concrete compression test report imastermix.co.nz/.../12/fire-mortar-test-reports.pdf · concrete...

3
I . CONCRETE COMPRESSION TEST REPORT Project : Location: Client: Contractor : Sampled by : Date sampled: Sampling method: Sample description: Sample condition Source: Grade: Actual slump (mm) : Specified slump (mm) : - Material Evaluation Foxton Plant Mastermix and Packaging Ltd. Mastermix and Packaging Ltd. Client 23/07/07 Unknown Fire Mortar 30kg Bag Client Project No : Lab Ref No : Oient Ref No : 5WT033.M5 2726 (Report 2726.1) Fire Mortar Comments Water added:-135ml per kg. Cylinders were moulded to NZS 3112: Part 2: Section 3 3.4.1b, Compaction by Vibrating table 3.4.2a, Hardened vertically Date reported: 20/09/07 This report may only be reproduced in full Approved RJones ~ / Laboratory . r 28/09/0 Designation: Date: .~~.~.~??~.~.~.~.(.??.e~~~.1 :P~g~J..2q i OpusInternational ConsultantsLimited i Wanganui Office ! QualityManagement SystemsCertifiedtoISO9001 OpusHouse, 104GuytonStreet PO Box 654 Wanganui,NewZealand i Telephone(06) 349 6600 i Facsimile(06) 348 4601 i Websitewww.opus.co.nz Test Results Lab reterence no Client reference no 1 2 Date made 23/08/07 23/08/07 Date tested 27/08/07 27/08/07 Age of material (days) 4 4 Average diameter (mm) 99.8 99.9 Length (mm) 199.4 199.7 Mass of block in air (g) 3663 3665 Design stren (MPa) Density (kg/m') 2330 2330 Height diameter ratio 2.00 2.00 Compressive strength (MPa) 51.0 53.0 Ends capped ONE ONE Defects prior to testing NIL NIL Test Methods Notes Compression, NZS 3112 : 1986, Pt 2 Clause 6 See report LR2726.2 and LR2726.3 for 7 and 28 day strengths. Density, NZS 3112 : 1986, Pt 3 Clause 5 Capping NZS 3112 : 1986, Pt 2 Clause 4 (amendment No 2 2000)

Upload: others

Post on 19-Apr-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONCRETE COMPRESSION TEST REPORT Imastermix.co.nz/.../12/Fire-mortar-test-reports.pdf · CONCRETE COMPRESSION TEST REPORT Material Evaluation Foxton Plant Mastermix and Packaging

I .

CONCRETE COMPRESSIONTEST REPORT

Project :Location:Client:Contractor :Sampled by :Date sampled:Sampling method:Sample description:Sample conditionSource:Grade:Actual slump (mm) :Specified slump (mm) : -

Material EvaluationFoxton Plant

Mastermix and Packaging Ltd.Mastermix and Packaging Ltd.Client23/07/07UnknownFire Mortar

30kg BagClient

Project No :Lab Ref No :Oient Ref No :

5WT033.M5

2726 (Report 2726.1)Fire Mortar

Comments

Water added:-135ml per kg.

Cylinders were moulded to NZS 3112:Part 2: Section 33.4.1b, Compaction by Vibrating table3.4.2a, Hardened vertically

Date reported: 20/09/07 This report may only be reproduced in full

ApprovedRJones ~ /

Laboratory . r28/09/0

Designation:Date:

.~~.~.~??~.~.~.~.(.??.e~~~.1 :P~g~J..2q

i OpusInternationalConsultantsLimitedi WanganuiOffice! QualityManagementSystemsCertifiedto ISO9001

OpusHouse,104GuytonStreetPOBox654

Wanganui,NewZealand

i Telephone(06)349 6600

i Facsimile(06)348 4601

i Websitewww.opus.co.nz

Test ResultsLab reterence noClient reference no 1 2

Date made 23/08/07 23/08/07Date tested 27/08/07 27/08/07Age of material (days) 4 4Average diameter (mm) 99.8 99.9

Length (mm) 199.4 199.7Mass of block in air (g) 3663 3665Design stren (MPa)Density (kg/m') 2330 2330Height diameter ratio 2.00 2.00

Compressive strength (MPa) 51.0 53.0

Ends capped ONE ONEDefects prior to testing NIL NIL

Test Methods Notes

Compression, NZS 3112 : 1986, Pt 2 Clause 6 See report LR2726.2 and LR2726.3 for 7 and 28 day strengths.Density, NZS 3112 : 1986, Pt 3 Clause 5Capping NZS 3112 : 1986, Pt 2 Clause 4 (amendment No 2 2000)

Page 2: CONCRETE COMPRESSION TEST REPORT Imastermix.co.nz/.../12/Fire-mortar-test-reports.pdf · CONCRETE COMPRESSION TEST REPORT Material Evaluation Foxton Plant Mastermix and Packaging

CONCRETE COMPRESSIONTEST REPORT

Material EvaluationFoxton PlantMastermix and Packaging Ltd.Mastermix and Packaging Ltd.Client23/07/07UnknownFire Mortar30k~ Ba~Client

Project :Location:Client:Contractor:

Sampled by :Date sampled:Sampling method:Sample description:Sample conditionSource:Grade:

Actual slump (mm) :Specified slump (mm) : -

Project No :Lab RefNo:ClientRefNo:

5WT033.M5

2726(Report 2726.2)Fire Mortar

Comments

Water added:-13Sml per kg.

Cylinders were moulded to NZS 3112:Part 2: Section 33.4.1b, Compaction by Vibrating table3.4.2a, Hardened vertically

Date reported: 20/09/07

Approved

This report may only be reproduced in full

Designation:Date:

RJones ~Laboratory r28/09/07

.~.~~.~~~.~.~.~(,~.e~~.! r.~g~..l..!?t)

! OpusInternationalConsultantsLimitedi WanganuiOffice: Quality Management Systems Certified to ISO 9001

OpusHouse, 104Guy/onStreetPOBox 654

Wanganui,NewZealand

i Telephone(06)349 6600

i Facsimile(06) 3484601

I Websilewww.opus.co.nz

Test ResultsLab reference noClient reference no 3 4

Date made 23/08/07 23/08/07Date tested 30/08/07 30/08/07Age of material (days) 7 7Average diameter (mm) 103.0 99.9

Length (mm) 202.8 199.7Mass of block in air (g) 3968 3677Design strength (MPa)Density (kg/mO) 2340 2340

Height diameter ratio 1.97 2.00

Compressive strength (MPa) 59.0 61.0

Endscapped ONE ONEDefects prior to testing NIL NIL

Test Methods Notes

Compression, NZ5 3112 : 1986, Pt 2 Clause 6 See report LR2726.1 and LR2726.3 for 4 and 28 day strengths.

Density, NZS 3112 : 1986, Pt 3 Clause 5Capping NZ5 3112 : 1986, Pt 2 Clause 4 (amendment No 2 2000)

Page 3: CONCRETE COMPRESSION TEST REPORT Imastermix.co.nz/.../12/Fire-mortar-test-reports.pdf · CONCRETE COMPRESSION TEST REPORT Material Evaluation Foxton Plant Mastermix and Packaging

CONCRETE COMPRESSIONTEST REPORT

Material EvaluationFoxton PlantMastermix and Packaging Ltd.Mastermix and Packaging Ltd.Client23/07/07UnknownFire Mortar30kg BagClient

Project :Location:Client:Contractor:

Sampled by :Date sampled:Sampling method:Sample description:Sample conditionSource:Grade:

Actual slump (mm) :Specified slump (mm) : -

Project No :Lab Ref No :Oient Ref No :

SWT033.MS

2726 (Report 2726.3)Fire Mortar

Comments

Water added:-135ml per kg.

Cylinders were moulded to NZS 3112:Part 2: Section 33.4.1b, Compaction by Vibrating table3.4.2a, Hardened vertically

Date reported: 20/09/07 This report may only be reproduced in full

IANZ Approved SignatoryRJones ~Designation: Laboratory "

Date: 28/09/07lA

All tests reportedherein have been

0 '='" performed in accordance

I ~ with the laboratory's-Iab-- scope of accreditation

ora~ory

.~.~~.~~~.~.~.~(~!.:??~.! , ,., ~!!!g~J..9.f.)

! OpUSInternational Consultants Limited

! WanganuiOffice~Quality Management Systems Certified to ISO 9001

OpusHouse,104GuytonStreetPOBox654

Wanganui,NewZealand

! Telephone(06)349 6600

! Facsimile (06) 3484601

i Website www.opus.co.nz

Test ResultsLab reference noClient reference no 5 6

Date made 23/08/07 23/08/07Date tested 20/09/07 20/09/07Age of material (days) 28 28Average diameter (mm) 99.9 100.0

Length (mm) 199.8 199.4Mass of block in air (g) 3684 3671Design strength (MPa)Density (kg/m") 2340 2340Height diameter ratio 2.00 1.99

Compressive strength (MPa) 69.5 69.5

Ends capped ONE ONE

Defects prior to testing NIL NIL

Test Methods Notes

Compression, NZS 3112 : 1986, Pt 2 Clause 6 See report LR2726.1 and LR2726.2 for 4 and 7 day strengths.Density, NZS 3112: 1986, Pt 3 Clause 5Capping NZS 3112 : 1986, Pt 2 Clause 4 (amendment No 2 2000)