chemical feed system operation and design considerations. awwa pnws - chem presentation...chemical...

40
PNWS – AWWA MAY 7, 2014 EUGENE, OREGON Chemical Feed System Operation and Design Considerations Kevin Batridge – Lake Oswego Tigard Water Partnership Austin Peters – MWH Global

Upload: others

Post on 22-May-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

PNWS – AWWAMAY 7, 2014

EUGENE, OREGON

Chemical Feed System Operation and Design 

ConsiderationsKevin Batridge – Lake Oswego Tigard Water Partnership

Austin Peters – MWH Global

Page 2: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

AgendaChemical Delivery and Storage

Chemical Delivery 

Bulk Storage Considerations

Chemical Containment

Dry Chemicals & Polymers

Chemical  Metering and Delivery

Chemical Metering Pumps

Chemical Feed Piping

Feed Piping Leak Containment 

Chemical Feed Optimization 

Inventory Measurement

Chemical Feed Control Strategies

Dose Optimization

Page 3: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Pumps

Instrumentation

Delivery and Storage

Page 4: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Delivery and Storage Challenges

Truck access Indoor vs. outdoor installation Acid and base general layout Tank materials Containment Tank Maintenance

Delivery and Storage

What are some other chemical delivery and storage challenges?

Page 5: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk Tank Delivery Truck Routes Truck Site Access Commercial Vs. Residential 

environment Supplier Availability Their Specific RequirementsOrder Lead time

Delivery and Storage

What are some other chemical delivery and storage challenges?

Page 6: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk Tank Delivery Continued

Traffic patterns Covered truck pad Spill containment

and management

Delivery

Page 7: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk Tank Delivery Offloading

Bulk tank volumes  Overfill protection Freeze protection Truck Sampling

Delivery

Page 8: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk Tank Delivery Safety

Eyewashes and showers

Tempered water Remote or local 

alarming  Fire Code Requirements

Lighting

Delivery

What PPE is required during chemical deliveries?

Page 9: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Delivery

Page 10: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Delivery

Page 11: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk Tank Location

Indoor Vs. Outdoor CorrosionInsulation/Temperature ControlAppropriate WeatherCost

Storage

Page 12: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk Tank Material

Material Compatibility & LongevityFRP, HDPE, LDPE, lined steel Indoor vs. Outdoor locationsCapital and Maintenance Cost.

Storage

Which materials have worked best in your experience?

Page 13: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk Tank Inspection & Maintenance

Top or side entry Access catwalk Tank 

Replacement Containment 

Considerations

Storage

Page 14: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Storage

No Side Entry Manways

Catwalk Access to Top of Tank

Top Entry Manway

Page 15: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Chemical Containment

Regulatory requirements Indoor vs. outdoor 

locations Fire Protection Containment for tanks and 

pumps Tank Replacement

Containment

Page 16: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Chemical Containment

Fire CodeOregon: Chapter 27 – Hazardous MaterialsSecondary containment required when vessel exceeds 55 gallons or aggregate capacity of multiple vessels exceeds 1,000 gallons

Containment

Page 17: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Containment Volume

Indoor Storage: Designed to contain a spill from the largest vessel plus the volume of fire sprinkler water for a period of 20 minutes.

Outdoor Storage: Designed to contain a spill from the largest vessel plus the volume of a 24‐hour rainfall from a 25‐year storm.

Containment

Page 18: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Containment

Containment Walls

Page 19: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

ContainmentSunken Containment

Page 20: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

ContainmentTote (IBC) Containment

Grated Containment Sump

No Containment

Containment Pallet

Which containment system do you prefer? Why?

Page 21: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Other Considerations for Totes

Handling and StorageForklift accessLoading dockContainment berms

Inventory ControlManifold tote connectionsWeigh scales

Bulk Chemical Storage

Page 22: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Dry Chemicals & Polymers

Lifting Safety 50lb Bags Vs. Super Sacks

Polymer Mixing SystemsDry Vs. EmulsionVacuum assisted hopper

Bulk Chemical Storage

Page 23: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Containment

Caustic Soda  Filter Aid

Polymer

Calcium Thiosulfate

Secondary Coagulant 

Sodium Hypochlorite

Alum Electrical Room

Containment Piping Sump

Ballasted Floc.Polymer

Page 24: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Pumps Located in Containment Area

Sunken Containment 

with Stair Access

Pipes in Trench to Avoid Trip Hazard

Containments drain to individual 

exterior sumps

Containment

Page 25: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Overhead Door

Overhead Door

Drive Through Access Corridor

Other Storage Considerations

Page 26: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Pumps

Instrumentation

Delivery and Storage

Page 27: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Diaphragm Vs. Peristaltic Vs. Gear Pumps Integral pump controls Vs. External Local Control Station Pump Mounting in Relation to Tank Invert When to Use Carrier Water? Piping Containment

Pumping and Feeding ChallengesPumps

What are some other chemical pumping and feeding challenges?

Page 28: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Diaphragm or Peristaltic (Hose) or Gear Pumps?

Pump Maintenance

Chemical Metering PumpsPumps

Which type of chemical pump do you prefer? Why?

Page 29: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Integrated or centralized local control?

Flow measurement / detection

Pump Calibration

Metering Pump ControlsPumps

Page 30: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Position is important  Not all pumps provide 

positive suction Raise the tanks or… Lower the pumps

Spill control and safety Maintenance access Wash‐down and sump 

placement

Pump PlacementPumps

Page 31: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Flexibility Vs. Complexity Access to piping for 

maintenance Off‐gassing Sloped runs Eccentric reducers Vents at high points & 

Vented Valves

PipingPumps

Page 32: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Leak Containment Clear PVC Double or single wall Spill control and safety Maintenance impacts

Piping Leak ContainmentPumps

Page 33: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Pumps located on a shelf for easy access, but close to bottom of tank elevation for flooded suction 

Organized pipe/instrument 

rack

Uncontained piping transitions to contained 

tubing between buildings

Page 34: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Pumps

Instrumentation

Delivery and Storage

Page 35: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Tools for inventory management Analyzers and Control 

Elements Programming and 

Automation Process Control for efficient chemical use

Instrumentation

Chemical Feed Control

What are some other tools to optimize chemical use?

Page 36: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Bulk tank level tracking Sight glass Vs Reverse Float Level Ultrasonic, radar, pressure

Chemical Flow metering Mini‐mag flow metering Thermal dispersion switch

Inventory MeasurementInstrumentation

Page 37: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Chemical Feed Control StrategiesInstrumentation

Hypochlorite Feed

Sample

SCADA

Process Stream

Raw Water Flow Meter

Chemical Feed Mag‐Meter

Carrier Water

Residual Chlorine Analyzer

Controlling Feedback LoopsMinimize lag time Position analyzer element close to sample source

Flow metering / monitoring Flow pacing Vs. Manual dose control

Streaming current

Page 38: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Inventory & Dose Control Inventory monitoring Dose Calibration Performance Monitoring Performance Optimization

Instrumentation

Page 39: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Chemical Systems are the Heart of the Treatment ProcessThere are lots of important things to consider in Chemical

System Design, including:SafetyReliabilityOperability

No one size fits all

Last Impressions

What are the most important components of a chemical system?

Page 40: Chemical Feed System Operation and Design Considerations. AWWA PNWS - Chem Presentation...Chemical Feed Control Strategies Instrumentation Hypochlorite Feed Sample SCADA Process Stream

Kevin Batridge - [email protected] Peters - [email protected]