code of practice 41 cp 41 - rev 2 - for... · 2018. 10. 23. · 11. fuel quality 61 11.1 proton...

90
CODE OF PRACTICE 41 THE DESIGN, CONSTRUCTION, MAINTENANCE AND OPERATION OF FILLING STATIONS DISPENSING GASEOUS FUELS REVISION 2: 2018

Upload: others

Post on 25-Jan-2021

10 views

Category:

Documents


1 download

TRANSCRIPT

  • CODE OF PRACTICE 41

    THE DESIGN, CONSTRUCTION,

    MAINTENANCE AND OPERATION OF

    FILLING STATIONS DISPENSING

    GASEOUS FUELS

    REVISION 2: 2018

  • 1 BCGA 41 – Revision 2

    CODE OF PRACTICE 41

    THE DESIGN, CONSTRUCTION, MAINTENANCE

    AND OPERATION OF FILLING STATIONS

    DISPENSING GASEOUS FUELS

    REVISION 2: 2018

    Copyright © 2018 by British Compressed Gases

    Association. First printed 2014. All rights reserved. No

    part of this publication may be reproduced or transmitted in

    any form or by any means, electronic or mechanical,

    including photocopy, without permission from the

    publisher:

    BRITISH COMPRESSED GASES ASSOCIATION Registered office: 4a Mallard Way, Pride Park, Derby, UK. DE24 8GX

    Company Number: 71798, England

    Website:

    www.bcga.co.uk

    ISSN 2398-9440

    http://www.bcga.co.uk/

  • 2 BCGA 41 – Revision 2

    PREFACE

    The British Compressed Gases Association (BCGA) was established in

    l971, formed out of the British Acetylene Association, which existed

    since l901. BCGA members include gas producers, suppliers of gas

    handling equipment and users operating in the compressed gas field.

    The main objectives of the Association are to further technology, to

    enhance safe practice, and to prioritise environmental protection in the

    supply and use of industrial, food and medical gases, and we produce a

    host of publications to this end. BCGA also provides advice and makes

    representations on behalf of its Members to regulatory bodies, including

    the UK Government.

    Policy is determined by a Council elected from Member Companies,

    with detailed technical studies being undertaken by a Technical

    Committee and its specialist Sub-Committees appointed for this

    purpose.

    BCGA makes strenuous efforts to ensure the accuracy and current

    relevance of its publications, which are intended for use by technically

    competent persons. However this does not remove the need for

    technical and managerial judgement in practical situations. Nor do they

    confer any immunity or exemption from relevant legal requirements,

    including by-laws.

    For the assistance of users, references are given, either in the text or

    Appendices, to publications such as British, European and International

    Standards and Codes of Practice, and current legislation that may be

    applicable but no representation or warranty can be given that these

    references are complete or current.

    BCGA publications are reviewed, and revised if necessary, at five-

    yearly intervals, or sooner where the need is recognised. Readers are

    advised to check the Association’s website to ensure that the copy in

    their possession is the current version.

    This document has been prepared by BCGA Technical Sub-

    Committee 9. This document replaces BCGA Code of Practice 41,

    Revision 1: 2016. It was approved for publication at BCGA Technical

    Committee 159. This document was first published on 23/10/2018.

    For comments on this document contact the Association via the

    website www.bcga.co.uk.

    http://www.bcga.co.uk/

  • 3 BCGA 41 – Revision 2

    CONTENTS

    Section Page

    TERMINOLOGY AND DEFINITIONS 6

    1. INTRODUCTION 12

    2. SCOPE 16

    3. RISK MANAGEMENT 19

    3.1 General 19

    3.2 Principle legal requirements 19

    3.3 Environmental risk assessments 20

    4. PRE-DESIGN 21

    5. PLANNING PERMISSION AND PERMITS 22

    5.1 General 22

    5.2 Storage 22

    5.3 Multi-fuel stations 23

    6. LAYOUT AND SITE SELECTION CRITERIA 23

    6.1 General 23

    6.2 Location of storage installation 24

    6.3 Access and egress for fuel delivery vehicles 28

    6.4 Location and installation of dispensing points 30

    6.5 Connecting pipework 31

    6.6 On-site fuel generation equipment and related process

    equipment.

    32

    6.7 Vent systems 32

    6.8 Vent recovery 32

    6.9 Other filling station activities 33

    7. DESIGN OF FILLING STATION 33

    7.1 General 33

  • 4 BCGA 41 – Revision 2

    7.2 Fuel gas storage and process equipment 40

    7.3 LNG vaporiser 43

    7.4 Fuel delivery 44

    7.5 Connecting pipework and valves 44

    7.6 Dispensing equipment 45

    7.7 Venting and vent stacks 49

    7.8 Dispenser plinth earthing and grounding 50

    7.9 Canopy 50

    7.10 Gas fuels on multi-fuel stations 50

    8. INSTALLATION AND COMMISIONING 50

    8.1 Installation 50

    8.2 Pre-commissioning 50

    8.3 Commissioning 53

    8.4 Handover for operation 54

    8.5 End of life 56

    9. OPERATION 56

    9.1 Delivery 56

    9.2 Vehicle filling – Fuel dispense 57

    10. PERIODIC EXAMINATION & MAINTENANCE 59

    11. FUEL QUALITY 61

    11.1 Proton Exchange Membrane hydrogen 62

    11.2 Non-Proton Exchange Membrane hydrogen 63

    11.3 CNG and LNG 63

    12. COMPETENCE OF PERSONNEL INCLUDING TRAINING 64

    13. PERSONNAL PROTECTIVE EQUIPMENT 68

    13.1 Public access filling 68

    13.2 Non-public access filling 68

  • 5 BCGA 41 – Revision 2

    13.3 Maintenance and fuel delivery 68

    14. EMERGENCY SITUATIONS AND PROCEDURES 68

    15. SECURITY 70

    16. REFERENCES * 71

    APPENDICES:

    APPENDIX 1 Minimum recommended separation distances for hydrogen

    storage installations

    81

    APPENDIX 2 Minimum recommended separation distances for natural

    gas storage installations

    82

    APPENDIX 3 Hydrogen - General data and safety considerations 83

    APPENDIX 4 Natural gas - General data and safety considerations 85

    APPENDIX 5 Checklist for approval to install and operate filling stations 87

    APPENDIX 6 Checklist for emergency services 88

    * Throughout this document numbers in brackets refer to references in Section 16. Documents

    referenced are the edition current at the time of publication of this Code of Practice, unless

    otherwise stated.

  • 6 BCGA 41 – Revision 2

    TERMINOLOGY AND DEFINITIONS

    Assembly A number of parts or combination thereof that are joined together to

    perform a specific function and subject to disassembly without

    degradation of any of the parts, e.g. a hose assembly combining a

    nozzle, hose set and breakaway coupling.

    Biomethane Biomethane is upgraded Biogas, a natural occurring gas with similar

    properties to natural gas, produced by the anaerobic digestion of

    waste such as organic matter, food waste, sewage, landfill etc. It

    can be stored in two forms, compressed (CBG) or liquefied (LBG).

    Boil-off gas Gas emissions caused by the evaporation of a liquefied gas in

    storage tanks and other parts of the station.

    Break-away device A device that stops the flow of gas allowing safe disconnection from

    the fuelling system in the event of accidental disconnection, i.e. a

    vehicle drive-away when the hose is still connected.

    Bulk storage For the purposes of this document bulk storage is defined as fuel gas

    storage which consists of either:

    fixed gas cylinders manifolded together; or

    tubes which may be either fixed in place or mounted on a transportable trailer; or

    one or more liquefied gas vessels.

    Bundle Assembly of cylinders that are fastened together and which are

    interconnected by a manifold and transported as a unit, having a total

    water capacity not exceeding 3000 litres.

    Bund A containment structure typically made of concrete that diverts a

    liquefied gas to a safe area for dissipation into the atmosphere.

    Canopy A roof, overhead shelter, or hood providing the station or fuel

    dispenser with a degree of weather protection.

    Competence The employer is responsible for ensuring that employees are

    competent to carry out each task safely and correctly. For

    additional information on competence refer to BCGA GN 23 (97),

    Gas safety. Information, instruction and training.

    There are specific roles, such as a ‘Competent Person’, which are

    defined in legislation, for example, the Pressure System Safety

    Regulations (11).

    Compressed

    natural gas

    Compressed natural gas (CNG), including methane and biomethane.

  • 7 BCGA 41 – Revision 2

    Control point A position in a kiosk or other building at an attended self-service

    filling station from which an attendant can view and supervise

    activities at the dispenser, activate the equipment, and shut-off the

    dispenser, in the case of emergency.

    Cryogenic Cryogenic liquids are liquefied gases that are kept in their liquid

    state at very low temperatures, typically lower than -150 °C.

    Cylinder Transportable pressure receptacle of a water capacity not exceeding

    150 litres.

    Dead man’s button

    / switch

    A device that automatically shuts down an operation in a safe

    manner, i.e. when refuelling a vehicle or during a fuel transfer.

    Automatically operated if the operator releases pressure on the

    button/switch.

    Deflagration A rapid chemical reaction in which the output of heat is sufficient to

    enable the reaction to proceed and be accelerated without input of

    heat from another source. Deflagration is a surface phenomenon

    with the reaction products flowing away from the unreacted material

    normal to the surface at subsonic velocity. The effect of a

    deflagration under confinement is an explosion. Confinement of the

    reaction increases pressure rate of reaction and temperature and may

    cause transition into a detonation.

    Detonation An exothermic reaction wave which follows, and also maintains, a

    supersonic shock front from an explosion. Such transitions are

    promoted by the increased turbulence arising from a deflagration

    flame front interacting with strong structures.

    Dispenser Pump or equipment used to dispense fuel at a filling station.

    Docking station A docking station is a housing, pad or post where the dispenser

    nozzle is stored to prevent damage, ingress of dirt, or moisture. A

    docking station for an LNG nozzle may be heated to prevent the

    build up of ice and condensation.

    Dry air Air with a maximum dew point of -40 ºC.

    Embrittlement Embrittlement is a loss of ductility of a material making it brittle.

    Embrittlement of some carbon steels may be caused as a result of

    exposure to low temperature gases, for example, from a liquefied

    gas. Hydrogen embrittlement is the effect of hydrogen absorption

    on some metals and alloys. The degradation of a structural material

    may result in failure or a leak.

    Explosion A nuclear, chemical or physical process leading to the sudden

    release of energy (and usually gases and heat) giving rise to external

    pressure waves.

  • 8 BCGA 41 – Revision 2

    Equipment supplier

    / installer

    The company or companies, as contracted by the Owner / User, to

    provide and install the equipment used to store, distribute and

    dispense a specific fuel gas.

    Fast-fill For natural gas, a filling operation that takes a similar amount of

    time as current liquid fuels to fill.

    Filling station A facility for the storage and dispensing, normally to the general

    public, of products used as fuels for motor vehicles. These can

    include petrol, diesel, autogas (LPG), hydrogen, CNG, LNG and

    LCNG.

    NOTE: Hydrogen filling stations may typically be referred to as

    Hydrogen Refuelling Stations (HRS), however the term filling

    station is used for consistency with other UK documents concerning

    petrol, diesel and LPG filling stations.

    Flammable gas Gases which at 20 °C and at standard atmospheric pressure:

    (i) are ignitable when in a mixture of 13 % or less by volume with air; or

    (ii) have a flammable range with air of at least 12 percentage points regardless of the lower flammability limit.

    Forecourt attendant Responsible to the Site Operator. Directly operates and controls

    the dispenser and the discharge nozzle on behalf of the customer.

    Gas supplier The company contracted by the Owner / User to provide a specific

    fuel gas product for dispense at the filling station.

    Gaseous storage A system which includes containers, pressure regulators,

    instruments, safety-relief devices, manifolds, inter-connecting

    piping and controls. The storage system terminates at the point

    where the gas enters the distribution piping.

    Hazardous area Any place in which an explosive atmosphere may occur in quantities

    such as to require special precautions to prevent ignition during

    construction, installation or use, as applicable.

    Heavy goods

    vehicle

    Heavy Goods Vehicle (HGV) (also known as LGV, Large Goods

    Vehicle). Commercial truck with a gross combination mass of more

    than 3500 kg.

    Installation Equipment (vessels, pumps, compressors, electrolysers, reformers

    etc.), pipework, hoses, valves, instruments etc. that have been

    assembled into one or more systems that enable the generation,

    storage or dispensing of gaseous fuels.

  • 9 BCGA 41 – Revision 2

    Invacuation A variant of the commonly understood concept of evacuation (for

    example, in the event of a fire). Invacuation involves the removal

    of people to an alternative area within the site.

    Leakage See Methane Leakage

    Liquefied

    Compressed

    Natural Gas

    (LCNG)

    LNG warmed and vaporised to product CNG for dispensing

    Liquefied natural

    gas

    Liquefied natural gas (LNG), including methane and biomethane

    (LBG).

    LNG Vaporiser A heat exchanger used for regasifying liquefied gases.

    LPG Liquefied petroleum gas

    Maintenance staff Typically employed by the equipment supplier / installer, or the

    gas supplier. Has significant understanding of the design and

    operational elements of both the gas dispensing and storage /

    generation equipment, as appropriate.

    May An option available to the user of this Code of Practice.

    Methane leakage The loss, emission of methane due to leakage, venting, coupling

    losses, for example, of the storage system. This concept is distinct

    from that of ‘methane slip’, which concerns poor combustion

    (combustion efficiency) i.e. in a vehicle using an internal

    combustion engine. Methane leakage has an undesirable

    environmental and safety impact.

    Mobile station A fueling station that can be transported with product onboard.

    Mobile workers Persons who work in more than one place or travel as part of their

    job, i.e. HGV and public service vehicle drivers.

    Multi-fuel

    dispenser

    Dispenser delivering multiple fuels, liquid or gaseous.

    Non-hazardous area Any place in which an explosive atmosphere is not expected to

    occur in quantities such as to require special precautions to prevent

    ignition during construction, installation and use.

    Odorization The process of adding an odorant to gas in order that it can be

    detected by smell.

    Owner / user The owner of a filling station. Within this Code of Practice the

    owner has the same responsibilities as the user, as defined in the

    Pressure Systems Safety Regulations (11).

  • 10 BCGA 41 – Revision 2

    Public service

    vehicle

    Public service vehicle. A vehicle such as a bus used by members

    of the public to travel to and from places on particular routes.

    Self-service

    attendant

    Responsible to the site operator. Supervises customers operating

    dispensers, with the responsibility to activate or, in the case of

    emergency, shut-off the dispenser from a defined control point.

    Separation

    distances

    Horizontal and vertical distances between the nearest part of the

    gas storage and distribution system and any specified feature (for

    example, occupied buildings, facilities, process areas, site

    boundary). The purpose of a separation distance is to protect the

    gas storage and distribution system from heat radiation should

    there be a fire in the local area, also to protect the local area from

    the effects of a fuel gas release. The intention is to provide

    sufficient time for emergency evacuation as appropriate and the

    mobilisation of additional fire-fighting equipment.

    NOTE: The term separation distance should not be confused with

    the distances involved with hazardous area classification.

    Shall Indicates a mandatory requirement for compliance with this Code

    of Practice and may also indicate a mandatory requirement within

    UK law.

    Should Identifies a preferred, but not mandatory requirement for

    compliance with this Code of Practice.

    Site operator Responsible to the owner / user. Person (or company) in charge of

    (with day to day control) a filling station i.e. the petroleum spirit

    licence holder. In some cases this will be the owner.

    Slow-fill For natural gas, a slow (or timed) filling operation that takes a

    longer amount of time than current liquid fuels to fill, and can take

    several hours.

    Tanker stand The position on a filling station where a fuel delivery tanker is

    located during the fuel delivery process.

    Tube A transportable pressure receptacle of seamless or composite

    construction having a water capacity exceeding 150 litres and of not

    more than 3000 litres.

    NOTE: Tube design is evolving and it is possible to obtain tubes

    with a water capacity greater than 3000 litres, but these do not

    comply with the current transport Regulations which define a tube.

    Unattended self-

    service

    A filling station where the dispenser is activated and operated by a

    customer without supervision by an attendant.

    Venting Controlled and uncontrolled release of gas into the atmosphere.

  • 11 BCGA 41 – Revision 2

    Vapour recovery

    equipment

    Recovers boil-off gas to prevent it from escaping into the

    atmosphere. Equipment may include a receiver, ambient vaporiser,

    compressor and buffer storage, enabling recovered gas to be

    dispensed as CNG. It may also consist of an assembly for re-

    liquefying boil-off gas from the vehicle fuel tank or road tanker,

    which is returned as LNG to the station storage vessel.

    Vulnerable

    populations

    Vulnerable populations include those who may not be easy to

    evacuate from premises because of, for example, age or infirmity,

    including schools, hospitals, old people’s homes and other

    residential accommodation.

  • 12 BCGA 41 – Revision 2

    CODE OF PRACTICE 41

    THE DESIGN, CONSTRUCTION, MAINTENANCE AND OPERATION

    OF FILLING STATIONS DISPENSING GASEOUS FUELS

    1. INTRODUCTION

    Globally there is a growing awareness of the environmental concerns around the use of

    traditional fuels. Low, or zero emissions from exhausts and a reduced carbon footprint are

    part of the future. The use of alternative fuels for vehicles is becoming more widespread in

    the UK. The use of liquefied petroleum gas (LPG) is well established and the technical and

    safety requirements for other gaseous fuels are being developed. All fuels are subject to UK

    legislation or guidance.

    Alternative gaseous fuels have a part to play in reducing UK carbon emissions, as recognised

    in the European Commission Clean Power for Transport package of measures, which aims to

    ensure the build-up of alternative fuel stations across Europe together with common standards

    for their design and use. This package includes a European alternative fuels strategy,

    European Communication 2013/17/EC (31), and a Directive on the deployment of a

    European alternative fuels infrastructure, European Directive 2014/94/EU (35). To

    implement this Directive the UK has enacted the Alternative Fuels Infrastructure Regulations

    (23).

    A number of international standards, national standards and industry documents from other

    countries relating to the design and operation of alternative fuel vehicle filling stations have

    been published, or are currently in the process of being developed.

    The British Compressed Gases Association (BCGA) recognises that the alternative gaseous

    fuels industry is still developing and this document signposts the important points of multiple

    guidance documents.

    The BCGA acknowledges that there are discrepancies between several of these documents

    and that there will inevitably be revisions required in future. However, given the legally-

    binding UK national requirement to reduce carbon emissions, the BCGA has taken the

    decision to publish this signpost document to facilitate the timely development of alternative

    gaseous filling station infrastructure.

    The BCGA seeks to provide with this Code of Practice a minimum industry standard to

    ensure a consistent high level of safety and to provide a reference document for those

    involved in the design, planning, operation and regulatory approval of alternative gaseous

    fuel stations.

    The BCGA will review this document at intervals to continually reflect the experience of this

    growing industry and welcomes suggestions from interested parties.

    This code of practice is intended to outline the major technical and safety considerations

    required in the UK during the design, construction, maintenance and operation of vehicle

    filling stations which incorporate filling facilities for liquefied natural gas (LNG),

  • 13 BCGA 41 – Revision 2

    compressed natural gas (CNG) and hydrogen (H2), drawn from existing BCGA publications

    and other major documents in order to comply with more general safety regulations and to

    ensure safe operation.

    For more traditional vehicle fuels such as petrol, diesel and LPG , the primary publication for

    the requirements of the design, construction, modification, maintenance and

    decommissioning of filling stations, published by the Association for Petroleum and

    Explosives Administration (APEA) and Energy Institute (EI), is the Design, construction,

    modification, maintenance and decommissioning of filling stations (the Blue Book) (103). It

    has been produced jointly by the APEA and the EI with input from the Health and Safety

    Executive (HSE) and other industry stakeholders.

    This code of practice is designed to be complementary to the Blue Book (103). Where

    gaseous fuels and traditional fuels are dispensed at the same filling station, due regard should

    be taken of both this code of practice and the Blue Book (103). Specific guidance for

    dispensing hydrogen alongside traditional vehicle fuels is available in a supplement to the

    Blue Book (103), Guidance on hydrogen delivery systems for refuelling of motor vehicles co-

    located with petrol fuelling stations (104), which has been jointly developed by the EI, APEA

    and BCGA.

    There are differences between the various gaseous fuels covered by this code of practice and

    these should be taken into account.

    Whilst both CNG and gaseous hydrogen are typically stored at high pressure, the pressures

    involved in hydrogen vehicle filling are likely to be considerably higher than those involved

    with CNG vehicle filling. The risk of harm / damage to the surroundings due to leakage from

    the installation should therefore take into consideration the storage and operational pressures

    of the gas, and may require more extensive safeguards for high pressure hydrogen systems.

    In addition, the security of the storage and delivery areas shall be assessed. It is likely

    however that both CNG and hydrogen fuel installations will have the same risk of damage by

    3rd parties etc. Thus civil engineering protection of both types of filling stations is similar.

    The principle hazards associated with hydrogen are:

    Flammability;

    Asphyxiation;

    Material embrittlement and subsequent mechanical failure;

    Increased likelihood of leakage from joints, due to smaller molecular size and where applicable, higher pressures;

    Undetected leaks due to lack of odour;

    Undetected fire due to invisible flame;

    Increased likelihood of ignition of a leak;

    For liquid hydrogen, cold burns when exposed to the skin;

  • 14 BCGA 41 – Revision 2

    Increased risk of injury as a result of uncontrolled release of high pressure gas;

    Potential transition of an explosion from deflagration to detonation.

    CNG and LNG are relatively new road fuels in the UK. Although natural gas as an energy

    source for domestic households, commercial property and industry is well accepted, there are

    major differences that have to be observed when using natural gas as a road fuel.

    CNG is natural gas that has been compressed to a high pressure, typically 200 to 300 bar (20

    to 30 MPa) in order that large volumes of energy can be stored, enabling it to be used in

    vehicles as a replacement or substitute to current liquid fuels. The high-pressure gas can be

    stored in steel or composite cylinders of various diameters and lengths.

    The principle hazards associated with CNG are as follows:

    Flammability;

    Asphyxiation;

    Undetected leaks due to lack of odour, where applicable;

    Undetected fire due to difficult to see flame. CNG has a blue flame, which under certain light conditions may be hard to see.

    Increased risk of injury as a result of uncontrolled release of high-pressure gas.

    LNG is natural gas in a liquid form, as a cryogenic it is cooled to approximately -162 ºC. It is

    mainly used as an energy source for heavy-duty road transport and can be converted back

    into a gaseous state when delivered to a cryogenic storage vessel and warmed to ambient

    temperature.

    The principle hazards associated with LNG are as follows:

    Flammability;

    Asphyxiation;

    Cold burns when exposed to the skin;

    Undetected leaks due to lack of odour;

    Undetected fire due to difficult to see flame;

    Material low-temperature embrittlement and subsequent mechanical failure (to mild and carbon steels);

  • 15 BCGA 41 – Revision 2

    If LNG is released it flashes. The vapours are initially heavier than air and will form a gas cloud close to the ground, which will eventually dissipate. However, under

    specific conditions, where a vapour cloud exists with LNG between its lower and

    higher flammability limits in air (5 % to 15 %), if a source of ignition is present the

    vapour cloud could ignite, and this may be some distance from the actual release

    source. Vapour clouds also introduce hazards from the visual impairment they create.

    Other specific considerations are outlined in Appendix 4.

    Some of the important international reference documents addressing the design and operation

    of hydrogen vehicle filling stations include:

    ISO/TS 20100 (64), Gaseous hydrogen. Fuelling stations. (Document withdrawn, reference only).

    ISO/TS 19880 (63), Gaseous hydrogen. Fuelling stations. Part 1. General requirements.

    USA - NFPA 2 (109), Hydrogen technologies code.

    Germany - VdTÜV MB DRGA 514 (113), Requirements for hydrogen fuelling stations, Compressed gases 514.

    Some of the important international reference documents addressing the design and operation

    of CNG vehicle filling stations include:

    ISO 16923 (56), Natural gas fuelling stations. CNG stations for fuelling vehicles.

    The Institute of Gas Engineers and Managers (IGEM) UP/20 (99), Natural gas fuelling stations.

    USA - NFPA 52 (110), Vehicular natural gas fuel systems code.

    Germany - G651/vdTUV M510 (112), Natural gas stations.

    Netherlands – PGS 25 (114), Natural gas delivery systems for vehicles.

    Israel - SI 6236 (116), Compressed natural gas (CNG) fuelling stations for vehicles.

    Some of the important international reference documents addressing the design and operation

    of LNG vehicle filling stations include:

    ISO 16924 (57), Natural gas fuelling stations. LNG stations for fuelling vehicles.

    IGEM/UP/21 (100), Liquefied natural gas fuelling stations. (Draft under development).

    NFPA 52 (110).

  • 16 BCGA 41 – Revision 2

    Netherlands – PGS 33 (115), Natural Gas. Liquefied natural gas (LNG) delivery installations for vehicles.

    Other relevant documents that may be of interest to the reader are listed in Section 16.

    This document is not a Design Code. The user of this Code of Practice shall make reference

    where applicable to UK legislation and internationally recognised Standards where these

    apply and should also take into account the specific practices of the UK industrial gases

    companies.

    All new installations or modifications to existing installations shall, as far as is reasonably

    practicable, comply with this Code of Practice for the products or services involved.

    This Code of Practice, along with the range of other BCGA publications, represents the

    BCGA’s view of minimum requirements for safe practice.

    2. SCOPE

    This Code of Practice covers the location, design, installation, commissioning, operation,

    maintenance and inspection of equipment used in a filling station for vehicle filling with

    gaseous hydrogen, CNG, or LNG, with or without the dispensing of other vehicle fuels such

    as petrol, diesel, liquefied petroleum gas (LPG) etc.

    This document covers the delivery or on-site generation of the fuel (including compression as

    appropriate), and equipment associated with storage and dispensing of the fuels included in

    the scope. It includes guidance on emergency procedures, appropriate signage, and the

    requirement for competent operating staff for the site, it also covers those carrying out filling

    activities, which may include members of the public.

    Storage of the fuel may be as a compressed or liquefied gas.

    Recommendations of best practice are outlined to assist in compliance with UK regulations to

    ensure the safety of the general public, and employees at a vehicle filling station:

    BCGA Code of Practice (CP) 4 (91), Industrial gas cylinder manifolds and gas distribution pipework (excluding acetylene), covers the distribution of gases.

    BCGA CP 33 (92), The bulk storage of gaseous hydrogen at users’ premises, covers storage and distribution of gaseous hydrogen in the UK.

    BCGA CP 39 (93), In-service requirements of pressure equipment (gas storage and distribution systems).

    BCGA CP 44 (94), The storage of gas cylinders, where gas cylinders are not connected.

    BCGA CP 46 (95), The storage of cryogenic flammable fluids, covers the storage of liquid hydrogen and LNG in the UK.

  • 17 BCGA 41 – Revision 2

    IGEM UP/20 (99) covers the supply of natural gas from the grid or mobile CNG storage, compression and dispensing of CNG to vehicles in the UK.

    IGEM UP/21 (100) covers the supply of LNG from road tanker to storage and dispensing of LNG to vehicles and mobile stations in the UK.

    NOTE: IGEM UP/21 (100) is still under development.

    The relationship and interactions between these primary documents prepared to cover LNG,

    CNG and hydrogen vehicle filling is shown in Figures 1 & 2. Where petrol is also dispensed

    at the filling station, the requirements of the Blue Book (103 & 104) should be addressed.

    Further reference appropriate to the use of flammable gases in the UK is made to:

    European Industrial Gases Association (EIGA) Document 6 (82), Safety in storage, handling and distribution of liquid hydrogen.

    EIGA Document 15 (83), Gaseous hydrogen stations, covers gaseous hydrogen, compression, purification, filling into containers and storage installations at consumer

    sites.

    BS EN 13645 (47), Installation and equipment for liquefied natural gas. Design of onshore installations with a storage capacity between 5t and 200t, in the primary

    case.

    In the absence of any other appropriate UK guidance for gaseous fuelled vehicle filling,

    separation distances have been incorporated based on existing published guidance. It should

    however be recognised that those currently included for compressed hydrogen, taken from

    BCGA CP 4 (91) and BCGA CP 33 (92), are not necessarily intended for the pressures

    encountered in a hydrogen vehicle filling station, which can be as high as 1000 bar. To allow

    for this, where these distances are used, a reduced maximum internal pipe diameter of 8 mm

    is recommended for hydrogen systems above 200 bar. For greater pipe diameters, it may be

    appropriate to extend these distances. For systems operating at lower pressures, e.g.

    production equipment, these separation distances may be conservative, and other methods of

    determining the appropriate separation distances may be justifiable.

    For potential leak points in the pipework and equipment involved in the dispensing of

    gaseous hydrogen, isolated from the storage vessels outside of a filling activity, separation

    distances taken from BCGA CP 4 (91) are recommended, again assuming a maximum

    internal pipe diameter of 8 mm.

    This Code of Practice does not include the requirements for a gaseous-fuelled vehicle, for

    which up-to-date information should be sought from the Department for Transport (DfT). It

    does not cover the general requirements of petroleum, diesel or liquid petroleum gas (LPG)

    vehicle filling station, which are all adequately covered in other industry standard

    publications. For information on LPG refer to the UKLPG Trade Association and their

    document UKLPG CP 20 (117), Automotive LPG refuelling facilities.

  • 18 BCGA 41 – Revision 2

    Figure 1. LNG and CNG

    Figure 2: Hydrogen

  • 19 BCGA 41 – Revision 2

    3. RISK MANAGEMENT

    3.1 General The control of risks shall be managed throughout the lifetime of the filling station.

    Suitable and sufficient risk assessments shall be conducted. Advice on carrying out

    risk assessments is available on the BCGA website (www.bcga.co.uk – Gas Topics –

    Risk Assessments).

    3.2 Principle legal requirements

    Health and Safety at Work etc. Act

    Compliance with Health and Safety at Work etc. Act (1) and its subsidiary health and

    safety legislation shall be maintained and should be demonstrable.

    Management of Health and Safety at Work Regulations

    The Management of Health and Safety at Work Regulations (10) contain general

    requirements for employers and the self-employed to assess the risks to workers and

    others (including the general public) who may be affected by their undertaking, so that

    they can decide on what measures should be taken to comply with health and safety

    law.

    ATEX Directives / Dangerous Substances and Explosive Atmospheres Regulations

    Areas in filling stations used for the production, storage and dispensing of flammable

    gases are within the scope of the Dangerous Substances and Explosive Atmospheres

    Regulations (DSEAR) (14) and will require a risk assessment, with classification into

    appropriate hazardous areas, based on the anticipated size of a release of flammable

    material and the degree of ventilation in each area.

    Further guidance is available in HSE L138 (79), DSEAR. Approved code of practice

    and guidance. Guidance on DSEAR (14) risk assessments is available in BCGA

    Guidance Note (GN) 13 (96), DSEAR Risk Assessment.

    In the UK the requirements of the ATEX Workplace Directive (25) were put into effect

    through DSEAR (14). The requirements of the ATEX Equipment Directive (24) were

    implemented by the Equipment and Protective Systems Intended for Use in Potentially

    Explosive Atmospheres (EPS) Regulations (6). Compliance with DSEAR (14) and the

    EPS Regulations (6) is sufficient to confirm compliance with these Directives.

    NOTE: ATEX is the name commonly given to the two European Directives for

    controlling explosive atmospheres. These are:

    European Directive 99/92/EC (25) (also known as 'ATEX 137' or the 'ATEX Workplace Directive') on minimum requirements for improving the health

    and safety protection of workers potentially at risk from explosive atmospheres.

    European Directive 94/9/EC (24) (also known as 'ATEX 95' or 'the ATEX Equipment Directive') on the approximation of the laws of Members States

    concerning equipment and protective systems intended for use in potentially

    explosive atmospheres.

    http://www.bcga.co.uk/

  • 20 BCGA 41 – Revision 2

    All equipment installed in hazardous areas shall be appropriately certified according to

    the ATEX Equipment Directive (24) for the type of hazardous area in which the

    equipment is installed. On sites where multiple fuels are dispensed, consideration shall

    be given to the properties and hazards of each fuel. This may require different ATEX

    gas group classifications, for instance for hydrogen installations which due to the low

    ignition energy of hydrogen, require equipment rated for gas group IIC hazardous

    areas.

    A document defining the hazardous areas associated with the plant and equipment

    throughout the life cycle of the plant and the safety precautions that need to be taken

    shall be created and kept up to date. This could take the form of a DSEAR (14) risk

    assessment or an Explosion Protection Document, refer to the ATEX Workplace

    Directive (25). Notably DSEAR (14) makes no mention an Explosion Protection

    Document but the requirement for up to date information is very much a part of the UK

    regulation and an Explosion Protection Document fits the need.

    Where gaseous fuels and traditional fuels are dispensed at the same filling station,

    specific guidance for the hazardous areas associated with petrol and diesel delivery,

    storage, dispensing and service ducts and chambers etc. is available in the Blue Book

    (103 & 104).

    For specific information for natural gas installations refer to IGEM SR/25 (101),

    Hazardous area classification of natural gas installations.

    Provision and Use of Work Equipment Regulations

    The Provision and Use of Work Equipment Regulations (PUWER) (9) requires that an

    inspection and maintenance regime shall be in place to ensure the safety and suitability

    of equipment on site. Refer to BCGA CP 39 (93).

    Pressure Systems Safety Regulations

    The Pressure Systems Safety Regulations (PSSR) (11) require a Written Scheme of

    Examination to be drawn up or certified by a competent person. Examinations shall be

    undertaken prior to use and thereafter in accordance to the Written Scheme of

    Examination. For further information refer to HSE L122 (77), Safety of pressure

    systems. PSSR 2000. Approved Code of Practice, and BCGA CP 39 (93).

    Refer to Section 7, Design of filling station, for all other relevant legislation.

    3.3 Environmental risk assessments

    Risk assessments shall take into consideration the potential effect of gaseous fuels on

    the environment.

    Specific legislation requires environmental risks from dangerous, hazardous or

    polluting substances to be assessed and controlled and it is therefore important that any

    risk assessment is carried out not in isolation but as part of an overall assessment for a

    site. Consideration may be required for potential cross-contamination of and

    interaction between different products.

    Where environmental risks dictate, for example, where fuel spillages may have an

    impact, an effective incident response plan should be implemented.

  • 21 BCGA 41 – Revision 2

    European Directive 2010/75/EU (28) on industrial emissions (integrated pollution

    prevention and control) (IED), requires permits where a site is manufacturing

    hydrogen. This is implemented in the UK through legislation such as the

    Environmental Permitting (England and Wales) Regulations (22) and the Pollution

    Prevention and Control (Scotland) Regulations (16).

    4. PRE-DESIGN

    The pre-design phase is a recommended important step in the station design and installation

    process. The level of detail should be suitable to determine all relevant factors including

    existing site conditions and refuelling requirements.

    The pre-design assessment should consider:

    Location - new or integration into existing;

    Size and types of vehicles to be refuelled;

    Retail or non-retail; public or private access;

    Permanent or mobile facility;

    Projected growth;

    Fuelling behaviour and ergonomics (personnel and vehicles), access and egress, and vehicle traffic flow on site;

    Fuel type(s);

    Fuel quality;

    Integration with existing fuels on site (e.g. in compliance with the Blue Book (103 & 104), etc.);

    Number and type of dispensers to meet refuelling requirements, including any interoperability requirements, refer to the Alternative Fuels Infrastructure Regulations

    (23);

    Planning permission and permit control;

    Quantity of fuel to be stored (consents and permitting), including compliance, as appropriate, with the Control of Major Accident Hazards Regulations (COMAH) (19);

    Available space, boundary and separation distances;

  • 22 BCGA 41 – Revision 2

    Available utilities (water, access to grid, electrical power);

    Site conditions in relation to construction (wind loading, stability for vertical vessels or other equipment, seismic activity if applicable, flood risks, etc.);

    Location of drains, manholes and culverts and other services including overhead and underground power lines;

    Civil engineering;

    Dedicated off-loading areas for incoming fuel deliveries, refer to BCGA CP 46 (95);

    Tanker movements on site;

    Site management, supervision and security.

    5.0 PLANNING PERMISSION AND PERMITS

    5.1 General

    Responsibility for planning rests with the local planning authorities (in accordance with

    the Town and Country Planning Act (2)). If planning permission is required, it should

    be obtained before any work begins. The local fire authority should be involved at

    planning stage.

    Stability and ground evaluation, landscaping, height restrictions and grid connection

    should all, where relevant, be taken into consideration.

    Generation of hydrogen on site, (whether from steam methane reforming (SMR),

    electrolysis or other sources), for commercial activities currently requires a permit

    under the IED (28), refer to Section 3.3.

    5.2 Storage

    Depending on the quantity of stored fuel gas, refer to Table 1, consent may be required

    from the Hazardous Substances Authority (HSA) in accordance with the Planning

    (Hazardous Substances) Regulations (20) or the COMAH (19) Regulations. Under

    COMAH (19), where sub-threshold quantities of dangerous substances are stored,

    consideration should be given to the total quantity of products stored on a site

    according to the aggregation rule, this will include petroleum, diesel, LPG and other

    listed substances, in addition to any alternative vehicle fuels.

    NOTE: The requirements of the EU Seveso III Directive 2012/18/EU (30) are

    implemented by COMAH (19) in the UK.

    In addition, the Dangerous Substances (Notification and Marking of Sites) Regulations

    (NAMOS) (5) require notification to the authorities where a total quantity of hazardous

    products of 25 tonnes or more are stored. Specific exemptions apply.

  • 23 BCGA 41 – Revision 2

    Planning (Hazardous

    Substances) Regulations

    COMAH Regulations

    Lower tier Upper tier

    Hydrogen 2 tonnes 5 tonnes 50 tonnes

    CNG 15 tonnes 50 tonnes 200 tonnes

    LNG 15 tonnes 50 tonnes 200 tonnes

    Table 1: Thresholds for the different fuel gases

    5.3 Multi-fuel stations

    The Petroleum (Consolidation) Regulations (17) require that anyone operating a petrol

    filling and/or storage station shall have a storage certificate issued by their local

    Petroleum Enforcement Authority (PEA). The PEA will usually require the installation

    to meet the requirements of the Blue Book (103 & 104).

    The requirement applies both to retail and non-retail filling stations i.e. those that

    dispense petrol to the general public and those, which only dispense petrol into their

    own vehicles. As part of the PEA assessment of a petrol filling station, prior to issuing

    a storage certificate, the PEA will ensure that the arrangements for any other fuels

    stored and dispensed on the site are also appropriate, and that the risks associated with

    the fuels are controlled so as not to impact upon each other.

    6. LAYOUT AND SITE SELECTION CRITERIA

    6.1 General

    Storage installations and production equipment shall be contained within secured areas.

    Table 2 displays the typical components of an installation for various fuels.

    The principle hazard from gaseous fuels is fire, but there may also be an environmental

    hazard. Certain gases, such as methane or refrigerant gases, if released, are greenhouse

    gases. Hydrogen does not generally have an environmental impact. Where there is an

    impact on traditional fuels (petrol, diesel) these can contaminate the local land (and

    therefore water courses). Where assessments for different hazards (i.e. fire and

    environmental) indicate different standards are required then the most stringent control

    measures should be applied.

    Where multiple fuel types are installed on a site, it may be useful to consider the detailed

    design of these areas separately, although the influence of each area on other aspects of

    the filling station shall also be reviewed holistically within the risk assessment. This is

    particularly important where there are a large number of variables and there are gaps or

    inconsistencies in standards and guidance, as may be the case with these emerging

    technologies. Risk assessments shall take into account the anticipated effects and

    consequences, including those offsite, of potential fire and explosion hazards.

    Recommended minimum separation distances to non-classified electrics on installations

    are listed in Appendix 1 and Appendix 2.

  • 24 BCGA 41 – Revision 2

    Fuel as

    stored

    Fuel

    deliveries

    Fuel as

    dispensed

    Compression Storage Pipework Dispenser

    Hydrogen

    (gaseous)

    Cylinder /

    tube trailer

    / on-site

    generation Hydrogen

    (gaseous) Optional Yes Yes Yes

    Hydrogen

    (liquid) Tanker

    CNG Pipeline /

    cylinders /

    tube trailer

    CNG Yes Yes Yes Yes

    LNG Tanker LNG No Yes Yes Yes

    Table 2: Typical components of a fuel filling installation

    Where there is a desire to convert existing liquid-fuel dispense installations to gas fuel

    dispensing (either as an exchange or both types together), the inherent hazards of the

    various (and alternative) fuels with respect to buoyancy and ignition energy shall be

    addressed through the DSEAR (14) risk assessment process.

    NOTE: Such aspects will usually be significantly different to those encountered

    when dealing with traditional liquid fuels alone. Consideration should be given to

    unintentional releases, vents and leaks.

    Forecourt design criteria for petrol filling stations can be obtained from the Petroleum

    Enforcement Liaison Group (PELG), Petrol filling stations guidance on managing the

    risks of fire and explosion (The Red Guide) (105) and the Blue Book (103 & 104).

    Further information is available from the Energy Institute (EI) 15 (102), Model code of

    safe practice Part 15: Area classification code for installations handling flammable

    fluids.

    NOTE: EI 15 (102) covers hydrogen installations in the context of refineries,

    chemical plants, battery rooms and analyser houses.

    Suitable access to all areas of the filling station for emergency personnel and equipment

    shall be considered as part of the fire risk assessment. Refer to the Regulatory Reform

    (Fire Safety) Order (15).

    6.2 Location of storage installation

    The location of storage vessels is often critical within a filling station layout. Storage

    vessels are typically designed for external use; however, some components may require

    weather protection. Wherever practicable, the storage installation should be located:

    in an external area;

    in an area that is secure;

    where there is good natural ventilation;

  • 25 BCGA 41 – Revision 2

    where there are no sources of ignition, or where any potential sources of ignition are managed, for example, in compliance with DSEAR (14).

    Other locations are discouraged but may be considered after a suitable and sufficient

    risk assessment has been completed.

    Cryogenic storage vessels for flammable fluids shall be located in accordance with and

    conform to BCGA CP 46 (95).

    Where location of storage vessels underground is essential, recommendations for

    underground natural gas storage installations can be found in IGEM/UP/20 (99), ISO

    16923 (56), IGEM UP/21 (100) and ISO 16924 (57). Recommendations for

    underground hydrogen storage installations can be found in ISO/TS 20100 (64) and

    EIGA Document 171 (89), Storage of hydrogen in systems located underground.

    Where there are enclosed or semi-enclosed storage areas (for example, to provide

    protection from the weather), they shall be constructed in such a way as to provide no

    opportunity for the build-up of flammable gases in enclosed or confined spaces.

    Requirements for ventilation shall be determined according to BS EN 60079-10-1 (68),

    Explosive atmospheres - Part 10-1 - Classification of areas - Explosive gas

    atmospheres, or equivalent guidance as part of the DSEAR (14) risk assessment process

    with hazardous areas defined as appropriate. Consideration should be given to any

    potential hazards or risks relating to the location and operation of the installation.

    Different layout requirements may be necessary for each fuel according to their

    physical properties. CNG is typically stored at pressures of 200 bar to 300 bar.

    Hydrogen may be stored at significantly higher pressures, up to 1000 bar. Separation

    distances should take into consideration the gas pressures used. LNG and liquid

    hydrogen are stored at lower pressures, typically less than 20 bar. However, they are

    stored at low temperatures with LNG around -162 °C and liquid hydrogen around

    -253 °C. Filling stations for cryogenic liquids require unique layout considerations to

    allow for the management of released vapour. The layout and design should consider

    the effects of a release of a cryogenic liquid, such that any release can rapidly evaporate

    and will have only a minimum effect on the storage tank supporting structure, such that

    the storage tank will remain adequately supported.

    This requirement, location, efficiency and access to connecting pipework shall be

    considered during the early stages of concept design, refer to Section 6.5.

    Gaseous hydrogen bulk storage installations shall conform to BCGA CP 33 (92).

    Further information on compressed hydrogen storage can be found in NFPA 2 (109)

    and NFPA 55 (111), Compressed gases and cryogenic fluids code, also ISO/TS 20100

    (64).

    LNG bulk storage installations shall conform to BCGA 46 (95). Further guidance is

    available in IGEM UP/21 (100) and ISO 16924 (57).

    Further guidelines for general practice can be found in EIGA Document 114 (87),

    Operation of static cryogenic vessels, and BS EN ISO 21009-2 (65), Cryogenic vessels.

    Static vacuum insulated vessels. Operational requirements.

  • 26 BCGA 41 – Revision 2

    Specific recommendations for liquid hydrogen storage can be found in EIGA

    Document 6 (82). Further information for liquid hydrogen storage can be found in

    NFPA 2 (109), NFPA 55 (111) and ISO/TS 20100 (64).

    Specific recommendations for LNG storage installations can be found in BS EN 13645

    (47). Further information for LNG storage installations can be found in IGEM/UP/21

    (100), ISO 16924 (57), BCGA CP 46 (95) and NFPA 52 (110).

    Physical separation of the storage installation from exposures or sources of hazard shall

    be enforced to minimise the consequences of minor incidents. Consideration shall be

    given to hazards arising from both flammable atmospheres and heat flux following

    ignition. Consideration shall also be given to the method of delivery of fuel to the

    storage installation. The DSEAR (14) risk assessment shall cover all hazards that may

    arise during the delivery of fuel, and any additional control measures that may be

    required during this period. Where necessary, guidance on vehicle impact protection is

    included in Section 6.4. Consideration should also be given to impact avoidance for the

    road tanker or mobile gaseous fuel trailer during offloading, and when the tanker or

    trailer is parked (e.g. by using cones or possibly barriers). Vehicle refuelling whilst the

    tanker or trailer is offloading should be justified by a suitable risk assessment. The

    arrangements for delivery of fuels should be considered at an early stage, as this could

    significantly increase the inventory at a site albeit it for a short period, and could

    influence other aspects of the installation design (e.g. its floor -plan).

    The separation distances in this document are intended as a guideline for both planning

    authorities and system designers and installers. They are the minimum recommended

    separation distances based upon generic considerations, which reflect both UK and

    worldwide industry experience on design and installation of liquefied and compressed

    flammable gas operations. It is the duty of the designer to ensure a comprehensive

    viewpoint is given to separation distances at multi-fuel stations, including the differing

    requirements for high-pressure ambient gaseous fuels and cryogenic liquid fuels.

    Recommended minimum separation distances for hydrogen storage installations are

    presented in Appendix 1. Where appropriate, these separation distances should be

    applied both vertically and horizontally.

    Recommended minimum separation distances for CNG and / or LNG storage

    installations are presented in Appendix 2.

    Based upon the details of a given installation it may be acceptable to reduce the

    separation distances relative to those detailed in this document. Any reductions should

    be justified based upon a site-specific risk assessment, or through the use of fire risk

    modelling or standard mitigation factors (refer to the Blue Book (103 & 104) and

    relevant industry documents).

    The risk assessment shall specifically address the nature and use of adjacent property.

    Recommended minimum separation distances may be extended where higher risks are

    identified, for instance:

    where the site is close to a heavily populated area;

  • 27 BCGA 41 – Revision 2

    where the site is close to a vulnerable population: school, hospital etc.;

    where the site is remote from external help (such as the fire authority);

    where existing site conditions may foreseeably change on either a temporary or permanent basis, i.e. change of use, future planning considerations,

    increased personnel or maintenance activities.

    If a bespoke safety case is required, guidance on a number of different methodologies

    that exist for the determination of recommended minimum separation distances can be

    found in EIGA Document 75 (86), Determination of safety distances, NFPA 2 (109)

    and ISO/TS 20100 (64). It should be noted however that these methodologies may give

    distances that are not consistent with the minimum separation distances recommended

    by the BCGA.

    In the event of a spill of a liquefied fuel gas, the liquid will both rapidly evaporate and

    travel until it settles at the lowest point (before full evaporation). It is important to

    ensure containment of the spill above ground in an area remote from personnel, where

    the liquid can evaporate safely without presenting a risk of asphyxiation, cold burns,

    ignition, or thermal shock to mechanical components. Vapour clouds which fail to

    quickly disperse may be blown by the wind and in some circumstances may have a

    potential to blow far beyond the site with a potential risk of asphyxiation or ignition.

    Where liquefied fuel gas leaks may have entered confined spaces, appropriate measures

    should be taken before personnel entry in accordance with the Confined Space

    Regulations (8). The actions to be taken in the event of a spill should be clearly

    identified, trained for, and included in the emergency response procedure, refer to

    Section 14.

    Consideration should be given to the appropriate use of civil engineering features for

    risk mitigation, for example diversion kerbs or grading, to ensure that liquid leakage

    from any adjacent hazardous store is prevented from accumulating in undesirable

    locations (e.g. within the fuel gas store). When liquefied fuel gas storage is present,

    measures should be employed to prevent spilled liquid fuel gas from flowing onto the

    forecourt, onto cold-sensitive components (e.g. non-cryogenic rated storage vessel

    support legs or skirts), into public areas or in the vicinity of other features, for example

    drains, manholes, culverts, etc. which might lead to the creation of a hazard elsewhere,

    in certain circumstances. The design and construction of the station base should allow

    for the safe dispersal (e.g. evaporation) of liquid leakage. Options such as boil-off

    pads, sloped surfaces, pits, walls, bunds etc. may be considered in this respect, noting

    that other hazards may thereby be introduced and so any such proposal should be

    validated by risk assessment. Further guidance is contained in BCGA CP 46 (95).

    Where appropriate, storage areas shall be designed to be readily accessible to mobile

    supply equipment, refer to Section 3.3 and to mobile service and safety equipment.

    The liquid storage installation shall meet the requirements of BCGA CP 46 (95).

    Fencing, civil engineering and general provisions for non-liquid installations shall

    follow the same principles (such as buffer stores, compressor houses, etc.).

  • 28 BCGA 41 – Revision 2

    The minimum recommended separation distances of Appendix 1 and Appendix 2 shall

    apply regardless of the position of the barrier or fence. If a fire resistant wall is used,

    then by the methodology outlined in BCGA CP 4 (91), the safety distance may be

    measured as the shortest distance around the ends of the wall to the storage installation.

    An important principle in the hazardous area classification is the availability of

    sufficient ventilation. The effect of firewalls can be to reduce ventilation, and this

    should be considered in the site risk assessments. Firewalls shall provide a minimum of

    30 minutes fire resistance in respect of integrity, insulation, and where applicable load

    bearing capacity. Where the wall separates vulnerable populations from the dangerous

    substance, the fire resistance provided shall be for a minimum of 60 minutes. Fire tests

    are covered in BS 476 (37), Fire tests on building materials and structures.

    If the storage area contains individual and / or bundles of cylinders, the layout shall be

    designed to allow the use of suitable manual handling equipment and as appropriate,

    forklift trucks.

    Site areas where installations used for the production, storage and dispensing of

    flammable liquids and gases and areas used for the delivery of fuels, shall not be

    located beneath overhead electrical power lines. Installations shall be sited so that

    damage to the installations or delivery vehicles by electric arcing from overhead or

    other cables cannot occur.

    6.3 Access and egress for fuel delivery vehicles

    Access and egress may be required for delivery vehicles. For cryogenic flammable

    fluids refer to BCGA CP 46 (95). Points for consideration include:

    Protection of the tank(s) and pipes from vehicle impact, for example by barriers, bollards or kerbs. Guidance on vehicle impact protection is included in

    Section 6.4;

    Avoiding, wherever practical, the requirements for delivery vehicles to reverse;

    Emergency arrangements for delivery vehicles and the delivery team; for example, requirements for the vehicle being able to drive away in a forward

    direction without complex manoeuvring in the event of an emergency, subject to

    the anti-drive-away provisions that should apply;

    Hose lengths and hose handling arrangements; for example, parking post, storage space, purging, weather protection, capping, etc.;

    Demarcation of the delivery vehicle parking location;

    Signage, lighting and surface condition;

    Drainage and spill arrangements from the delivery area;

    The construction of the delivery pad surface, taking account of the actual delivery vehicle weight, size and layout;

  • 29 BCGA 41 – Revision 2

    Space (including height clearance) for use of cranes, fork-lift trucks or other accessories when making deliveries; for example, bundles of cylinders;

    Restriction of access to the tanker stand when deliveries are being made;

    Restriction of access to the tanker stand when deliveries are not being made;

    Line-of-sight maintenance from vehicle control position to tank gauges and indicators;

    Line-of-sight maintenance from station control position to the tanker stand;

    The position of any sensors, alarms, alarm repeaters, indicators etc. for the use of the delivery team including the on-site competent person;

    Electrical earthing and equi-potential bonding facilities (and any necessary signage and instructions);

    Supply of nitrogen or dry air for road tanker discharge operation. Where relevant refer to BCGA CP 44 (94);

    Special site rules which may need to apply during (and immediately before and after) deliveries;

    The impact on the site zoning under DSEAR (14);

    Security (such as measures to prevent unauthorised removal of the road tanker or trailer from the stand, i.e. to prevent theft);

    Anti-drive-away provisions, to prevent damage to the installation (including hoses) in the event of tanker drive-away.

    For fuel delivery, the tanker stand should be designed and managed exclusively for that

    purpose. If the delivery operation cannot be contained within a secured area, temporary

    demarcation and/or other reasonable means (e.g. cones) should be considered to restrict

    public access during the delivery process.

    At stations where multiple fuels are stored or dispensed, simultaneous bulk deliveries of

    differing fuels should be prevented unless a suitable risk assessment determines

    otherwise. Further information on the delivery requirements of other fuels is detailed in

    the Blue Book (103 & 104).

    HSE L133 (78), Unloading petrol from tankers. DSEAR. Approved Code of Practice

    and guidance, whilst prepared for the delivery of petroleum products to filling stations,

    contains relevant transferable information on principles appropriate to the risk

    assessment and safe delivery of fuels to filling stations.

  • 30 BCGA 41 – Revision 2

    6.4 Location and installation of dispensing points

    A specific area should be defined for vehicle fuelling. Wherever practicable,

    dispensing equipment should be located outdoors in a freely ventilated area. Indoor

    locations may only be considered after a suitable and sufficient risk assessment has

    been completed. Further guidance for indoor hydrogen vehicle filling can be found in

    NFPA 2 (109).

    The location and proximity of dispensing equipment shall be established by risk

    assessment. Based upon the details of a given installation it may be appropriate to

    propose increased or reduced minimum separation distances relative to those detailed in

    this document. Any reductions should be justified by, for example, the use of fire risk

    and gas dispersion modelling or standard mitigation factors (refer to the Blue Book

    (103 & 104) and other relevant industry documents). The minimum separation

    distances within BCGA CP 4 (91) are recommended for the dispensing of gaseous

    hydrogen. Once established, minimum separation distances and hazardous zone

    requirements for additional dispensers and equipment shall be observed. For the

    minimum recommended separation distances refer to Appendix 1 and Appendix 2.

    Specialist storage and dispensing requirements for LNG shall be taken into

    consideration when carrying out the risk assessment.

    Where multiple dispensers are installed, e.g. for simultaneous refuelling, consideration

    shall be given to the position of the dispensers and their proximity to planned or

    existing dispensing equipment, storage and buildings, occupied and unoccupied.

    When determining the location and positioning of dispensers consideration should be

    given to traffic flow restrictions, traffic movements in the immediate vicinity of the

    station, and the size and length of the vehicles to be refuelled. Measures to prevent

    dangerous manoeuvres, for example, reversing into the path of traffic should be taken

    when considering the design of the station and the location of dispensing points.

    The vehicle fuelling area should be level, except for a minimal slope to aid surface

    drainage.

    Physical protection shall be provided to protect the dispenser from vehicular impact.

    The characteristics of the specific vehicles to be fuelled at the installation should be

    used to determine the civil engineering feature dimensions.

    Height above the road

    surface (mm)

    Clearance between

    dispenser and the edge of

    the plinth (mm)

    Stations serving light passenger

    vehicles only 120 200

    Stations serving heavy goods

    and passenger-service vehicles 415 500

    Table 3 – Typical dimensions for dispenser plinths

  • 31 BCGA 41 – Revision 2

    Dispensers shall be mounted on a plinth (or ‘island’) unless alternative physical

    protection is employed. Table 3 provides guidance on typical dimensions for dispenser

    plinths. The dimensions in Table 3 take into consideration the large diameter wheels of

    Heavy Goods Vehicles (HGV) or Public Service Vehicles and the typical vehicle

    overhang. If a station is being designed with specific vehicle types in mind, it may be

    possible to establish exact vehicle dimensions and hence design the station and plinth

    for those vehicles. Alternatively, suitable protection shall be provided to prevent

    mechanical damage to all parts of the installation and associated pipework, for example

    by the use of crash barriers or bollards. The type of vehicle expected to use the filling

    station should be considered when specifying physical protection measures. Physical

    protection arrangements for commercial vehicle filling may need to be more robust,

    larger and with greater clearances than for light passenger vehicles.

    Plinths should typically be of reinforced concrete construction, with suitable kerbs.

    Vehicle restraints are covered in BS 7669 (42), Part 3, Vehicle restraint systems. Guide

    to the installation, inspection and repair of safety fences.

    Dispensers and associated equipment may be housed in enclosures. Such enclosures

    may change the extent of the DSEAR (14) hazardous area. This may assist in the siting

    of electrical equipment, refer to Section 3. However, this advantage may be at the

    expense of the potentially explosive area within the enclosure, hence classification

    inside the enclosure or housing shall be carried out, and appropriate electrical devices

    installed, refer to Section 7.1.

    As with other areas of the filling station, where new or existing electrical equipment is

    within the hazardous area surrounding dispensing equipment, this equipment shall be

    rated for the appropriate gas group(s), for example, group IIC for hydrogen.

    If a canopy is provided over the dispensing area, refer to Section 7.9.

    All electrical devices or lighting mounted within hazardous areas around or above the

    dispenser shall be appropriately classified. Where the accumulation of flammable gas

    or vapour cannot be avoided, the inclusion of gas detection equipment should be

    considered. The gas detection system should automatically stop filling operations and

    render the installation safe, in the event of gas detection. Refer to Section 7.1.

    Dispensers shall be secured against unauthorised use and access control measures

    should be considered, for example, swipe card readers. The fuel gas supply to the

    dispenser shall be capable of being isolated. To prevent unauthorised or inadvertent re-

    activation of isolated services it is strongly recommended that the isolation point is in a

    secure location. Where the isolation point is in an area accessible to the public or

    unauthorised parties outside operating hours, it shall be fitted with appropriate security

    devices.

    6.5 Connecting pipework

    Manifolds and fuel gas distribution pipework shall comply with the requirements of

    BCGA CP 4 (91). CNG installation connections to gas supply network pipework and

    manifolds shall conform to the requirements of IGEM UP/20 (99). Further guidance

    for CNG storage as part of a vehicle filling station can be found in ISO 16923 (56) and

  • 32 BCGA 41 – Revision 2

    NFPA 52 (110). The material of construction shall be compatible with the gas,

    pressure and temperature.

    Wherever practicable, the connecting pipework between production, storage and

    dispensing equipment should be located in the open air. Where dispensers (especially

    for cryogenic services) are located on remote dispenser islands pipework should be laid

    in suitably constructed ducts.

    All pipework shall be accessible to facilitate periodic inspection, examination and/or

    testing.

    Where there is a requirement to maintain the product as a cryogenic liquid then

    pipework should be insulated, for example vacuum insulated, and kept as short and as

    straight as is reasonably practical. This will assist in minimising boil-off.

    Pipework should be marked with the pipe contents, and if possible the flow direction

    and pressure and be colour coded. Where pipework is protected by insulation materials

    then the identification markings are to be on the outside of the insulation.

    6.6 On site fuel generation equipment and related process equipment

    Fuel generation equipment shall be installed and operated according to the

    manufacturer’s recommendations.

    Where the equipment is fully enclosed, for example, for weather protection,

    requirements for explosion relief shall be considered as part of the risk assessment.

    Access is to be restricted to authorised personnel.

    6.7 Vent systems

    All gaseous fuels within the scope of this code are stored and used under pressure. As

    such they are fitted with over pressure protection devices to release excess pressure

    under normal operating conditions and in emergency situations such as fire. Manually

    operated valves may also be fitted to release pressure, for example, for maintenance.

    When these devices operate any product that is subsequently vented shall be dispersed

    safely to reduce the risk of accumulation, ignition, or impingement on personnel,

    equipment and buildings. This shall be achieved by the use of a vent system where the

    product is released via a remote vent stack.

    For information on the design, installation and marking of vent stacks installed for

    cryogenic flammable fluids refer to BCGA CP 46 (95) and EIGA 211 (90), Hydrogen

    vent systems for customer applications.

    6.8 Vent recovery

    Consideration shall be given to vent recovery and the prevention of boil-off gas

    escaping from LNG vehicles and static equipment during the refuelling process, for

    example, through the use of vapour recovery or vapour management equipment. Refer

    to ISO 16924 (57).

  • 33 BCGA 41 – Revision 2

    6.9 Other filling station activities

    Consideration should be given to the layout of the filling station with relation to

    vehicular and pedestrian movements arising from all other foreseeable filling station

    activities, for example, petrol / diesel / LPG dispensing and deliveries, shop, tyre

    inflation, car wash, customer parking etc. As far as is reasonably practicable, activities

    unrelated to vehicle filling should be located outside of hazardous areas and vehicles

    and pedestrians should not have to pass through hazardous areas to get to those

    activities. The recommended minimum separation distances should be maintained.

    Access requirements for personnel, plant and equipment shall be taken into

    consideration for operational, maintenance, inspection, testing and decommissioning

    activities.

    Large vehicles should not have to perform complex manoeuvres and the site should be

    designed and laid-out to facilitate this. An awareness should be maintained of

    pedestrian movements around the installation, in order that hazards (for example, due to

    driver’s blind-spots) may be minimised.

    7. DESIGN OF FILLING STATION

    7.1 General

    The filling station shall be designed to minimise risk to users, operating personnel,

    general public, nearby properties and the environment, as well as taking account of any

    security requirements. This is referred to as safety by design; a concept which

    incorporates fail-safe mechanisms, features and philosophy.

    Commonly, potential methods of failure, the associated consequences and mitigating

    safeguards are explored through a combination of risk identification and assessment

    methodologies including DSEAR (14) risk assessments, Hazard and Operability

    Studies (HazOpS or HAZOPS), Failure Mode and Effect Analysis (FMEA) and Layer

    of Protection Analysis (LOPA). Where in-scope safety instrumented systems are

    present, consideration shall be given to applying Safety Instrumented System (SIL)

    techniques in accordance with BS EN 61511 (71), Functional safety. Safety

    instrumented systems for the process industry sector. Specific and more detailed

    information can be obtained from BS EN 61508 (70), Functional safety of electrical /

    electronic programmable electronic safety related systems.

    Designers engaged and involved in the outline definition, detailed design, specification,

    installation and commissioning of installations in the scope of this document shall be

    suitably competent and shall have experience in the relevant field(s). Table 4 provides

    a guide to the competence requirements for Designers of specific types of installation.

    The appropriate level of reliability of control and safety systems should be determined

    through appropriate analysis and suitable risk assessment.

  • 34 BCGA 41 – Revision 2

    Fuel

    Storage

    Competence and experience required in the fields of:

    Compressed

    gases Liquefied

    cryogenic

    gases

    Flammables

    including

    ATEX/DSEAR

    Pressure

    systems

    engineering

    Fuel

    dispense

    equipment

    Hydrogen

    (gaseous) Y

    N (unless liquid

    is present) Y Y Y

    Hydrogen

    (liquefied) Y Y Y Y

    Y (if in scope)

    CNG Y N

    (unless liquid

    is present) Y Y Y

    LNG Y Y Y Y Y

    Table 4: Competence and experience guide

    The installation shall have appropriate automated safety shutdown and isolation

    capabilities and easily accessible manual emergency shutdown devices. For LNG

    automated shutdown and isolation capabilities refer to ISO 16924 (57). Due regard

    shall be given to the combination of shutdown and isolation functions for all other

    hazardous products, systems and services on the filling station site, including

    appropriately positioned emergency switching devices in accordance with the Blue

    Book (103 & 104). Safety circuitry should be hard wired using suitable latching relays

    or via a safety validated BS EN 61508 (70) compliant computer control system(s).

    The design shall comply with DSEAR (14) (taking into account fuel buoyancy), the

    PSSR (11) and, where appropriate, shall be CE marked to the relevant applicable

    European Directives, such as:

    The Pressure Equipment Directive, European Directive 2014/68/EU (PED) (34), implemented in the UK through the Pressure Equipment (Safety)

    Regulations (21);

    The Machinery Directive, European Directive 2006/42/EC (26);

    The Low Voltage Directive, European Directive 2014/35/EU (33);

    The Electromagnetic Compatibility Directive, European Directive 2014/30/EU (32);

    DSEAR (14) / ATEX European Directive 99/92/EC (25);

    European Directive 2009/104/EC (27) the Use of Work Equipment Directive for minimum health and safety requirements for the use of work

    equipment by workers at work, implemented in the UK through PUWER (9).

  • 35 BCGA 41 – Revision 2

    The design shall protect against hazards associated with loss of containment of fuel.

    The designer should typically consider the following:

    Minimising the number of potential release points and reducing the likelihood of release.

    Ventilation to maximise dilution of leaked fuel, hence keeping any resulting mixtures below flammable limits and avoiding the build-up of potentially

    explosive atmospheres or the risk of asphyxiation in confined spaces. Refer to

    the Confined Spaces Regulations (8).

    Fuel leak detection, refer to:

    o BS EN 60079 (68) Part 29, 1 to 4, Explosive atmospheres. Gas detectors;

    o Hydrogen sensing, BS ISO 26142 (67), Hydrogen detection apparatus. Stationary applications;

    o Use of LNG low temperature sensors, ISO 16924 (57) to indicate product loss.

    Emergency shutdown system(s), as appropriate.

    Hazardous area classification including of potential leak points, vents (and any hazards arising from these vents) and drains.

    Ignition protection, earthing and bonding to prevent static (and other) charge build-up.

    Mitigation against the effects of ignition, for instance blast walls, explosion relief, fire protection, etc.

    A major concern associated with the storage and dispensing of all vehicle fuels is the

    risk of fire and explosion. Both electrical and mechanical equipment can be a source of

    ignition.

    The probability of a fire and explosion hazard is reduced by the provision of good

    design and layout, as well as appropriate operating and maintenance procedures.

    Generally there are two elements to fire risk assessment. The first is the special,

    technical and organisational measures which, in respect of fuel stations, are essentially

    the precautions required to prevent the outbreak and rapid spread of a fire or explosion

    due to work activities concerning the receipt, storage and dispensing of vehicle fuels.

    Secondly, appropriate measures need to be taken to address ‘everyday’ or general fire

    risks. These include those measures necessary to prevent fire and restrict its spread and

    those measures necessary in the event of outbreak of fire, to enable those present

    (including the general public) to safely evacuate the premises.

    These general fire precautions include the means for detecting fire and giving fire

    warning, the means for fire-fighting, the means of escape, ensuring escape routes can

  • 36 BCGA 41 – Revision 2

    be used safely and effectively by employees and members of the public visiting the site,

    and the competence of employees in fire safety. The presence of a variety of different

    fuel types, comprising a blend of flammable components with differing properties

    including those soluble in water, may influence the form and consequences of any fire

    and therefore the required range of the general fire precautions. It is of critical

    importance that the presence of dangerous substances is taken into account in

    determining the general fire precautions necessary. A fire risk assessment shall be

    carried out in accordance with the Regulatory Reform (Fire Safety) Order (15). Fire

    protection equipment shall be provided as required by the site fire risk assessment.

    In hydrogen and high purity natural gas (LNG and CNG) installations consideration

    should be given to the detection of a fire. When their flames burn they can be (in

    daylight) difficult to detect by eye. The use of technologies, such as thermal imaging,

    will be advantageous.

    Other flammable substances and combustible materials shall not be stored or be

    allowed to accumulate in the vicinity of the storage or dispensing areas.

    Electrical installations shall as a minimum, conform to BS 7671 (43), Requirements for

    electrical installations. IET wiring regulations.

    All fixed electrical equipment located in hazardous zones shall have the appropriate

    ATEX rating, refer to BS EN 60079 (68), Explosive atmospheres. Part 14, Electrical

    installations design, selection and erection, taking into account the relevant gas group(s)

    classification.

    Where gaseous fuels and traditional fuels are dispensed at the same filling station,

    mandatory requirements for electrical installations are detailed in the Blue Book (103 &

    104).

    Where applicable, electrical equipment which is necessary for the installation shall be to

    BS EN 60529 (61), Specification for degrees of protection provided by enclosures,

    protection class IP54 or better. For more severe environmental conditions protection class

    IP55 (designed to protect against water jets) should be used.

    Lightning protection may be necessary to comply with local conditions or site

    regulations. Lightning protection should be considered and implemented as

    appropriate, refer to BS EN 62305 (72), Protection against lightning.

    Conductive parts (e.g. metal fitments) on the installation including fencing, gates,

    tanks and all pipework, vent stacks and vent recovery hoses, shall be adequately equi-

    potential (earth) bonded. Refer to BS 7430 (41), Code of practice for protective

    earthing of electrical installations.

    Where gas detection is identified as necessary within the risk assessment, a suitable gas

    detection system is to be fitted. For information on gas detectors refer to BS EN 60079

    (68), Explosive atmospheres – Part 29-2: Gas detectors – Selection, installation, use

    and maintenance of detectors for flammable gases and oxygen.

  • 37 BCGA 41 – Revision 2

    The locations for the gas detection equipment shall take into account the physical

    properties of the respective gases, potential release points and areas where they may

    accumulate.

    Audio / visual alarms, along with appropriate warning notices, safety signs and

    instructions, shall be positioned at strategic locations within the area and at control

    centres, as determined by the risk assessment. Alarm levels are to be set to allow action

    to be taken in the event of a release of product, providing an early warning system, but

    not such that it creates false alarms; thus allowing time for personnel to evacuate the

    area before hazardous conditions are reached i.e. flammability range and/or workplace

    exposure limits are reached.

    Detection equipment should be installed, maintained and tested in accordance with the

    manufacturer’s recommendations. Alarms should be tested regularly.

    All systems should be fail safe and programmable devices should have an appropriate

    SIL (Safety Integrity Level) rating. The gas detection system and/or any process

    control system, may interface with the emergency shut-down system.

    Adequate lighting shall be provided to allow for the identification of the product(s)

    (signage and labels), to allow normal operations, maintenance, manual handling

    activities and deliveries to be undertaken safely, as well as to assist with security. The

    light source used shall give suitable colour rendering to enable colour labelling to be

    easily recognised by persons with normal colour vision. Lighting is required to be

    appropriately located, lighting equipment and ancillaries shall be suitably rated for the

    hazardous area (if any)