CitectSCADA Communications with Mitsubishi FX3U-ENET. Open FX configuartor-EN to define the FX3U-ENET ethernetcard. And Set module nummer  Module 1 = 2de special module at the right side. Operational settings. Select “Binary code” Select “Always wait for open” Give in the IP adress - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: CitectSCADA Communications with Mitsubishi FX3U-ENET

CitectSCADA Communications with Mitsubishi FX3U-ENET

Page 2: CitectSCADA Communications with Mitsubishi FX3U-ENET

Open FX configuartor-EN to define the FX3U-ENET ethernetcard

• And Set module nummer Module 1 = 2de special module at the right side

Page 3: CitectSCADA Communications with Mitsubishi FX3U-ENET

Operational settings

• Select “Binary code”

• Select “Always wait for open”

• Give in the IP adress– PLC1 192.168.3.1– PLC2 192.168.3.2

• Check all setting andsave these with End

Page 4: CitectSCADA Communications with Mitsubishi FX3U-ENET

Operational settings

• Define one or more ports as MELSOFT connections for GX IEC Developer and FX configutor-EN

• Define a port for CitectSCADA– TCP– Unpassive– Procedure exit (MC)– Portnumber 1300

• Check all setting andsave these with End

Page 5: CitectSCADA Communications with Mitsubishi FX3U-ENET

Write settings to the FX3U-ENET• Push the Write button

• Select the right COM-portto connect to the PLCand press OK

• Push the Write button todownload the settings

• Set the PLC to stop

• Click OK on the message

• With Yes the PLC comes back in run

• Power the PLC OFF and ON to reset the ethernet card

Page 6: CitectSCADA Communications with Mitsubishi FX3U-ENET

Diagnose via serial• Push the Diagnostics button

• Connection interface is still set to a COM-port• Push the Diagnostics button in this window as well

• Select the different diagositics tabs

Page 7: CitectSCADA Communications with Mitsubishi FX3U-ENET

Diagnose via ethernet• Push the Diagnostics button

• Change the transfer setupto the IP adress of this PLC

• Push the Diagnostics button in this window as well

• Select the different diagositics tabs

Page 8: CitectSCADA Communications with Mitsubishi FX3U-ENET

GX IEC Developer via ethernet

• Select the Ethernet board on the PC side

• Select the Ethernet module in thePLC side

• Give in the IP adressof the PLC

• Set the timeout to 5 sec

• Press Connection test

• Save these setting by closing all windwos with OK

Page 9: CitectSCADA Communications with Mitsubishi FX3U-ENET

Operational settings

• Define one or more ports as MELSOFT connections for GX IEC Developer and FX configutor-EN

• Define a port for CitectSCADA– TCP– Unpassive– Procedure exit (MC)– Portnumber 1300

• Check all setting andsave these with End

Page 10: CitectSCADA Communications with Mitsubishi FX3U-ENET

Open Citect project en start de Express Communications wizard

Page 11: CitectSCADA Communications with Mitsubishi FX3U-ENET

Express Communications wizard steps

• IOserver– name = IOserver

• IOdevice– name = PLC1– external I/Odevice– Mitsubishi FX Serie FX3U

Ethernet(TCP/IP)– Adress 255 (host PLC)

• IP adress en port are not asked. See next page.

Page 12: CitectSCADA Communications with Mitsubishi FX3U-ENET

Set IP - and port adress

• Open de port settings of PLC1• Set the special opt

-i10.10.10.160 -p1300• Press replace to save settings

(PLC has IP adress 10.10.10.160 andport 1300 open for Citect)

Page 13: CitectSCADA Communications with Mitsubishi FX3U-ENET

Cluster needed in Citect v7

• Open clusters• Make a cluster and

press “Add”• Open I/O servers• Attach your IOServer to a your cluster and

press Replace

Page 14: CitectSCADA Communications with Mitsubishi FX3U-ENET

Open Variable tags and define tags

• Define a 16 bits tag– Name = RegD0_PLC1– Adress = D0– IO Device Name = PLC1– Data type = INT

• Press add

• Define a 16 bits tag– Name = RegX0_PLC1– Adress = X0– IO Device Name = PLC1– Data type = Digtal

• Press add

Page 15: CitectSCADA Communications with Mitsubishi FX3U-ENET

Create a page

Page 16: CitectSCADA Communications with Mitsubishi FX3U-ENET

Place a register on the page

• Past genie• Select libary keyentery• Select parameter2• Press OK• Set tag• Press OK• Move object and resize

to your wish

Page 17: CitectSCADA Communications with Mitsubishi FX3U-ENET

Place a register on the page

• Set symbol• Place it on the page• Insert a tag• Press OK

Page 18: CitectSCADA Communications with Mitsubishi FX3U-ENET

Save your page

Page 19: CitectSCADA Communications with Mitsubishi FX3U-ENET

Check your Communications settings Cluster1 > IOServer > BOARD1 > PORT1_BOARD1 > PLC1 > D0_PLC1

PORT• IP adres ENET

192.168.3.1• Portnumber ENET

1300• Special Opt

-i10.10.10.160 –p1300• Default TCP & BIN

IO DEVICE• Adress

255 (host)• Protocol

MELSCNET1

Tag = D0_PLC1

Page 20: CitectSCADA Communications with Mitsubishi FX3U-ENET

Compile your Project

Page 21: CitectSCADA Communications with Mitsubishi FX3U-ENET

Run Computer setup wizard

Page 22: CitectSCADA Communications with Mitsubishi FX3U-ENET

Run your project in demo mode

• Run your project• Press OK and

run in demo mode for 15 minutes• Via menu update pages and select page01

Page 23: CitectSCADA Communications with Mitsubishi FX3U-ENET

Connect more FX3U-ENET modules

• Open de ports• Change

– portname to PORT2_BOARD1– Port Number to 2– IP adress to 10.10.10.X– Press Add

• Open de IOdevices• Change

– Name to PLC2– Number to 2– Press Add

• You have now 2 record of ports and of IOdevices

Page 24: CitectSCADA Communications with Mitsubishi FX3U-ENET

Define tags of PLC2

• Open the tag RegD0_PLC1• Change

– Name to RegD0_PLC2– IO Device Name to PLC2

• Press add

• Open the tag RegX0_PLC1 • Change

– Name to RegX0_PLC2– IO Device Name = PLC2

• Press add

Page 25: CitectSCADA Communications with Mitsubishi FX3U-ENET

Add the PLC2 object on the page

• Copy the 2 objectfrom PLC1

• Change the tagsof the copiedobjects

• Close the pageand save it

Page 26: CitectSCADA Communications with Mitsubishi FX3U-ENET

Run Citect