7/12/19
Building Guide Colorado Chapter of the International Code Council
Single Family Residential Patio Covers & Carports
How to Use this Guide Check with your jurisdiction regarding type of submittal(paper or electronic) and for additional requirements. Draw to scale and complete the following(hint: use graph paper with¼" squares. Example: ¼" = 1').
1 Complete this Building Gulde by filling in the blanks on page two, and indicatingwhich construction details will be used.
2 Provide a Plot Plan (site plan) showing dimensions of your project or additionand its relationship to existing buildings or structures on the property and the distance to existing property lines drawn to scale. See Page 2
3 Fill out a building permit application. The majority of permit applications are processed with little delay. The submitted documents will help determine if the project is in compliance with building safety codes, zoning ordinances and other applicable laws.
The Colorado Chapter of the International Code Council is a professional organization seeking to promote the public health, safety and welfare to building construction. We appreciate your feedback and suggestions, please write to the Colorado Chapter of the International Code Council, P.O. Box 961, Arvada, CO 80001. This building guide can be found on Colorado Chapter of the International Code Council website at: http://www.coloradochaptericc.org
This handout was developed by the Colorado Chapter of the International Code Council as a
basic plan submittal under the 2018 International
Residential Code. It is not intended to cover all
circumstances. Check with your Department of Building Safety for additional requirements.
1
CO

Single Family Residential Patio Covers & Carports
131 .0
N
1"=20' Or:ie
Note: Olmenslons .... ------·· Stary
cl are for reference Fr�me
purposes only QJ
(�I Walkwa Ill
0 wl vi l;- Proposed " =1
...................... 30.0 ...,
Addition :::> in I
I 26.0 Concrete Drive
I 45.8 q Concrete g0 Slab for 59.2
I N N
Garage in
I vi N
111 ll)
131 .0
Note: Manufactured homes require independent/self supported patio structure
I ()J" :ill dt·l<1ils 0111).1µt •l - �"1d1t·s ,111 ,;111lt·liVt'rt'll
p, >rlic >JlS ,if 1.1i"1ns :11'L· lll'l"llllllnl p11 n'ilbl lilt'
,irrllt'llsillll • ll0
lhl' l'L'lll.tilllll� jl< >J"illlll • 1rl'1t· !'<ilit'I' IS llOI
It-,'-111.111 _; · - ir 1d1c·s(Klj1lll 11) ;111d till· k·,1�111, it ill
G111tikverd11t's 11t1l t',\ltnl _!...J i11--!1t·� !: (, I 1_1111111)
This handout was developed by the Colorado Chapter of the International Code Council as a basic plan submittal under the 2018 International Residential Code. It is not intended to cover all circumstances. Check with your Department of Building Safety for additional requirements.
..... Cl.I
V1
q C
in " 0 Cl.I
E 0
7/12/19
CO

7/12/19
Single Family Residential Patio Covers & Carports
Directions
1. Fill in the blanks with dimensions and materials whichwill be used to build the structure. Please print legibly. �--
2. Indicate in the check boxes which details from page 4 will be used. Please note if any of the sides of yourcarport addition are closer than 5'-0" to the property line, that side of the carport must be enclosed with a solidl hour fire rated wall as shown in Alternate Details B and C. You must however, keep at least two sides of thecarport open to conform to the building code requirements. Zoning approval is required.
3. Roofing to be installed per manufacturer's instructions, including low slope application and requiredinspections made.
Roof covering ______ � A (BKampie: DIMENSIONAL
Size and Amount of Lags
Vnderlayment_-,-__,.-=����fexampte: 15ff felt wilh 19'/aps)
Sheathing �(ex_a_
mpJ_e_: �,12=•-ex-teni�o-r p�1yw-ooa��-
2x __ rafters spaced __ " O.C. (example: 2 x B rafters spaced 24' O.C.)
Note: Walls, posts, and overhangs closer than 5' to the property line to be 1 hr. rated
Existing building
I •
O Detail A
o Alternate A
0 Other (provide detail) (see page 4)
S an
Concrete Slab
Minimum Diameter Pier 8" (size determined by load)
This handout was developed by the Colorado Chapter of the International Code Council as a basic plan submittal under the 2018 International Residential Code. It is not intended to cover all circumstances. Check with your Department of Building Safety for additional requirements.
No closer than 2 feet to property line
Beam splices to occur over posts with 1 1 /2'' bearing
( ) "x "beam -(example: (2) 2'�
(for Alternate B only)
__ "x __ "posts (example: 4''x4")
spaced __ apart (example: 6)
W�=:!:===::::==; Footing __ "x __ " (for Alternate Conly)
3
CO

7/12/19
Single Family Residential Patio Covers & Carports
Secure ledger to wall with lag screws @ 16" 0.C.
C Locate lag screws to penetrate top plate or studs
Note: Remove brick veneer at top of wall Existing wall before installing continuous 2x ledger
8" minimum diameter concrete caisson
Roof tie downs required
Galvanized metal post/beam connector
Treated or decay resistive post
This handout was developed by the Colorado Chapter of the International Code Council as a basic plan submittal under the 2018 International Residential Code. It is not intended to cover all circumstances. Check with your Department of Building Safety for additional requirements.
Existing Roof (remove existing shingles)
Cont. 2x6 secured to existing roof with fasteners at each rafter or truss
Solid 2x fire blocking on 2x12 or greater Roof tie downs required �
5/8" type "X" exterior - "\gypsum sheathing
Galvanized metal post/beam connector
Exterior siding ---Infill between posts
w/ 2x4's @ 16" O.C.
Bottom plate shall be treated wood
( No closer than 2 l feet to property line
One hour fire rated on the underside
Infill between posts w/ 2x4's @ 16" O.C.
- Galvanizedcolumn base w/ 1"spacer to concrete
Check local building department for swelling soils. caissons may be required. Footing
CO

Address:
Deck Section
Remove siding at ledger
9/20/19
SHEATHING
SIDING
FLASHING
DECKING
FLOORJOIST
DECK JOIST
JOIST HANGER
2X LEDGER
TENSION DEVICE. MINIMUM 750lbCAPACITY AT FOUR LOCATIONS. DISTRIBUTE EVENLY ALONG THEDECK AND ONE WITHIN 24" OF EACHEND OF THE LEDGER. FOLLOWMANUFACTURER'S INSTRUCTIONSFOR INSTALLATION
3/8" DIAMETER LAG BOLT WITHMINIMUM 3" PENETRATIONINTO CENTER OF TOP PLATE,STUD, HEADER OR RIM JOIST.
DECK LATERAL ATTACHMENT
2'-0"
2'-0
"
POST
BEAM
2X6 DIAGONALBRACES
1/2" THROUGH BOLTW/ WASHERS*PRE-DRILL
DECKING
JOISTS
DECK DIAGONAL BRACING
1/2 X 4 LAG BOLT*PRE-DRILL
1 7⁄16"
11⁄2"
71⁄8"
415⁄16"
DTT1Z
POST CAP
DECK / CARPORT / PATIO COVER BRACING
OR ROOFING
T.
City of Thornton Building Inspection Division 9500 Civic Center Drive Thornton, CO 80229
303-538-7250 [email protected]
Suggested website for deckconnector instructions.
https://www.youtube.com/watch?v=JvsoRUqJeqE

Last Update: October 5, 2018
Approved Asphalt Shingles Atlas: StormMaster Slate
StormMaster LM
Pinnacle1
Certain Teed: Grand Manor
Centennial Slate
Carriage House
Presidential Shake TL
(&AR)
Landmark TL (AR & IR)
Presidential Shake (&AR)
Independence (&AR)
Hatteras
Landmark Woodscape1
Landmark Solaris
Landmark Special
Landmark Plus (&AR)
Landmark Canada
Landmark (&AR)
Northgate IR
GAF – Elk Camelot
Grand Slate
Country Mansion
Grand Canyon
Grand Sequoia
Capstone
Slateline
Timberline Ultra HD
Timberline HD1
Timberline Cool Series
Timberline ArmourShield
II
Timberline Prestique 40
Timberline Natural
Shadow2
Marquis WeatherMax
IKO: Armourshake
Cambridge LT
Grandeur
Crowne Slate
RoofShake 40
Royal Estate
Cambridge 301
Cambridge 30 AR1
Dynasty
Malarkey: Legacy1
Ecoasis
Highlander
Windsor
Windsor XL
Vista
Owens Corning: Woodmoor Collection
Woodcrest Collection
WeatherGuard HP
Duration Shingle (All)
Oakridge Shingles1
Pabco: Paramount Advantage
Paramount
Cascade
Premier Advantage
Precise
Premier Radiance 50
Pabco Premier 50
Pabco Premier 40
Pabco Premier 303
SG-303
Tamko: Heritage IR
Heritage Vintage
Heritage 50
Heritage XL
Heritage 30
1
Must be installed in accordance with the manufacturer’s high wind installation requirements. 2 Requires installation of six nails per shingle and GAF specific starter strip on both the rake and eves.
3 Must be properly installed with six nails, Pabco Universal Starter, and paramount Starter (when required).
The manufacturers and shingle types are not all inclusive. The Building Inspection Division will consider any shingle that carries a national wind warranty for 80 mph sustained or 90 mph 3- second gust. Shingles shall be approved prior to permit issuance.
NOTICE: Some manufacturers require that a warranty upgrade be purchased in order to be covered for the stated wind speed. Please consult the shingle manufacturer’s representative for details.