chapter 2 literature review -...
TRANSCRIPT
24
CHAPTER 2
LITERATURE REVIEW
The present research is focused on the free cooling of buildings
with the PCM-based thermal energy storage heat exchanger. Hence, a detailed
literature survey has been made on the various studies carried out by the
researchers on the different passive cooling techniques, free cooling potential
and night ventilation, free cooling with direct ambient air circulation, free
cooling with PCM for cold storage applications, studies on PCM and
modelling of the phase change storage system.
2.1 PASSIVE COOLING TECHNIQUES
2.1.1 Solar and Heat Protection Techniques (Reduce Heat Gains)
The presence of water, plants and trees contributes to microclimate
cooling, and is an important source of moisture within the mostly arid urban
environment (Robitu et al (2006)). Indoor simulations still tend to be isolated
from an important element affecting urban microclimate, such as urban trees.
The main advantage of urban trees, as a bioclimatic responsive design
element is to produce shade, whereas its main disadvantage is blocking the
wind (Yoshida et al (2006)). In addition, the effects of specific urban tree
types - for example, the different leaf area densities and evapotranspiration
rates of urban trees influence solar access and heat exchanges, if planted
around buildings (Radhi (2009)). Eumorfopoulou and Kontoleon (2009) and
Kontoleon and Eumorfopoulou (2010) analysed thoroughly the influence of
the orientation and proportion (covering percentage) of plant-covered wall
25
sections on the thermal behaviour of typical buildings in Greece during the
summer. Limor et al (2010) have analysed the thermal effect on an urban
street due to three levels of building densities. The study indicated the
importance of urban trees in alleviating the heat island effect in a hot and
humid summer. In all the studied cases, the thermal effect of the tree was
found to depend mainly on its canopy coverage level, and planting density in
the urban street, and a little on other species characteristics.
Gijón-Rivera et al (2011) made an assessment of the thermal
performance of an office on the top of a building with four different
configurations of window glass, and their influence on the indoor conditions.
NohPat et al (2011) observed that the use of solar control film in their
numerical analysis observed that the double glassing unit (DGU) is highly
recommended due to the energy gain reduction by 55%, compared to the
traditional DGU without the solar control film. Baetens et al (2010a) made a
survey on the prototype and the currently commercial dynamic tintable smart
windows, and concluded that the commercial electro-chromic windows seem
most promising to reduce cooling loads, heating loads and lighting energy in
buildings, where they have been found most reliable, and able to modulate the
transmittance of up to 68% of the total solar spectrum.
Belusko et al (2011) investigated the thermal resistance for the heat
flow through a typical timber framed pitched roofing system, measured under
outdoor conditions for the heat flow up. However, with higher thermal
resistance systems containing bulk insulation within the timber frame, the
measured result for a typical installation was as low as 50% of the thermal
resistance determined, considering two dimensional thermal bridging using
the parallel path method. This result was attributed to the three-dimensional
heat flow and insulation installation defects, resulting from the design and
construction method used. Translating these results to a typical house with a
26
200 m2 floor area, the overall thermal resistance of the roof was at least 23%
lower than the overall calculated thermal resistance, including the two
dimensional thermal bridging. Ong (2011) reported that the heat transmission
through the roof could be reduced by providing insulation in the attic under
the roof or above the ceiling. A roof solar collector could provide both
ventilation and cooling in the attic. Several laboratory-sized units of passive
roof designs were constructed and tested side-by-side under outdoor
conditions to obtain the temperature data of the roof, attic and ceiling, in order
to compare their performances.
2.1.2 Heat Modulation or Amortization Techniques (Modify Heat
Gains)
The PCM wallboard is considered to be an effective and less costly
replacement of the standard thermal mass, to store solar heat in buildings, in
which the PCM is embedded into a gypsum board, plaster or other building
structures. Neeper (2000) impregnated fatty acid and paraffin waxes into the
gypsum wallboard and examined the thermal dynamics under the diurnal
variation of the room temperature (the radiation absorbed was not considered)
with the PCM on the interior and exterior portions respectively. Their
investigation indicated that when the PCM’s melting temperature was close to
the average room temperature, the maximum diurnal energy storage occurred
and diurnal energy storage decreased if the phase change transition occurred
over a range of temperature.
In order to evaluate the capacity of the PCM to stabilise the internal
environment when there were external temperature changes and solar
radiations, Kuznik et al (2008) designed an experimental test room
MINIBAT, using a battery of 12 spotlights to simulate an artificial sunning,
and they got the results that the PCM wallboard can reduce the air
temperature fluctuations in the room and enhance the natural convection
27
mixing of the air, avoiding uncomfortable thermal stratifications. Kuznik and
Virgone (2009) also tested two identical test cells under two kinds of external
temperature evolutions, heating and cooling steps with various slopes and
sinusoidal temperature evolutions, in a 24 hours period. They found there was
a time lag between the indoor and outdoor temperature evolutions and the
external temperature amplitude in the cell was reduced.
Lv et al (2006) built an ordinary room as well as a room using PCM
gypsum wallboard in the northeast of China, and they found that the PCM
wallboards can attenuate indoor air fluctuation, reduce the heat transfer to the
outdoor air and have the function to keep warm. Recently, Kuznik et al (2011)
used Dupont de Nemours PCM wallboards for the renovation of a tertiary
building, and found that they were really efficient if the outside temperature
was varying in melting temperature by monitoring the building for a whole
year.
Another method of applying PCMs into building structures is to
incorporate them into the concrete matrix or open cell cement. This composite
is called thermocrete. Cabeza et al (2007) studied a new innovative concrete
with PCM on its thermal aspects, in order to develop a product which would
not affect the mechanical strength of the concrete wall. They set up two real
size concrete cubicles to demonstrate the possibility of using
microencapsulated PCM in concrete. They found that the concrete reached a
compressive strength, over 25 MPa and a tensile splitting strength, over
6 MPa and no difference occurred in the effects of the PCM after 6 months of
operation. Baetens et al (2010b) reported that enhancing the thermal mass of
concrete buildings seemed better than the use of PCM wallboards; however,
the high cost of PCMs was the biggest concern.
Koschenz and Lehmann (2004) put forward a new concept of a
thermally actived ceiling panel for refurbished buildings. In this system, the
28
mixture of microencapsulated PCM and gypsum was poured into a sheet steel
tray which was used as a support for maintaining the mechanical stability of
the panels. A capillary water tube system was applied to control the thermal
mass. They tested the thermal performance of this system, and indicated that
only a 5 cm layer of microencapsulated PCM and gypsum was enough for a
standard office to keep within comfortable temperatures.
Pasupathy et al (2008a) presented a detailed review on the PCMs’
incorporation in buildings, and the various methods used to contain them for
thermal management in residential and commercial establishments. Among
all the PCM applications for high-performance buildings, the PCM integration
in wallboards, roof & ceiling, and windows is most commonly studied, due to
its relatively more effective heat exchange area and more convenient
implementation. Pasupathy et al (2008b) constructed an experimental setup
consisting of two identical test rooms, to study the effect of having a PCM
panel in the roof for the thermal management of a residential building. One
room is constructed without the PCM on the roof, to compare the thermal
performance of an inorganic eutectic PCM which has a melting temperature
in the range of 26-28°C. A numerical model was also developed by them, and
the results of the model were validated with the experimental results, and
several simulation runs were conducted for the average ambient conditions for
all the months in a year, and for various other parameters of interest.
Pasupathy and Velraj (2008) recommended a double-layer PCM concept in
the roof to achieve year round thermal management in a passive manner.
2.1.3 Heat Dissipation Techniques (Remove Internal Heat)
Bassindowa et al (2007) and Farmahini et al (2009) investigated the
experimental and theoretical applications of long-wave radiance, nocturnal
radiative cooling, its potential in different climate conditions, and the effects
of various parameters on this passive method. Prapapong and Surapong
29
(2007) showed that a cooling tower could be employed to provide cooling
water for radiant cooling and for pre-cooling of the ventilation air to achieve
thermal comfort. No active cooling is required. If a more exacting condition is
required, then pre-cooling the ventilation air with cooling water generated
from active cooling can help achieve thermal comfort, superior to that of
conventional air-conditioning, while substantial energy saving can still be
achieved.
Farahani et al (2010) studied the results of an investigation on a
two-stage cooling system; it consists of a nocturnal radiative unit, a cooling
coil and an indirect evaporative cooler; this investigation has been carried out
in the weather conditions in the city of Teheran, and the results demonstrated
that the first stage of the system increases the effectiveness of the indirect
evaporative cooler. Also, the regenerative model provides the best comfort
conditions. Heidarinejad et al (2010a) studied a hybrid system of nocturnal
radiative cooling, and direct evaporative cooling in Teheran. This system
complements direct evaporative cooling, as it consumes low energy to
provide cold water, and is able to fulfil the comfort conditions, whereas direct
evaporative alone is not able to provide summer comfort conditions, and the
results showed that the overall effectiveness of the hybrid system is more than
100%.
Heidarinejad et al (2010b) analysed a ground-assisted hybrid
evaporative cooling system in Teheran. A ground coupled circuit (GCC)
provides the necessary pre-cooling effects, enabling a Direct Evaporative
Cooler (DEC) that cools the air even below its wet-bulb temperature. The
simulation results showed that a combination of the GCC and DEC systems
could provide comfort conditions, whereas the DEC alone could not. Based
on the simulation results the cooling effectiveness of a hybrid system is found
30
to be more than 100%. Thus, this novel hybrid system could decrease the air
temperature below the ambient wet-bulb temperature.
Maerefat and Haghighi (2010) studied a low-energy consuming
passive cooling technique (solar chimney together with earth-to-air heat
exchanger) to remove undesirable interior heat from a building in the hot
seasons. He found that it is possible to use the solar chimney to power the
underground cooling system during the daytime, without any need for
electricity. Moreover, this system with a proper design may also provide a
thermally comfortable indoor environment for a large number of hours during
the scorching summer days.
Recently, Geetha and Velraj (2012) reviewed the various possible
methods of passive cooling for buildings and discussed the representative
applications of each method. They broadly classified the passive cooling
methods under three categories: (i) Heat prevention techniques (ii) Thermal
moderation techniques and (iii) Heat dissipation techniques.
2.2 FREE COOLING POTENTIAL
Various studies carried out to assess the free cooling potential in
different regimes of the world are summarised. Lam et al (2005) measured the
long-term hourly and daily weather data for five cities in China, namely
Harbin, Beijing, Shanghai, Kuming and Hong Kong and analysed them.
These cities were selected to represent the five main architectural climates -
severe cold, cold, hot summer and cold winter, mild and hot summer, and
warm winter. Statistical techniques and graphical methods were used to study
the long-term weather characteristics of these five climatic zones. Three
common climatic variables, namely temperature (dry-bulb and wet-bulb),
solar radiation (global, direct and diffuse) and wind conditions (wind speed
and wind direction), were investigated.
31
The potential of free cooling represents a measure of the capability
of ventilation to ensure indoor comfort without using the mechanical cooling
system (Ghiaus and Allard (2006)). The potential for passive cooling of
buildings by nighttime ventilation was evaluated by analysing the climatic
data, without considering any building-specific parameters (Artmann et al
(2007)). An approach for calculating the degree–hours based on a variable
building temperature – within a standardised range of thermal comfort – is
presented and applied to the climatic data of 259 stations all over Europe. The
results show a high potential for night-time ventilative cooling over the whole
of Northern Europe and still significant potential in Central, Eastern and even
in some regions of Southern Europe.
Medved and Arkar (2008) studied the free-cooling potential for
different climatic locations in Europe. The size of the LHTES was optimised
on the basis of the calculated cooling degree-hours. Six representative cities
were selected in Europe that covers a wide range of different climatic
conditions. Numerical investigations of the free-cooling potential were made
for a time period of 3 summer months. Bulut and Aktacir (2011) studied the
free cooling potential of Istanbul, Turkey by using hourly dry-bulb
temperature measurements during a period of 16 years. It is found that the
free cooling potential varies with the supply air temperature and months. It is
determined that although there are substantial energy savings during a
significant portion of the year, especially in the transition months (April, May,
September and October), the high outdoor air temperatures from June to
August, made the system not beneficial for free cooling except at high supply
air temperature. The HVAC systems which have a free cooling option should
be preferred, if the climate is favourable.
32
2.3 NIGHT VENTILATION
Various literatures pertaining to free cooling by night ventilation
are reviewed and presented. Pfafferott et al (2003) have done a study on the
design of passive cooling by night ventilation. They identified the
characteristic building parameters and determined the night ventilation effect
with these parameters. Geros et al (2005) have investigated the impact of the
urban environment on night ventilation, and reported that the increase in air
temperature and decrease in wind velocity decreases the efficiency of night
ventilation.
Becker et al (2007) determined the internal air quality improvement
for school buildings by night ventilation techniques. Kubota et al (2009)
investigated the effectiveness of the night ventilation technique for residential
buildings in the hot humid climate of Malaysia. The results from the field
experiment showed that night ventilation would provide better thermal
comfort for occupants in Malaysian terraced houses, compared with the other
ventilation strategies in terms of operative temperature.
2.4 FREE COOLING WITH DIRECT AMBIENT AIR
CIRCULATION
Olsen et al (2003) showed that low energy cooling systems that
maximise free cooling from the outside air have the best energy performance
under mild UK climatic conditions. Emmerich et al (2011) described an
adaptive thermal comfort option as a tool for implementing the climatic
suitability methodology for natural ventilation in the U.S. climate. The
adaptive thermal comfort option has the potential to substantially increase the
effectiveness of natural ventilation cooling for many U.S. cities. Parys et al
(2012) studied the feasibility of passive cooling of buildings, solely by the
diurnal manual window operation in the temperate climate of Belgium.
33
2.5 FREE COOLING TECHNIQUES WITH PCM STORAGE
Free cooling is a concept developed for air conditioning
applications, in which coolness is collected from the ambient air during the
night and is released into the room during the hottest hours of the day. The
effectiveness of free cooling applications is highly dependent on the local
climate. Interior and desert regions are the most suitable because they have
large diurnal temperature variations (15°C is desired). The properties of the
PCM are very important, the melting temperature in particular. It should be in
the midrange of the diurnal temperature variation. Great importance for the
successful operation has an air flow. If it is large, then the heat transfer will be
sufficient, but at the expense of energy needed for the fans.
Free cooling differs from natural ventilation in which air exchange
takes place through mechanical fans. Otherwise, an additional power is
needed for the operation of fans but there is an improvement of the cooling
potential of the AHU. The significance of improvement depends on several
factors and one of them is the diurnal temperature range, where 15K between
the day and night temperature is desired (Zalba et al (2004)). Another is the
mode of air circulation. Some authors have proposed systems where during
the day indoor air circulation is used (Zalba et al (2004), Turnpenny et al
(2000a)), which is favourable in terms of the cooling load, but it is less
favourable when it comes to indoor air quality.
Turnpenny et al (2000b) studied a novel ventilation cooling system
for reducing air-conditioning in buildings (Figure 2.1). A latent heat storage
unit incorporating heat pipes embedded in the PCM was developed and tested
for a novel application in low energy cooling of buildings.
34
Figure 2.1 Schematic of proposed design by Turnpenny et al
A theoretical model of heat transfer between the air and the PCM
via a heat pipe was designed and tested. The developed model gives heat
storage of about 270 Watt-hour over an eight hour office day. Assuming heat
gains of 30 W/m2 in an office floor area of 15 m2, over eight hours, 3600
Watt-hour of storage is required, i.e. 13 units. In most cases, the model over-
predicted the heat transfer rate by about 100%, but predicted the heat pipe
surface temperature within 2°C. The measurements of the model showed that
a large temperature difference between the air and the PCM (15°C or more)
was needed to melt and freeze the material in practical timescales (7 ± 10
hour). At more reasonable temperature differences and flow rates (e.g. 5°C,
0.18 m3/s), the heat transfer falls below 40 W, and the melt time increases
significantly.
A Night Ventilation system with PCM packed bed storage (NVP)
was proposed by Yanbing et al (2003), for increasing a building's energy
efficiency (Figure 2.2). During the night, the cold air from outside is blown
through the LHTES system, which charges it with the cold. In the daytime,
35
the cold stored in the PCM is released to the air, which circulates between the
LHTES system and the room.
Figure 2.2 Schematic of the NVP system proposed by Yanbing et al
In order to analyse the thermal behaviour of the NVP system, a
mathematical model was derived, which considered the energy storage
(LHTES) system and the ventilation scheme. Besides that, an experimental
installation was also made, where 20 shelves with three layers (2.4 m × 3 m ×
0.12 m) were attached to the ceiling of an experimental room with 10 m2. All
together, about 2000 capsules containing some kind of fatty acid developed
by the authors (190 kJ/kg, temperature of melting between 22°C and 26°C)
were used and the total mass of the PCM was 150 kg. The experimental
results proved that with the NVP system the room temperature decreases and
the thermal comfort level increases.
Zalba et al (2004) outlined the development of an installation for
free cooling (Figure 2.3.a) that allows testing the performance of the PCMs.
Part of the experimental setup was a flat plate heat exchanger (Figure 2.3.b)
36
with encapsulated PCM (RT25, Rubitherm GmbH). Experiments were
performed using 3 kg of PCM, which means a storage density of 28 kWh/m3.
(a) (b)
Figure 2.3 Schematic of proposed design by Zalba et al (a) General
sketch of the installation (b) Configuration of the TES
device
The main focus of the study was on: the ratio of energy/volume in
the encapsulates, the load / unload rate of storage, and the cost of the
installation. It was found that the effects with significant influence in the
solidification and melting process are the thickness of the encapsulation, the
inlet temperature of the air, the air flow, and the interaction between the
thickness and the temperature. The authors later proposed an improved
system, using a graphite matrix in a flat plate encapsulate (Marin et al (2005))
to overcome the low heat transfer rates. Comparing both systems it was
concluded that with the same thickness for the plates, the response time was
much lower (50% in time) and could be reached with a very low reduction of
the energy stored.
A paper by Takeda et al (2004) discusses the development of a
ventilation system, using direct heat exchange between the PCM granules and
the air. A PCM packed bed was installed vertically in a supply air duct, and
37
air was blown through the packed bed under certain conditions, releasing heat
or cold to it (Figure 2.4). The total weight of the PCM bed was 4.59 kg, and it
consisted of 65% ceramic materials and 35% paraffinic hydrocarbon by
weight, having a latent heat of 38 kJ/kg. First, they periodically varied the
inlet air temperature between 21.5°C and 28.0°C, and measured the outlet air
temperature in order to simulate changes of the outdoor ambient air
temperature. It was shown that the outlet air temperature was stabilised and
remained within the phase change temperature range. Then, computer
simulations were performed, analysing the potential of such a system in
reducing the ventilation load during summer for eight Japanese cities. It was
found that the maximum benefit could be obtained in Kyoto with a reduction
of ventilation load by 62.8%. Besides that they concluded that the range of
daily temperature variation has a greater influence on the benefit, than the
average temperature.
Figure 2.4 Elevation view of the experimental apparatus by Takeda et al
38
Nagano et al (2004) embedded the PCM directly on the floor
boards in the form of granules, several millimeters in diameter. This PCM
packed bed is permeable to air, and so is suitable for use in floor supply air-
conditioning systems. During the night, the circulation of cool air through the
under floor space allows cool energy to be charged to the concrete slab, floor
board and the PCM packed bed. During the daytime, the cool energy can be
used to remove the cooling load in the room. This method shown in
Figure 2.5 is superior compared to a sensible storage system, because the
building’s thermal mass storage capacity is limited.
Figure 2.5 System proposed by Nagano et al
An investigation into the efficiency of free cooling in a
heavyweight and lightweight low energy building was performed by Arkar et
al (2007). Two units of latent heat thermal energy storage (LHTES), one for
cooling the fresh supply air and the other for cooling the recirculated indoor
air, were integrated into a mechanical ventilation system (Figure 2.6). Both
LHTESs were filled with the PCM (RT 20, Rubitherm GmbH) encapsulated
into spheres. With the help of the developed and experimentally verified
39
numerical model, the temperature response functions, the air flow rates and
the PCM’s thermal properties were implemented into the TRNSYS building
thermal response model. The results showed that the total mass of the PCM in
LHTES-1 and LHTES-2 is 6.75 kg/m2 of floor area in the heavyweight
building and 13.5 kg/m2 in the lightweight building. Moreover, the free
cooling enables a reduction in the size of the mechanical ventilation system
and provides more favourable temperatures. Arkar and Medved (2007)
proposed another system but with only one LHTES. For their case study, they
analysed the optimum PCM peak temperature, optimum size of the LHTES
and the efficiency of the free cooling. It was found that the peak temperature
should be between 20°C and 22°C (continental climate), spheres should have
a diameter of 25 mm, and the optimal size should be 6.4 kg/m2 of floor area.
Figure 2.6 Different mechanical ventilation modes proposed by Arkar
et al (a) Mechanical ventilation, (b) free cooling - daytime
operation, (c) free cooling - nighttime operation
Based on the outcome of the experiments of Zalba et al, two
different real scale prototypes of the air-to-PCM heat exchangers (Figure 2.7)
were designed and tested by Lazaro et al (2009) following the
ANSI/ASHRAE standard 94.1-2002 (Method of testing the active latent heat
storage devices based on thermal performance). In this method, in order to
obtain accuracy in the measurement of the air flow, and the temperature
40
difference between the inlet and the outlet, precision thermopiles were used
for the measurement of the inlet and outlet temperatures.
Figure 2.7 Prototype 1 configuration proposed by Lazaro et al
A latent heat storage unit was proposed by Stritih and Butala (2009,
2010) for free cooling (Figure 2.8). An experiment was conducted using
3.6 kg of paraffin with a melting point of 22°C (RT 20, Rubitherm GmbH)
and heat storage capacity of 172 kJ/kg. A metal box with external and internal
fins was filled with the PCM, and the air was blown through it. The authors
have presented outlet air temperatures, heat fluxes and heat as a function of
time for different air velocities and inlet temperatures. A numerical model
was developed and there was good agreement with the experimental results. It
was shown that the cold storage can cool the air to a temperature below 24 °C
for more than 2.5 hours when the air velocity is 1 m/s and the inlet air
temperature 26°C.
41
Figure 2.8 Testing line scheme for measuring daily cold storage
efficiency proposed by Stritih and Butala
A detailed survey on the free cooling of building using phase
change materials was carried out by Antony Aroul Raj and Velraj (2010). In
addition to various researches on free cooling, the heat transfer problems and
design considerations associated with free cooling were also discussed by
them. In their view, the type of cooling system is to be designed, based on the
diurnal temperature of the place that depends on the geographical and micro
climatic conditions of the location.
An experimental study carried out by Waqas and Kumar (2011)
was conducted to investigate the thermal performance of the latent heat
storage for the free cooling of buildings in a dry and hot climate. The PCM
storage unit was an open air circuit type (Figure 2.9) which was fabricated
and installed in a controlled environmental chamber (to simulate the ambient
conditions of hot and dry climate). 13 kg of PCM (SP 29, Rubitherm GmbH)
was used, encapsulated in the containers of galvanised steel (0.5m × 0.5m ×
42
0.01m). The authors focused on the influence of the air flow rate and the inlet
air temperature on cold accumulation, and it was found that the solidification
of the PCM was more sensitive to the charging air temperature compared to
the air flow rate. When the charging air temperature was reduced from 22°C
to 20°C, 33% less time was needed to completely solidify the PCM. In the
case when the air flow rate changed from 4 m3/h to 5 m3/h, the solidification
time reduced up to 16%. Experimental observations also showed that lower
ambient temperatures and higher air flow rates are advantageous to complete
the solidification.
Figure 2.9 The experimental PCM storage unit proposed by Waqas
and Kumar
Antony Aroul Raj and Velraj (2011) developed a shell and tube
type heat exchanger (Figure 2.10.a) with the PCM in the shell portion of the
module, and a passage for the flow of air through the tubes. Its arrangement
(modules of the heat exchanger are stacked one over another with air spacers
in between) allows using it in free cooling applications where the diurnal
temperature variation is low.
43
(a) (b)
Figure 2.10 Schematic of the proposed system by Antony Aroul Raj and
Velraj (a) Operation of the free cooling system
(b) Photographic view of one module
Recently, Zhou et al (2012) reviewed the thermal storage with
phase change materials in building applications. This paper summarises
previous works on latent thermal energy storage in building applications,
covering PCMs, the impregnation methods, current building applications and
their thermal performance analyses, as well as the numerical simulation of
buildings with PCMs. Osterman et al (2012) studied the PCM based cooling
technologies for buildings. All studies have shown that the use of PCMs
helped to improve the energy performance of buildings, and they also
discussed the problems encountered in heat transfer, and the amount of PCM
needed for storage.
2.6 AIR CONDITIONING SYSTEM BASED ON PCM
Weather conditions, and industrial, commercial and residential
activities change during the day, and an air-conditioning system has to adapt
to these changes. This means that the electrical demand varies significantly,
reaching its peak load during the day. By using the cold storage with the
44
PCM, the load can be reduced and even shifted to the nighttime when the
electricity tariff is low. This entails steadier operation; moreover, the size of
the air-conditioning (AC) system can be adjusted (smaller power).
A detailed study of the phase change materials based cool thermal
energy storage (CTES) system integrated with a large building air-
conditioning system as shown in Figure 2.11, was presented by Velraj et al
(2006). In this system, the storage tank is kept separate away from the
building.
Figure 2.11 Layout of air conditioning system using thermal energy
storage
45
The major focus of this study was to provide technical information
about the encapsulated phase change material (PCM) based storage system for
air-conditioning applications, and the importance of a careful design load
calculation. The economic benefits of load shift operations are highlighted. It
was found that the PCM based storage system reduces the monthly demand
charge of INR 1.2 million. It was also estimated that a cost saving of INR
2.26 million per annum could be achieved through energy management. The
author suggested that the CTES system can be introduced economically for
air conditioning in residential / commercial establishments.
Kondo and Ibamoto (2006) examined the effects of a peak shaving
control of air-conditioning systems using PCM for ceiling boards in an office
building (Figure 2.12). A rock wool PCM ceiling board was enhanced by
adding a micro capsulate PCM with a melting point of about 25°C, and the
floor area was approximately 16 m2. The experiment was designed so that
during the night (from 4 AM to 8 AM) cold air from the air-handling unit
(AHU) flows into the ceiling chamber space and chills the PCM ceiling
board. The cold is then stored for peak hours (from 1 PM to 8 PM) when the
air from the room flows through a ceiling chamber to the AHU. With such an
arrangement, the air is pre-cooled and the result was that the maximum
thermal load using the PCM ceiling board was 85.2% of that, using the rock
wool ceiling board. The results also revealed that the transition rate of the
thermal load to the night was 25.1%, thus lowering the running cost to 91.6%,
compared to the rock wool ceiling board (for Japan).
46
Figure 2.12 Outline of the proposed system by Kondo and Ibamoto
2.7 PHASE CHANGE MATERIALS FOR BUILDING
APPLICATIONS
Thermal energy can be stored in PCMs as the heat of vaporization
(liquid–vapour transition) or heat of fusion (solid–liquid transition), where the
latter is mainly used nowadays (Farid et al (2004), and Tyagi et al (2011)).
PCMs allow large amounts of energy to be stored in a relatively small
volume, resulting in some of the lowest storage media costs of any storage
concepts. Most of the comparative studies for phase change heat energy
storage and sensible heat storage have shown that a significant reduction in
storage volume can be achieved, using the PCM compared to sensible heat
storage (Morrison et al (1978)).
47
Phase change materials are categorized as organic, inorganic and
eutectic materials. Organic materials are further divided into fatty acids,
paraffins and non-paraffins. Inorganic materials are divided into salt hydrates
and metallics. However, a eutectic is a minimum-melting composition of two
or more organic or inorganic PCMs like organic-organic, organic-inorganic
and inorganic-inorganic (Sharma et al (2009)). The materials to be used for
phase change thermal energy storage must have a large latent heat and high
thermal conductivity. They should have melting / freezing temperatures in the
practical range of application (Agyenim et al (2010)). The hydrated salts,
paraffin waxes, fatty acids and eutectics of organic and non-organic
compounds have been widely used as phase change materials for the last 30
years. In building applications, the PCMs with a phase change temperature
(18–30°C) are preferred to meet the need of thermal comfort. Some potential
PCMs are listed here, including organic PCMs, salt hydrates and eutectics, as
well as commercial PCMs, seen in Tables 2.1 and 2.2.
2.7.1 PCM Encapsulation
The technology of PCMs encapsulated in a container, for example,
tubes, spheres or panels, is called macro encapsulation. Several studies have
been made of various configurations like flat plate, cylindrical, and spherical
encapsulation as shown in Figure 2.13. With flat plates, it is possible to
achieve more surface area per unit volume of storage material, and low PCM
thickness for reducing the solidification time. According to Zalba et al (2004),
the flat plate configuration with a channel width of 15 mm, resulted in a
charging time of 4 hours and discharging time of 6 hours, which is reasonably
accepted for free cooling. PCM cylindrical pipes have lesser fabrication
difficulty, comparable heat transfer characteristics and a lower heat loss rate.
48
Table 2.1 Thermal properties of potential PCMs
PCMs TypeMelting
temperature(°C)
Heat of fusion
(kJ/kg)
Paraffin C16–C18 Organic 20–22 152
Paraffin C13–C24 Organic 22–24 189
Paraffin C18 Organic 28 244
Butyl stearate Organic 19 140
1-Dodecano 1 Organic 26 200
n-Octadecane Organic 28 200
Vinyl stearate Organic 27–29 122
Dimethyl sabacate Organic 21 120–135
Polyglycol E600 Organic 22 127.2
45/55 capric + lauric acidOrganiceutectic
21 143
Propyl palmitate Organic 19 186
Octadecyl 3-mencaptopropylate Organic 21 143
KF.4H2OHydrate
salts18.5 231
Mn(NO3).6H2OHydrate
salts25.8 125.9
Cacl2.6H2OHydrate
salts29.7 171
CaCl2.6H2O + Nucleat +MgCl2.6H2O (2:1)
Inorganiceutectics
25 127
48% CaCl2 + 4.3% NaCl +0.4% KCl + 47.3% H2O
Inorganiceutectics
26.8 188
Source: Zhou et al (2011)
49
Table 2.2 Thermal properties of commercial PCMs
PCMs
Melting
temperature
(°C)
Heat of
fusion
(kJ/kg)
Specific heat
(kJ/kgK)
Thermal
conductivity
(W/mK)
Source
RT 20 22 172 - -Rubitherm
GmbH
RT 25 25 1472.9(s)
2.1(l)
1.02(s)
0.56(l)
Rubitherm
GmbH
RT 27 26–28 1791.8 (s)
2.4 (l)0.2
Rubitherm
GmbH
STL 27 27 213 - -Mitsubishi
Chemicals
Climsel C23 23 148 - - Climator
Climsel C24 24 216 - - Climator
S 27 27 1901.5 (s)
2.22 (l)
0.79 (s)
0.48 (l)Cristopia
TH 29 29 188 - - TEAP
SP 22 A 17 22 150 - 0.6Rubitherm
GmbH
SP 25 A 8 25 180 2.5 0.6Rubitherm
GmbH
SP 29 29 157 - 0.6Rubitherm
GmbH
50
Figure 2.13 Various types of PCM encapsulations
PCM balls have a larger surface area per unit volume compared to
the cylindrical geometry of the length equal to the diameter. Heat transfer and
pressure drop can be controlled by selecting the size of the balls. Arkar and
Medved (2005) used 25 mm balls. PCM pouches and panels were tested by
Lazaro et al (2009), and the panel was found to be superior to the pouch.
2.7.2 Thermal Stability of PCMs
The long-term stability of the PCMs is required by the practical
applications of latent heat storage, and therefore, there should not be major
changes in the thermal properties of PCMs after undergoing a great number of
thermal cycles. Thermal cycling tests to check the stability of PCMs in latent
51
heat storage systems were carried out for organics, salt hydrates and salt
hydrate mixtures by many researchers (Ting et al (1987), Fernanda et al
(1988), Sharma et al (1999), Sharma et al (2002), and Kimura et al (1988)).
Some potential PCMs were identified to have good stability and thermo-
physical properties. Shukla et al (2008) carried out the thermal cycling tests
for some organic and inorganic PCMs selected on the basis of thermal,
chemical and kinetic criteria, and their results showed that organic PCMs tend
to have better thermal stabilities than inorganic PCMs. Tyagi and Buddi
(2008) conducted the thermal cycling test for calcium chloride hexahydrate,
and found minor changes in the melting temperature and heat of fusion; only
about 1–1.5°C and 4% average variation respectively was recorded during
1000 thermal cycles. They recommend calcium chloride hexahydrate as a
promising PCM for applications.
2.8 MODELLING OF THE PHASE CHANGE STORAGE
SYSTEM
The numerical approach of solving phase change problems is
categorized as Temperature based models or variable domain models, and
Enthalpy based models or fixed domain models. In the temperature based
models, also called as variable domain models the volume of each region
changes with respect to time, and the temperature is the sole dependent
variable. The energy conservation equations are written separately for each
region, and the solutions of these equations are coupled through the energy
balance at the interface. The major disadvantage in the temperature based
model applied in PCMs is the continuous tracking of the solid-liquid
interface, by solving simultaneously all the three energy equations.
The most common method used is the enthalpy method. The
enthalpy model introduced in the 1940s is widely employed in modelling
52
phase change problems. The main advantage of this model is its ability to
accommodate PCMs with a wide phase change temperature range. In
addition, the phase change problems can be reduced to a single equation in
terms of enthalpy. There is no boundary condition to be satisfied at the
interface, and the total domain volume does not change with respect to time.
But from the calculation point of view, this can be determined from the
enthalpy function H (T) of the PCM, which is equal to the sum of the sensible
and the latent heat required for the phase change.
Lacroix (1993) developed a theoretical model to predict the
transient behaviour of a shell-and-tube storage unit with the PCM on the shell
side, and the heat transfer fluid (HTF) circulated inside the tube. Rady and
Mohanty (1996) had applied an enthalpy-porosity fixed grid method to the
melting and solidification of pure metals in a rectangular cavity. Kurklu et al
(1996) developed a numerical model for the prediction of the thermal
performance of a PCM, the polypropylene tube, utilising air as the heat
transfer fluid. Velraj et al (1997) carried out an experimental analysis and
numerical modelling of the inward solidification in a finned vertical tube for a
latent heat storage unit. Patrick and Lacroix (1998) numerically estimated the
thermal behaviour of a multi-layer heat storage unit. The model is based on
the conservation equation of energy for the PCM and the fluid heat transfer.
Zivkovic and Fujii (2001) simulated the transient behaviour of a phase change
material for both cylindrical and rectangular geometries, and their rectangular
geometry showed a good agreement with the experiment. Elgafy et al (2004)
developed a computational model to investigate and predict the thermal
performance of a high melting point phase change material, during its melting
and solidification processes within a cylindrical enclosure. Trp et al (2005)
carried out a theoretical and experimental heat transfer analysis of a shell and
tube heat exchanger, with the cold fluid inside and solidification outside.
53
An alternative formulation called the apparent heat capacity
method, is employed to solve the melting and solidification problem, by
including the effect of the PCM storage through the apparent heat capacity
model in the energy equation. Various shapes of the apparent heat capacity,
like rectangular and triangular profiles were studied by Beasley et al (1989)
and Lamberg et al (2004). Arkar and Medved (2005) simulated the heat
transfer in the cylindrical packed bed by using the apparent heat capacity
method, utilising the DSC results as a model of the heat capacity value.
Hed and Bellander (2006) developed a mathematical model of the
PCM air heat exchanger, which was verified with the measurement on a
prototype heat exchanger. Their model can fit into indoor climate and energy
simulation software, based on the finite difference method where the thermal
properties of the material are considered. A fictive heat transfer coefficient
was established, which includes aspects of the geometry and the airflow as
well as the PCM properties. For an air velocity of 4 m/s it ranged between 16
and 30 W/m2K depending on the surface of the unit. If the surface was rough,
then the heat transfer coefficient increased significantly, but at the same time
a higher input of energy for the fans is needed. Considerations were also taken
of different shapes of the cp(T) curve. It was concluded that special attention
should be paid to the time-dependent behaviour of the equipment, since there
is a great difference between the ideal and commercially available material.
Dubovsky et al (2011) analysed a shell and tube type tubular heat
exchanger in which the PCM melts inside the tubes while air flows across the
tube banks. Considering the sensible heat capacity of the liquid PCM, and the
tubes as small in comparison with the latent heat of melting, a system of
partial differential equations, which describes the heat transfer and melting of
the PCM inside the tubes and heat transfer in the air, has been derived and
solved. An analytical solution of the system of equations has been compared
54
with the results of a numerical solution, demonstrating a very good
agreement.
A one-dimensional liquid-based model of a flat slab phase change
thermal storage unit was developed by Liu et al (2011). The melting and
freezing processes are analysed, based on the temperatures of the heat transfer
fluid nodes, the wall nodes and the PCM nodes during melting and freezing.
The mathematical model developed was validated using two sets of
experimental data. The numerical results show a good agreement with the
experimental ones.
Antony Aroul Raj and Velraj (2011) carried out a transient and
steady state CFD analysis, for a single module (Figure 2.10.b) and two air
spacers. With the steady state CFD analysis, the authors determined the
pressure drop across the module, the flow and temperature variations in order
to select the right geometrical and flow parameters. With the transient
analysis, they determined the PCM solidification characteristics and verified
the suitability of the selected geometrical dimensions.
2.9 SUMMARY OF THE LITERATURE SURVEY
Much research has been done on cool energy storage, using solid-
liquid phase change materials focusing on applications for the cooling of
buildings. The studies were based on experimental work, and numerical
simulations primarily focused on the variation of indoor air temperature due
to the installation of PCMs. A lot of emphasis was also placed on the
possibility of reducing the electricity consumption for cooling. To determine
this possibility, it was necessary to know the characteristics of the system,
such as the charging / discharging rate, mass of the PCM, air flow rate, inlet
and outlet air temperatures, etc. Though plenty of research has been done on
free cooling potential, the free cooling concept was not implemented in any
55
buildings, due to the need for demonstration setups to create confidence
among the building owners. Further, this free cooling technology is site
specific. Hence the design also has to be carried out with respect to the
particular site of the building.
2.10 SPECIFIC OBJECTIVES OF THE PRESENT RESEARCH
A study carried out to assess the free cooling potential for
Bangalore city in India, revealed that this concept is highly suitable for this
city, and it is possible to eliminate totally a mechanical air conditioner.
Considering the potential and also the need for the demonstration setup, the
major objectives of the present work are formulated as below.
To develop a PCM based storage type heat exchanger suitable
for free cooling applications of buildings in Bangalore city.
To investigate the charging characteristics of the PCM under
various ambient conditions that prevails during the early-
morning hours in Bangalore city.
To determine the temperature reduction possible with the
present heat exchanger under various room heat load
conditions.
To carry out the CFD analysis for the configuration similar to
the experimental setup, to make it useful for designing such a
system under various operating conditions.