REPORT Contact person Date Reference Page
Alar Just 2015-12-04 5P07616-02 1 (18) Wood Building Technology +46 10 516 62 42 [email protected]
Staffan Wedekull Wekla AB Fabriksgatan 38 41251 Göteborg
Charring analysis for timber frame assemblies with cellulose cavity insulation and Aquastone board (1 appendix)
General
This report is a result of non-loaded model scale fire test with different beam configurations insulated with cellulose fiber insulation TT Original from Svenska Termoträ AB and covered by Aquastone board from Wekla AB on the fire exposed side.
Model scale test was made on 20th of October 2015 in a model furnace at SP Wood Building Technology in Stockholm.
The results of the fire test together with analysis is given in this report. Charring scenario of timber beams is analyzed.
This report is confidential. The publishing of the results is allowed only with permission by Svenska Termoträ AB and Wekla AB.
Reference number
5P07616-02
Internal test number of SP Wood Technology´s model scale test furnace: 105
SP Technical Research Institute of Sweden Postal address Office location Phone / Fax / E-mail This document may not be reproduced other than in full, except with the SP Box 5609 SE-114 86 STOCKHOLM Sweden
Drottn Kristinas väg 67 SE-114 28 STOCKHOLM
+46 10 516 50 00 +46 8 10 80 81 [email protected]
prior written approval of SP.
REPORT Date Reference Page
2 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
1 Introduction
TT ORIGINAL is a cellulose fibre insulation.
Non-load bearing floor test was conducted at the model scale furnace of SP Wood Building Technology in Stockholm.
A test was sponsored by Wekla AB.
The scope of the presented test was to investigate the effect of TT ORIGINAL and Aquastone board on charring of studs and joists in timber frame assemblies.
This study is a pre-study for the research programme Väx Med Skogen initiated by Svenska Termoträ AB.
2 Materials
For the test specimens timber graded to C24 was used. Cellulose fibre insulation and magnesium board were used to investigate the performance of the insulation material and its coaction with the timber beams in the protection phase before failure of the cladding.
All specimens were built at SP Wood Building Technology and conditioned in a controlled climate chamber at 20 °C and 65% RH before the fire tests.
2.1 Timber
Four timber beams with different cross-sections were tested in the specimen.
Rectangular sections 45x150 mm and 45x137,5 mm.
I-beams with heights 150 mm and 137,5 mm.
See Figure 6 to Figure 10 for the layout and measures for the beams.
Timber with strength grade C24 was used.
2.2 Insulation
Tests were done with cavity insulation of TT Original with a nominal density of 30 kg/m3.
The insulation material was manufactured and installed by blowing to the test specimen by Svenska Termoträ AB.
2.3 Boards, fasteners and additional material
Wekla Aquastone® boards with thickness 9 mm were used. Density of the board was measured 953 kg/m3. Board consists of magnesiumoxide, sulphate, silicate and EPS according to the producer (www.wekla.com).
Self-drilling screws with lengths 55 mm and a nominal diameter of 3,0 mm were used to fasten boards to the test specimens. Distance between the screws was 300 mm.
REPORT Date Reference Page
3 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Wooden particle board with thickness of 19 mm was used on the unexposed side.
To keep the specimens as air-tight as possible an aluminium tape was attached in the joints at the non-exposed side as well as on the sides of the specimens.
For temperature measurements different types of thermocouples type K were used. Crimped junctions with a contact length of about 3 mm were used for internal temperature measurements while the length was about 5 mm for measurements of the non-exposed surface of the gypsum plasterboard on the fire exposed side. For measurements at the non-exposed surface thermocouples according EN 1363-1 were used.
3 Fire test TT1C
3.1 General
Fire test was conducted at model scale furnace of SP Wood Building Technology. Test was done to study the influence of the insulation material and the cladding on the charring of a timber member.
Non-loaded test was performed with horizontal test specimen with outer dimensions 1,2 x 1,2 m. Fire exposed surface was 1,0 x 1,0 m.
The aim of the non-loaded tests was to measure charring at protected and unprotected phase with different beam configurations.
Figure 1. Building of test specimen. Insulation installed.
REPORT Date Reference Page
4 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Figure 2. Test specimen placed on the furnace. Unexposed side.
Figure 3. Test specimen placed on the furnace. Exposed side.
REPORT Date Reference Page
5 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
The fire exposure was started and the temperature in the furnace was increased following the standard fire temperature-time curve according to ISO 834. Recorded data for furnace temperature and pressure can be found in Clause 3.3. The recorded temperature-time curves during the tests can be found in Figure 17.
Test time was 60 minutes. After that the burners were turned off, the specimen removed from the furnace and the fire was extinguished with water. The time elapsed from turning off the burners, breaking the boards and extinguishing the fire was around 7 minutes.
Figure 4. Plan of test specimen.
REPORT Date Reference Page
6 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Figure 5. Cross-section of test specimen.
3.2 Location of the thermocouples
All thermocouples were type K. Thermocouples were set in the loaded timber members in different arrangements: The holes (depth 23 mm) for the wires were drilled from and perpendicular to the wide side of the member. Thermocouple wires were crimped (twisted length 3 mm) and tested for contact before inserting.
A number of thermocouples were also placed on the sides of cross-section to measure the recession of the insulation.
A B TC 30
TC 33 C D
TC 27 TC 28 TC 29
Figure 6. Cross-section of test specimen. Definition of beams. Location of thermocouples.
TC 31 TC 32 15
0
REPORT Date Reference Page
7 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
TC 11 TC 13
TC 10 TC 12
TC 9 TC 8
45
A
TC 7
TC 6
Figure 7. Location of thermocouples of beam A.
B
Figure 8. Location of thermocouples of beam B.
TC 4
TC 3 TC 2 TC 1
TC 5
45
100
100
50
50
6mm
18
mm
6m
m
REPORT Date Reference Page
8 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
18
TC 17
TC 16 TC 15 TC 14
TC
TC 1
47
TC 26
TC 25
TC 22 TC 21
TC 24
TC 23
47
C
TC 20
9
Figure 9. Location of thermocouples of beam C.
D
Figure 10. Location of thermocouples of beam D.
116m
m
103m
m
47
47
18m
m
6mm
6m
m
REPORT Date Reference Page
9 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
3.3 Furnace data
Furnace temperature and pressure during the fir test are presented in Figure 11 and Figure 12.
1100 1000 900 800 700 600 500 400 300 200 100
0
TT1C
0 10 20 30 40 50 60
t [min] Figure 11.Furnace temperature.
40
35
30
25
20
15
10
5
0 0 10 20 30 40 50 60
t [min] Figure 12.Furnace pressure.
TT1C
T [°C
] p
[Pa]
REPORT Date Reference Page
10 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
3.4 Observations
The Wekla Aquastone board did not fall down during the entire test. There was a crack observed that appeared on 24th minute. See also Figure 14
After removing the board when extinguishing, the insulation was observed to be on place and the colour of the insulation was black.
Figure 13. Test specimen mounted on the furnace. Fire exposed side.
Figure 14. Specimen after removing from the furnace.
REPORT Date Reference Page
11 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Figure 15. Test specimen after removing of board.
Figure 16. Test specimen after removing of board.
REPORT Date Reference Page
12 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
3.5 Temperatures
Temperatures measured in the specimen during the fire test can be found on Figure 17 and Figure 18.
1100 1000 900 800 700 600 500 400 300 200 100
0
TC 01 TC 02
TT1C TC 03 TC 04 TC 05 TC 06 TC 07 TC 08
TC 09 TC 10 TC 11 TC 12
TC 13 TC 14 TC 15 TC 16
TC 17 TC 18
TC 19 TC 20 TC 21 TC 22
TC 23 TC 24 TC 25 TC 26
TC 27 TC 28
TC 29 TC 30 TC 31 TC 32
TC 33 0 10 20 30 40 50 60
t [min]
Figure 17.All thermocouple measurements.
1100 1000 900 800 700 600 500 400 300 200 100
0
TT1C TC 27 TC 28
TC 29
TC 30
TC 31
TC 32
TC 33
0 10 20 30 40 50 60
t [min]
Figure 18. Temperatures measured by TC 27 to TC 33.
T [°C
] T
[°C]
REPORT Date Reference Page
13 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
4 Analyse
4.1 Start time of charring
The start time of charring of the beams is given in Table 1.
Beams B and D had two protective layers for wood – Aquastone board and stripe of gypsum plasterboard, Type A with thickness 12,5 mm.
Table 1. Start times of charring and failure times.
Beam Start time of charring
tch
[min]
A 14,3.
B 48,8
C 15,3
D 47,7
The start of charring time is measured by thermocouples.
4.2 Residual cross-sections
After the fire test was terminated the specimen was removed from the furnace and extinguished within 4 minutes.
The residual cross-sections were cut and the charring depth measured.
See Figure 19 to Figure 23.
REPORT Date Reference Page
14 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Figure 19.Charred beams.
Figure 20.Residual cross-sections from beam A.
D
C
B
A
REPORT Date Reference Page
15 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Figure 21.Residual cross-sections from beam B.
Figure 22.Residual cross-sections from beam C.
REPORT Date Reference Page
16 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Figure 23.Residual cross-sections from beam D.
Table 2. Charring depths and remaining heights of beam cross-sections in the middle of span.
Beam Height of cross- section
Remaining height of cross-section
Charring depth in the middle of cross- section width
h [mm] hfi [mm] dchar,m [mm]
A 150 108 42
B 137,5 127 10,5
C 150 108 42
D 137,5 125 12,5
4.3 Charring rate
The charring rate is measured by thermocouples during the test and by measuring the residual cross-section after the test.
As the temperature for charring is regarded 300°C.
REPORT Date Reference Page
17 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
30
25
20
15
10
5
0 0 15 30 45 60
t [min]
A B C D
Figure 24. Charring of the beams along the vertical axle of the cross-section. Thermocouple measurements.
Table 3. Charring rates.
Beam Charring rate at protected phase, charring depth from 0 to 6 mm
tch<t<tf
[mm/min]
Charring rate at protected phase, charring depth from 6 mm to the final
tch<t<tf
[mm/min]
A 0,58 1,01
B 0,60 3,75
C 0,47 1,12
D 0,76 1,48
4.4 Load-bearing capacity
Load-bearing capacity based on test results are presented in Table 4.
Rough calculations of bearing capacity are added as Annex B.
Beam height is chosen 150 mm for the load-bearing capacity for all beams.
Calculations are made with reduced cross-section method according to the European technical guideline “Fire Safety in Timber Buildings”.
char
ing
dept
h d 3
00 [m
m]
REPORT Date Reference Page
18 (18) 2015-12-04 5P07616-02
SP Technical Research Institute of Sweden
Table 4. Load-bearing capacities for bending Duration of test
Beam 30 min 60 min
M [kNm] M [kNm]
A 2,89 1,58
B 2,73 2,29
C 3,52 0,32
D 3,37 2,49
References [1] EN 1995-1-2:2004 Eurocode 5: Design of timber structures – Part 1-2: General –
Structural fire design. European Standard. European Committee for Standardization, Brussels, 2004.
[2] Fire safety in timber buildings, technical guideline for Europe, SP report 2010:19, Stockholm 2010.
SP Technical Research Institute of Sweden Wood Technology
Performed by Examined by
Alar Just Karin Sandberg
Appendices
Annex 1. Indicative fire resistance calculations
SP Technical Research Institute of Sweden
REPORT Date Reference Page
1 (1) 2015-12-04 5P07616-02
Appendix 1