Channeled Adhesive CI Design with MaxGrip Veneer Mortar Continuously Insulated System with Adhered Veneer Typical Details

Upload: others

Post on 18-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar Continuously Insulated System with Adhered Veneer Typical Details

Page 2: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

(THIS PAGE INTENTIONALLY LEFT BLANK)

Page 3: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

1. Typical Channeled Adhesive Profile

2. Typical Application

3. Typical Outside Corner Application

4. Typical Pipe Penetration

5. Typical Vertical Expansion Joint

6. Typical Expansion Joint at Change in Substrate

7. Typical Expansion Joint at Floorline

8. Typical Drainage at Floorline

9. Typical Termination at Foundation

10. Typical Termination at Foundation (Flush)

11. Typical Window Head (Flush)

12. Typical Window Head (Flush) with Weeps

13. Typical Window Head (Flush) with Diverter Track

14. Typical Window Head with Sealant End Dam

15. Typical Window Jamb (Flush)

16. Typical Window Sill (Flush)

17. Typical Window Head (Recessed)

18. Typical Window Jamb (Recessed)

19. Typical Window Sill (Recessed)

20. Typical Flanged Window Head

21. Typical Flanged Window Jamb

22. Typical Flanged Window Sill

23. Typical Coping

24. Typical Railing Attachment

Channeled Adhesive CI Designwith MaxGrip Veneer MortarTypical Details

Table of Contents

Notes:

Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.

The details within represent BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. They are presented in good faith by BASF Wall Systems. The details are subject to change without notice. BASF Wall Systems accepts no liability for the end use of the details. For conditions not shown, consult BASF Wall Systems for review of speci�c detail.

Install BASF materials in accordance with current installation instructions.•

Continuously Insulated System with Adhered Veneer

Page 4: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

(THIS PAGE INTENTIONALLY LEFT BLANK)

Page 5: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-01 190904

• Install BASF materials in accordance with current installation instructions.

• Apply mixed base coat to entire surface of insulation board using a stainless steel trowel with 1/2" x 1/2" (13 mm x 13 mm) notches spaced 2" (50 mm) apart. Ribbons of adhesive must be applied parallel to the 2' (610 mm) dimension of the EPS insulation board to ensure they are vertical when the EPS insulation board is applied to the substrate.

• Set EPS insulation board into place and apply pressure over entire surface of board to ensure positive uniform contact and high initial grab. Do not slide board into place.

TYPICAL CHANNELED ADHESIVE PROFILE

APPROVED EPS INSULATION BOARD

VERTICAL NOTCHES OF SENERGY ADHESIVE APPLIED TO APPROVED EPS INSULATION BOARD

Page 6: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-02 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure a means for drainage is provided at system terminations.

• Adhered veneer shall not exceed 15 lbs. (6.8 kg) per sq. ft.

TYPICAL APPLICATION

FRAMING*

ACCEPTIBLE SHEATHING*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY SENERSHIELD-R/-RS/-VB SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR BASF MAXGRIP VENEER MORTAR

ADHERED VENEER* BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

FLASHING*

Page 7: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-03 190904

• Install BASF materials in accordance with current installation instructions.

• BASF INTERMEDIATE 12 reinforcing mesh is lapped a minimum of 8" (203 mm) around corners.

TYPICAL OUTSIDE CORNER APPLICATION

FRAMING*

ACCEPTIBLE SHEATHING*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

Page 8: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced basecoat.

• Ensure all penetrations into the system are properly sealed.

• Provide continuous air seal around perimeter of penetration prior to EPS insulation board application.

CAM-04 190904

TYPICAL PIPE PENETRATION

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

SEALANT* OR BASF MAXFLASH AT PERIMETER OF PENETRATION

PIPE*

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

Page 9: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-05 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Install expansion joints in the system at all changes in substrate, terminations at dissimilar materials, through existing expansion joints, floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.

• Ensure drainage plane is continuous and unobstructed at expansion joint.

TYPICAL VERTICAL EXPANSION JOINT

FRAMING*

ACCEPTABLE SHEATHING*

BASF WS FLASH WITH FLASHING PRIMER

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

ADHERED VENEER*

SENERGY SENERSHIELD-R/-RS/-VB

Page 10: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure drainage plane is continuous and unobstructed at expansion joint.

• Install expansion joints in the system at all changes in substrate, terminations at dissimilar materials, through existing expansion joints, floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.

CAM-06 190904

TYPICAL EXPANSION JOINT AT CHANGE IN SUBSTRATE

FRAMING*

ACCEPTABLE SUBSTRATE*

ACCEPTABLE SHEATHING*

BASF WS FLASH WITH FLASHING PRIMER

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

SENERGY SENERSHIELD-R/-RS/-VB

Page 11: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-07 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Install expansion joints in the system at all changes in substrate, terminations at dissimilar materials, through existing expansion joints, floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.

• It is recommended that a means for drainage is provided at every third floor. (See TYPICAL DRAINAGE AT FLOORLINE detail).

• Do not apply finish to areas that will receive sealant.

TYPICAL EXPANSION JOINT AT FLOORLINE

FLOOR SLAB*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

BASF WS FLASH WITH FLASHING PRIMER

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

BASF MAXGRIP VENEER MORTAR

Page 12: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-08 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Do not apply finish to areas that will receive sealant.

• Install expansion joints in the system at all changes in substrate, terminations at dissimilar materials, through existing expansion joints, floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.

• It is recommended that a means for drainage is provided at every third floor.

TYPICAL DRAINAGE AT FLOORLINE

FLOOR SLAB*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT

FLASHING*

BASF WS FLASH WITH FLASHING PRIMER

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

Page 13: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

TYPICAL TERMINATION AT FOUNDATION

CAM-09 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure a means for drainage is provided at system termination at foundation.

• Terminate system a minimum of 8" (203 mm) above grade.

• Extend system a minimum of 2" (50 mm) and a maximum of 12" (305 mm) at the sole plate foundation transition.

FRAMING*

ACCEPTABLE SHEATHING*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH W FLASHING PRIMER

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

FLASHING*

ACCEPTABLE SEALANT*

FOUNDATION*

Page 14: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure a means for drainage is provided at system termination at foundation.

• Place weeps a minimum of 24" (610 mm) on center.

TYPICAL TERMINATION AT FOUNDATION (FLUSH)

CAM-10 190904

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BASF WS FLASH WITH FLASHING PRIMER

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WEEP*

FOUNDATION*

Page 15: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

TYPICAL WINDOW HEAD (FLUSH)

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure a means for drainage is provided at system terminations at all window, door and PTAC unit heads.

• Provide end-dams at flashing terminations.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

CAM-11 190904

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH W FLASHING PRIMER

ADHERED VENEER*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

FLASHING*

WINDOW*

ACCEPTABLE SEALANT*

Page 16: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure a means for drainage is provided at system terminations at all window, door and PTAC unit heads.

• Provide end-dams at flashing terminations.

• Place weeps a minimum of 16" (406 mm) on center.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

CAM-12 190904

TYPICAL WINDOW HEAD (FLUSH) WITH WEEPS

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

ADHERED VENEER*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WEEP*

FLASHING*

ACCEPTABLE SEALANT*

WINDOW*

Page 17: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure that the diverter flashing extends 6" (152 mm) beyond opening on either side of the opening to allow potential moisture to drain down the wall to the side of the opening. BASF MAXFLASH or SHEATHING FABRIC embedded in SENERSHIELD-R/-RS/-VB or WS FLASH with Flashing Primer must be extended over flange of diverter track. Ensure the diverter track flashing is sloped to provide a means for drainage. Length of diverter track not to exceed 10 ft. (3 m).

• Maintain a minimum of 3/4" (19 mm) EPS insulation thickness over diverter track.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

CAM-13 190904

TYPICAL WINDOW HEAD (FLUSH) WITH DIVERTER TRACK

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

DIVERTER TRACK*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WINDOW*

Page 18: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-14 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure a means for drainage is provided at system terminations at all window, door and PTAC unit heads.

• Provide end-dams at flashing terminations.

• EPS insulation boards must be a single piece around corners of openings.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

TYPICAL WINDOW HEAD WITH SEALANT END DAM

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

ACCEPTABLE SEALANT*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

FLASHING*

ACCEPTABLE SEALANT*

WINDOW*

Page 19: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-15 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

• Provide a back wrapped joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).

TYPICAL WINDOW JAMB (FLUSH)

FRAMING*

ACCEPTABLE SHEATHING*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WINDOW*

Page 20: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-16 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

• Provide a back wrapped joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).

TYPICAL WINDOW SILL (FLUSH)

WINDOW*

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

ADHERED VENEER*

BASF MAXGRIP VENEER MORTAR

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SENERGY BASE COAT

APPROVED EPS INSULATION BOARD

SENERGY SENERSHIELD-R/-RS/-VB

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

ACCEPTABLE SHEATHING*

FRAMING*

Page 21: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Provide a back wrapped joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).

• Ensure that the diverter flashing extends 6" (152 mm) beyond opening on either side of the opening to allow potential moisture to drain down the wall to the side of the opening. BASF MAXFLASH or SHEATHING FABRIC embedded in SENERSHIELD-R/-RS/-VB or WS FLASH with Flashing Primer must be extended over flange of diverter track. Ensure the diverter track flashing is sloped to provide a means for drainage. Length of diverter track not to exceed 10 ft. (3 m).

• Maintain a minimum of 3/4" (19 mm) EPS insulation thickness over diverter track.

• BASF INTERMEDIATE 12 reinforcing mesh is lapped around corners.

TYPICAL WINDOW HEAD (RECESSED)

CAM-17 190904

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

DIVERTER TRACK*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WINDOW*

Page 22: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-18 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

• Provide a back wrapped joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).

• BASF INTERMEDIATE 12 reinforcing mesh is lapped around corners.

TYPICAL WINDOW JAMB (RECESSED)

FRAMING*

ACCEPTABLE SHEATHING*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COATSKIM COAT OF BASF MAXGRIP VENEER MORTARBASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WINDOW*

Page 23: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-19 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

• Ensure that pan flashing extends onto the system a minimum of 2” (50 mm) down the face and that end dams are provided.

TYPICAL WINDOW SILL (RECESSED)

WINDOW*

PAN FLASHING WITH END DAMS*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

ACCEPTABLE SEALANT*

ADHERED VENEER*

BASF MAXGRIP VENEER MORTAR

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SENERGY BASE COAT

APPROVED EPS INSULATION BOARD

SENERGY SENERSHIELD-R/-RS/-VB

ACCEPTABLE SHEATHING*

FRAMING*

Page 24: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-20 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure a means for drainage is provided at system terminations at all window heads.

• Provide end-dams at flashing terminations.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

TYPICAL FLANGED WINDOW HEAD

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

FLASHING*

ACCEPTABLE SEALANT*

WINDOW*

Page 25: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-21 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

• Provide a back wrapped joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).

TYPICAL FLANGED WINDOW JAMB

FRAMING*

ACCEPTABLE SHEATHING*

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WINDOW*

Page 26: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-22 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure Senergy air/water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.

• Provide a back wrapped joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).

• Consult window manufacturer for recommendations for treatment of window sill flange.

TYPICAL FLANGED WINDOW SILL

BASF MAXFLASH OR SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR WS FLASH WITH FLASHING PRIMER

WINDOW*

BACKER ROD AND SEALANT (WIDTH PER DESIGN)*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

ADHERED VENEER*

BASF MAXGRIP VENEER MORTAR

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SENERGY BASE COAT

APPROVED EPS INSULATION BOARD

SENERGY SENERSHIELD-R/-RS/-VB

ACCEPTABLE SHEATHING*

FRAMING*

Page 27: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

CAM-23 190904

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure that coping/ flashing extends over the system a minimum of 2" (50 mm).

• Extend the Senergy air/water-resistive barrier on to the bottom and face of blocking.

TYPICAL COPING

COPING*

ROOF SYSTEM*

CLEAT*

WRAP SENERGY BASE COAT AND SENERGY FLEXGUARD 4 REINFORCING MESH

ADHERED VENEER*

ACCEPTABLE SEALANT*

BASF MAXGRIP VENEER MORTAR

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SENERGY BASE COAT

APPROVED EPS INSULATION BOARD

SENERGY SENERSHIELD-R/-RS/-VB

ACCEPTABLE SHEATHING*

FRAMING*

Page 28: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

Channeled Adhesive CI Design with MaxGrip Veneer Mortar

* NOTE: BY OTHERS

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com

This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.

• Install BASF materials in accordance with current installation instructions.

• All terminations must be fully encapsulated with mesh reinforced base coat.

• Ensure all penetrations through the system and railing plate are properly sealed.

CAM-24 190904

TYPICAL RAILING ATTACHMENT

FRAMING*

ACCEPTABLE SHEATHING*

SENERGY SENERSHIELD-R/-RS/-VB

SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD

APPROVED EPS INSULATION BOARD

SENERGY BASE COAT

BASF INTERMEDIATE 12 REINFORCING MESH EMBEDDED IN SENERGY BASE COAT

SKIM COAT OF BASF MAXGRIP VENEER MORTAR

BASF MAXGRIP VENEER MORTAR

ADHERED VENEER*

WOOD BLOCKING*

MECHANICAL FASTENER SET IN SEALANT*

SLEEVE SET IN SEALANT*

RAILING PLATE SET IN SEALANT*

RAILING*

Page 29: Channeled Adhesive CI Design with MaxGrip Veneer Mortar ... · floor lines in multi-level wood frame construction, at slip track in steel framed construction and where movement is

WarrantyBASF warrants this product to be free from manufacturing defects and to meet the technical properties on the current Product Bulletin, if used as directed within shelf life. Satisfactory results depend not only on quality products but also upon many factors beyond our control. BASF MAKES NO OTHER WARRANTY OR GUARANTEE, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO ITS PRODUCTS. The sole and exclusive remedy of Purchaser for any claim concerning this product, including but not limited to, claims alleging breach of warranty, negligence, strict liability or otherwise, is shipment to purchaser of product equal to the amount of product that fails to meet this warranty or refund of the original purchase price of product that fails to meet this warranty, at the sole option of BASF. In the absence of an extended warranty issued by BASF, any claims concerning this product must be received in writing within one (1) year from the date of shipment and any claims not presented within that period are waived by Purchaser. BASF WILL NOT BE RESPONSIBLE FOR ANY SPECIAL, INCIDENTAL, CONSEQUENTIAL (INCLUDING LOST PROFITS) OR PUNITIVE DAMAGES OF ANY KIND. Purchaser must determine the suitability of the products for the intended use and assumes all risks and liabilities in connection therewith. This information and all further technical advice are based on BASF’s present knowledge and experience. However, BASF assumes no liability for providing such information and advice including the extent to which such information and advice may relate to existing third party intellectual property rights, especially patent rights, nor shall any legal relationship be created by or arise from the provision of such information and advice. BASF reserves the right to make any changes according to technological progress or further developments. The Purchaser of the Product(s) must test the product(s) for suitability for the intended application and purpose before proceeding with a full application of the product(s). Performance of the product described herein should be veri�ed by testing and carried out by quali�ed experts.

BASF Corporation - Wall Systems | 889 Valley Park Drive Shakopee, MN 55379 P: 800.589.1336 www.senergy.basf.com© 2019 BASF Corporation rev 09/2019