978-1-5386-6159-8/18/$31.00 ©2018 IEEE Circulating Current Minimization and load sharing control of the DC Microgrid based on Optimal Droop parameters Shivam Electrical Engineering Department National Institute of Technology Kurukshetra, India [email protected] Ratna Dahiya Electrical Engineering Department National Institute of Technology Kurukshetra, India [email protected] Abstract—The DC microgrids are getting popular as an effective means to integrate various renewable energy sources. The droop control is effectively utilized in order to minimize circulating current among sources of microgrid. The unbalanced cable line impedance is the main cause to enhance circulating current. In this paper, the circulating current among source converter is minimized based on optimal droop parameters. The trade-off between effective load sharing and bus voltage regulation of DC micro grid is mitigated for a range of loading condition of unequal cable line parameters. The optimal droop parameters are calculated based on Grey Wolf Optimization (GWO) technique of the system. The performance analysis of the microgrid is verified by real-time simulator in the dSPACE 1202 platform. Keywords— Droop control, hysteresis current control, microgrid, Grey wolf optimization. I. INTRODUCTION Renewable energy sources like wind, solar, fuel cell etc. connected together due to preserve conventional energy sources and to reduce environmental pollution [1]. Micro grid is a feasible solution to integrate renewable energy sources. Microgrids can be operated either in island and grid- connected modes. Microgrids can be classified into AC and DC microgrids. Due to various applications of DC sources in commercial sectors, telecommunication and data centres, the DC microgrid is nowadays important objective [2,3]. The DC microgrid is somehow simplex in aspects of absence of frequency control and reactive power control [4-6]. The DC bus voltage variation is generated due to abruptly change in input powers and voltage or current feedback error. The circulating current among source converters is raised by the unbalance cable line impedances between the DC bus and source converters [7]. The poor load sharing can rise over stress of any source converter and facilitates maximum power to the load so, the current sharing between the source converter is particularly important [8,9]. The three control structure is consisted by a hierarchical approach as: primary, secondary, and tertiary control. The primary control level consists bus voltage regulation and generally performs based on the droop control method [10-11]. The bus voltage and power flow coordination are regulated by secondary control level. The tertiary control regulates the power flow coordination among microgrids. The hierarchical control level is also classified based on the communication link as decentralized, centralized and distributed control [8-11]. The decentralized control use the bus voltage reference based on droop control. The source converters can regulate independently. In centralized control, the source converters communicate through central control unit in order to make effective equal load sharing and regulate bus voltage [12]. The centralize control facilitates the flexibility level to achieve aforementioned control objectives. It has a basic problem that is a single point of failure possibility which can reduce the reliability. The distributed control works with only communication link and free from central control units [13-14]. The communication channels are commonly implemented for operating modes. The communication links operate based on the consensus algorithm [15-16]. Therefore, the distributed control provides more reliable and scalable over centralized control. The distributed control scheme is implemented by average output current signal [9,14] and output voltage signal [12] of source converters. The output current and voltage sharing error are compensated through cascaded proportional integral (PI) controller of the source converter. The operating frequency of the inner and outer loop of cascaded PI controller is different due to inner-loop faster than outer- loop. Therefore, the tuning procedure of cascaded PI parameters is a complex process. In [7,17,18], the dynamic droop resistance are estimated with the help of a droop index algorithm. In [19], the optimal droop parameters are utilized for decentralized control scheme. Therefore, the performance of the distributed control scheme needs to improve in terms of simplex control and for dynamic loading condition. The distributed control scheme is performed in this paper based on optimal droop parameters (nominal voltage references and droop gain) in order to minimize circulating current within the bus voltage regulation. The droop parameters of the system are optimized by fast convergence GWO algorithm. The optimization problem is considered for various loading conditions. The maximum power on the load side can be achieved by optimizing droop parameters. With the help of real-time simulation, the control objectives of the DC microgrid are successfully validated. The analysis of the distributed control scheme is described in section II. In section III, the optimization of error problem and GWO algorithm are covered. The real time simulation results are summarized in section IV. In section V, the conclusions are drawn. Proceedings of the National Power Systems Conference (NPSC) - 2018, December 14-16, NIT Tiruchirappalli, India

Upload: others

Post on 27-Feb-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Circulating Current Minimization and load sharing control

978-1-5386-6159-8/18/$31.00 ©2018 IEEE

Circulating Current Minimization and load sharing control of the DC Microgrid based on Optimal

Droop parameters

Shivam

Electrical Engineering Department National Institute of Technology

Kurukshetra, India [email protected]

Ratna Dahiya

Electrical Engineering Department National Institute of Technology

Kurukshetra, India

[email protected]

Abstract—The DC microgrids are getting popular as an

effective means to integrate various renewable energy sources. The droop control is effectively utilized in order to minimize circulating current among sources of microgrid. The unbalanced cable line impedance is the main cause to enhance circulating current. In this paper, the circulating current among source converter is minimized based on optimal droop parameters. The trade-off between effective load sharing and bus voltage regulation of DC micro grid is mitigated for a range of loading condition of unequal cable line parameters. The optimal droop parameters are calculated based on Grey Wolf Optimization (GWO) technique of the system. The performance analysis of the microgrid is verified by real-time simulator in the dSPACE 1202 platform.

Keywords— Droop control, hysteresis current control, microgrid, Grey wolf optimization.

I. INTRODUCTION

Renewable energy sources like wind, solar, fuel cell etc. connected together due to preserve conventional energy sources and to reduce environmental pollution [1]. Micro grid is a feasible solution to integrate renewable energy sources. Microgrids can be operated either in island and grid-connected modes. Microgrids can be classified into AC and DC microgrids. Due to various applications of DC sources in commercial sectors, telecommunication and data centres, the DC microgrid is nowadays important objective [2,3]. The DC microgrid is somehow simplex in aspects of absence of frequency control and reactive power control [4-6].

The DC bus voltage variation is generated due to abruptly change in input powers and voltage or current feedback error. The circulating current among source converters is raised by the unbalance cable line impedances between the DC bus and source converters [7]. The poor load sharing can rise over stress of any source converter and facilitates maximum power to the load so, the current sharing between the source converter is particularly important [8,9].

The three control structure is consisted by a hierarchical approach as: primary, secondary, and tertiary control. The primary control level consists bus voltage regulation and generally performs based on the droop control method [10-11]. The bus voltage and power flow coordination are regulated by secondary control level. The tertiary control regulates the power flow coordination among microgrids.

The hierarchical control level is also classified based on the communication link as decentralized, centralized and

distributed control [8-11]. The decentralized control use the bus voltage reference based on droop control. The source converters can regulate independently. In centralized control, the source converters communicate through central control unit in order to make effective equal load sharing and regulate bus voltage [12]. The centralize control facilitates the flexibility level to achieve aforementioned control objectives. It has a basic problem that is a single point of failure possibility which can reduce the reliability. The distributed control works with only communication link and free from central control units [13-14]. The communication channels are commonly implemented for operating modes. The communication links operate based on the consensus algorithm [15-16]. Therefore, the distributed control provides more reliable and scalable over centralized control.

The distributed control scheme is implemented by average output current signal [9,14] and output voltage signal [12] of source converters. The output current and voltage sharing error are compensated through cascaded proportional integral (PI) controller of the source converter. The operating frequency of the inner and outer loop of cascaded PI controller is different due to inner-loop faster than outer-loop. Therefore, the tuning procedure of cascaded PI parameters is a complex process. In [7,17,18], the dynamic droop resistance are estimated with the help of a droop index algorithm. In [19], the optimal droop parameters are utilized for decentralized control scheme. Therefore, the performance of the distributed control scheme needs to improve in terms of simplex control and for dynamic loading condition.

The distributed control scheme is performed in this paper based on optimal droop parameters (nominal voltage references and droop gain) in order to minimize circulating current within the bus voltage regulation. The droop parameters of the system are optimized by fast convergence GWO algorithm. The optimization problem is considered for various loading conditions. The maximum power on the load side can be achieved by optimizing droop parameters. With the help of real-time simulation, the control objectives of the DC microgrid are successfully validated.

The analysis of the distributed control scheme is described in section II. In section III, the optimization of error problem and GWO algorithm are covered. The real time simulation results are summarized in section IV. In section V, the conclusions are drawn.

Proceedings of the National Power Systems Conference (NPSC) - 2018, December 14-16, NIT Tiruchirappalli, India

Page 2: Circulating Current Minimization and load sharing control

II. THE DISTRIBUTED CONTROL SCHEME

A. Droop control

The DC microgrid is considered with two parallel sources due to basic droop control analysis in Fig. 1. The nominal voltage reference and output source current is written as

*, , , ,o i o i d i o iV V r i= + (1)

, , ,o i o c i o iV V R i= + (2)

Therefore, the output current of source converter is summarized as:

*,

,, ,( )o i o

o id i c i

V Vi

r R

−=

+ (3)

where io,i, rd,i, Rc,i, Vo,i and V*o,i are output current, droop

resistance, cable line resistance, output voltage and nominal voltage reference.

The circulating current by two DEU is calculated as:

* *,1 ,2 ,2 ,2 ,1 ,1

12,1 ,1 ,2 ,2

( )( ) ( )( )

( )( )o o d c o o d c

d c d c

V V r R V V r Ri

r R r R

− + − − +Δ =

+ + (4)

where Δi12 (circulating current error) may be equal to zero and can be assured by optimal nominal voltage reference and droop gain. The load sharing of two source converter for optimal droop gain and nominal voltage reference is expressed in Fig. 2.

Fig. 1. Simplified with two source model of DC micorgrid

Fig. 2. Droop characteristic of two source model of microgrid

Fig. 3. Simulated the DC microgrid block diagram

(b)

Fig. 4. The distributed control block diagram

B. The Distributed control method

The DC microgrid consists with three source converters and unequal cable line impedances as shown in Fig. 3. The distributed control scheme of the DC microgrid is shown in Fig. 4. The distributed control is implemented based on voltage droop control. The output voltage is regulated by the hysteresis current control. The source converters are communicated with low bandwidth communication line and it is utilized to make average reference current signal. This current signal from control block diagram can be simplified as

, , ,, , ,

, , ,

14

Lpf i Lpf i o iref i ref i o i

i Lpf i s i d i

w w VI V V

sT s w V r

= + − +

(5)

where wLpf is used to mitigate high frequency ripples of output voltage.

The average reference current signal of the DC micro grid is calculated as

Proceedings of the National Power Systems Conference (NPSC) - 2018, December 14-16, NIT Tiruchirappalli, India

Page 3: Circulating Current Minimization and load sharing control

,1

n

ref ii

ref

II

n==

(6)

The average reference current signal with communication delay for three system is given as

,1 ,2 ,2 ,3 ,3,1

. .

3ref ref d ref d

ref

I I G I GI− + +

= (7)

and communication delay by the ith source converter is

,,

1

1 .d id i

GT s

= +

(8)

Therefore, the average reference current signal with communication time delay of the converter is finalized as

,, ,2 ,3,1

, ,

,, ,

,

1( ) 1 *

4 3

Lpf io i d dref

s i d i i

Lpf iref i o i

Lpf i

wV G GI s

V r sT

wV V

s w

− + + = +

− +

(9)

III. OPTIMAL DROOP PARAMETERS BASED ON GWO

The droop parameters need to optimize in order to minimize circulating current and bus voltage regulation. The optimization problem can be developed for the optimal droop parameters. In [9,19], the aforesaid control objectives of the system can be achieved by minimizing voltage drop and current sharing error [9]

m ax m ax 2,1 , , ,1

m ax 22 ,

( )

( )

No o i o i o

ci o i

i i i ie

i=

−=

(10)

,

1

No i

v oi

Ve V

N=

= − (11)

The total error in the system is described as

T c c v ve w e w e= + (12)

The fluctuation in output current is found faster than the bus voltage variation. Therefore, the current weight factor wc is consider more value than the voltage weight factor wv.

The specific constraints of micro grid are summarized as:

min max,

min max,

d d i d

o o i o

r r r

V V V

≤ ≤

≤ ≤ (13)

T c c v v oe we we e= + + (14)

If there is constraint violate the constant value eo is added in (13). The optimization tools such as the grey wolf and particle swarm can be implemented for the satisfactory solutions [20]. The grey wolf optimization has advantages over these heuristic optimization techniques such as it is easy to implement in terms of simple structure, convergence and less storage requirement than the other techniques [21,22]. The flow chart of the GWO algorithm is expressed in Fig. 5 (a).

(a)

0 10 20 30 40 500.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Iteration

ET

(T

otal

err

or)

Fig. 5. (a) The flow chart of global alpha particle and (b) total minimum fitness error trajectory

The droop parameters of the DC microgrid are random particles of GWO algorithm. The range of droop gains and nominal voltage references are defined in Table I. The number of particles in each dimension is responsible to minimize the total error which is calculated after load flow analysis (simulation). The DC microgrid parameters are summarized as system parameters in Table II. The number of particles and iterations are considered 50 each for GWO algorithm. In Fig. 5 (b), the total error values are computed for alliteration. At the end of the final iteration, optimized alpha particle for each dimension are considered for optimum droop resistances and voltage references which are summarized in Table III

TABLE I. GWO PARAMETERS

Parameters Symbol Value Unit

Min and Max Nominal Voltage references

570, 630

V

Min and Max Droop resistances

0, 2 Ω

Current weight factor wc 0.9 -

Proceedings of the National Power Systems Conference (NPSC) - 2018, December 14-16, NIT Tiruchirappalli, India

Page 4: Circulating Current Minimization and load sharing control

Voltage weight factor wv 0.1 -

Maximum number of iteration

50

No. of particles 100

TABLE II. SIMULATION PARAMETERS

Parameters Symbol Value Unit

Bus voltage Vo 600 V

Source Converter inductance and

capacitance L,C 10e-3, 44e-3 H,F

Operating frequency of LPF

wLpf 100π rad/s

Communication time delay Td 5 ms Hysteretic current band ΔI 0.5 A Input voltage of source Vs,i 200 V

Line impedances #1,2,3 [Zc,1, Zc,2,

Zc,3]

[2+50e-3i, 3+50e-3i, 4+50e-3i]

Ω

TABLE III. ALPHA PARTICLE OF GWO

Optimal droop parameters

Values Unit

[rd,1, rd,2, rd,3] [1.5122, 1.5588, 1.4982] Ω

[Vref,1, Vref,2, Vref,3] [628.5824, 626.3382, 629.9854] V

IV. REAL-TIME SIMULATION RESULTS

In order to minimize circulating current as well as bus voltage regulation of the DC micro grid, the system performance are observed based on optimal droop parameters. The communication time delay of the source converter is considered 5 ms for all the source models.

The DC microgrid performance is observed by conventional droop controller and proposed distributed controller with low (Rload= 75 Ω ), medium (Rload= 24 Ω) and full (Rload= 12 Ω) loading conditions. In Fig. 6, the load sharing is validated by real-time simulator. The load sharing is achieved by conventional droop control in starting and after 80 s, it performs based on the distributed control scheme. The circulating current value by the conventional droop controller are 1.06, 4.43 and 9.8 A with low, medium and full loading conditions respectively. Whereas, the circulating current by the distributed control scheme are 0.002, 0.21 and 0.85 A respectively.

The reference DC bus voltage is considered 600 V. In Fig. 7, the bus voltage regulations by a conventional droop control are +20.3, +4.6, and -17 V with low, medium and full loading condition respectively, whereas +20, +3, and -20 V by the distributed control scheme. The output voltages of distributed energy units are unequal due to unbalanced voltage drop across the cable lines. Therefore, the bus voltage deviation with loading conditions is maintained within the permissible limits.

(a)

(b)

(c)

Fig. 6. The output source current at (a) low (b) medium, and (c) full load

(a)

Proceedings of the National Power Systems Conference (NPSC) - 2018, December 14-16, NIT Tiruchirappalli, India

Page 5: Circulating Current Minimization and load sharing control

(b)

(c)

Fig. 7. The performance of the bus voltage and source converter output voltage with (a) low (b) medium (c) full load

(a)

(b)

Fig. 8. The load transient response where the proposed droop controller and load are activated after 75 sec and at 87 sec and 97 sec respectively

The transient performance of the microgrid is performed in Fig. 8. The load resistance is stepped 24 to 18 Ω at 87 s and 18 to 28.8 Ω at 97 s. The load current transients are found satisfactory in both conditions. Similarly, the bus voltage transient in those conditions is found within a sustainable

range. The quantitative observation of exact values of output current and voltage is given in Table IV.

TABLE IV. QUANTIFY RESULTS

Decentralized #DEC

Distributed #DIS

Load current of source converter#

Max curren

t sharing error

(A)

Bus Volt. (V)

#1 #2 #3

Low loading condition (Rload=75 Ω)

DEC 3.5 2.78 2.44 1.06 620.3

DIS 2.762 2.76 2.758 0.002 620

Medium loading condition (Rload=24 Ω)

DEC 10.9 8.0 6.47 4.43 604.6

DIS. 8.5 8.4 8.29 0.21 603

Full loading condition (Rload=12 Ω)

DEC 21.6 15.2 11.8 9.8 583

DIS. 16.6 16.2 15.75 0.85 580

V. CONCLUSION

The performance of the DC system is observed with the optimal droop parameters. The circulating current is suppressed with the help of optimal nominal voltage reference by GWO algorithm. The bus voltage deviation for unequal and large value of cable line impedances is maintained within the permissible limits. The transient response of the distributed control of the system is perofrmed in the specific range. The real-time simulation results are observed in dSPACE 1202 platform. Further, the distributed controller may be utilized in the DC microgrid clusters.

REFERENCES

[1] M. Soshinskaya, H.J. Wina Crijns-Graus, J.M. Guerrero, J.C. Vasquez, “Microgrids:Experiences, barriers and success factors,” Renewable Sustainable Energy Rev. vol.40, pp. 659–672, 2014.

[2] Talapko D. Telecom data center power infrastructure availability comparison of DC and AC UPS. In Proc. IEEE Intelec, 1–5, 2012.

[3] Becker D-J, Sonnenberg B. DC microgrids in buildings and data centers. In Proc. 2011 IEEE 33rd Int. Telecommunications Energy Conf. (INTELEC) 2011.

[4] D. Dong, I. Cvetkovic, D. Boroyevich, W. Zhang, R. Wang, and P. Mattavelli, ‘‘Grid-interface bi-directional converter for residential dc distribution systems---Part One: High-density two-stage topology,’’ IEEE Trans. Power Electron., vol. 28, no. 4, pp. 1655---1666, Apr. 2013.

[5] Kwasinski A, Onwuchekwa C. Dynamic behavior and stabilization of dc microgrids with instantaneous constant-power loads. IEEE Transactions Power Electronics, 26(3):822–834, 2011.

[6] H. Kakigano, Y. Miura, and T. Ise, ‘‘Low-voltage bipolar-type dc micro grid for super high quality distribution,’’ IEEE Trans. Power Electron.,vol. 25, no. 12, pp. 3066---3075, Dec. 2010

[7] Augustine S, Mishra M. K., Lakshiminarasamma N. Adaptive droop control strategy for load sharing and circulating current minimization in low-voltage standalone DC micro grid. IEEE Trans. Sustainable Energy, vol. 6, no.1, pp. 132-141, 2015.

[8] Shivam and Ratna Dahiya, “Distributed Control for DC Microgrid based on Optimized Droop Parameters,” IETE journal of research, (Taylor & Francis Publications), online published 22-06-2018.

[9] Dragicevic T, Lu X, Vasquez J. C., Guerrero J. M. DC microgrids—part I: A review of control strategies and stabilization techniques. IEEE Transactions. Power Electronics, vol. 31, no. 7, pp. 4876–4891, 2016.

Proceedings of the National Power Systems Conference (NPSC) - 2018, December 14-16, NIT Tiruchirappalli, India

Page 6: Circulating Current Minimization and load sharing control

[10] Gao F, Bozhko S, Costabeber A, Patel C, Wheeler P, Hill C. I, Asher G. Comparative stability analysis of droop control approaches in voltage-source-converter-based DC microgrids. IEEE Transactions Power Electronics, vol. 32, no. 3, pp. 2395–2415, 2017.

[11] J. M. Guerrero, J. Matas, L. G. D. Vicuña, M. Castilla, “Hierarchical control of droop-controlled AC and DC microgrids -A general approach toward standardization,” IEEE Transactions Industrial Electronics, vol. 58, no. 1, pp. 158–172, 2011.

[12] J. M. Guerrero, J. Matas, L. G. D. Vicuña, M. Castilla, and J. Miret, ‘‘Decentralized control for parallel operation of distributed generation inverters using resistive output impedance,’’ IEEE Trans. Ind. Electron., vol. 54, no. 2, pp. 994---1004, Apr. 2007

[13] Wang P, Lu X, Yang X, Wang W, Xu D. An improved distributed secondary control method for DC microgrids with enhanced dynamic current sharing performance. IEEE Transactions Power Electronics, vol. 31, no. 9, pp. 6658-3376, 2016.

[14] Cook M. D, Parker G. G., Robinett R. D., Weaver W.W. Decentralized mode-adaptive guidance and control for DC microgrid. IEEE Transactions Power Delivery, vol. 32, no. 1, pp. 263–271, 2017.

[15] Yang N, Paire D, Gao F, Miraoui A, Liu W. Compensation of droop control using common load condition in DC microgrids to improve voltage regulation and load sharing. International journal of Electrical Power and energy systems, vol. 64, pp. 752-760, 2015.

[16] L. Meng, T. Dragicevic, J. M. Guerrero, and J. C. Vasquez, ‘‘Dynamic consensus algorithm based distributed global efficiency optimization of a droop controlled DC microgrid,’’ in Proc. IEEE Int. Energy Conf., 2014, pp. 1276---1283.

[17] Q. C. Zhong, ‘‘Robust droop controller for accurate proportional load sharing among inverters operated in parallel,’’ IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 1281---1290, Apr. 2013.

[18] Shivam and Ratna Dahiya, “Intelligent distributed control techniques for effective current sharing and voltage regulation in DC distributed systems”, Arabian Journal for Science and Engineering,(Springer Publications), vol. 42, no. 12, pp. 5071-5081, December 2017.

[19] Shivam, Ratna Dahiya, “Robust decentralized control for effective load sharing and bus voltage regulation of DC microgrid based on optimal droop parameters”, Journal of Renewable and Sustainable Energy, (AIP Publications), vol. 9, no. 4, pp. 45301-453021, July 2017.

[20] S.Mirjalili, S. M.Mirjalili, and A.Lewis, “Grey wolf optimizer”, Advances in Engineering Software, vol. 69, pp. 46-61, 2014.

[21] K. Y. Lee, and M. A. E.Sharkawi, “Modern heuristic optimization techniques: theory and applications to power systems”, Hoboken, NJ IEEE Press/Wiley Inter science. Chaps, pp. 3–6, 2008.

[22] S. Mohanty, B. Subudhi, and P. K. Ray, “A grey wolf-assisted perturb & observe MPPT algorithm for a PV system”, IEEE Trans. on Energy Conversion, vol. 32, no. 1, Mar. 2017.

.

Proceedings of the National Power Systems Conference (NPSC) - 2018, December 14-16, NIT Tiruchirappalli, India