chapter 6 part a slides

Upload: fahad-al-shammeri

Post on 05-Apr-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Chapter 6 Part a Slides

    1/44

    CHAPTER 6:

    COMPENSATION

    TECHNIQUES

    (Part A)

  • 7/31/2019 Chapter 6 Part a Slides

    2/44

    Introduction

    Control system design involves the following three

    steps:

    Determine what the system should do and how

    to do it (design specifications).

    Determine the controller or compensator

    configuration relative to how it is connected to

    the controlled process.

    Determine the parameter values of the

    controller to achieve the design goal.

  • 7/31/2019 Chapter 6 Part a Slides

    3/44

    Design Specifications

    Used to describe what the system should do and

    how it is done.

    Examples of specifications: relative stability,steady-state accuracy (error), transientresponse, and frequency-responsecharacteristics.

  • 7/31/2019 Chapter 6 Part a Slides

    4/44

    Frequency Domain Design Graphical tools such as Bode plot, Nyquist plot, Nichols

    chart.

    Advantages:

    High order systems do not pose any particularproblem.

    Pure time delay (e-sT) only affects the phase response.

    Pure time delay does not need to be an integermultiple of the sampling interval.

    Disadvantage:

    Final measure of system performance more commonlyspecified as a time domain requirement.

  • 7/31/2019 Chapter 6 Part a Slides

    5/44

    Time Domain Design

    Includes transient response, limits on control signal,

    integrated absolute error (area between the curve of the

    desired response and that of the actual response).

    Advantages:

    Final measure of system performance more commonly specified as

    a time domain requirement.

    Commonly applied in auto-tuning using relays.

    Disadvantages:

    Feasible analytically only for second order systems.

    Pure time delay has to be an integer multiple of the sampling

    interval.

  • 7/31/2019 Chapter 6 Part a Slides

    6/44

    Controller Configurations

    Most conventional design methods rely on the fixed-

    configuration design.

    Control efforts involve the modification or compensation

    of the systems performance characteristics. The general design using fixed configuration is also called

    compensation.

    A compensator is an additional component or circuit thatis inserted into a control system to compensate for a

    deficient performance.

    Examples: PID-type controllers, lag, lead and lag-leadcompensators

  • 7/31/2019 Chapter 6 Part a Slides

    7/44

    Controller Configurations in

    Control System Compensation

    Series or Cascade compensation

    Feedback compensation

    State Feedback ControlCompensation

    Series-feedback compensation

  • 7/31/2019 Chapter 6 Part a Slides

    8/44

    Controller Configurations in

    Control System Compensation

    Forward Compensation with series compensation

    Feedforward compensation

  • 7/31/2019 Chapter 6 Part a Slides

    9/44

    Fundamental Pr inciples of

    DesignController configuration> Controller type>

    Controller parameter values

    Controller parameter values are typically thecoefficients of one or more transfer functions

    making up the controller.

    Can be selected only if the process transfer

    function is known. Determine how individual parameter values

    influence the design specifications and system

    performance.

  • 7/31/2019 Chapter 6 Part a Slides

    10/44

    Fundamental Pr inciples of

    DesignGeneral guidelines:

    Complex-conjugate polesof the closed-loop transferfunction lead to a step response that is underdamped. If

    all system poles are real, the step response isoverdamped.

    The response of a system is dominated by the polesclosest to the origin in the s-plane. Transient due tothose poles farther to the left decay faster.

    The farther to the left in the s-plane the systemsdominant poles are, the faster the system will respondand the greater its bandwidth will be.

    The farther to the left in the s-plane the systems

    dominant poles are, the larger its internal signals will be.

  • 7/31/2019 Chapter 6 Part a Slides

    11/44

    Fundamental Pr inciples of

    DesignGeneral guidelines (cont.):

    When a pole and zero of a system transfer functionnearly cancel each other, the portion of the system

    response associated with the zero-pole pair will have asmall magnitude.

    Time and frequency domain specifications are loosely

    associated with each other.

    Rise Time:

    Phase Margin:

    Resonance Peak:

    10

    16.260.0

    n

    rt

    degrees60marginphase0100

    marginphase

    0.707

    12

    1

    2

    rM

  • 7/31/2019 Chapter 6 Part a Slides

    12/44

    Cascade Compensation

    Networks Compensator GC(s) is cascaded with the unalterable

    process GP(s).

    GC(s) can be chosen to alter the shape of the root locus.

    In general,

    Problem reduces to the selection of the zeros and poles

    ofGC(s).

    n

    j

    j

    m

    i

    i

    C

    ps

    zsK

    sG

    1

    1

    )(

    )(

    )(

  • 7/31/2019 Chapter 6 Part a Slides

    13/44

    Process: Second order prototype with T.F.

    Controller: PD type with the T.F.

    Control signal applied to the process

    Design with PD (Propor tional-

    Der ivative) Controller

    )2()(

    2

    n

    nP

    sssG

    )()( CDPc zsKsKKsG

    dt

    tdeKteKtu DP

    )()()(

  • 7/31/2019 Chapter 6 Part a Slides

    14/44

    Electronic-circuit realization

    of the PD controller

    For the two-op-amp circuit , the input impedance of stage 1,

    Output voltage of stage 1,

    11

    1

    1

    1

    11

    1

    1

    1 1

    11

    RsC

    R

    R

    RsCsC

    R

    inin ERsCR

    RE

    RsC

    R

    RE 11

    1

    2

    11

    1

    21 1

    1

  • 7/31/2019 Chapter 6 Part a Slides

    15/44

    Output voltage of stage 2,

    Transfer function of op-amp circuit:

    Transfer function of PD controller:

    Comparing with PD equation

    Advantage: Only two op-amps are needed.

    Disadvantage: Does not allow independent selection ofKPandKD, as they are commonly dependent on R2.

    inERsC

    R

    REE 11

    1

    210 1

    sCRR

    R

    sE

    sEsG

    in

    c 12

    1

    20

    )(

    )()(

    sKKsG DPc )(

    1212 / CRKRRK DP

  • 7/31/2019 Chapter 6 Part a Slides

    16/44

    For the three-op-amp circuit ,

    Stage 1:

    Stage 2:

    inER

    RE

    1

    21 indd ECsRE 2

    R

    E

    R

    E

    R

    E 021 000

    0

    1

    2 EECsRE

    R

    Rinddin

  • 7/31/2019 Chapter 6 Part a Slides

    17/44

    Transfer function of op-amp circuit:

    Transfer function of PD controller:

    Forward-path transfer function of the compensated system:

    PD control is Equivalent to adding a simple zero at s = -KP/KDto

    the forward-path transfer function.

    sCR

    R

    R

    sE

    sEsG dd

    in

    C 1

    20

    )(

    )()(

    sKKsG DPc )(

    n

    DPnPC

    ss

    sKKsGsG

    sE

    sYsG

    2)()(

    )(

    )()(

    2

  • 7/31/2019 Chapter 6 Part a Slides

    18/44

    Summary of Effects of PD

    Control Improves dampingand reduces maximum overshoot

    Reduces rise time and settling time

    Increases BW

    Improves gain margin, phase margin and resonancepeak

    May accentuate noise at higher frequencies

    Not effective for lightly damped or initially unstable

    system May require a relatively large capacitor in circuit

    implementation

  • 7/31/2019 Chapter 6 Part a Slides

    19/44

    Example 6.1

    Consider a second order model of an aircraft attitude

    control system as follows:

    Performance specifications:

    Steady-state error due to unit ramp input 0.000443

    Maximum overshoot 5%

    Rise time tr 0.005s

    Settling time ts 0.005s

    )2.361(

    4500

    )( ss

    K

    sG

  • 7/31/2019 Chapter 6 Part a Slides

    20/44

    Uncompensated system:

    The ramp error constant =

    Steady-state error due to a unit ramp input,

    ess 0.000443

    ess= 1/Kv361.2/(4500K) 0.000443 => K 181.17.

    Characteristic equation

    Natural Frequency: rad/s

    Damping ratio: (quite low)

    2.361

    4500)(lim

    0

    KssGK

    sv

    0)17.181(45002.3612 ss08152652.3612 ss

    92.902815265 n

    2.02

    2.361

    n

    %7.52)-1/100exp(-overshootMaximum 2

  • 7/31/2019 Chapter 6 Part a Slides

    21/44

    System compensated with PD controller

    - Inserting PD controller in forward-path of the system

    - The damping and maximum overshoot are improved- Maintain the essdue to the unit ramp input at 0.000443

    With the PD controller and K= 181.17, the forward-path transferfunction is

    The closed-loop transfer function is

    Effects of the PD controller:

    Add a zero at s= -KP/KDto the closed-loop transfer function.

    Increase the damping term.

    )2.361(

    )(815265

    )(

    )(

    )(

    ss

    sKK

    s

    s

    sGDP

    e

    y

    pD

    DP

    r

    y

    KsKs

    sKK

    s

    s

    815265)8152652.361(

    )(815265

    )(

    )(2

  • 7/31/2019 Chapter 6 Part a Slides

    22/44

    The ramp error constant is

    The steady state error due to a unit ramp input is

    ess= 1/Kv= 0.000443/KP.

    Characteristic equation

    Arbitrarily set KP= 1. (Which acceptable from the essrequirement)

    => Increased damping!

    If we wish to have critical damping = 1, KD= 0.001772.

    P

    P

    sv K

    K

    ssGK 1.22572.361

    815265

    )(lim0

    0815265)8152652.361(2 PD KsKs

    rad/s92.902815265 n

    DD K

    K46.4512.0

    84.1805

    8152652.361

  • 7/31/2019 Chapter 6 Part a Slides

    23/44

    Unit step responses of the attitude control

    system with and without PD control

  • 7/31/2019 Chapter 6 Part a Slides

    24/44

    Table below gives the results for KP= 1, KD= 0, 0.0005, 0.00177 and0.0025.

    Performance requirements are all satisfied with KD 0.00177.

    Constraints on KD:

    Large KDcorresponds to large BW, which may cause high-

    frequency noise problem. The capacitor value in the op-amp circuit implementation should

    not be too large.

    PD controller decreases the maximum overshoot and settling time

    KD t r (s) ts (s) Max. overshoot (%)

    0 0.00125 0.0151 52.2

    0.0005 0.00144 0.0076 25.7

    0.00177 0.00119 0.0015 4.2

    0.0025 0.00103 0.0013 0.7

  • 7/31/2019 Chapter 6 Part a Slides

    25/44

    A certain industrial plant synthesizes a chemical product from raw

    materials at high temperature in a reactor. It is required to design a

    controller for the system in order to control the temperature of the

    reactor, which is considered an important parameter affecting the

    quality of the chemical product. The transfer function between its

    input (desired temperature) and the output (actual temperature) is

    estimated to be

    a) The system is known to be lightly damped. Find the damping ratio

    of the system in closed-loop without any controller.

    b) Design a Proportional-Derivative (PD) controller in order toimprove the damping ratio by five times of the original value

    found in part (a). It is also required that the steady-state error in

    response to a unit ramp input be equal to 0.01.

    c) State, in general, two positive effects of improving the damping

    ratio of a lightly damped system.

    )2.0(

    1)(

    ss

    sGP

  • 7/31/2019 Chapter 6 Part a Slides

    26/44

    Process: Second order prototype with T.F.:

    Controller: PI type with the T.F.:

    Control signal applied to the process:

    )2()(

    2

    n

    nP

    sssG

    Design with PI Controller

    s

    zsK

    s

    KKsG CIPC

    )(

    dtteKteKtu IP )()()(

  • 7/31/2019 Chapter 6 Part a Slides

    27/44

    Electronic-circuit realization

    of the PI controller

    For the two-op-amp circuit , the transfer function,

    Comparing with PI equation:

    sCRR

    R

    sE

    sEsG

    in

    c

    211

    20 1

    )(

    )()(

    211

    2 1CR

    KR

    RK IP

  • 7/31/2019 Chapter 6 Part a Slides

    28/44

    For the three-op-amp circuit ,

    Transfer function:

    Comparing with PI equation:

    sCRR

    R

    sE

    sEsG

    iiin

    C

    1

    )(

    )()(

    1

    20

    ii

    IPCR

    KR

    RK

    1

    1

    2

  • 7/31/2019 Chapter 6 Part a Slides

    29/44

    The forward-path transfer function of the compensated

    system is

    Immediate effects of PI controller:

    Adds a zero at s= -KI/KPto the forward-path transfer function. Adds a pole at s= 0 to the forward-path transfer function.

    System type is increased from type-1 to type-2.

    System order increased from second order to third order.

    )2(

    )()()()(2

    2

    n

    IPnPC

    ss

    KsKsGsGsG

  • 7/31/2019 Chapter 6 Part a Slides

    30/44

    Advantages and disadvantages of PI control:

    Reduces rise time

    Increases settling time

    Decreases BW

    Filters out high frequency noise

    May need a large capacitor value

    Feasible method of designing the PI controller: Select the zero at s = -KI/KPso that it is relatively close to the

    origin and away from the most significant poles of the process.

    KPand KIshould both be relatively small.

    A zero close to the origin provides the effects of pole-zero

    cancellation. Improves stability by reducing phase lag.

    s

    sKKK

    s

    KKsG

    I

    PI

    IPC

    1

    )(

  • 7/31/2019 Chapter 6 Part a Slides

    31/44

    The smaller KI/ KPis, the faster approaches +90degrees.

    KPshould be small to avoid a large gain at phase crossoverfrequency.

    Increase stability.

    I

    P

    K

    K1tan

    I

    PC

    K

    KjG 1tan90)(

    222

    2

    1

    |)(|PII

    PI

    C

    KKK

    KK

    jG

  • 7/31/2019 Chapter 6 Part a Slides

    32/44

    Example 6.2

    Consider the second order attitude control systemdiscussed in Example 6.1. Applying the PI controller, the

    forward-path transfer function of the system becomes

    Time domain performance requirements:

    Steady-state error due to parabolic input t2us(t)/2 0.2

    Maximum overshoot 5%

    Rise time tr 0.01s

    Settling time ts 0.02s

    )2.361(

    )/(4500)()()(

    2

    ss

    KKsKKsGsGsG PIPPC

  • 7/31/2019 Chapter 6 Part a Slides

    33/44

    System compensated with PI controller

    The parabolic error constant is

    The steady state error constant is

    Set K= 181.17 (The value used in Example 6.1)

    => KI 0.002215 (Minimum value ofKI= 0.002215 )

    I

    I

    PIP

    ssa

    KK

    KK

    ss

    KKsKKssGsK

    46.122.361

    4500

    )2.361(

    )/(4500lim)(lim

    2

    2

    0

    2

    0

    0.2)(08026.01

    Ia

    ss

    KKK

    e

  • 7/31/2019 Chapter 6 Part a Slides

    34/44

    Characteristic equation of the closed-loop system:

    Rouths test:

    Stable for 0 < KI

    /KP

    < 361.2.

    Arbitrarily select

    08152658152652.361 23 IP

    KsKss

    I

    IP

    I

    P

    Ks

    KKs

    Ks

    Ks

    815265

    2.361/815265815265

    8152652.361

    8152651

    0

    1

    2

    3

    2.361P

    I

    K

    K

    10P

    I

    K

    K

  • 7/31/2019 Chapter 6 Part a Slides

    35/44

    Forward-path:

    Starting points (poles): 0, 0, -361.2

    Ending points (zeros): -10, ,

    Intersection of asymptotes:

    )2.361()10(815265

    )2.361()10()17.181(4500)(

    22

    sssK

    sssKsG PP

    13

    zerosfiniteofsum-polesfiniteofsum

    175

    2

    (-10)-361.2-

  • 7/31/2019 Chapter 6 Part a Slides

    36/44

    Breakaway points:

    s= 0, -21, -175

    0ds

    dKP

    )10(815265

    )2.361(2

    s

    ssKP

    010

    4.7223

    )10(

    2.361

    815265

    12

    2

    23

    s

    ss

    s

    ss

    ds

    dKP

    072242.3912 23 sss

  • 7/31/2019 Chapter 6 Part a Slides

    37/44

    Root loci with KI/KP= 10, KPvaries

  • 7/31/2019 Chapter 6 Part a Slides

    38/44

    Assume we wish to have a relative damping ratio of 0.707

    From the root loci, KP= 0.08 and KI= 0.8

    At the design point, the three characteristic equation roots are

    at

    s = -10.605 -175.3 + j175.4 and -175.3 j175.4

    Relationship between complex conjugate poles, and n

    Consider a pair of complex conjugate poles given by

    Roots =

    0222 nnss

    2

    222

    12

    442

    nn

    nnnj

  • 7/31/2019 Chapter 6 Part a Slides

    39/44

    Table below gives the attributes of the unit step responses of

    the system with PI control for various values ofKI/KP, with KP=

    0.08.

    KI/ KP KI KP Maximum overshoot

    (%)

    tr (s) ts (s)

    0 0 1.00 52.7 0.00135 0.015

    20 1.60 0.08 15.16 0.0074 0.049

    10 0.80 0.08 9.93 0.0078 0.0294

    5 0.40 0.08 7.17 0.0080 0.023

    2 0.16 0.08 5.47 0.0083 0.0194

    1 0.08 0.08 4.89 0.0084 0.0114

    0.5 0.04 0.08 4.61 0.0084 0.0114

    0.1 0.008 0.08 4.38 0.0084 0.0115

  • 7/31/2019 Chapter 6 Part a Slides

    40/44

    Unit step responses of the system in Example 6.2 with PI control

  • 7/31/2019 Chapter 6 Part a Slides

    41/44

    A process has a transfer function of

    The process is to be controlled in closed loop using

    a PI controller. Design the controller such that the

    steady-state error in response to a ramp input is

    10% of the magnitude of the ramp. The closed-

    loop zero should be placed at 10.

    5

    1)(

    s

    sGP

  • 7/31/2019 Chapter 6 Part a Slides

    42/44

    Design with PID Controller

    We can regard design of controllers as a filter design problem PD controller => High-pass filter

    PI controller => Low-pass filter

    To improve both the ess(which is achieved using PI controller)and transient response (which is achieved using PD controller)

    independently, a PID controller can be used PID controller => band-attenuate filter

    Transfer function of the PID controller:

    s

    zszsK

    s

    KsKsKsK

    s

    KKsG

    leadlagIPD

    D

    I

    pC

    ))(()(

    2

    dtde

    KdteKeKu DIp

  • 7/31/2019 Chapter 6 Part a Slides

    43/44

    Bode plot for PID controller with KP=KI=KD= 1

  • 7/31/2019 Chapter 6 Part a Slides

    44/44

    When designing a PID controller for a given system, followthe steps shown below to obtain a desired response:

    Obtain an open-loop response and determine what

    needs to be improved

    Add a proportional control to improve the rise time

    Add a derivative control to improve the overshoot

    Add an integral control to eliminate the steady-state

    error

    Adjust each ofKP, KIand KDuntil you obtain a desired

    overall response