COMPONENTS FOR BIOMASS SYSTEMS
2014
M
Flue gas
Thermal exchange
Comburent air
Primary andsecondary air
M
M
The CALEFFI BIOMASS® product series has been created specifically to be used in circuits ofsystems with wood solid fuel generators, operating at high temperature with water or glycolsolutions as thermal medium. The materials of the components and their performance takeaccount of the specific system needs in terms of efficiency and safety of the generators andsystems.
Biomass is “the biodegradable fraction of products, waste and residues from biologicalorigin from agriculture (including vegetal and animal substances), forestry and relatedindustries (including fisheries and aquaculture), as well as the biodegradable fraction ofindustrial and municipal waste”. Biomass can be in the form of a solid, liquid or gas.This line of Caleffi products has been specifically designed for wood solidbiomass (solid fuel).
Solid fuel generators can be classified in two macro-categories:1) Boilers: generators “for solid fuels, hand and automatically stoked”, to be installedin specific technical rooms. Heating takes place via a hydraulic connection to theheating system.
2) Residential devices: “residential solid fuels burning appliances with boiler, notexceeding a total nominal heat output of 35 kW”, installed directly inside the dwelling.Hand or automatically stoked. Heating takes place via air and water circulation, witha hydraulic connection to the heating system. Residential devices can be classifiedin three types:- Fireplace heating systems- Thermostoves- Thermocookers
The generators are further divided according to their fuel stoking system:Hand stoking, typically that of log-burning generators, requires an operator to putthe blocks of wood into the generator stoking compartment.
Automatic stoking refers to the last device conveying the fuel (for example pelletsor woodchips) from the storage tank to the combustion chamber.
Hand and automatically stoked boiler
Hand and automatically stoked residential device
BIOMASS
SOLID FUEL GENERATORS
2 ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
M
LOGS
PELLETS
WOODCHIPS
≤1 m ≤1 m
RIARMO
542
1 1/2 X 1 1/2
542
RIARMO
542
1 1/2 X 1 1/2
542
RIARMO
542
1 1/2 X 1 1/2
542
PPM
S
C
≤1 m
≤1 m
Termostato di blocco ariarmo manuale
Termostato di regolazione ariarmo automatico
Termostato di controllo
Pressostato di blocco ariarmo manuale
Dispositivo di protezionelivello minimo
Dispositivo di protezionepressione minima
Dispositivo arrestoaria comburente
Allarme acusticoe ottico
Termometro
Manometro
Rubinetto manometrocampione INAIL
Pozzetto di controlloINAIL
Valvola di sicurezza
Vaso di espansionechiuso
Valvola di scaricotermico
Valvola di scarico disicurezza termica
Valvola di scaricotermico con reintegroincorporato
TR T PPMP
CALDAIAA
COMBUSTIBILESOLIDO
PLM AC
GENERATOREA
COMBUSTIBILESOLIDO
ALTR T
GENERATOREA
COMBUSTIBILESOLIDO
P
In prossimità delgeneratore
All’accumulo(solo con caricamentomanuale e su richiesta
del costruttore.Volume minimo 300 litri)
TL T
DISPOSITIVODOMESTICO
TC TC
DISPOSITIVODOMESTICO
AL
ALTR
T
P
PPM
AC
PLM
TC
AL
S
C
REFERENCE STANDARDS
The standards classify systems according to the expansion system (open or closed vessel) and according to the system for stoking fuel intothe generator, by hand (logs) or automatic (pellets, woodchips etc.).
Here we give some significant examples of open and closed vessel systems made in accordance with applicable standards
3ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
PLMTR T P
SOLIDFUEL
BOILER
Near the generator To storage (only for hand stocked boilers
and on manufacturer’s request. Minimum volume 300 l )
≤1 m
S
C
TL T
RESIDENTIALDEVICE
TC
TR T PPMP
SOLIDFUEL
BOILER
Near the generator To storage (only for hand stocked boilers
and on manufacturer’s request. Minimum volume 300 l )
TP PPM TC
SOLIDFUEL
GENERATOR
Near the generator
RIARMO
542
1 1/2 X 1 1/2
542
≤1 m
PLM AC AL
SOLIDFUEL
GENERATOR
EN 303-5 (2012): Heating boilers for solid fuels, hand andautomatically stoked, nominal heat output of up to 500 kW. Open vessel.
EN 12828 (2012): Heating system in buildings - Design forwater-based heating systems. Closed vessel.
EN 303-5 (2012): Heating boilers for solid fuels, hand andautomatically stoked, nominal heat output of up to 500 kW. Closed vessel.
Black devices: mandatory according to standardsMagenta or “framed” devices: optional or as an alternativeaccording to standards
UNI 10412-2 (2009): Hot water heating systems - Safetyrequirements.Part 2: Requirements for systems with residential solid fuelsburning appliances with boiler, not exceeding a total nominalheat output of 35 kW.Automatically stoked. Closed vessel.
Collection R ISPESL (2009): Applicatory technicalspecifications of Title II of Italian Ministerial Decree DM 1.12.75in accordance with art. 26 of the decree. (P>35 kW for Italy).Hand and automatically stoked. Open vessel.
Generator Power rating Product standard System standard
Boiler Up to 500 kW EN 303-5 (2012) EN 12828 (2012) Europe
Boiler < 35 kW EN 12828 (2012) Italy
Boiler > 35 kW Collection R ISPESL (2009) Italy
Residential Up to 35 kWEN 13229 (2006)EN 13240 (2006)EN 12815 (2006)EN 14785 (2006)
EN 12828 (2012) EuropeUNI 10412-2 (2009) Italy
SAFETY DEVICES
Function
The temperature relief valvedischarges the system water onreaching the setting temperature.Equipped with positive action. Itcan be used with non-pulverizedsolid fuel generators with open orclosed vessel in accordance withcurrent regulations.
INAIL reference standardsAccording to the provisions ofCollection R Ed. 2009, concerning“central heating systems using hotwater with temperatures no greaterthan 110°C and a maximum nominalheat output greater than 35 kW”, theuse of the temperature relief valve iscontemplated in the followingcases:Open vessel systems- Systems with generators stokedwith non-pulverized solid fuel, inplace of the consumption water heater or emergency exchanger(chap. R.3.C., point 2.1, letter i2).
Closed vessel systems- Thermal systems with generators stoked with non-pulverized solidfuels up to a nominal heat output of 100 kW with partial cut-off inplace of the residual power dissipation device (chap. R.3.C., point 3.2).
Function
The temperature safety reliefvalve limits the watertemperature in solid fuelgenerators equipped with abuilt-in storage or emergencyexchanger (for immediatecooling).On reaching the settingtemperature, the valve opensthe flow of mains waterthrough the emergencyexchanger or built-in storageunit, so as to draw off theexcess heat and therebylower the temperature of thesystem water contained in theboiler jacket.
Reference standardsIts use is contemplated in the INAIL standards, Collection R - ed.2009, chapter R.3.C., point 2.1, letter i2; point 3.1, letter i; point 3.3.The valve complies with EN 14597, it can be combined with solidfuel generators with a heat output of less than 100 kW, according tothe system provisions of the standards EN 12828, UNI 10412-2 andEN 303-5.
SOLID FUELGENERATOR
RIARMO
542
1 1/2 X 1 1/2
542
SOLID FUELGENERATOR
4 ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
542 tech. broch. 01001
Temperature relief valve, with fail-safe action.Manual reset for burner switch off or alarm activation.Working pressure: 0,3 ≤ P ≤ 10 bar.Working temperature range: 5–100°C.Setting temperature 98°C and 99°C.Certified and calibrated to INAIL.Discharge rating:1 1/2” x 1 1/4” - 136 kW.1 1/2” x 1 1/2” - 419 kW.
Code
542870542880
1 1/2” M x 1 1/4” F1 1/2” M x 1 1/2” F
98°C99°C
Setting
543 tech. broch. 01057
Temperature safety relief valve,with double safety sensor, for solid fuel generators.Max. working pressure: 10 bar.
Working temperaturerange: 5–110°C. Setting temperature: 98°C (0/-4°C).
Discharge flow rate with Dp of 1 bar and T=110°C: 3000 l/hLength of capillary: 1300 mm.Certified to EN 14597 standard.
Code
543513 3/4” F 98°C
Setting
5ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
SAFETY DEVICES
Function
The draught regulating valve,installed on the boiler with thethermostatic element immersed inthe medium, automaticallyadjusts the flow rate of thecomburent air to provide a moreregular and completecombustion.
529 tech. broch. 01226
Draught regulating valve.Male threaded connection.Adjustment range: 30–90°C.Certified to EN 14597 standard.
Function
On reaching the settingtemperature, the temperature reliefvalve discharges the water of thesystem with a solid fuel generator.The device integrates in a singlegroup a temperature relief valvewith a positive safety remotesensor and a filling valve. Thedischarge of water enables limitingthe system water temperature,while the filling inlet enables thereplacement of the dischargedflow rate.
Reference standardsUsed when there is no emergencyexchanger and for heat outputs < 35 kW (Italy).
S
C
RESIDENTIALDEVICE
544 tech. broch. 01058
Temperature relief valve, with positiveaction, with automatic filling.For solid fuel generators.Max. working pressure: 6 bar.Max. working temperature: 110°C.Working temperature range: 5–110°C.Ambient temperature range: 1–50°C.Setting temperature: 100°C (0/-5°C).Discharge flow rate with Dp of 1 barand T=110°C: 1600 l/h.Length of capillary: 1300 mm.
Code
544400 1/2” F
Code
529150 3/4” M ISO 7/1
100°C
Setting
Function
The device integrates in a singlegroup a temperature relief valveand a filling valve that operatesimultaneously by means of asensor integrated in the valvebody. On reaching the setting value,the valve opens the dischargeoutlet to eliminate the excess heatand, at the same time, the fillinginlet to replace the discharged flowrate of the system water.
Reference standardsUsed when there is no emergencyexchanger and for heat outputs < 35 kW (Italy).
Cold waterinlet
To heatingsystem
From heatingsystem
Drain
Filling group
RESIDENTIALDEVICE
Alimentazioneelettrica
Centralina
3 5
9
8
6
7
1 2 4
544Temperature relief valve with automaticfilling for solid fuel generators, with knob for manual discharge Max. working pressure: 6 bar.Max. working temperature: 120°C.Setting temperature: 100°C (0/-5°C).Discharge flow rate with Dp of 1 barand T=110°C: 1800 l/h.
Code
544501 3/4” 100°C
Setting
6 ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
Flowby-pass
Syst
emre
turn
Retu
rnto
gen
erat
or
2
5
3
4
1
M
Flue gas andemission control
Zones of condensationforming:• Deposits and tar• Corrosion• Reduction in heat
exchanger efficiency• Flammability
Primary andsecondary air:• Combustion
efficiency Accumulationof ash and residues
SR
ANTI-CONDENSATION
SF
ANTI-CONDENSATION VALVE
Function
The anti-condensation valve, used in heating systems with a solidfuel generator, automatically regulates at the set value thetemperature of the water returning to the generator. Keeping the boiler at a high temperature prevents condensation ofthe water vapour contained in the flue gas.Condensation produces tarry deposits that, accumulating on themetal surfaces of the flue gas-system water exchanger, causecorrosion, reduce the thermal efficiency of the flue gas-systemwater exchanger and are a source of danger for the flue gaschimney as they are flammable.The anti-condensation valve gives the generator a longer life andensures greater efficiency.
Technical specifications
PerformanceMedium: water, glycol solutionsMaximum percentage of glycol: 50%Max. working pressure: 10 barWorking temperature range: 5–100°CSetting temperature (Tset): z45°C, 55°C, 60°C, 70°CSetting accuracy: ±2°CBy-pass complete closing temperature: Tmix= Tset + 10°C = Tr
Connections: 3/4” - 1” - 1 1/4” M with union
Installation in mixing mode (anti-condensation) Installation in diverter mode
Characteristic components
1) Thermostatic sensor2) Obturator3) Spring
4) Plug5) Valve body
Thermostat replacement to modify settingThe adjustment sensor can easily be removed for maintenance orto change the set, with no need to remove the valve body from thepiping.
InstallationThe valve can be fitted onboth sides of the generator inany position, vertical orhorizontal.Installation is recommendedon the return to thegenerator in mixing mode; itis also allowed on the flowfrom the generator in divertermode.
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Tf
TrTmix
Tset
280 tech. broch. 01223
Anti-condensation valve with thermostatic control of the return temperature to solid fuel generators.Brass body.
Setting 45°C 55°C 60°C 70°C� 4 5 76
�Code completion
28005�
28026�*
28006�
28007�
Code
3/4”1”1”
1 1/4”
Connection
3,23,2912
Kv (m3/h)
20202532
DN
45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C
Settings
Valve selectionThe valve selection should be made according to the Kv value(corresponding to a specific DN body size) and not only according tothe threaded connections. Given the system flow rate, thecorresponding head losses on the valve should be calculated by usingthe Kv value. The sum of the head losses on the valve and the headlosses of the rest of the system should be compatible with theavailable head of the generator pump.
* Caution: same Kv value of 3/4” valve.
M M
SOLID FUELGENER ATOR
M M
SOLID FUELGENER ATOR
7ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
Tf
TrTmix
Tset
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Tf
TrTmix
Tset
ANTI-CONDENSATION VALVE
Operating principle
The thermostat, completely immersed in the medium, controls the movement of an obturator that regulates the flows in by-pass and toward thesystem. On starting up the generator, the anti-condensation valve recirculates the flow water so as to bring the generator up to temperature asquickly as possible (1). When the flow temperature Tf exceeds the set of the anti-condensation valve Tset, the valve’s cold port starts openingto produce the mixing Tmix: in this phase the system loading begins (2). When the generator return temperature Tmix is greater than the settingof the anti-condensation valve by approximately 10°C, the by-pass port gets closed and water returns to the generator at the same temperatureof the system return (3 and 4).
1
Tmix = Tset + 10°C BY-PASS CLOSINGby-pass closedsystem return open
Tf > Tmix = Tset +10°C, Tmix=Tr
Tmix > Tset + 10°C SYSTEM LOADEDby-pass closedsystem return open
Tf > Tmix > Tset +10°C, Tmix=Tr
Tf > Tset START OF SYSTEM LOADINGby-pass opensystem return open
Tf > Tset, Tr < Tset, Tmix=Tset
Application diagram
System with inertial storage
2
3 4
Tf ≤ Tset SYSTEM START UP TRANSIENTby-pass opensystem return closed
Tf ≤ Tset, Tmix=Tf
Tf = Flow temperatureTset = Anti-condensation set temperature
Tmix = Mixed water temperature of generator returnTr = System return temperature
Safety devices to choose according tocurrent regulations
Construction details
Compact constructionThe unit features all the functional components assembled in a kitand ready for installation.
Anti-condensation valveThis device incorporates a thermostatic sensor to control thetemperature of the water returning to the generator so as to preventcondensation. The sensor has been specifically realised to beremoved from the valve body for maintenance or replacement ifnecessary.
Check valveThis device prevents reverse circulation of the medium. The checkvalve is useful when the circulation unit is used on its own for adirect connection to the system or for the connection to a manifoldnot equipped with a hydraulic separator.
ANTI-CONDENSATION CIRCULATION UNIT
Systemreturn
Systemflow
Generatorreturn
Generatorflow
8 ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
Function
The anti-condensation circulation unit performs the function ofconnecting the solid fuel generator to the distribution manifold,controlling the return temperature to the generator, to avoidcondensation by means of the built-in thermostatic device. The unitalso enables connecting the generator to the inertial storage ordirectly to the user system.
Both centre distances, 90 and 125 mm, have been specificallydesigned for the connection to the separator/distribution manifold559 series, both for the external use and the recess mountingversions.
Technical specifications
Performance
Medium: water, glycol solutionsMax. percentage of glycol: 50%Working temperature range: 5–100°CMax. working pressure: 10 bar Temperature gauge scale: 0–120°C
Connections: - system circuit: 1” F with union- generator circuit: 1” F- connection centre distance: 90 mm / 125 mm
Anti-condensation valveWorking temperature range: 5–100°CSetting temperature (Tset): 45°C, 55°C, 60°C, 70°CSetting accuracy: ±2°CBy-pass complete closing temperature: Tmix = Tset +10°C = Tr
PumpHigh-efficiency pump: models 25-60 ALPHA2 L and UPML 25-95
Technical specifications of insulationMaterial: closed cell expanded PE-XThickness: 20 mmDensity: internal part 30 kg/m3
external part 50 kg/m3
Thermal conductivity (DIN 52612): at 0°C 0,038 W/(m·K)at 40°C 0,045 W/(m·K)
Coefficient of resistance to the diffusion of water vapour (DIN 52615): > 1.300Temperature range: 0–100°CReaction to fire (DIN 4102): class B2
Characteristic components
1) Anti-condensation valve2) High-efficiency pump3) Shut-off valves4) Check valve
5) Flow temperature gauge6) Return temperature gauge7) Insulation
282 tech. broch. 01225
Circulation unitwith anti-condensation valve,with thermostatic control of the return temperature to solid fuel generators.With insulation.
Setting 45°C 55°C 60°C 70°C� 4 5 76
� Code completion
Code Connection
Code Connection
Connectioncentredistance
Connectioncentredistance
Generator return on LH side
Generator return on RH sideSettings
Settings
28261�A2L28265�UPM28263�A2L28267�UPM
1” F1” F1” F1” F
190 mm190 mm125 mm125 mm
45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C
28260�A2L28264�UPM28262�A2L28266�UPM
1” F1” F1” F1” F
190 mm190 mm125 mm125 mm
45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C
9ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
ANTI-CONDENSATION CIRCULATION UNIT
Ser
ie 1
67S
erie
167
230
V23
0 V
˜̃ ±1
0%±1
0% 6
VA
6 V
AA
mb.
tem
p. ra
nge
-10÷
55°C
Am
b. te
mp.
rang
e -1
0÷55
°CO
peni
ng/c
losin
g tim
e 50
sO
peni
ng/c
losin
g tim
e 50
s90
° ro
tatio
n90
° ro
tatio
nIP
65
IP 6
5
Cod. 167012 Cod. 167012
AU
TOA
UTO
MA
NM
AN
Ope
nO
pen
BBO
pen
Ope
nAA
1313
SOLID FUEL GENERATOR
Application diagram
System with SEPCOLL, solid fuel generator combined with gasgenerator
In the event of multiple presence ofgenerators, apply the current regulations
Ser
ie 1
67S
erie
167
230
V23
0 V
˜̃ ±1
0%±1
0% 6
VA
6 V
AA
mb.
tem
p. ra
nge
-10÷
55°C
Am
b. te
mp.
rang
e -1
0÷55
°CO
peni
ng/c
losin
g tim
e 50
sO
peni
ng/c
losin
g tim
e 50
s90
° ro
tatio
n90
° ro
tatio
nIP
65
IP 6
5
Cod. 167012 Cod. 167012
AU
TOA
UTO
MA
NM
AN
Ope
nO
pen
BBO
pen
Ope
nAA
1313
Connection to the primary side of the 559 series SEPCOLLseparator/manifold.The solid fuel generator is used as a single energy source (primaryside) and is therefore connected upstream of the hydraulicseparation zone of the 559 series SEPCOLL unit.
Connection to inertial storage.The unit performs the function of connection and hydrauliccirculation between the solid fuel generator and the inertial storage,both in direct mode and with coil exchanger immersed in thestorage.
Direct connection to the system. The unit can be directly connected to the system, using the pumpas a circulator for the entire system.
Connection to manifold with storage in parallelThe unit connects the generator to the manifold for direct supply tothe secondary circuits or in parallel to the inertial storage.
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
SOLID FUEL GENERATOR
code. 28261.A2Lcode. 28263.A2Lcode. 28265.UPMcode. 28267.UPM
code. 28260.A2Lcode. 28262.A2Lcode. 28264.UPMcode. 28266.UPM
code. 28261.A2Lcode. 28263.A2Lcode. 28265.UPMcode. 28267.UPM
code. 28261.A2Lcode. 28263.A2Lcode. 28265.UPMcode. 28267.UPM
code. 28261.A2Lcode. 28263.A2Lcode. 28265.UPMcode. 28267.UPM
Flowby-pass
Generatorreturn
Systemreturn
2
4
1
3
5
5
54
4 6
Function
The anti-condensation recirculation and distribution unit enables theconnection of the solid fuel generator to the user system (direct orwith inertial storage). It controls the return temperature to thegenerator to avoid condensation, by means of the built-inthermostatic sensor.
Technical Specifications
Performance
Medium: water, glycol solutionsMax. percentage of glycol: 50%Working temperature range: 5–100°CMax. working pressure: 10 barMaximum recommended flow rate: 2 m3/hTemperature gauge scale: 0–120°C
Connections: 1” F and 1 1/4” F with union
Anti-condensation valveWorking temperature range: 5–100°CSetting temperature (Tset): 45°C, 55°C, 60°C, 70°CSetting accuracy: ±2°CBy-pass complete closing temperature: Tmix = Tset +10°C = Tr
PumpThree-speed pump / high-efficiency pump:
RS 4-3 / YONOS PARA 25/6 RKC
Technical specifications of insulationMaterial: EPPMean thickness: 30 mmDensity: 45 kg/m3
Working temperature range: 5–100°CThermal conductivity: 0,037 W/(m·K) at 10°CReaction to fire (UL94): class HBF
Construction details
Single casting and reversibilityThe compact brass single casting, that houses the pump andfunctional components, enables immediate installation of thedevice, either on the right or left of the solid fuel generator,respecting the flow directions as shown. The temperature gaugescan be extracted from the housings and re-inserted in the sameposition on the back side of the unit.
Anti-condensation valveThis device incorporates a thermostatic sensor to control thetemperature of the water returning to the solid fuel generator so asto prevent condensation. The sensor has been specifically realisedto be removed from the valve body for maintenance or replacementif necessary.
Natural circulation clapet valveThe function of this clapet device is to ensurenatural circulation of the medium in the event ofpump stop due to an electric power failure.When the pump is active, the thrust of mediumkeeps the valve closed, forcing the water to flowthrough the anti-condensation thermostaticvalve. If the event of pump stop, when the waterwithin the boiler is at high temperature, a naturalcirculation of the water begins, by-passing the anti-condensationvalve, thus preventing the temperature in the generator fromreaching dangerous high levels. The unit is provided with naturalcirculation valve locked. To activate its function, remove the lockingscrew.
Dirt separatorIn order to carry out continuous dirt separationin the system it is available the 5462 seriesDIRTCAL® dirt separator as accessory.
Characteristic components
1) Anti-condensation thermostatic device2) Three-speed pump / High-efficiency pump3) Natural circulation clapet valve4) Union with built-in ball valve5) Temperature gauge housing6) Insulation
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
ANTI-CONDENSATION RECIRCULATION AND DISTRIBUTION UNIT
10
281 tech. broch. 01224
Anti-condensation recirculationand distribution unit,
with thermostatic control of the return temperatureto solid fuel generators. Brass body.With insulation.
Flowby-pass
Generatorreturn
Systemreturn
2
4
1
3
5
5
54
4 6
Setting 45°C 55°C 60°C 70°C� 4 5 76
� Code completion
Code SettingsConnectionDN
28106�
28106�WYP28107�
28107�WYP
45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C45°C 55°C 60°C 70°C
1” F1” F
1 1/4” F1 1/4” F
25252525
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
ANTI-CONDENSATION RECIRCULATION AND DISTRIBUTION UNIT
Tf
TrTmix
Tset
Tf
Tf
Tmix Tmix
Tset Tset
TrTr
Tf
TrTmix
Tset
Tf
Tf
Tmix Tmix
Tset Tset
TrTr
Tf
TrTmix
Tset
Tf
Tf
Tmix Tmix
Tset Tset
TrTr
Tf
TrTmix
Tset
Tf
Tf
Tmix Tmix
Tset Tset
TrTr
Operating principle
The thermostat, completely immersed in the medium, controls the movement of an obturator that regulates the flows in by-pass and toward thesystem. On starting up the generator, the recirculation unit recirculates the flow water so as to bring the generator up to temperature as quicklyas possible (1). When the flow temperature Tf exceeds the set of the anti-condensation valve Tset, the unit’s cold port starts opening to producethe mixing Tmix: in this phase the system loading begins (2). When the generator return temperature Tmix is greater than the set of the anti-condensation valve by approximately 10°C, the by-pass port gets closed and water returns to the generator at the same temperature of thesystem return (3).
M M
SOLID FUELGENERATOR
M M
SOLID FUELGENERATOR
Application diagram
System with inertial storage
11
1
Tmix > Tset + 10°C SYSTEM LOADEDby-pass closedsystem return open
Tf > Tmix > Tset +10°C, Tmix=Tr
PUMP OFFNatural circulation valve openNatural circulation of the medium
Tf > Tset START OF SYSTEM LOADINGby-pass opensystem return open
Tf > Tset, Tr < Tset, Tmix=Tset
2
3 4
Tf ≤ Tset SYSTEM START UP TRANSIENTby-pass opensystem return closed
Tf ≤ Tset, Tmix=Tf
Tf = Flow temperatureTset = Anti-condensation set temperature
Tmix = Mixed water temperature of generator returnTr = System return temperature
Safety devices to choose accordingto current regulations
CONNECTION AND ENERGY MANAGEMENT COMPACT UNIT(heating version)
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
12
285060HE1285065HE1285060HE2285065HE2
Code
without anti-condensation valve
without anti-condensation valve
RS 4-3
RS 4-3
Y. P. 25/6
Y. P. 25/6
Primarycirculationpump
1”1”1”1”
DN
2850 tech. broch. 01259
Connection and energymanagement compact unit.
BOILER FLOWSYSTEMFLOW
BOILER RETURNSYSTEMRETURN
SOLID FUEL GENER.FLOW
SOLID FUEL GENER.RETURN
Function
Main functional features:- connection of new solid fuel generators (both boilers andresidential devices, with maximum heat output of 35 kW, bothwith open or closed vessel);
- automatic operation management between the solid fuel generatorand boiler;
- built-in anti-condensation system (optional) for solid fuel generator;
- compact unit with reduced overall dimensions, with easy hydraulic connection
Characteristic components
1) Single casting unit with RS 4-3 or YONOS PARA 25/6 RKC pump, complete with anti-condensation valve (optional), primary side
2) YONOS PARA 15/6 RKA pump, secondary side (system)3) Brazed plate heat exchanger4) Digital regulator5) Shut-off valve6) Wall mounting tamplate7) Check valve8) Manual air vent9) Temperature gauge
Code
285010
Painted steel cover RAL 9010.
Technical specification
Performance
Medium: water, glycol solutionsMax. percentage of glycol: 30%Working temperature range: 5-100°CMax. working pressure: 10 barMax. heat exchanger net output: 35 kWMax. recommended primary circuit flow rate: 1,7 m3/hMax. recommended secondary circuit flow rate: 1,7 m3/hAnticondensation setting temperature (Tset): 55°CSetting accuracy: ±2°CBy-pass complete closing temperature: Tmix = Tset+10°C = TrConnections: - primary side: 1” F
- secondary side, system: 1” F- secondary side, boiler: 3/4” F
RegulatorElectric supply: 230 V - 50/60 Hz
PumpPrimary circuit: 3 speed pump RS 4-3
or high-efficiency YONOS PARA 25/6 RKCSecondary circuit: high-efficiency pump YONOS PARA 15/6 RKA
Open vessel
Closed vessel
TP 1 P 2
RT
Heating system
S1
SOLID FUELGENERATOR
S1
R4
HEATINGBOILER
Check valve to be compulsory installed
*
SOL ID FUELGENERATOR *
SOLID FUELGENERATOR
FLOW
SOLID FUELGENERATOR
RETURN
BOILERFLOW
SYSTEMFLOW
BOILERRETURNSYSTEMRETURN
TP 1 P 2
R T
S1
S1
R4
Open vessel
Closed vessel
Heating system
SOLID FUELGENERATOR
HEATINGBOILER
Check valve to be compulsory installed
*
SOLID FUELGENERATOR
*
SOLID FUELGENERATOR
FLOW
SOLID FUELGENERATOR
RETURN
BOILERFLOW
SYSTEMFLOW
BOILERRETURNSYSTEMRETURN
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
CONNECTION AND ENERGY MANAGEMENT COMPACT UNIT(heating version)
Operating conditions
The digital regulator automatically manages the unit’s operation, receiving the signal from the probe on the solid fuel generator flow pipe andactivating the pumps. If the solid fuel generator is not active, the boiler is actived for the heating system.
13
Phase 1: solid fuel generator active- Coloured components = active, grey components = not active- Pumps P1 and P2 ON- Boiler OFF- Pump P2 supplies the heating system with water
Phase 2: solid fuel generator off or not at temperature- Coloured components = active, grey components = not active- Pumps P1 and P2 OFF- Boiler active- Boiler pump supplies the heating system with water
Heating with solid fuel generator
Heating with boiler
CONNECTION AND ENERGY MANAGEMENT UNIT(heating version)
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
SOLI
D FU
ELG
ENER
ATO
RFL
OW
SOLI
D FU
ELG
ENER
ATO
RRE
TURN BO
ILER
FLO
W
BOIL
ERRE
TURN
SYST
EMRE
TURN
SYST
EMFL
OW
Function
The connection and energy management unit preassembled in thebox enables combining solid fuel generators with another type ofgenerator, which may already be present in the heating system.Main functional features:- connection of new solid fuel generators (both boilers andresidential devices, with maximum heat output of 35 kW, bothwith open or closed vessel) with other closed vessel generators;
- possibility of not adding the power outputs of the twogenerators as described in INAIL (Italy);
- automatic system management with a specific digital regulator forheating circuits and simple thermal solar system;
- built-in anti-condensation system (optional) for solid fuel generator;- easy access to components for maintenance; - practical installation thanks to the arrangement in a box.
Technical specifications
Performance
Medium: water, glycol solutionsMax. percentage of glycol: 30%Working temperature range: 5–100°CMax. working pressure: 10 barMax. heat exchanger net output: 35 kWMax. recommended primary circuit flow rate: 1,5 m3/hMax. recommended secondary circuit flow rate (system): 1,5 m3/h
Anti-condensation set temperature (optional)(Tset):45°C, 55°C, 60°C, 70°C
Setting accuracy: ±2°CBy-pass complete closing temperature: Tmix = Tset+10°C = Tr
Connections: 3/4” M
RegulatorElectric supply: 230 V - 50/60 Hz
PumpsHigh-efficiency pump: YONOS PARA 25/6 RKA
YONOS PARA 15/6 RKA
Diverter valve with spring returnMax. working pressure: 10 barDp max: 1 bar
Diverter valve actuator with spring returnSynchronous motorNormally closedPower supply: 230 V - 50 HzOpening time: 70–75 sClosing time: 5–7 s
Characteristic components
1) Wilo YONOS PARA 25/6 RKA pump on primary side for solid fuel generator
2) Wilo YONOS PARA 15/6 RKA pump on secondary side (system)
3) Brazed plate heat exchanger4) Anti-condensation valve (optional)5) Three-way diverter valve
with spring return6) Dirt separator7) Digital regulator8) Shut-off ball valves 9) Box for exposed mounting
A) Code 285150WYP without anti-condensation valve
14
28515.WYP285150WYP
Codice
3/4” M
3/4” M without anti-condensation valve
2851 tech. broch. 01227
Connection and energy management unit, heating version.
45°C 55°C 60°C 70°C —
Settings
Setting 45°C 55°C 60°C 70°C� 4 5 76
� Code completion
A
Code 285150WYP without anti-condensation valve
Open vessel
Closed vessel
SO
LID
FU
EL
GE
NE
RA
TO
R
FLO
W
SOLI
D F
UEL
GEN
ERA
TOR
RET
UR
N
BO
ILER
FLO
W
BO
ILER
RET
UR
N
SYST
EMR
ETU
RN
SYST
EMFL
OW
D
T
P 1
P 2
C
V1
RT
Heating system
BOILERHEATING
K
S1
K
S1
SOLID FUELGENER ATOR
SOLID FUELGENER ATOR
K
S1
K
S1
D
T
P1
P2
C
V1
TR
SO
LID
FU
EL
GE
NE
RA
TO
R
FLO
W
SO
LID
FU
EL
GE
NE
RA
TO
RR
ET
UR
N
BO
ILE
RFL
OW
BO
ILE
RR
ET
UR
N
SY
ST
EM
RE
TU
RN
SY
ST
EM
FLO
W
Open vessel
Closed vessel
Heating system
BOILERHEATING
SOLID FUELGENERATOR
SOLID FUELGENERATOR
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
CONNECTION AND ENERGY MANAGEMENT UNIT(heating version)
Operating conditions
The digital regulator automatically manages the unit’s operation, receiving the signal from the probes and activating the pumps, the motorizedvalve and the generators. The heating circuit is managed according to need.
15
Phase 1: solid fuel generator active- Coloured components = active, grey components = not active- Pumps P1 and P2 ON- Boiler OFF- Valve V1 connects the system to the solid fuel generator via the heat exchanger
Phase 2: solid fuel generator off or not at temperature- Coloured components = active, grey components = not active- Pumps P1 and P2 OFF- Boiler active- Valve V1 connects the system to the boiler
Heating with solid fuel generator
Heating with boiler
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
CONNECTION AND ENERGY MANAGEMENT UNIT(heating and domestic hot water with storage version)
Open vessel
Closed vessel
Heating system
BOILERHEATING
SOLID FUELGENERATOR
SOLID FUELGENERATOR
SOLI
D FU
ELG
ENER
ATO
RFL
OW
SOLI
D FU
ELG
ENER
ATO
RRE
TURN
BOIL
ER F
LOW
BOIL
ER R
ETU
RN
SYST
EMRE
TURN
SYST
EMFL
OW
DHW
STO
RAG
ERE
TURN
DHW
STO
RAG
EFL
OW
Function
The connection and energy management unit preassembled in thebox enables combining solid fuel generators with another type ofgenerator, which may already be present in the heating system.The unit is fitted for the production of domestic hot water with aconnection to a storage.Main functional features:- connection of new solid fuel generators (both boilers andresidential devices, with maximum heat output of 35 kW, bothwith open or closed vessel) with other closed vessel generators
- possibility of not adding the power outputs of the twogenerators as described in INAIL (Italy)
- automatic system management with a specific digital regulator forheating circuits, domestic water storage and simple solar thermalsystem
- built-in anti-condensation system (optional) for solid fuelgenerator
- easy access to components for maintenance- practical installation thanks to the arrangement in a box.
Technical specifications
Performance
Medium: water, glycol solutionsMax. percentage of glycol: 30%Working temperature range: 5–100°CMax. working pressure: 10 barMax. heat exchanger net output: 35 kWMax. recommended primary circuit flow rate: 1,5 m3/hMax. recommended secondary circuit flow rate (system): 1,5 m3/h
Anti-condensation set temperatures (optional) (Tset):45°C, 55°C, 60°C, 70°C
Setting accuracy: ±2°CBy-pass complete closing temperature: Tmix = Tset+10°C = Tr
Connections: 3/4” M
RegulatorElectric supply: 230 V - 50/60 Hz
PumpsSee 2851 series
Diverter valves with spring returnSee 2851 series
Diverter valve actuator with spring returnSynchronous motorNormally closedPower supply: 230 V - 50 HzOpening time: 70–75 sClosing time: 5–7 s
16
Characteristic components
1) Wilo YONOS PARA 25/6 RKA pump on primary side for solid fuel generator
2) Wilo YONOS PARA 15/6 RKA pump on secondary side (system)
3) Brazed plate heat exchanger4) Anti-condensation valve (optional)5) Three-way diverter valve
with spring return6) Dirt separator7) Digital regulator8) Shut-off ball valves 9) Box for exposed mounting10) Three-way diverter valve
with spring return for priority on domestic water with storage
A) Code 285350WYP without anti-condensation valve
A
Code 285350WYPwithout anti-condensation valve
28535.WYP285350WYP
Codice
3/4” M
3/4” M without anti-condensation valve
45°C 55°C 60°C 70°C —
Settings
Setting 45°C 55°C 60°C 70°C� 4 5 76
� Code completion
2853 tech. broch. 01228
Connection and energy management unit, heating and domestic hot water with storage version.
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
TA
K
S1
K
S1
D
T
P1V2
P2
C
V1
S2
RT
Domestic watersystem
DCW
DHW
D
SO
LID
FU
EL
GE
NE
RA
TO
R
FLO
W
SO
LID
FU
EL
GE
NE
RA
TO
RR
ET
UR
N
BO
ILE
R F
LOW
BO
ILE
R R
ET
UR
N
SY
ST
EM
RE
TU
RN
SY
ST
EM
FLO
W
Open vessel
Closed vessel
Heating system
BOILERHEAT ING
SOLID FUELGENERATOR
DHW
STO
RAG
ERE
TURN
DHW
STO
RAG
EFL
OW
SOLID FUELGENERATOR
TA
K
S1
K
S1
D
T
P1V2
P2
C
V1
S2
RT
DCW
DHW
D
Domestic watersystem
SO
LID
FU
EL
GE
NE
RA
TO
R
FLO
W
SO
LID
FU
EL
GE
NE
RA
TO
RR
ET
UR
N
BO
ILE
R F
LOW
BO
ILE
R R
ET
UR
N
SY
ST
EM
RE
TU
RN
SY
ST
EM
FLO
W
Open vessel
Closed vessel
Heating system
BOIL ERHEATING
SOL ID FUELGENER ATOR
DHW
STO
RAG
ERE
TURN
DHW
STO
RAG
EFL
OW
SOL ID FUELGENER ATOR
Operating conditions
The digital regulator automatically manages the unit’s operation, receiving the signal from the probes and activating the pumps, the motorizedvalves and the generators. The heating circuit and the preparation of domestic hot water with storage are managed according to need.
NOTE: for heating operation, please refer to the diagrams in “Connection and energy management unit, heating version”2851 series
CONNECTION AND ENERGY MANAGEMENT UNIT(heating and domestic hot water with storage version)
17
Phase 1: solid fuel generator active- Coloured components = active, grey components = not active
- Pumps P1 and P2 ON- Boiler OFF- Valve V1 connects the system to the solid fuel generator via the heat exchanger- Valve V2 diverts the flow of system water towards the domestic water storage
Phase 2: solid fuel generator off or not at temperature- Coloured components = active, grey components = not active
- Pumps P1 and P2 OFF- Boiler active- Valve V1 connects the system to the boiler- Valve V2 diverts the flow of system water towards the domestic water storage
Domestic hot water production with solid fuel generator
Domestic hot water production with boiler
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
CONNECTION AND ENERGY MANAGEMENT UNIT(heating and instantaneous domestic hot water version)
DHW
OU
TLET
DCW
INLE
T
BOIL
ER F
LOW
BOIL
ER R
ETU
RN
SYST
EMRE
TURN
SYST
EMFL
OW
SOLI
D FU
ELG
ENER
ATO
RFL
OW
SOLI
D FU
ELG
ENER
ATO
RRE
TURN
Function
The connection and energy management unit preassembled in thebox enables combining solid fuel generators with another type ofgenerator, which may already be present in the heating system.The unit is fitted for the production of instantaneous domestic hotwater with a heat exchanger.Main functional features:- connection of new solid fuel generators (both boilers andresidential devices, with maximum heat output of 35 kW, bothwith open or closed vessel) with other closed vessel generators
- possibility of not adding the power outputs of the twogenerators as described in INAIL (Italy)
- automatic system management with a specific digital regulator forheating circuits, instantaneous production of domestic hot waterand simple solar thermal system
- built-in anti-condensation system (optional) for solid fuelgenerator
- easy access to components for maintenance- practical installation thanks to the arrangement in a box.
Technical specifications
Performance
Medium: water, glycol solutionsMax. percentage of glycol: 30%Working temperature range: 5–100°CMax. working pressure: 10 barMax. heat exchanger net output: 35 kWMax. recommended primary circuit flow rate: 1,5 m3/hMax. recommended secondary circuit flow rate (system): 1,5 m3/hMax. domestic hot water heat exchanger net output: 35 kWMax. domestic hot water flow rate delivery: 1,1 m3/h
Anti-condensation set temperatures (optional) (Tset):45°C, 55°C, 60°C, 70°C
Setting accuracy: ±2°CBy-pass complete closing temperature: Tmix = Tset + 10°C = Tr
Connections: 3/4” M
RegulatorElectric supply: 230 V - 50/60 Hz
PumpsSee 2851 series
Flow switchContacts normally open (NO)Contacts close with increasing flow at: 156 l/h Contacts open with decreasing flow at: 108 l/h
Diverter valve with spring returnSee 2851 series
Diverter valve actuator with spring returnSee 2851 series
Diverter ball valve for DHW priorityMax. working pressure: 10 barDp max: 10 bar
Diverter ball valve actuator for DHW prioritySynchronous motorElectric supply: 230 V (±10%) - 50/60 HzOperating time (angle of rotation 90°): 10 s
18
Characteristic components
1) Wilo YONOS PARA 25/6 RKA pump on primary side for solid fuel generator
2) Wilo YONOS PARA 15/6 RKA pump on secondary side (system)
3) Brazed plate heat exchanger4) Anti-condensation valve (optional)5) Three-way diverter valve
with spring return6) Dirt separator7) Digital regulator8) Shut-off ball valves 9) Box for exposed mounting10) Three-way three point diverter ball valve
for DHW priority11) Brazed plate heat exchanger for DHW12) Flow switch
A) Code 285550WYP without anti-condensation valve
A
Code 285550WYPwithout anti-condensation valve
28555�WYP285550WYP
Code
3/4” M
3/4” M without anti-condensation valve
45°C 55°C 60°C 70°C —
Settings
Setting 45°C 55°C 60°C 70°C� 4 5 76
� Code completion
2855 tech. broch. 01229
Connection and energy management unit, heating and instantaneous domestic hot water version.
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
TA
D
D
T
P1V3
P2
C
V1
F
S3
RT
Domesticwater system
D
SOLARINCAL
M
DHW
K
S1
K
S1
Open vessel
Closed vessel
Heating system
BOILERHEATING
SOL ID FUELGENERATOR
SOL ID FUELGENERATOR
DHW
OU
TLET
DCW
INLE
T
BOIL
ER F
LOW
BOIL
ER R
ETU
RN
SYST
EMRE
TURN
SYST
EMFL
OW
SOLI
D FU
ELG
ENER
ATO
RFL
OW
SOLI
D FU
ELG
ENER
ATO
RRE
TURN
TA
D
D
T
P1V3
P2
C
V1
F
S3
RT
D
SOLARINCAL
M
DHW
K
S1
K
S1
Domesticwater system
DHW
OU
TLET
DCW
INLE
T
BOIL
ER F
LOW
BOIL
ER R
ETU
RN
SYST
EMRE
TURN
SYST
EMFL
OW
SOLI
D FU
ELG
ENER
ATO
RFL
OW
SOLI
D FU
ELG
ENER
ATO
RRE
TURN
Open vessel
Closed vessel
Heating system
BOILERHEATING
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Operating conditions
The digital regulator automatically manages the unit’s operation, receiving the signal from the probes and activating the pumps, the motorizedvalves and the generators. The heating circuit and the instantaneous preparation of domestic hot water are managed according to need.
NOTE: for heating operation, please refer to the diagrams in “Connection and energy management unit, heating version”2851 series
CONNECTION AND ENERGY MANAGEMENT UNIT(heating and instantaneous domestic hot water version)
19
Phase 2: solid fuel generator OFF or not at temperature- Coloured components = active, grey components = not active- Pumps P1 and P2 OFF- Valve V1 connects the system to the boiler- Boiler active for the production of DHW by means of thermal integration via the kit SOLARINCAL 265 series type
Phase 1: solid fuel generator active- Coloured components = active, grey components = not active- Pumps P1 ON, P2 OFF- Boiler OFF- Valve V1 connects the system to the solid fuel generator via the heat exchanger- Valve V3, activated by the flow switch F, diverts the flow of the solid fuel generator towards the DHW heat exchanger
Domestic hot water production with solid fuel generator
Domestic hot water production with boiler
DIGITAL REGULATOR FOR SYSTEMS WITH SOLID FUEL GENERATOR
Function
The digital regulator makes it possible to combine a solid fuelgenerator with another type of generator already present in theheating system.The digital regulator automatically manages the two generators,receiving the signal from the probes and activating the pumps, themotorized diverter valves in the system, according to the heatingcircuit needs.Depending on the type and quantity of installed probes, theregulator supports the following system solutions:- heating;- production of domestic hot water by means of storage orinstantaneous with plate heat exchanger;
- management of inertial water storage in parallel on the heatingcircuit or alternatively management of an independent solarsystem and direct inertial water storage.
The regulator has different programs which can be customized byuser to several system situations.
Description of controls
1. Functional status indicator LED.2. Mini DIN connector on front of panel for PC connection.3. Display: menu display.4. Select knob: selection of menu, functions and parameter editing.5. Function keys.
20 ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
12
34
5
152200
Code
V5
M M
S5
DD
T
P1
P2
C
V1
BOIL ERHEATING
D
Closed vessel
K
S1
SOL ID FUELGENERATOR
Open vessel
K
S1
S4
V4
Inertialstorage
SOLID FUELGENERATOR
Program diagrams
The regulator allows the management of a thermal system complete with solid fuel generator, a boiler and an inertial water storage in parallel.
The phases of storage loading and unloading are automatically controlled, according to the system needs, with the consequent activation ordeactivation of the boiler and the solid fuel generator.
Depending on the system type, different programs are available to design various functional configurations, both for the heating and thedomestic hot water production.
1522Digital regulatorfor systems with solidfuel generator.Electric supply:230 V (ac); ±10%, 50/60 Hz.Protection class: II.Protection class: IP 40.Complet with three probes.Optional probes to be chosen according to system type.
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
21
DIGITAL REGULATOR FOR SYSTEMS WITH SOLID FUEL GENERATOR
- +
Optimiser ®
ACCUMULOINERZIALEDIRETTO
Sol 2
TR
D
T
P1V2
P2
C
V1
S2
RTAFS
ACS
HEAT INGBOIL ER
D
Sol 1
Psol
S1
DIRECTINERTIALSTORAGE
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Open vessel
Closed vessel
Heating system
Heating with direct inertial water storage, domestic hot water production with storage integrated with solar system
TA
- +
Optimiser ®
ACCUMULOINERZIALEDIRETTO
TRSol 2
V4
T
D
DP1V3
P2
C
V1
F
S3
RT
domesticwater system
D
SOL ARINCAL
M
DHW
D
optionaldissipator
S1
Sol 1
Psol
DIRECTINERTIALSTORAGE
HEATINGBOILER
SOLID FUELGENERATOR
SOLID FUELGENERATOR
Open vessel
Closed vessel
Heating with direct inertial water storage integrated with solar system, instantaneous domestic hot water production
SOLID FUEL GENERATOR-TO-GAS BOILER CONNECTION KIT
22 ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
The integration kits make it possible to combine solid fuel generators, equipped with domestic water storage or instantaneous heat exchanger,with gas boilers. Depending on the temperature, the domestic water arriving from the solid fuel generator is sent directly to the user or divertedinto the boiler for thermal integration.
265 tech. broch. 01163
SOLARINCAL
Function
The thermostat, by means of the probe positioned on the hot waterflow from the storage or the DHW heat exchanger built-into the solidfuel generator, controls the diverter valve at the kit inlet. Dependingon the temperature setting, the valve diverts the water towards theuser circuit or the boiler circuit, with thermal integration.A thermostatic anti-scald mixing valve, at the kit outlet, constantlycontrols the temperature of the water sent to the user.
265352
Code
3/4”
Spare parts for connection kit 265 series.
F29525F29466F29467
Code
switch relay box, 3 contact type
probe Ø 15 mm
pocket probe Ø 15 mm
262 tech. broch. 01164
SOLARINCAL-T.
Function
A thermostatic diverter valve, at the kit inlet, receives hot watercoming from the storage or the DHW heat exchanger built-into thesolid fuel generator.Depending on the temperature setting, the valve diverts the waterautomatically and in a proportional manner towards the user circuitor the boiler with storage circuit, with thermal integration.The valve modulates the flow rates to optimize the energy containedin the storage or instantaneously produced by the heat exchangerbuilt-into the solid fuel generator and reduces boiler operation timesto a minimum.A thermostatic anti-scald mixing valve, at the kit outlet, constantlycontrols and limits the temperature of the water sent to the user.
262350
Code
3/4”
263350
Code
3/4”
263 tech. broch. 01164
SOLARINCAL-T PLUS
Funzione
A thermostatic diverter valve, at the kit inlet, receives hot water comingfrom the storage or the DHW heat exchanger built-into the solid fuelgenerator. Depending on the temperature setting, the valve diverts thewater automatically and proportionally towards the user circuit or theinstantaneous boiler circuit, with thermal integration.The valve modulates the flow rates to optimise the energy contained inthe storage or instantaneously produced by the heat exchanger built-into the solid fuel generator and reduces boiler operation times to aminimum.A specific thermostatic control device limits the boiler inlet temperatureto prevent it being switched on and off too often, which leads to huntingand irregular operation.A thermostatic anti-scald mixing valve, at the kit outlet, constantlycontrols the temperature of the water sent to the user.
SOLID FUEL GENERATOR-TO-GAS BOILER CONNECTION KIT
ACCREDITED
ISO 9001 No. 0003ISO 9001 FM 21654
23
DHWSTORAGE
INSTANTANEOUSDHW WITH COIL
OR HEATEXCHANGER
SOLID FUELGENERATOR
SOLID FUELGENERATOR
MIXEDCOLD
DCWINLET
Application diagram of SOLARINCAL-T 262 series kit with solid fuel generator
MODULATINGBOILER
DHWSTORAGE
INSTANTANEOUSDHW WITH COIL
OR HEATEXCHANGER
SOLID FUELGENERATOR
SOLID FUELGENERATOR
MIXEDCOLD DCW
INLET
Application diagram of SOLARINCAL 265 series kit with solid fuel generator
MODULATINGBOILER DHW
STORAGE
INSTANTANEOUSDHW WITH COIL
OR HEATEXCHANGER
SOLID FUELGENERATOR
SOLID FUELGENERATOR
MIXEDCOLD DCW
INLET
Application diagram of SOLARINCAL-T PLUS 262 series kit with solid fuel generator