NYC Department of Education Building Condition Assessment Survey 2018-2019 M615 Architectural Inspection Inspection Type Last Edited Time In InspectionId CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 School: 412 2018-11-29 07:03AM 2019-06-27 04:19PM ARCHITECTURAL - SENIOR 443 2018-11-29 08:44AM 2019-01-14 11:11AM ARCHITECTURAL - ASSOCIATE Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principal(s) Information Principal Name Jaivelle Reed Principal Organization Chelsea Vocational HS- Manhattan Meeting with Principal? Yes Principal Feedback The Principal provided the following comments: 1) The Bell system functionality needs adjustments. 2) The Doors locks need replacement in various locations. Principal Name Isora Bailey Principal Organization NYC iSchool- Manhattan Meeting with Principal? Yes Principal Feedback The Principal provided the following comments: 1) The roof is leaking in various sections and needs to be repaired. 2) The floors are deteriorated and are in need of repairs. 3) The Plumbing throughout the school is deficient and requires improvements. Custodian Was not present Fireman Adam Infante Building Square Footage 83,000 Comments on the Area (Square Feet) N/A Comments on the Stories (Floors) plus Basements 5+B+PH Comments on the Year Built 1905 Comments on the Student Population 912 Comments on the Staff Population 108 Comments on the Number of Classrooms 49 Weather Fair Facade Photo Corner of 6th Ave. and Broome St. - Northwest view Page 1 of 31 Print Date: 7/3/2019 Mobile Validity Version 2.0 (P)

Upload: others

Post on 02-Aug-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Inspection Type Last EditedTime InInspectionId

CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013School:

412 2018-11-29 07:03AM 2019-06-27 04:19PMARCHITECTURAL - SENIOR

443 2018-11-29 08:44AM 2019-01-14 11:11AMARCHITECTURAL - ASSOCIATE

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principal(s) Information

Principal Name Jaivelle Reed

Principal Organization Chelsea Vocational HS- Manhattan

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comments: 1) The Bell

system functionality needs adjustments. 2) The Doors locks need

replacement in various locations.

Principal Name Isora Bailey

Principal Organization NYC iSchool- Manhattan

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comments: 1) The roof is

leaking in various sections and needs to be repaired. 2) The floors

are deteriorated and are in need of repairs. 3) The Plumbing

throughout the school is deficient and requires improvements.

Custodian Was not present

Fireman Adam Infante

Building Square Footage 83,000

Comments on the Area (Square Feet) N/A

Comments on the Stories (Floors) plus Basements 5+B+PH

Comments on the Year Built 1905

Comments on the Student Population 912

Comments on the Staff Population 108

Comments on the Number of Classrooms 49

Weather Fair

Facade Photo

Corner of 6th Ave. and Broome St. - Northwest view

Page 1 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 2: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural InspectionMain Entrance Photo

Facade A ( 6thAve.)

Roof Photo

Roof 1 - North view

Have any Systems/Major Building Components been upgraded? Systems: Limited Foundation Wall flood elimination

Years: 2016

Systems: Limited Roofing replacement (Metal); Limited

Bulkhead repairs; Complete Parapet reconstruction .

Years: 2011

Systems: Limited Roofing replacement, Complete Exterior Door

replacement, Limited Foundation Wall, Exterior

Masonry and Chimney Masonry repairs .

Years: 2010

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Page 2 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 3: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

NoExterior Entrances & Exits

DISTANCE BETWEEN OPEN DOORS < 4'

SADDLE HEIGHT > 1/2"

NoNoExterior H/C Lifts

NoNoExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

NoYesInterior Corridor Doors And Hardware

YesInterior Corridors & Lobbies

NoInterior Elevators

NoInterior Lobby Doors And Hardware

CLEAR OPENING < 32"

NoInterior Ramps

Rooms & Spaces

Art Rooms

Yes NoRoom 502

NOT ON ACCESSIBLE ROUTE

Auditorium

Yes NoFirst floor

NO STAGE ACCESS

NOT ON ACCESSIBLE ROUTE

Cafeteria

Yes NoFirst floor

NOT ON ACCESSIBLE ROUTE

Classrooms

Yes NoNone on Accessible Route

NOT ON ACCESSIBLE ROUTE

Computer Rooms

Yes NoRoom 103, 205, 305, 310, 405

NOT ON ACCESSIBLE ROUTE

NoGymnasium

NoLibrary

Main Office

Yes NoRoom 211 and 5th Floor Common Room

NOT ON ACCESSIBLE ROUTE

NoMulti-purpose Room

Nurse's Office

Yes No5th floor

NOT ON ACCESSIBLE ROUTE

NoPool

Science Lab

Yes No313, 413

NOT ON ACCESSIBLE ROUTE

Toilet Rooms (boys)

Yes NoNone on Accessible Route

NOT ON ACCESSIBLE ROUTE

Toilet Rooms (girls)

Yes NoNone on Accessible Route

Page 3 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 4: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

NOT ON ACCESSIBLE ROUTE

Toilet Rooms (staff)

Yes NoNone on Accessible Route

NOT ON ACCESSIBLE ROUTE

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

InspectedAREAWAY

Instance on AW1-AW8 Inspected

4- Between Fair and PoorInstance Condition

Instance Quantity 8

Instance Quantity Uom EACH

AREAWAY GRATINGS:MAJOR RUSTING / OR BROKENDeficiency

Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 4 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 5: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

AREAWAY

Facade A

Violations No violations recorded

AREAWAY DRAINS:CLOGGEDDeficiency

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade K

Violations No violations recorded

Does not existAWNINGS AND CANOPIES

InspectedCHIMNEY

MasonryMaterial Type(s)

Condition 4- Between Fair and Poor

BRICK:MINOR CRACKS AND SPALLINGDeficiency

Deficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Chimney

Page 5 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 6: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

CHIMNEY

Deficiency Photo 2

Chimney

Violations No violations recorded

InspectedCOPING

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedCORNICE

Condition 1- Good

No deficiencies recordedDeficiency

InspectedDOORS

InspectedDOOR HARDWARE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existEXTERIOR SOFFITS

InspectedEXTERIOR WALLS

MasonryMaterial Type(s)

33,000Replacement Quantity

Replacement Uom S.F.

Instance on All facades Inspected

3- FairInstance Condition

Instance Quantity 33,000

Instance Quantity Uom S.F.

BRICK:OPEN JOINTSDeficiency

Roof Plan Reference

Elevation

Page 6 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 7: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation Reference All facades

600Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPARAPETS

Masonry, MetalMaterial Type(s)

5,000Replacement Quantity

Replacement Uom C.F.

Instance on Facade D,E,G,H,I Inspected

2- Between Good and FairInstance Condition

Instance Quantity 2,000

Instance Quantity Uom CF

No deficiencies recordedDeficiency

Instance on A,B,C,K Inspected

2- Between Good and FairInstance Condition

Instance Quantity 3,000

Instance Quantity Uom CF

No deficiencies recordedDeficiency

Does not existPLAZA DECK

InspectedROOF

InspectedROOFING

Replacement Quantity 19,000

Replacement Uom S.F.

InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOF BARRIER

1- GoodCondition

No deficiencies recordedDeficiency

Does not existROOF CAGE

InspectedROOF FENCE

1- GoodCondition

No deficiencies recordedDeficiency

Does not existROOF HATCH/SMOKE HATCH

InspectedROOFING

Instance on Built-Up:Roof 1 and 2 Inspected

Page 7 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 8: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

3- FairInstance Condition

Instance Quantity 12,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2010

Source of Installation Year Documented

BUILT-UP:ROOFING:LOSS OF GRAVELDeficiency

Deficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL NEW GRAVEL

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1

Violations No violations recorded

Instance on Metal:Roof 3 Inspected

2- Between Good and FairInstance Condition

Instance Quantity 7,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2011

Source of Installation Year Documented

No deficiencies recordedDeficiency

InspectedROOFING DRAINS

4- Between Fair and PoorCondition

DETERIORATEDDeficiency

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

Page 8 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 9: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING DRAINS

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

NW corner of Roof 1

Violations No violations recorded

InspectedSPECIALTIES

InspectedBULKHEAD/PENTHOUSE

3- FairCondition

BULKHEAD/PENTHOUSE DOORS:DETERIORATED DOORDeficiency

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE DOOR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Penthouse 1

Violations No violations recorded

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

InspectedDUNNAGE STEEL

3- FairCondition

MAJOR RUSTINGDeficiency

Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom L.F.

Page 9 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 10: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

ROOF

SPECIALTIES

DUNNAGE STEEL

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1 - Southwest corner

Violations No violations recorded

InspectedROOF/GRAVITY TANK

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existSKYLIGHT/ROOF VENT

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existRAILINGS

InspectedSTAIRS/RAMPS

Condition 5- Poor

CONCRETE:WORN-OUT TREAD/RISER/NOSINGDeficiency

Deficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B

Page 10 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 11: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo 2

Main entrance

Violations No violations recorded

InspectedWINDOWS

17,000Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 3- Fair

RUST - MINORDeficiency

Roof Plan Reference

Elevation

100Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Double Hung:All facades Inspected

4- Between Fair and PoorInstance Condition

Instance Quantity 15,000

Page 11 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 12: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Instance Quantity Uom S.F.

Installation Year 1985

Source of Installation Year Custodial Staff

ALUMINUM - DOUBLE HUNG:INOPERABLE BALANCEDeficiency

Roof Plan Reference

Elevation

Elevation Reference All facades

40Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE BALANCES

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade D

Deficiency Photo 2

Facade A

Violations No violations recorded

Instance on Wood:All Basement Facades Inspected

5- PoorInstance Condition

Instance Quantity 2,000

Instance Quantity Uom S.F.

Installation Year 1905

Source of Installation Year Custodial Staff

WOOD:BROKEN PANEDeficiency

Page 12 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 13: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan Reference

Elevation

Elevation Reference Facade A, B and K

20Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B

Violations No violations recorded

WOOD:DETERIORATEDDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A, B and D

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE WINDOW

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Page 13 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 14: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Deficiency Photo 1

Facade B

Violations M-002-89

INTERIOR Inspected

AUDITORIUM

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

Ceiling

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed H/C Lift

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Does not exist

Fixed Seating

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

5- PoorInstance Condition

DAMAGED/BROKEN/INOPERABLEDeficiency

Seats C/1Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Seat C/1

Violations No violations recorded

DAMAGED/BROKEN/INOPERABLEDeficiency

Seats B/22, C/8, E/7, 9, 11, 15, F/3, 23Deficiency Location/Instance

11Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

Page 14 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 15: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Fixed Seating

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Seat E/9

Violations No violations recorded

IMPROPERLY ANCHOREDDeficiency

Seats G/1, 3, H/1, 3, 5, 7, 9Deficiency Location/Instance

7Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Seat G/1

Violations No violations recorded

Floor Finish

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Does not exist

Stage

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

Stage

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtain Rigging

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Does not exist

Stage Curtains

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Does not exist

Walls

Page 15 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 16: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Walls

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats

288)

Does not exist

CAFETERIA

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on 1st Floor Does not exist

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor Does not exist

Stage

Instance on 1st Floor Does not exist

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Room 514Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 514

Page 16 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 17: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Violations No violations recorded

InspectedDoor(s)

Condition 3- Fair

WOOD:DETERIORATED DOORDeficiency

Rooms 305, 211, 213Deficiency Location/Instance

3Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 305

Violations No violations recorded

METAL CLAD WOOD:DETERIORATED DOORDeficiency

Room 101Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 101

Violations No violations recorded

InspectedFloor Finish

Condition 5- Poor

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Main Entrance Lobby, Corridor near Rooms 210, 508, Rooms

409, 506and other locations

Deficiency Location/Instance

6,700Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 17 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 18: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo 1

Main Entrance Lobby

Violations No violations recorded

VINYL TILES:DETERIORATED SUBSTRATEDeficiency

Rooms 314, 413 Corridor near Rooms 103, 308Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 413

Violations No violations recorded

Does not existSpecialties

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existGYMNASIUM

InspectedINTERIOR DOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

DETERIORATED/TORN-OUT/MISSINGDeficiency

Stair C/5Deficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 18 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 19: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

INTERIOR GUARDS

Stair C/5

Violations No violations recorded

KITCHEN

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

QUARRY TILE:BROKEN/MISSING TILESDeficiency

North near EntranceDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

North near Entrance

Violations No violations recorded

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Near Sinks, Entrance, Northeast corner of RoomDeficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Sinks

Violations No violations recorded

Does not existLIBRARY

Page 19 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 20: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

Does not existLOCKER ROOM

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

SCIENCE DEMO ROOM

Instance on Room 514 Inspected

YesAlternative Use

Instance on Room 314 Inspected

NoAlternative Use

Instance on Room 414 Inspected

NoAlternative Use

Instance on Room 511 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 514 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 314 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 414 Inspected

2- Between Good and FairInstance Condition

CABINETRY:MISSING/DAMAGEDDeficiency

Room 414Deficiency Location/Instance

6Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 414

Violations No violations recorded

Instance on Room 511 Inspected

2- Between Good and FairInstance Condition

CABINETRY:MISSING/DAMAGEDDeficiency

Room 511Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 20 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 21: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

SCIENCE DEMO ROOM

Fixed Equipment

Deficiency Photo 1

Room 512

Violations No violations recorded

SCIENCE LAB

Instance on Room 313 Inspected

YesAlternative Use

Instance on Room 413 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 313 Inspected

5- PoorInstance Condition

CABINETRY:MISSING/DAMAGEDDeficiency

South, East, West, North of RoomDeficiency Location/Instance

36Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

South of Room

Violations No violations recorded

Instance on Room 413 Inspected

5- PoorInstance Condition

CABINETRY:MISSING/DAMAGEDDeficiency

North, West, South, East of RoomDeficiency Location/Instance

46Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 21 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 22: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

SCIENCE LAB

Fixed Equipment

West of Room

Violations No violations recorded

SCIENCE PREP ROOM

Instance on Room 411A Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 411A Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existSHOWER ROOM

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? 1

InspectedCeiling

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Stair C/5Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/5

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPartition

Condition 3- Fair

METAL FRAME:DAMAGED/DETERIORATEDDeficiency

Stairs A/5, C/5, E/4, G/2, 3 and othersDeficiency Location/Instance

22Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair A/5

Page 22 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 23: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Partition

Violations No violations recorded

METAL PANEL:DAMAGED/DETERIORATEDDeficiency

Stairs AB/2, 3, CD/2, 5, EF/4 and othersDeficiency Location/Instance

180Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair EF/4

Violations No violations recorded

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 3- Fair

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Stairs A/2, C/1, 5, E/2, G/ 3 and other locationsDeficiency Location/Instance

420Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/5

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Stair C/5Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 23 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 24: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo 1

Stair C/5

Violations No violations recorded

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 4- Between Fair and Poor

STEEL COLUMNS/BEAMS:DETERIORATED/MISSING

SPRAY-ON FIREPROOFING

Deficiency

All BasementDeficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Boiler Room

Violations No violations recorded

InspectedFLOOR STRUCTURE

Condition 4- Between Fair and Poor

CONCRETE SLAB ON GRADE:WATER INFILTRATION IN

ELECTRICAL PANEL ROOM

Deficiency

Electrical roomDeficiency Location/Instance

60Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

PRIORITY 5Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Electrical Room

Violations 35317137Y

CLAY TILE:PLASTER MISSINGDeficiency

Page 24 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 25: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

BasementDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Boiler room

Violations No violations recorded

InspectedFOUNDATION WALLS

Material Type(s) Masonry

Condition 4- Between Fair and Poor

BRICK:CRACKED/SPALLEDDeficiency

All BasementDeficiency Location/Instance

300Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Basement corridor

Deficiency Photo 2

Basement storage

Violations No violations recorded

BRICK:WATER INFILTRATION IN ELECTRICAL PANEL

ROOM

Deficiency

Electrical roomDeficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Page 25 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 26: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo 1

Electrical room

Violations 35317137Y

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedVAULTS-BUNKERS

InspectedFoundation Walls

3- FairCondition

CRACKS, SPALLINGDeficiency

VaultDeficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Vault

Violations No violations recorded

InspectedSlab Structure

3- FairCondition

CONCRETE SLAB ON GRADE:WATER INFILTRATION IN

ELECTRICAL PANEL ROOM

Deficiency

Electrical roomDeficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

PRIORITY 5Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Electrical room

Page 26 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 27: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Slab Structure

Violations 35317137Y

InspectedVault/Ash Hoist Doors and Framing

4- Between Fair and PoorCondition

DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS

AND FRAMING

Deficiency

Vault/AshDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Vault / Ash

Violations No violations recorded

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 5- Poor

WOOD:DETERIORATED DOORDeficiency

Room 203ADeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 203A

Violations No violations recorded

WOOD:DAMAGED LOUVERDeficiency

1st Floor - MenDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 27 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 28: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STAFF

Door(s)

Deficiency Photo 1

1st Floor - Men

Violations No violations recorded

InspectedFloor Finish

Condition 3- Fair

CERAMIC TILE:BROKEN/MISSING TILESDeficiency

1st Floor - MenDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

1st Floor - Men

Violations No violations recorded

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Room 515Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 515

Violations No violations recorded

InspectedTOILET ROOMS - STUDENTS

Page 28 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 29: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 5- Poor

METAL CLAD WOOD:DETERIORATED DOORDeficiency

Room 406BDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 406B

Violations No violations recorded

WOOD:DAMAGED LOUVERDeficiency

1st Floor- BoysDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

1st Floor- Boys

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

Page 29 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 30: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

SITE

Does not existCONTAINERIZATION

Does not existDRAINAGE SYSTEM FOR ASPHALT

Does not existDRAINAGE SYSTEM FOR CONCRETE

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 3- Fair

WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency

Along Dominick StreetDeficiency Location/Instance

120Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Dominick Street

Violations No violations recorded

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along 6th Avenue, Along Broome StreetDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along 6th Avenue

Violations No violations recorded

InspectedPavers

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existSite Sidewalks & Walkways

InspectedStudent Non-Use

Gravel Exists? No

Does not existAsphalt

Page 30 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 31: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE …School: CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013 412 ARCHITECTURAL - SENIOR 2018-11-29 07:03AM 2019-06-27

NYC Department of Education

Building Condition Assessment Survey 2018-2019

M615Architectural Inspection

Question Response

SITE

PAVING

Student Non-Use

InspectedConcrete

2- Between Good and FairCondition

CRACKS - MAJORDeficiency

Along Dominick StreetDeficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Dominick Street

Violations No violations recorded

Does not existPavers

Does not existStudent Use

Does not existPLAYGROUNDS

Does not existPLAYING SURFACE

Does not existRETAINING WALLS

Does not existSEATING

Does not existSITE WALLS (NOT RETAINING WALLS)

Does not existSTAIRS/RAMPS: EXTERIOR

Page 31 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)