communication interface - schneider electric · pdf filecommunication interface ... (w ater,...

6
Communication Interface Technical data sheet Com'X 200/Com'X 210/Com'X 510

Upload: vonga

Post on 30-Jan-2018

296 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Communication Interface - Schneider Electric · PDF fileCommunication Interface ... (w ater, air, gas, Electricity, Steam) ... These energy servers also provide an interface

Communication Interface

Technical data sheet

Com'X 200/Com'X 210/Com'X 510

Page 2: Communication Interface - Schneider Electric · PDF fileCommunication Interface ... (w ater, air, gas, Electricity, Steam) ... These energy servers also provide an interface

2 PLSED310098EN

Communications Energy Server Com'X 200/ Com'X 210/Com'X 510Functions and characteristics

PB

1120

41

Ethernet GPRS data logger functionThe Enerlin'X Com'X 200, Com'X 210, and Com'X 510 Energy Servers collect and store wagES consumptions (water, air, gas, Electricity, Steam) and environmental parameters such as temperatures, humidity, and CO2 levels in a building. Data is periodically transmitted as a report to an Internet database server or to natively supported web pages and dashboards (Com'X 510).

Data processing and displayOnce received by the server, the data is ready to be processed and displayed as web pages through web services provided by Schneider Electric, such as Struxureware Energy Operation and Struxureware Energy Online. (Com'X 510 allows data visualization via web pages.)

These energy servers also provide an interface (and a Modbus transparent gateway)between Ethernet-based networks and field devices. This gateway function supports the use of monitoring software for data collection, trending, event management, analysis and further processing of serial Modbus connected devices. This gateway function supports the use of monitoring software for data collection, trending, event management, analysis and further processing of serial Modbus and I/O connected devices.

b Energy Operation. b Energy Online (Com'X 200 & Com'X 210 only). or by any private energy management platform.

b Struxureware™ Power Monitoring Expert software.

Architectureaccess to the web: choice of 3 media

Energy Server Com'X 200

PB

1143

27

Page 3: Communication Interface - Schneider Electric · PDF fileCommunication Interface ... (w ater, air, gas, Electricity, Steam) ... These energy servers also provide an interface

3PLSED310098EN

Communications Energy Server Com'X 200/ Com'X 210/Com'X 510Functions and characteristics

PB

1120

47

Com'X 200 - top view

Features b From a simple metering installation with 1 device to large metering systems, Com'X 200, Com'X 210, and Com'X 510 collect data from any Modbus TCP or serial devices, from any pulse meter, actuator and analogue sensor.

b automatic discovery of connected Modbus devices. b Connectivity to the cloud through Ethernet, wiFi and gPRS. b 2 Ethernet ports to separate upstream connection from field devices network. b Com'X 510 provides access to on-board device and circuit summary web pages, as well as on-board data logging and historical trending.

b Protocols: HTTP, HTTPS, FTP, SMTP with Proxy management. b Data publishing: Native connection to Schneider Electric Service platforms (Energy Operation, Energy Online) – CSV file export for other database servers.

b Modbus gateway functionality via Modbus TCP/Modbus RTU. b Setup through convenient built-in web pages. b Compliant with electrical switchboard environment (Temperature, electro- magnetic compatibility).

b Storage of data in case of communication failure. b Local backup of the configuration parameters. b Supports custom models of tier devices (non-Schneider Electric). when associated with Schneider Electric Services:

b Remotely managed (configuration backup, troubleshooting, parameters setting). b gPRS contract management with SIM card provided.

Part numbers

Item Com'X 200 Com'X 210 Com'X 510

Energy server EBX200 EBX210 EBX510

wi-Fi USB stick EBXa-USB-wiFi EBXa-USB-wiFi EBXa-USB-wiFi

gPRS modem with SIM card

EBXa-gPRS-SIM EBXa-gPRS-SIM EBXa-gPRS-SIM

gPRS modem without SIM card

EBXa-gPRS EBXa-gPRS EBXa-gPRS

External gPRS antenna

EBXa-aNT-5M EBXa-aNT-5M EBXa-aNT-5M

Zigbee dongle EBXa-USB-Zigbee EBXa-USB-Zigbee EBXa-USB-Zigbee

Radiotech Modbus concentrator

* * *

* Ask your SE representative for current reference information

Page 4: Communication Interface - Schneider Electric · PDF fileCommunication Interface ... (w ater, air, gas, Electricity, Steam) ... These energy servers also provide an interface

4 PLSED310098EN

Communications Energy Server Com'X 210 Com'X 510Functions and characteristics (cont.)

PB

1143

27P

B11

4326 Selection guide Com'X 200 Com'X 210 Com'X 510

Inputs6 Digital inputs

Max impulse frequency

25 Hz (min duration 20ms) IEC 62053-31 Class a b b b

Power supply Provided by Com'X 200: 12 V DC – 60 maExternal: from 10 to 30 V DC

b b b

2 analogue inputsSensor compatibility

PT100 – PT1000 2-wires probes (accuracy 1%)Sensors with 4 -20 ma or 0-10 V output (accuracy 0.5%)

b b b

Power supply Provided by Energy Server: 24 V DC - 50 ma per input b b b

CommunicationMeter Network 1 RS485 Modbus serial port, RJ45

connector, for 32 Modbus components maximum

b b b

Configuration / Data transfer

2 Ethernet ports RJ45 10/100 Base, DPwS ready b b b

Ethernet 1 PoE class 3 (802.3af), DHCP client b b b

Ethernet 2 DHCP client or server b b b

Protocols IPv4, IPv6 – HTTP, HTTPS, Modbus TCP/IP, SMTP, SNTP

USB Ports 3 b b b

For memory stick

USB port on front faceb b b

For wi-Fi stick USB port 2 behind coverb b b

gPRS modemFrequency range

880-915 MHz1710 MHz - 785 MHz824-849 MHz1850-1910 MHz

External antenna (Tri band)Frequencies

gSM: 880-896 MHz/900 MHz USaPCN: 1710-1880 MHzDCS: 18500-1990 MHzUMTS: 2.1 gHzCoax 50 Ohm

LED indicators 11b b b

Power / Boot status b b b

gPRS modem status and signal level

b b b

Modbus communication b b bEthernet communication b b bwi-Fi communication mode (access point / Infrastructure) and status

b b b

Digital inputs status and pulse reception

b b b

Power SupplyaC 100-230 V (+/- 15%)(50-60Hz) bDC 24 V (+/- 10%) b b bPower over Ethernet 15.4 w DC b b bMax power 26 w max b b b

MechanicalIP Front face IP40, terminals IP20 b b bDimensions (HxwxD) 91 x 144 x 65.8 mm b b bweight 450 g b b b

Energy Server Com'X 200 with the front face in open position, GPRS modem and Wi-Fi USB stick are connected.

PB

1120

50

Energy Server Com'X 510

Energy Server Com'X 210

Page 5: Communication Interface - Schneider Electric · PDF fileCommunication Interface ... (w ater, air, gas, Electricity, Steam) ... These energy servers also provide an interface

5PLSED310098EN

Communications Energy Server Com'X 210 Com'X 510Functions and characteristics (cont.)

Wi-Fi USB stick

PB

1120

44P

B11

2045

GPRS modem (antenna in folded position)

PB

1120

42

EnvironmentOperating temperature -25º to +60°C (-13º to +140°F)

b b b

Storage temperature -40º to +85°C (-40º to +185°F) b b b

gPRS dongle

Operating temperature

-20º to +60°C (-4º to +140°F)b b b

gPRS dongle

Storage temperature

-40º to +85°C (-40º to +185°F)b b b

wif-Fi dongle

Operating temperature

0º to +50°C (32º to +122°F)b b b

wi-Fi dongle

Storage temperature

-20º to +80°C (-4º to +176°F)b b b

Humidity 5 to 95% relative humidity (without condensation) at +55ºC b b b

Pollution Class III b b b

Safety standards / regulationInternational (CB scheme)

IEC 60950b b b

USa UL 508 b b bUSa UL 60950 b bCanada cUL 60950 b bCanada cULus 508 b b bEurope EN 60950 b b b

Quality BrandsCE, UL b b b

Page 6: Communication Interface - Schneider Electric · PDF fileCommunication Interface ... (w ater, air, gas, Electricity, Steam) ... These energy servers also provide an interface

PLSED310098EN

AR

T /

© 2

015

- S

chne

ider

Ele

ctric

- A

ll rig

hts

rese

rved

Schneider Electric Industries SAS

35, Rue Joseph Monier,

CS 30323

F - 92506 Rueil Malmaison Cedex

RCS Nanterre 954 503 439

Capital social 896 313 776

www.schneider-electric.com

As standards, specifications and designs develop from time to time, please ask

for confirmation of the information given in this document.

Design: Schneider Electric

Photos: Schneider Electric

02-2015