Computer Room Requirements for High Density Rack Mounted

Servers

Rhys Newman

Oxford University

Page 2: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Outline• Why do we need computer rooms?

– Why in the past.– Why in the future.

• Design of the environment.– Cooling– Humidity– Power

• Proposal at Oxford Physics• Conclusion

Page 3: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Why do we need them (Past)

• Security– Equipment is valuable.

• Convenience – Specialist Knowledge is needed to look after them.– Networking was relatively difficult.

• Bulk– A single (useful) installation was large

Page 4: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Why we need them (future)

• Specialist Environmental Requirements – High density implies more sensitive.

• Convenience – Human time cost of software maintenance.

Will be needed for the immediate future, but the Grid will reduce the need long term.

Page 5: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Cooling - Then

• Rack mounting designed to get high CPU density – optimise space usage given the effort needed to allocate secure facility.– Until recently, maximum power usage was

about 2-3kw per rack.– Air cooling sufficient, cool air taken directly

from under the floor.– Even conventional air conditioning on the

ceiling was often enough.

Page 6: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Cooling Now: too much Success!• Modern 1U servers are 300W heaters =>

12KW per rack (18KW for blade servers).

• Rule of thumb: 1000 litres/sec of cool air can handle 12KW. – In detail a Dell 1750 uses 1200 l/min.

• For 40 racks, this is 32000 l/sec which in a typical 600mm duct is a wind speed of 320km/hr!

Page 7: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Cooling - Solutions• Focus on airflow!

– Place racks in rows – hot aisle, cold aisle.

– Leave doors off the racks.– Identify hotspots statically,

or dynamically (HP smart cooling).

• Rule of thumb: air cooling can manage 1200W/m2

Page 8: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Major Problem – no bang for buck

• As the processor speeds increase =>

• They get hotter =>• Fewer can exist per

sqr metre =>• Overall CPU power in

datacentre goes DOWN.

All this irrespective of how well you design the air cooling systems!

Page 9: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Cooling Solution II• Try self contained

systems.• Try water cooled units

(self contained or otherwise).

• Use “smarter” systems which actively manage hotspots. HP smart cooling claims to get up to 2.5KW/m2 in this way (??).

Page 10: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Humidity• Computers (in a datacentre) have tighter

tolerances than humans – 45%-55% (despite manufacturer limits of 8%-80%).– Too low, risks static eletricity (fans in the computers

themselves cause this).– Too high, localised condensation, corrosion and

electrical short. Note: Zinc in floor tiles!

• Air conditioning units must be better than for normal offices – how many rooms use conventional units?

No magic bullet of simply importing external air and venting it to the outside!!!

Page 11: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Power• All this heat comes

from the power supply– 1.2A per server– 50A per rack– 4000A for a 40 rack

centre

• And for the cooling systems, a total of 5000A => 1.25 MW.

Page 12: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Summary so far….• Modern machines need a well designed physical

environment to get the most out of them. Most current facilities are no longer well suited (a recent thing).– Intel scrapped 2 chip lines to concentrate on lower

power chips, rather than simply faster.– Sun (and others) are working on chips with multiple

cores and lower clock speeds (good for internet servers, not so good for physics!).

• The cost of the surrounding room is a substantial cost of the entire facility.

Page 13: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Example: 40 Racks for Oxford

• We have an ideal location– Lots of power– Underground (no heat from

the sun and very secure).– Lots of headroom (false

floor/ceiling for cooling systems)

– Basement • no floor loading limit• Does not use up office

space.

Page 14: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Bottom Line• The very basic estimate for the room,

given the shell, is £80k. • Adding fully loaded cooling, UPS, power

conditioning, fire protection etc will probably take this to £400k over time.

• Cost of 40 racks ~ £1.6 million• Infrastructure costs: 25% of setup and up

to 50% of running costs.

Page 15: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Hang on!• There are about 50000

computers already in Oxford university alone.

• Assume 20000 are OK.• Already have a major data

centre, with essentially no infrastructure problems!

• The problem is software – the Grid will exploit these resources and thereby save millions in datacentre costs – medium term!

Page 16: Computer Room Requirements for High Density Rack Mounted Servers Rhys Newman Oxford University

Thank you!

• Sun has a detailed paper at: http://www.sun.com/servers/white-papers/dc-planning-guide.pdf

• APC has a number of useful white papers: http://www.apc.com/tools/mytools/