closed cooling water sizing

Upload: swapnadiph

Post on 01-Jun-2018

236 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/9/2019 Closed Cooling Water Sizing

    1/20

    OWNER

    EPC CONTRACTOR

    PACO POWER PLANT

    Calculation - Calculation For CCW System

    Document No: LTCA P-6032 CCW

    Project No: 12889-001

    Minera Panama S.A.

    SK E&C USA

  • 8/9/2019 Closed Cooling Water Sizing

    2/20

  • 8/9/2019 Closed Cooling Water Sizing

    3/20

    Minera Panama

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Calc No.: LTCA P-6032 CCW

    Rev A, 27Mar12

    Page 1 of 18

    SL. NO DESCRIPTION PAGE NO.

    1 PURPOSE AND SCOPE 2

    2 DESIGN INPUT 2

    3 ASSUMPTIONS 2

    4 METHODOLOGY AND ACCEPTANCE CRITERIA 3

    5 CALCULATIONS 3

    6 RESULTS 3

    7 REFERENCES 3

    8 ATTACHMENTS 3

  • 8/9/2019 Closed Cooling Water Sizing

    4/20

    Minera Panama

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Calc No.: LTCA P-6032 CCW

    Rev A, 27Mar12

    Page 2 of 18

    1.0 PURPOSE AND SCOPE

    1.1 Heat Load Calculation for Plate Heat Exchangers (PHE) & CCW design flow across PHE.

    1.2 Capacity of CCW pumps1.3 Total Developed Head of CCW pumps

    1.4 Net Positive Suction Head Available at CCW pumps suction

    1.5 Pumps Shaft Input Power

    1.6 Design Pressure for Piping

    1.7 Design Temperature for Piping

    1.8 Pipe Sizing (including thickness calculation and PDT selection)

    1.9 Pressure Drop in Pipe

    2 .0 DESIGN INPUT

    2.1 2 nos. Reference 7.2

    2.2 1 nos. Reference 7.2

    2.3 10 % Reference 7.2

    2.4 2 nos. Reference 7.2

    2.5 1 nos. Reference 7.2

    2.6 10 % Reference 7.2

    2.7 Design ACW inlet temperature to PHE 30 C Reference 7.2

    2.8 1025.0 kg/m3 Reference 7.1

    2.9 32.0 C Reference 7.2

    2.10 1000.0 kg/m3 Reference 7.1

    2.11 0.0480 Bar (a) Reference 7.1

    2.12 0.7646 c.poise Reference 7.1

    2.13 4.2 kjoule/kg C Reference 7.1

    2.14 A 106 Gr B Reference 7.2

    2.15 1.6 mm Reference 7.22.16 3 m/s Reference 7.2

    2.17 1310 m3/hr Reference 7.4

    3.0 ASSUMPTIONS ( V=Verified, U= Unverified , EJ = Engineering judgment )

    3.1 85.0 % U

    3.2 0.50 Bar U

    3.3 0.70 Bar U

    3.4 0.01 Bar U

    3.5 Pressure drop across temporary suction strainers (50 % clogged condition) 0.15 Bar U

    3.6 30.7 m U

    3.7 29.3 m U3.8 1.0 m U

    3.9 Design cold end TTD for PHE 2 C U

    3.10 10 % (EJ)

    3.11 1.0 Bar U

    3.12 Refer

    Attachment 8.7

    3.13 U

    Attachment 8.1 & 8.2

    CCW Flow and Heat Load

    Elevation of CCW pump suction centre line from TG building Ground Floor FFL

    Pipe length and associated fittings as considered in the calculation are based on the tentative

    piping layout. It would be frozen after the finalization of pipe routing.

    Flow rate of ACW

    Margin to be considered on required heat load for PHE

    The purpose of this calculation is to determine the following parameters of CCW System for PACO Coal Fired Power Plant:

    Viscosity of CCW at Design temperature

    Margin to be considered on total flow for CCW pumps capacity calculation

    Density of CCW at Design temperature

    Design CCW temperature going to various coolers from PHE

    Total number of PHE working

    Total number of CCW pumps (per unit)

    Minimum water level in CCW expansion tank from TG building Ground Floor FFL

    Density of ACW at Design temperature

    Total number of CCW pumps working (per unit)

    Corrosion allowance considered for piping

    Pipeline material of construction

    Margin to be considered on required ACW Flow and CCW flow to arrive at

    Design ACW and CCW flow across PHE

    Total number of PHE

    Pressure drop across plate heat exchangers (Including nozzle pressure loss)

    Vapor pressure at Design CCW temperature

    Maximum allowable velocity in CCW Pipe Sizing

    Pressure drop across expansion joint

    Specific heat of CCW at Design temperature

    Pump efficiency

    Pressure drop across control valve ( at the outlet of selected coolers )

    Maximum Pressure Drop across individual cooler

    Maximum water level in CCW expansion tank from TG building Ground Floor FFL

  • 8/9/2019 Closed Cooling Water Sizing

    5/20

    Minera Panama

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Calc No.: LTCA P-6032 CCW

    Rev A, 27Mar12

    Page 3 of 18

    4.0 METHODOLOGY AND ACCEPTANCE CRITERIA

    Methodology

    4.1 Determine CCW design flow across PHE

    4.2 Determine CCW design outlet & inlet Temperature of PHE .

    4.3 Determine PHE Design Heat Load.

    4.4 Determine CCW design pump Flow.

    4.5 Determine Pipe size.

    4.6 Determine Pump size.

    4.7

    4.8

    4.9

    4.10

    4.11

    4.12

    4.13

    4.14 Acceptance Critieria

    (a)

    (b)

    (c)

    5 .0 CALCULATION

    5.1 Refer Attachment 8.1 for CCW Heat load estimation

    5.2 Refer Attachment 8.2 for details of PHE sizing calculation

    5.3 Refer Attachment 8.3 for details of CCW Pump sizing calculation

    5.4

    5.5

    5.6

    6.0 RESULTS

    6 .1 PHE heat load 31200000 kjou le /h r

    6.2 Capacity of CCW pump 1250 m3

    /hr6.3 Total Developed Head of CCW pump 46 mLC

    6.4 Net Positive Suction Head Available at CCW pump suction 33 mLC

    6.5 Pump Shaft Input power 184.3 kW

    6.6 Design Pressure for Piping 9.0 Bar(g)

    6.7 Design Temperature of CCW Piping 42 C

    6.8

    6.9

    The design temperature for the supply side is the maximum operating temperature plus 5 C.

    Thedesigntemperature for thereturnside is the maximum operating temperature plus 10C. This1 0 C marginencompasses the temperature rises across

    each individual cooler

    Refer Attachment 8.4 for details of Pipe Sizing, Thickness Calculation

    An appropriate PDT will be selected based on the system conditions. The PDTs sizes, pipe thicknesses and pressure rating will be verified with pipe

    sizing and thickness calculation.

    Determine NPSHA.

    The specified NPSHA should be at least 10% less than the calculated NPSHA & shall be round down to nearest 1 mWC to arrive at the design NPSHA.

    Refer Attachment 8.6 for details of Pressure Drop Summary Sheet

    The design flow of theCCW system is used to size the pump. Thepump shutoffheadis the calculatedTDH plus a 25% margin.The minimum pump

    flow is 30% of the calculated design capacity.

    The design flow through thepump is theflowforeach of the individual coolers is themaximum operating flow plus a 10% margin, rounding up to the

    next 5 cum/hr increment. The design flow of the headers is the sum of the individual cooler design flows in which it serves.

    The pipe materials must be acceptable for use at the design temperature and pressure.

    PDT selection

    Determine CCW piping material.

    ASTM A 106 GR. B (S) material is used for CCW Piping

    The design flow across PHE,is the sum of flow through individual coolers plus a 10% margin, rounding up to the next 5 cum/hr increment.

    Minimum Wall Thickness is calculated as per ASME B 31.1.

    Refer Attachment 8.5 for details of Pressure Drop Calc ulation

    The maximum operating pressure is based on the minimum flow TDH plus the static head from the high-high water level in the Closed Cooling Water

    Head Tank to the lowest point in the system, rounded up to the nearest 0.5 bar. The de sign pressure will be based on the pump shutoff head plus the

    static head from the high-high water level in the Closed Cooling Water Head Tank to the lowest point in the system plus 5% margin on the shutoff head,

    rounded up to the nearest 0.5 bar.Based on the design pressure and design temperature, a pressure class for the system will selected using ASME

    B16.34.The hydrostatic test pressure is calculated as 1.5 times the design pressure per ASME B31.1.

    For pump head calculation the cooler circuit with the maximum pressure drop among the various coolers circuit is selected.

    Piping frictional pressure drop is estimated based on the design flow.A 10% margin is added to the piping frictional losses.Darcy Weisbach equation is

    used for the frictional pressure drop calculation in pipes Crane technical paper 410 is used for calculating pressure drop across valves and fittings.

    Pipe size and routing must meet the terminal point pressure at the required flow

    Pipe size(s) must keep the fluid flow velocity less than 3.0 m/sec.

    Pipe sizes are calculated using the design flows. The minimum pipe sizes are based on maximum recommended velocity limits.

    A nominal internal diameter equal to or greater than the minimum diameter calculated is chosen.

    PDT selected based on design temp, design pressure and construction material

    & schedule as per as

    S&L 0105 Class D

    Pipe size done is within allowable velocity & it comes less than 3.0 m/sec.

    CCW outlet temperature is taken as ACW design inlet temperature with TTD of 2C temperature r ise for PHE & CCW inlet temperature to PHE isselected as CCW inlet temperature plus the average temperature rise of 7 C in CCW across the all coolers .

    Design Heat Load for PHE is based on the sum of heat load across all individual cooler plus 10% margin, rounding up to the next 1000000 kjoule/hr

    increment.

    Determine Pressure drop.

    Determine design temperature.

    Determine design Pressure.

  • 8/9/2019 Closed Cooling Water Sizing

    6/20

  • 8/9/2019 Closed Cooling Water Sizing

    7/20

    Minera Panama

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Calc No.: LTCA P-6032 CCW

    Rev A, 27Mar12

    Page 5 of 18

    Item No Particulars Formulae Unit Values Remarks

    1.0 Heat Load (CCW Side)

    1.1 Required Heat Load for PHE Hr kjoule/hr 28336534 Attachment

    8.1

    1.2 Margin on Heat Load (10 %) M % 10

    1.3 Number of PHE operating N 1

    1.4 Design Heat Load for each Plate Heat Exchanger H = (Hr * (1+M/100)) / N kjoule/hr 31170187

    1.5 Selected Design Heat Load for each Plate Heat

    Exchanger

    HD kjoule/hr 31200000

    2.0 CCW outlet temperature of PHE

    2.1 ACW inlet temperature T C 30.0

    2.2 TTD for plate heat exchanger TTD C 2.0

    2.3 CCW outlet temperature of PHE T1 = T + TTD C 32.0

    3.0 CCW flow across PHE3.1 Combined CCW flow across plate heat exchanger qCCW cum/hr 1131 Attachment

    8.1

    3.2 Margin to be considered on flow mCCW % 10

    3.3 Design CCW flow across each operat ing PHE QCCW= qCCWx (1 + mCCW/ 100) / N cum/hr 1245

    3.4 Selected Design CCW flow across each PHE QCCWD cum/hr 1250

    4.0 CCW inlet temperature of PHE

    4.1 Design CCW flow across plate heat exchanger QCCWD cum/hr 1250.0

    4.2 Density of CCW DCCW kg/m3 1000.0

    4.3 Design heat load for PHE HD kcal/hr 31200000

    4.4 Specific heat of CCW SPCCW K joule/kg C 4.2

    4.5 Average temperature rise in CCW across coolers TCCW= HD/ (QCCWDx SPCCWx DCCW) C 6.0

    Selected Average temperature rise in CCW across

    coolers

    TCCWS C 7.0

    4.6 Design CCW inlet temperature to PHE T2 = T1 + TCCWS C 39.0

    5.0 ACW flow across PHE

    5.1 Selected heat load HD kjoule/hr 31200000

    5.2 ACW inlet temperature T C 30.0

    5.3 Mass flow rate of ACW MACW m3/hr 1310.0

    5.4 Density of ACW at average temperature to heat

    exchanger

    DACW kg/m3 1025.0

    5.5 Mass flow rate of ACW MACW Kg/hr 1342750.0

    5.6 Specific heat of ACW (approx.) SPACW k joule/kg C 4.2

    5.7 Temprature rise of ACW through plate heat

    exchanger

    T=HD/MACW*SPACW C 6

    5.8 ACW outlet temperature T ' = TACW+ T C 35.6

    Plate Heat Exchanger

    T = 30 C CCW OUT 1250 m3/hr

    1310 T1 = 32 C

    ACW OUT T2 = 39 C

    T' = 35.6 C CCW IN

    31200000 kcal/hr

    ATTACHMENT 8.2: PHE SIZING CALCULATION

  • 8/9/2019 Closed Cooling Water Sizing

    8/20

    Minera Panama

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Calc No.: LTCA P-6032 CCW

    Rev A, 27Mar12

    Page 6 of 18

    Particulars Formulae Unit Value Remarks

    Required CCW flow across plate heat exchanger Q1 m3/hr 1131.0 Attachment 8 .1

    Number of pumps working N Nos. 1.0

    Flow through each pump Qp=(Q1)/N m3/hr 1131.0

    Calculated CCW design flow (with 10% margin) Qdp=1.10 x Qp m3/hr 1244.1

    Capacity of CCW pump QSEL m3/hr 1250

    Maximum pressure drop in CCW circuit is for ID Fan coolers DP Bar 4.32 Attachment 8.6

    Pressure drop across temporary strainer DPs Bar 0.15

    Pressure drop across expansion joint (four number in circuit) DPex Bar 0.04

    CCW pump discharge pressure P1 = DP + DPs + Dex Bar 4.51

    Density of CCW water at Design temperature DCCW Bar 1000.00

    Head of CCW Pump H1 = P1 x 10000 / Dccw mLC 45.10

    Selected Head of CCW Pump H1sel mLC 46.0

    Atmospheric Pressure PATA Bar 1.00

    Vapor pre ssure of water at CCW opera ting tempera ture PVAP Bar 0.0480

    Minimum water level in CCW expansion tank from TG building

    Ground Floor FFL

    E1 m 29.3

    Elevation of CCW pump suction centre line from TG building

    Ground Floor FFL

    E2 m 1.0

    Density of CCW water at Design temperature DCCW kg/m3 1000.0

    mLC 28.30

    Bar (g) 2.78

    Bar (a) 3.73

    mLC (a) 37.3

    Net Positive Suction Head Available at CCW pump suction mLC (a) 33.0

    Pump Efficiency Eff pump % 85.0

    Pump Shaft Input power P power in=DCCW x QSELx PTDHx

    9.81 x 100 /(3600x1000xEff

    pump)

    KW 184.3

    Density of CCW water at Design temperature DCCW kg/m3 1000

    mLC 57.50

    Bar (g) 5.64

    Maximum water level in CCW expansion tank from TG building

    Ground Floor FFL

    E3 m 30.70

    Elevation of CCW pump suction centre line from TG building

    Ground Floor FFL

    E2 m 1.0

    mLC 29.70

    Bar (g) 2.91

    Design pressure for CCW piping

    (with 5 % margin on shut off head)

    PDE = HMAX+ PSHUT x 1.05 Bar (g) 8.70

    Design Pressure of CCW Piping Bar (g) 9.00

    Maximum CCW temperature TCCW Max C 39.00

    1.2

    3.6

    6.1

    1.3

    3.7

    3.8

    1.4

    1.5

    2.5

    2.7

    3.3

    3.4

    5.5

    5.6

    5.7

    Pump Suction and discharge piping design temperature6

    Maximum suction static head available

    5.1

    5.2 Pump shut off head PSHUT= 1.25 x DCCW

    5.3

    5.4

    HMAX= E3 - E2

    2.3

    2.4

    2.6

    3.1

    3.2

    Minimum suction static head available

    2.2

    2

    ATTACHMENT 8.3 CCW PUMP SIZING CALCULATION

    Item No

    1

    1.1

    Pump discharge pressure (CCW head tank at elevation above all coolers)

    2.1

    Pump Capacity

    NPSH available

    3.5

    3

    Pump discharge pipeline design pressure (CCW head tank at elevation above all coolers)

    NPSHA=PATA -PVAP + HAWLNet positive suction head

    Estimated Pump Shaft Input Power4

    4.2

    5

    4.1

    HAWL = E1 -E2

  • 8/9/2019 Closed Cooling Water Sizing

    9/20

  • 8/9/2019 Closed Cooling Water Sizing

    10/20

  • 8/9/2019 Closed Cooling Water Sizing

    11/20

    Minera Panama Calc No : LT

  • 8/9/2019 Closed Cooling Water Sizing

    12/20

    Minera Panama

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Calc No.: LT

    ATTACHMENT 8.5: PRESSURE DROP CALCULATION

    From Node - To Node FORMULAE N1-N2 N3-N4 N4-N5 N5-N6 N5-N7 N7-N8 N7-N9 N9-N10 N9-N11 N4-N13 N13-N14 N13-N15 N15-N16 N15-17 N17-18 N17-N19 N19-N20 N19-N21 N21-N22 N22-N23 N21-N24 N24-N25

    OPERATING MODE Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design

    PIPE SEGMENT

    Major Inside Diameter - d1(mm) 438.15 438.15 202.72 49.25 202.72 202.72 49.25 38.10 49.25 304.80 304.80 304.80 102.26 304.80 62.71 254.51 97.18 254.51 62.71 49.25 254.51 202.72

    Length - L (M) 20.00 30.00 40.00 15.00 20.00 15.00 20.00 10.00 20.00 20.00 15.00 20.00 15.00 20.00 25.00 20.00 15.00 40.00 25.00 10.00 60.00 50.00

    BENDS

    Elbow

    90 Short Radius - Quantity

    45 Short Radius - Quantity

    90 Long Radius - Quantity 4 5 4 2 2 2 1 1 2 2 1 2 1 1 1 2 2 4 2 1 2 4

    45 Long Radius - Quantity

    Pipe Bend

    Radius - r/d

    Included Angle of Bend - (degrees)

    Quantity n (nos.)

    Miter Bend

    Included Angle of Bend - (degrees)

    Number of Miter Breaks

    Quantity

    TEES

    90 deg. Converging - Flow Through Run

    Branch Inside Diameter - d2 (mm) 203 49 203 38

    Quantity n (nos.) 1 1 1 1

    90 deg. Diverging - Flow Through Run

    Branch Inside Diameter - d2 (mm) 305 305 63 97 62.71 49 203

    Quantity n (nos.) 1 1 1 1 1 1 1

    90 deg. Converging - Flow Through Br.

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    90 deg. Diverging - Flow Through Branch

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Converging - Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Diverging - Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Converging - Flow Through Br.

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Diverging - Flow Through Branch

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    135 deg. Converging Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    135 deg. Diverging Flow Through Run

    Attachment:8.5 Pressure Drop Calculation

  • 8/9/2019 Closed Cooling Water Sizing

    13/20

  • 8/9/2019 Closed Cooling Water Sizing

    14/20

    Minera Panama

    PACO P Pl t P j t

    Calc No.: LT

  • 8/9/2019 Closed Cooling Water Sizing

    15/20

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    From Node - To Node FORMULAE

    OPERATING MODE

    PIPE SEGMENT

    Major Inside Diameter - d1(mm)

    Length - L (M)

    BENDS

    Elbow

    90 Short Radius - Quantity

    45 Short Radius - Quantity

    90 Long Radius - Quantity

    45 Long Radius - Quantity

    Pipe Bend

    Radius - r/d

    Included Angle of Bend - (degrees)

    Quantity n (nos.)

    Miter Bend

    Included Angle of Bend - (degrees)

    Number of Miter Breaks

    Quantity

    TEES

    90 deg. Converging - Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    90 deg. Diverging - Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    90 deg. Converging - Flow Through Br.

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    90 deg. Diverging - Flow Through Branch

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Converging - Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Diverging - Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Converging - Flow Through Br.

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    45 deg. Diverging - Flow Through Branch

    Run Inside Diameter - d2 (mm)

    Quantity n (nos.)

    135 deg. Converging Flow Through Run

    Branch Inside Diameter - d2 (mm)

    Quantity n (nos.)

    135 deg. Diverging Flow Through Run

    N24-N26 N26-N27 N6'-N5' N8'-N7' N10'-N9' N11'-N9' N9'-N7' N7'-N5' N25'-N24' N24'-N21' N23'-N22' N22'-N21' N21'-N19' N19'-N17' N17'-N15' N15'-N13' N13'-N4' N4'-N1' N20'-N19' N18'-N17' N16'-N15' N14'-N13' N5'-N4' N27'-N26' N26'-N24'

    Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design Design

    77.93 49.25 38.10 202.72 38.10 49.25 49.25 202.72 202.72 254.51 49.25 62.71 254.51 254.51 303.23 303.23 387.35 438.15 102.26 62.71 102.26 303.23 202.72 49.25 77.93

    180.00 10.00 10.00 20.00 15.00 20.00 20.00 20.00 40.00 70.00 15.00 35.00 30.00 30.00 40.00 15.00 25.00 40.00 40.00 15.00 15.00 60.00 40.00 10.00 180.00

    4 1 2 1 1 3 4 1 2 3 2 2 1 1 3 2 1 1 1 2 1 1

    53 63 49 102 63 303 303 203

    1 1 1 1 1 1 1 1

    24

    1

    203 255 255 303

    1 1 1 1

    Attachment:8.5 Pressure Drop Calculation

  • 8/9/2019 Closed Cooling Water Sizing

    16/20

  • 8/9/2019 Closed Cooling Water Sizing

    17/20

    Minera Panama Calc No.: LTCA P-6032 CCW

  • 8/9/2019 Closed Cooling Water Sizing

    18/20

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Rev A, 27Mar12

    Page 16 of 18

    S.No Cooler Considered Nodes considered to calc ulate pressure dr op in Piping,

    Valves & Fittings from pump discharge unto inlet of

    cooler

    Pressure drop

    up to inlet of

    cooler

    Nodes considered to calculate pressure drop in Piping,

    Valves & Fittings from outlet of cooler unto pump

    suction

    Pressure drop

    from cooler

    discharge to

    pump suction

    Total line

    frictional

    pressure drop

    Margin in line

    frictional

    pressure drop

    ( 10 % )

    Pressure drop

    across plate

    heat

    exchanger

    N5-N6

    Pressure drop

    across control

    valve at cooler

    outlet (wherever

    applicable)

    Pressure drop

    across cooler /

    Terminal point

    pressure

    Total pressure

    drop

    Bar Bar Bar Bar Bar Bar Bar Bar

    1 Vaccum Priming Pump coolers N1-N2-N3-N4-N5-N7-N9-N11 0.51 N11'-N9'-N7'-N5-N4-N1' 0.68 1.18 0.12 0.70 0.00 1.00 3.00

    2 Station Air Compressor coolers N1-N2-N3-N4-N13-N15-N17-N19-N20 0.48 N20'-N19'-N17'-N15'-N13'-N1' 0.41 0.88 0.09 0.70 0.00 1.00 2.67

    3 BFP coolers N1-N2-N3-N4-N13-N15-N17-N19-N21-N22 0.82 N22'-N21'-N19'-N17'-N15'-N13'-N4'-N3'-N2'-N1' 1.01 1.83 0.18 0.70 0.00 1.00 3.71

    4 BoilerAuxilaries coolers N1-N2-N3-N4-N13-N15-N17-N19-N21-N24-N25 0.73 N25'-N24'-N21'-N19'-N17'-N15'-13'-N4'-N3'-N2'-N1' 0.59 1.32 0.13 0.70 0.00 1.00 3.15

    5 ID Fan coolers N1-N2-N3-N4-N13-N15-N17-N19-N21-N24-N26-N27 1.23 N27'-N26'-N24'-N21'-N19'-N17'-N15'-N13'-N4'-N2'-N1' 1.16 2.39 0.24 0.70 0.00 1.00 4.32

    6 Cep coolers N1-N2-N3-N4-N5-N7-N9-N10 0.57 N10'-N9'-N7'-N5'-N4'-N3'-N2'N1' 0.46 1.03 0.10 0.70 0.00 1.00 2.83

    7 Turbine Lub oil cooler N1-N2-N3-N4-N5-N7-N8 0.27 N8'-N7'-N5'-N4'-N3'-N2'-N1' 0.20 0.48 0.05 0.70 0.00 1.00 2.22

    8 EH Fluid cooler N1-N2-N3-N4-N5-N7-N9-N11 0.43 N11'-N9'-N7'-N5-N4-N1' 0.17 0.60 0.06 0.70 0.00 1.00 2.36

    9 Generator cooler N1-N2-N3-N4-N13-N14 0.32 N14'-N13'-N4'-N4'-N3'-N1' 0.21 0.53 0.05 0.70 0.00 1.00 2.28

    10 AC compressor cololer N1-N2-N3-N4-N13-N15-N16 0.38 N16'-N15'-N13'-N4-N3'-N2'-N1' 0.24 0.61 0.06 0.70 0.00 1.00 2.37

    11 SWAS N1-N2-N3-N4-N13-N15-N17-N18 0.00 N18'-N17'-N15'-N13'-N4'-N15-N2'-N1' 0.00 0.00 0.00 0.70 0.00 1.00 1.70

    MAXIMUM PRESSURE DROP (CRITICAL PA TH) IN Bar 4.32

    ATTACHMENT 8.6 - PRESSURE DROP SUMMARY SHEET

    Attachment8.6: Pressure Drop Summry sheet

    Minera Panama

    PACO Power Plant Project

    Calc No.: L

  • 8/9/2019 Closed Cooling Water Sizing

    19/20

    Project No 12889-001

    Calc for CCW System

    ATTACHMENT 8.7 : CCW FLOW DIAGRAM

    NODEN1-N2 N3-N4 N4-N5 N5-N6 N5-N7 N7-N8 N7-N9 N9-N10 N9-N11 N4-N13 N13-N14 N13-N15 N15-N16 N15-17 N17-18 N17-N19 N19-N20 N19-N21 N21-N22 N22-N23 N21-N24 N24-N25 N24-N26 N26-N27 N6'-N5'

    Length - L (M) 20. 00 3 0.00 40.0 0 15.0 0 20.00 15.00 20.00 10.00 20.00 20.00 1 5.00 2 0.00 1 5.00 2 0.00 2 5.00 20 .00 15 .00 40 .00 25 .00 10 .00 60 .00 50. 00 180 .00 10. 00 10.0 0

    NO. OF BENDS 4 5 4 2 2 2 1 1 2 2 1 2 1 1 1 2 2 4 2 1 2 4 4 1 0

    NO. OF VALVES 1 1 1 1 2 2 1 1 1 1 2 3 1 1

    NODEN7'-N5' N25'-N24'

    N24'-

    N21'

    N23'-

    N22'

    N22'-

    N21'

    N21'-

    N19'

    N19'-

    N17'

    N17'-

    N15'

    N15'-

    N13' N13'-N4' N4'-N1'

    N20'-

    N19'

    N18'-

    N17'

    N16'-

    N15'

    N14'-

    N13' N5'-N4'

    N27'-

    N26'

    N26'-

    N24' N8'-N7' N10'-N9' N11'-N9' N9'-N7'

    Length - L (M) 20. 00 4 0.00 70.0 0 15.0 0 35.0 0 30.00 30.00 40.00 15.00 25.00 4 0.00 4 0.00 1 5.00 1 5.00 6 0.00 4 0.00 10 .00 18 0.00 20 .00 15 .00 20 .00 20. 00

    NO. OF BENDS 1 3 4 1 2 3 2 2 1 1 3 2 1 1 1 2 1 1 0 0 2 1

    NO. OF VALVES 3 1 2 1 2 1

    PHE

    PHE

    GENERATORCOOLER

    VACCUM

    PRIMING

    PUMP

    COOLER

    BFP

    COOL

    ER

    BFP

    COOLER

    BFP

    COOL

    ER

    AIR COND COMPCOOLER

    SWAS

    CEPCOOLER

    TURBINE

    LUB

    OILCOOLER

    EH

    FLUID

    OOLER

    BOILER

    AUXILARIES

    COOLER

    ID

    FAN

    COOLER

    ID

    FAN

    COOLER

    STATION AIRCOMPRESSOR

    4 19171513

    13'

    5'

    7'

    9'

    11'

    11

    9

    7 5

    1

    26'

    23'

    21'

    26

    25'

    24'

    25

    1'

    24

    23

    22

    21

    27

    27'

    23

    14

    22'

    16 18

    14' 16' 18' 20'

    10' 8' 6'

    108 6

    20

    15' 17' 19'

    4'

    Attachment8.7: CCW Flow Diagram

    Minera Panama

    PACO Power Plant Project

    Calc No.: LTCA P-6032 CCW

    Rev A 27Mar12

  • 8/9/2019 Closed Cooling Water Sizing

    20/20

    PACO Power Plant Project

    Project No 12889-001

    Calc for CCW System

    Rev A, 27Mar12

    Page 18of 18

    ATTACHMENT 8.8

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    50

    55

    60

    65

    0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800

    HeadinMLC

    Capacity in M3/Hr

    PACO POWER PLANT - System Resistance curve for CCW System

    Attachment 8.8: System Resistance curve