clemson university dg conference update on the current status of dg interconnection protection what...

23
CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION Chuck Mozina Consultant Beckwith Electric Co., Inc.

Upload: gregory-gibbs

Post on 20-Jan-2016

231 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

UPDATE ON THE CURRENT STATUS OF DG

INTERCONNECTION PROTECTION

WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

Chuck MozinaConsultant

Beckwith Electric Co., Inc.

Page 2: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

OUTLINE

Update the Current Status of DG Interconnection Protection

Tell You What IEEE 1547 Doesn’t

Discuss New DG Method and Practices

+ Calf. Rule 21

Page 3: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

Types of DG Generators

• Induction

• Synchronous

• Asynchronous

Page 4: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

Typical Interconnection Protection

• Disconnects the generator when it is no longer operating in parallel with the utility.

• Protects the utility system from damage caused by connection of the generator (fault current and overvoltage).

• Protects the DG generator from damage from the utility system, especially through automatic reclosing.

Local Loads

Utility System

IPP System

InterconnectionRelay

InterconnectionTransformer

To Utility System

Point of common coupling

Page 5: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

Typical Generator Protection• Generator internal short circuits.

• Abnormal operating conditions (loss of field, reverse power, overexcitation and unbalance currents).

Local Loads

Page 6: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

IEEE 1547

Addresses Generators 10 MVA or Less

Started Work in 1997

Has Over 300 Participants

Met Every Other Month

Referred Most Issues of Substance to 3 New Standards Groups

Page 7: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCEWhat 1547 SAYS

A DG SHALL: Not Cause Overvoltages or Loss of Utility Relay Coordination

Disconnect When No Longer Operating in Parallel With the Utility.

+ Only Discusses 81O/U and 27, 59

Not Energize the Utility when it is De-energized

Not Create an Unintentional Islands

Use “Utility Grade” Relays

Not Cause Objectionable Harmonics

Not Cause Loss of Synchronism That Results in Objectionable Flicker

Page 8: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

What 1547 SAYSA DG SHALL: Not Cause Overvoltages or Loss of Utility Relay Coordination

Disconnect When No Longer Operating in Parallel With the Utility.

+ Only Discusses 81O/U and 27, 59

Not Energize the Utility when it is De-energized

Not Create an Unintentional Islands

Use “Utility Grade” Relays

Not Cause Objectionable Harmonics

Not Cause Loss of Synchronism That Results in Objectionable Flicker

Page 9: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

OVERVOLTAGE AND LOSS OF COORDINATION

Two Sources of Overvoltage +Choice of Delta Interconnection Transformer Primary Winding + Ferroresonance

Loss of Coordination +Choice of Grounded Interconnection Transformer Primary Winding.

Page 10: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

Typical 4-Wire Distribution Feeder Circuit

Pole-top transformer rated for line-to-neutral voltagesexample: 13.2 KV 3 7.6 KV

DG

Page 11: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

Ungrounded Interconnection Transformers

Problems

Advantages

Can supply the feeder circuit from an underground sourceafter substation breaker A trips causing overvoltage

Provide no ground faultbackfeed for fault at F1 &F2. No ground current from breaker A for a fault at F3.

LowVoltage(SEC.)

HighVoltage(PRI.)

DG

Page 12: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCEGrounded Primary Interconnection

Transformers

Problems

AdvantagesNo ground current from breaker A for faults at F3(

). No overvoltagefor ground fault at F1.

No overvoltage for ground fault at F1.

LowVoltage(SEC.)

HighVoltage(PRI.)

Provides an unwanted ground current for supply circuit faultsat F1 and F2.

Allows source feeder relaying at A to respond to a secondary ground fault at F3( ).

DG

2

3

Page 13: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

FERRORESONANCENEW YORK FIELD TESTS –1989

FIELD TEST CIRCUIT

Page 14: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

FERRORESONANCENEW YORK FIELD TESTS -1989

50KW Synchronous DG, 9KW load, 100KVAR Capacitance and Wye-Delta Interconnection Transformer

A=2.74 pu B=2.34 pu C=2.92 pu

Page 15: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

FERRORESONANCENEW YORK FIELD TESTS -1989

50KW Synchronous DG, 9KW load, 100KVAR Capacitance and Wye-Delta Interconnection Transformer

A=2.74 pu B=2.34 pu C=2.92 pu

PROTECTION SOLUTION: MEASURE PEAK OVERVOLTAGE NOT RMS (59I)

Page 16: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

CONDITIONS FOR FERRORESONANCE

1. DG Must be Separated From the Utility System (islanded condition)

2. KW Load in the Island Must be Less than 3 Times DG Rating

3. Capacitance Must be Greater Than 25 and Less Than 500 Percent of DG Rating

4. There Must be a Transformer in the Circuit to Provide Nonlinearity

Page 17: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

PROTECTION FUNCTION BEYOND 81O/U,27 AND 59

Total Interconnect Package

Loss of Parallel

Fault backfeed removal

Damaging conditions Abnormal power flow Restoration

Page 18: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

TYPICAL INTERCONNECTION PROTECTION FOR WYE-GROUNDED (PRI.) INTERCONNECTION TRANSFORMER

Page 19: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

TYPICAL INTERCONNECTION PROTECTION FOR UNGROUNDED (PRI.) INTERCONNECTION TRANSFORMER

Page 20: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

RECIPROCATING ENGINE OUT OF SYNCHRONISM CONDITION

Page 21: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

Power

Pm=Pe

PFAULT

Angle

A2

180

PMax

= Eg ESX

120

UNSTABLE

A1

g-s

Line Recloser

Trips

STABLE

Power Angle Analysis of Out-of-Synchronism Condition

If A1>A2 DG goes unstable and slips a pole, results in high levels of transient shaft torque

LocalLoad

UtilitySubstation

DG

X

LineRecloser

FAULT

Page 22: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

CONCLUSIONS1. DGs Interconnected on Distributions Systems Present Significant Technical

Problems

2. There are No “Standard” Solutions Only Choices with Undersirable Drawbacks

3. IEEE 1547 Provides Limited Real Guidance – Simply Cites Obvious Requirements

4. Hopefully, the Three Newly Formed IEEE Standards Groups Will Address the Technical Issues Raised in this Paper

Page 23: CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION

CLEMSON UNIVERSITY DG CONFERENCE

THE ENDUPDATE ON THE CURRENT STATUS OF DG

INTERCONNECTION PROTECTION

QUESTIONS