21 21 21 21 21 21 21 GENERAL NOTES: CONTRACTOR SHALL READ THESE DRAWINGS IN CONJUNCTION WITH THE CANADIAN ELECTRICAL CODE (CURRENT EDITION), BC BUILDING CODE (CURRENT EDITION) AND ALL PROJECT RELATED DOCUMENTATION, INCLUDING DRAWINGS AND SPECIFICATIONS FROM ALL OTHER DISCIPLINES. SCOPE OF WORK IS NOT LIMITED TO THESE DRAWINGS BUT INCLUDES ALL ITEMS AS LISTED ON DRAWINGS, SPECIFICATIONS AND ALL OTHER PROJECT RELATED DOCUMENTATION. CONTRACTOR SHALL VERIFY EXISTING SITE CONDITIONS BEFORE SUBMITTING BID AND IMMEDIATELY NOTIFY ENGINEER OF ANY SITE CONDITION THAT MIGHT HINDER OR OBSTRUCT THE ELECTRICAL INSTALLATION AND/OR DESIGN INTENT. FIELD COORDINATE INSTALLATION OF ELECTRICAL SLEEVES, CONDUITS, PULL BOXES, DEVICES AND EQUIPMENT WITH OTHER DIVISIONS ON SITE. ADJUST ELECTRICAL DEVICE AND EQUIPMENT PLACEMENT AS REQUIRED TO SUIT FIELD CONDITIONS. ALL NEW ELECTRICAL INSTALLATION SHALL BE IN CONFORMANCE WITH THE CANADIAN ELECTRICAL CODE (CURRENT EDITION) AND BC BUILDING CODE (CURRENT EDITION) INCLUDING ALL CLEARANCES AND SETBACKS. CONTRACTOR SHALL COORDINATE INSTALLATION OF ELECTRICAL DEVICES AND COMPONENTS WITH EQUIPMENT MANUFACTURERS AND SUPPLIER. NOT ALL SYSTEM COMPONENTS ARE SHOWN. CONTRACTOR SHALL PROVIDE ALL COMPONENTS, DEVICES, AND MATERIAL AS REQUIRED TO ENSURE INSTALLATION OF A COMPLETE AND OPERATIONAL SYSTEM. CONTRACTOR SHALL CONFIRM WIRING SIZING AND ENSURE THAT VOLTAGE DROPS IN ALL BRANCH CIRCUIT AND FEEDER MEET CODE REQUIREMENT. ALL WIRING SHALL BE INSTALLED IN CONDUIT SYSTEMS AS INDICATED. ALL CONDUITS SHALL BE SECURELY FASTENED TO THE BUILDING STRUCTURE. ENSURE THAT POWER, COMMUNICATION CABLES AND CONTROL WIRING ARE INSTALLED IN SEPARATE CONDUIT SYSTEMS. CONTRACTOR SHALL BOND ALL NON-CURRENT CARRYING METAL PARTS OF THE SYSTEM AS REQUIRED BY CODE. ENSURE ALL REQUIRED PARTS OF THE SYSTEM ARE BONDED AND PROTECTED. CONTRACTOR SHALL VERIFY THE NEW ELECTRICAL SYSTEMS ARE TESTED, STARTED, AND READY FOR USE PRIOR TO TURNOVER TO THE OWNER. CONTRACTOR SHALL FIELD TEST THE ENTIRE SYSTEM AND ENSURE IT IS OPERATIONAL AND READY FOR USE. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER OF ALL SYSTEMS AS PART OF THIS SCOPE OF WORK. ALL TEST REPORTS SHALL BE SUBMITTED TO ENGINEER. COMMUNITY SPORTS FIELD ELECTRICAL VERNON, BRITISH COLUMBIA AREA OF WORK DRAWING LIST NO. TITLE E-001 COVER SHEET, GENERAL NOTES, AND KEYPLAN E-002 ELECTRICAL SPECIFICATIONS 1 E-100 ELECTRICAL SITE PLAN E-102 ELECTRICAL FIELD HOUSE LIGHTING PLAN E-103 ELECTRICAL FIELD HOUSE POWER PLAN E-400 ELECTRICAL ROOM PLAN E-501 ELECTRICAL DETAILS E-600 ELECTRICAL SINGLE LINE DIAGRAM E-700 ELECTRICAL SCHEDULES 1 E-701 ELECTRICAL SCHEDULES 2 E-001 COVER SHEET, GENERAL NOTES, AND KEYPLAN SYMBOL DESCRIPTION POLE MOUNTED LIGHTING FIXTURE, TYPE AS INDICATED. SURFACE OR SUSPENDED 1X4 FIXTURE 2FT LONG WALL MOUNTED FIXTURE 4FT LONG WALL MOUNTED FIXTURE WALL MOUNTED FIXTURE CEILING MOUNTED FIXTURE SINGLE GANG SWITCH DOUBLE GANG SWITCH DUPLEX RECEPTACLE QUAD RECEPTACLE STRUCTURED WIRING OUTLET - 2 PORTS/DROPS OS OCCUPANCY SENSOR GFI GROUND FAULT INTERRUPTION SPD SURGE PROTECTED DEVICE ABOVE COUNTER ELECTRIC HEATER, TYPE AS INDICATED CEILING OCCUPANCY SENSOR PHOTOCELL BASEBOARD HEAT (SIZE AS INDICATED) COMBINATION MOTOR STARTER SOME SYMBOLS SHOWN MAY NOT APPEAR ON THE DRAWINGS SCOPE OF WORK: BUILDINGS PACKAGE: CONTRACTOR IS RESPONSIBLE FOR ALL BUILDING ELECTRICAL WORK INCLUDING FEEDER CABLES FROM THE ELECTRICAL ROOM AND BRANCH CIRCUIT WIRING TO THE FIELD HOUSE BUILDING (SOME BREAKERS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT IN THE ELECTRICAL ROOM ARE PROVIDED AS PART OF A SEPARATE PACKAGE - REFER TO THE SINGLE LINE DIAGRAM FOR DETAILS.) ALL IN BUILDING WORK AS OUTLINED IN THESE DRAWINGS, INCLUDING COORDINATION WITH OTHER DISCIPLINES, IS INCLUDED IN THIS CONTRACTORS SCOPE. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING EXTENSIONS AND PROVIDING NEW CONDUITS FOR ALL IN-GROUND CONDUITS AROUND THE BUILDING THAT WERE PROVIDED AS PART OF THE ELECTRICAL CIVIL WORKS CONTRACTOR.

Upload: vuongnhi

Post on 23-Aug-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

21

21

21

21

21

21

21

GENERAL NOTES:

CONTRACTOR SHALL READ THESE DRAWINGS IN CONJUNCTION WITH THE CANADIAN ELECTRICAL CODE (CURRENT EDITION), BC

BUILDING CODE (CURRENT EDITION) AND ALL PROJECT RELATED DOCUMENTATION, INCLUDING DRAWINGS AND SPECIFICATIONS

FROM ALL OTHER DISCIPLINES. SCOPE OF WORK IS NOT LIMITED TO THESE DRAWINGS BUT INCLUDES ALL ITEMS AS LISTED ON

DRAWINGS, SPECIFICATIONS AND ALL OTHER PROJECT RELATED DOCUMENTATION.

CONTRACTOR SHALL VERIFY EXISTING SITE CONDITIONS BEFORE SUBMITTING BID AND IMMEDIATELY NOTIFY ENGINEER OF ANY

SITE CONDITION THAT MIGHT HINDER OR OBSTRUCT THE ELECTRICAL INSTALLATION AND/OR DESIGN INTENT.

FIELD COORDINATE INSTALLATION OF ELECTRICAL SLEEVES, CONDUITS, PULL BOXES, DEVICES AND EQUIPMENT WITH OTHER

DIVISIONS ON SITE. ADJUST ELECTRICAL DEVICE AND EQUIPMENT PLACEMENT AS REQUIRED TO SUIT FIELD CONDITIONS. ALL NEW

ELECTRICAL INSTALLATION SHALL BE IN CONFORMANCE WITH THE CANADIAN ELECTRICAL CODE (CURRENT EDITION) AND BC

BUILDING CODE (CURRENT EDITION) INCLUDING ALL CLEARANCES AND SETBACKS.

CONTRACTOR SHALL COORDINATE INSTALLATION OF ELECTRICAL DEVICES AND COMPONENTS WITH EQUIPMENT MANUFACTURERS

AND SUPPLIER. NOT ALL SYSTEM COMPONENTS ARE SHOWN. CONTRACTOR SHALL PROVIDE ALL COMPONENTS, DEVICES, AND

MATERIAL AS REQUIRED TO ENSURE INSTALLATION OF A COMPLETE AND OPERATIONAL SYSTEM.

CONTRACTOR SHALL CONFIRM WIRING SIZING AND ENSURE THAT VOLTAGE DROPS IN ALL BRANCH CIRCUIT AND FEEDER MEET

CODE REQUIREMENT.

ALL WIRING SHALL BE INSTALLED IN CONDUIT SYSTEMS AS INDICATED. ALL CONDUITS SHALL BE SECURELY FASTENED TO THE

BUILDING STRUCTURE.

ENSURE THAT POWER, COMMUNICATION CABLES AND CONTROL WIRING ARE INSTALLED IN SEPARATE CONDUIT SYSTEMS.

CONTRACTOR SHALL BOND ALL NON-CURRENT CARRYING METAL PARTS OF THE SYSTEM AS REQUIRED BY CODE. ENSURE ALL

REQUIRED PARTS OF THE SYSTEM ARE BONDED AND PROTECTED.

CONTRACTOR SHALL VERIFY THE NEW ELECTRICAL SYSTEMS ARE TESTED, STARTED, AND READY FOR USE PRIOR TO TURNOVER TO

THE OWNER. CONTRACTOR SHALL FIELD TEST THE ENTIRE SYSTEM AND ENSURE IT IS OPERATIONAL AND READY FOR USE.

CONTRACTOR SHALL COORDINATE WITH MANUFACTURER OF ALL SYSTEMS AS PART OF THIS SCOPE OF WORK. ALL TEST REPORTS

SHALL BE SUBMITTED TO ENGINEER.

COMMUNITY SPORTS FIELD ELECTRICAL

VERNON, BRITISH COLUMBIA

AREA OF WORK

DRAWING LIST

NO. TITLE

E-001COVER SHEET, GENERAL NOTES, AND KEYPLAN

E-002 ELECTRICAL SPECIFICATIONS 1

E-100 ELECTRICAL SITE PLAN

E-102 ELECTRICAL FIELD HOUSE LIGHTING PLAN

E-103 ELECTRICAL FIELD HOUSE POWER PLAN

E-400 ELECTRICAL ROOM PLAN

E-501 ELECTRICAL DETAILS

E-600 ELECTRICAL SINGLE LINE DIAGRAM

E-700 ELECTRICAL SCHEDULES 1

E-701 ELECTRICAL SCHEDULES 2

E-001

COVER SHEET,

GENERAL NOTES,

AND KEYPLAN

SYMBOL DESCRIPTION

POLE MOUNTED LIGHTING FIXTURE, TYPE AS INDICATED.

SURFACE OR SUSPENDED 1X4 FIXTURE

2FT LONG WALL MOUNTED FIXTURE

4FT LONG WALL MOUNTED FIXTURE

WALL MOUNTED FIXTURE

CEILING MOUNTED FIXTURE

SINGLE GANG SWITCH

DOUBLE GANG SWITCH

DUPLEX RECEPTACLE

QUAD RECEPTACLE

STRUCTURED WIRING OUTLET - 2 PORTS/DROPS

OS OCCUPANCY SENSOR

GFI GROUND FAULT INTERRUPTION

SPD SURGE PROTECTED DEVICE

ABOVE COUNTER

ELECTRIC HEATER, TYPE AS INDICATED

CEILING OCCUPANCY SENSOR

PHOTOCELL

BASEBOARD HEAT (SIZE AS INDICATED)

COMBINATION MOTOR STARTER

SOME SYMBOLS SHOWN MAY NOT APPEAR ON THE DRAWINGS

SCOPE OF WORK:

BUILDINGS PACKAGE:

CONTRACTOR IS RESPONSIBLE FOR ALL BUILDING ELECTRICAL WORK INCLUDING FEEDER

CABLES FROM THE ELECTRICAL ROOM AND BRANCH CIRCUIT WIRING TO THE FIELD HOUSE

BUILDING (SOME BREAKERS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT IN THE

ELECTRICAL ROOM ARE PROVIDED AS PART OF A SEPARATE PACKAGE - REFER TO THE SINGLE

LINE DIAGRAM FOR DETAILS.) ALL IN BUILDING WORK AS OUTLINED IN THESE DRAWINGS,

INCLUDING COORDINATION WITH OTHER DISCIPLINES, IS INCLUDED IN THIS CONTRACTORS

SCOPE. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING EXTENSIONS AND PROVIDING

NEW CONDUITS FOR ALL IN-GROUND CONDUITS AROUND THE BUILDING THAT WERE PROVIDED

AS PART OF THE ELECTRICAL CIVIL WORKS CONTRACTOR.

vkusznir
Text Box
RDNO ATHLETIC PARK AMENTIES BUILDINGS

E-002

ELECTRICAL

SPECIFICATIONS 1

1.1.0 GENERAL MATERIALS AND LABOR

1.1.1 PERFORM ELECTRICAL INSTALLATIONS SO AS TO FORM COMPLETE AND OPERATING SYSTEMS.

PROVIDE EVERYTHING NECESSARY TO FORM A COMPLETE AND OPERATING SYSTEM EVEN IF NOT

SPECIFICALLY CALLED FOR IN THESE DRAWINGS AND SPECIFICATIONS.

1.1.2 ALL INSTALLATIONS ARE TO COMPLY WITH THE CANADIAN ELECTRICAL CODE, THE BRITISH

COLUMBIA BUILDING CODE AND THE REQUIREMENTS OF THE LOCAL INSPECTION AUTHORITY

HAVING JURISDICTION.

1.1.3 OBTAIN ALL PERMITS REQUIRED BY LOCAL AUTHORITIES PRIOR TO BEGINNING WORK. PROVIDE A

FINAL ACCEPTANCE CERTIFICATE FROM THE LOCAL INSPECTION AUTHORITY HAVING JURISDICTION

UPON COMPLETION OF THE WORK.

1.1.4 SUBMIT TO THE LOCAL INSPECTION DEPARTMENT THE REQUIRED NUMBER OF DRAWING SETS AND

INCLUDE IN THIS TENDER ALL COSTS FOR DRAWING PRINTS, PLAN REVIEWS, PERMIT COSTS AND

SURVEYS.

1.1.5 NOTIFY THE ENGINEER OF ANY CHANGES REQUESTED BY THE LOCAL INSPECTION AUTHORITY

HAVING JURISDICTION PRIOR TO MAKING SAID CHANGES.

1.1.6 THE WORD 'PROVIDE' MEANS THE SUPPLY, DELIVERY AND INSTALLATION OF DEVICE OR EQUIPMENT

REFERENCED TO THE LEVEL REQUIRED TO BE COMPLETE AND OPERATIONAL. 'SUPPLY' MEANS TO

OBTAIN AND DELIVER TO THE PROJECT SITE, READY FOR UNPACKING ASSEMBLY AND INSTALLATION.

'INSTALL' MEANS THE UNLOADING, UNPACKING, ASSEMBLING, ERECTING, APPLYING, FINISHING,

PROTECTING, CLEANING AND SIMILAR OPERATIONS AT THE PROJECT SITE TO COMPLETE ITEMS OF

WORK SUPPLIED BY OTHERS.

1.1.7 EXAMINE THE SITE PRIOR TO SUBMITTING TENDER. NO EXTRAS WILL BE PROVIDED FOR WORK THAT

WOULD HAVE BEEN EVIDENT UPON A THOROUGH INVESTIGATION OF THE SITE.

1.1.8 PROVIDE COPIES OF THE ENGINEERED DRAWINGS TO LOCAL UTILITY SUPPLY AUTHORITIES. PRIOR

TO ORDERING MATERIALS OR PERFORMING WORK, NOTIFY ENGINEER OF ANY REVISIONS TO THE

WORK REQUIRED BY UTILITY SUPPLY AUTHORITIES.

1.4.0 WARRANTY

1.4.1 PROVIDE A WRITTEN WARRANTY GUARANTEEING THAT THE WORK PERFORMED WILL BE FREE OF

DEFECTS FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE AND THAT ANY

DEFECTIVE WORK OR MATERIAL WILL BE REPAIRED OR REPLACED WITHOUT COST TO THE OWNER

DURING THIS PERIOD PROVIDED THAT SUCH FAILURES ARE NOT DUE TO IMPROPER USAGE OR

NEGLECT.

1.4.2 THE WARRANTY SHALL STATE THAT THE PERIOD OF GUARANTEE WILL IN NO WAY SUPPLANT ANY

OTHER GUARANTEE OF A LONGER PERIOD.

1.2.0 MATERIALS AND WORKMANSHIP

1.2.1 EQUIPMENT AND MATERIAL TO BE NEW AND CERTIFIED BY AN ACCREDITED CERTIFICATION BODY OF

THE STANDARDS COUNCIL OF CANADA (SCC). WHERE THERE IS NO ALTERNATIVE TO SUPPLYING

EQUIPMENT WHICH IS NOT SCC APPROVED, OBTAIN SPECIAL APPROVAL AND PAY ALL ASSOCIATED

FEES. NOTIFY ENGINEER PRIOR TO SUPPLYING MATERIAL THAT IS NOT SCC APPROVED.

1.2.2 KEEP A COMPETENT FOREMAN AND TRADESMEN QUALIFIED FOR WORK IN THE PROVINCE OR

TERRITORY OF THE PROJECT LOCATION AT ALL TIMES DURING WORK IN PROGRESS. ALL WORKERS

ON THE SITE ARE TO BE SATISFACTORY TO THE ENGINEER.

1.2.3 OBTAIN CLARIFICATION FROM THE ENGINEER WHERE THE INTENT OF THE DRAWINGS OR

SPECIFICATIONS IS NOT CLEAR. MAKE CORRECTIONS TO WORK PERFORMED CONTRARY TO THE

INTENT OF THE DRAWINGS OR SPECIFICATIONS AND BEAR ALL COSTS FOR MAKING SAID

CORRECTIONS.

1.2.4 COORDINATE ALL WORK DESCRIBED BY THESE DRAWINGS AND SPECIFICATIONS WITH THAT OF

OTHER TRADES WORKING ON THE SITE SO AS TO NOT HOLD UP THE PROGRESS OF OTHER TRADES.

1.2.5 NO SUBSTITUTION OF MATERIALS IS PERMITTED WITHOUT THE WRITTEN ACCEPTANCE OF THE

ENGINEER 10 DAYS PRIOR TO TENDER CLOSING.

1.3.0 CUTTING, PATCHING, EXCAVATION & BACKFILLING

1.3.1 ARRANGE AND PAY FOR ALL CUTTING, PATCHING, EXCAVATION AND BACKFILLING COSTS RELATED

TO THE WORK OF THIS CONTRACT.

1.3.2 RESTORE ALL EXCAVATIONS TO ORIGINAL CONDITION SUBSEQUENT TO COMPLETION OF

ELECTRICAL INSTALLATIONS DESCRIBED IN THESE DRAWINGS AND SPECIFICATIONS.

1.3.3 SURROUND ALL CABLES OR CONDUITS INSTALLED IN TRENCHES WITH SAND OR 200MM OF NOMINAL

SCREENED EARTH AS INDICATED ON DETAILS AND AS REQUIRED BY THE C.E.C.

SECTION 1.0 DIVISION 26 GENERAL REQUIREMENTS

2.1.0 CONDUIT AND WIRING

2.1.1 BUILDING WIRING TO BE COPPER RW90 XLPE INSTALLED IN CONDUIT. AC90 CABLING IS NOT

ALLOWED EXCEPT, EXCEPT WHERE OTHERWISE INDICATED ON THESE DRAWINGS. CONDUIT IS

PERMITTED TO BE RUN ON THE SURFACE IN SERVICE AREAS ONLY. CONCEAL CONDUIT

THROUGHOUT THE COMMON AREAS OF THE BUILDING. STRUCTURED WIRING CABLES ARE

PERMITTED TO BE INSTALLED WITH J-HOOKS IN SERVICE ROOMS, BUT ARE REQUIRED TO BE

INSTALLED IN HIDDEN CONDUIT IN ALL FINISHED AREAS.

2.1.2 TECK CABLE TO BE RW90, 1000 VOLT, COPPER WITH GROUNDING CONDUCTOR AND ALUMINUM

INTERLOCKING ARMOUR. CABLE IS TO BE ROUTED INSIDE SUITABLY SIZED CONDUIT WHERE TECK

CABLE IS EXPOSED TO MECHANICAL INJURY.

2.1.3 USE LIQUID-TIGHT FLEXIBLE CONDUIT FOR FINAL CONNECTIONS TO ALL MOTORS AND VIBRATING

EQUIPMENT.

2.1.4 UNDERGROUND CONDUITS TO BE RPVC CONDUIT.

2.1.2 ENSURE THAT CONDUIT IS DRY PRIOR TO WIRING INSTALLATION. SEAL CONDUIT THAT MAY BECOME

EXPOSED TO MOISTURE.

2.1.3 REFER TO SITE PLAN FOR ROUTING OF CONDUITS.

2.1.4 DO NOT CUT STRUCTURAL MEMBERS EXCEPT WHERE SPECIFICALLY INDICATED.

2.1.5 PROVIDE PULL CORD IN ALL EMPTY CONDUIT RUNS THAT EXCEED 3 METERS IN LENGTH OR THE

TOTAL SUM OF BENDS EXCEED 90 DEGREES. ENSURE THAT PROVIDED PULL CORDS NEWTON/FORCE

RATINGS MEET OR EXCEED THE MAXIMUM PULL FORCE REQUIRED TO PULL THE MAXIMUM POSSIBLE

SIZE CONDUCTOR FOR EACH RESPECTIVE CONDUIT.

SECTION 2.0 PRODUCTS AND EXECUTION

2.2.0 IDENTIFICATION

2.2.1 LABEL BOTH ENDS OF ALL CONDUITS TO SHOW ROUTING. PROVIDE ASBUILT DRAWINGS SHOWING

THE ROUTING OF ALL CONDUIT.

2.3.0 GROUNDING AND BONDING

2.3.1 PROVIDE GROUNDING AND BONDING INSTALLATIONS NECESSARY TO MEET THE REQUIREMENTS OF

THE CURRENT CANADIAN ELECTRICAL CODE AND ADDITIONAL REQUIREMENTS INDICATED ON THESE

DRAWINGS OR SPECIFICATIONS.

2.9.0 LIGHTING

2.9.1 PROVIDE LUMINAIRES AS INDICATED ON LUMINAIRE SCHEDULE. LUMINAIRES TO BE COMPLETE

WITH ALL TERMINATIONS, BALLASTS AND LAMPS AND ARE TO BE LEFT CLEAN AT PROJECT

COMPLETION.

2.11.0 PANELBOARDS

2.11.1 120/208V: 240V, WITH BUS RATED FOR CONTINUOUS CURRENT AS INDICATED ON SCHEDULE AND

10,000 AMPS FAULT WITHSTAND CAPACITY. NUMBER OF CIRCUITS AS INDICATED ON THE SCHEDULE

AND SINGLE LINE DIAGRAM. SEQUENCE STYLE COPPER BUSSING WITH ODD NUMBERED BREAKERS

ON THE LEFT AND EVEN ON THE RIGHT WITH EACH CIRCUIT IDENTIFIED BY PERMANENT

IDENTIFICATION AS TO THE CIRCUIT NUMBER. LOCKING PANEL DOOR WITH TWO KEYS FOR EACH

PANEL. STANDARD OF ACCEPTANCE CUTLER-HAMMER POW-R-LINE WITH RATINGS MEETING OR

EXCEEDING THE SINGLE LINE REQUIREMENTS. PROVIDE TYPEWRITTEN PANEL DIRECTORY.

2.11.2 347/600V: 600V WITH BUS RATED FOR CONTINUOUS CURRENT AS INDICATED ON SCHEDULE AND

10,000 AMPS FAULT WITHSTAND CAPACITY AT 600V. NUMBER OF CIRCUITS AS INDICATED ON THE

SCHEDULE AND SINGLE LINE DIAGRAM. SEQUENCE STYLE COPPER BUSSING WITH ODD NUMBERED

BREAKERS ON THE LEFT AND EVEN ON THE RIGHT WITH EACH CIRCUIT IDENTIFIED BY PERMANENT

IDENTIFICATION AS TO THE CIRCUIT NUMBER. LOCKING PANEL DOOR WITH TWO KEYS FOR EACH

PANEL. STANDARD OF ACCEPTANCE CUTLER-HAMMER POW-R-LINE WITH RATINGS MEETING OR

EXCEEDING THE SINGLE LINE REQUIREMENTS. PROVIDE TYPEWRITTEN PANEL DIRECTORY.

2.11.4 CONTRACTOR IS RESPONSIBLE FOR PROVIDING EQUIPMENT THAT FITS WITHIN THE ELECTRICAL

ROOM PROVIDED. WHERE ALTERNATE ELECTRICAL EQUIPMENT IS SELECTED, IT IS THE

CONTRACTORS RESPONSIBILITY TO COORDINATE WITH OTHER DIVISIONS AND THE ROOM

DIMENSIONS AS SHOWN.

2.16.0 SEISMIC

2.16.1 CONTRACTOR IS RESPONSIBLE FOR PROVIDING LETTER FROM A SEISMIC ENGINEER REGISTERED

TO PRACTICE IN BRITISH COLUMBIA INDICATING APPROVAL AND REVIEW OF ALL ELECTRICAL

RELATED SYSTEMS INCLUDING, BUT NOT LIMITED TO:

.1 ALL ELECTRICAL DISTRIBUTION EQUIPMENT

.2 ALL SUSPENDED LIGHTING FIXTURES

.3 ALL EQUIPMENT BASES / MOUNTING HARDWARE

2.17.0 STRUCTURED WIRING SYSTEM

2.17.1 REFERENCE STANDARDS, LATEST APPLICABLE VERSIONS OF:

.1 CAN/CSA-T528, DESIGN GUIDELINES FOR ADMINISTRATION OF TELECOMMUNICATIONS

INFRASTRUCTURE IN COMMERCIAL BUILDINGS

.2 CAN/CSA-T529, TELECOMMUNICATIONS CABLING SYSTEMS IN COMMERCIAL BUILDINGS

.3 CAN/CSA-T530, BUILDING FACILITIES DESIGN GUIDELINES FOR TELECOMMUNICATIONS

.4 IEEE STD 802.3, TELECOMMUNICATIONS AND INFORMATION EXCHANGE BETWEEN SYSTEMS

.5 TIA/EIA-606, ADMINISTRATION STANDARD FOR THE TELECOMMUNICATIONS INFRASTRUCTURE

OF COMMERCIAL BUILDINGS

.6 TIA/EIA-607, COMMERCIAL BUILDING GROUNDING AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS

.7 ANSI/TIA/EIA-568-A, COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD

.8 CSA C22.1, CANADIAN ELECTRICAL CODE

2.17.2 PROVIDE A COMPLETE, TELECOMMUNICATIONS DISTRIBUTION SYSTEM FOR VOICE AND DATA

THROUGHOUT THE BUILDING.

2.17.3 PROVIDE CAT6 OPERATING LEVEL AS PER MANUFACTURERS SPECIFICATIONS.

2.17.4 WIRING AND DEVICES SHALL CONFORM TO CAN/CSA-T528, CAN/CSA-T529 AND CAN/CSA-T530.

2.17.5 SYSTEM IS LIMITED TO CABLING INSTALLATIONS BETWEEN COMMUNICATION OUTLETS AND

ACCESSORY WIRING SPECIFICALLY INDICATED ON DRAWINGS OR SPECIFICATION. PROVIDE PATCH

PANELS, RACKS, JACKS, PATCH CORDS AND OTHER EQUIPMENT AS REQUIRED FOR A COMPLETE

AND FUNCTIONAL SYSTEM.

2.17.6 ALL STRUCTURED WIRING OUTLET BOX FACEPLATES TO BE WHITE IN COLOR.

2.17.7 SUBMIT PRODUCT DATA IN ACCORDANCE WITH THIS SPECIFICATION.

2.17.8 PROVIDE TWO (2) CAT6 RUNS TO EACH OUTLET BOX. LABEL ALL CAT6 CONNECTION PORTS WITH A

PERMANENT LABEL AT THE OUTLET AND THE PATCH PANEL. TERMINATE ALL CAT6 CABLE PORTS IN

PATCH PANEL.

2.17.9 PATCH PANELS AS INDICATED ON THE DRAWINGS, MINIMUM 24 PORT SUMMING THE TOTAL

OUTLINED ON THE DRAWINGS, HINGED, WALL MOUNTED, 0.09" THINK ALUMINUM, BLACK POWDER

COAT FINISH. STANDARD OF ACCEPTANCE: HUBBELL, LEVITON OR APPROVED EQUIVALENT.

2.18.0 ELECTRIC HEATERS

2.18.1 FORCED FLOW HEATER (FF): 18-GAUGE STEEL FRONT COVER, CLOSED, FACTORY LUBRICATED

MOTOR, 208V 1Ø, MINIMUM WATTAGE OUTPUT AS NOTED ON THE DRAWINGS, ENCASED IN

PROTECTIVE LOCKABLE CAGE WHERE INDICATED, BUILT IN THERMOSTAT WITH TAMPERPROOF

CONTROL, TUBULAR HEATING ELEMENT WITH FINS, STANDARD EPOXY/POLYESTER POWDER PAINT.

COLOR TO BE COORDINATED WITH ARCHITECT. SURFACE MOUNTING IN FURRED OUT WALL - TO BE

COORDINATED WITH ARCHITECT. 1 YEAR WARRANTY. TO BE OUELLET OAC COMMERCIAL WALL

HEATER OR APPROVED EQUIVALENT.

2.18.2 UNIT HEATER (UH): 20-GAUGE STEEL, ADJUSTABLE LOUVERS, HIGH-LIMIT TEMPERATURE CONTROL

WITH AUTOMATIC RESET, 208V 1Ø, MINIMUM WATTAGE OUTPUT AS NOTED ON THE DRAWINGS, BUILT

IN THERMOSTAT, STAINLESS STEEL TUBULAR HEATING ELEMENT, 1 YEAR WARRANTY. CEILING

MOUNTING BRACKET THAT ALLOWS 360° OF ROTATION. TO BE OUELLET OAE ECONOMICAL UNIT

HEATER OR APPROVED EQUIVALENT.

2.18.3 BASEBOARD HEATER (BB): ROBUST 20 GAUGE STEEL CONSTRUCTION. EXPOXY POLYESTER POWDER

COATING, WHITE, SIZE AND VOLTAGE AS INDICATED ON THE DRAWINGS, HIGH-DENSITY TYPE TO FIT

IN LOCATIONS SHOWN ON THE DRAWINGS, BUILT IN THERMOSTAT, TEN YEAR ELEMENT WARRANTY, 1

YEAR UNIT WARRANTY. ENCASED IN LOCKABLE PROTECTIVE CAGE WHERE INDICATED. MOUNT AT

LOW LEVEL. TO BE DIMPLEX LINEAR CONVECTOR LC SERIES OR APPROVED EQUIVALENT.

2.19.0 EMERGENCY LIGHTING

2.19.1 BATTERY ENCLOSURE (WITH REMOTE HEADS): EMERGENCY LIGHTING BATTERY PACKS TO INCLUDE

10 YEAR LIFE, SEALED LEAD ACID BATTERIES, AUTOMATIC CHARGER AND TRANSFER SWITCH, 347

VAC INPUT, 24 VDC OUTPUT, RATED FOR 30 MINUTES, INTEGRAL DOUBLE 4 WATT LED LIGHTING

HEADS - LD13. LUMACELL RGS OR APPROVED EQUIVALENT.

2.19.2 STANDARD EMERGENCY LIGHTING HEADS: 10 YEAR LIFE, 24VDC, DOUBLE 4 WATT LED LIGHTING

HEADS. FACTORY WHITE. LUMACELL MQM SERIES OR APPROVED EQUIVALENT.

2.19.3 WEATHERPROOF EMERGENCY LIGHTING HEADS: 10 YEAR LIFE, 24 VDC, DOUBLE 4W WATT LIGHTING

HEADS. NEMA 4X RATED. LUMACELL MQMP-NX OR APPROVED EQUIVALENT.

2.19.4 STANDARD EXIT LIGHTING: ENAMEL FINISH, WHITE LIGHT EMITTING DIODE SOURCE, 24V DC

VOLTAGE OPTION, 5 YEAR WARRANTY, SINGLE OR DOUBLE FACE (AS SHOWN). GREEN RUNNING MAN

STYLE, DC POWERED FROM BATTERY PACKS AS INDICATED, 2.5WATTS. LUMACELL LA SERIES OR

APPROVED EQUIVALENT.

2.19.5 EMERGENCY LIGHTING DC WIRING TO BE MINIMUM OF #10 AWG. USE LARGER WIRE SIZING AS

NECESSARY TO ENSURE VOLTAGE DROP DOES NOT EXCEED 3%.

2.19.6 EMERGENCY LIGHTING MONITOR MODULE: 347V, CAPABLE OF SENSING MINIMUM THREE (3)

CIRCUITS. PUSH BUTTON FOR ZONE TESTING. PRODUCT OF ACCEPTANCE ZONE SENSING LUMACELL

VSR SERIES OR APPROVED EQUIVALENT.

2.20.0 IN BUILDING LIGHTING CONTROL

2.20.1 IN BUILDING LIGHTING TO BE CONTROLLED AS SHOWN IN THE DRAWINGS.

2.20.2 STANDARD OF ACCEPTANCE: SENSOR SWITCH NLIGHT OR APPROVED EQUIVALENT.

2.20.3 PROVIDE ALL LIGHTING COMPONENTS TO MAKE FOR A COMPLETE AND OPERATIONAL SYSTEM.

2.21.0 EXTERIOR LIGHTING CONTROL

2.21.1 REFER TO DETAILS WITHIN THESE DRAWINGS FOR REQUIRED OPERATION OF EXTERIOR LIGHTING.

(BOTH IN BUILDING AND SITE).

2.21.2 PHOTOCELL: NEMA 3R RATED, STEM MOUNTING, DUSK TO DAWN LIGHTING CONTROL, DELAY

ACTION, CADMIUM SULFIDE PHOTOCELL AND SONIC-WELDED POLYCARBONATE LENS TO SEAL OUT

MOISTURE, LIGHT LEVEL SLIDE ADJUSTMENT, TO BE INTERMATIC OR APPROVED EQUIVALENT.

2.21.3 TIMERS: DIGITAL, PROGRAMMABLE TIMER, SET TO TURN ON AND OFF AT HOURS OF OWNERS

CHOOSING. TO BE INTERMATIC OR APPROVED EQUIVALENT.

2.21.4 PROVIDE ALL FITTINGS, RELAYS, HOA SWITCHES, CONTRACTORS AND OTHER DEVICES REQUIRED

FOR A COMPLETE AND OPERATIONAL LIGHTING CONTROL SYSTEM.

2.22.0 HAND DRYERS

2.22.1 INPUT VOLTAGE TO BE 120V, 60HZ, POLYCARBONATE ABS CASING, 1400W RATED WATTAGE,

BRUSHLESS DC MOTOR, HEPA FILTER, TOUCH FREE INFRA-RED ACTIVATION, 12 SECOND HAND DRY

TIME, COLOR TO BE COORDINATED WITH ARCHITECT, COORDINATE MOUNTING OF HAND DRYERS

WITH FURRED OUT WALLS, 5 YEAR PARTS AND 1 YEAR LABOR WARRANTY. TO BE DYSON AIRBLADE

DB SERIES OR APPROVED EQUIVALENT.

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

PROVIDE

PULLBOXES TO

RE-ROUTE

CONDUITS

TOWARDS NEW

ELECTRICAL ROOM

6A-5

1

1X35MM RPVC:

2C #12 CU XLPE RW90 + #10 CU BOND

1X35MM RPVC:

2C#10 CU RW90 XLPE + #12 CU BOND

CAM1: 2C #12 CU XLPE RW90 + #14CU BOND

CAM2: 2C #12 CU XLPE RW90 + #14CU BOND

1X35MM RPVC:

2C#10 CU RW90 XLPE + #12 CU BOND

2X103MM RPVC

CONDUCTOR SIZING BY

BC HYDRO

1X35MM RPVC:

2C#12 CU XLPE RW90 + #14CU BOND

1X53MM RPVC:

120V RECEPTACLES - 2C #8 CU XLPE RW90 + BOND

208V RECEPTACLE - 2C #8 CU XLPE RW90 + BOND

WEST HOUSEKEEPING PAD AND KIOSK.

REFER TO E-500 AND E-501 FOR DETAILS.

1X53MM RPVC

FOR FUTURE IRRIGATION CONTROLLER

COORDINATE LOCATION ON SITE

2C #12 CU WITH #14 BOND

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

5

5

LOCATION OF BC HYDRO PMT AND

CONCRETE PAD REFER TO 5/E-600.

COORDINATE LOCATION CHANGES

WITH BC HYDRO DESIGN.

6

6

6

6

4

4

4

4

4

NORTH EAST HOUSEKEEPING PAD AND KIOSK.

REFER TO E-500 AND E-501 FOR DETAILS.

3

8

7

9

11

11

11

11

15

15

15

15

15

1X35MM RPVC:

600V CONNECTION TO FUTURE SIGNAGE.

COORDINATE FINAL LOCATIONS ON SITE

600V CONNECTION TO

FUTURE SIGNAGE.

COORDINATE FINAL

LOCATIONS ON SITE.

6A-1

6A-16A-1

6A-1

6A-1

6A-1

6A-1

6A-1

6A-1

6A-1

6A-1

6A-3

6A-3

6A-3

6A-3

6A-3

6A-3

6A-3

6A-3

6A-3

6A-3

2B-5

19

19

2B-13/15

2B-11

2A-9

2D-3

6A-5

6A-5

6A-5

6A-5

6A-5

6A-5

2X53MM RPVC:

2C #6CU XLPE RW90 + #8 CU BOND

2C #3CU XLPE RW90 + #8 CU BOND

2C #3CU XLPE RW90 + #8 CU BOND

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

6A-5

6A-5

6A-3

1X35MM RPVC:

600V CONNECTION TO FUTURE SIGNAGE.

COORDINATE FINAL LOCATIONS ON SITE

2X53MM RPVC:

EMPTY

3

6A-1

NEW HYDRO POLE. CONTRACTOR TO INSTALL

FIBERGLASS PILASTER (SUPPLIED BY BC

HYDRO) AND CONCRETE BASE. COORDINATE

REQUIREMENTS WITH BC HYDRO.

1X53MM RPVC

CAM1: 2C #12 CU XLPE RW90 + #14CU BOND

CAM2: 2C #12 CU XLPE RW90 + #14CU BOND

2D-3

SOUTH EAST HOUSEKEEPING PAD AND KIOSK.

REFER TO E-500 AND E-501 FOR DETAILS.

1X53MM RPVC:

4C #4 CU + #8 CU BOND XLPE RW90

1X35MM RPVC:

EMPTY (STUB UP AND CAP OFF ON OUTSIDE OF POLE)

1X35MM RPVC:

EMPTY (STUB UP AND CAP OFF ON OUTSIDE OF POLE)

1X53MM RPVC:

4C #6CU + #8 CU BOND XLPE RW90

1X53MM RPVC:

EMPTY (STUB UP AND CAP

OFF ON OUTSIDE OF POLE)

1X35MM RPVC:

EMPTY (STUB UP AND CAP

OFF ON OUTSIDE OF POLE)

2A-7

1X53MM RPVC:

FOR FUTURE PA/COMM

1X53MM RPVC:

3C #6 CU RW90 XLPE + #8 CU BOND

#6 CU GREEN INSULATED

2C#10 CU RW90 XLPE + #12 CU BOND

1X53MM RPVC:

4C #4 CU RW90 XLPE + #8 CU BOND

1X78MM RPVC:

3C #6 CU RW90 XLPE + #8 CU BOND

#6 CU GREEN INSULATED

4C #4 CU RW90 XLPE + #8 CU BOND

2C#10 CU RW90 XLPE + #12 CU BOND

1X53MM RPVC:

4C #4 CU RW90 XLPE + #8 CU BOND

1X53MM RPVC:

3C #8 CU RW90 XLPE + #10 CU BOND

#6 CU GREEN INSULATED COPPER

2C#10 CU RW90 XLPE + #12 CU BOND

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

1X35MM RPVC

1X35MM RPVC:

CAM1: 2C #12 CU XLPE RW90 + #14CU BOND

CAM2: 2C #12 CU XLPE RW90 + #14CU BOND

1X35MM RPVC:

EMPTY (STUB UP AND CAP OFF ON OUTSIDE OF POLE)

1X35MM RPVC:

CAM1: 2C #12 CU XLPE RW90 + #14CU BOND

1X35MM RPVC:

EMPTY (STUB UP AND CAP OFF ON OUTSIDE OF POLE)

1

1X35MM RPVC:

EMPTY (STUB UP AND CAP OFF ON OUTSIDE OF POLE)

11X35MM RPVC:

2C #3CU XLPE RW90 + #8 CU BOND

2C #3CU XLPE RW90 + #8 CU BOND

1X53MM RPVC:

2C #3CU XLPE RW90 + #8 CU BOND

2C #3CU XLPE RW90 + #8 CU BOND

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU

BOND (TYPICAL)

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

1X103MM RPVC:

3C #8 CU RW90 XLPE + #10 CU BOND

3C #6 CU RW90 XLPE + #8 CU BOND

#6 CU GREEN INSULATED COPPER

#6 CU GREEN INSULATED COPPER

4C #4 CU RW90 XLPE + #8 CU BOND

4C #4 CU RW90 XLPE + #8 CU BOND

2C #10 CU RW90 XLPE + #12 CU BOND

2C #10 CU RW90 XLPE + #12 CU BOND

2X53MM RPVC:

CAPPED OFF CONDUIT STUB UPS

2X103MM RPVC:

SEE DOWNSTREAM

CONDUCTOR FOR FILL

1X53MM RPVC:

FOR FUTURE PA/COMM

EE

EE

EE

EE

EE

EE

EE

EE

EE

E

E

E

E

E

E

3X78MM RPVC:

CONDUCTOR SIZING BY BC HYDRO

3X78MM RPVC

2

2

E

E

E

E

E

E

E

2

2

EXISTING TELUS SERVICE VAULT 506. PROVIDE 2X103MM

CONDUITS TO THE LOCATION OF THE TELEPHONE

BACKBOARD. COORDINATE ROUTING WITH TELUS DEISGN

E

E

E

HYDRO SUPPLIED PULLBOX

CONTRACTOR INSTALLED.

COORDINATE ALL CONDUIT CROSS POINTS

(TYPICAL). PROVIDE PHYSICAL SEPARATION

AND VERTICAL SEPARATOR FROM HYDRO

PRIMARY CONDUITS IN ACCORDANCE WITH BC

HYDRO STANDARDS.

1X103MM RPVC:

3C #6 CU RW90 XLPE + #8 CU BOND

#6 CU GREEN INSULATED COPPER

4C #4 CU RW90 XLPE + #8 CU BOND

4C #4 CU RW90 XLPE + #8 CU BOND

2C#10 CU RW90 XLPE + #12 CU BOND

HYDRO SUPPLIED PULLBOX

CONTRACTOR INSTALLED

E

E

E

E

E

21

6A-5

15

15

6A-5

6A-5

6A-5

4X53MM RPVC NEW

12

14

15

1

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

2X53MM RPVC:

3C #4 CU RW90 XLPE

#6 CU GREEN INSULATED BOND

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

1X35MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

(TYPICAL)

1X35MM, 1X53MM RPVC NEW:

ONE FOR FUTURE CONDENSING

UNIT AND ONE FOR FUTURE SPARE

1X78MM RPVC NEW

1X78MM RPVC NEW

1X78MM RPVC NEW

1X78MM RPVC NEW

1X53MM RPVC:

2C#10 CU XLPE RW90 + #12 CU BOND

21

21

21

21

21

21

1X35MM RPVC:

2C #12 CU XLPE RW90 + #14 CU BOND

2A-1

2A-5

2A-3

2A-7

2C-1

2C-3/5

2B-1

2B-3

NEW TX-D (2x53MM PVC) SEE

SLD FOR CONDUCTORS

1X35MM RPVC:

FUTURE CONDENSING UNIT

1X78MM AND 1X53MM RPVC:

CAP OFF CONDUIT

1X53MM RPVC:

CAP OFF AND ABANDON

AVOID FUTURE WASHROOMS

BUILDING FOOTPRINT

4X53MM RPVC NEW

20

20

E-100

ELECTRICAL SITE PLAN

IN GROUND CONDUITS ARE TO BE RUN FROM THE CAPPED OFF CONDUITS TO

THE IN BUILDING LOCATIONS AS SHOWN. COORDINATE ELECTRICAL ROOM STUB

UP LOCATIONS WITH ELECTRICAL CIVIL WORKS CONTRACTOR. REFER TO SINGLE

LINE DIAGRAM FOR ADDITIONAL DESIGN INFORMATION.

CALL BC-ONE PRIOR

TO DIGGING

1-800-474-6886

DRAWING NOTES

# DESCRIPTION

1

PRIOR TO DIGGING, COORDINATE WITH UTILITIES AND CIVIL

DIVISION FOR ROUTING OF UNDERGROUND CONDUITS. AVOID

EXISTING SERVICE SUCH AS THE GAS LINE AND OVERHEAD

POWER LINES. COORDINATE REQUIRED CLEARANCES WITH

UTILITY.

2

PROVIDE T DRAIN AT LOW POINTS OF CONDUIT SYSTEM.

T-DRAIN TO BE PROVIDED AT LOW POINT OF CONDUIT PRIOR

TO CONDUIT SWEEPS, ENTERING PULLBOXES, JUNCTION

BOXES, CONDUIT STUB UPS, AND LIGHTING FIXTURES.

3

WHERE CONDUCTORS ARE NOT INDICATED, REFER TO THE

SINGLE LINE DIAGRAM. AFTER ALL CONDUCTORS ARE

PULLED, DUCT SEAL THE TOPS OF ALL EXPOSED CONDUITS.

4

CONTRACTOR TO CONFIRM THAT ALL CONDUCTORS SHOWN

ON PLANS MEETS THE INTENT OF INSTALLATION. WHERE

DISCREPANCIES OCCUR, OR ADDITIONAL CONDUCTORS ARE

REQUIRED FOR EQUIPMENT, CONTRACTOR IS TO PULL

ADDITIONAL CONDUCTORS AS REQUIRED.

KEY NOTES

# DESCRIPTION

REFER TO DRAWING E-400 FOR SPECIFIC LOCATIONS OF

ELECTRICAL ROOM CONDUIT STUB UPS. COORDINATE FINAL

LOCATION OF BUILDING ELECTRICAL ROOM WITH OTHER

DIVISIONS AND ARCHITECT ON SITE. SEAL ALL EXPOSED

STUBBED UP CONDUIT ENDS.

COORDINATE WITH BC HYDRO TO PROVIDE PULLBOXES, POLE

RISERS AND PMT IN ACCORDANCE WITH BC HYDRO

STANDARDS. PROVIDE 3X78MM CONDUIT STUBS FROM EACH

HYDRO PULLBOX IN ACCORDANCE WITH HYDRO

REQUIREMENTS.

PATHWAY LIGHTING STANDARD BASE, PULLBOX AND FIXTURE.

REFER TO 6/E-500 FOR BASE DETAILS OF INSTALLATION.

PROVIDE FOUNDATIONAL BASE THAT FOR POLE HEIGHT OF

6100MM. COORDINATE BASE REQUIREMENTS WITH

MANUFACTURER.

FUTURE PEDESTAL MOUNTED RECEPTACLE. CONDUIT AND

BASES FOR THE FUTURE PEDESTAL MOUNTED RECEPTACLES

ARE TO REMAIN. BASES ARE NOT TO INCLUDE BOLTS.

PROVIDE CAPS FOR ALL CONDUIT STUBS AND PULL STRINGS

IN ALL EMPTY CONDUITS.

LOCATION OF TIMECLOCK. PROVIDE POLE FOUNDATION AND

GROUND ROD AT THE BASE OF EACH POLE IN ACCORDANCE

WITH MANUFACTURER'S REQUIREMENTS PROVIDE PULLBOX

AS INDICATED. COORDINATE WITH MANUFACTURER TO

PROVIDE FIXTURE, FOUNDATION BASE AND GROUNDING FOR

EACH TIMECLOCK . REFER TO THE SPECIFICATIONS FOR TIME

CLOCK DETAILS. REFER TO 6/E-501 FOR DETAILS.

LOCATION OF START/FINISH SENSORS WITH PULL BOX.

COORDINATE FINAL LOCATION ON SITE WITH ARCHITECT.

REFER TO E-502 FOR ADDITIONAL INSTALLATION DETAILS.

COORDINATE INSTALLATION WITH MANUFACTURERS

WRITTEN INSTRUCTIONS.

REFER TO DETAIL 7/E-500 AND 7/E-501 FOR CONDUIT STUB UP

LOCATIONS FOR HOUSE KEEPING PAD AND KIOSK LAYOUT.

COORDINATE FINAL LOCATION OF HOUSEKEEPING PADS WITH

ARCHITECT.

REFER TO DETAIL 8/E-500 AND 8/E-501 FOR CONDUIT STUB UP

LOCATIONS FOR HOUSE KEEPING PAD. COORDINATE FINAL

LOCATION OF HOUSEKEEPING PADS WITH ARCHITECT. REFER

TO DETAIL 5/E501 FOR DETAILS OF LIGHTING CONTROL.

REFER TO DETAIL 9/E-500 AND 9/E-501 FOR CONDUIT STUB UP

LOCATIONS FOR HOUSE KEEPING PAD. COORDINATE FINAL

LOCATION OF HOUSEKEEPING PADS WITH ARCHITECT. REFER

TO DETAIL 5/E501 FOR DETAILS OF LIGHTING CONTROL.

NOT USED

COORDINATE FINAL LOCATION OF FIELD LIGHTING

STANDARDS WITH ARCHITECT AND CIVIL DIVISION. PROVIDE

CONDUIT AND PULL BOX AS INDICATED AT LOCATION OF

FUTURE FIELD LIGHTING POLE. CONDUIT TO CONNECT TO

LIGHTING POLE APPROXIMATELY 610MM BELOW FINISHED

GRADE. COORDINATE REQUIREMENTS WITH FIELD LIGHTING

MANUFACTURER. REFER TO 3/E-501 FOR TYPICAL DETAILS OF

PULLBOX INSTALLATION. MUSCO POLES AND EQUIPMENT

SUPPLIED BY OWNER PROVIDED BY THIS CONTRACTOR.

LOCATION OF GROUNDING ELECTRODE SYSTEM. REFER TO

2/E500 FOR GROUNDING REQUIREMENTS. REFER TO 1/E-400

FOR APPROXIMATE STUB UP LOCATION.

NOT USED

PROVIDE CONDUITS TO LOCATION OF THE FUTURE PANEL E IN

THE ELECTRICAL CLOSET AS INDICATED. COORDINATE

LOCATION OF CONDUIT STUB UPS WITH BUILDING

ELECTRICAL CLOSET. EXTEND CONDUITS FROM THIS

LOCATION TO THE EAST SIDE OF THE BUILDING EXTERIOR AS

SHOWN FOR FUTURE EXPANSION OF THE FIELDS BUILDING.

REFER TO DRAWING E-103 FOR DETAILS OF CONDUIT

ROUTING.

STAIRWAY LIGHTING, FIXTURE, BASE AND PULLBOX.

COORINATE LOCATION OF STAIRS WITH CIVIL AND

ARCHITECTURAL DIVISIONS. REFER TO 6/E-500 FOR GENERAL

DETAILS OF STAIRWAY BASE INSTALLATION. FOR ALL

STAIRWAY LIGHTING, PROVIDE FOUNDATIONAL BASE FOR

POLE HEIGHT OF 6100MM. COORDINATE BASE REQUIREMENTS

WITH MANUFACTURER. REFER TO THE SPECIFICATIONS FOR

STAIRWAY FIXTURE DETAILS.

NOT USED

NOT USED

NOT USED

RECESSED RECEPTACLE BOX - IP66 RATED. COORDINATE

FINAL LOCATION WITH ARCHITECT. REFER TO THE

SPECIFICATIONS FOR ADDITIONAL INFORMATION. ALL

RECEPTACLES IN BOX TO BE GFI PROTECTED.

COORDINATE WITH SHAW AND TELUS TO INSTALL CONDUITS

IN ACCORDANCE WITH SHAW AND TELUS REQUIREMENTS.

COORDINATE FINAL STUB UP LOCATION WITH UTILITIES AND

CIVIL WORKS ELECTRICAL CONTRACTOR ON SITE.

PROVIDE 16MM RPVC BURIED CONDUIT FROM THE

ELECTRICAL PANEL 6A TO THE EXTERIOR SIGNAGE

LOCATIONS. REFER TO DRAWING E-102 FOR LOCATION

DETAILS.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

6A-23

6A-23

6A-23

6A-23

6A-23

3

3

3

3

3

6A-23

1

6A-23

1

6A-23

1

6A-23

1

6A-23

1

6A-23

1

6A-23

1

6A-23

6A-23

6A-23

1

1

2

6A-23

2

6A-23

1

6A-23

2

6A-23

2

6A-23

2

6A-23

2

6A-23

2

6A-23

2

OS

OS

OS

OS

OS

DIM

ZONE3

ZONE2

ZONE2

ZONE1

ZONE1

OS

OS

OS

OS

OS

OS

OS

OS

BP#1

BP#1

BP#1

BP#1

BP#1

BP#1

BP#1

BP#1

BP#2

BP#2

BP#2

BP#2

BP#2

BP#2

BP#2

BP#2

BP#3

BP#3

BP#3

THREE (3) ZONE

DIMMER SWITCH

BP#3

BP#2

BP#2

BP#2

BP#1

6A-23

2

6A-23

1

BP#1

BP#1

OS

BP#1

4

5

5

5

5

5

5

OS

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-19

6A-21

6A-21

6A-21

6A-21

6A-21

6A-17

2E-19

2E-19

2E-19

2E-19

2E-19

2E-19

2E-19

2E-19

2E-19

2E-19

2E-19

2E-19

6A-19

OS

OS

ZONE3

6A-17

OS

6A-23

3

6A-17

6A-17

OS

6

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6A-17

6

6A-17

6A-17

E-102

ELECTRICAL FIELD

HOUSE BUILDING

LIGHTING PLAN

DRAWING NOTES

# DESCRIPTION

1

EMERGENCY LIGHTING TO BE CIRCUITED IN SUCH A WAY

THAT UPON FAILURE OF THE NORMAL ROOM LIGHTING,

THE EMERGENCY LIGHTS ACTIVATE. PROVIDE

MONITORING MODULES AS REQUIRED TO MEET THIS

REQUIREMENT. ALLOW FOR A MINIMUM OF TWO (2)

MONITORING MODULES FOR THE LIGHTING CIRCUITS

SHOWN ON THIS DRAWING.

2

COORDINATE WITH CIVIL CONTRACTOR TO PROVIDE ALL

FOUNDATIONAL CONDUIT TRENCHING AS REQUIRED FOR

THE FIELD HOUSE BUILDING.

3

EXTERIOR LIGHTING TO BE CONTROLLED BY PHOTOCELL

AND TIMECLOCK. REFER TO 5/E-501 FOR DETAILS. SEE

KEYNOTES BELOW FOR LIGHTING BANK DESIGNATIONS.

4

COORDINATE FINAL LIGHTING LOCATIONS WITH

OVERHEAD DOORS, MECHANICAL DUCTING AND OTHER

OBSTRUCTIONS.

5

ALL ROOM OCCUPANCY SENSORS TO BE SETUP TO

WORK AS VACANCY SENSORS (MANUAL ON AUTOMATIC

OFF).

6

COORDINATE FINAL MOUNTING HEIGHT OF ABOVE

BATHROOM SINK FIXTURES WITH MIRROR HEIGHT.

APPROXIMATE MOUNTING HEIGHT IS TO BE

APPROXIMATELY 2286 ABOVE FINISHED FLOOR.

KEY NOTES

# DESCRIPTION

EXTERIOR FIELD HOUSE ENTRANCE BUILDING LIGHTING

EXTERIOR CLASSROOM CANOPY LIGHTING

EXTERIOR WEST SIDE ENTRANCE CANOPY LIGHTING

PHOTOCELL TO BE MOUNTED AT HIGH LEVEL AWAY

FROM SOURCES OF ARTIFICIAL LIGHT. COORDINATE

FINAL LOCATION ON SITE.

PROVIDE POWER FOR SIGNAGE. COORDINATE FINAL

MOUNTING HEIGHT WITH ARCHITECTURAL DIVISION.

COORDINATE WITH CIVIL CONTRACTOR TO PROVIDE

UNDERGROUND CONDUIT TO THE FUTURE SIGNAGE AS

REQUIRED. PROVIDE JUNCTION BOX ON BUILDING

EXTERIOR TO HOUSE FUTURE SIGNAGE CONDUCTORS.

MOUNT IN ROOM FIXTURES AT ~2591MM AFF.

COORDINATE FINAL MOUNTING HEIGHT WITH

EQUIPMENT ON SITE. COORDINATE FINAL LOCATIONS

AND MOUNTING METHOD WITH MECHANICAL DUCTING IN

ROOM. PROVIDE SEISMIC BRACING OF FIXTURES.

CONTRACTOR IS PERMITTED TO WALL MOUNT FIXTURES

AT LOWER LEVEL WHERE THE MAKEUP AIR UNIT DOES

NOT ALLOW PENDANT FIXTURES TO BE INSTALLED.

1

2

3

4

5

6

BATTERY PACK SCHEDULE

# DESCRIPTION

BP#1347V, 24V, 250W

BP#2347V, 24V, 250W

BP#3120V, 24V, 150W

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

2D-41

HD-5

CU-1

6A-38/40/42

CU-2

2E-32/34

3

2E-44

3

2E-42

3

2D-40

BB-2

2D-44/46

1kW

1

.

2E-13

HD-6

BB-3

2E-2/4

1kW

1

.

HD-7

BB-4

2E-6/8

1kW

1

.

2E-17

HD-8

BB-5

2E-6/8

1kW

1

.

HD-4

HD-2

2D-37

HD-3

GFR

GFR

GFR

GFR

SPD

GFR

GFR

GFR

GFR

GFR

GFR

5-20R

2D-33

HD-1

3

2D-38

5-20R

FF-6

3kW.

FC-1

6A-32/34/36

5-20R

GFR

5-20R

GFR

4

5

2

DF-1

RECEPTACLE FOR

TELEPHONE BACKBOARD

LOCATION OF NEW PANEL E. EXISTING 2X78MM RPVC UNDER

LOCATION OF PANEL. ONE (1) FROM ELECTRICAL ROOM AND

ONE (1) TO EAST SIDE OF BUILDING. SEE SLD FOR NEW FEEDER.

PROVIDE 19MM G1S PLYWOOD BACKBOARD

PAINTED WITH FIRE RETARDANT PAINT FOR SUB

TELEPHONE BACKBOARD. REFER TO DRAWING

2/E-501 FOR DETAILS.

LOCATION OF FUTURE 600V PANEL. EXISTING 2X78MM RPVC

UNDER LOCATION OF FUTURE PANEL. ONE (1) FROM

ELECTRICAL ROOM AND ONE (1) TO EAST SIDE OF BUILDING.

SPD

WP

WP

WP

4

5-20R

GFR

GFR

5-20R

GFR

GFR

UH-1

FF-1

FF-2

3KW

2KW

FF-3

3KW

FF-4

1KW

.

FF-5

3KW

BB-1

2D-44/46

1kW

1

.

6

MUA-1

EF-2

EF-1

DHW-1

P-1

2D-5

2D-7

5-20R

2D-7

2D-27

2D-29

2D-27

2D-9

2D-13

2D-39

2D-14/16

2D-18/20

2D-22/24

2D-26/28

2D-30/32

2D-34/36

2D-9

2D-21

2D-21

3KW

2D-48/50

2D-11

2D-13

2D-35

2D-17

2D-17

2D-17

2D-23

6A-26/28/30

2D-47

2D-47

2E-21

2D-15

6A-44/46/48

2D-43

2D-45

2D-4

2D-4

2D-4

2E-35

2E-35

2E-35

2E-37

2E-37

2E-37

2E-36

2E-39

2E-39

2E-39

2E-15

2E-25

2E-27

2E-27

2E-38

2E-29

2E-31

2E-31

2E-25

SPD

E-103

ELECTRICAL FIELD

HOUSE BUILDING

POWER PLAN

DRAWING NOTES

# DESCRIPTION

1

EMERGENCY LIGHTING TO BE CIRCUITED IN SUCH A WAY

THAT UPON FAILURE OF THE NORMAL ROOM LIGHTING,

THE EMERGENCY LIGHTS ACTIVATE. PROVIDE

MONITORING MODULES AS REQUIRED TO MEET THIS

REQUIREMENT. ALLOW FOR A MINIMUM OF TWO (2)

MONITORING MODULES FOR THE LIGHTING CIRCUITS

SHOWN ON THIS DRAWING.

2

COORDINATE WITH CIVIL CONTRACTOR TO PROVIDE ALL

FOUNDATIONAL CONDUIT TRENCHING AS REQUIRED FOR

THE FIELD HOUSE BUILDING.

3

ALL FORCED FLOW HEATERS TO BE RECESSED. REFER

TO PANEL SCHEDULES FOR BREAKER SIZING. REFER TO

SPECIFICATIONS FOR HEATER DETAILS. ALL FORCED

FLOW HEATERS IN THE CHANGE ROOM AREA TO BE

ENCASED WITH MESH STEEL COVER BOX.

4

FOR EACH BATHROOM SINK , URINALS AND TOILET

(TYPICAL OF THIRTEEN (13) SINKS , TWO (2) URINALS,

TWENTY (20) TOILETS ON THIS DRAWING, PROVIDE LINE

VOLTAGE WIRING CONNECTION TO THE LOW VOLTAGE

TRANSFORMER. TRANSFORMER, JUNCTION BOX, SINK

HARDWARE, TOILET HARDWARE AND LOW VOLTAGE

WIRING ARE PART OF THE MECHANICAL CONTRACTORS

SCOPE. LINE VOLTAGE WIRING TO THE TRANSFORMER

BY THIS CONTRACTOR. PULL WIRING FROM NEAREST

SINK RECEPTACLE CIRCUIT. COORDINATE WITH

MECHANICAL DIVISION TO ENSURE CONDUIT IS

CONCEALED IN WALL.

5

THIS CONTRACTOR IS RESPONSIBLE FOR EXTENDING

CIVIL PACKAGE CONDUITS TO THE BUILDING AND

PROVIDED NEW CONDUITS IN THE BUILDING FOOTPRINT.

REFER TO THE SITE PLAN FOR CONDUITS TO BE

EXTENDED/PROVIDED.

KEY NOTES

# DESCRIPTION

PROVIDE CUSTOM VANDAL PROOF, LOCKABLE,

PROTECTIVE CAGE AROUND NOTED ELECTRIC HEATER

EQUIPMENT. PAINT CAGE FINISH TO MATCH WALL

COLOR.

COORDINATE FINAL LOCATION OF ELECTRIC HEATER ON

SITE.

OVERHEAD DOOR MOTOR. COORDINATE CONNECTION

LOCATION, DISCONNECT AND OTHER ELECTRICAL

REQUIREMENTS OF OVERHEAD DOOR ON SITE. PROVIDE

ACCESSIBLE PUSHBUTTON FOR BOTH SIDES OF

OVERHEAD DOORS AT 1200MM AFF ON CENTER FOR

OPENING AND CLOSING OF OVERHEAD DOOR. PROVIDE

KEY SWITCH LOCKOUT OF OVERHEAD DOORS AS

REQUIRED.

OUTLET AND RECEPTACLE MOUNTED AT 1800MM AFF

FOR WIFI ACCESS POINT.

PROVIDE 53 MM CONDUIT FROM THE SUB TELEPHONE

BACKBOARD CLOSET TO A 6X6 RECESSED JUNCTION

BOX AT THE INDICATED LOCATION. PROVIDE CONDUITS

FROM THE JUNCTION BOX TO EACH STRUCTURED

WIRING OUTLET IN THE CLASSROOM.

REFER TO DRAWING E-400 FOR ELECTRICAL EQUIPMENT

LAYOUT.

1

2

3

4

5

6

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

WIREWAY

METER SOCKET

IN BC HYDRO

METER CABINET

PNL-6A

LIGHTING

CONTROL

CABINET 1

SPD

MDB-1

LIGHTING

CONTROL HOA

SWITCHES

PNL-2D

GROUND

BUS

TELEPHONE BACKBOARD

JANITOR ROOM

DOOR

TX-D

TELEPHONE BACKBOARD

2X103MM RPVC

SHAW/TELUS

1X53MM RPVC FROM

MDB-1 FOR TX-D PRIMARY

1X53MM RPVC TO PNL-2D FOR

TX-D SECONDARY TO PNL-2D

TX-D NEMA 3R ENCLOSURE

TX-D HOUSE KEEPING PAD

53MM RPVC FOR POWER TO IRRIGATION

VALVES. COORDINATE CONNETION LOCATION

WITH IRRIGATION CONTRACTOR ON SITE

PROPOSED LOCATION OF FUTURE

IRRIGATION CONTROLLER. COORDINATE

FINAL LOCATION ON SITE.

RPVC CONDUIT STUB

WIREWAY

ME

TE

R S

OC

KE

T

IN B

C H

YD

RO

ME

TE

R C

AB

INE

T

PN

L-6

A

PNL-2D

LIG

HT

ING

CO

NT

RO

L

CA

BIN

ET

1

2X103MM RPVC BC

HYDRO SERVICE

1X53MM RPVC

POLE S1

SP

D

LIGHTING

CONTROL HOA

SWITCHES

1X35MM RPVC FOR

GROUNDING CONNECTION

2X35MM RPVC

FUTURE COMMS/PA - POLES S1,S2

1X53MM RPVC

WEST PATHWAY, STAIR AND

WALKWAY LIGHTING

1x103MM RPVC

POLES S3, S4 AND E LOADS

1X103MM RPVC

TO PNL-6A

1X103MM RPVC

FROM MDB-1

1X53MM RPVC

FROM TX-D

1X53MM RPVC

TO TX-D

MDB-1

2X53MM RPVC

TO WEST KIOSK

1X53MM RPVC

FUTURE COMMS/PA - POLES S3,S4

1X53MM RPVC

FUTURE POWER TO POLE S2

1X53MM RPVC

TO WEST KIOSK AND START

FINISH CAMS, N TIMECLOCK

1X53MM RPVC

POLE S2

4X53MM RPVC

TO CLASSROOM AND EXPANSION

CONDUITS TO EAST OF BUILDING

2X53MM RPVC

TO WEST KIOSK

2x103MM RPVC

POLES S3, S4 AND EAST LOADS

1X53MM, 2X35MM RPVC

SPARE WEST STUB + FUTURE CONDENSING UNITS

1X78MM RPVC TO CLASSROOM AND

EXPANSION CONDUITS TO EAST OF BUILDING

1X78MM RPVC TO CLASSROOM AND EXPANSION

CONDUITS TO EAST OF BUILDING

1X103MM RPVC SPARE TO

THIS ELECTRICAL ROOM

1X103MM RPVC SPARE TO

THIS ELECTRICAL ROOM

GROUND

BUS

RPVC CONDUITS TO BUILDING SIGNAGE LOCATIONS

1X78MM RPVC

STUB UP FOR FUTURE

WASHROOM BUIDLING

1X53MM RPVC

STUB UP FOR FUTURE

WASHROOM BUIDLING

E-400

ELECTRICAL ROOM

PLAN

NOTES:

1. ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN IN THE ELECTRICAL ROOM HAS ALREADY BEEN

PROVIDED. REFER TO THE SINGLE LINE, DETAILS, AND PANEL SCHEDULES FOR INFORMATION ON

FEEDER, BREAKER, CONDUCTOR AND OTHER REQUIREMENTS FOR THIS CONTRACT.

3. LIGHTING CONTROL FOR ALL FIXTURES INSTALLED AS PART OF THIS CONTRACT TO BE

COMPLETED BY THIS CONTRACTOR. THIS INCLUDES ALL IN-BUILDING AND BUILDING MOUNTED

LIGHTING.

4. ALL ELECTRICAL EQUIPMENT MOUNTED TO WALL TO BE MOUNTED ON 19MM GIS PLYWOOD

BACKBOARD PAINTED WITH FIRE RETARDANT PAINT. COORDINATE WITH GENERAL CONTRACTOR

TO ENSURE INSTALLATION OF BACKBOARDS FOR ALL MOUNTED ELECTRICAL EQUIPMENT

LOCATIONS.

5. PROVIDE 2C #12 CU XLPE RW90 + BOND IN THE EXISTING 53MM RPVC CONDUIT TO THE VALVE

LOCATION. COORDINATE FINAL LOCATION AND DETAILS WITH IRRIGATION CONTRACTOR ON SITE.

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

TELEPHONE BACKBOARD

SPACE RESERVED FOR OWNER

SUPPLIED TELCOM EQUIPMENT

PROVIDE NEW SPD 20A

QUAD RECEPTACLE

PROVIDE WALL MOUNTED

24 PORT CAT6 PATCH

PANEL. TERMINATE ALL

CAT 6 OUTLET CABLES IN

THIS PATCH PANEL. EACH

OUTLET IS TO HAVE ONE

PHONE LINE AND ONE

VOICE LINE. SEPARATE

AND LABEL VOICE AND

TELEPHONE PORTS ON

THE PATCH PANEL AND

EACH CABLE.

CONDUITS SHOWN TYPICAL OF MAIN

ELECTRICAL ROOM. REFER TO THE

SITE PLAN FOR FIELD HOUSE

TELEPHONE BACKBOARD CONDUITS.

2X103MM RPVC

SHAW/TELUS

2X35MM RPVC

FUTURE COMMS/PA - POLES S1,S2

1X53MM RPVC

FUTURE COMMS/PA - POLES S3,S4

4X53MM RPVC

TO ELECTRICAL CLOSET THEN TO EAST

SIDE OF BUILDING

2X53MM RPVC

TO WEST KIOSK

SUB TELEPHONE BACKBOARD

SPACE RESERVED FOR FUTURE

TELCOM EQUIPMENT

PROVIDE NEW SPD 20A

QUAD RECEPTACLE

4X53MM RPVC FROM MAIN TELEPHONE BACKBOARD

4X53MM RPVC TO EAST OF BUILDING

CONDUITS TO CLASSROOM

E-501

ELECTRICAL DETAILS

C

L

C

L

C

L

NATIVE

BACKFILL

MARKER TAPE

150MM SAND BACKFILL AND/OR

BEDDING AROUND CONDUITS

BACKFILL COMPACTED TO

97% STANDARD PROCTOR

DENSITY

RPVC CONDUIT SIZED AS

INDICATED ON

DRAWINGS (TYPICAL)

NOTES:

1. TRENCH IS TO BE CLEARED OF ALL ROCKS AND DIRT CLUMPS BEFORE

PLACING CONDUITS IN TRENCH. CONDUITS TO BE SURROUNDED WITH SAND.

2. WHERE ADDITIONAL CONDUITS CARRYING THE SAME VOLTAGE ARE

INSTALLED SPACE THESE CONDUITS AT 190MM FROM EDGE TO EDGE. WHERE

CONDUITS OF DIFFERING VOLTAGES ARE INSTALLED, SPACE CONDUITS AT

300MM FROM EDGE TO EDGE. REFER TO THE DRAWINGS FOR DETAILS OF

UNDERGROUND CONDUITS.

3. CONDUIT DEPTHS UNDER THE BUILDINGS ARE TO BE COORDINATED WITH

THE BUILDING FOUNDATION, BUT AT MINIMUM MUST BE 1000MM BELOW

FINISHED GRADE.

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

E-600

ELECTRICAL SINGLE

LINE DIAGRAM

HYDRO EQUIPMENT LIST

FEEDER/EQUIPMENT DESIGNATION

1

BC HYDRO PAD MOUNT TRANSFORMER.

2

PRIMARY DUCT FROM BC HYDRO SERVICE POLE.

COORDINATE REQUIREMENTS WITH BC HYDRO.

3

3-78mm CONDUIT, INCOMING PRIMARY DUCTS.

4

2-103 mm CONDUIT, SECONDARY DUCTS.

5

MIN. 0.9m RADIUS BEND.

6

PROVIDE T-DRAIN AT LOW POINT.

7

MAIN INCOMING WIREWAY SECTION.

8

MAIN ELECTRICAL ROOM. SEE DRAWING E-400.

9

HYDRO PULLBOX INSTALLED IN GROUND. PROVIDE

PROTECTION POSTS IN FRONT AS DIRECTED BY BC

HYDRO.

TELECOM EQUIPMENT LIST

FEEDER/EQUIPMENT DESIGNATION

1

TELUS PEDESTAL (REFER TO SITE PLAN FOR LOCATION)

2

SHAW PEDESTAL (REFER TO SITE PLAN FOR LOCATION)

3

2-103MM DUCTS FOR TELUS SERVICES

1-103MM DUCT FOR SHAW SERVICES

SEE SITE PLAN

4

MIN. 0.9m RADIUS BEND

5

NOT USED

6

PROVIDE T-DRAIN AT LOW POINT OF DUCT RUN.

COODINATE CONNECTION TO MAIN BUILDING DRAIN.

7

MAIN ELECTRICAL ROOM TELEPHONE BACKBOARD. SEE

LAYOUT ON DRAWING E-400.

8

MAIN ELECTRICAL ROOM. SEE DRAWING E-400.

9

TELECOM AND TV DISTRIBUTION PLYWOOD BACKBOARD.

1.0m 2.2m 1.0m

UNOBSTRUCTED AREA

PROPERTY LINE

UNOBSTRUCTED AREA

EDGE OF PAD

DUCT OPENING

PROTECTION POSTS

(AS REQUIRED)

GROUND RODS

UNOBSTRUCTED

AREA ON ACCESS

SIDE OF XFMR.

(TYP.)

NOTE:

DIMENSIONS SHOWN FOR UNOBSTRUCTED AREAS ARE MIN.

DIMENSIONS ONLY. ANY LANDSCAPING ON PERIMETER OF

UNOBSTRUCTED AREAS MUST BE UPFIELD TO MAINTAIN MINIMUM

CLEARANCES. FOR FURTHER CLARIFICATION OF KIOSK DIMENSIONS

AND CLEARANCES, REFER TO BC HYDRO STANDARD DWGS. ES54

F3-05.01, 02, 03 AND R1.01.01. COORDINATE FINAL REQUIREMENTS WITH

BC HYDRO.

MDB-1, 400A, 347/600V, 3Ø, 50kA

3P400A, 347/600V, 3Ø, 22kAIC

TX-A

347/600V:120/208

7.5kVA, 3Ø

EXISTING TX-D

347/600V:120/208V

112.5 kVA

CONDUCTOR SCHEDULE

CONDUCTOR # DESCRIPTION BOND

4C #10 CU RW90 XLPE IN 21MM EMT #8 CU

#6 CU GREEN INSULATED COPPER - REFER TO SITE PLAN FOR CONDUIT

ROUTING/SIZING

N/A

3C #4 CU RW90 XLPE - REFER TO SITE PLAN FOR CONDUIT ROUTING/SIZING #8 CU

3C #6 CU RW90 XLPE - REFER TO SITE PLAN FOR CONDUIT ROUTING/SIZING #8 CU

4C#10 CU RW90 XLPE IN 21MM EMT #12 CU

4C#2 CU RW90 XLPE IN 27MM EMT #8 CU

2 RUNS [4C#3/0 CU RW90 XLPE IN] SINGLE 78MM CONDUIT

2X#6 CU

4C#1 CU RW90 XLPE SINGLE 78MM CONDUIT #6 CU

3C#8 CU RW90 XLPE IN 53MM EMT #10 CU

0

1

2

3

4

5

6

7

8

3P30

SPARE

3P100

SPARE

NE KIOSK

3P15 3P15

3P400 3P150

3P200A

PNL-2D, 120/208V, 400A, 3Ø, 84CCT

3P100A

7

DIGITAL METER

M

METER SOCKET. COORDINATE METERING

REQUIREMENTS WITH BC HYDRO.

3P40

TX-B

347/600V:120/208

7.5kVA, 3Ø

SE KIOSK

TX-C

347/600V:120/208

30kVA, 3Ø

W KIOSK

3P30

SPD

NON-FUSED

DISCONNECT

NON-FUSED

DISCONNECT

NON-FUSED

DISCONNECT

160kA

RATING

NEMA 3R

ENCLOSURE

PROVIDE DUCTS, TRANSFORMER PAD, AND PULLBOXES FROM

NEW BC HYDRO POLE MOUNTED TRANSFORMER ALL THE WAY TO

THE ELECTRICAL ROOM. REFER TO SITE PLAN FOR DUCT SIZE

DETAILS. ALL INSTALLATIONS TO BE IN CONFORMANCE WITH BC

HYDRO STANDARDS. COORDINATE WITH BC HYDRO AS REQUIRED.

1

2

5

2

3

4

2

1

PNL-6A, 347/600V, 400A, 3Ø, 84CCT

BRANCH

CIRCUITS

(SEE PANEL

SCHEDULES FOR

ADDITIONAL

LOADS AND

DETAILS)

BRANCH

CIRCUITS

(SEE PANEL

SCHEDULES FOR

ADDITIONAL

LOADS AND

DETAILS)

COMBINATION

PANEL

PROVIDED

AS PART OF

SEPARATE

CONTRACT

4

1

9

2

6

0

1

1

6

8

NOTES:

1. ITEMS IN LIGHT LINES ARE NOT IN CONTRACT. ITEMS IN DARK LINES ARE IN CONTRACT.

2. DISTRIBUTION EQUIPMENT PROVIDED AS PART OF THIS CONTRACT TO MATCH THE

EQUIPMENT SUPPLIER PROVIDED AS PART OF THE ELECTRICAL CIVIL WORKS CONTRACT.

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

E-700

ELECTRICAL

SCHEDULES 1

PANEL AND FEEDER IS EXISTING. PROVIDE

BRANCH CIRCUIT WIRING FOR ALL IN BUILDING

LOADS (ODD NUMBERED CIRCUITS)

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING

E-701

ELECTRICAL

SCHEDULES 2

PANEL, FEEDER AND BRANCH CIRCUIT WIRING IS

EXISTING AND HAS BEEN PROVIDED FOR

REFERENCE ONLY.

PANEL, FEEDER AND BRANCH CIRCUIT WIRING IS

EXISTING AND HAS BEEN PROVIDED FOR

REFERENCE ONLY.

PANEL, FEEDER AND BRANCH CIRCUIT WIRING IS

EXISTING AND HAS BEEN PROVIDED FOR

REFERENCE ONLY.

PANEL, FEEDER AND BRANCH CIRCUIT BREAKERS

ARE EXISTING. CONTRACTOR TO WIRE ALL

BRANCH CIRCUITS THAT SERVE BUILDING LOADS.

(ALL BRANCH CIRCUITS OTHER THAN #1 AND #3.)

PROVIDE PANEL, FEEDER AND ALL BRANCH

CIRCUITS AND WIRING. REFER TO SITE PLAN FOR

DETAILS OF CONDUIT RUNS. REFER TO THE

SINGLE LINE DIAGRAM FOR CONDUCTORS SIZING.

vkusznir
Text Box
RDNO ATHLETIC PARK AMENITY BUILDING