7

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Exercise: Sequence Control - Temperature

START

L<33

SP=70

H>67

SP=50

L<53

SP=30

L<32

END

70

50

30

SP_EXTPV_IN

t

Step enabling condition:Process value PV_IN less than 33?

Step enabling condition:Process value PV_IN greater than 67?

Action:Set setpoint SP_EXT to 70

• Linear sequence• Conditions in transitions• Actions in steps• Test

Start step

Exercise Create a setpoint control for the temperature controller of reactor A (see slide). If specific process values are not reached or are exceeded, the setpoint must be set to defined values.----------------------------------------------------------------------------------------------------------

Steps 1. Create the SFC chart "SFC_Temp" in the same folder containing the CFC chart for the temperature controller.2. First create the layout of the sequencer as per the above illustration, with the prescribed names for the steps and transitions.3. Then configure the steps and transitions. 4. Next, compile ("Changes") and download ("Changes") the program. 5. Test the sequence in test mode.----------------------------------------------------------------------------------------------------------

Procedure Procedure for configuring the steps:Configure steps Select a step from the sequencer and open it by double-clicking.

In the "General" tab, enter the name, min. and max. runtime, the step comment in the control, the step comment in the visualization, and acknowledgment information (if leaving the step has to be acknowledged).

The "Initialization", "Processing" and "Termination" tabs must be used to configure the actions in this step.Go to the "Processing" tab, place the cursor in the first free line, and click the "Browse" button (at the bottom of the screen) to look the charts in either the "Plant view" or "Component view" tab until you reach the controller block. Select this block and select the required parameter in the right pane, e.g.

The SP_EXT parameter from the CTRL_PID block for the reactor heating control.

Page 8: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 8

You now have to assign a value to the selected parameter in your statement (to the right of := ). Enter the temperature value, e.g. 70.0, in accordance with the function of the step.

Configure transitionSelect a transition from the sequencer and open it by double-clicking.In the "General" tab,

enter the name, the comment (ES), the OS comment and the acknowledgment information.

The "Condition" tab is used to configure individual conditions within the step enabling condition. Here too you can use "Browse" to select the required parameter from the CFC charts and then use the symbols

=, <>, =>, =<, >, < to compare it with a specific value or another parameter, e.g.

PV_IN from CTRL_PID < 33.0 (degrees)

Compile and DownloadThe program is compiled and downloaded (as described in detail in the CFC section) from the SFC chart using the same procedure as for the CFC.Compile and download the changes.The compile and download operation always applies to all CFC and SFC charts in the program to which the SFC chart belongs, i.e. from where you are initiating the procedure (they form a common program).

Testing the SFC Test mode is enabled and disabled using the commandDebug Test Mode

Compared to edit mode, the SFC chart window in test mode is expanded to show an operating and display section at the bottom of the window.In addition to selection of the operating mode (MANUAL, AUTO); you can also see the following buttons for the SFC: - Start - Hold - Resume- Abort - Complete - Stop- Restart - Reset - Error (handling)

When the steps and transitions are cycled through, they will display different colors depending on their state:

Step active pale greenStep held yellowStep contains errors red(e.g. maximum runtime exceeded)Step is inactive but has been processed dark greenStep is inactive and has not yet been processed gray

Transition fulfilled dark greenTransition not fulfilled dark redTransition inactive gray

Page 9: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 9

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.9

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Open SFC (in Test Mode)

1

2

3

5

Menu: Debug Test ModeDebug Open SFCs

Select statuses- Multiple selection possible- No selection means no limitation

Select the operating mode

4 Find

Result

6 Select andopen

Analyze SFC In test mode it is possible to display SFCs that correspond to a defined combination of statuses. To do this, open any SFC and set it to test mode. Only then is the menu item

Debug Open SFCs offered.The required steps are shown in the above slide.

Remark The conditions are linked by logical ANDing.

Page 10: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 10

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.10

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Sequence Control - Reactor

Go to initial stateReactor C empty and

cold

Fill first component X to 20% level

Cold and empty

Level >= 20%

Speed monitorfor mixer ON

Speed monitorfor mixer ON

Level >= 80%

Core temperatureto 90 degrees

Process temperature reached

Settling time 2 min

Setpoint tolerance oftemperature controller

reached

Open drain valve, mixer OFF,

close temperature controller

End initial stateReactor empty and cold

Fill second component Y

to 80% levelEnd step

Exercise The sequence for the manufacturing procedure in Reactor A was described in the "Configuration Overview" tab, page 2. Now implement this sequence using an SFC chart. Configure, compile, download and test this SFC chart.----------------------------------------------------------------------------------------------------------

Requirement You have implemented and tested the example in the chart "Exer_Reaci" with the MOTOR, VALVE and CTRL_PID blocks.

Steps 1. In the plant hierarchy under "Reactors\UnitA", create an SFC chart, "SFC_ReacA".2. Establish the sequence of the SFC (see picture above).3. Configure the actions in the individual steps and the signals to be queried in the transitions.4. Compile and download the program.5. Test the project. ----------------------------------------------------------------------------------------------------------

Procedure You can derive the sequence from the above picture.Control the filling valves and the drain valve using the VALVE blocks.Control the mixer via the MOTOR block.For the "heating" step, set the controller to AUTOMATIC and the external setpoint to 90°C.You can include waiting times by inserting an empty step (with a minimum runtime setting) and an empty transition.

Page 11: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 11

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.11

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Parameter Control via the SFC

Active outputs of the blocks

SFC releases the operating mode switchover again (but does not change the operating mode)

LIOP_MAN_SEL=0LIOP_INT_SEL=0

LIOP_SEL=0LIOP_SEL=0Relinquish control of block's operating mode

SFC control assumes the control of the blocks (operator cannot operate)

LMNQSTARTQCONTROLPass to system

SFC control relinquishes control of the blocks (operator can operate again)

SP_EXT = (value)AUT_ON (1=on)AUT_OC (1=open)Output commands

For controllers onlyLIOP_INT_SEL=1SPEXON_L=1

Set external setpoint

AUT_L=1AUT_L=1AUT_L=1Set Automatic mode

SFC determines operating mode (LInk is active, not OPerator)

LIOP_MAN_SEL=1LIOP_SEL=1LIOP_SEL=1Assume control of block's operating mode

RemarkCTRL_PIDMOTORVALVEBlockEffect

Operating Modes For the SFC to be able to pass its commands to the valves or motors via the above listed blocks, it must be able to influence the blocks' operating mode (set the operating mode to AUTOMATIC) and write commands to the suitable inputs. It must also be possible for the plant operator to intervene manually when the control has finished. This means the control must relinquish its control over the blocks again.

Page 12: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 12

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.12

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Notes

Page 13: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 13

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.13

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

SFC Operating Mode Logic

Buttons for testing the SFC

(Online Help Index: operating state logic or OSL)

Operating State Logic for SFCState The current operating state of the SFC OSL can be modified by the following

events:- Commands (Start, Resume, Hold, etc.) in operating modes "MANUAL" or "AUTO".- External signals (SFC inputs, commands from another SFC, etc.).- Internal signals (commands from custom sequencers, from test mode or SFC visualization).- Implicit state change.

Step enable commandsStart Trigger start processingComplete Trigger complete processingHold Trigger hold processingResume Trigger continue processing, e.g. after an errorError Trigger error processingAbort Trigger cancel processingStop Trigger stop processingRestart Trigger start processingReset Change to Ready state

Page 14: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 14

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.14

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Run Behavior of an SFC

M

Cyc

leof

the

SFC

Cyc

leof

the

CFC

Interaction with Basic Automation (CFC) The sequential control in the AS is connected to the basic automation via the action and transition functions. A specific runtime behavior is assigned to each SFC. Basic automation using the blocks contained in the CFC charts can have a different runtime behavior than the SFC. You can control an SFC chart using the external view of the SFC chart contained in the CFC chart. The structure of the sequence system makes it possible for the sequential control and the basic automation blocks to run in different cycles, thereby reducing the cyclical load. In the same way, SFCs can be integrated into runtime groups, and can be given a different scan rate or phase offset via these groups.

SFC Runtime OptionsYou can set the sequential control behavior in the runtime options. These can be set in the dialog field

"SFC Properties Tab: Operating Parameters CPU".

Instruction Output On: The actions of active steps will be processed.Off: The actions of active steps will not be processed.

Cyclic Execution With "Cyclic Execution: On" the program will automatically revert to "Starting" following the "Completed" operating state. With "Cyclic Execution: Off", the program remains in "Completed" state.

Time Monitoring With "Time Monitoring: On", the active time of the step is continuously compared against the monitoring time after the step is activated (object properties for the step, "General" tab, "Maximum Runtime" option), and a step error is reported if the time is exceeded.

Page 15: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 15

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.15

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Restart Behavior of the SFC(1)

Restart Behavior With PCS 7 Version 7.0 and higher there is an additional possibility for setting the behavior following a CPU restart (see arrow in slide). In the previous versions, the SFC was always initialized, and the data valid prior to the stop were lost (this is now the default setting).In the new version, the SFC status can be retained. Following a CPU restart, the SFC then retains its status. Using the SFC and process states, the operator can then decide how the SFC is to continue working.

Page 16: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 16

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.16

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Restart Behavior of the SFC(2)

!

?

STOPRestart

Exercise Set the SFC from the previous exercise such that it retains its state following a CPU restart. Test the restart behavior of the SFC (by means of CPU stop followed by a CPU restart) in the "Component X" and "Heat" step. What happens to the configuration due to this behavior? What happens, for example, with the filling of component X in the reactor in the meantime (between the CPU Stop and Resume command by plant operator, once the CPU is running again)?---------------------------------------------------------------------------------------------------------

Steps 1. Open the SFC, select the menuSFC Properties "Operating parameters CPU" tab

and select the "Retain SFC status" option.2. Compile and download the changes.3. Switch on test mode, and start the SFC.4. When the "Component X" step is reached in the SFC, stop the CPU (using PLC Operating Mode Stop).What is output by the output modules to which the valves (simulation) are connected? What does this mean for a real plant?5. From the last screen form, carry out the CPU restart. You must then decide at some time whether the SFC is to continue or stop/abort.A new command is not output by the SFC up to this point. What commands are output by the valve, motor and controller blocks? Note that the blocks mentioned also exhibit a restart behavior when the CPU is restarted, but they then call their program cyclically in the cyclic interrupt OB with the parameters which they find there.

Page 17: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 17

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.17

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

External View of SFC

External View The SFC chart has a standard interface through which it can be controlled using CFC interconnections. This interface is represented as a graphic "external view" of the chart. Activate the following menu command in the SFC

View External Viewto open the CFC with an external view window.

Representation The external view shows the SFC as a block with an SFC chart symbol in the block header. The block name is the SFC chart name and cannot be changed.

Interconnection Inputs can be interconnected to other objects, global addresses or textual interconnections.Please refer to the online help for more information about the individual parameters (Help on SFC External View... See also... Standard interface for SFC charts).There the parameters are listed both alphabetically and according to their use.You cannot add further objects to the CFC chart showing the external view of the SFC. All interconnections must pass over the edge of this chart.

Tip Open the external view of the SFC (= a CFC window) and the CFC chart from which the control is to be influenced (= a second CFC window). Arrange both windows side by side. Interconnect the blocks as described in the CFC chapter.

Page 18: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 18

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.18

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Exercise: Adding Two Sequencers to the Sequential Control

Start conditionRUN sequencer

Start conditionHOLD sequencer

DB

SFC_ReacA

Save state

Safe stateOutput commandsSet operating modes foroperation

Restore state

HOLD!

Start conditionResuming sequencer

?

?

Exercise Supplement the sequential control for Reactor A as follows: If the plant operator issues a hold command for the SFC control, a second "HOLD sequencer" will start up. This is to ensure that valves V1, V2 and V3 close, the mixer is switched off and the temperature controller is set to manual operation with a preset manual value. The HOLD operating state must not be reached until the two above-mentioned commands have become effective. This state must be saved in a DB.The operator can perform operations in the HOLD state. If the control is to exit the "HOLD" state, the valves, mixer and controller must be switched back to the state saved in the DB, i.e. the state they were in when the HOLD command was issued. This is achieved by using a third "CONTINUE sequencer" which resets the blocks to the desired state and is only exited after a check has been performed.-------------------------------------------------------------------------------------------------------

Steps 1. Insert additional sequencers in the SFC_ReacA.2. Set the chart properties for the two additional sequencers.3. Create data block to save data when control is in HOLD state.4. In SFC_ReacA complete programming of the "HOLD" and "CONTINUE" sequencers.-------------------------------------------------------------------------------------------------------

Procedure 1. Insert two additional sequencers in SFC_ReacA. With the SFC open, go to the "RUN" tab (below),

right-click and select Insert Sequence at Endto insert another sequencer. One SFC can process up to eight sequencers in alternation. With the SFC open, set the chart properties via

Chart Properties Operating Parameters tabas follows:Step Control Mode: T, Operating mode: MANUAL; Instruction Output: checked, Use default operating parameters when SFC chart starts: checked.

Page 19: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 19

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.19

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Holding Sequencer with Data Block for Values to be Saved

"Normal" reactor sequencer

START(save

or restore)

END(empty)

Checking

Create Data BlockCreate a data block (DB) (e.g., DB1 with a symbolic name, "ReacA_DB"). This block is to be used to save the necessary states when the main sequencer is held (see above for possible structure).To do this, you need to switch to the project component view. Select the block folder, then

right-click and select New Object... Data Blockto create the global DB1. Enter the symbolic name "ReacA_DB" in the Properties window. Then select the block,

right-click and select Open to start the data block editor (see above).Define the necessary parameters in the corresponding data formats.

Configuring SFC with Two Additional SequencersConfigure the HOLDING SFC and the RESUMING SFC.

HOLDING SFC This is started when a command is received to hold the RUN SFC. "Save" Step In the "Save" step, the relevant pending commands/data are saved in DB1 (see

above, content of DB1) and then the desired settings are made.Transition This checks whether the operating modes and values that were set as a

precautionary measure have become effective. The sequencer is completed only after the transition is fulfilled. The SFC chart then changes to HOLD state.

RESUMING SFC This is started when a command is received to resume the RUN SFC. "Restore" Step The "Restore" step is the opposite to the "Save" step in the HOLDING sequencer,

i.e. the data is read from DB1 and distributed across the relevant block parameters/inputs (from right to left).

Transition This checks whether the saved states have become effective again before the RUN sequencer resumes activity.

Page 20: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 20

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.20

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Creating an SFC Type

Several sequencers possible for one SFC type

SFC Type In SFC V6.1 there is an SFC type in addition to the SFC chart. This makes it possible to define sequential controls, including an interface. The runtime logic of the SFC type is based on the interface of the SFC type, i.e. the SFC type cannot access just any process signals. Like function blocks, SFC types must be placed on a CFC chart, where they are given an SFC instance.

Creating an SFC TypeSFC types cannot be inserted into the plant hierarchy, since they cannot run on their own. Instead, they are created using

Insert new object -> SFC typein the component view in the SIMATIC Manager or

SFC -> New (select "SFC type" in the "Object type" field)in the SFC editor.

Manipulating the SFC TypeThe SFC type is a manipulable object like the SFC chart; however, it has its own symbol to distinguish it from the latter. The attributes necessary for the SFC type (e.g. S7_m_c) are preset. Seven messages requiring acknowledgement and five that do not require acknowledgement can be configured for each SFC type. The other available messages are required by the SFC type itself.

Configuring Using the SFC TypeOnly the interfaces for the SFC type can be used to configure actions in the steps and the start and step enabling conditions. In other words, external access is via the SFC type interface only.

Page 21: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 21

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.21

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Creating an SFC Instance

Operating modes

Commands

Command enables

LockControl strategyStep control mode

Execution option

Operating state

Operating mode

Group display

Fault indication

Control strategy

SFC Instance If an SFC type is used, it is inserted into a CFC chart. An SFC instance will be assigned to it at this point. SFC instances are therefore always assigned to the CFC chart and are addressed via the chart. By assigning the CFC chart to the plant hierarchy, the instances that it contains are also indirectly assigned to the plant hierarchy.

Messages SFC instance messages can be configured in the SFC via SFC Message

or in the CFC in the object properties dialog box. The messages are PCS-7-compliant and can also be provided with associated values, for instance.

Configuration When you configure SFC instances, the interface and the sequencers must not be changed, as they are specified identically for all instances through the SFC type. Changes that are made directly to the instances may be loaded at any time, even if the SFC instance is currently being processed in the automation system. After you have configured any changes, you must use the function

OS Compileto ensure that the current data are also available on the OS.

Compile If the program is compiled on the ES side, the SFC instances will be compiled along with them. For any given SFC instance, 1+n data blocks will be created (where n = number of sequencers within an SFC).

Page 22: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 22

Date: 07.12.2006File:ST-PCS7SYS_V70_sfc.22

SIMATIC PCS 7Siemens AG 2005. All rights reserved.

SITRAIN Training forAutomation and Drives

Miscellaneous Reference Data

Run Sequence

Calling up Reference DataWhen you have opened a CFC or SFC chart, you can use

Options Chart Reference Data... or the symbol in the function bar to display and print the information shown below in list form or in tree structure. You can search for the desired output using the View menu command.

Run sequence Graphic representation of the entire run sequence of a CPU.Cross References Chart Element Address

A list of all global addresses used in the project, with the elements that have access to them.

Cross References SFC Chart ElementThis displays the existing accesses to the block interfaces in the CFC from any SFC charts.

Block interconnectionsList of all interconnected chart elements.

Access in SFC typesList of all read and write accesses of the SFC types to their own interface.

Cross References Chart Element Runtime GroupsExisting accesses from any CFC and SFC charts for all runtime groups.

Cross References Block TypesThe block types used and the locations (CFC chart) where they are used.

S7 Resource AllocationThe assignment between CFC configuration objects and S7 resources.

Page 23: Ch6 v70 sfc_en

Training Centerfor Automation and Drives

SIMATIC PCS 7 System TrainingConfiguring with SFCPage 23

Local Data All OBs in the program, with the calculated local data requirement and the local data sizes for the individual priority classes as configured offline, and those actually available online.

Block Call HierarchyGraphic representation of the call hierarchy for all blocks in the current program.

Textual InterconnectionsAll open textual interconnections are listed.

Statistics Number of all objects used by CFC, SRC; S7 resources and the time stamp from the current program, as well as the HMI-relevant block instances for the project.

You can use this information to check your configuration structure. For example, you can use the "Cross-References Chart Element Addresses" list to determine which symbols are used and how often, and whether write accesses are synchronized. See the online help for further information.

Note The "Reference Data" function is also available in SIMATIC Manager. With PCS 7 projects it is only offered in the context of the chart folder of the CPU.