  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    1/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 1

    PremsetMedium Voltage Distribution

    Compact Modular Vacuum Switchgear

    Shielded Solid Insulation System

    Innovation for

    MV distributionIntroducing Premset switchgear,

    a new way to design, install,

    and operate MV networks

    January 2012

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    2/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 2

    Index

    A new generation of switchgeartechnology

    Where is Premset

    implemented?

    Key Benefits

    Range offer descriptionand technical features

    Premset

    KeyBenefits

    Rang

    e

    Where?

    Index - Indoor version

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    3/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 3

    The new generation

    in switchgear technology

    Premset

    Schneider Electric Infrastructure Business MV Premset presentation January 2012

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    4/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 4

    Taking advantage of the experience

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    SM6 + Fluokit + Ringmaster:1 000 000 functions installed

    - Modular

    - Versatile

    - Wide and comprehensive offer

    RM6 + FBX + RN2C:

    2 500 000 functions installed

    - Compact solution for Utilities MV

    distribution, ready-to-connect

    - Insensitive to harsh environments or bad

    conditions of installation

    - Minimum maintenance

    - Extensible for network evolution

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    5/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 5

    Innovative architecture designedwith your needs in mind

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    - you have to take in account the smart grid trend

    - expected life duration of switchgear is increasing

    - maintenance-free is far more important than SF6-free

    - maintenance and operation teams know-how is decreasing

    - cost effective and compact Circuit Breakers are neededfor small primary substations or loop management

    - no problems with GIS switchgear, because reliable in harsh

    environment (humidity, temperature, dust, poor installation, partialdischarges)

    - Ill never compromise about end-users safety

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    6/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 6

    Like Air Insulated Switchgear- Modular

    - Versatile

    - Comprehensive

    Premset: a technological breakthrough, opening the way

    to unprecedented safety, efficiency, and ease of use

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    Like Gas Insulated switchgear

    - Compact

    - Easy to install

    - Severe environment robust

    - Minimized maintenance

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    7/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 7

    Premset:Shielded Solid Insulation System (2SIS)

    - Safe and reliable in any environment

    - Flexible, simple, modular, and functional

    - Smart grid-ready, distributed intelligence

    Premset: a technological breakthrough, opening the way

    to unprecedented safety, efficiency, and ease of use

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    Premset

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    8/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 8

    Premset: GIS+AIS = 2SIS*:Shielded Solid Insulation System

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    It is a new concept, aiming to achieve

    the highest level ofreliability,

    safety and advanced power

    management solutions foryour MV network

    Premset offer target is to take advantages

    of both technologies GIS and

    AIS, in creating Modular, Severe

    Environment Insensitiveswitchgear, using SF6-free technologies

    and Flexible / ready forSmart Grids* Gas Insulated Switchgear + Air Insulated

    Switchgear = Shielded and Solid InsulationSystem (2SIS)

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    9/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 9

    Premset: modular 2SIS technology

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    PremsetPremset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    10/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 10

    Premset: a disruptive technological breakthroughopening to a new generation of switchgear

    EfficiencySmart grid and advanced management

    solutions across the network

    ReliabilityLong-lasting performance with the Shielded

    Solid Insulation System (2SIS)

    SafetyAn intuitive 3-in-1 architecture for breaking,

    disconnection, and earthing

    FlexibilityA compact and modular design for all

    functions

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    11/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 11

    Premset: a disruptive technological breakthroughopening to a new generation of switchgear - Efficiency

    Smart grid and advanced management solutions across the networkIntelligent, smart grid-ready solutions:- Feeder automation

    - Load management

    - Asset management

    - Automatic Transfer System

    Architecture with distributed intelligence

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    12/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 12

    Premset: a disruptive technological breakthroughopening to a new generation of switchgear - Reliability

    Long-lasting performance withShielded Solid Insulation System

    (2SIS)

    - Extending protection to the entire

    switchgear assembly, in any harsh

    environment

    - Enhanced safety, reduced internal

    arcing risk

    - Longer life expectancy, gas-free

    2SIS is applicable for any functionsuch as:

    - Load break switches or circuit breakers

    - New compact metering functions

    - Current and Voltage transformers

    Thenewg

    eneration

    ofswitchgeartec

    hnology

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    13/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 13

    Premset: a disruptive technological breakthroughopening to a new generation of switchgear -Safety

    An intuitive 3-in-1 architecture forbreaking, disconnection, and earthing

    Simple and user-friendly scheme

    Intuitive operation, reducing risk

    for user

    The safest MV switchgear

    in its class

    Thenewg

    enera

    tion

    ofswitchgeartec

    hnology

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    14/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 14

    Premset: a disruptive technological breakthroughopening to a new generation of switchgear - Flexibility

    A compact and modular design for all functions- Fast, stress-free installation, upgrading, and maintenance

    Modular combination and optimized circuit breakers

    - Straightforward assembly with identical busbar and cable

    connections for the entire range

    - Easy-to-install patented universal flat power connection system

    - Easy cabling since all cable connections are at a heightof 700 mm

    - Extended possibilities of cable entry management

    - No preventive maintenance and servicing required

    Thenewg

    enera

    tion

    ofswitchgeartec

    hnology

    Premset

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    15/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 15

    Where?

    Where isPremsetimplemented?

    Schneider Electric Infrastructure Business MV Premset presentation January 2012

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    16/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 16

    Field of applications

    BuildingsEnergy

    Industry

    Buildings

    Industry

    Energy

    Where?

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    17/83

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    18/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 18

    Applications targeted

    Energy

    Primary substation (> 20 MVA)

    Large switching substation (< 4 MVA)

    MV/LV substations (< 2 MVA)

    Buildings, Industry, MMM, O&G

    Heavy industry primary substation (> 20 MVA)

    Large MV consumers site (5 10 MVA)

    MV consumer site (1 5 MVA)

    132kV/11kV Busbar > 2000A

    630-1250A, fixed, pilot protections

    630A Ring Main Unit - Kiosks or Buildings

    132kV/11kV, 10-50MVA, Busbar < 3150A, draw outPetrochemical, Automotive, Steel & Cement plants, Paper mills

    630A-1250A, fixed, pilot protectionsHospitals, Universities, Regional airports, Food & Beverage factories, .

    630A, Kiosks or BuildingsShopping center, light manufacturing, retail or industrial park, .

    Where?

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    19/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 19

    Applications targeted

    Energy

    Primary substation (> 20 MVA)

    Large switching substation (< 4 MVA)

    MV/LV substations (< 2 MVA)

    Buildings, Industry, MMM, O&G

    Heavy industry primary substation (> 20 MVA)

    Large MV consumers site (5 10 MVA)

    MV consumer site (1 5 MVA)

    132kV/11kV Busbar > 2000A

    630-1250A, fixed, pilot protections

    630A Ring Main Unit - Kiosks or Buildings

    132kV/11kV, 10-50MVA, Busbar < 3150A, draw outPetrochemical, Automotive, Steel & Cement plants, Paper mills

    630A-1250A, fixed, pilot protectionsHospitals, Universities, Regional airports, Food & Beverage factories, .

    630A, Kiosks or BuildingsShopping center, light manufacturing, retail or industrial park, .

    Where?

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    20/83

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    21/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 21

    Typical application for Building -Compact MV consumer substation with MV metering

    WhereisPremset

    implemented?

    2.25 m

    Where?

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    22/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 22

    SF6-free RMU package offer for Energy :from 2 to 5 functional units (any order) packaged in single unit,ready to install

    Harsh environment withstand Marine, Water

    treatment, Mining

    Modular and consistent system Infrastructures,Light industry applications

    Embedded solutions in Control & Monitoring Data centers,

    Hospitals

    Outdoor rural outdoor substations, including simpleprimary substations (overhead substitution)

    WhereisPremset

    implemented?

    Other applicationsTaking opportunity of Premset assets

    Where?

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    23/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 23

    Where

    isPremset

    implem

    ented

    Specific types

    Ring Main Unit version Outdoor version

    Where?

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    24/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 24

    Key

    benefits

    Key

    Benefits

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    25/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 25

    Key Benefits

    Simple-Safe-S

    mart

    Safety

    Reliability

    Flexibility

    Key

    Benefits

    Efficiency

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    26/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 26

    Premset

    keybenefits

    Voice of Customers - Selected examples (reminder)

    Key

    Benefits

    - you have to take in account the smart grid trend

    - expected life duration of switchgear is increasing

    - maintenance-free is far more important than SF6-free

    - maintenance and operation teams know-how is decreasing

    - cost effective and compact Circuit Breakers are neededfor small primary substations or loop management

    - no problems with GIS switchgear, because reliable in harsh

    environment (humidity, temperature, dust, poor installation, partialdischarges)

    - Ill never compromise about end-users safety

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    27/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 27

    Premset

    keybenefits

    2SIS (Shielded Solid Insulated System) design

    Entire live parts path is touchable

    (double isolation everywhere)

    - Total safety for user

    MV system is totally protected against severe environment impacts

    (pollution, aggressive atmosphere, condensation, humidity, dust)

    - Longer life expectancy and maximum reliability in any condition

    MV system is insulated, but shielded by earthed screen

    - No more risk when ineffective maintenance

    No more bare live parts in regard

    - Internal arc probability extremely reduced

    All functions with shielded solid insulation have a longer life expectancy,

    including the M06S compact metering unit.

    Key

    Benefits

    Safe and reliable in any environmentLong-lasting performance with Shielded Solid Insulation System

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    28/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 28

    Premset

    keybenefits

    Safe and reliable in any environmentIntuitive 3-in-1 architecture for breaking, disconnection and earthing

    Failsafe and intuitive operation- Simplest way of operation : unmatched 3 positions scheme

    - Easiest and positively driven built-in interlocks

    Simplest association of disconnection in vacuum and

    earthing in controlled air device on cable side- Double isolating gap between live busbar and earthed cable

    Direct downstream earthing

    - No need for reclosing upstream device- Visibility on earthing switch contacts (when required)

    Intuitive mimic diagram- Clear and positive indications, whatever the function

    Advanced dedicated device for network cables testing

    and diagnosis- Front face access and fully interlocked

    Advanced dedicated device for protection testing- Allows primary injection testing without disconnecting cables

    Live cable interlock- Prevent the operation of earthing switch when live cables

    Key

    Benefits

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    29/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 29

    Premset

    keybenefits

    FlexibleA compact and modular design for all functions

    Easy engineer to order- Functional brick design on single platform

    - With common auxiliaries and accessories

    Easy to install- Reduced and coherent dimensions:

    same width, same depth all over the range

    - Reduced footprint: small dimensions, embedded functions

    (metering and measurement, control, monitoring)

    - Easy cabling: screened, front, high (700mm) and in line cable connections ;patented, easy-to-use universal flat power connection system ;

    identical busbar dimensions and connections for the entire range

    - Easy settings: dedicated circuit breakers for transformer protection,

    built-in relaysKey

    Benefits

    Trouble-free installation

    With a reduction of up to 50% in footprint

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    30/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 30

    Premset

    keybenefits

    FlexibleA compact and modular design for all functions

    Easy to upgrade- Modularity, plug & play design

    - Same auxiliaries, accessories, and monitoring devices being used for

    the entire range

    - Self-addressing Intelligent Electronic Devices

    - Last minute modification of auxiliaries & accessories, without any tool orspecific training

    Easy end of life

    - No hazardous emission : SF6-free, RoHS compliant- No care of future SF6 regulation : SF6-free. Can be installed in any public areaor building

    - Innovative design for increased environmental impacts control

    Key

    Benefits

    Up to 30%The increase in life expectancy due to the absenceof pressurized gases

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    31/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 31

    Premset

    keybenefits

    Advanced and integrated protection, network control andmonitoring features- Self-powered or dual-power VIP protection relay range

    - Integrated compact solutions for power measurement and power metering

    Smart grid-ready- Feeder automation

    - Load management

    - Asset management

    - Automated Metering Management

    Thanks to distributed intelligence- Flexible approach

    - Distributed intelligence

    - Embedded intelligence

    - Integrated in solutions

    - Web technology

    Key

    Benefits

    EfficiencySmart grid and advanced management solutions across the network

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    32/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 32

    Premset

    keybenefits

    Total Cost of Ownership optimization

    Key

    Benefits

    Longer life expectancy- Insensitive to harsh environment (dust, pollution, humidity) and uncontrolledinstallation conditions : solid and screened design, no partial discharge issues

    - Gas-free, no over-pressure

    True maintenance free- No maintenance, nor servicing required. Entire system is solid and shielded : no electrical field in open air

    . No gas, so no gas monitoring

    . Sealed for life system, servicing-free mechanism

    Modularity- Reduced delivery times

    - On site last-minute modifications without tools or training

    Reduction of time and money spent during the installation- Uniform dimensions

    - Reduced footprint

    - Simple front power connections- Modification of auxiliaries & accessories, without any tool or specific training

    Wide and consistent range of optimized-to-application corefunctions- 2 types of loading switches (I06T, I06H)

    - 4 types of Circuit-Breakers (D01N, D02N, D06N, D06H)

    - 3 types of power measurement/metering ( M06S, M06A, integrated)

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    33/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 33

    Premset

    keybenefits

    Safety&Reliabi

    lity

    Totally Shielded Solid Insulation System design foroptimized safety and extended equipment life

    Key

    Benefits

    3

    1

    2

    1 Low Voltage cabinet

    2- Cable test

    3- Top connections

    4 Core unit

    5 Bottom connections

    6 Bottom compartment

    7 Sensors (CTs and VTs)

    8 Gas exhaust duct

    4

    5

    6

    7

    8

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    34/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 34

    Single bus bar (630A) Cable connection

    Key

    Benefits

    Busbars with shielded solid insulation

    Premset

    keybenefits

    Safety&Reliabi

    lity

    Totally Shielded Solid Insulation System design foroptimized safety and extended equipment life

    Patented flat connectics

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    35/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 35

    Premset

    keybenefits

    Safety&Reliabi

    lity

    Key

    Benefits

    The most intuitive operations for breaking, disconnection and

    earthing

    3-in-1 integrated architecture: easiest and safest operation,with built-in interlocking

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    36/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 36

    3-in-1 integrated architecture: easiest and safest operation,with built-in interlocking

    Premset

    keybenefits

    Safety&Reliability

    Key

    Benefits

    The most intuitive operations for breaking, disconnection and

    earthing

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    37/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 37

    Disconnection in vacuum & earthing switchin controlled air

    redundancy of isolation- vacuum bottles for breakingand disconnection

    - controlled airfor downstreamearthing switch in sealed-for-life screened tank.

    Premset

    keybenefits

    Safety

    Key

    Benefits

    Breaking and

    disconnection

    Earthing

    switch

    Operationof earthing

    switchOperationof mainswitch

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    38/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 38

    Disconnection in vacuum & earthing switchin controlled air

    Key

    Benefits

    Premset

    keybenefits

    Safety

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    39/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 39

    "Universal" connecting system

    Cable connections are made with a single design andcable clamping, with limited number of components

    Cable connections and clamping allowing- Any cable configuration : bottom-front, top-rear, cable in cable out

    - Last-minute differentiation of measurement CTs, front located

    Premset

    keybenefits

    Simplicity

    Key

    Benefits

    Front connection - Bottom in Rear connection Top inRear connection Top out

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    40/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 40

    Cable testing and diagnosis: dedicated device,for easy access and total safety

    Cable testing without accessingcable box or dismantling cable

    connections

    Test device connection from the

    front of the switchboard, while cables

    remain earthed

    Failsafe interlocks with earthed starpoint

    Premset

    keybenefits

    Safety

    Key

    Benefits

    Easy cablingAll cables

    connections arealigned in front

    at a height of 700 mm

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    41/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 41

    Key

    Benefits

    Cable testing and diagnosis: dedicated device,for easy access and total safety

    Premset

    keybenefits

    Safety

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    42/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 42

    Live cable interlockElectrical lock-out of earthing switch when live cables

    Earthing switch lock-out function- Prevent the earthing switch to be closed

    on earth when cables are still alive

    - Positively blocked in case of auxiliary power loss

    - Override unlocking by key

    - Remote indication of locked position

    Premset

    keybenefits

    Safety

    Key

    Benefits

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    43/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 43

    Ready for feeder automationEnsuring optimized efficiency across MV network

    State-of-the-art Smart Grid andadvanced management solutions

    Switchgear ready for communication- Communicating FPI

    - Smart switchgear controller

    - Communicating protection

    Remote communication withDistributed Management System- Remote alarming

    - Remote control

    Local automatism- Recloser

    - Self healing medium voltage ring

    - Source transfer

    Key

    Benefits

    Premset

    keybenefits

    Smartgrid-ready

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    44/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 44

    Ready for load managementArchitecture with distributed intelligence

    Integrated smart metering- Power meter

    - Optimized metering cubicle

    - Low power sensors

    Remote communication to

    load flow management solution

    Premset

    keybenefits

    Smartgrid-ready

    Key

    Benefits

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    45/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 45

    Ready for asset management

    Monitoring of switchgear- Over current and breaking profile

    - Backup power supply monitoring

    - Motorization monitoring

    Monitoring of transformer- Load

    - Temperature

    - Trends and alarming

    - Ageing monitoring

    Maintenance- Protection chain test

    - Remote alarming by mail, SMS,

    - Type stamped events recorded

    Easy diagnostic on local web pages

    Key

    Benefits

    Premset

    keybenefits

    Smartgrid-ready

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    46/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 46

    Ready for Automated Metering Management (AMM)

    LV smart meter reading- Concentration of LV smart meters

    - Power line carrier interface

    - Connection to billing system

    LV network monitoring- Phases unbalance

    - Lack of voltage on one phase

    Detect technical and non technicallosses

    Key

    Benefits

    Premset

    keybenefits

    Smartgrid-ready

    Local

    network

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    47/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 47

    Flexible approach

    Today: set of products to connect- Protections: Sepam

    - Measurement metering: Power Logic

    - Local fault monitoring & Remote control: Easergy

    Sepam

    Easergy

    Key

    Benefits

    Power Logic

    Premset

    keybenefits

    Smartgrid-ready

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    48/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 48

    Easy to implement monitoring & control

    Easy installation, configuration and exploitation- Modular and plug and play architecture with serial communication

    - Built in web page showing single line diagram for monitoring & control

    Key

    Benefits

    Premset

    keybenefits

    Smartgrid-ready

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    49/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 49

    Embedded intelligence in switchgear

    Functional approach based onoptional and independent modules

    to cover various combination- Protection, Control, Measurement

    Modules fully integrated in functional

    unit- Including sensors, switchgear interface, powersupply, communication, HMI

    - Pre- engineered, factory-tested, cost effective

    - Easy integration based on :. Field bus communication between modules

    . Pre-cabling inside cubicle

    - Gradual solution : from local control up to complexfeeder automation

    Key

    Benefits

    Premset

    keybenefits

    Smartgrid-ready

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    50/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 50

    Integrated in Schneider Electric solutions

    SCADA or EMS for feederautomation with standard protocols

    (through R200, T200)

    Energy monitoring, energy

    management, building management

    MV Loop automation solution

    IEC61850 access to Substationautomation through gateway (G3200)

    Modbus

    Key

    Benefits

    Prem

    set

    keyb

    enefits

    Smar

    tgrid-ready

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    51/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 51

    Low cost Supervision & Control system

    Key

    Benefits

    Example of web accessPrem

    set

    keyb

    enefits

    Smar

    tgrid-ready

    Switchboard information is stored in a Web page

    Need just a PC with a standard Web browser-

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    52/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 52

    Functional system oriented design: configurable,type tested, made by Schneider Electric

    Optimized system of functional bricks

    Type-tested" switchgear assembly

    Optimized interfaces between bricks

    Key

    Benefits

    Prem

    set

    keyb

    enefits

    Simplicity

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    53/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 53

    A new approach for MV switchgear functional concept

    Key

    Benefits

    D02 ND06 NI06 TI06 T D02 N

    Improving functionality with an advanced compact

    and modular design

    Prem

    set

    keyb

    enefits

    Simplicity

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    54/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 54

    A new approach for MV switchgear assembly of functional bricks

    D02 ND06 NI06 TI06 T D02 N

    LV cabinet

    Cable test

    Top connection

    Bottom

    connections

    Bottom

    compartment

    Switchingdevice

    M06 S

    Key

    Benefits

    Prem

    set

    keyb

    enefits

    Simplicity

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    55/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 55

    Ra

    nge

    Range offerdescription

    and technical features

    Schneider Electric Infrastructure Business MV Premset presentation January 2012

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    56/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 56

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    A consistent architecture

    Ra

    nge

    Same dimensions for all Premsetfunctional units- Width, same pitch = 375mm,

    - Depth = 900 / 1100mm (IAC)

    - Height = 1350 / 1950mm

    - Front aligned connections, height = 700mm

    Electrical characteristics- Ur: 12 kV & 15 kV

    - Fr: 50/60 Hz

    - Ud: 42-48 kV

    - Up: 95-110 kV

    Internal arc- Standard design is virtually arc free,

    - Optional: type tested 21KA 1s A-FLR,

    top or bottom exhaust

    Protection index; indoor version- IP3X

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    57/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 57

    Premset, architecture and components

    Unsurpassed safety and reliabilitywith 2SIS Solid and Shielded

    Insulation System

    - Modular busbar system with shielded solidinsulation (1)

    - Vacuum bottles with shielded solid insulation

    for breaking and disconnection (2)

    - Integrated air-insulated earthing switch enclosed

    in tank with shielded solid insulation (3)

    - Built-in voltage and current sensors for optimised

    protection and control, available in versions withshielded solid insulation where required (4)

    - Front aligned cable connections with shieldedsolid insulation, designed for easy clamping (5)

    1

    3

    4

    Ra

    nge

    5

    2

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    4

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    58/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 58

    Premset, architecture and components

    Unsurpassed simplicity with mix-and-match modular architecture based

    on functional blocks

    - Low Voltage cabinet (different heights) (1)

    - Cable test (2)

    - Top connections (3)

    - Core unit (different types) (4)

    - Bottom connections (5)

    - Bottom compartment (different heights anddepths) (6)

    - Sensors (CTs and VTs) (7)

    - Gas exhaust duct (8)

    1

    3

    4

    Ra

    nge

    5

    2

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    6

    7

    8

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    59/83

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    60/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 60

    Four basic functional units

    Ra

    nge

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    630A switchdisconnector

    I06 TNetworkmanagement

    200A circuit breakerdisconnectorO-15 sec- CO

    2000 operations

    D01-02 NTransformerprotection

    630A circuit breakerdisconnectorO-15 sec-CO.

    2000 operations

    D06 NFeeder protectionSingle shot

    630A circuit breakerdisconnectorO-0,3s-CO-15s-CO

    10,000 operations D06 HFeeder protectionAuto-reclose

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    61/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 61

    Technical performances, dedicated applications

    Ra

    nge

    Typicalapplication

    I06 TDisconnecting

    switch

    D01 N - D02 NTransformer

    protection

    D 06 NGeneral

    protection

    D 06 HLine

    protection

    In 630 A 100 - 200 A 630 A 630 A

    Ik x tk 20 kA x 4s

    21 kA x 3 s

    25 kA x 2 s

    20 kA x 4s

    21 kA x 3 s

    25 kA x 2 s

    20 kA x 4s

    21 kA x 3 s

    25 kA x 2 s

    20 kA x 4s

    21 kA x 3 s

    25 kA x 2 s

    Endurance

    class

    1 000 op.

    (M1, E3)

    2 000 op.

    (M1, E2)

    2 000 op.

    (M1, E2)

    10 000 op.

    (M2, E2)

    Testing

    sequence

    na O - 15 s - CO O - 15 s - CO O - 0.3 s - CO -15 s - CO

    Endurance

    Isc

    5 5 5 > 50

    Total clearing,With VIP relay

    na < 60 ms < 100 ms < 100 ms

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    62/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 62

    3 mechanisms, 1 design platform:same operation, same auxiliaries

    CITfor I06 T

    Ra

    nge

    CI1for D01 N, D02 N

    D06 N

    OCOfor D06 H, I06 H

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    63/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 63

    Flexible Metering unit options

    Ra

    nge

    Conventional tariff metering M06 A-Air insulated IP54 degree of protection

    - 750mm wide (double pitch)

    - Traditional cast resin CTs and VTs

    - Easy to adapt to local requirements

    Compact metering unit M06 S- Screened VTs accessible from the front

    - Toroidal CTs over screened busbar- Compact size: 375mm wide (single pitch)

    - Harsh environment withstand

    Integrated in circuit breaker panel- Screened VTs in bottom compartment

    - Toroidal metering CTs in cable box

    - No extra width required in switchboard

    - Harsh environment withstand

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    64/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 64

    Current Transformers integrated in main functions

    (1) Current transformers locatedunder the core unit- Dedicated current transformer for VIP integrated

    self-powered protection (CuaCUb)

    - Low power current transformer for Sepam or

    any conventional relay (TLPU1)

    -1 A ring-type current transformer for Sepam or

    any conventional relay (ARU2).

    (2) Current transformers located

    around bushings- Zero sequence current transformer for VIP high

    sensitivity earth fault protection (CSHU)

    - Measurement current transformer for faultpassage

    indication and power measurement (ARU1).

    (3) Current transformers located

    around cables- Ring-type current transformer for power

    measurement or metering (ARC6 and ARC7)

    - Earth fault toroidal current transformer for high

    sensitivity earth fault protection (CSH120/200).

    Ra

    nge

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    1

    3

    4

    5

    2

    6

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    65/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 65

    Voltage Transformers integrated in main functions

    (4) Low Power Voltage Transformers

    located under the core unit or in

    the busbar system (5)- Low Power Voltage Transformer for protection

    or measurement (VLPU1)

    (6) Voltage transformers located

    behind the cables

    - Phase-to-earth voltage transformers (VRT4).

    Ra

    nge

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    1

    3

    4

    5

    2

    6

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    66/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 66

    Sepam & MiCOM digital relay

    ranges: open protection & monitoring- External power

    - Open range

    - Standard CT, shunt trip actuation

    - From basic to sophisticated protection

    - Existing catalog

    Wide range of protection relay choices

    VIP, performance optimized for

    Premset- Self powered

    - Optimized for Premset

    - Specific CT, Mitop actuator

    - Simple protection, easy to implement

    - Perfectly adapted to dedicated application

    VIP 40

    . MV/LV transformer

    protection

    . Dedicated to D02

    . Low cost

    Easiest setting

    . Fuse killer!

    VIP 400

    . Feeder protection

    . Overcurrent

    . Earth fault

    . Sensitive earth fault

    . Communications

    Ra

    nge

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    Sepam10

    . MV feeder protection

    . Communications

    Sepam20, 40, 80

    . Advanced protection,

    monitoring, communication

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    67/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 67

    VIP self-powered protection relay for higher

    MV network availability

    Ra

    nge

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    VIP relays are self-poweredwhile traditional relays requirean auxiliary power supply

    Self-powered protection relays increase

    the availability of the MV networkand are perfectly suited to most applications

    - Insensitive to voltage drop due to faults- Not dependent on UPS systems (weak point of electrical installations)

    - Less dependent on the external environment (EMC, LV overvoltages) because they requireno external connections

    In addition, the VIP offers optimized performancesdue to integrated protection chain- Complete and pre-tested protection system: special CT and Mitop actuator savings on space

    and cabling time- Fast clearing time in case of transformer short-circuit ( 60 ms): no fuse needed

    - High sensitivity sensors

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    68/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 68

    Ra

    nge

    Panorama of protection functions / selection table

    VIP series Sepam series

    Integrated self-powered protectionoptimised for Premset

    General

    Transformer

    protection

    General use

    protection

    VIP 40 VIP 45 VIP 400 VIP 410 Sepam 20 Sepam 40

    Protection functions

    Phase overcurrent

    (ANSI 50-51)

    Earth fault (ANSI 50N-51N) Standard (sum of current method)

    High sensitivity (earth fault CTs)

    Thermal overload (ANSI 49)

    Cold load pick-up

    Other protection functions

    Measurement functions

    Phase and earth currents

    Phase peak demand current

    Load history Cumulative time

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    69/83

    P t ti it i d t l

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    70/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 70

    Ra

    nge

    Protection, monitoring and controlTest operation for VIP relays

    Primary injection testA primary injection circuit may be permanently installed (option)through the CTs, inside the cubicle, to test the physical integrity

    of the complete protection system including the CTs

    - The test is carried out without disconnecting

    the CTs and the VIP relay displays the injected current during testing

    - If necessary, a temporary VIP test mode can be activated to test

    the tripping of the circuit breaker by pressing a test pushbutton

    Test with

    the Pocket

    Battery moduleThis accessory can be

    connected on the VIP

    relay front plate to

    energize the relay to

    carry out a quick test

    even though the relay

    is not powered.The temporary test

    mode can be activated

    with the keypad to testthe circuit breaker

    1. VIP

    2. Pocket Battery

    3. Injection test case

    1 2

    3

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    P t ti it i d t l

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    71/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 71

    Protection, monitoring and controlEmbedded fault passage indicator (FPI)

    Stand alone FPI- Fault passage detection

    - Local indication: Led + external lamp

    - Remote indication: Dry contact

    - Current, peak demand : local

    Communicating FPI- Fault passage detection

    - Local indication: Led + external lamp

    - Remote indication: Communication

    - Current, peak demand: local & remote

    - Voltage relay for ATS & ESW lock

    Flair 23DM-V

    . 12-48V power supply

    . 16 h indication

    . Communication port

    Voltage relay

    Ra

    nge

    Flair 21D Flair 22D

    . Self power . Battery

    . 4 h indication . 16 h indication

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    Flair 21D

    Flair 22D

    P t ti it i d t l

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    72/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 72

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    Protection, monitoring and controlEmbedded fault passage indicator (FPI) / selection table

    Range

    FLAIR

    FLAIR 21D FLAIR 22D FLAIR 23DM

    Power supply Self-powered

    Dual-powered

    Detection Overcurrent

    Earth-fault

    Display (4 digit LCD) Ammeter

    Maximeter

    Options SCADA interface (relay)

    External lamp

    External reset

    Extended setting (keypad)

    Communication 2-volatge output relays

    Serial communication port

    P t ti it i d t l

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    73/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 73

    Protection, monitoring and control

    Monitoring and Control

    Remote Terminal Unit R200- Substation interface with SCADA through:. Local Area Network : Ethernet (industrial/infrastructure)

    . Wide Area Network : GSM, Radio, GPRS (Energy)

    Automatic change over- 2 MV incoming

    - 1 MV incoming, 1 generator

    - 2 MV incoming and a busbar coupling

    Switchgear control SC100- Achieve open/close electrical orders

    - Switchgear Human interface

    - Include safe remote control

    Secured Power Supply PS200- Substation power supply for motors

    and control & monitoring modules

    - Monitoring of the battery

    Power on

    Readyto close

    Motor OKUnit ready

    Local Remote Range

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    M t

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    74/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 74

    Measurement

    Basic ammeter: Amp 21D

    Communicating ammeter:

    Amp 23D

    Energy Monitoring & Power Quality:

    PM800 & ION 8800

    Amp

    PM 850

    ION 8800Range

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures

    P t

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    75/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 75

    PremsetMedium Voltage Distribution

    Compact Modular Vacuum Switchgear

    Shielded Solid Insulation System

    Appendix

    Premset architect re and components

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    76/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 76

    Premset, architecture and components

    Unsurpassed safety and reliability

    with 2SIS Solid and Shielded

    Insulation System

    Rang

    eofferdes

    cription

    andtechnicalfe

    atures Shielded Solid Insulation System (2SIS)

    - The entire main circuit is solid insulated withepoxy or EPDM, eliminating all live parts in free air

    - The solid insulation is shielded, i.e. its surface is

    at earth potential everywhere (no electrical field infree air)

    Innovative single ligne diagram, newarrangement of main functions

    - Disconnecting load break switch or disconnectingcircuit breaker using vacuum interrupters

    - Earthing switch within sealed tank with air atatmospheric pressure

    3-in-1 integrated core units

    All the necessary functions: breaking, disconnection

    and earthing, are embedded in a single device

    Consistent range of two switches and fourcircuit breakers to suit any application

    Modular system architecture, simplifyinginstallation and upgrading

    Functional units designation

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    77/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 77

    Premset 15I D06N BC-Ms

    Core unit function- I: load break switch

    - D: Circuit-Breaker

    - M: metering

    - G: riser

    Rating: 01 / 02 / 06

    Core unit type- T: tumbler mechanism (CIT lever mechanism)

    - N: standard performance (CI1 single latch mechanism)

    - H: high performance (OCO stored energy mechanism)

    Metering type- A: Air Insulated

    - S: Solid Insulated

    Connections

    (top / left, right / bottom)B: bus bars

    C: cable,

    L: bar from left

    R: bar to right

    Metering embedded- Ms: solid insulated metering

    - Ma: air insulated metering

    Functional units designation

    Rang

    eofferdes

    cription

    andt

    echnicalfe

    atures

    Premset environment appraisal vs existing Air Insulated

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    78/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 78

    Premset environment appraisal vs existing Air Insulatedand Gas Insulated typical switchgears

    Prem

    set&Environment

    Premset design and innovative technology (*)

    are allowing lower environmental impacts- Integration of functions allows downsizing components dimensions

    - Less materials

    - Optimised global weight

    Premset design is complying with RoHS directive

    Premset SF6 Free technology is making easier

    maintenance process with an increased life expectancy

    Up to 30%The increase in life expectancy due to the absenceof pressurized gases

    Safe and reliable in any environment

    Trouble-free service life withinsulation and screening of live parts

    Peace of mind with SF6-free

    technology

    Premset environment appraisal vs existing Air Insulated

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    79/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 79

    Premset environment appraisal vs existing Air Insulatedand Gas Insulated typical switchgears -Average weight of main materials

    Prem

    set&Environment

    Premset: feeder function with 630A fixed vacuum CB

    AIS: feeder function with 630A fixed vacuum CB in typical Air Insulated switchgear

    Metalclad: feeder function with 630A drawout vacuum CB in typical metalclad switchgear

    1000

    900

    800

    700

    600

    500

    400

    300

    200

    100

    0

    Masse(kg)

    Premset AIS Metalclad

    Product weight 148.3 326.0 923.0

    Steel 73.0 154.0 732.4

    Copper 9.0 45.0 95.2

    Aluminium 10.0 10.0 10.6

    Epoxy Resin 34.0 52.0 60.1

    Autres 22.3 65.0 24.7

    Premset environment appraisal vs existing Air Insulated

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    80/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 80

    Premset environment appraisal vs existing Air Insulatedand Gas Insulated typical switchgears - Raw Material Depletion

    Prem

    set&Environment

    Premset: feeder function with 630A fixed vacuum CB

    AIS: feeder function with 630A fixed vacuum CB in typical Air Insulated switchgear

    Metalclad: feeder function with 630A drawout vacuum CB in typical metalclad switchgear

    1.20 E-11

    Premset AIS Metalclad

    1.00 E-11

    8.00 E-12

    6.00 E-12

    4.00 E-12

    2.00 E-12

    0.00 E+00

    Raw Material Depletion (Y-1)

    M+D+U, 20 years, 30%In

    Premset environment appraisal vs existing Air Insulated

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    81/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 81

    Premset environment appraisal vs existing Air Insulatedand Gas Insulated typical switchgears - Energy Depletion

    Prem

    set&Environment

    Premset: feeder function with 630A fixed vacuum CB

    AIS: feeder function with 630A fixed vacuum CB in typical Air Insulated switchgear

    Metalclad: feeder function with 630A drawout vacuum CB in typical metalclad switchgear

    3.00 E+05

    Premset AIS Metalclad

    2.50 E+05

    2.00 E+05

    1.50 E+05

    1.00 E+05

    5.00 E+04

    0.00 E+00

    Energy Depletion (MJ)

    M+D+U, 20 years, 30%In

    Premset environment appraisal vs existing Air Insulated

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    82/83

    Schneider Electric Infrastructure Business MV Premset presentation January 2012 82

    Premset environment appraisal vs existing Air Insulatedand Gas Insulated typical switchgears - Global Warming

    Prem

    set&Environment

    Premset: feeder function with 630A fixed vacuum CB

    AIS: feeder function with 630A fixed vacuum CB in typical Air Insulated switchgear

    Metalclad: feeder function with 630A drawout vacuum CB in typical metalclad switchgear

    Premset AIS Metalclad

    1.50 E+07

    1.00 E+07

    5.00 E+06

    0.00 E+00

    Global Warming (g ~CO2)

    M+D+U, 20 years, 30%In

    Innovation for MV distribution

  • 8/12/2019 Compact Vacuum Circuit Breakers -Premset

    83/83

    Innovation for MV distributionIntroducing Premset switchgear, a new way to design, install, and operate MV networks