NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Inspection Type Last EditedTime InInspectionId
CHELSEA VOC HS - MANHATTAN, 131 AVE OF THE AMERICAS, MANHATTAN, NY, 10013School:
412 2018-11-29 07:03AM 2019-06-27 04:19PMARCHITECTURAL - SENIOR
443 2018-11-29 08:44AM 2019-01-14 11:11AMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Jaivelle Reed
Principal Organization Chelsea Vocational HS- Manhattan
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comments: 1) The Bell
system functionality needs adjustments. 2) The Doors locks need
replacement in various locations.
Principal Name Isora Bailey
Principal Organization NYC iSchool- Manhattan
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comments: 1) The roof is
leaking in various sections and needs to be repaired. 2) The floors
are deteriorated and are in need of repairs. 3) The Plumbing
throughout the school is deficient and requires improvements.
Custodian Was not present
Fireman Adam Infante
Building Square Footage 83,000
Comments on the Area (Square Feet) N/A
Comments on the Stories (Floors) plus Basements 5+B+PH
Comments on the Year Built 1905
Comments on the Student Population 912
Comments on the Staff Population 108
Comments on the Number of Classrooms 49
Weather Fair
Facade Photo
Corner of 6th Ave. and Broome St. - Northwest view
Page 1 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural InspectionMain Entrance Photo
Facade A ( 6thAve.)
Roof Photo
Roof 1 - North view
Have any Systems/Major Building Components been upgraded? Systems: Limited Foundation Wall flood elimination
Years: 2016
Systems: Limited Roofing replacement (Metal); Limited
Bulkhead repairs; Complete Parapet reconstruction .
Years: 2011
Systems: Limited Roofing replacement, Complete Exterior Door
replacement, Limited Foundation Wall, Exterior
Masonry and Chimney Masonry repairs .
Years: 2010
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Page 2 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
NoExterior Entrances & Exits
DISTANCE BETWEEN OPEN DOORS < 4'
SADDLE HEIGHT > 1/2"
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
NoInterior Elevators
NoInterior Lobby Doors And Hardware
CLEAR OPENING < 32"
NoInterior Ramps
Rooms & Spaces
Art Rooms
Yes NoRoom 502
NOT ON ACCESSIBLE ROUTE
Auditorium
Yes NoFirst floor
NO STAGE ACCESS
NOT ON ACCESSIBLE ROUTE
Cafeteria
Yes NoFirst floor
NOT ON ACCESSIBLE ROUTE
Classrooms
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Computer Rooms
Yes NoRoom 103, 205, 305, 310, 405
NOT ON ACCESSIBLE ROUTE
NoGymnasium
NoLibrary
Main Office
Yes NoRoom 211 and 5th Floor Common Room
NOT ON ACCESSIBLE ROUTE
NoMulti-purpose Room
Nurse's Office
Yes No5th floor
NOT ON ACCESSIBLE ROUTE
NoPool
Science Lab
Yes No313, 413
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (boys)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (girls)
Yes NoNone on Accessible Route
Page 3 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (staff)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on AW1-AW8 Inspected
4- Between Fair and PoorInstance Condition
Instance Quantity 8
Instance Quantity Uom EACH
AREAWAY GRATINGS:MAJOR RUSTING / OR BROKENDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 4 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
AREAWAY
Facade A
Violations No violations recorded
AREAWAY DRAINS:CLOGGEDDeficiency
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade K
Violations No violations recorded
Does not existAWNINGS AND CANOPIES
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 4- Between Fair and Poor
BRICK:MINOR CRACKS AND SPALLINGDeficiency
Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Chimney
Page 5 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
CHIMNEY
Deficiency Photo 2
Chimney
Violations No violations recorded
InspectedCOPING
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCORNICE
Condition 1- Good
No deficiencies recordedDeficiency
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existEXTERIOR SOFFITS
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
33,000Replacement Quantity
Replacement Uom S.F.
Instance on All facades Inspected
3- FairInstance Condition
Instance Quantity 33,000
Instance Quantity Uom S.F.
BRICK:OPEN JOINTSDeficiency
Roof Plan Reference
Elevation
Page 6 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation Reference All facades
600Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
Masonry, MetalMaterial Type(s)
5,000Replacement Quantity
Replacement Uom C.F.
Instance on Facade D,E,G,H,I Inspected
2- Between Good and FairInstance Condition
Instance Quantity 2,000
Instance Quantity Uom CF
No deficiencies recordedDeficiency
Instance on A,B,C,K Inspected
2- Between Good and FairInstance Condition
Instance Quantity 3,000
Instance Quantity Uom CF
No deficiencies recordedDeficiency
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 19,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
1- GoodCondition
No deficiencies recordedDeficiency
Does not existROOF CAGE
InspectedROOF FENCE
1- GoodCondition
No deficiencies recordedDeficiency
Does not existROOF HATCH/SMOKE HATCH
InspectedROOFING
Instance on Built-Up:Roof 1 and 2 Inspected
Page 7 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
3- FairInstance Condition
Instance Quantity 12,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2010
Source of Installation Year Documented
BUILT-UP:ROOFING:LOSS OF GRAVELDeficiency
Deficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL NEW GRAVEL
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Violations No violations recorded
Instance on Metal:Roof 3 Inspected
2- Between Good and FairInstance Condition
Instance Quantity 7,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2011
Source of Installation Year Documented
No deficiencies recordedDeficiency
InspectedROOFING DRAINS
4- Between Fair and PoorCondition
DETERIORATEDDeficiency
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
Page 8 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING DRAINS
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
NW corner of Roof 1
Violations No violations recorded
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
3- FairCondition
BULKHEAD/PENTHOUSE DOORS:DETERIORATED DOORDeficiency
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE DOOR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Penthouse 1
Violations No violations recorded
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
InspectedDUNNAGE STEEL
3- FairCondition
MAJOR RUSTINGDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom L.F.
Page 9 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
DUNNAGE STEEL
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1 - Southwest corner
Violations No violations recorded
InspectedROOF/GRAVITY TANK
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existRAILINGS
InspectedSTAIRS/RAMPS
Condition 5- Poor
CONCRETE:WORN-OUT TREAD/RISER/NOSINGDeficiency
Deficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Page 10 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo 2
Main entrance
Violations No violations recorded
InspectedWINDOWS
17,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 3- Fair
RUST - MINORDeficiency
Roof Plan Reference
Elevation
100Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Double Hung:All facades Inspected
4- Between Fair and PoorInstance Condition
Instance Quantity 15,000
Page 11 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Instance Quantity Uom S.F.
Installation Year 1985
Source of Installation Year Custodial Staff
ALUMINUM - DOUBLE HUNG:INOPERABLE BALANCEDeficiency
Roof Plan Reference
Elevation
Elevation Reference All facades
40Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE BALANCES
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade D
Deficiency Photo 2
Facade A
Violations No violations recorded
Instance on Wood:All Basement Facades Inspected
5- PoorInstance Condition
Instance Quantity 2,000
Instance Quantity Uom S.F.
Installation Year 1905
Source of Installation Year Custodial Staff
WOOD:BROKEN PANEDeficiency
Page 12 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan Reference
Elevation
Elevation Reference Facade A, B and K
20Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Violations No violations recorded
WOOD:DETERIORATEDDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A, B and D
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE WINDOW
PRIORITY 4Urgency of Action
LEVEL 4Purpose of Action
Page 13 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Deficiency Photo 1
Facade B
Violations M-002-89
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
Ceiling
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Does not exist
Fixed Seating
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
5- PoorInstance Condition
DAMAGED/BROKEN/INOPERABLEDeficiency
Seats C/1Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Seat C/1
Violations No violations recorded
DAMAGED/BROKEN/INOPERABLEDeficiency
Seats B/22, C/8, E/7, 9, 11, 15, F/3, 23Deficiency Location/Instance
11Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
Page 14 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Fixed Seating
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Seat E/9
Violations No violations recorded
IMPROPERLY ANCHOREDDeficiency
Seats G/1, 3, H/1, 3, 5, 7, 9Deficiency Location/Instance
7Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Seat G/1
Violations No violations recorded
Floor Finish
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Does not exist
Stage
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
Stage
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Does not exist
Stage Curtains
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Does not exist
Walls
Page 15 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Walls
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor (Occupancy 540 Seats - Actual Existing Seats
288)
Does not exist
CAFETERIA
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Does not exist
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Room 514Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 514
Page 16 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Violations No violations recorded
InspectedDoor(s)
Condition 3- Fair
WOOD:DETERIORATED DOORDeficiency
Rooms 305, 211, 213Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 305
Violations No violations recorded
METAL CLAD WOOD:DETERIORATED DOORDeficiency
Room 101Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 101
Violations No violations recorded
InspectedFloor Finish
Condition 5- Poor
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Main Entrance Lobby, Corridor near Rooms 210, 508, Rooms
409, 506and other locations
Deficiency Location/Instance
6,700Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 17 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo 1
Main Entrance Lobby
Violations No violations recorded
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Rooms 314, 413 Corridor near Rooms 103, 308Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 413
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existGYMNASIUM
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
DETERIORATED/TORN-OUT/MISSINGDeficiency
Stair C/5Deficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 18 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
INTERIOR GUARDS
Stair C/5
Violations No violations recorded
KITCHEN
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
QUARRY TILE:BROKEN/MISSING TILESDeficiency
North near EntranceDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
North near Entrance
Violations No violations recorded
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Near Sinks, Entrance, Northeast corner of RoomDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Sinks
Violations No violations recorded
Does not existLIBRARY
Page 19 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
Does not existLOCKER ROOM
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
SCIENCE DEMO ROOM
Instance on Room 514 Inspected
YesAlternative Use
Instance on Room 314 Inspected
NoAlternative Use
Instance on Room 414 Inspected
NoAlternative Use
Instance on Room 511 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 514 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 314 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 414 Inspected
2- Between Good and FairInstance Condition
CABINETRY:MISSING/DAMAGEDDeficiency
Room 414Deficiency Location/Instance
6Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 414
Violations No violations recorded
Instance on Room 511 Inspected
2- Between Good and FairInstance Condition
CABINETRY:MISSING/DAMAGEDDeficiency
Room 511Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 20 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
SCIENCE DEMO ROOM
Fixed Equipment
Deficiency Photo 1
Room 512
Violations No violations recorded
SCIENCE LAB
Instance on Room 313 Inspected
YesAlternative Use
Instance on Room 413 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 313 Inspected
5- PoorInstance Condition
CABINETRY:MISSING/DAMAGEDDeficiency
South, East, West, North of RoomDeficiency Location/Instance
36Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South of Room
Violations No violations recorded
Instance on Room 413 Inspected
5- PoorInstance Condition
CABINETRY:MISSING/DAMAGEDDeficiency
North, West, South, East of RoomDeficiency Location/Instance
46Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 21 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
SCIENCE LAB
Fixed Equipment
West of Room
Violations No violations recorded
SCIENCE PREP ROOM
Instance on Room 411A Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 411A Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Stair C/5Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/5
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPartition
Condition 3- Fair
METAL FRAME:DAMAGED/DETERIORATEDDeficiency
Stairs A/5, C/5, E/4, G/2, 3 and othersDeficiency Location/Instance
22Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/5
Page 22 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Partition
Violations No violations recorded
METAL PANEL:DAMAGED/DETERIORATEDDeficiency
Stairs AB/2, 3, CD/2, 5, EF/4 and othersDeficiency Location/Instance
180Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair EF/4
Violations No violations recorded
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 3- Fair
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Stairs A/2, C/1, 5, E/2, G/ 3 and other locationsDeficiency Location/Instance
420Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/5
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Stair C/5Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 23 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo 1
Stair C/5
Violations No violations recorded
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 4- Between Fair and Poor
STEEL COLUMNS/BEAMS:DETERIORATED/MISSING
SPRAY-ON FIREPROOFING
Deficiency
All BasementDeficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Boiler Room
Violations No violations recorded
InspectedFLOOR STRUCTURE
Condition 4- Between Fair and Poor
CONCRETE SLAB ON GRADE:WATER INFILTRATION IN
ELECTRICAL PANEL ROOM
Deficiency
Electrical roomDeficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Electrical Room
Violations 35317137Y
CLAY TILE:PLASTER MISSINGDeficiency
Page 24 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
BasementDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Boiler room
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Masonry
Condition 4- Between Fair and Poor
BRICK:CRACKED/SPALLEDDeficiency
All BasementDeficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Basement corridor
Deficiency Photo 2
Basement storage
Violations No violations recorded
BRICK:WATER INFILTRATION IN ELECTRICAL PANEL
ROOM
Deficiency
Electrical roomDeficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Page 25 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo 1
Electrical room
Violations 35317137Y
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedVAULTS-BUNKERS
InspectedFoundation Walls
3- FairCondition
CRACKS, SPALLINGDeficiency
VaultDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Vault
Violations No violations recorded
InspectedSlab Structure
3- FairCondition
CONCRETE SLAB ON GRADE:WATER INFILTRATION IN
ELECTRICAL PANEL ROOM
Deficiency
Electrical roomDeficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Electrical room
Page 26 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Slab Structure
Violations 35317137Y
InspectedVault/Ash Hoist Doors and Framing
4- Between Fair and PoorCondition
DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS
AND FRAMING
Deficiency
Vault/AshDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Vault / Ash
Violations No violations recorded
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 5- Poor
WOOD:DETERIORATED DOORDeficiency
Room 203ADeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 203A
Violations No violations recorded
WOOD:DAMAGED LOUVERDeficiency
1st Floor - MenDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 27 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s)
Deficiency Photo 1
1st Floor - Men
Violations No violations recorded
InspectedFloor Finish
Condition 3- Fair
CERAMIC TILE:BROKEN/MISSING TILESDeficiency
1st Floor - MenDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
1st Floor - Men
Violations No violations recorded
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Room 515Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 515
Violations No violations recorded
InspectedTOILET ROOMS - STUDENTS
Page 28 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 5- Poor
METAL CLAD WOOD:DETERIORATED DOORDeficiency
Room 406BDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 406B
Violations No violations recorded
WOOD:DAMAGED LOUVERDeficiency
1st Floor- BoysDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
1st Floor- Boys
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Page 29 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
SITE
Does not existCONTAINERIZATION
Does not existDRAINAGE SYSTEM FOR ASPHALT
Does not existDRAINAGE SYSTEM FOR CONCRETE
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 3- Fair
WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency
Along Dominick StreetDeficiency Location/Instance
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Dominick Street
Violations No violations recorded
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along 6th Avenue, Along Broome StreetDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along 6th Avenue
Violations No violations recorded
InspectedPavers
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existSite Sidewalks & Walkways
InspectedStudent Non-Use
Gravel Exists? No
Does not existAsphalt
Page 30 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M615Architectural Inspection
Question Response
SITE
PAVING
Student Non-Use
InspectedConcrete
2- Between Good and FairCondition
CRACKS - MAJORDeficiency
Along Dominick StreetDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Dominick Street
Violations No violations recorded
Does not existPavers
Does not existStudent Use
Does not existPLAYGROUNDS
Does not existPLAYING SURFACE
Does not existRETAINING WALLS
Does not existSEATING
Does not existSITE WALLS (NOT RETAINING WALLS)
Does not existSTAIRS/RAMPS: EXTERIOR
Page 31 of 31 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)