challenges and traps of assessing life cycle costs of lighting

19
IEA SHC Task 50 Fukuola, Japan 29 September 2014 Challenges and traps of assessing Life Cycle Cost analysis (LCC) Prof Marc Fontoynont, Lærke Andersen Danish Building Research Institute Aalborg University in Copenhagen Denmark 1

Upload: phunghuong

Post on 01-Jan-2017

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Challenges and traps of assessing life cycle costs of lighting

IEA SHC Task 50 Fukuola, Japan 29 September 2014

Challenges and traps of assessing Life Cycle Cost analysis (LCC) Prof Marc Fontoynont, Lærke Andersen Danish Building Research Institute Aalborg University in Copenhagen Denmark

1

Page 2: Challenges and traps of assessing life cycle costs of lighting

IEA SHC Task 50 Fukuola, Japan 29 September 2014

« Lighting retrofit issue is mainly a decision process cocerning possible benefits to change, before their end of life, the lighting installations » Tasks: 1) to identify the « low hanging fruits » 2) To identify the winning schemes

2

Page 3: Challenges and traps of assessing life cycle costs of lighting

IEA SHC Task 50 Fukuola, Japan 29 September 2014

What are are the Life Cycle Costs (LCC) of major lighting schemes?

3

Page 4: Challenges and traps of assessing life cycle costs of lighting

Industrial buillding

Office building School Store

OLD (15 – 30 yrs)

New (2014-2015)

Looking for « low hanging fruits » and best solutions

Page 5: Challenges and traps of assessing life cycle costs of lighting

Industrial buillding

Office building School Store

OLD (15 – 30 yrs)

New (2014-2015)

Looking for « low hanging fruits » and best solutions / Daylighting and controls

Occupancy sensor

Daylight sensor

Daylight sensor

Insufficient daylight, aging roof monitors, steady

electrical lighting

Individual shadings, on-off and clock controls

Manually controlled shading and lamps.

Manual switches, or clock driven

Roof monitors with improved performance and sunlight

control. Daylight responsive sensors

Sensors and intelligent managemen tof sunbeams.

Roof monitors with improved performance and sunlight

control. Daylight responsive sensors

Automatic controls of shading, override, clocks

Page 6: Challenges and traps of assessing life cycle costs of lighting

IEA SHC Task 50 SBi January 2014

Cumulated costs for good fluorescent lights

Garage 5600 hr/yr 1.5 W/m2 Office hallways 2400 hr/yr 2.5 W/m2

Office 3500 hr/yr 10 W/m2 Commercial 4000 hr/yr 16 W/m2

SUM – 127 Euro/m2 SUM – 96.6 Euro/m2

SUM – 832 Euro/m2 SUM – 516.2 Euro/m2

6

3,4

33,8

10,4

61,4

18,0

Change ofelectronic ballast

Investment with allcomponents

Change oflighttubes

Electricity Price

Installation price

1,7

33,8

5,2

43,9

12,0

6,8

135,0

62,4 256,0

56,0

6,8

216,0

83,2

462,3

64,0

Page 7: Challenges and traps of assessing life cycle costs of lighting

IEA SHC Task 50 SBi January 2014

Lighting cost storyboard for ”good” fluorescent lights

Garage 5600 hr/yr 1.5 W/m2 Office hallways 2400 hr/yr 2.5 W/m2

Office 3500 hr/yr 10 W/m2 Commercial 4000 hr/yr 16 W/m2

7

0,00

10,00

20,00

30,00

40,00

50,00

60,00

70,00

80,00

90,00

100,00

0 5 10 15 20 25 30 35 40 45 50

Euro

/m2

/yea

r

0,0

10,0

20,0

30,0

40,0

50,0

60,0

70,0

80,0

90,0

100,0

0 5 10 15 20 25 30 35 40 45 50

0,0

10,0

20,0

30,0

40,0

50,0

60,0

70,0

80,0

90,0

100,0

0 5 10 15 20 25 30 35 40 45 50

Euro

/m2

/yea

r

0,0

10,0

20,0

30,0

40,0

50,0

60,0

70,0

80,0

90,0

100,0

0 5 10 15 20 25 30 35 40 45 50

Years

Electricity Price Change of electronic ballast Investment with all components Change of lighttubes Installation price

Page 8: Challenges and traps of assessing life cycle costs of lighting

IEA SHC Task 50 SBi January 2014

Change from fluorescent 15 W/m2 to SSL

Benefit in all cases, but one can wait until 2025 until performing change to SSL: it may be useful to wait until prices of SSL drops significantly after 2020 or 2025)

2014 2025

8

0,0

100,0

200,0

300,0

400,0

500,0

600,0

700,0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

Cu

mm

ula

ted

co

st [

Euro

/m2

/yr]

Years

Office 3500hrs 15 W/m2 1.scenario - Change to SSL after 14 yrs 3xFL=SL 1.scenario - Change to SSL after 25 yrs 3xFL=SL

2.scenario -Change to SSL after 25 yrs - 2XFL=SL 3. scenario - Change to SSL after 25 yrs SL=FL

Page 9: Challenges and traps of assessing life cycle costs of lighting

Investor _ Industrial building (Processing)

Typical installation to replace Approx 15 to 30 years old

Typical new generation installation

Double fluorescent with cheap reflector Suspended HP sodium

Suspended HID

Typical illuminance_500 lux Typical power density_30 W/m2

Linear LED tubes Suspended LED

Typical illuminance_ 750 lux Typical power density_15 W/m2

Investment cost (incl. Installation) - LED (15 W/m2) _21 €/m2

Based on: Typical operating hours_ 4000 hours/yr Typical lifespan of products (LED/SSL)_60000 hrs/yr For industrial building 10 m2 is thought for every luminaire Installation_ 60 min_ 40 E/hr_ 10m2/luminaire LED /SSL 5W/m2_ the same price as a 6 W/m2 fluorescent lamp. Price for LED (15 W/m2) defined based on this and taking the difference in power density into consideration.

Page 10: Challenges and traps of assessing life cycle costs of lighting

Investor _ Office building

Typical installation to replace Approx 15 to 30 years old

Typical new generation installation

60 X 60 recessed luminaire Circular compact fluorescent downlighters

Typical illuminance_500 lux (designed) 350 lux (service) Typical power density_15W/m2 and 10 W/m2

Single T5 luminaires, prismatic Rails with LED spots (Suspended direct indirect)

Stand alone luiminaires

Typical illuminance_500 lux (desk space) 350 lux(floor space) Typical power density_5 W/m2

Investment cost (incl. Installation) - Fluorescent (6 W/m2) _ 57 €/m2 - LED/SSL (5 W/m2) _57 €/m2

Based on: Typical operating hours_ 3500 hours/yr Typical lifespan of products (fluorescent)_ 15000 hrs/yr for fluorescent tubes, 50000 hrs/yr for ballast and 25 yrs for fixtures. Typical lifespan of products (LED/SSL)_60000 hrs/yr For office 6 m2 is thought for every luminaire Installation_ 60 min_ 40 E/hr_ 6m2/luminaire LED /SSL 5W/m2_ the same price as a 6 W/m2 fluorescent lamp.

Page 11: Challenges and traps of assessing life cycle costs of lighting

Investor _ Schools

Typical installation to replace Approx 15 to 30 years old

Typical new generation installation

2 x 1,20 T8 low price ptics

Typical illuminance _ 300 lux Typical power density_ 10 W/m2

Single T5 luminaires, continuous Suspended direct indirect (3 tubes)

Typical illuminance_500 lux Typical power density_ 6 W/m2

Investment cost (incl. Installation) - Fluorescent (6W/m2)_ 68 €/m2

Based on: Typical operating hours_ 1500 hours/yr Typical lifespan of products (fluorescent)_ 15000 hrs/yr for fluorescent tubes, 50000 hrs/yr for ballast and 25 yrs for fixtures. For schools 5 m2 is thought for every luminaire Installation_ 60 min_ 40 E/hr_ 5m2/luminaire

Page 12: Challenges and traps of assessing life cycle costs of lighting

Investor _Store

Typical installation to replace Approx 15 to 30 years old

Typical new generation installation

Double fluorescent Suspended HID

Typical illuminance_ 750 lux Typical power density_20 W/m2

Linear LED tubes Suspended LED

Typical illuminance_ 750 lux Typical power density_12 W/m2

Investment cost (incl. Installation) - LED (12 W/m2) _28 €/m2

Based on: Typical operating hours_ 4000 hours/yr Typical lifespan of products (LED/SSL)_60000 hrs/yr For commercial 6 m2 is thought for every luminaire Installation_ 60 min_ 40 E/hr_ 6m2/luminaire LED /SSL 5W/m2_ the same price as a 6 W/m2 fluorescent lamp. Price for LED (12 W/m2) defined based on this and taking the difference in power density into consideration.

Page 13: Challenges and traps of assessing life cycle costs of lighting

Retrofit: roof openings

Typical installation to replace Approx 15 to 30 years old

Typical new generation installation

No daylighting or poor daylighting

Typical illuminance 0 – 100 lx

1.40 m x 1.40 m Roof apertures 10% of roof area , DF = 2 to 2.5 %

Diffuse horizontal illuminance of 16 000 lx exceeded 50 % of daylight hours with 10% of roof area.

Investment/installation and maintenance cost Retrofit: 2200 € to install a 1.4 x 1.4 m (2m2 ) roof monitor in an existing building ( less than 1500€ if new) . Investment is 110€/m2.

Based on: Roof top area = 10% of floor area for DF average 2%, and > 50% electricity savings during daylight hours. Investment cost 110€$/m2 for retrofit

Page 14: Challenges and traps of assessing life cycle costs of lighting

Retrofit: lighting controls

Installation with manual / clock control Fluorescent with Daylight sensors On –off or dimming ( HF ballast or LEDs)

Operation 2000 to 8000 hrs /yr.

Savings can reach 50% of lighting electricity

Investment/installation and maintenance cost on top of an industrial luminaire single tube 120€ extra

Based on: 1.5 m , 35 W Single T5 no diimming 130 € , with dimming ( 0-10 v, DALI) : 250€ Typical savings per year 1500 hrs x 6 W/m2 = 9 Kwh/m2.yr value 1,35€/m2

Investment, per m2 : one luminaire per 10 m2: 12 €/m2

Occupancy sensor

Daylight sensor

Page 15: Challenges and traps of assessing life cycle costs of lighting

Retrofit: improved shading / redirecting shading devices

Textile shading Louvre system, with controllable angles

Operation when daylight is glary, leading to possible unnecessary us of electricity 200 to 800 hrs /yr.

Possibility to adjust teh right level of daylight indoor, and, with specifiv louver design, tio bring daylight

deeper into interiors.

Benefit: some extra saving in lighting electricity ( above 200 hrs per year in area located between 3 an6 meter from facade) and reduction of glare

Based on: Investment : 200 € /m2 of facade, 40€/m2 of floor Savings: maximum 0.5 cts / m2 per year

Page 16: Challenges and traps of assessing life cycle costs of lighting

Actor Investment Costs Life

Installation costs Installation simplicity

Maintenance costs Cleaning simplicity Failures

Energy consumption Controls to reduce consumption

Lighting quality Comfort Flexibility

Investor /owner *** ** ***

Installer **

User Maintenance ** *** ***

Concerns by actors : how to promote lighting retrofit? Where are the benefits

Page 17: Challenges and traps of assessing life cycle costs of lighting

17

Early finding statements 1. There are many “low hanging fruits” in lighting leading to return on investments

below 3 years), and often increasing lighting quality

2. These low hanging fruits are found mainly in industrial buildings and stores where lighting is independent from ceiling systems

3. In office buildings and schools, it is essential to estimate possible schedule of ceiling refurbishment, to conduct lighting retrofit at the same time.

1. Anticipating retrofitting a lighting installation can be justified if cost of new

(high efficiency) luminaires remains low: for example if SSL costs are close from fluorescent luminaires

Page 18: Challenges and traps of assessing life cycle costs of lighting

18

Early finding statements ( Cont’d)

5. In offices, hybrid task ambient strategies, with electric power densities around 4W/m2 are the most energy efficient solutions, and can be easily implemented

6. Other benefits should dominate: added rental value, lighting quality, lower maintenance

7. Market seems to move to disposable luminaires (life below 60 000 hrs) with maintenance limited to simple cleaning

8. Evolution of ceiling systems may also lead to reduction of life of ceiling components.

9. Daylighting measures can dimish electric lighting by 50%, bur without possibbilities of return on investment related to these savings only

Page 19: Challenges and traps of assessing life cycle costs of lighting

19

Questions to lighting industry and professionals

Is the energy saving model the dominant argument for investing in new lighting, or is it a secondary one? Is there a growing interest , in Japan, for retrofitting lighting before the end of life Will a technological gap modify