    CP

    Sigma CP

    Conventional

    Fire Alarm

    Control Panels

    Fully compliant with & testedto BS EN54-2 and BS EN54-4

    2-wire and standardversions in 2, 4 or 8 zones

    Compatible for use onBS5839: Part 1: 2002installations

    2-wire repeaters andancillary boards

    Fully programmable usingsimple menu options

    Simple, single boardconstruction

    Installer friendly

    Compatible withwide range ofdetection devices

    Two monitoredsounder outputs

    3 Amp power supply

    Auxiliary power output

    Two, four and eight

    zone, 2-wire or standard,programmable fire

    control panels

    conventional detection

    systems requiring high

    performance and quality.

    The S igma CP range consists of a series of

    conventional f ire alarm control panels designed in

    accordance with European standards BS EN54-2

    and BS EN54-4 Fire D etection and Fire A larm

    systems - Control and Indicating Equipment.

    The range consists o f 2, 4 and 8 zone control

    panels. A ll control panels are available in t wo

    versions:

    Sigma K11 r ange in which detectors and call

    points are wired on separate circuits t o

    sounders (two sounder circuits are provided).

    Sigma T11 r ange in w hich detectors, c all

    points and sounders are wired to the same pair

    of cables. Commonly referred to as a two-wire

    system.

    Wiring sounders to the detection circuits eliminates

    the need to i nstall s ounder circuit cables and also

    offers the ability t o provide zoned or t wo stage

    sounder operation.

    All control panels have an integral, mains powered

    battery charger and power s upply designed in

    accordance with the requirements of BS EN54-4.

    Features Product Overview

    Adjustable sounder delay time

    Sounder configuration options

    Zonal sounder delay detectors only

    Zonal sounder delay call points only

    Coincidence input selection

    I.S Barrier selection by zone

    Short circuit fire by zone

    Non latching zones

    Silent zones

    Zone input delay

    General panel configuration

    BS EN54-2

    BS EN54-4

    KM 73505

    Model No. K11080M2

    Page 36

  • 7/28/2019 Cigma Cp 2 4 8 Zones SIT

    2/2

    DS37.05.2005

    Technical

    Specifications

    The manufacturer reserves the right to amend specifications without prior notice

    Size

    Construction

    Colour

    Supply voltage

    Mains supply fuse

    Power supply DC rating

    Maximum battery size

    Fault contact rating

    Local fire contact rating

    Fire contact rating

    Sounder output rating

    Detection zone current

    Detection zoneend of line resistor

    Sounder outputend of line resistor

    Cable capacity

    Operating temperature

    Operating humidity

    385mm(W) x 310mm(H) x 92mm(D)

    1.2mm mild steel

    BS 00 A 05 (grey texture) - lid & boxRal 7047 (light grey) - controls plate

    230V AC (+10%/-15%)

    1.6 Amp 250V

    24V 3 Amps

    7Ah 12V (2 per panel)

    30V DC 1 Amp

    30V DC 1 Amp

    30V DC 1 Amp

    0.5A per output (max 1.6A over all outputs)

    1.6 milliamps

    6k8 5%

    10k 5%

    -----

    -----------

    -

    Certificate No. FM 32987BS EN ISO 9001: 2000

    Certificate No. 360BS EN ISO 9001: 2000

    Panels

    ProductCode

    K11020M2

    K11040M2

    K11080M2T11020M2

    T11040M2

    T11080M2

    Description

    2 zone control panel

    4 zone control panel

    8 zone control panel2 zone, 2 wire panel

    4 zone, 2 wire panel

    8 zone, 2 wire panel

    StandbyCurrent

    0.065 Amps

    0.075 Amps

    0.093 Amps0.065 Amps

    0.075 Amps

    0.093 Amps

    AlarmCurrent

    0.1 Amps

    0.21 Amps

    0.55 Amps0.15 Amps

    0.3 Amps

    0.63 Amps

    Page 37