cmp cmp products cable gland catalogue · examples: 32e1u1ra534 = nickel plated brass 1-1/4” npt,...

6
25 www.cmp-products.com CMP INDUSTRIAL CABLE GLAND PRODUCTS CMP CMP PRODUCTS CABLE GLAND CATALOGUE Cable Gland Size Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding Diameter “A” Overall Cable Diameter “B” Armour Range † Across Flats “D” Across Corners “D” Protrusion Length “F” Combined Ordering Reference (*Brass Metric) Shroud Cable Gland Weight (Kgs) Standard Option Metric Thread Length (Metric) “E” NPT Thread Length (NPT) “E” NPT Min Max Min Max Grooved Cone (X) Stepped Cone (W) Max Max Size Type Ordering Suffix Min Max Min Max 20s16 M20 10.0 1/2” 19.9 3/4” 3.1 8.6 6.1 13.1 0.3 1.0 0.8 1.25 24.0 26.4 72.5 20S16 E1U 1RA PVC04 0.163 20S M20 10.0 1/2” 19.9 3/4” 6.1 11.6 9.5 15.9 0.3 1.0 0.8 1.25 24.0 26.4 70.0 20S E1U 1RA PVC04 0.150 20 M20 10.0 1/2” 19.9 3/4” 6.5 13.9 12.5 20.9 0.4 1.0 0.8 1.25 30.5 33.6 73.0 20 E1U 1RA PVC06 0.210 25S M25 10.0 3/4” 20.2 1” 11.1 19.9 14.0 22.0 0.4 1.2 1.25 1.6 37.5 41.3 89.0 25S E1U 1RA PVC09 0.330 25 M25 10.0 3/4” 20.2 1” 11.1 19.9 18.2 26.2 0.4 1.2 1.25 1.6 37.5 41.3 89.0 25 E1U 1RA PVC09 0.330 32 M32 10.0 1” 25.0 1 1/4” 17.0 26.2 23.7 33.9 0.4 1.2 1.6 2.0 46.0 50.6 86.0 32 E1U 1RA PVC11 0.430 40 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 32.1 27.9 40.4 0.4 1.6 1.6 2.0 55.0 60.5 90.0 40 E1U 1RA PVC15 0.620 50S M50 15.0 1 1/2” 26.1 2” 29.5 38.1 35.2 46.7 0.4 1.6 2.0 2.5 60.0 66.0 91.0 50S E1U 1RA PVC18 0.750 50 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 40.4 53.0 0.6 1.6 2.0 2.5 70.1 77.1 95.0 50 E1U 1RA PVC21 0.950 63S M63 15.0 2” 26.9 2 1/2” 40.1 49.9 45.6 59.4 0.6 1.6 2.0 2.5 75.0 82.5 102.0 63S E1U 1RA PVC23 1.340 63 M63 15.0 2 1/2” 39.9 3” 47.2 55.9 54.6 65.8 0.6 1.6 2.0 2.5 80.0 88.0 104.0 63 E1U 1RA PVC25 1.340 75S M75 15.0 2 1/2” 39.9 3” 52.8 61.9 59.0 72.0 0.6 1.6 2.0 2.5 90.0 99.0 115.0 75S E1U 1RA PVC28 2.110 75 M75 15.0 3” 41.5 3 1/2” 59.1 67.9 66.7 78.4 0.6 1.6 2.5 3.0 100.0 110.0 117.0 75 E1U 1RA PVC30 2.420 90 M90 24.0 3 1/2” 42.8 4” 66.6 78.6 76.2 90.3 0.8 1.6 3.15 4.0 114.3 125.4 147.0 90 E1U 1RA PVC32 4.210 100 M100 24.0 4” 44.0 5” 76.0 90.9 86.1 101.4 0.8 1.6 3.15 4.0 123.0 135.3 140.0 100 E1U 1RA LSF33 4.450 115 M115 24.0 4” 44.0 5” 86.0 97.9 101.5 110.2 0.8 1.6 3.15 4.0 133.4 146.7 162.0 115 E1U 1RA LSF34 6.190 130 M130 24.0 5” 46.8 6” 97.0 114.9 110.2 123.2 0.8 1.6 3.15 4.0 152.4 167.6 174.0 130 E1U 1RA LSF35 8.340 *Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1” For NPT options add the following digits to the material suffix; 1/2” = 31; 3/4” = 32; 1” = 33; 1 1/4” = 34; 1 1/2” = 35; 2” = 36; 2 1/2” = 37; 3” = 38; 3 1/2” = 39; 4” = 310 (Brass requires prefix ‘0’) Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20 Dimensions are displayed in millimetres unless otherwise stated TECHNICAL DATA Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444 Mechanical Classifications* Impact = Level 8, Retention = Class D Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only Electrical Classifications* Category B (Category A when used with braid, tape or pliable wire armour cables) GOST R Certificate No. POCC GB. 05.H00187 GOST K Certificate No. KZ 7500361.01.01.25266 RoK Permit For Use Number 19-02-UL-1957 Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401-2-PDA Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)** Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium Seal Material CMP Thermoset Rubber Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Wire Braid Armour, Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Armoured & Jacketed Armour Clamping Reversible Armour Cone & AnyWay Universal Clamping Ring Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath Cable Gland Selection Table Refer to illustration at the top of the page E1U E1U Double Seal Industrial Cable Gland For all types of Armoured Cables Metal-to-metal armour clamping Direct & remote installation Permanently crimped, low impedance earth termination Secure against self-loosening Displacement type inner seal Controlled outer ‘load retention’ seal Unique OSTG prevents overtightening Designed to prevent Coldflow Deluge protection option -60˚C to +130˚C (standard), -20˚C to 200˚C (ThermIn option page 91) EMC tested Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444 Note : ** Refer to page 7 or www.cmp-products.com for further information on Ingress Protection Ratings Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W). Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below. Stepped (W) Cone is suitable for Single Wire Armour (SWA), or Aluminium Wire Armour (AWA) cables.

Upload: others

Post on 07-Jul-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CMP CMP PRODUCTS CABLE GLAND CATALOGUE · Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20 Dimensions

25 www.cmp-products.com

CMP

IND

UST

RIA

L CA

BLE

GLA

ND

PRO

DU

CTS

CMP CMP PRODUCTS CABLE GLAND CATALOGUE

Cable Gland Size

Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding

Diameter “A”Overall Cable Diameter “B”

Armour Range †Across Flats “D”

Across Corners

“D” Protrusion Length

“F”

Combined Ordering Reference

(*Brass Metric)Shroud

Cable Gland

Weight (Kgs)

Standard Option

MetricThread Length

(Metric) “E”NPT

Thread Length

(NPT) “E”NPT Min Max Min Max

GroovedCone (X)

Stepped Cone (W)

Max Max Size TypeOrdering

SuffixMin Max Min Max

20s16 M20 10.0 1/2” 19.9 3/4” 3.1 8.6 6.1 13.1 0.3 1.0 0.8 1.25 24.0 26.4 72.5 20S16 E1U 1RA PVC04 0.16320S M20 10.0 1/2” 19.9 3/4” 6.1 11.6 9.5 15.9 0.3 1.0 0.8 1.25 24.0 26.4 70.0 20S E1U 1RA PVC04 0.15020 M20 10.0 1/2” 19.9 3/4” 6.5 13.9 12.5 20.9 0.4 1.0 0.8 1.25 30.5 33.6 73.0 20 E1U 1RA PVC06 0.21025S M25 10.0 3/4” 20.2 1” 11.1 19.9 14.0 22.0 0.4 1.2 1.25 1.6 37.5 41.3 89.0 25S E1U 1RA PVC09 0.33025 M25 10.0 3/4” 20.2 1” 11.1 19.9 18.2 26.2 0.4 1.2 1.25 1.6 37.5 41.3 89.0 25 E1U 1RA PVC09 0.33032 M32 10.0 1” 25.0 1 1/4” 17.0 26.2 23.7 33.9 0.4 1.2 1.6 2.0 46.0 50.6 86.0 32 E1U 1RA PVC11 0.43040 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 32.1 27.9 40.4 0.4 1.6 1.6 2.0 55.0 60.5 90.0 40 E1U 1RA PVC15 0.62050S M50 15.0 1 1/2” 26.1 2” 29.5 38.1 35.2 46.7 0.4 1.6 2.0 2.5 60.0 66.0 91.0 50S E1U 1RA PVC18 0.75050 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 40.4 53.0 0.6 1.6 2.0 2.5 70.1 77.1 95.0 50 E1U 1RA PVC21 0.95063S M63 15.0 2” 26.9 2 1/2” 40.1 49.9 45.6 59.4 0.6 1.6 2.0 2.5 75.0 82.5 102.0 63S E1U 1RA PVC23 1.34063 M63 15.0 2 1/2” 39.9 3” 47.2 55.9 54.6 65.8 0.6 1.6 2.0 2.5 80.0 88.0 104.0 63 E1U 1RA PVC25 1.34075S M75 15.0 2 1/2” 39.9 3” 52.8 61.9 59.0 72.0 0.6 1.6 2.0 2.5 90.0 99.0 115.0 75S E1U 1RA PVC28 2.11075 M75 15.0 3” 41.5 3 1/2” 59.1 67.9 66.7 78.4 0.6 1.6 2.5 3.0 100.0 110.0 117.0 75 E1U 1RA PVC30 2.42090 M90 24.0 3 1/2” 42.8 4” 66.6 78.6 76.2 90.3 0.8 1.6 3.15 4.0 114.3 125.4 147.0 90 E1U 1RA PVC32 4.210100 M100 24.0 4” 44.0 5” 76.0 90.9 86.1 101.4 0.8 1.6 3.15 4.0 123.0 135.3 140.0 100 E1U 1RA LSF33 4.450115 M115 24.0 4” 44.0 5” 86.0 97.9 101.5 110.2 0.8 1.6 3.15 4.0 133.4 146.7 162.0 115 E1U 1RA LSF34 6.190130 M130 24.0 5” 46.8 6” 97.0 114.9 110.2 123.2 0.8 1.6 3.15 4.0 152.4 167.6 174.0 130 E1U 1RA LSF35 8.340

*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1”For NPT options add the following digits to the material suffix; 1/2” = 31; 3/4” = 32; 1” = 33; 1 1/4” = 34; 1 1/2” = 35; 2” = 36; 2 1/2” = 37; 3” = 38; 3 1/2” = 39; 4” = 310 (Brass requires prefix ‘0’)

Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20

Dimensions are displayed in millimetres unless otherwise stated

TECHNICAL DATA

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444

Mechanical Classifications* Impact = Level 8, Retention = Class D

Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only

Electrical Classifications* Category B (Category A when used with braid, tape or pliable wire armour cables)

GOST R Certificate No. POCC GB. 05.H00187

GOST K Certificate No. KZ 7500361.01.01.25266

RoK Permit For Use Number 19-02-UL-1957

Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401-2-PDA

Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)**

Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium

Seal Material CMP Thermoset Rubber

Cable TypeSingle Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Wire Braid Armour, Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Armoured & Jacketed

Armour Clamping Reversible Armour Cone & AnyWay Universal Clamping Ring

Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal

Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath

Cable Gland Selection TableRefer to illustration at the top of the page

E1UE1U Double Seal Industrial Cable Gland

For all types of Armoured Cables

• Metal-to-metal armour clamping

• Direct & remote installation

• Permanently crimped, low impedance earth termination

• Secure against self-loosening

• Displacement type inner seal

• Controlled outer ‘load retention’ seal

• Unique OSTG prevents overtightening

• Designed to prevent Coldflow

• Deluge protection option

• -60˚C to +130˚C (standard), -20˚C to 200˚C (ThermIn option page 91)

• EMC tested

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444Note : ** Refer to page 7 or www.cmp-products.com for further information on Ingress Protection Ratings

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below.

Stepped (W) Cone is suitable for Single Wire Armour (SWA), or Aluminium Wire Armour (AWA) cables.

Catalogue Product Pages AUGUST.indd 25 17/08/2015 11:21:15

Page 2: CMP CMP PRODUCTS CABLE GLAND CATALOGUE · Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20 Dimensions

26www.cmp-products.com

CMP

IND

UST

RIA

L CA

BLE

GLA

ND

PRO

DU

CTS

CMP CMP PRODUCTS CABLE GLAND CATALOGUE

TECHNICAL DATA

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444

Mechanical Classifications* Impact = Level 8, Retention = Class D

Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only

Electrical Classifications* Category B (Category A when used with braid, tape or pliable wire armour cables)

GOST R Certificate No. POCC GB. 05.H00187

GOST K Certificate No. KZ 7500361.01.01.25266

RoK Permit For Use Number 19-02-UL-1957

Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401-2-PDA

Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)**

Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium

Seal Material CMP Thermoset Rubber

Cable Type

Lead Sheathed & Single Wire Armour (LC/SWA), Lead Sheathed & Wire Braid Armour, Lead Sheathed & Steel Tape Armour (LC/STA), Lead Sheathed & Pliable Wire Armour (LC/PWA), Lead Sheathed & Strip Armour (LC/ASA)

Armour Clamping Reversible Armour Cone & AnyWay Universal Clamping Ring

Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal

Sealing Area(s) Cable Inner Lead Sheath & Outer Sheath

Cable Gland Selection TableRefer to illustration at the top of the page

Cable Gland Size

Available Entry Threads “C” (Alternate Metric Thread Lengths Available)

Cable Lead Sheath

Diameter “A”

Overall Cable Diameter “B”

Armour Range †Across Flats “D”

Across Corners

“D”Protrusion

Length “F”

Combined Ordering Reference

(*Brass Metric)

Shroud

Cable Gland

Weight (Kgs)

Standard Option

Metric

Thread Length (Metric)

“E”

NPTThread Length

(NPT) “E”NPT Min Max Min Max

GroovedCone (X)

Stepped Cone (W)

Max Max Size TypeOrdering

SuffixMin Max Min Max

20s16 M20 10.0 1/2” 19.9 3/4” 3.1 7.8 6.1 13.1 0.3 1.0 0.8 1.25 24.0 26.4 72.5 20S16 E2U 1RA PVC04 0.16020S M20 10.0 1/2” 19.9 3/4” 6.1 11.0 9.5 15.9 0.3 1.0 0.8 1.25 24.0 26.4 70.0 20S E2U 1RA PVC04 0.15020 M20 10.0 1/2” 19.9 3/4” 6.5 13.4 12.5 20.9 0.4 1.0 0.8 1.25 30.5 33.6 73.0 20 E2U 1RA PVC06 0.21025S M25 10.0 3/4” 20.2 1” 11.1 19.3 14.0 22.0 0.4 1.2 1.25 1.6 37.5 41.3 89.0 25S E2U 1RA PVC09 0.33025 M25 10.0 3/4” 20.2 1” 11.1 19.3 18.2 26.2 0.4 1.2 1.25 1.6 37.5 41.3 89.0 25 E2U 1RA PVC09 0.33032 M32 10.0 1” 25.0 1 1/4” 17.0 25.5 23.7 33.9 0.4 1.2 1.6 2.0 46.0 50.6 86.0 32 E2U 1RA PVC11 0.43040 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 31.2 27.9 40.4 0.4 1.6 1.6 2.0 55.0 60.5 90.0 40 E2U 1RA PVC15 0.62050S M50 15.0 1 1/2” 26.1 2” 29.5 37.2 35.2 46.7 0.4 1.6 2.0 2.5 60.0 66.0 91.0 50S E2U 1RA PVC18 0.75050 M50 15.0 2” 26.9 2 1/2” 35.6 42.6 40.4 53.0 0.6 1.6 2.0 2.5 70.1 77.1 95.0 50 E2U 1RA PVC21 0.96063S M63 15.0 2” 26.9 2 1/2” 40.1 48.5 45.6 59.4 0.6 1.6 2.0 2.5 75.0 82.5 102.0 63S E2U 1RA PVC23 1.35063 M63 15.0 2 1/2” 39.9 3” 47.2 54.2 54.6 65.8 0.6 1.6 2.0 2.5 80.0 88.0 104.0 63 E2U 1RA PVC25 1.35075S M75 15.0 2 1/2” 39.9 3” 52.8 60.2 59.0 72.0 0.6 1.6 2.0 2.5 90.0 99.0 115.0 75S E2U 1RA PVC28 2.12075 M75 15.0 3” 41.5 3 1/2” 59.1 65.2 66.7 78.4 0.6 1.6 2.5 3.0 100.0 110.0 117.0 75 E2U 1RA PVC30 2.43090 M90 24.0 3 1/2” 42.8 4” 66.6 77.1 76.2 90.3 0.8 1.6 3.15 4.0 114.3 125.4 147.0 90 E2U 1RA PVC32 4.230100 M100 24.0 4” 44.0 5” 76.0 88.1 86.1 101.4 0.8 1.6 3.15 4.0 123.0 135.3 140.0 100 E2U 1RA LSF33 4.470115 M115 24.0 4” 44.0 5” 86.0 94.1 101.5 110.2 0.8 1.6 3.15 4.0 133.4 146.7 162.0 115 E2U 1RA LSF34 6.210130 M130 24.0 5” 46.8 6” 97.0 110.1 110.2 123.2 0.8 1.6 3.15 4.0 152.4 167.6 174.0 130 E2U 1RA LSF35 8.360

*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1”For NPT options add the following digits to the material suffix; 1/2” = 31; 3/4” = 32; 1” = 33; 1 1/4” = 34; 1 1/2” = 35; 2” = 36; 2 1/2” = 37; 3” = 38; 3 1/2” = 39; 4” = 310 (Brass requires prefix ‘0’)

Examples: 32E2U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE2U1RA035 = Brass 1-1/2” NPT, 20E2U1RA5 = Nickel Plated Brass M20

Dimensions are displayed in millimetres unless otherwise stated

E2UE2U Double Seal Industrial Cable Gland

For all types of Lead Sheathed Armoured Cables

• Effectively earths / grounds lead sheathed cables

• Metal-to-metal armour clamping

• Direct & remote installation

• Permanently crimped, low impedance earth termination

• Secure against self-loosening

• Displacement type inner seal

• Controlled outer ‘load retention’ seal

• Unique OSTG prevents overtightening

• Designed to prevent Coldflow

• Deluge protection option

• -60˚C to +130˚C

• EMC tested

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444Note : ** Refer to page 7 or www.cmp-products.com for further information on Ingress Protection Ratings

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below.

Stepped (W) Cone is suitable for Single Wire Armour (SWA), or Aluminium Wire Armour (AWA) cables.

Catalogue Product Pages AUGUST.indd 26 17/08/2015 11:21:17

Page 3: CMP CMP PRODUCTS CABLE GLAND CATALOGUE · Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20 Dimensions

27 www.cmp-products.com

CMP

IND

UST

RIA

L CA

BLE

GLA

ND

PRO

DU

CTS

CMP CMP PRODUCTS CABLE GLAND CATALOGUE

Cable Gland Selection TableRefer to illustration at the top of the page

TECHNICAL DATA

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444

Mechanical Classifications* Impact = Level 8, Retention = Class D

Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only

Electrical Classifications* Category B

GOST R Certificate No. POCC GB. 05.H00187

GOST K Certificate No. KZ 7500361.01.01.25266

RoK Permit For Use Number 19-02-UL-1957

Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401A/2-PDA

Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)**

Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium

Seal Material CMP Thermoset Rubber

Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA)

Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring

Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal

Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath

Cable Gland Size

Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding

Diameter “A”Overall Cable Diameter “B”

Armour Range

Across Flats “D”

Across Corners

“D”Protrusion Length “F”

Combined Ordering Reference

(*Brass Metric)Shroud

Cable Gland

Weight (Kgs)

Standard Option

Metric

Thread Length (Metric)

“E”

NPTThread

Length (NPT) “E”

NPT Min Max Min Max Min Max Max Max Size TypeOrdering

Suffix

20s16 M20 10.0 1/2” 19.9 3/4” 3.1 8.6 6.1 13.1 0.8 1.25 24.0 26.4 72.5 20S16 E1W 1RA PVC04 0.16320S M20 10.0 1/2” 19.9 3/4” 6.1 11.6 9.5 15.9 0.8 1.25 24.0 26.4 70.0 20S E1W 1RA PVC04 0.15020 M20 10.0 1/2” 19.9 3/4” 6.5 13.9 12.5 20.9 0.8 1.25 30.5 33.6 73.0 20 E1W 1RA PVC06 0.21025S M25 10.0 3/4” 20.2 1” 11.1 19.9 14.0 22.0 1.25 1.6 37.5 41.3 89.0 25S E1W 1RA PVC09 0.33025 M25 10.0 3/4” 20.2 1” 11.1 19.9 18.2 26.2 1.25 1.6 37.5 41.3 89.0 25 E1W 1RA PVC09 0.33032 M32 10.0 1” 25.0 1 1/4” 17.0 26.2 23.7 33.9 1.6 2.0 46.0 50.6 86.0 32 E1W 1RA PVC11 0.43040 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 32.1 27.9 40.4 1.6 2.0 55.0 60.5 90.0 40 E1W 1RA PVC15 0.62050S M50 15.0 1 1/2” 26.1 2” 29.5 38.1 35.2 46.7 2.0 2.5 60.0 66.0 91.0 50S E1W 1RA PVC18 0.75050 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 40.4 53.0 2.0 2.5 70.1 77.1 95.0 50 E1W 1RA PVC21 0.95063S M63 15.0 2” 26.9 2 1/2” 40.1 49.9 45.6 59.4 2.0 2.5 75.0 82.5 102.0 63S E1W 1RA PVC23 1.34063 M63 15.0 2 1/2” 39.9 3” 47.2 55.9 54.6 65.8 2.0 2.5 80.0 88.0 104.0 63 E1W 1RA PVC25 1.34075S M75 15.0 2 1/2” 39.9 3” 52.8 61.9 59.0 72.0 2.0 2.5 90.0 99.0 115.0 75S E1W 1RA PVC28 2.11075 M75 15.0 3” 41.5 3 1/2” 59.1 67.9 66.7 78.4 2.5 3.0 100.0 110.0 117.0 75 E1W 1RA PVC30 2.42090 M90 24.0 3 1/2” 42.8 4” 66.6 78.6 76.2 90.3 3.15 4.0 114.3 125.4 147.0 90 E1W 1RA PVC32 4.210100 M100 24.0 4” 44.0 5” 76.0 90.9 86.1 101.4 3.15 4.0 123.0 135.3 140.0 100 E1W 1RA LSF33 4.450115 M115 24.0 4” 44.0 5” 86.0 97.9 101.5 110.2 3.15 4.0 133.4 146.7 162.0 115 E1W 1RA LSF34 6.190130 M130 24.0 5” 46.8 6” 97.0 114.9 110.2 123.2 3.15 4.0 152.4 167.6 174.0 130 E1W 1RA LSF35 8.340

*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1”For NPT options please add the following digits to the material suffix ; 1/2” = 31, 3/4” = 32, 1” = 33, 1 1/4” = 34, 1 1/2” = 35, 2” = 36, 2 1/2” = 37, 3” = 38,3 1/2” = 39, 4” = 310 (Brass requires prefix “0”)

Examples: 32E1W1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1W1RA035 = Brass 1-1/2” NPT, 20E1W1RA5 = Nickel Plated Brass M20

Dimensions are displayed in millimetres unless otherwise stated

E1WE1W Double Seal Industrial Cable Gland

For all types of Steel & Aluminium Wire Armoured Cables

• Metal-to-metal armour clamping

• Direct & remote installation

• Permanently crimped, low impedance earth termination

• Secure against self-loosening

• Displacement type inner seal

• Controlled outer ‘load retention’ seal

• Unique OSTG prevents overtightening

• Designed to prevent Coldflow

• Deluge protection option

• -60˚C to +130˚C

• EMC tested

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444Note : ** Refer to page 7 or www.cmp-products.com for further information on Ingress Protection Ratings

Catalogue Product Pages AUGUST.indd 27 17/08/2015 11:21:18

Page 4: CMP CMP PRODUCTS CABLE GLAND CATALOGUE · Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20 Dimensions

28www.cmp-products.com

CMP

IND

UST

RIA

L CA

BLE

GLA

ND

PRO

DU

CTS

CMP CMP PRODUCTS CABLE GLAND CATALOGUE

Cable Gland Selection TableRefer to illustration at the top of the page

TECHNICAL DATA

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444

Mechanical Classifications* Impact = Level 8, Retention = Class D

Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only

Electrical Classifications* Category B

GOST R Certificate No. POCC GB. 05.H00187

GOST K Certificate No. KZ 7500361.01.01.25266

RoK Permit For Use Number 19-02-UL-1957

Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401A/3-PDA

Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)**

Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium,

Seal Material CMP Thermoset Rubber

Cable TypeLead Sheathed & Single Wire Armour (LC/SWA), Lead Sheathed & Aluminium Wire Armour (LC/AWA)

Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring

Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal

Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath

Cable Gland Size

Available Entry Threads “C” (Alternate Metric Thread Lengths Available)

Cable Lead Sheath

Diameter “A”

Overall Cable Diameter “B”

Armour Range

Across Flats “D”

Across Corners

“D” Protrusion Length

“F”

Combined Ordering Reference

(*Brass Metric)Shroud

Cable Gland

Weight (Kgs)

Standard Option

Metric

Thread Length (Metric)

“E”

NPTThread

Length (NPT) “E”

NPT Min Max Min Max Min Max Max Max Size TypeOrdering

Suffix

20s16 M20 10.0 1/2” 19.9 3/4” 3.1 7.8 6.1 13.1 0.8 1.25 24.0 26.4 72.5 20S16 E2W 1RA PVC04 0.16020S M20 10.0 1/2” 19.9 3/4” 6.1 11.0 9.5 15.9 0.8 1.25 24.0 26.4 70.0 20S E2W 1RA PVC04 0.15020 M20 10.0 1/2” 19.9 3/4” 6.5 13.4 12.5 20.9 0.8 1.25 30.5 33.6 73.0 20 E2W 1RA PVC06 0.21025S M25 10.0 3/4” 20.2 1” 11.1 19.3 14.0 22.0 1.25 1.6 37.5 41.3 89.0 25S E2W 1RA PVC09 0.33025 M25 10.0 3/4” 20.2 1” 11.1 19.3 18.2 26.2 1.25 1.6 37.5 41.3 89.0 25 E2W 1RA PVC09 0.33032 M32 10.0 1” 25.0 1 1/4” 17.0 25.5 23.7 33.9 1.6 2.0 46.0 50.6 86.0 32 E2W 1RA PVC11 0.43040 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 31.2 27.9 40.4 1.6 2.0 55.0 60.5 90.0 40 E2W 1RA PVC15 0.62050S M50 15.0 1 1/2” 26.1 2” 29.5 37.2 35.2 46.7 2.0 2.5 60.0 66.0 91.0 50S E2W 1RA PVC18 0.75050 M50 15.0 2” 26.9 2 1/2” 35.6 42.6 40.4 53.0 2.0 2.5 70.1 77.1 95.0 50 E2W 1RA PVC21 0.95063S M63 15.0 2” 26.9 2 1/2” 40.1 48.5 45.6 59.4 2.0 2.5 75.0 82.5 102.0 63S E2W 1RA PVC23 1.34063 M63 15.0 2 1/2” 39.9 3” 47.2 54.2 54.6 65.8 2.0 2.5 80.0 88.0 104.0 63 E2W 1RA PVC25 1.34075S M75 15.0 2 1/2” 39.9 3” 52.8 60.2 59.0 72.0 2.0 2.5 90.0 99.0 115.0 75S E2W 1RA PVC28 2.11075 M75 15.0 3” 41.5 3 1/2” 59.1 65.2 66.7 78.4 2.5 3.0 100.0 110.0 117.0 75 E2W 1RA PVC30 2.42090 M90 24.0 3 1/2” 42.8 4” 66.6 77.1 76.2 90.3 3.15 4.0 114.3 125.4 147.0 90 E2W 1RA PVC32 4.210100 M100 24.0 4” 44.0 5” 76.0 88.1 86.1 101.4 3.15 4.0 123.0 135.3 140.0 100 E2W 1RA LSF33 4.450115 M115 24.0 4” 44.0 5” 86.0 94.1 101.5 110.2 3.15 4.0 133.4 146.7 162.0 115 E2W 1RA LSF34 6.190130 M130 24.0 5” 46.8 6” 97.0 110.1 110.2 123.2 3.15 4.0 152.4 160.6 174.0 130 E2W 1RA LSF35 8.340

*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1”For NPT options add the following digits to the material suffix; 1/2” = 31; 3/4” = 32; 1” = 33; 1 1/4” = 34; 1 1/2” = 35; 2” = 36; 2 1/2” = 37; 3” = 38; 3 1/2” = 39; 4” = 310 (Brass requires prefix ‘0’)

Examples: 32E2W1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE2W1RA035 = Brass 1-1/2” NPT, 25E2W1RA432 = Stainless Steel 3/4” NPT, 20E2W1RA5 = Nickel Plated Brass M20

Dimensions are displayed in millimetres unless otherwise stated

E2WE2W Double Seal Industrial Cable Gland

For Lead Sheathed Steel & Aluminium Wire Armoured Cables

• Effectively earths / grounds lead sheathed cables

• Metal-to-metal armour clamping

• Direct & remote installation

• Permanently crimped, low impedance earth termination

• Secure against self-loosening

• Displacement type inner seal

• Controlled outer ‘load retention’ seal

• Unique OSTG prevents overtightening

• Designed to prevent Coldflow

• Deluge protection option

• -60˚C to +130˚C

• EMC tested

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444Note : ** Refer to page 7 or www.cmp-products.com for further information on Ingress Protection Ratings

Catalogue Product Pages AUGUST.indd 28 17/08/2015 11:21:19

Page 5: CMP CMP PRODUCTS CABLE GLAND CATALOGUE · Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20 Dimensions

29 www.cmp-products.com

CMP

IND

UST

RIA

L CA

BLE

GLA

ND

PRO

DU

CTS

CMP CMP PRODUCTS CABLE GLAND CATALOGUE

Cable Gland Selection TableRefer to illustration at the top of the page

TECHNICAL DATA

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444

Mechanical Classifications* Impact = Level 8, Retention = Class D

Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only

Electrical Classifications* Category B (Category A when used with braid, tape or pliable wire armour cables)

GOST R Certificate No. POCC GB. 05.H00187

GOST K Certificate No. KZ 7500361.01.01.25266

RoK Permit For Use Number 19-02-UL-1957

Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401/2-PDA

Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)**

Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium

Seal Material CMP Thermoset Rubber

Cable TypeWire Braid Armour, Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Aluminium Strip Armour (e.g. ASA)

Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring

Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal

Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath

Cable Gland Size

Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding

Diameter “A”Overall Cable Diameter “B”

Armour Range †Grooved Cone

(X)

Across Flats “D”

Across Corners

“D”Protrusion Length “F”

Combined Ordering Reference

(*Brass Metric)Shroud

Cable Gland

Weight (Kgs)

Standard Option

Metric

Thread Length (Metric)

“E”

NPTThread Length

(NPT) “E”NPT Min Max Min Max Min Max Max Max Size Type

Ordering Suffix

20s16 M20 10.0 1/2” 19.9 3/4” 3.1 8.6 6.1 13.1 0.3 1.0 24.0 26.4 72.5 20S16 E1X 1RA PVC04 0.16320S M20 10.0 1/2” 19.9 3/4” 6.1 11.6 9.5 15.9 0.3 1.0 24.0 26.4 70.0 20S E1X 1RA PVC04 0.15020 M20 10.0 1/2” 19.9 3/4” 6.5 13.9 12.5 20.9 0.4 1.0 30.5 33.6 73.0 20 E1X 1RA PVC06 0.21025S M25 10.0 3/4” 20.2 1” 11.1 19.9 14.0 22.0 0.4 1.2 37.5 41.3 89.0 25S E1X 1RA PVC09 0.33025 M25 10.0 3/4” 20.2 1” 11.1 19.9 18.2 26.2 0.4 1.2 37.5 41.3 89.0 25 E1X 1RA PVC09 0.33032 M32 10.0 1” 25.0 1 1/4” 17.0 26.2 23.7 33.9 0.4 1.2 46.0 50.6 86.0 32 E1X 1RA PVC11 0.43040 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 32.1 27.9 40.4 0.4 1.6 55.0 60.5 90.0 40 E1X 1RA PVC15 0.62050S M50 15.0 1 1/2” 26.1 2” 29.5 38.1 35.2 46.7 0.4 1.6 60.0 66.0 91.0 50S E1X 1RA PVC18 0.75050 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 40.4 53.0 0.6 1.6 70.1 77.1 95.0 50 E1X 1RA PVC21 0.95063S M63 15.0 2” 26.9 2 1/2” 40.1 49.9 45.6 59.4 0.6 1.6 75.0 82.5 102.0 63S E1X 1RA PVC23 1.34063 M63 15.0 2 1/2” 39.9 3” 47.2 55.9 54.6 65.8 0.6 1.6 80.0 88.0 104.0 63 E1X 1RA PVC25 1.34075S M75 15.0 2 1/2” 39.9 3” 52.8 61.9 59.0 72.0 0.6 1.6 90.0 99.0 115.0 75S E1X 1RA PVC28 2.11075 M75 15.0 3” 41.5 3 1/2” 59.1 67.9 66.7 78.4 0.6 1.6 100.0 110.0 117.0 75 E1X 1RA PVC30 2.42090 M90 24.0 3 1/2” 42.8 4” 66.6 78.6 76.2 90.3 0.8 1.6 114.3 125.4 147.0 90 E1X 1RA PVC32 4.210100 M100 24.0 4” 44.0 5” 76.0 90.9 86.1 101.4 0.8 1.6 123.0 135.3 140.0 100 E1X 1RA LSF33 4.450115 M115 24.0 4” 44.0 5” 86.0 97.9 101.5 110.2 0.8 1.6 133.4 146.7 162.0 115 E1X 1RA LSF34 6.190130 M130 24.0 5” 46.8 6” 97.0 114.9 110.2 123.2 0.8 1.6 152.4 160.6 174.0 130 E1X 1RA LSF35 8.340

*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1”For NPT options add the following digits to the material suffix; 1/2” = 31; 3/4” = 32; 1” = 33; 1 1/4” = 34; 1 1/2” = 35; 2” = 36; 2 1/2” = 37; 3” = 38; 3 1/2” = 39; 4” = 310 (Brass requires prefix ‘0’)

Examples: 32E1X1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1X1RA035 = Brass 1-1/2” NPT, 20E1X1RA5 = Nickel Plated Brass M20

Dimensions are displayed in millimetres unless otherwise stated

E1XE1X Double Seal Industrial Cable Gland

For Braid & Steel Tape Armoured Cables

• Metal-to-metal armour clamping

• Direct & remote installation

• Permanently crimped, low impedance earth termination

• Secure against self-loosening

• Displacement type inner seal

• Controlled outer ‘load retention’ seal

• Unique OSTG prevents overtightening

• Designed to prevent Coldflow

• Deluge protection option

• -60˚C to +130˚C

• EMC tested

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444Note : ** Refer to page 7 or www.cmp-products.com for further information on Ingress Protection Ratings

If Tape Armour is to be used please contact CMP for advice.

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below.

Catalogue Product Pages AUGUST.indd 29 17/08/2015 11:21:20

Page 6: CMP CMP PRODUCTS CABLE GLAND CATALOGUE · Examples: 32E1U1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE1U1RA035 = Brass 1-1/2” NPT, 20E1U1RA5 = Nickel Plated Brass M20 Dimensions

30www.cmp-products.com

CMP

IND

UST

RIA

L CA

BLE

GLA

ND

PRO

DU

CTS

CMP CMP PRODUCTS CABLE GLAND CATALOGUE

Cable Gland Selection TableRefer to illustration at the top of the page

TECHNICAL DATA

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444

Mechanical Classifications* Impact = Level 8, Retention = Class D

Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only

Electrical Classifications* Category B (Category A when used with braid, tape or pliable wire armour cables)

GOST R Certificate No. POCC GB. 05.H00187

GOST K Certificate No. KZ 7500361.01.01.25266

RoK Permit For Use Number 19-02-UL-1957

Marine Approvals LRS: 01/00171 (E1), ABS: 01-LD234401/2-PDA

Ingress Protection Rating IP66 as standard (IP67, IP68 available upon request)**

Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium

Seal Material CMP Thermoset Rubber

Cable TypeLead Sheathed & Wire Braid Armour, Lead Sheathed & Steel Tape Armour (LC/STA), Lead Sheathed & Pliable Wire Armour (LC/PWA), Lead Sheathed & Aluminium Strip Armour (LC/ASA)

Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring

Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal

Sealing Area(s) Cable Inner Lead Sheath & Outer Sheath

Cable Gland Size

Available Entry Threads “C” Cable Lead Sheath

Diameter “A”

Overall Cable Diameter “B”

Armour Range †

Grooved Cone (X)

Across Flats “D”

Across Corners

“D”Protrusion Length “F”

Combined Ordering Reference

(*Brass Metric)Shroud

Cable Gland

Weight (Kgs)

Standard Option

Metric

Thread Length (Metric)

“E”

NPTThread

Length (NPT) “E”

NPT Min Max Min Max Min Max Max Max Size TypeOrdering

Suffix

20s16 M20 10.0 1/2” 19.9 3/4” 3.1 7.8 6.1 13.1 0.3 1.0 24.0 26.4 72.5 20S16 E2X 1RA PVC04 0.16020S M20 10.0 1/2” 19.9 3/4” 6.1 11.0 9.5 15.9 0.3 1.0 24.0 26.4 70.0 20S E2X 1RA PVC04 0.15020 M20 10.0 1/2” 19.9 3/4” 6.5 13.4 12.5 20.9 0.4 1.0 30.5 33.6 73.0 20 E2X 1RA PVC06 0.21025S M25 10.0 3/4” 20.2 1” 11.1 19.3 14.0 22.0 0.4 1.2 37.5 41.3 89.0 25S E2X 1RA PVC09 0.33025 M25 10.0 3/4” 20.2 1” 11.1 19.3 18.2 26.2 0.4 1.2 37.5 41.3 89.0 25 E2X 1RA PVC09 0.33032 M32 10.0 1” 25.0 1 1/4” 17.0 25.5 23.7 33.9 0.4 1.2 46.0 50.6 86.0 32 E2X 1RA PVC11 0.43040 M40 15.0 1 1/4” 25.6 1 1/2” 22.0 31.2 27.9 40.4 0.4 1.6 55.0 60.5 90.0 40 E2X 1RA PVC15 0.62050S M50 15.0 1 1/2” 26.1 2” 29.5 37.2 35.2 46.7 0.4 1.6 60.0 66.0 91.0 50S E2X 1RA PVC18 0.75050 M50 15.0 2” 26.9 2 1/2” 35.6 42.6 40.4 53.0 0.6 1.6 70.1 77.1 95.0 50 E2X 1RA PVC21 0.96063S M63 15.0 2” 26.9 2 1/2” 40.1 48.5 45.6 59.4 0.6 1.6 75.0 82.5 102.0 63S E2X 1RA PVC23 1.35063 M63 15.0 2 1/2” 39.9 3” 47.2 54.2 54.6 65.8 0.6 1.6 80.0 88.0 104.0 63 E2X 1RA PVC25 1.35075S M75 15.0 2 1/2” 39.9 3” 52.8 60.2 59.0 72.0 0.6 1.6 90.0 99.0 115.0 75S E2X 1RA PVC28 2.12075 M75 15.0 3” 41.5 3 1/2” 59.1 65.2 66.7 78.4 0.6 1.6 100.0 110.0 117.0 75 E2X 1RA PVC30 2.43090 M90 24.0 3 1/2” 42.8 4” 66.6 77.1 76.2 90.3 0.8 1.6 114.3 125.4 147.0 90 E2X 1RA PVC32 4.230100 M100 24.0 4” 44.0 5” 76.0 88.1 86.1 101.4 0.8 1.6 123.0 135.3 140.0 100 E2X 1RA LSF33 4.470115 M115 24.0 4” 44.0 5” 86.0 94.1 101.5 110.2 0.8 1.6 133.4 146.7 162.0 115 E2X 1RA LSF34 6.210130 M130 24.0 5” 46.8 6” 97.0 110.1 110.2 123.2 0.8 1.6 152.4 167.6 174.0 130 E2X 1RA LSF35 8.360

*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass “5”, Copper Free Aluminium “1”For NPT options add the following digits to the material suffix; 1/2” = 31; 3/4” = 32; 1” = 33; 1 1/4” = 34; 1 1/2” = 35; 2” = 36; 2 1/2” = 37; 3” = 38; 3 1/2” = 39; 4” = 310 (Brass requires prefix ‘0’)

Examples: 32E2X1RA534 = Nickel Plated Brass 1-1/4” NPT, 50SE2X1RA035 = Brass 1-1/2” NPT, 20E2X1RA5 = Nickel Plated Brass M20

Dimensions are displayed in millimetres unless otherwise stated

E2XE2X Double Seal Industrial Cable Gland

For Lead Sheathed Braid Armoured Cables

• Effectively earths / grounds lead sheathed cables

• Metal-to-metal armour clamping

• Direct & remote installation

• Permanently crimped, low impedance earth termination

• Secure against self-loosening

• Displacement type inner seal

• Controlled outer ‘load retention’ seal

• Unique OSTG prevents overtightening

• Designed to prevent Coldflow

• Deluge protection option

• -60˚C to +130˚C

• EMC tested

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444Note : ** Refer to page 7 or www.cmp-products.com for further information on Ingress Protection Ratings

If Tape Armour is to be used please contact CMP for advice.

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below.

Catalogue Product Pages AUGUST.indd 30 17/08/2015 11:21:21