column lecture

23
Column Column: Columns are defined as members that carry loads chiefly in compression. Columns are generally referred as compression member because compression force or stress dominates their behavior. Compression member includes Arch ribs Rigid frame member Compression member in trusses Shells Portion that carry axial compression Fig: Column

Upload: ahamedtouhid899

Post on 12-Apr-2015

32 views

Category:

Documents


1 download

DESCRIPTION

Design of column

TRANSCRIPT

Page 1: Column lecture

Column

Column: Columns are defined as members that carry loads chiefly in compression. Columns are generally referred as compression member because compression force or stress dominates their behavior.

Compression member includes

Arch ribs Rigid frame member Compression member in trusses Shells Portion that carry axial compression

Fig: Column

Page 2: Column lecture

Fig: Arch

Fig: Rigid Frame

Page 3: Column lecture

Fig: Compression member in trusses

Types of column according to reinforcement used

1. Member reinforced with longitudinal bars and lateral ties.2. Member reinforced with longitudinal bars and continuous spirals.3. Composite compression member reinforced with structural steel.

Type-2 Type-3

Page 4: Column lecture

Concrete contribution

Steel contribution

Column may be divided into two broad categories: Short column – fail by crushing of concrete, lateral bucking need not to be considered. Long / Slender column – fail by lateral bucking

According to loading condition column can be classified into following categories

Axially Loaded Column:

Pn= 0.85f’c (Ag-Ast) + fyAst

According to ACI Code 10.3.6

For spirally reinforced column, with ø=0.70

∅ pn( max )=0.85∅ [ 0.85 f c' ( Ag−A st )+f y A st ]

For tied reinforced column, with ø=0.65∅ pn( max )=0.80∅ [ 0.85 f c

' ( A g−A st )+f y A st ]

Page 5: Column lecture

According to ACI Code 10.9.1 (Steel Ratio of column)

Reinforcement ratio is defined by, ρ = As/Ag and the its range is 0.01≤ρ≤0.08

According to this minimum steel ration in column is 1% of gross concrete area of column

To avoid congestion most column are designed with a ratio below 0.04.

According to ACI Code 10.9.2 (Minimum no. of bar)

A minimum four longitudinal bar is required when the bar s are enclosed by spaced rectangular or circular ties.

A minimum six longitudinal bar is required when the bar s are enclosed by a continuous spiral.

According to ACI Code 7.10.5 (Design of tie)

All bars of tied columns shall be enclosed by lateral ties. At least #3 (10 mm) tie for longitudinal bars up to #10(32 mm) and at least #4 (12 mm) tie for

#11,14, and 18(36,43,57 mm) and bundled longitudinal bars must be used. Spacing should not exceed 16 diameters of longitudinal bars, 48 diameters of tie bars, nor the

least dimension of column. Every corner and alternative longitudinal bar shall have lateral support by ties having a included

angle not more than 135⁰. No bar shall be farther than 6 in. (150 mm) clear on either side from laterally supported bar.

According to ACI 7.7.1(c)

Minimum clear cover for column member = 1.5”

According to ACI 7.6.3

Clear distance between longitudinal bars shall not be less than 1.5db nor less than 1.5”.

Why value of ø is lower for column than beam:

A beam failure would normally affect only a local region, where as a column failure could result in the collapse of entire structure.

The strength of axially loaded members depends strongly on the concrete compressive strength whose quality control is very difficult in site.

Page 6: Column lecture

Fig: Tie arrangement

Page 7: Column lecture

Lateral Ties and Spiral

According to ACI code 10.9.3 (Minimum spiral reinforcement Ratio)

Spiral Reinforcement ratioρ s=0.45( Ag

Ac

−1) f c'

f y

,

Spacing of spiral can be found by, s=4 A sp

ρs dc

ACI 7.10.4: Spacing may not be less than 1” and may not be larger than 3”

Page 8: Column lecture

# 3 Tie @ 15 in c/c

15”

12.5”

2.5”

14 no # 8

Fig: Design Column Section

Example 1

Design a square tied column to support an axial dead load of 400 K and a live lode of 210 K using

f’c = 5 Ksi, and fy = 60 Ksi, and a steel ratio of about 5%. Design the necessary ties.

Solution:

1. Pu=1.2 PD+1.6 PL=1.2 × 400+1.6 ×210=816

Pu=816=0.80∅ [0.85 f c' ( Ag−A st )+ f y A st ]

→ 816=0.80∅ [0.85 f c' ( Ag−0.05 Ag )+ f y 0.05 Ag ]

→ 816=0.80(0.65) [0.85× 5 (1−0.05 )+60 × 0.05 ] Ag

→ Ag=209¿2

Column side = 14.48∈.≅ 15∈.

2. Because larger section is adopted, the steel percentage may be reduced by using Ag=225¿2

→ 816=0.80∅ [0.85 f c' ( Ag−A st )+ f y A st ]

→ 816=0.80∅ [0.85 f c' × Ag−0.85 f c

' A st+ f y A st ]→ 816=0.80× 0.65 [0.85×5×225+ A st(60−0.85 ×5)]→ A st=¿ 11 ¿2

Use fourteen no #8 bars ( A st=11.06 ¿2)`

Page 9: Column lecture

3. Design of tie: choose # 3 bar. Spacing least of following(1) S=16 db of main ¿̄16 ×1=16∈.

(2) S=48 db of tie ¿̄ 48 ×0.375=18∈.

(3) least column dimension=15∈¿ Use # 3 bar @ 15 in. c/c

Compression plus Bending of Rectangular Column

Columns loaded with axial load and uniaxial moment is designed based on factored load, which must not exceed the design strength, i.e.

øMn ≥ Mu

øPn ≥ Pu

Fig: Equivalent eccentricity of column load

Page 10: Column lecture

Strain compatibility Analysis and Interaction Diagram

Equilibrium between external and internal axial forces shown in figure c

Pn=0.85 f c' ab+ A s

' f s' −A s f s

Taking moment about the centerline of the section

M n=Pn e=0.85 f c' ab ( h

2−a

2 )+ A s' f s

' ( h2−d ')+ A s f s(d−h

2 )A column can be designed by solving the above two equations for a specific column section.

A better approach, providing the basis for practical design, is to construct a strength interaction diagram defining failure load and failure moment for a given column for the full range of eccentricities from zero to infinity.

Figure: Column subjected to eccentric compression. (a) Loaded column;

(b) Strain distribution;

(c) Stresses and force at nominal strength.

Page 11: Column lecture

Figure: Interaction diagram for nominal column strength in combined axial and bending load.Compression failure range

Tension failure range

Pn

Mn

e small

Load path for given e

eb

e large

e = 0

e =

Design Aid: With a representative column design chart column can be designed easily. And this can de done by two methods

1.a) Select trial cross section dimensions b and hb) Calculate the ratio γ based on required cover distances to the bar centroid, and select

the corresponding column design chart.

c) Calculate Kn=Pu/(∅ f c' Ag ) and Rn=Pue / (∅ f c

' A gh ), where Ag=bh .

d) From the graph, for the values found in (c), read the required reinforcement ratio ρg .

e) Calculate the total steel area A st=ρg bh.

2.a. Select the reinforcement ratio ρg

b. Choose a trial value of h and calculate e /h and γ

c. From the corresponding graph, read Kn=Pu/(∅ f c' Ag ) and calculate the required Ag

d. Calculate b=Ag/he. Revise the trial value of h if necessary to obtain a well-proportioned sectionf. Calculate the total steel area A st=ρg bh.

Example 3 [example 8.3, Nilson 14th edition]

Page 12: Column lecture

Selection of reinforcement for column of given size : In a three-story structure, an exterior column is to be designed for a service dead load of 222 kips, maximum live load of 297 kips, dead load moment of 136 ft-kips, and live load moment of 194 ft-kips. The minimum live load compatible with the full live load moment is 166 kips, obtained when no live load is placed on the roof but a full live load is placed on the second floor. Architectural considerations require that a rectangular column be used, with dimensions b = 20 in. and h = 25 in.

(a) Find the required column reinforcement for the condition that full live load acts.

(b) Check to ensure that the column is adequate for the condition of no live load on the roof.

Material strengths are F y=60,000 psi andf c' =4,000 psi.

Solution

(a) The column will be designed initially for full load, then checked for adequacy when live load is partially removed. According to the ACI safety provisions, the column must be designed for a factored load Pu=1.2 ×222+1.6 × 297=742 kips and a factored moment M u=1.2 ×136+1.6 × 194=474 ft−kips .. A column 20 ×25∈. is specified, and

reinforcement distributed around the column perimeter will be used. Bar cover is esti-mated to be 2.5 in. from the column face to the steel centerline for each bar. The column parameters (assuming bending about the strong axis) are

Kn=Pu

∅ f c' Ag

= 7420.65× 4 ×500

=0.570

Rn=M u

∅ f c' Ag h

= 474 ×120.65 × 4 ×500 ×25

=0.175

With 2.5 in. cover, the parameter,γ=(25−5)/25=0.80. For this column geometry and material strengths, Graph A.7 of Appendix A applies. From that figure, with the calculated values ofKn andRn,ρg=0.024. Thus, the required reinforcement is

A st=0.024 × 500=12¿2. Twelve No. 9 (No. 29) bars will be used, one at each corner and

two evenly spaced along each face of the column, providing A st=12¿2.

(b) With the roof live load absent, the column will carry a factored load Pu=1.2 ×222+1.6 × 166=532 kips and factored moment,M u=1.2 ×136+1.6 × 194=474 ft−kips as before. Thus, the column parameters for this

condition are

Page 13: Column lecture

# 3 Tie @ 18 in c/c

20”

22.5”

2.5”

12 no # 9

Fig: Design Column Section

Kn=Pu

∅ f c' Ag

= 5320.65× 4 ×500

=0.409

Rn=M u

∅ f c' Ag h

= 474 ×120.65 × 4 ×500 ×25

=0.175

andγ=0.80 as before. From Graph A.7 it is found that a reinforcement ratio of ρg=0.017is sufficient for this condition, less than that required in part (a), so no

modification is required.

Selecting No. 3 (No. 10) ties for trial, the maximum tie spacing must not exceed48 × 0.375=18∈. ,16 ×1.128=18.05∈¿, or 20 in. Spacing is controlled by the diameter of the ties, and No. 3 (No. 10) ties will be used at 18 in. spacing.

Page 14: Column lecture

# 4 Tie @ 15 in c/c

15”

22.5”

2.5”

8 no # 11

Fig: Design Column Section

Example 4 [example 8.4, Nilson 13th edition]

Selection of column size for a given reinforcement ratio: A column is to be designed to carry a factored load Pu=481and factored moment M u=492ft-kips. Material strengths F y=60,000 psi and f c

' =4,000 psi are specified. Cost studies for the particular location indicate

that a reinforcement ratio ρg of about 0.03 is optimum. Find the required dimensions b and h of the column. Bending will be about the strong axis, and an arrangement of steel with bars concentrated in two layers, adjacent to the outer faces of the column and parallel to the axis of bending, will be used.

Solution

It is convenient to select a trial column dimension h, perpendicular to the axis of bending; a value of h = 25 in. will be selected, and assuming a concrete cover of 2.5 in. to the bar centers, the parameterγ=0.80. Graph A. 11 of Appendix A applies. For the stated loads the eccentricity is

e=492×12481

=12.3∈., ande /h=12.3/25=0.49. From Graph A. 11 with e /h=0.49 and

ρg=0.03 , Kn=Pu /∅ f c' A g=0.51from the trial dimensionh=25∈., the required column width is

b=Pu

∅ f c' Kn hh

= 4810.65×4 ×0.51 ×25

=14.5∈.

A column 15 ×25∈. in. will be used, for which the required steel area is

A st=15 ×25 × 0.03=11.25¿2. Eight No. 11 (No. 36) bars will be used, providing A st=12.48¿2,

arranged in two layers of four bars each, similar to the sketch shown in Graph A.11

Page 15: Column lecture

Biaxial Bending: Interaction diagram of biaxially loaded column

Approximate method:

1. Load Contour Method2. Reciprocal Load Method

Reciprocal Load Method

1Pn

= 1Pnx 0

+ 1Pny 0

− 1P0

Where Pn=¿ approximate value of nominal load in biaxial bending with eccentricities ex and e y

Pny 0=¿ nominal load when only eccentricity ex is present (e y=0)

Pnx 0=¿ nominal load when only eccentricity e y is present (ex=0)

P0=¿ nominal load for concentrically loaded column

Page 16: Column lecture

Example 5 [example 8.5, Nilson 14th edition]

Design of column for biaxial bending: The 12 ×20∈.column shown below is reinforced with eight No. 9 (No. 29) bars arranged around the column perimeter, providing an area

A st=8.00¿2. A factored load P0of 255 kips is to

be applied with eccentricities e y=3in. and ex=6∈., as shown. Material strengths are

F y=60,000 psi and f c' =4,000 psi. Check Ihe

adequacy of the trial design using the reciprocal load method.

Solution

By the reciprocal load method, first considering bending about the Y axis,γ=15 /20=0.75, and e /h=6/20=0.30 . With the reinforcement ratio A st /bh=8.00/240=0.033, using the average of Graphs A.6 (γ=0.70) and A.7 (γ=0.80),

Pny 0

f c' Ag

(avg )=0.62+0.662

=0.64 → Pny 0=0.64 × 4 × 240=614 kips

P0

f c' Ag

=1.31 → P0=1. 31× 4 ×240=1258 kips

Then the bending about the X axis, γ=7 /12=0.58, and e /h=3/12=0.25Graph A.5 of the Appendix A gives

Pnx 0

f c' Ag

=0.65→ Pnx 0=0.65 × 4 ×240=624 kips

Substituting these value in 1

Pn

= 1Pnx 0

+ 1Pny 0

− 1P0

1Pn

= 1624

+ 1614

− 11258

=0.00244

From which Pn=410 kips .Thus, according to the Bresler method, the design load of Pu=0.65× 410=267 kipscan be applied safely.

[In general biaxial bending should be taken into account when the estimated eccentricity ratio approaches or exceeds 0.2]

Page 17: Column lecture
Page 18: Column lecture
Page 19: Column lecture