collector system design
TRANSCRIPT
-
8/7/2019 Collector System Design
1/17
1
Collector System DesignCollector System DesignConsiderations for Wind FarmsConsiderations for Wind Farms
Sean CarrSean Carr
Ernst CammErnst Camm
S&C Electric Co.S&C Electric Co.
-
8/7/2019 Collector System Design
2/17
2
OverviewOverview
Challenges in wind farmChallenges in wind farm
collector systemscollector systems Design considerationsDesign considerations
for collector systemsfor collector systems
SummarySummary
The presentation will discuss theThe presentation will discuss themost prevalent collector systemmost prevalent collector systemdesign for land based wind farmsdesign for land based wind farmswith underground collectorwith underground collectorsystems.systems.
-
8/7/2019 Collector System Design
3/17
3
Challenges in Wind Farm CollectorChallenges in Wind Farm Collector
SystemsSystems
Location and terrain of windLocation and terrain of wind
farm sitefarm site Installation methodologyInstallation methodology
and constructabilityand constructability
Ice throw from windIce throw from windturbinesturbines
Length of collector systemLength of collector system
cable circuitscable circuits
Cable testing and faultCable testing and fault
locating of collector circuitslocating of collector circuits
-
8/7/2019 Collector System Design
4/17
4
Design Considerations for CollectorDesign Considerations for Collector
SystemsSystems
Most common voltage levels for collector systemsMost common voltage levels for collector systems
15 kV15 kV
25 kV25 kV
35 kV (most typical)/46 kV (Canada)35 kV (most typical)/46 kV (Canada) 35 kV is the most common system voltage utilized35 kV is the most common system voltage utilized
for wind farm collector systems because of the longfor wind farm collector systems because of the longcircuit lengths and loading requirementscircuit lengths and loading requirements
UK voltages typically 11 kV and 33 kVUK voltages typically 11 kV and 33 kV
-
8/7/2019 Collector System Design
5/17
5
Cable DesignCable Design
Cable insulation levelsCable insulation levels
Cable type and sizesCable type and sizes CableCable ampacitiesampacities
Load factorLoad factor
Number of circuitsNumber of circuits Cable installation geometryCable installation geometry
and methodand method
ThermalThermal resistivityresistivity andand
temperaturetemperature
Cable shield voltages andCable shield voltages and
bonding methodbonding method
-
8/7/2019 Collector System Design
6/17
6
Circuit Configuration and Soil ThermalCircuit Configuration and Soil Thermal
ResistivityResistivity Impact on AmpacityImpact on Ampacity
1 Circuit, 3 Cables, Trefoil, 90 C, 1/3 Neutral, 35 kV, 40 Direct Buried,Spaced 12 Between Circuits
270
241
2
20
19
5
162
142
134
117
0
50
100
150
200
250
300
Ampacity
90 150 300 450
RHO
Ampacity vs RHO for Single and Parallel Circuits
Trefoil
Double Ckt. Trefoil
-
8/7/2019 Collector System Design
7/17
7
Cable Sheath Bonding and GroundingCable Sheath Bonding and Grounding
Three basic methods ofThree basic methods of
sheath bondingsheath bonding singlesingle--point bondingpoint bonding
solid bondingsolid bonding
cross bondingcross bonding
NESC Sec. 9 Rule 92CNESC Sec. 9 Rule 92C
4 grounds per mile4 grounds per mile includes grounds atincludes grounds at
transformers, splices, etc.transformers, splices, etc.
Parallel groundingParallel groundingconductorconductor
-
8/7/2019 Collector System Design
8/17
8
Surge Protection Considerations for CollectorSurge Protection Considerations for Collector
SystemsSystems
Surge protection typically installed at last padSurge protection typically installed at last pad--
mounted transformer on each feeder string ofmounted transformer on each feeder string ofcollector circuitcollector circuit
Considerations in application of surge arrestersConsiderations in application of surge arresters location of arresters, type of mountinglocation of arresters, type of mounting
system groundingsystem grounding
circuit lengthcircuit length
transient analysis (EMTP) may be requiredtransient analysis (EMTP) may be required
-
8/7/2019 Collector System Design
9/17
9
System Protection Considerations forSystem Protection Considerations for
Collector SystemsCollector Systems Considerations for protection of collector systemsConsiderations for protection of collector systems
long circuit lengths may not allow for easy detection oflong circuit lengths may not allow for easy detection ofground faultsground faults system grounding (grounded vs. ungrounded)system grounding (grounded vs. ungrounded) selective coordination of collector system circuitsselective coordination of collector system circuits selective coordination with upstream padselective coordination with upstream pad--mountedmounted
transformers at WTGtransformers at WTG temporary overvoltages caused by ground faultstemporary overvoltages caused by ground faults
loss of phase during fault with single phase tripping andloss of phase during fault with single phase tripping andreclosingreclosing on transmission system or downed conductoron transmission system or downed conductor WTG may feed faults for several cyclesWTG may feed faults for several cycles
-
8/7/2019 Collector System Design
10/17
10
Collection SwitchgearCollection Switchgear
Underground distributionUnderground distribution
switchgearswitchgear MetalMetal--enclosed switchgearenclosed switchgear
Circuit breakersCircuit breakers
-
8/7/2019 Collector System Design
11/17
11
Reactive Power CompensationReactive Power Compensation
Reactive powerReactive power
compensation systems forcompensation systems formeeting interconnectmeeting interconnectrequirements (FERC 661requirements (FERC 661--A)A)for power factor and LVRT:for power factor and LVRT:
powerpower--electronicallyelectronicallyswitched capacitorsswitched capacitors
distributed staticdistributed static
compensatorscompensators mechanicallymechanically--switchedswitched
capacitorscapacitors
-
8/7/2019 Collector System Design
12/17
12
Other ConsiderationsOther Considerations
FerroresonanceFerroresonance
can occur in collector system circuits with ungrounded wyecan occur in collector system circuits with ungrounded wyeor delta primary transformer connections because of:or delta primary transformer connections because of:
single pole switching or reclosingsingle pole switching or reclosing
single phasing during faulted conditionssingle phasing during faulted conditions
preventing ferroresonance on collector systemspreventing ferroresonance on collector systems
provide grounding transformersprovide grounding transformers size of grounding transformers > 5% of feeder loadsize of grounding transformers > 5% of feeder load
-
8/7/2019 Collector System Design
13/17
13
Other ConsiderationsOther Considerations
Fault locatingFault locating
long circuit lengths can make locating and isolation oflong circuit lengths can make locating and isolation offaults difficultfaults difficult
provide sectionalizing points for circuits that do notprovide sectionalizing points for circuits that do not
exceed capabilities of fault locating equipmentexceed capabilities of fault locating equipment
include sectionalizing points for isolation and restorationinclude sectionalizing points for isolation and restoration
Use directional fault indicators at WTG transformers toUse directional fault indicators at WTG transformers to
provide for fault detection and isolationprovide for fault detection and isolation
-
8/7/2019 Collector System Design
14/17
14
Other ConsiderationsOther Considerations
SCADA systemsSCADA systems
typically installed as a part of the collector systemtypically installed as a part of the collector system design considerationsdesign considerations
circuit lengthcircuit length number of turbines on a circuitnumber of turbines on a circuit
communications protocolcommunications protocol
fiber typefiber typesinglesingle--mode fibermode fiber
multimulti
--mode fibermode fiber
-
8/7/2019 Collector System Design
15/17
15
Analytical Studies for Collector SystemsAnalytical Studies for Collector Systems
Analytical studies typically performed during theAnalytical studies typically performed during the
design phase:design phase:
cable ampacitycable ampacity
system lossessystem losses voltage drop/regulationvoltage drop/regulation
shortshort--circuit and coordinationcircuit and coordination
transients and insulation coordination (EMTP)transients and insulation coordination (EMTP)
harmonicsharmonics
-
8/7/2019 Collector System Design
16/17
16
SummarySummary
Key considerations in collector system designKey considerations in collector system design
system voltagesystem voltage insulation levelsinsulation levels
cable ampacity parameterscable ampacity parameters
load factor, installation method, bonding method,load factor, installation method, bonding method,thermal considerationsthermal considerations
other factorsother factors
surge protection, system protection, ferroresonance,surge protection, system protection, ferroresonance,SCADASCADA
collection switchgear and compensation requirementscollection switchgear and compensation requirements
-
8/7/2019 Collector System Design
17/17
17
IEEE PES Support for Wind Farm CollectorIEEE PES Support for Wind Farm Collector
System DesignSystem Design
Recommended practices/standardsRecommended practices/standards
Equipment application guidelinesEquipment application guidelines
Development and validation of equipment modelsDevelopment and validation of equipment models
TrainingTraining